Am Chiller Abs-M-10a - 04012001

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 80

Operation/

Maintenance

Horizon™
Single-Stage Steam or
Hot Water Absorption Chiller

Unit Model: ABSD

X39640542-02 ABS-M-10A
General
Information

How to Use This Manual


Contents
This manual describes the operation and
maintenance requirements for the Trane
Horizon Single-Stage Steam or Hot
Water Absorption Chiller. The
instructions are intended to provide the
machine operator with sufficient detailed
information to safely operate the chiller
This manual has been developed and
approved within a quality system
certified as conforming to ISO 9001.

©American Standard Inc. 2001 ABS-M-10A


Contents

Owner
General Information 2
Mechanical Specification, Component Identification,
Unit Nameplate Location and Description,
Model Number Description
Sequence of Operation 13
Machine Solution Cycle, Control Panel and Unit Controls,
Machine Sequence of Operation, Machine Control
Strategies, Purge System Operation
Operator Guide 29
Operator Display Reports, Settings, Test and Diagnostics,
Adjustable Frequency Drive Display Menu
Maintenance 42
Daily, Seasonal, Purge, Inspection Items, Evap., Abs. and
Condenser Care, AFD’s, Pumps, Filter Replacement

Troubleshooting/Diagnostics
Troubleshooting/Diagnostics 58
Control Panel Diagnostics, AFD Diagnostics, Pumps
Troubleshooting Checklist 59
Unit Wiring Diagrams 60
Electrical Connections, Field Wiring, Electrical Data,
Unit Wiring Diagrams

ABS-M-10A 3
General
Information

Mechanical Specifications Heat Exchangers Machine Description


A brazed plate solution heat exchanger
General is provided to reduce energy use and The following chapter contains machine
The Trane Horizon™ Model ABSD chiller improve unit performance. Heat identification of major components and
is a complete single effect steam or hot exchanger surfaces are 300 series warning and caution label locations. The
water fired absorption chiller package stainless steel. items identified are referenced
built in an ISO 9001 environment. Chiller throughout this manual in each
consists of generator/condenser section, Pumps applicable section.
evaporator/absorber section, controls, Solution and refrigerant are circulated by
means of 3 hermetic, single stage Figure 1 illustrates the major
pumps, heat exchanger, and energy components of a typical ABSD
control valve. All Horizon chillers are of centrifugal pumps. The pump impeller is
cast iron with a steel shaft supported by Absorption Chiller.
hermetic design, factory assembled and
leak tested prior to shipment. Horizon 2 tapered carbon bearings. The bearings Figure 2 identifies control panel labels,
chillers can be separated and shipped are lubricated and the motor is cooled by tags and warning or cautions that
disassembled for rigging purposes. the fluid that is pumped. An adjustable pertain to unit identification, installation
Horizon chiller controls are factory frequency drive is provided on the and operation.
mounted and wired including micro generator pump and absorber pump to
electronic control panel, sensors and provide solution control.
purge system, energy valve can be Automatic Purge System
factory mounted and wired as an option The purge system utilizes an eductor for
on steam fired units. Horizon chillers are moving non-condensables to the
painted prior to shipping with two coats condenser, Purifier™ purge to collect the
of a water base air dry primer. Standard non-condensables in an external storage
method of shipment is by truck from tank, and vacuum pump for removal of
the USA. the non-condensables. The purge
Generator/Condenser-Evaporator/ operates automatically to remove non-
Absorber condensables from the unit during
The shell material is carbon steel. periods of chiller operation and
Standard generator tube material is shutdown. Logging of purge information
cupro-nickel, evaporator is copper, is provided via the unit control panel.
absorber is cupro-nickel and condenser Generator
is copper. Tubes are mechanically rolled The shell is carbon steel. Tube sheets are
into the tube sheets and are replaceable steel and standard generator tubes are
from either end. Condenser, evaporator constructed of cupro-nickel. The
and absorber tube supports are fixed. generator has fixed and floating tube
Generator consists of fixed and floating supports to allow for even tube
tube supports to allow for even tube expansion. The steam side of the
expansion. Solution spray systems are generator is designed and stamped for
replaceable from end of unit without 50-PSI ASME construction. Generator/
sacrificing the hermetic integrity of the condenser includes rupture disk, which
unit. is sized to meet ANSI/ASHRAE B 15.
Generator/Condenser-Evaporator/ Lithium Bromide Filter
Absorber The filter system consists of the filter
Design working pressure for the water assembly and the associated piping and
boxes is 150 psig (10.5 kg/cm2). All tube filter isolation valves needed for
bundles are tested at 150 percent of operation and maintenance. The main
design working pressure. All water filter body is stainless steel with a
boxes have gasketed removable covers replaceable element. The filter isolation
for access. Optional Marine type water valves allow service of the filter
boxes can be provided on the condenser assembly without disturbing operation
and absorber section. Water connections of the rest of the machine.
are provided with either victaulic or
raised-face flanged connections.

4 ABS-M-10A
General
Information

Component Identification and Location


A typical Horizon ABSD steam machine is illustrated in Figure 1. Major components are identified in a front, back, right-end, and
left-end view. Figure 2 illustrates the machine labels location.
Figure 1 – Typical 500 Two-Stage Steam Machine

[47 mm]

ABS-M-10A 5
General
Information

Figure 1 (Continued) – Typical 500 Two-Stage Steam Machine

6 ABS-M-10A
General
Information

Machine Panel Labeling


The unit control panel ships with the
labeling indicated in Figure 2. The
various labels are identified as well as
the ship with literature pieces.

Figure 2 – Machine Labels Location

Legend
1. C.E. Compliance Label
2. ETL Listing Label
3. Nameplate Label
4. Customer Notes
5. Nameplate (Horizon)
6. Voltage Warning Label
7. Field Wiring Connection Diagram
8. Flat 9 x 12 Plastic Bag *
9. Operation and Maintenance Manual
10. Installation Manual
11. Poly Clear Envelope
12. Plastic SH Antistatic Foam
13. Lift/Move/Level Label
14. Inspect/Damage Label
15. Customer ID Tag
16. Customer Marked Package Tag
17. AFD Drive Manuals
*Contains installation and operation/
maintenance, AFD drive manuals and
includes as-built schematic wiring
diagram prints (laminated).
Note: UCP panel “keys” ship in an
envelope taped behind the control
panel.

ABS-M-10A 7
General
Information

Nameplate Nameplate
The ABSD unit nameplate is located on
the chiller control panel. The nameplate
illustrated is an ABSD 800 ton, Single -
Stage Steam Absorption.
Note: For temperature, pressure drops,
and water flow data see the order
write-up. Trane Horizon Absorption Series
Single-Stage Absorption Liquid Chiller

The Unit Nameplate contains very Catalog Model Number


important service information such as ABSD800

the unit serial number, sales order Service Model Number


number and the service model number. ABSD080GF0KXXXXXANXXAVAMBEEBGAHDCAXXXXAXAXXXX0
Always have this information readily Sales Order Number Unit Serial Number
available when requesting service. AXB123 L00D12345M

Maximum Inlet Steam Pressure: 14PSIG

Electrical Characteristics
Rated Voltage: 460 Volt 60 HZ 3 PH
Voltage Utilization Range: 414-506 VAC
Rated Current: 39.0 Amps
Minimum Circuit Ampacity: 47.0 Amps
Max Overcurrent Protective Device: 50.0 Amps
Purge Compressor RLA: 4.8 Amps
Control Circuit: 115 VAC 2000VA

Motors KW FLA
Purge Pump: .19 4.4
Refrigerant Pump: 3.7 2.0
Absorber Solution Pump: 5.6 15.0
Low Temp Solution Pump: 3.7 12.0

Service Literature
Installation Manual ABS-IN-10A
Oper/Maint. Manual ABS-M-10A

Manufactured Under the Following U.S. Patents:


4223539, Other Patents Pending

This advanced model ABSD HORIZON Single-Stage Absorption Unit


was developed with the assistance of the Gas Research Institute.

Product Description:

MODL ABSD DSEQ FO NTON 800


VOLT 460 BURN NSEL BOPA NSEL
FTAA NSEL SMHC NSEL ENSR STM
ENPR 50 PVCN STD PURG AUTO
LGTM SB04 HGTM NSEL CDTM SB09
EVTM ES12 ABTM SB00 GNWA GN02
CAWA CA17 EVWA EV01 CAWC RERE
EVWC LEFR CAFT WTR EVFT WTR
EVLV BF03 EVIN FACT EVPN SSTL
UPNT SFPT WCNM SNMP SPKG DAU
ELPP SELP PPCO NFDS LCLD CLDO
WVUO YES OPTM YES AFDS YES

8 ABS-M-10A
General
Information

Service Model Number


Single Stage Absorption
Standard Options Only
Service Model
digit / variable Description Selection
1-4 Absorption Unit Model
ABSD Single Stage Absorption
5-7 Unit Nominal Tonnage
050 500 Nominal Tons
060 600 Nominal Tons
070 700 Nominal Tons
080 800 Nominal Tons
097 975 Nominal Tons
110 1100 Nominal Tons
122 1225 Nominal Tons
135 1350 Nominal Tons
8 Unit Voltage
A 190 Volt - 50 HZ
B 200 Volt - 60 HZ
C 220 Volt - 50 HZ
D 230 Volt - 60 HZ
E 380 Volt - 50 HZ
F 415 Volt - 50 HZ
G 460 Volt - 60 HZ
H 575 Volt - 60 HZ
9 Unit Energy Source
J Steam Energy Source
G Hot Water Energy Source
10 Design Sequence
11 Design Sequence
12 Generator Waterbox Design Pressure
K Steam - 50 PSIG ASME Required
M Hot Water - 150 PSIG ASME Required
N Hot Water - 400 PSIG ASME Required
E Pressure Vessel Construction
Standard construction (includes ASME generator)
13 X Not Applicable
14 X Not Applicable
15 X Not Applicable
16 X Not Applicable
17 X Not Applicable
18 - 19 Low-Temperature Generator Tubes
AN .028 Wall 90-10 CUNI Smooth Surface
AP .035 Wall 90-10 CUNI Smooth Surface
AR .049 Wall 90-10 CUNI Smooth Surface
BD .028 wall 409 SST Smooth Surface
20 X Not Applicable
21 X Not Applicable

ABS-M-10A 9
General
Information

Service Model
digit / variable Description Selection
22 - 23 Condenser Tubes
AV .028 Wall Copper Smooth Surface
AW .035 Wall Copper Smooth Surface
AN .028 Wall 90-10 CUNI Smooth Surface
AP .035 Wall 90-10 CUNI Smooth Surface
AR .049 Wall 90-10 CUNI Smooth Surface
BF .028w 316L SST Smooth Surface
24 - 25 Evaporator Tubes
AM .025 Wall Copper Enhanced Surface
AL .025 Wall 90-10 CUNI Enhanced Surface
AE .035 Wall 90-10 CUNI Enhanced Surface

26 - 27 Absorber Tubes
BE .022 Wall 95-5 CUNI Smooth Surface
AK .028 Wall 95-5 CUNI Smooth Surface
AL .035 Wall 95-5 CUNI Smooth Surface
AM .049 Wall 95-5 CUNI Smooth Surface
AN .028 Wall 90-10 CUNI Smooth Surface
AP .035 Wall 90-10 CUNI Smooth Surface
AR .049 Wall 90-10 CUNI Smooth Surface
BF .028 Wall 316L SST Smooth Surface
AV .028 Wall Copper Smooth Surface
28 Pressure Vessel Construction
E Standard construction (ASME Generator)
29 Generator Water Box Arrangement
B 1-Pass Non-Marine RF Flange
C 2-Pass Non-Marine RF Flange
30 Condenser & Absorber Water Box Arrangement
G 150 PSI Marine Victaulic
H 150 PSI Marine RF Flange
J 150 PSI Non-Marine Victaulic
K 150 PSI Non-Marine RF Flange
31 Evaporator Water Box Arrangement
C 1-Pass 150 PSI Non-Marine Victaulic
D 1-Pass 150 PSI Non-Marine RF Flange
A 2-Pass 150 PSI Non-Marine Victaulic
B 2-Pass 150 PSI Non-Marine RF Flange
32 Unit Energy Valve
G 2-Way 3" 150# Wafer Btrfly
H 2-Way 4" 150# Wafer Btrfly
J 2-Way 6" 150# Wafer Btrfly
K 2-Way 8" 150# Wafer Btrfly
L 3-Way 3" 150# Flanged tee Wafer Btrfly
M 3-Way 4" 150# Flanged tee Wafer Btrfly
N 3-Way 6" 150# Flanged tee Wafer Btrfly
P 3-Way 3" 300# Flanged tee Wafer Btrfly
R 3-Way 4" 300# Flanged tee Wafer Btrfly
T 3-Way 6" 300# Flanged tee Wafer Btrfly
U 2-Way 3" 150# Flanged Btrfly
V 2-Way 4" 150# Flanged Btrfly
W 2-Way 6" 150# Flanged Btrfly
Y 2-Way 8" 150# Flanged Btrfly
A 2-Way 2" 150# Wafer V-Ball
10 ABS-M-10A
General
Information

Service Model
digit / variable Description Selection
B 2-Way 3" 150# Wafer V-Ball
C 2-Way 4" 150# Wafer V-Ball
D 2-Way 2" 300# Wafer V-Ball
E 2-Way 3" 300# Wafer V-Ball
F 2-Way 4" 300# Wafer V-Ball
Z 2-Way 2" 150# Flanged V-Ball
1 2-Way 3" 150# Flanged V-Ball
2 2-Way 4" 150# Flanged V-Ball
33 Electrical Protection Package
D Standard Electrical Package
34 Control Panel Power Connection
A Circuit Breaker
B Fused Disconnect Switch
C Non-Fused Disconnect Switch
D Terminal Block
35 Local Clear Language Display
A Clear Language Display - Complex Character
B Clear Language Display - Suitable for Outdoor Use
36 X Not Applicable
37 Tracer Interface Control Module
A Tracer 100 Interface Module (com3)
B Tracer Summit Interface Module (com4)
38 Printer Interface Control Module
A Printer Interface Module
39 Ambient Chilled Water Reset
A Ambient Chilled Water Reset
40 Under/over Phase Voltage Protection
A Under/over Voltage Protection
41 Chiller/tower Water Flow Display
A Differential Water Pressure Transducers
42 Options Control Module
A Options Module
43 X Not Applicable
44 Unit Insulation
C Cold Unit Insulation Only
45 Lithium Bromide Filter
A Lithium Bromide Filter
46 Unit Special Features
X Not Applicable
S Special
47 X Not Applicable
48 Purge System
1 Automatic Purge System
2 Manual Purge System
49 Adjustable frequency drive
1 Frequency drive

ABS-M-10A 11
General
Information

WARNING Safety Precautions

CAUTION WARNING CAUTION


HAZARDOUS VOLTAGE! ELECTRICAL COMPONENTS!
Warnings and cautions appear at
appropriate intervals throughout this DISCONNECT ALL ELECTRIC POWER KEEP PAINT AWAY FROM ALL
manual. Warnings are provided to alert INCLUDING REMOTE DISCONNECTS ELECTRICAL COMPONENTS AND
installing contractors to potential hazards BEFORE SERVICING. NEVER PAINT WHILE THE MACHINE IS
that could result in personal injury or FAILURE TO DISCONNECT POWER ENERGIZED.
death. Cautions are used to alert BEFORE SERVICING CAN CAUSE FUMES MAY BE PRESENT CAUSING
personnel to conditions that may result SEVERE PERSONAL INJURY OR DEATH. EXPLOSIVE CONDITIONS.
in minor or moderate injury or
equipment damage.
IMPORTANT WARNING CAUTION
Operation without proper water pump
and flow sensing interlocking will void HAZARDOUS VOLTAGE! LITHIUM BROMIDE!
unit warranty. DO NOT USE WATER ON A MOTOR OR LITHIUM BROMIDE IS NORMALLY
ELECTRICAL FIRE. USE CO2 (CARBON NONTOXIC; HOWEVER, OTHER
Note: This machine uses lithium
DIOXIDE) OR ANSAL (DRY CHEMICAL) CHEMICALS MIXED WITH THE
bromide inhibited with lithium
(CLASS ABC OR BC). SOLUTION CAN CAUSE IRRITATION
molybdate and lithium hydroxide.
USE OF WATER ON AN ELECTRICAL AND ADDITIVE VAPORS CAN CAUSE
Lithium bromide that contains other
FIRE MAY RESULT IN SERIOUS NAUSEA. ALWAYS PROVIDE
inhibitors cannot be used in this
PERSONAL INJURY OR DEATH VENTILATION TO REMOVE
equipment.
CAUSED BY ELECTRICAL SHOCK. ACCUMULATED VAPORS.
To avoid risk of injury never climb over a IN CASE OF ACCIDENTAL CONTACT
machine or step on components. Always WITH THE SOLUTION, WASH THE
use a platform, ladder or similar. AFFECTED AREA WITH WATER
To avoid risk of injury always use a crane IMMEDIATELY.
or hoist to lift or move machine
components.
Lift locations are marked.
CAUTION
SOLUTION VAPOR AND CONDENSATE
PIPES!
SOLUTION VAPOR AND CONDENSATE
PIPES CONNECTED TO THE
GENERATOR SECTIONS OF THE
MACHINE HAVE SURFACE
TEMPERATURES AS HIGH AS 300°F.
AVOID CONTACT WITH THESE AREAS
WHILE THE MACHINE IS IN SERVICE TO
PREVENT PERSONAL INJURY IN THE
FORM OF SEVERE BURNS.

12 ABS-M-10A
Sequence of
Operation

To understand the Horizon chiller Machine Solution Cycle


operation, a thorough understanding of
The machine solution cycle is discussed in this section. Refer to the cooling cycle
the various aspects of the machine are
required. This section of the manual, schematic, Figure 3, during the cycle explanation and reference Table 1.
therefore, explains the lithium bromide Figure 3 – Single-Stage Absorption Refrigeration Cycle
cycle, the controls utilized to control the
lithium bromide cycle, and the sequence
of operation of the cycle and associated
controls. 14
13

15 6

7 12

10

9
3

8
1
4 5

11

Table 1 – Machine Cooling Cycle (Ref. Figure 3) (Typical Temperatures)


Concentration Temperature Temperature
Point LiBr Solution or Refrigerant Water % (°F) (°C)
1 Absorber Dilute Solution 60.8 107 42
2 Absorber Dilute Solution Entering the LTG 60.8 185 85
3 Solution Leaving the LTG 64.4 216 102
4 Solution Entering ABS Sump/Spray Pump 64.4 129 54
5 ABS Spray Solution (Mixed w/abs dilute) 63.1 121 49
6 LTG Refrigerant Vapor NA 208 98
7 Condensed Refrigerant NA 110 43
8 Evaporator Pump Refrigerant NA 41 5
9 System Chilled Water/Entering NA 54 12
10 System Chilled Water/Leaving NA 44 7
11 Absorber Cooling Water NA 85 29
12 Absorber Leaving/Condenser Entering Cooling Water NA 94 34
13 Condenser Leaving Cooling Water NA 101.6 38.6
14a Steam Entering Unit @12 psig @ Sea Level NA 244 118
14b Hot Water Entering Unit @270°F (option) NA 270 132
15a Condensate Leaving Generator NA 244 118
15b Hot Water Leaving Generator (option) NA 222 106

ABS-M-10A 13
Sequence of
Operation

Refrigerant Cycle Absorber


(Ref. Figure 3) Refrigerant vapor is absorbed by the
lithium bromide solution (dilute) to be
Refrigeration Cycle circulated and cycled again. The solution
This is an example of typical machine is pumped through the solution heat
operation at a standard rating point exchanger to the generator. Absorber
condition (i.e., 85°F/29°C tower, 44°F/ Heat (acquired in the evaporator) is
6.7°C leaving chilled water) at full load. rejected via the cooling water inside the
Dilute solution has a relatively high tube bundle (11-12).
refrigerant content and low lithium
bromide content. An intermediate Absorption Process
solution is a mixture of dilute and Solution (concentrated) enters the spray
concentrated solutions. A concentrated system from the generator and enters
solution is one with a relatively low the spray system wetting the tubes and
refrigerant content and high lithium providing a liquid surface for the
bromide content. refrigerant vapor from the evaporator to
absorb into the lithium bromide solution.
Generator The solution temperature/concentration
Dilute solution (1) is pumped into the sprayed in the absorber controls the
generator (2) where it is boiled by the absorber pressure thereby controlling
steam or hot water in the tube bundle, the evaporator refrigerant temperature.
creating refrigerant vapor. The
refrigerant vapor is drawn to the Solution Heat Exchanger
condenser (6). The now concentrated Solution flows through the heat
solution flows by gravity through the exchanger being preheated reducing the
solution heat exchanger (3) to the heat energy required to induce boiling
absorber (4) spray system where it is within the generator and to decreasing
mixed with dilute solution (1) from the the temperature of the solution being
absorber and sprayed on the absorber returned to the absorber, thus
tubes (5). decreasing the load on the cooling
tower.
Condenser
Refrigerant vapor (produced by the low
temperature generator) enters the
condenser (6) to be reduced in pressure/
temperature via expansion device for
delivery to the evaporator. The heat of
condensation is rejected to the cooling
water inside the tube bundle (12-13).
Evaporator
System water runs through the tube
bundle (9-10) where its heat is
transferred to the sprayed refrigerant
water (8) causing the refrigerant to
vaporize/boil. The refrigerant vapor is
drawn to the slightly lower pressure in
the absorber.

14 ABS-M-10A
Sequence of
Operation

Control Panel Location and Voltages in Panels


Internal Hardware Voltages present within the unit control panel include:
Component Description • Three phase line voltage (power side only)
The main control panel (Figure 4) has • 115 Vac control circuits
two sections. The left side (control side) • 24 Vac module power supply
includes clear language display Low voltage, low power (30 Vdc or less – Class II) circuit connection points are located
(mounted through door), chiller, circuit, on the left side of modules. High voltage, high power (greater than 30 Vdc – Class I)
purge, stepper, and optional circuit connection points are located on the right side of modules. All 115 Vac circuits
communications modules, a terminal are Class 1.
block, and a 115 Vac-control voltage to
The stepper drive uses less than 30 Vdc however, the output signals are Class 1 due to
24 Vac transformer. The right side its output current (amps).
(power side) consists of a main line
voltage terminal block or disconnect Class 1 and Class 2 wiring must not be routed together without shielding.
service for line power connections, line Figure 5 – Panel Layout
voltage to control voltage transformer,
relays, transformers, starter module and
purge module. Line voltage is restricted
to the right-hand side.

Figure 4 – Machine Control Panel

Control Side Power Side

The components within the control


panel are illustrated in Figure 5. Modules
are stacked and located top, bottom or
middle configuration.

Panel Layout Legend


1U1 - Starter Module 1TB2 - Pump Motor Terminal Block
1U2 - Circuit Module 1TB3 - UCP2 Control Panel Mounted Terminal Strip
1U3 - Chiller Module 1S1 - Line Voltage Fused Disconnect Switch*
1U4 - Purge Module 1K1 - Refrigerant Pump Abnormal Relay
1U5 - Stepper Module 1K6 - Purge Relay
1U7 - Options Module* 1K11 - Refrigerant Pump Contactor
1U8 - Tracer Communication Module* 1U11 - Refrigerant Pump Overload
1T1-2-3 - Phase Current Transformer 1F1, F2 - Line Voltage Transformer Fuses
1T4 - Line Voltage Transformer 1F3 - Phase Voltage Transformer Fuse*
1T5 - Control Voltage Transformer 1F4, F5, F6 - Refrigerant Pump and Absorber
1T6-7-8 - Under-Over Phase Voltage Transformers* Solution Pump Motor Fuses
L1-2-3 - Main Power Entrance 1F7, F8, F9 - Low Temp Solution Pump Motor Fuses
*Optional

ABS-M-10A 15
Sequence of
Operation

Signal Block Diagram Figure 6


The following signal block diagram
illustrates the interrelationship of the
interprocessor communications (IPC) link
that allows the various module
microprocessors to communicate. All
control modules are mounted in the
chiller control panel. The option and
communication modules are present
only when specified. The Trane Tracer
Automation System provides
communications outside the unit control
panel.
The Chiller Module (1U3) serves as the
master control. This module is
responsible for implementing the
algorithms that control chiller operation.
It manages the functions of machine
safety, operating limits, chilled water
temperature control by monitoring unit
mounted sensors and information from
other modules on the interprocessor Unit Control Panel with Modules
communications (IPC) link.
The chiller module initiates and controls
all data communications. Internal control Setpoint Communication and Storage 1U4 Purge Module
algorithms and external input data are The machine setup information selected The purge module provides automatic
used to produce chilled water at the operator interface is stored in the purge pumpout logic. A sensor located
temperature while maintaining safe chiller modules non-volatile memory on the purge condensing unit suction
reliable chiller operation. The input/ that is retained when the panel is not line is monitored to determine when
output ports on the chiller module powered. The chiller module is pumpout is required. An output then
monitor and control-chilled water and responsible for verifying that the setup turns on the pumpout cycle. The
cooling water pump operation. The memory is not corrupted, and for pumpout period duration is monitored
evaporator and condenser water pumps substituting default settings if the stored and stored for analysis.
are electrically controlled and interlocked settings become corrupted.
to the unit control panel. This 1U5 Stepper Module
interlocking arrangement provides 1U1 Starter Module Stepper module 1U5 collects input from
protection from improper system water The starter module controls external unit sensors and binary input devices.
pump control or loss of flow conditions, water pump operation and provides an The stepper output is used for control of
which can damage the machine. interface to an adjustable frequency the energy valve.
variable speed drive for solution pump 1U6 Local Clear Language Display
This module communicates through the control.
interprocessor communications (LCLD, or Operator Interface) (std)
connection to other modules such as: 1U2-Circuit Module The LCLD is located on the control side
the stepper drive module to control the The circuit module is located in the lower door. The module connecting wiring is
energy input, the starter module to start/ portion of the control section beneath accessible on the door backside. This
stop the solution pumps and control the starter module. The main purpose of module accepts operator keypad input
solution flow, and to the operator the circuit module is that of an input/ and communicates with the other
interface to display machine status output (I/O) expander for the chiller control elements within the control
information to the operator. module. The circuit module provides panel. See operator interface for
input data from unit temperature complete details.
sensors, unit pressure and switch inputs, 1U7 Options Module (optional)
and makes this information available by Present only when optional features are
way of an interprocessor specified that required additional input
communication link. This module or outputs (I/O).
provides output contact closures for
control of the purge and lithium bromide 1U8 Tracer Communications
concentration sensing, detection, and Interface Module (optional)
recovery control. Required for Tracer communications.

16 ABS-M-10A
Sequence of
Operation

Terminal Blocks Transformers Control System Features and Functions


Terminal blocks are used for various Transformers are used to reduce voltage • Operator interface with a 40 character,
connection points within the control to required levels. Some are used to 2-line display and a 16 key keypad.
panel as identified below. distribute power and others for module • The microprocessor automatically
• 1TB1 Main terminal block (standard). input signals. The various transformers dilutes the lithium bromide solution,
• 1TB2 Pump Motor Terminal Block – are identified below. before shutting down the machine.
Line voltage distribution point for the 1T1, 1T2, 1T3 Phase Current • Chilled water pump control output
three phase motors. Transformers contacts.
• 1TB3 Control Panel Mounted Terminal Current transformers are used to sense • Absorber/Condenser pump control
Strip-Provides termination points for the total 3 phase line current draw. The output contacts.
internal wiring, and for field wiring output of each current transformer is • Automatic and manual control of
interface points. See the electrical input to the 1U1 starter module. Current solution and refrigerant pumps.
connection’s points on the typical unit transformers are polarity sensitive. • Adjustable frequency drive for solution
schematics. Typically there is a marking ”dot” on one flow control of the low temp solution
Main Power Termination Point side and the secondary wires are black pump and absorber spray pump.
The connection point in the power and white. The installation of the • Automatic and manual purge system
section used for customer three phase transformers must be with the markings incorporating the Trane Purifier
power. all facing the same direction regarding Purge™.
• 1TB1 Main terminal block (standard). the current flow through the primary • Dilution control Refrigerant Dump
Valve provides refrigerant where it’s
• 1S1 Line voltage non-fused disconnect wiring. The current transformer outputs
needed to properly reduce solution
switch-optional. are input to the starter module and
concentration during a dilution cycle or
• Circuit breaker, or shunt trip circuit displayed at the LCLD with in the Purge/
loss of power.
breaker - optional. Pump Report.
Circuit Breakers and Fuses 1T4 Line Voltage Transformer
• If an extended loss of power occurred
while running, a dilution cycle will be
Circuit breakers and fuses that provide Transformer that steps down line voltage initiated when the power is restored.
the branch circuit protection. to 115 Vac control powered circuits. This dilution cycle will attempt to
• 1CB2 Line voltage transformer circuit 1T5 - Control Voltage Transformer reduce the solution concentration to
breaker. Transformer that steps down the 115 Vac prevent crystallization.
• Circuit breaker provides branch circuit control voltage to 24 Vac power. Additional System Protection:
protection to 1T5 primary winding.
• 1F1, 1F2 Line voltage transformer 1T6, 1T7, 1T8 Under-Over Phase Voltage • Under/over voltage detection (optional)
fuses. Transformer (Optional) • Chilled water flow confirmation input
• 1F3 Phase voltage transformer fuse. Voltage potential transformers provide • Condenser water flow confirmation
input
• 1F4 ,1F5, 1F6 Refrigerant and absorber an isolated secondary voltage that is a
proportional representation of the • Emergency stop shutdown input
solution pump motor fuses.
• 1F7, 1F8, 1F9 Low temperature solution primary voltage. Each line voltage of the
three phase supply to the unit control
pump motor fuses.
panel is sensed. Each potential
Relays transformer’s low voltage output is input
The following relays are used to isolate to the 1U5 starter module.
115 volt signals from low voltage
module input signals.
• 1K1 - Refrigerant pump abnormal relay
• 1K6 - Vacuum pump relay

ABS-M-10A 17
Sequence of
Operation

Control Locations
Machine controls are factory mounted and wired. External controls are connected with field wiring, and are controlled by the
chiller or used by the chiller system.
Figure 7 – Machine Sensor Locations

18 ABS-M-10A
Sequence of
Operation

Table 2

ABS-M-10A 19
Sequence of
Operation

Machine Control Sequence of Operation Time Line Machine Start-up


Referenced Notes During the machine start sequence the
This section identifies sequence of chiller relies on external devices to
operation and control strategy, machine 1) See “Operator Guide” for a listing of
valid modes that may occur during provide correct feedback specifically, the
control panel details and specific chilled water pump starter and flow
machine mounted controls. “Unit is Running.”
switch confirmation, condenser water
The illustration represents time and 2) Upon power up, refrigerant dilution pump starter and flow switch
event proceeding from left to right. The valve 1 (4B6) remains off for thirty confirmation. During machine start-up,
operator interface displays, time and the seconds. the appropriate message will be
events in the sequence that they occur. 3) When a “need to cool” exists, an displayed that confirm the sequences
Follow the sequence to understand incomplete dilution cycle can be occurred.
when external and internal control exited by pressing the Auto key. The The Unit Control Panel (UCP) waits up to
devices are used. The time line provides chiller will continue with a new start- four minutes and fifteen seconds for
information that may not be obvious up sequence. proof of chilled water flow after a water
when watching the display. Additionally, pump start command output is given.
this information can be used for trouble 4) The “Auto, waiting for a need to cool”
shooting purposes. can be exited by pressing Stop. Failure to receive chilled water flow
5) Power loss at this point will result in a within the allotted time confirmation
The sequence of operation illustrates results in a message stating
time and events that occur at initial dilution cycle upon re-establishing
power, if there is no need to cool. “Diagnostics -auto.” This is a Machine
power-up, during start-up when auto is shutdown Auto Restart (MAR)-
selected, auto off cycle operation, or 6) Power loss at this point will result in diagnostic where the chiller will start
manual stop operation. The time line 1 the remainder of a dilution cycle being once the chilled water flow switch logic
and 2 (page 21) and time line 3 (top half completed upon re-establishing is satisfied.
of page 22) pictorially illustrates the power.
events that occur during normal Failure to receive condenser water flow
7) Chilled water pump will be stopped within the time periods’ results in an
operation. after the dilution cycle is completed Machine shutdown Manual Restart
for all MAR and MMR except in the (MMR)- diagnostic where the chiller
case of chilled water pump flow must be reset before continued
overdue where the chilled water operation is allowed.
pump signal remains on.
Dilution Cycle
8) Panic stop; operator presses the stop A 3 to 15 minute dilution cycle is
key twice within 5 seconds. This state performed on all shutdown modes with
may be exited by pressing either the one exception. The exception is a “Panic
stop or auto key. Stop” that consists of an operator
depressing the stop key twice (or
continuously) within a 5-second period.
This will execute a pump stop command
and all pumps will stop without the
normal dilution cycle. A restart can be
initiated at anytime by pressing the auto
key. A dilution cycle may be entered by
pressing the stop key. If “Stop” is
selected, the events following a stop
command is pictorially illustrated on the
bottom half of page 22.

20 ABS-M-10A
Sequence of
Operation

Figure 8 – Sequence of Events from a Stop or Auto condition through Start

Standard Mode Stop Auto Starting Absorber/Condenser Pumps


Display:

Wait for Cond. Water


Wait for Chilled Water Flows, if flow not
Flow, If flow not Wait for a established in less
established in less than Call for than 4 min. and 15
4 min and 15 sec. then Cooling sec. then issue: Cond.
issue: Chilled Wtr Flow (See Note 4) Wtr Flow not Est.
not Est. MAR MMR
Variable 6 sec to 4 min, Variable 6 sec. to
15 sec Variable 4 min. 15 sec.
Time
Line 1
START
Go to
Time
AUTO Selected Chilled Water
Chilled Water Pump Off
Flow
Line 2
Cond. Water Pump Off Established Differential to Start (Below)
Chilled Water Pump is Reached (Cooling
Solution Pumps Off Started Required)
Events:
ABS and RFGT Pumps Off Condenser Water Pump
Started
Energy Valve Closed
Time
Line 1a Low Temp Solution Pump
Started (AFD at Min. Speed)
All other Diagnostics are Point of Re-Entry if the Operator
active Hits AUTO from Dilution Cycle Hot Water Machines
or Hot Water Pump On
RDV1 Closed Reset from Diagnostic Auto
or
Waiting for Differential to Start
(System in AUTO Mode)

Indicates Time Line (1,2 or 3) Location


Standard
Mode Start Filling Start - Preheating Solution Unit is Running
Generator (See Note 5) See Note 1 and 5)
Display:
Waiting to Establish
Concentration of 54% Hold for 3 min.
30 LiBr - Var. Based to Stabilize Go to Time
Seconds on Concentration System Line 3
(Next Page)
Time Line 2
Refrigerant Modulate Low Temp Solution
Command Energy Valve Pump Started Pumps AFD to satisfy LWT
Events: 40% of allowable range Absorber
and begin Pre-Heat with Pump Started Modulate energy Valve to Satisfy
Absorber and Refrigerant LTHX Crystallization Margin
Pumps Off

ABS-M-10A 21
Sequence of
Operation

Figure 8 (Continued) – Sequence of Events: From Running through Dilution Cycle

22 ABS-M-10A
Sequence of
Operation

Machine Control Strategy Absorber spray solution concentration Along with the microprocessor control of
determines the absorber vapor pressure LWT and concentration control as stated
The objective of the unit control system that controls the refrigerant vapor previously, the microprocessor monitors
is to reliably achieve and maintain pressure and temperature. The refrig. operating conditions that could alter
leaving chilled water setpoint. The unit spray temperature then controls the LWT machine operation. If such a condition is
control panel (UCP) monitors chilled to the leaving water temperature detected the limit control system will
water temperature and its relation to the setpoint. override LWT and concentration control
panel set point, and adjusts the amount requests. The override limit occurs when
of solution supplied to the generator, 2. Concentration Control
Solution concentration control adjusts a control output (from LWT or
and the energy applied as needed. concentration control) request is greater
Adjusting the solution flow maintains the generator energy input to hold
solution concentration to optimum than allowed by the particular limit
the leaving water temperature. Adjusting schedule. The limit control modifies
the energy input maintains solution efficiency. The strong solution
concentration is typically maintained machine control to continue operation.
concentration. These two adjustments
are the two primary control algorithms 15°F [-9.4°C] from theoretical When a limit or safety takes priority
employed in the UCP. Reference crystallization point. This is called the control, the clear language display will
Figure 9. low temperature heat exchanger (LTHX) so indicate the active limit mode. A limit
temperature margin. As strong solution mode does not necessarily mean that a
1. Leaving Water Temperature (LWT) concentration is varied by LWT solution problem exists. In many cases this limit
The unit control panel compares leaving flow control, the theoretical is a normal function such as soft load
chilled water temperature to the leaving crystallization temperature is changed. during start-up.
water set point and adjusts the The control system adjusts the energy
refrigerant vapor pressure in the input to maintain the LTHX temperature
evaporator to achieve control. The margin throughout the load range. The
refrigerant vapor pressure is determined simplified control illustration below
by the absorber spray concentration. The illustrates the two control inputs and
absorber spray concentration is changed indicates that these inputs must pass
by adjusting the generator solution flow through the “limit control” before the
with the adjustable frequency drive signals are output the solution pump
(AFD) control of the absorber spray and AFD and/or energy input control.
low temperature solution pumps.

Figure 9 – Simplified Diagram of LWT Control and Concentration Control

ABS-M-10A 23
Sequence of
Operation

The microprocessor will shutdown the new setpoint will be reached as the new Low Refrigerant Temperature Limit and
chiller if a safety set point is violated. target setpoint at the end of the set soft Cutout
Figure 10 illustrates the limits that can loading time period. The soft loading This limit prevents the machine from
override LWT and concentration control. time period is factory set to 15 minutes driving down the refrigerant temperature
The primary control signal can be and can be set from 1 to 100 by the start- below safe and reliable temperatures. If
modified by any limit. up personnel. an unsafe level is approached the control
Low Condensing Temperature Limit strategy will first limit loading, then enter
Soft Loading a hold where continued loading is not
Soft loading is accomplished via a Low temperature may limit solution flow
to prevent salt carryover and/or allowed. If the refrigerant temperature
filtered setpoint change function in that it continues to fall, the unit will unload in
affects the speed that the machine loads crystallization. The factory default setting
is designed to provide reliable chiller an attempt to keep the chiller on line
or unloads when given a new setpoint avoiding a low temperature trip. If the
target. This occurs at start-up and operation with low tower temperatures.
To do this the solution flow may need to refrigerant temperature continues to
whenever the chilled water setpoint is decrease and the cutout is reached then
changed. On start-up, this allows the be limited at condensing temperatures
below design. The further below design an MMR will occur requiring manual
machine to warm-up gradually, and reset. For example, with a typical low
allows for the tower water to warm-up. and the higher the load will increase the
likelihood of this limit mode becoming refrigerant temperature setpoint of 36°F
Soft loading is also active when a chilled [2.2°C] the following will be active points;
water setpoint change is received. The active.
limit loading will begin with a decreasing
refrigerant temperature reaching 38.5°F
Figure 10 – Limit Conditions that could Override LWT and Concentration Control [3.6°C], hold loading will occur @ 38°F
[3.3°C], and unload will occur at 37.5°F
[3.1°C]. Cutout will occur @ 36°F [2.2°C]
resulting in a machine shutdown manual
reset- MMR- diagnostic. The factory
default setting is 36°F [2.2°C] and can be
adjusted, if required by Trane service
personnel.
Low Chilled Water Temperature Limit
Low chilled water temperature limit
operates similarly to the low refrigerant
temperature limit previously discussed.
For example, with a typical low chilled
water temperature setpoint of 38°F
[3.3°C], limited loading begins @ 40.5°F
[4.7°C], hold loading @ 40°F [4.4°C],
unload at 39.5°F [4.2°C], and trip @ 38°F
[3.3°C] resulting in a machine shutdown
manual reset- MMR- diagnostic. The
factory default setting is 38°F [3.3°C] and
can be adjusted, if required by Trane
service personnel. The minimum
difference between these limits is 2°F or
1°C.

24 ABS-M-10A
Sequence of
Operation

Sensing Detection and Recovery (SDR) Adjustable Frequency Drive (AFD) AFD Operation within the Absorption
Solution flow sensing provides the input The low temperature solution pump and System
information for proper solution flow absorber spray pump flow rate are The output from the AFD's provides
detection. This is a back up system controlled by adjusting the operational power for the Absorber (4B2) and Low
providing a second line of defense if speed of the pumps. This is done by the Temp Solution (4B3) pumps.
concentration control fails to maintain AFD’s. The main unit control panel Operating Frequency
the set margin of degrees away from the outputs an analog signal to the AFD’s Figure 11 illustrates the solution range of
crystallization point. If an incorrect flow that drive the solution pumps at the frequencies used for typical pump motor
pattern is detected the control system desired speed to provide the correct control, 25 Hz minimum to 54 Hz
enters a recovery mode of operation that amount of solution flow for the machine maximum. The minimum and
cycles the solution pumps and load condition. This section discusses maximum stop values, used in this
refrigerant dump valve to dilute the the AFD. example, are the frequency utilized
strong solution, reestablishing the AFD Description: range. The end points will change by
correct flow pattern. The control system An adjustable frequency AC drive is a machine size and are factory selected.
will, on the first and second occurrence, device for controlling the speed of an AC The end stop locations, indicated in
increase the set concentration margin by motor by changing the frequency of the Figure 11, illustrate the difference
5°F [-15°C] in an attempt to prevent a power supplied to the motor. The between available and actual
reoccurrence, and an informational adjustable frequency drive is a solid- frequencies that could be used during a
warning message will be displayed on state power conversion unit that receives factory calibration of the controls.
the clear language display. Upon the 3 phase, 60 Hz input power, converts it to
third occurrence a machine shutdown See operator guide for AFD Keypad
DC power, filters it, and then inverts it to illustration and flow chart of menu item.
manual reset (MMR) diagnostic will be provide motor power that is modulated
set and require manual reset after to the frequency desired. The AC drive
corrective action is established. also regulates the output voltage in
Steam Input Flow Control proportion to the frequency to provide a
Steady steam input flow is important to nominally constant ratio of voltage to
maintain stable concentration control. frequency as required by the
The control rate at which steam enters characteristics of the AC motor.
the unit is a function of: A) supply
pressure, B) saturation pressure in the
generator, and, C) the steam valve
position. With steady steam supply Figure 11 – Pump Motor Supply Frequency
pressure the flow can be controlled quite
well with the valve position alone.
However, in cases where building steam
supply pressure variations do occur
various flow rates would occur. The
control system would sense this via the
absorption fluid pressures and
temperature, and then make
adjustments as necessary. Today’s
Steam Input Flow Control incorporated
in our ABSD and ABTF chillers utilizes
steam pressure transducers to measure
the pressures to the valve and at the
machine. This information is then
utilized to calculate steam flow to
determine the proper valve position
during these undesired pressure
changes. The energy valve has a stepper
control motor with 16,300 steps of
resolution providing very precise valve
position control. The flow control
algorithm and the finite control of the
stepper motor provide the best possible
steam input control.

ABS-M-10A 25
Sequence of
Operation

Purge System Operation Timed Pumpout


The purge system will initiate a “timed
The machine is factory leak checked to pumpout” cycle periodically, as
high standards. Hermetic integrity is the determined by the timed pumpout
focus of this design since stability of the settings within the Service Settings field
unit vacuum is required to maintain start-up menu. This pumpout will pump
chiller efficiency and reliability. out of the absorber via the lower
Consistent maintenance practice will motorized valve. Usage depends on
ensure that the factory established machine characteristics and load
hermetic integrity is maintained. Non- conditions.
condensables that accumulate in the
machine must be removed by purging. Automatic Purifier™ Purge Operation
Figure 12 – Purge tubes and collection Automatic purge operation occurs with
Absorber Removal of Non- the absorption machine “on”. The
chamber (early design)
Condensables normal mode of operation is with the
Absorber removal of non-condensables purge set to “On” on the control panel
from the absorber/evaporator shell is clear language display. With “On” purge
accomplished via the pickup tubes and operation, the purge condensing unit
the eductor. Depending on the chiller operates during chiller operation, and
configuration, the purge pickup tubes vacuum pump runs continuously. The
will be through a collection chamber or condensing unit draws non-
drop down tubes. Refer to Figures 12 condensables out of the condenser to a
and 13 to see the differences. non-condensable collection tank.
The eductor uses the solution being The purge senses when the collection
pumped by the Low Temperature tank contains non-condensables via
Solution Pump (LTSP) to remove the suction temperature and executes the
non-condensables from the chamber pumpout cycle as necessary. A pumpout
and pickup tubes. The discharge of the Figure 13 – Purge drop tubes (used on later valve opens to allow the vacuum pump
eductor is to the suction side of the LTSP chillers) to expel the collection tank of non-
where the non-condensable are condensables. Pumpout time is
transported to the Low Temperature monitored and stored for analysis.
Generator (LTG). The dilute solution If the purge suction temperature drops
pumped through the LTSP carries the below the 30°F [-1.1°C] inhibit level, the
non-condensable to the LTG section. In purge system will go into a “standby”
the LTG the non-condensable are mode.
released from solution and migrate to
the lower pressure of the condenser. Automatic operation of the purge
From the condenser, the Purifier Purge system when the chiller is in the off
removes the non-condensable by position is slightly different. Only the
creating even a lower pressure in the vacuum pump operates and the
purge tank. Any non-condensable from motorized valve(s) open and close based
the high temperature generator are on the purge pumpout time and
passed to the condenser through a vent duration interval defined in the Field
line. The Purifier Purge pumpout cycle Start-up menu.
initiates and terminates per the suction Figure 13 – Eductor Position
temperature of the compressor. The
lower temperature creates a lower
pressure to draw non-condensables
from the condenser into the purge
collection tank.

26 ABS-M-10A
Sequence of
Operation

Purge Operation Modes


Within Operator settings, purge operation can be selected as: Off, On, or Service/Pumpout.
Table 3 identifies the modes and the status of the major components in each mode.

Table 3 – Modes and Status of Major Components in Each Mode


Purge Operating Mode Chiller Operating Mode Condensing Unit Vacuum Pump Pumpout Valve (s)
Off On/Off Off Off Closed/Off
On On On On Pumpout By Temperature
On On On On Pumpout by timed interval
(absorber valve, if installed
On Off Off On Pumpout by timed interval
(condenser tank valve only)
Service Pumpout NA On On Open/On
Note: Normally, purge should be in the “on” mode position.

Purge Components Figure 15 – Purifier Purge Components


Purifier Purge Operation
The purifier purge is active when the
purge-condensing unit is powered. The
evaporator coil of the condensing unit is
used to condense refrigerant vapor in
the purge collection tank. This results in
a slightly lower pressure in the purge
collection tank thus, drawing refrigerant
vapor and non-condensables into the
purge collection tank. Refrigerant vapor
and non-condensables enter the purge
tank through a pickup line connected at
the bottom of the purge tank.
Once inside the tank, the refrigerant
vapor condenses on the purge tank coil
and falls to the bottom of the tank,
leaving non-condensables to
accumulate. Liquid refrigerant returns to
the condenser through the return line.
The pickup and return lines have
isolation valves that can be closed when
tank service is required.

ABS-M-10A 27
Sequence of
Operation

Purifier Purge Operating Cycle Figure 16 – Purifier Purge Refrigerant Circuit


Figure 16 illustrates the cycle of the
active purge.
As non-condensables accumulate in the
purge tank (1) the available condensing
surface in the tank becomes limited, and
the condensing unit compressor suction
temperature (2) will begin to fall. When
the condensing unit compressor suction
temperature drops to the pumpout
temperature, a sensor signals the purge
module and a pumpout cycle begins.
Non-condensables in the purge tank are
then evacuated with a vacuum pump. As
the non-condensables are removed from
the purge tank, the condensing unit
compressor suction temperature
increases. This condensing temperature
is again sensed at the purge module that
will terminate the pumpout cycle when
this temperature rises sufficiently. The
pumpout suction temperature varies in
relationship to the units condensing
temperature. This allows purge
operation with condensing temperatures
from 50°F to 180°F [10°C to 82°C].

28 ABS-M-10A
Operator
Guide

Using the Control Panel Figure 17– Operator Interface


This section provides detail of the
operator interface display, operation,
keypad key functions, display group
menus-report and settings, and how to
use these functions.
Operator Interface (Local Clear
Language Display – LCLD)
The operator interface (LCLD) provides a
method to communicate with the chiller.
The operator selects information to be
displayed from eight group keys that
have predetermined menus. All operator
selections and monitored information
are entered and/or displayed from this
device. The operator interface obtains
the selected setup values and data from
the interprocessor communications (IPC)
link. The settings and temperatures will
not be displayed until they have been
read by way of the IPC. Displayed items,
such as temperature, will be updated
every two seconds. Service mode
menus provide machine setup, service
tests, and manual control operation.
Display 2) The alarm LED will illuminate Functional Keys
Figure 17 illustrates the operator continuously when a service test item The Next and Previous keys cause the
interface that features a two-line, forty- is placed into manual mode operation. display to step through the various
character display, an alarm indicator The LED serves as a reminder that menus within a group. The report group
(LED), and a keypad for the selection of something remains in manual mode. will sequence around to the top or
specific formatted chiller information bottom of the group when the end or
Normal machine operation does not
menus. The display has backlighting for beginning is reached, respectively. The
require manual mode operation of any
legibility in low light conditions. This (+) and (-) keys cause the setting being
service tests (password protected) items.
backlight is also used to maintain the displayed to increase or decrease,
operating temperature of the display. Operator Interface (LCLD) respectively. If the (+) or (-) key is held
During low ambient temperature periods Operation down for more than 1/2 second it will
the backlight will illuminate. This is done increment or decrement the setting
by the control module controlling the Keypad continuously at 10 counts per second,
backlight current, based on the Figure 17 illustrates the operator until the key is released. (Settings do not
equipment room ambient temperature. interface keypad. The keypad is a sealed wrap around when the end of range is
membrane type with 16 keys arranged 4 reached.) Once the (+) or (-) key has been
Menus by 4. The keys are separated into three
The display includes all operation status, pressed to select a particular setting, the
fields: Enter key or Cancel key must be pressed.
reports, settings, service, and diagnostic
messages. Details of these menus are 1) Report keys are located across the top (The Next or Previous keys will not
discussed later in this section row and are used for viewing of advance until Enter or Cancel is
preformatted information menus. pressed.) A Setting is not changed until
Alarm LED the Enter key is pressed. The Cancel key
2) The second row of keys are setting’s
1) The single red LED located to the right group menus. is pressed if a changed setting should
of the display will BLINK whenever a not be saved. When the Enter key is
machine manual reset (MMR) 3) Functional keys are located across the pressed the display will blank out
diagnostic exists and manual machine bottom two rows and are used to momentarily to indicate to the operator
reset is required to restore operation. input changes. that the keystroke was recognized.
The functional keys are discussed next
since the operation determines how the
user communicates with the report and
setting’s menus.
ABS-M-10A 29
Operator
Guide

If the boundaries of a specific selection 2. Press the Next key to advance, or 5. To reset the chiller press Next until the
are exceeded the operator interface will press the Previous key to backup, diagnostics clearing display stating
display out of range and will not allow while scrolling through the displays “Press (Enter) to clear all diagnostics
that selection to be entered. within each group menu. (To quickly and reset system” is displayed. Press
When Auto is pressed the chiller will go to the last menu item press the Enter. When the diagnostic is cleared
enter an auto mode of operation. When Previous key at the display header.) the chiller will return to the
Stop is pressed the chiller will stop, To Create the Custom Report: operational mode that was
entering the “Unit is Preparing to interrupted by the diagnostic. The
1. Go to one of the Report Groups chiller must not be reset until the
Shutdown” mode. (Chiller, Cycle, Pump/Purge) and select diagnostic condition is addressed, and
During the five-second period a message the desired menu item to add to the corrected. If required, contact the local
indicating the optional emergency stop Custom Report. Trane service agency for assistance.
command will be displayed. The Stop 2. Press the (+) key. The item is now
key is located in the lower right hand 6. Chiller may restart if in “auto” and
entered into the Custom Report differential to start is satisfied. Press
corner. group. stop to prevent starting, if desired.
IMPORTANT 3. To add another repeat step 1 and 2.
If the Stop key is pressed a second time To Change Setpoint
within five seconds an immediate “Panic 4. Up to twenty items can be entered 1. Press Operator Settings key.
Stop” will be executed, overriding the into the Custom Report group. When
there are twenty items in the report no 2. Using the Next key, advance to “Front
normal “Unit is Preparing to Shutdown” Panel Chilled Wtr Setpt.”
mode. more can be added until one is
removed. 3. Using the +/- keys, change the setpoint
To restart the dilution cycle, press Stop as desired. Press Enter.
key. To reenter auto mode press Auto. If 5. To remove an item from the Custom
the leaving water temperature does not Report, press the (-) key, while it is Purging
exceed the differential, to start the displayed. The purge operation mode is normally
dilution cycle is entered for the duration To Change Settings set to “on“ mode.
of the timer, and “Auto waiting need to While in on, purging will occur during
cool” will be displayed along with 1. Press the appropriate settings group
key. machine auto and stop modes of
dilution cycle time remaining. If the operation. To check or set to on:
leaving water temperature is greater 2. Press the Next key at the header
than differential to start, then the restart display. 1. Press Operator Settings key.
auto sequence will occur. 3. Enter password if required. 2. Press Next to advance to “Purge
When the Auto or Stop key is pressed Operating Mode” display.
4. Use the Next/Previous key to bring up
the display will go to the first display of the item to be changed. 3. Use +/- keys to toggle between modes.
the Chiller Report indicating the current Select On. Press Enter.
operating mode. 5. When the item to be changed is on the
display press the (+)(-) to bring up the For manual on purging see maintenance
Using Group Menus new value. section.
1. Select one of the group keys labeled 6. Press Enter to enter the new value.
Chiller, Cycle, or Purge-Pump since Press Cancel to keep the previous Operator Interface (LCLD)
these groups contain preformatted value. Overview
report menus. This will bring up the
respective header display. Pressing To Reset the Chiller The following is a listing of preformatted
Custom Report will bring up its menu information contained in the
1. Press the Diagnostics group key. operator interface, including options.
header display however; there may
not be any items within this group at 2. The Diagnostics display header will be Menu items are listed in sequence and in
this time. Pressing Operator Settings, shown. Press the Next key. columns under each group key.
Service Settings, Service Tests, or 3. Enter password if required.
Diagnostics will bring up its header 4. View all active diagnostics displayed.
display. See the operator interface Investigate and correct the problem
overview for a listing of display that caused the shut down, before
headers and the menu items. proceeding to restart the chiller.

30 ABS-M-10A
Operator
Guide

Figure 18 – Custom Report, Chiller Report, Cycle Report

ABS-M-10A 31
Operator
Guide

Figure 19 – Purge/ Pump Report

32 ABS-M-10A
Operator
Guide

Figure 20 – Operator Settings

ABS-M-10A 33
Operator
Guide

Figure 21 – Service Settings

34 ABS-M-10A
Operator
Guide

Figure 22 – Service Tests

ABS-M-10A 35
Operator
Guide

Figure 23 – Diagnostics

36 ABS-M-10A
Operator
Guide

Operator Interface Detail The custom report sequence starts with


Custom Cycle
the following header display: Chiller Pump/Purge
This section provides detailed menu Report Report Report Report
information.
User Defined Report
Report Menus Press (Next) (Previous) to Continue Cycle Report
The Report Keys (top row) allow the The CYCLE REPORT is used to display
operator to access four report groups machine temperatures and pressures.
that are labeled CUSTOM, CHILLER, If no entries are selected and the next
CYCLE, and PUMP/PURGE. The key is pressed the following is displayed:
CUSTOM report is formatted by the
machine operator. The report groups Custom Chiller Cycle Pump/Purge
No Items are Selected for Custom Report Report Report Report Report
(CHILLER, CYCLE, and PURGE/PUMP)
have preformatted menus. See Operators Manual to Select Entries

When a report group key is pressed the Purge/Pump Report


menu header is displayed. The header If entries exist they will be displayed in The PUMP/PURGE REPORT is used to
display indicates the title of the report the order that they were selected from display run time information regarding
group and a brief summary of the the other report groups. pumps in the machine.
reports contained in the group. This The Chiller Report, Cycle Report, and
enables a user to quickly review each Pump/Purge Report groups contain
report header to determine if the desired preformatted information that cannot be
information is in the group. The header changed.
also serves as the top of the report
indicator.
Custom Chiller Cycle Pump/Purge
Report Report Report Report
Custom Chiller Cycle Pump/Purge
Report Report Report Report

Chiller Report
Custom Report The Chiller Report contains unit
The Custom Report contains information operating condition information. Status,
selected by the operator. The custom water temperature, and setpoints.
report section allows the user to select Chiller Operating Mode: Two lines of
and display up to twenty items of their display indicate the Chiller Operating
choice selected from the CHILLER, Mode depending upon machine status,
CYCLE, and/or PUMP/PURGE report various chiller operation modes that can
groups. The Custom report is the only be displayed is illustrated in the column
report where the displayed information to the right. In the case of timing
is selected by the user. functions, line 2 indicates the associated
The custom report can easily be timer information. Timer functions are
programmed by the following sequence: displayed and inform the operator of
expected delays within the sequence of
Menu Items can be duplicated in the operation.
custom report by pressing the (+) key,
when the desired report is being Operating Mode Line 1 and Line 2
displayed from one of the other report (Two Lines Describing Operating Conditions)
menus. The custom report group can Press (Next) or (Previous) to Continue
contain up to twenty entries. Attempting
to enter another report when the user
custom report is full results in the display
indicating “User Report -> Full.” To
change or remove reports in the custom
report group, simply press the (-) key
while it is being displayed and the report
item is removed.

ABS-M-10A 37
Operator
Guide

Table 4 – Chiller Operation Mode Displays


Machine Condition Displayed Message (First Line/Second Line)
Reset Resetting
Stop Local Stop: Cannot be overridden by any External or Remote Device
Remote Stop Remote Display Stop: Chiller may be set to Auto by any Ext or Rmt Device
External Unit Stop Remote Run Inhibit from External Source
Unit Remote Stop Remote Run Inhibit from Tracer
Start Initializing
Start Starting is Inhibited by Staggered Start
Time Remaining: Min/Sec
Start Starting
Start Starting
Waiting for Chilled Water Flow
Auto Waiting for Tracer Communications to Establish Operating Status
Auto Auto
Waiting for a Need to Cool
Start Starting
Absorber/Condenser Water Flow
Start Starting Solution Pumps
Start Starting - Pre-heating Solution
Spray Pumps Off
Start Starting - Pre-heating Solution
Spray Pumps On
Run: Normal Cooling Only Unit is Cooling
Run: Low Cooling Unit is Running:
Water Temp Limit Low Absorber/Cds Temp Limit
Run: Evap Limit Unit Is Running
Low Evap Rfgt Temp Limit
Run: Crystallization Sensing Solution Recovery Pump Off
Detection and Recovery Time Remaining Min/Sec
Run: Crystallization Sensing Solution Recovery Pump On
Detection and Recovery Time Remaining Min/Sec
Dilution Cycle Dilution Cycle Remaining:
Min/Sec
Waiting for a Need to Cool
Dilution Cycle Dilution Cycle Remaining:
Min/Sec
Diagnostic Shutdown Auto
Dilution Cycle Dilution Cycle Remaining:
Min/Sec
Diagnostic Shutdown Stop
Dilution Cycle Dilution Cycle Remaining:
Min/Sec
Local Stop
Dilution Cycle Dilution Cycle Remaining:
Min/Sec
Remote Stop
Dilution Cycle Dilution Cycle Remaining:
Min/Sec
Remove Run Inhibit from Ext Source
Dilution Cycle Dilution Cycle Remaining:
Min/Sec
Remote Run Inhibit from Tracer
Stop: Transitioning to Stop Transitioning to Stop
Panic Shutdown Panic Shutdown Seq. Complete
Press Auto/Stop to Continue
Diagnostic Shutdown Diagnostic Shutdown Stop
Stop Mode
Diagnostic Shutdown Diagnostic Shutdown Auto
Auto from Auto Mode

38 ABS-M-10A
Operator
Guide

Settings Menus Operator Service Service


Normal machine operation does not
Diagnostics require the use of any service test items;
Settings Settings Tests
Operator Service Service therefore they remain within a
Diagnostics password-protected (+ + - - + +) menu.
Settings Settings Tests
The Service Settings menu has three Manual operation of these items will
submenus within it. The first is non- effect chiller operation and will cause
Operator Settings password protected and consists of all unreliable operation, if left in manual
The Settings keys (second row) allow the settings, feature enables, setpoints mode. It is therefore recommended that
the operator to select from four menu etc. While they are seldom changed by a only qualified personnel use service
groups. Entering a group allows the user, changes in them do not seriously tests.
operator to select any items contained effect the protection or reliability of the
within the group. A setting’s group starts chiller.
at a header display when the selected Operator Service Service
setting’s key is pressed. The other submenus (field start-up and Settings Settings Tests
Diagnostics
machine configuration) are protected,
Operator Level Password each with a separate service level
The operator settings, service settings password. These are for changing
(basic setup), and diagnostics group Diagnostics Menu
parameters and settings regarding field The Diagnostics Menu contains both
menu items can be secured by an commissioning and fundamental active and historical information. The
operator level password. protection and control of the chiller menu also contains the facility to clear
This feature is predetermined and set at subsystems (Field Start-up) or for active diagnostics, historic diagnostics,
the factory. If operator password is programming of the unit control module and purge diagnostics as individual
desired contact your local Trane service (UCM) as to how the specific chiller was groups. To clearly enunciate the
company. On all machines, this feature is built in the Factory (Machine occurrence of a diagnostic, the display
selected within a higher level security Configuration). will automatically go to this menu and
accessible within the service level Once properly set, these menus should display certain messages as explained
password field start-up group. never be changed again without specific below.
When this feature is enabled, the display knowledge of the effects of the changes. New Diagnostic Display Sequence
following the header will state either In rare instances, certain field problems When a new diagnostic is sensed by the
“Settings in this menu are LOCKED or may be corrected by making changes in system, the display will reset to the
UNLOCKED.” If LOCKED, the second line these protected menus but certain diagnostic menu. A “one-time” screen
will state “Enter password to unlock.” aspects of chiller reliability may be will be displayed to inform the user that
Operator level password is compromised. The main reason these a new diagnostic has been detected.
(-+-+-+ & Enter). An incorrect password are accessible at all is for field
will result in the message “access commissioning and to allow for the This “one-time” screen will vary
depending on the type of diagnostic
denied.” If UNLOCKED, the second line programming of service replacement
detected. The two major categories of
will state “Press (Enter) to lock.” modules.
Pressing ENTER will lock all the settings diagnostics are those which are
informational warning only (IFW), and
within the three groups (operator
those which have resulted in machine
settings, service settings (basic setup), Operator Service Service
and diagnostic groups). When locked, Settings Settings Tests
Diagnostics shutdown; machine shutdown manual
reset required (MMR) and machine
menu items can be viewed, however, the
shutdown auto reset (MAR).
second line of the displays will not
indicate “Press +/- to change setting” Service Tests
and any attempt to change a setting will The Service Test menu provides access
cause the second line to momentarily to screens used to change from “Auto”
indicate “setting is locked.” To UNLOCK, mode to Manual mode. Manual mode
sequence back to the screen that states control overrides specific auto control
enter password to unlock the three functions. Tests and status screens
groups (operator settings, service provide a means to check the operation
settings (basic setup), and the of some output and input devices.
diagnostics groups). Anytime a manual mode is selected the
When “Service Settings, Field Start-up” alarm light will remain on.
selection of this feature is disabled the
previous operator password displays
and indications of locked or unlocked is
bypassed and is not shown.

ABS-M-10A 39
Operator
Guide

Adjustable Frequency Drive (AFD) CAUTION


Keypad
Figure 24 illustrates the AFD keypad. The AFD is factory programmed for use
Machine operation does not require in this application. Do not attempt to
using this keypad. The AFD will normally reprogram any parameter as this may
operate in “auto” mode. Only in the case jeopardize machine operation and
of abnormal condition for reset, or by reliability.
service personnel, will this keypad
require usage.
Figure 24 – AFD Keypad Overview (Model JVOP-130P Illustrated)

40 ABS-M-10A
Operator
Guide

Pressing the “DSPL” key advances the Figure 25 – LED Description


Digital Operator through the Menus
illustrated in Figure 25.

ABS-M-10A 41
Maintenance

Maintenance CAUTION
This section contains maintenance
Always allow the chiller to complete a
information for the Steam or Hot Water
Absorption Chiller. dilution cycle before disconnecting the
chiller power source.
Daily Maintenance
To ensure reliable, safe and efficient
operation the following items should be
checked daily as routine maintenance.
This will avoid unnoticed problems that
could lead to down time, and provides
daily data that can highlight trends,
locating potential problems before they
occur:
1. Record and review operating data.
Use the operating log found on the
next page and log the points
suggested.
Familiarization with the daily log
temperatures and other items allows
the operator to identify when a
change occurs, possibly indicating an
abnormal condition. Review the daily
operating history with the service
personnel as necessary or at the next
inspection. (Verify temperatures and
pressure gauges for operation.)
2. Make sure the machine is operating
properly. Cycle the machine on and
off periodically to make sure it starts
and stops properly. This allows safety
devices to sequence through a start-
up to confirm operation.
3. Check the cooling tower for correct
water treatment, machine inlet
temperature and flow, and check
system chilled water (Evaporator
Circuit). Check water flow pressure
drop daily. Clean strainers yearly.
The owner should engage the
services of a qualified water treatment
specialist to obtain the treatment
needed to control tube fouling and
maintain machine efficiency.
Untreated or improperly treated water
will reduce machine efficiency, and
may require extensive tube cleaning
or possible tube replacement, if the
chemical balance of the water is not
controlled.

42 ABS-M-10A
Maintenance

Figure 26
Horizon – Absorption Operating Log
Job Name _____________________________________________ Serial Number ____________________________________________
Machine Model Number _________________________________ Date - Month: ________________ Week: ______________________

Sunday Monday Tuesday Wednesday Thursday Friday Saturday


Item AM PM AM PM AM PM AM PM AM PM AM PM AM PM

Evaporator IN
Pressure OUT

Absorber/Cond IN
Pressure OUT

Accumulated Run Time

Solution Cycle Data Items

S.D.R. Temp.

Solution Leaving LTG

Saturated Condenser Rfgt. Temp.

Absorber Entering Concentration

LiBr Crystallization Margin

Solution Temp. Entering Absorber

Absorber Spray Temp.

Solution Temp. Leaving Absorber

Solution Temp. Entering LTG

Saturated Evaporator Rfgt. Temp.

Evaporator Leaving Water Temp.

Evaporator Entering Water Temp.

Absorber Entering Water Temp.

Absorber Leaving Water Temp.

Condenser Leaving Water Temp.

Steam: Supply Pressure

Steam: Generator Pressure

Solution Pump AFD Auto Speed

Energy Input Command

Purge Status

“ “ Suction Temperature

“ “ Pump Out Rate

“ “ Pump Out Time

“ “ Time Since Pump Out Time Reset

“ “ Chiller Average Run Time

ABS-M-10A 43
Maintenance

Seasonal Maintenance 10. Replace bromide filter.


Cooling Season Preliminary Reminders 11. Purge the machine of non-
The following items should be checked condensibles. Check purge rate after
before seasonal start-up. Contact you the machine is started. Keep machine
local Trane service representative to energy rate reduced until purge rate
perform the service. diminishes during unit operation
1. Check unit vacuum. Check the actual 12. Log unit-operating data. Check
unit internal vacuum to determine if temperatures and pressures
purging is required, before the unit throughout the fluid cycle. Check that
can be safely started after extended LTSP, ASP, and RP Amp draw and
shutdown. See unit vacuum checkout. voltages are normal and not
The maximum internal pressure is excessive.
dependent on the machine 13. Water treatment It is recommended
temperature. If purging is required that all tubes be tested periodically
follow purging instructions (Purge by a qualified nondestructive tube
section). testing service. This testing will
2. Determine the purge pump condition. confirm tube condition and identify
Run the pump and verify potential problems.
performance. Check the ultimate Extended Shutdown
pressure performance and change oil/
repair pump if required. Drain water circuits (Evap, Cond/Abs)
completely, and blow out all water from
3. Prepare machine for cooling. Fill tubes and water boxes.
condenser, vent air from the
condenser water boxes. Venting will Main power must remain applied to the
remove air from within the piping and unit to allow automatic purging.
avoid nuisance trips of the condenser
flow switch input.
4. Check all piping connections for
possible water leakage. Check
absorber, condenser, evaporator
water piping. Assure that any off
season work and reassembly is
complete.
5. Check pressure drop across the chiller
evaporator and condenser sections.
Compare to unit design conditions.
6. Visually inspect electrical system. Look
for signs of any alterations performed
since the last operational season, and
verify wiring is intact. Clean AFD’s of
dust and grime.
7. Confirm the chilled/hot water pump,
cooling water pump and cooling
tower is interlocked. Check the field
proof of operation interlocking wiring
for the chilled/water flow, and for
condenser water flow.
8. Determine electrical condition of
pump motor contactors.
9. Test run the unit. Check machine
control sequence.

44 ABS-M-10A
Maintenance

Seasonal Start-Up Unit Chart 1 – Shutdown Machine Vacuum Chart


Vacuum Check
Start-up after extended shutdown
should not be attempted until the unit
vacuum is measured and compared with
Chart 1. Any combination of temperature
and pressure that falls on or below the
line of Chart 1 indicates a safe condition.
The unit purging is required before start-
up if the measured vacuum is above the
acceptable limit.
Check unit internal vacuum at the
absorber service valve located on the
side of the absorber shell. This valve is
above the liquid level in the chiller.

20 30 40 50 60 70 80 90 100 120 140


[-6.7] [-1.1] [4.4] [10] [15.6] [21.1] [26.7] [32.2] [37.8] [49.9] [60]
Machine Temperature °F [°C]

ABS-M-10A 45
Maintenance

Purging During Extended Unit Purge as a Maintenance Tool


Shutdown Purge activity indicates non-
During periods of extended shut down, condensables within the chiller.
when chiller will not be operated, the Excessive purging activity may indicate
operator can open an additional hand an air leak or unusual inhibitor
valve to provide a path for non- consumption. An inhibitor analysis may
condensables between the evaporator/ be required. The 24 hour fault timer
absorber section and the generator/ monitors the total pumpout time within
condenser section. Reclose this manual any 24 hour period, and if it exceeds the
valve before the chiller is placed into preset timer setting a fault signal is
operation. generated to alert the operator that
Purifier Purge Service Pumpout purge activity is excessive. The operator
Operation interface provides access to this data in
Servicing may require continuous the pump/purge report group.
pumping out of non-condensables. In Note: The pumpout time only
this case, “service pumpout” mode can accumulates the minutes of pumpout
be used. activity of the automatic pumpout
To enter Service pumpout mode select operation. It does not accumulate the
“Service Pumpout - ON” at the purge time of pumpout for service pumpout
screen within the Operators Settings operation or timed pumpout operation.
group. The condensing unit, vacuum
pump, and valve all turn “on.” Service
pumpout will run continuously until
manually selected to another mode. No
minutes will accumulate on the
pumpout timer in the service pumpout
mode.
Aux. Absorber Pumpout -Manual
The absorber is automatically depleted
of non-condensables during chiller
operation by the eductor operation, and
the absorber motorized valve. If manual
pumpout is desired, this can be
accomplished by way of the manual
hand valve and the temporary
connection of an auxiliary vacuum
pump. Manual purging the absorber
must only be performed during machine
operation when the dilute solution level
is below the top of the absorber.

46 ABS-M-10A
Maintenance

Machine Checkout Table 5 – Machine Inspection Recommendations


Machine Inspection Items Months
General For the following Machine Items, refer to the applicable section in this Manual
To assure machine reliability, safety, and and/or contact a Trane service technician. 3 6 12
efficiency, routine maintenance of the 1) Analyze unit solution to determine inhibitor consumption X
chiller/control system is required. 2) Check unit control panel Sequence of operation X
Check all wire terminal connections for tightness
During servicing, always operate the Check AFD’s for cleanliness. Follow the corrective action in Table 12. X
chiller from the unit local control panel. Always keep cover(s) closed on control panel and connection boxes.
Always allow the chiller to complete a 3) Check unit safeties setting and function – Contact a Trane service technician. X
dilution cycle before disconnecting 4) Check purge system: X
power. See sequence of operation for • Checking belt tension and condition. X
dilution cycle details located in the • Check purge pump - ultimate pressure. X
controls section. • Replacement or overhaul purge pump – Contact a Trane service technician. 3 yr
• Check for leaks, purge valves – Contact a Trane service technician. X
• Clean condensing unit coil – Contact a Trane service technician. X X
CAUTION • Check condition of purge vacuum pump oil – Contact a Trane service technician. X X X
5) Check volts and amps of solution pumps and refrigerant pump. X
Always turn electrical power supply(s) 6) Clean tubes. X
off before undertaking any maintenance • Brush tubes. X
that does not require machine • Check water quality analysis of evaporator water and cooling water. X*
operation. • Eddy current tube inspection should be conducted every third year of operation. 3 yr
7) Solution Pumps: Verify amps, Listen to operation. X
Machine inspections should be *Or as directed.
performed periodically. Some inspection
is recommended every 3 months, Service Frequency Recommendations The system water circuit is a closed
whereas others are at 6 and/or 12 These recommendations may vary circuit and normally will not accumulate
months. when unusual machine room conditions an appreciable amount of sludge or
exist. Lithium bromide analysis is scale. However, if cleaning should be
Inspection Frequency
recommended yearly. The purpose is to required, use the same method outlined
Recommendations
Table 5 illustrates machine related determine solution inhibitor levels and for the cooling water circuit.
replace as needed to control solution
inspection items and the appropriate
quality. Condenser and Absorber
frequency. Performing the maintenance Tube Care
at the intervals suggested will provide System Chilled Water (Evaporator)
the basis for machine reliability. Circuit and Water Treatment Internal fouling of the condenser and
It is recommended that the owner absorber tubes will seriously reduce
When appropriate, contact your local their ability to transfer heat to the cooling
engage the services of a qualified water
Trane service representative and follow water.
treatment specialist to make tests and
component manufacturer
recommendations in all cases, and check recommend the treatment necessary to The resulting higher temperature and
control any contaminating material from pressure have several undesirable
local codes for any additional regulations
the water. effects.
that may be required.
THE TRANE COMPANY ASSUMES NO 1. The refrigerant condensing capability
RESPONSIBILITY FOR EQUIPMENT of the condenser is reduced.
FAILURE RESULTING FROM
UNTREATED OR IMPROPERLY 2. The absorber saturation pressure is
TREATED WATER. increased because the solution is not
cooled.
It is further recommended that all tubes
be tested periodically by a qualified 3. The higher condenser saturation
nondestructive tube testing service. This temperature may cause the formation
testing will confirm tube condition and of hydrogen gas, which must be
identify potential problems. purged from the absorber.

Check water flow pressure drop daily. NOTE: To insure reliable and efficient
Clean strainers yearly. machine operation, the cooling water
must be properly treated. The Trane
Company assumes no responsibility for
equipment failure resulting from
untreated or improperly treated water.

ABS-M-10A 47
Maintenance

Cleaning the Tower Water Figure 27 – Tube Cleaning Arrangement


Circuit
Check water flow pressure drop daily.
Clean strainers yearly or as conditions
require.
Water available for cooling frequently
contains minerals that will precipitate out
on the walls of the tower water circuit in
the form of a carbonate scale. Cooling
towers collect foreign material that will
deposit in the tubes and limit machine
efficiency. At a minimum, condenser and
absorber tubes should be brushed after
each cooling season.
To insure maximum efficiency, the
cooling water circuit must be kept free of
both sludge and scale. Even a very thin
coating of scale will greatly decrease the
heat transfer capacity of the absorber
and condenser bundles. The condenser
tubes should be inspected once a year to
determine if mechanical cleaning is
required and if the water treatment is
effective.
Two methods for cleaning the tubes are:
1. Mechanical All materials used in the external
2. Chemical Water Box Cover Bolting
circulation system, quantity of solution, Requirements
The mechanical method is used to duration of cleaning period and any (Refer to Table 7)
remove sludge and loose material from required safety precautions should be
the tubes. Access to the tubes is approved by the company furnishing the To insure gasket sealing, the bolting
obtained by removing the absorber and materials or performing the cleaning. procedure of covers must be as follows:
condenser water headers. To loosen the Table 6 lists the liquid volume (in gallons/ • Use anti-seize compound on all bolts
material, work a nylon or brass bristle liters) of the tubes and water boxes. before installing water box covers.
brush through the tubes (a brass brush • Insert and snug up the first 6 to 10 bolts
is recommended). After the material has Table 6 – Tube and Water Box Liquid Volumes towards the centerline of each cover.
been loosened, flush the tubes with clear (Gallons) Insure the cover is flat against the
water. Tube and Water Box Volumes mating surface and the bolts are just
(US Gallons/Liter) more than finger tight.
Scale deposits are best removed by
chemical means. The tower water circuit
Unit Size
500
Evap.
164 / 622
Abs./Cds.
328 / 1241
• Tighten bolts starting from the center at
top and bottom of each cover and
is constructed of copper, steel and cupro- 600 189 / 717 375 / 1419
working outwards to the corners.
nickel. 700 244 / 923 435 / 1648
800 273 / 1032 481 / 1820
Figure 27 illustrates a typical chemical- 975 300 / 1137 570 / 2158 Table 7 – Bolt Torque Requirements
cleaning hookup. The cleaning hookup is 1100 325 / 1231 612 / 2317 Bolt Size Torque
made to pipe fittings installed in the 1225 350 / 1325 654 / 2476 (Inch) (Ft. Lbs.) N-M
absorber supply and condenser return 1350 375 / 1419 696 / 2635 1/4 7 9.5
piping. 5/16 15 20.0
3/8 40 54.0
7/16 52 70.0
1/2 100 135.0
5/8 160 216.0
3/4 295 400.0
7/8 410 555.0
1 550 745.0
Note: General bolt torque’s requirements for grade 5 zinc-
plated course threaded bolts are listed above.

48 ABS-M-10A
Maintenance

Cooling Tower Temperature


Control
Control The maximum rate of tower temperature
1. Cooling tower water temperatures change must be kept to a minimum.
must be maintained at or above 65 F Inherent problems with larger tower
for reliable operation. Control panel water fluctuations are:
logic circuits allow start-up at • First, the potential to drop the leaving
temperatures well below the design water temperature to the chillers
selection temperature and will protect differential to stop setpoint.
against unsafe conditions. • Second, cause a crystallization
detection and recovery cycle to be
2. To avoid oscillatory effects of tower entered (typically lasts approximately
water fluctuations being influenced on 11 minutes after which the chiller will
the leaving chilled water temperature restart and proceed to reestablish
entering tower water temperature chilled water temperature control).
control should be kept constant. • Inefficient operation because unable to
Any time tower entering temperature is maintain margin.
at or below design, the potential for A cooling tower bypass or variable
“Low cooling entering water speed fan is recommended for stable
temperature limit” exists. Depending on control of the chilled water circuit.
the chiller load, the actual temperature of
the water will determine the likelihood to See Figure 28.
see this limit actively limiting machine
capacity. The further away from design
that the water temperature deviates the
more limiting potential exists. This
control system logic feature is built in to
assure continued machine operation and
machine reliability, and to control the
potential for salt carryover and/or
crystallization.

Figure 28 – Typical Machine Piping and Instrumentation

ABS-M-10A 49
Maintenance

Tube Support Locations


Table 8 identifies the location of the internal tube supports.

Table 8
LH Tube
Unit sheet
Size Bundle to 1st 1st - 2nd 2nd - 3rd 3rd - 4th 4th - 5th 5th - 6th 6th - 7th 7th - 8th 8th - 9th 9th - 10th 10th - 11th 11th - 12th 12th - 13th 13th - 14th
500 abs 42 7/8 42 7/8 42 7/8 42 7/8 na
evap 42 7/8 42 7/8 42 7/8 42 7/8 na
Cond 42 7/8 42 7/8 42 7/8 42 7/8 na
gen 21 3/8 21 3/8 21 3/8 21 3/8 21 3/8 21 3/8 21 3/8 21 3/8 na
600 abs 40 5/8 40 5/8 40 5/8 40 5/8 40 5/8 na
5 5 5 5 5
evap 40 /8 40 /8 40 /8 40 /8 40 /8 na
Cond 40 5/8 40 5/8 40 5/8 40 5/8 40 5/8 na
gen 20 3/8 20 3/8 20 3/8 20 3/8 20 3/8 20 3/8 20 3/8 20 3/8 20 3/8 20 3/8 na
700 abs 39 ¼ 39 ¼ 39 ¼ 39 ¼ 39 ¼ 39 ¼ Na
evap 39 ¼ 39 ¼ 39 ¼ 39 ¼ 39 ¼ 39 ¼ Na
Cond 39 ¼ 39 ¼ 39 ¼ 39 ¼ 39 ¼ 39 ¼ Na
gen 19 5/8 19 5/8 19 5/8 19 5/8 19 5/8 19 5/8 19 5/8 19 5/8 19 5/8 19 5/8 19 5/8 19 5/8 na
800 abs 38 ¼ 38 ¼ 38 ¼ 38 ¼ 38 ¼ 38 ¼ 38 ¼ na
evap 38 ¼ 38 ¼ 38 ¼ 38 ¼ 38 ¼ 38 ¼ 38 ¼ na
Cond 38 ¼ 38 ¼ 38 ¼ 38 ¼ 38 ¼ 38 ¼ 38 ¼ na
gen 19 1/8 19 1/8 19 1/8 19 1/8 19 1/8 19 1/8 19 1/8 19 1/8 19 1/8 19 1/8 19 1/8 19 1/8 19 1/8 19 1/8
975 abs 35 3/8 35 3/8 35 3/8 35 3/8 35 3/8 35 3/8
evap 46 38 44 ½ 38 46 na
Cond 52 7/8 53 53 52 7/8 na
gen 23 3/8 26 ½ 26 ½ 26 ½ 26 ½ 26 ½ 26 ½ 23 3/8 na
1100 abs 35 ¼ 35 ¼ 35 ¼ 24 ½ 35 ¼ 35 ¼ 35 ¼ na
3 3
evap 47 /8 47 ¼ 47 ¼ 47 ¼ 47 /8 na
Cond 47 1/8 47 47 47 47 1/8 na
gen 23 5/8 23 ½ 23 ½ 23 ½ 23 ½ 23 ½ 23 ½ 23 ½ 23 ½ 23 5/8
1225 abs 35 35 24 7/8 35 35 24 7/8 35 35 na
evap 47 5/8 47 ¼ 47 ¼ 35 ¼ 35 ¼ 47 5/8 na
Cond 43 1/8 43 1/8 43 1/8 43 1/8 43 1/8 43 1/8 na
gen 21 9/16 21 9/16 21 9/16 21 9/16 21 9/16 21 9/16 21 9/16 21 9/16 21 9/16 21 9/16 21 9/16 21 9/16
1350 abs 35 3/8 35 ½ 35 ½ 35 ½ 35 ½ 35 ½ 35 ½ 35 3/8 na
evap 47 5/8 47 ¼ 47 ¼ 47 ¼ 47 ¼ 47 5/8 na
Cond 47 3/8 47 47 47 47 47 5/8 na
gen 23 ¾ 23 5/8 23 ½ 23 ½ 23 ½ 23 ½ 23 ½ 23 ½ 23 ½ 23 ½ 23 5/8 23 ¾
Table of Tube support locations. Column 1 indicates (inches) from left hand tube sheet to the 1st tube support, column 2 indicates inches between 1st and 2nd supports,
nd rd
column 3 indicates inches between 2 to 3 support, etc.

50 ABS-M-10A
Maintenance

Periodic Purge Maintenance 2. Adjust the tension of the belt once WARNING
again a week after unit operation to
The following information describes the compensate for stretch due to break- Do not touch the belt while it is rotating.
maintenance requirements of the purge in.
system. To assure efficient and reliable Serious personal injury can result from
machine operation, perform all 3. The adjustment of the belt tension contact with rotating parts. Turn power
inspections and procedures at the should be made by parallel shifting of OFF before servicing belt.
prescribed intervals. Keep a record of all the motor. Tighten adjusting nuts or
inspection results to establish proper bolts securely after adjustments.
The small residue remaining in the
service intervals and document changes 4. If required, clean the purge drive belts pump can be forced out by turning the
that occur in purge activity that could with an approved belt cleaner. pump pulley by hand, with the exhaust
reflect on chiller performance. port closed and the intake open. The oil
Periodic Checking
Purifier Purge Check the following points periodically. will spurt out suddenly and should be
The following sections describe the deflected into the drain pan. Avoid
required periodic maintenance: 1. Check if bolts and nuts are tight. extensive operation with the exhaust
2. Check to see if the gas ballast valve port sealed; excessive internal pressure
Weekly
and solenoid valve is operable. may loosen the shaft seal.
Check the vacuum pump oil quality.
Semi-Annually 3. Check for leakage of oil from the shaft WARNING
Inspect the air-cooled condensing unit seal or pump casing.
Use extreme care. The oil will be hot
coil and clean as needed. Clean the coil 4. Replace vacuum pump oil periodically and can cause severe burns.
from the fan side using compressed air to maintain pump performance.
or coil cleaner. A fouled coil will reduce Check the oil turbidity through the oil Oil Filling
purge efficiency and capacity. level window. 2. After removing all oil, close the drain
Purge Vacuum Pump and Motor Oil Replacement and pour three or four ounces of clean
Assembly Replace oil when the ultimate pressure Duo-seal oil into the intake port. Open
of the pump itself is unsatisfactory or the the exhaust port and run the pump for
Drive Belt Checkout and Adjustment oil becomes too dirty. Although the oil a short period to completely circulate
becomes somewhat dirty during the new oil. Drain the oil and force out
WARNING the residue as above. Repeat flushing
operation, the pump can be operated
Do not touch the belt while it is rotating. providing an adequate suction vacuum with new Duo-seal oil until flushing
is obtained. Milky oil indicates high remains clean and free of color and
Serious personal injury can result from moisture content. Excessive pumping foreign matter. One or two flushings
contact with rotating parts. Turn power and/or purging when noncondensables normally cleans accumulated residue
OFF before servicing belt. are not present will cause water vapor to and protects the pump.
be drawn from the chiller which Operate the pump and check the
CAUTION condenses into the oil. Limit the use of ultimate vacuum achievable.
service pumpout and verify correct
ballast settings, and verify timed 3. Repeat steps 1 - 2 several times if the
Belt tension maintenance is important.
pumpout settings. pump does not perform.
Too tight or loose adjustment can cause
damage to the shaft bearings. Too loose Oil Replacement 4. Replace the dust cap. Start the purge
an adjustment allows the belt to slip Replace the oil using the following pump with the manual hand valve
and shorten the lifetime of the belt. procedures: closed and allow it to operate one
hour to warm the oil. Recheck the oil
1. Check pulley alignment and V-belt 1. Warm the oil by operating the pump level with the oil at operating
tension. The belt should depress for approximately fifteen minutes with temperature.
about 1/2 to 3/4" [13 to 19 mm] under the intake closed. Stop the purge
light hand pressure applied to operation from operator setting group Recommended Oil
midway between the pulleys. Belt menu. Open the drain oil cock and Welch Duo Seal Oil, Oil-1
adjustments are made by loosening drain, almost all the oil. Most of the oil Once a Year
the motor hold-down bolts and sliding will drain out freely. Lubricate the purge pump motor with a
the motor toward or away from the good grade of machine oil.
vacuum pump as required.

ABS-M-10A 51
Maintenance

Solution Maintenance Solution Filter Procedure


Before opening the filter to clean or
To maintain machine efficiency, the Rinsing the Filter exchange elements, the following should
lithium bromide solution must be As the filter is used to remove solids be completed:
analyzed periodically to determine if the from the lithium bromide solution, some
inhibitor levels are within acceptable inhibited solution (lithium molybdate in 1. Close the inlet feed valve (LTSP on
limits. A laboratory test is required to the lithium bromide) will be collected Horizon) stopping the flow of Lithium
determine the inhibitor level (and other with the solids. Periodically this inhibited Bromide to the filter.
additive levels), and any necessary solution must be returned to the solution 2. Open the refrigerant pump discharge
adjustments. To maintain the correct for proper filter operation and before any service valve and the service valve
levels, additive and inhibitor must be time the filter is cleaned. Introducing from step 1. The purpose is to provide
added periodically to the lithium refrigerant water to dilute the brine refrigerant flow through the filter
bromide solution. It is recommended solution will return the lithium molybdate assembly.
that the solution be analyzed once a year inhibited solution but not remove the
if the machine is used for comfort filtered out solids and particles. Also, this 3. Operate the refrigerant pump for
cooling and twice a year if it is in will allow for easier filter element approximately 5 minutes. Do not
continuous or critical. (Monitor the lapse cleanup or changeout since the servicer exceed 10 minutes as this may cause
time meter and provide this information will be dealing with primarily refrigerant excessive lost of refrigerant water. The
when lithium bromide analysis is water versus a stronger lithium bromide refrigerant flow will be through the
performed). Contact your local Trane concentration. filter and returning to the brine side of
Service Agency for qualified lab testing. the chiller. Operation of the pump for
The filter assembly should not be used too long a period could deplete all
Air leaks will accelerate inhibitor for continuous operation. It should be refrigerant water. Continue procedure
depletion resulting in excessive periodically valved into operation as until the entire filter canister feels cold.
hydrogen production. Since absorption needed for cleanup purposes only. If the
machines are unable to cool effectively filter has been in operation for more than 4. Close the refrigerant pump discharge
when excessive hydrogen is formed, one month, the following procedure valve and the filter assembly service
machine operation under these must be completed to insure proper valve.
conditions is not recommended until the operation and solution maintenance. 5. Change or clean filter elements as
leak is eliminated. needed. Refer to Cleaning the Filter.
Note: This machine uses lithium
bromide inhibited with lithium
molybdate and lithium hydroxide.
Lithium bromide that contains other
inhibitors cannot be used in this
equipment.

52 ABS-M-10A
Maintenance

Cleaning the Filter 1. Close the filter system isolation


Periodic cleaning of the filter is valves. This isolates the filter system
necessary. Experience has shown a new from the unit. Servicing the filter will
filter, versus a full or plugged filter, will not affect unit operation.
have negligible differential pressure 2. Remove the pipe plug from the
between the inlet and outlet; therefore service valve located immediately
other means of determining flow can be next to the filter. Open the valve to
used, for example, a sight glass, flow break the vacuum in the filter system.
meters, etc. The particle size rating for A container may be necessary to
the cleanable filter is approximately 150 catch solution draining from the
micron. The disposable filter is rated at valve.
approximately 30 microns. While these
should not be considered absolute 3. Open the filter assembly by loosening
values, they do provide a range of the filter assembly bolt located in the
cleanliness that the solution can attain. center of the filter head. The filter
These ratings are based on nominal flow may be drained prior to disassembly
and will vary as flow rates vary. via the drain bolt located on the
bottom of the filter tank.
To clean the filter, follow the given
procedure. 4. Remove the filter tank from the filter
head.
Precaution: As will all chemicals, avoid
getting the solution ON YOU or IN YOU. 5. Clean the filter tank and the reusable
Do not eat or drink while handling the filter element. The element is most
Lithium Bromide solution. The effectively cleaned by backwashing
technician should use personal with a high-pressure spray device.
protective handling equipment. This 6. Place the clean element in the filter
should include, but not limited to, gloves tank.
for hand protection, splash goggles or
safety glasses, and an apron or 7. Reassemble the filter, making sure
equivalent for body protection. that the o-rings are properly seated. A
thin layer of silicone grease applied to
the o-rings assures a leaktight seal.
CAUTION
8. Tighten the filter assembly bolt. This
LITHIUM BROMIDE! should be torqued to 50-55 ft-lbs.
LITHIUM BROMIDE IS NORMALLY 9. Use the service valve located
NONTOXIC; HOWEVER, OTHER immediately next to the filter to
CHEMICALS MIXED WITH THE evacuate the filter system. After
SOLUTION CAN CAUSE IRRITATION evacuation, close and plug the valve.
AND ADDITIVE VAPORS CAN CAUSE
NAUSEA. ALWAYS PROVIDE 10. Open the filter system isolation
VENTILATION TO REMOVE valves.
ACCUMULATED VAPORS.
In case of accidental contact with the
solution, wash the affected area with
water immediately.
Precaution: Make certain that
appropriate application equipment is
locked and tagged-out safely, as
applicable. This should include, but not
limited to, pumps, motors and other
devices that may affect solution flow or
pressure.

ABS-M-10A 53
Maintenance

Pump Operational Care and Pump Maintenance WARNING


Maintenance The solution pump should be
disassembled and inspected at routine Certain procedures common to
Operation intervals. The need to inspect/or service refrigeration system service may expose
First time operation — on initial the pumps are expected to be very operating and/or servicing personnel to
operation or after installation or infrequent. The expected interval liquid and/or vaporous refrigerant. To
overhaul, make the following checks between start-up and the first parts avoid injury or death due to skin
before putting the unit back into replacement is approximately 50,000 exposure or inhalation of refrigerant,
operation. Be sure pump is completely hours of normal operation. This closely follow all safety procedures
filled with liquid. Run unit for only a few assumes proper solution analysis and described in the material safety data
seconds to make sure it operates maintenance is performed. High sheet, and to all labels on refrigerant
smoothly. There should be no unusual amounts of suspended solids may containers.
vibration, grinding, or scrapping noises. reduce the design life. Parts should be
Only certified service personnel should
replaced as determined by a qualified
CAUTION service the refrigerant system. To avoid
Trane Service Engineer.
injury or death due to electrical shock,
Do not run this unit dry. Even Since the interval between inspection never open access panels to inspect or
momentary operation without pump and repair is quite long it is logical to service the unit without first opening all
and motor casing filled with liquid will replace the wearing components to a like disconnect switches.
damage bearings. new condition anytime that the pumps
Use caution when working on certain
If pump trips on overload current are opened. Therefore pump parts
areas of this unit. Surface temperatures
perform the following checks: should be ordered and on hand any time
may exceed 150°F [65.1°C] on the
the pumps are opened. Table 9 indicates
a. Note discharge pressure with the condensing unit. Contact with bare skin
items that should be inspected and the
pump running. could result in burns and injuries.
action to be taken, whenever the pumps
b. Stop motor, but do not close or adjust are opened. For cutaway view of pump
valves. see Figure 29.
c. Disconnect all power.
d. Reverse any two line leads at motor
starter to reverse direction of rotation. Table 9 – Pump Inspection Items
Item Inspection Action Replace
e. Start motor and note discharge Impeller Balance Remove Material to Balance If Required
pressure. The direction of rotation that Wearing Rings Clearance .006/.009” Nominal Replace if 2 times nominal
provides the higher discharge [.15/.23 mm] Nominal
pressure is the correct rotation. Bearings Axial Wear 3/16” [4.8 mm] Max. Allowed X
Rotor/Journal Scoring Visual Check If Scored Replace with
new motor
Rotor/Stator Liners Wear/Scrapping Adjust/Repair/Replace If Cannot Repair
Circulation Passages Clean Check/Clean N/A
(Clean)
Motor Lead Insulation Abrasion Shrink-wrap/Tape If Required
Motor Windings Megohm Dry Out in Oven If Required
Check All Parts Check for Cracks/Wear Repair or Replace N/A

54 ABS-M-10A
Maintenance

Solution Pumps Motor/Pump Construction


The pump is a single stage, hermetically
This section provides detail of the three sealed, centrifugal pump designed for
pumps located on the machine. Also, Absorption application. The pump/motor
this section includes motor and pump consists of two sections: the motor stator
construction and pump motor cooling shell, and the pump casing. The motor
and lubrication. and impeller can be removed from the
Pumps pump casing without disturbing suction
There are three individual pumps and discharge piping by first separating
operating within the absorption cycle. the two sections, then removing the
Refer to the absorption cycle fluid motor rotor and impeller with the motor
schematic, Figure 3, which illustrates the stator shell as an assembly. The rotor is
fluids and piping arrangements supported with two self-centering
associated with each pump. bearings that are internally tapered to
• The low temperature solution pump mate with complimentary shaped
(LTSP) supplies dilute lithium bromide journals on motor shaft. A coil spring
solution from the absorber through the holds the bearings in firm contact with
heat exchanger then to the low the journals and compensates
temperature generator for automatically for wear.
concentration. Pump Motor Cooling and Lubrication
• The absorber spray pump (ASP) Part of the pumped liquid flows from the
supplies intermediate solution, which casing volute through a spacing
is a mixture of dilute and concentrated between the wearing ring housing and
to the absorber sprays. the attached bearing cap in the wearing
• The refrigerant pump (RP) supplies ring housing assembly through the
refrigerant to the evaporator sprays. bearing cap flange to the cavity between
The (LTSP) and (ASP) operate at variable the welded stator liner and rotor liner.
speeds. A solid-state adjustable The liquid returns to the pump suction
frequency drive (AFD) controls motor through the hollow shaft. The liquid
speed in response to an analog signal cools and lubricates the bearings, and
provided by the unit control module. The carries away heat generated by the
AFD also serves as the start/stop and motor rotor and stator.
overcurrent device for the associated
pump motors.
The refrigerant pump (RP) operates at
constant speed controlled by motor
starter contactors. The refrigerant pump
circuit has an individual current overload
protection device, and each pump has a
winding temperature thermostat.

ABS-M-10A 55
Maintenance

Figure 29 – Typical Pump Assembly and Recirculation Liquid Flow

56 ABS-M-10A
Maintenance

AFD Maintenance
Periodically, inspect the AFD as
described in Table 10, to prevent
accidents and to ensure high
performance reliability.
WARNING
To prevent electrical shock, disconnect
all power before servicing the inverter
and then wait at least five minutes after
the power supply is disconnected and all
LED’s are extinguished.

Table 10 – AFD Component Check and Corrective Action


External Terminals, Connectors,
Mounting Screws, etc. Loose screws or connectors Securely tighten.
Heat Sink Build-up of dust and dirt Blow with dry, compressed air
[39.2x104 to 58.8x104 Pa (4 to 6kg
cm2) pressure]
Printed Circuit Board (PCB) Accumulation of conductive dust or oil Blow with dry, compressed air
[39.2x104 to 58.8x104 Pa (4 to 6kg
cm2) pressure]. If dust and oil
cannot be removed, replace the
board.
Cooling Fan For abnormal noise and vibration Replace the cooling fan.
Cooling Fan Debris on fan blades. Blow off and wipe, if necessary.
Power Components Accumulation of dust and dirt Blow with dry, compressed air
[39.2x104 to 58.8x104 Pa (4 to 6kg
cm2) pressure].
Smoothing Capacitor Discoloration or odor Replace the capacitor or the AFD.

ABS-M-10A 57
Troubleshooting/
Diagnostics

General Information Control Panel Operator Adjustable Frequency Drive –


The following section contains general Interface (Clear Language AFD
trouble shooting information. When an Display) Diagnostics AFD Self Diagnostics
abnormal machine condition exists, the There are three types of diagnostics The AFD controls frequency drive
unit control panel clear language display screens. They are: operation. In the case of an AFD
(CLD) will indicate the condition and a abnormal fault conditions, the Chiller
brief message. Always determine the “Informational Warning Only” (IFW) clear language display will indicate
cause and perform corrective action diagnostics that do not shutdown the absorber spray pump, or low temp
before you restore full machine chiller. generator pump “Drive Fault.” The AFD
operation. “Machine Shutdown Automatic Reset” display will indicate the current fault
Review the indicated message and (MAR); This diagnostic turns the MAR condition. If a fault condition occurs, use
proceed to the appropriate section alarm relay ON, however the machine the reference instruction manual and/or
defined below. will automatically reset and allow restart call [ ] the local Trane Service agency
when the condition corrects itself.
to discuss the fault and determine the
“Machine Shutdown Reset Required” cause.
(MMR); This diagnostic turns the MMR
alarm relay “ON”. The alarm relay turns
“OFF” when the diagnostic is manually
reset.
The second line of the diagnostic
typically identifies additional information
intended to assist the operator to define
and correct problems. Contact the local
Trane Service Representative for
assistance when necessary.
The reason for all diagnostic must be
determined and corrected. Do not reset
and restart the chiller as this can cause a
repeat failure.
After corrective action, the chiller can be
reset and/or restarted. In the case of
“Unit Shutdown - Reset Required”
diagnostic types, the chiller will have to
be manually reset through the
Diagnostics group menu.
Note: For more information and an
overview of the various types of screens
see “Operators Guide: Using the control
panel” (where diagnostics group menu
of the clear language display (CLD) is
explained.

58 ABS-M-10A
Troubleshooting
Checklist

Pump Troubles and Table 11 – Troubleshooting Chart


Trouble Probable Cause (Item Number)
Corrections Pump will not start 12345678
In the event that trouble occurs refer to Pump will not deliver liquid 9 10 11 12 13 14 15 17
the Troubleshooting Table 11 for a listing Pump loses prime after starting 10 11 12 13 14 15 17
of the more common pump troubles and Capacity too low 10 11 12 13 14 15 16 17 18 19
probable causes Discharge pressure too low 10 11 12 13 14 15 16 17 18 19
Pump motor overload 1 2 5 8 10 15 16 18 20, 21
CAUTION Motor overheats 1 8 15 16 17 18 19 20 21 22
Noisy installation 11 12 13 14 15 17 18 20 23 24 25 26 27 28
If the pump has stopped for unknown Excessive vibration 24, 26, 28
reasons, the motor may be grounded to Excessive maintenance 2 10 11 12 13 14 15 16 17 18 20 21 22 24 26 27 28
full line voltage. Disconnect primary Leakage from motor frame 29 30
power before proceeding.

Probable Causes 9. Pump Not Running. Check power 22. No Fluid Flowing Through Motor.
1. Motor Incorrectly Wired. Refer to unit supply to assure power is at line side Fluid must circulate through wearing
wiring diagram and motor wiring of motor starter. ring-housing spacing and holes in
diagram on inside of motor terminal 10. Impeller Clogged. Inspect impeller wear ring (208) and back through
box cover. and remove obstructions. hollow shaft (229) to the pump
suction.
2. Incorrect Motor Voltage. Voltage at 11. Pump Not Completely Primed.
motor terminals must be within 10% Completely fill pump and suction 23. Noise Caused By Other Equipment.
of motor nameplate voltage. Check line, and purge unit. Investigate and correct.
voltage at load-side terminals on 12. Air Leaks In Suction Piping. Inspect 24. Loose Parts. Inspect pump. Tighten,
motor overload. suction piping, gaskets, and fittings. repair, and replace as necessary.
3. Fuses Blown. Replace using correct Repair or replace as necessary. 25. Magnetic Hum Due To Electrical
fuse size. See panel nameplate. 13. Air Or Gases In Liquid. Purge unit, Input. Check for high or unbalanced
4. Thermal Overload Protection Open. repair system to exclude non- voltage or broken line. Voltage must
With power removed, remove the condensables. be within 10% of motor nameplate
wires from K1 and K2 and check for voltage and (current) not more than
14. Motor Overheating. Investigate and 20% unbalanced.
continuity from K1 and K2 of the eliminate cause of overheating.
motor. If circuit is open, allow motor to 26. Mechanical Unbalance. Check with a
cool and check continuity again. If still 15. System Temperature Higher Than vibration meter or by pIacing hand
open, call service to check motor. Design Temperature. Check and on unit. Dismantle and correct
correct temperature. Check machine balance.
5. No Current In One Line To Motor. cycle temperatures.
Check voltage on all lines. Voltages 27. External Loading On Pump. Check for
must be within 10% of nameplate 16. Wrong Direction Of Rotation. Reverse external mechanical stress on pump
voltage and (current) not more than direction of rotation. from suction and discharge piping.
20% unbalanced. 17. Obstruction In Piping System. Inspect Adjust or add support if necessary.
6. Motor Winding Grounded To Motor piping, remove obstruction. 28. Bearing or Spring Damaged Causing
Frame. REMOVE ALL POWER. 18. Mechanical Defects. Check for worn Binding. Remove, disassemble, and
Contact you local Trane service wearing rings, damaged impeller, inspect parts.
representative. worn or seized bearings, or damaged 29. Condensate Due To Change In
7. Motor Windings Open. REMOVE ALL springs. Temperature. When subjected to
POWER. With motor leads 19. Speed Too Low. Check power supply changes in temperature, liquid
disconnected, check each motor and control, or excess mechanical or condenses on the encapsulated
winding resistances. Values should be hydraulic loads. stator windings and must be
within 10%. permitted to drain out of the
20. Speed Too High. Check power supply condensate drain holes provided in
8. Foreign Object in Motor or Pump. and control, or loss of mechanical or
REMOVE ALL POWER. Reconnect the stator housing.
hydraulic loads.
motor leads with any two leads 30. Hole In Stator Can. If liquid draining
interchanged: try starting the motor in 21. Foreign Material In Close Running from pump is pumpage rather than
reverse direction. If pump runs, Fits Of Unit. Disassemble and clean condensate, there may be a hole in
reconnect to original connection and thoroughly. the stator can. Disassemble and
determine if pump now runs. This inspect.
procedure will sometimes remove a
small obstruction blocking the unit.

ABS-M-10A 59
Unit Wiring
Diagrams

External Electrical Connections


The electrical wiring in this section is
intended to show the relationship
between externally connected devices
that are needed by the control panel to
sequence the machine.
If there is a machine diagnostic condition
occurring the main control panel clear
language display will provide a
message, and basic troubleshooting can
be performed. The local Trane service
agency can provide qualified personnel
for assistance to test appropriate points
within the electrical system; field wiring
to the machine, or machine wiring.
Required
Inputs and outputs that must be
provided are identified as Required.
Required wiring is used to provide
reliable machine operation. Failure to
provide this wiring may cause machine
failure.
Acronyms
1. Binary Output (contact closure) (BO)
2. Binary Input (BI)
3. Analog Input (4-20mA or 2-10Vdc) (AI)
4. Analog Output (AO)
External
The electrical connections between the
machine and external devices that are
not machine mounted are illustrated in
Figure 30.
The chiller control system must be field
wired to the items identified as
REQUIRED. Other items are identified as
recommended or optional.

60 ABS-M-10A
Unit Wiring
Diagrams

Required Wiring includes:


Chilled water pump control (start/stop) 1U3-J12-1-2 BO
Chilled water pump flow switch 1TB3-9-10 BI
Condenser water flow control (Start and stop) 1U3-J14-1-2 BO
Condenser water flow switch. 1TB3-11-12 BI
Energy Valve 1U5-J8-1-4 BO
Steam transducer 1U3-J9-1-10 AI
Optional
Optional use inputs and outputs are identified Optional. These connection points are
not required because the condition of use does not effect machine reliability or
operation. Note: 1U7, 1U8, 1U9 and 1U10 are optional modules that are provided
when specified on the sales order.
Optional Status Wiring (Std):
Limit Warning status 1U3-J20-1-2 BO
Alarm, Manual Reset required status (MMR) 1U3-J18-1-3 BO
Alarm, Auto Restart status (MMR) 1U3-J22-1-2 BO
Alarm, Purge Status 1U4-J16-1-3 BO
Output Signal
Hot water pump flow control (start/stop) 1U3-J10-1-2 BO
Optional Input Signals (Std):
External auto start/stop N.C. (local auto mode req.) 1U3-J5-1-2 BI
Emergency Stop N.C. (Manual reset req.) 1U3-J5-3-4 BI
Outdoor air temperature sensor for CWR 1U3-J5-5-6
External Chiller Capacity Limit Enable (Jumper
(1U3-J7 1 to 2)
Closed = Enable) BI
External Chiller Capacity Limit Analog Input 1U3-J7
11 (-) to 12 (+) AI
Optional Modules not Provided Unless
Specified on the Sales Order
1U7 – Options Module
1U8 – Tracer Communications Module
Options Module required for the following:
Optional Status:
Maximum Capacity status 1U7-J14-1-2 BO
Optional Control:
Tracer controlled relay 1U7-J18-1-3 BO
Tower Temp Low Relay 1U7-J20-1-2 BO
Optional Inputs:
Tracer temperature sensor 1U7-J7-7-8
External Chiller water setpoint isolated 2-10 Vdc
or 4-20mA 1U7-J9-4-5 AI
Optional Output
Steam or Hot Water Valve Energy Valve
Monitor Output 1U7-J7-1-2 AO
Optional modules for communications
outside of main unit control panel.
1U8 Tracer Communications module
Required for Comm. with Tracer 1U8-J3-1-2

ABS-M-10A 61
Unit Wiring
Diagrams

Figure 30 – Field Wiring Connection Diagram – Detail of Control Panel Connection Points

62 ABS-M-10A
Unit Wiring
Diagrams

ABS-M-10A 63
Unit Wiring
Diagrams

Figure 31 – Field Wiring Connection Diagram – Detail of Control Panel Connection Points

64 ABS-M-10A
Unit Wiring
Diagrams

ABS-M-10A 65
Unit Wiring
Diagrams

The chiller control panel requires proof Required Absorber/Condenser Water


of water flow for both evaporator Flow Control
(chilled) and absorber/condenser The chiller requires start and stop control
circuits. A flow switch and motor starter of the abs/cds water flow. The condenser
auxiliary contact connections satisfy this pump motor starter and water flow
requirement. This input must be hard control signal must be hard wired in
wired to the chiller control system. The series with the chiller panel output
flow switch must be set to open when contacts provided. Condenser water flow
flow drops to 70% or below of design must start and stop as determined by the
evaporator flow. control panel. Failure to stop flow risks
evaporator freeze-up.
CAUTION
The control panel is designed with a CAUTION
contact closure used for control of the
water pump operation. The evaporator Damage caused by operation without
and condenser water pumps are proper water pump and flow sensing
electrically interlocked and sequenced interlocking is not warranteed.
by the control panel. Proof of both Required Chilled Water Flow Control
chilled and condenser water flow must The chiller requires start and stop control
be provided to the control panel. Under of the chilled water flow. The chiller
no conditions can chiller operation be controls also provide a chilled water
terminated by stopping chilled water pump off delay feature. Under no
flow. Under no situation can condenser conditions can chiller operation be
water flow exist without chilled water terminated by stopping chilled water
flow. flow. For remote start/stop control,
The above interlocking arrangement always use the auto/start/stop input of
assures proper sequence of operation, the chiller and allow chilled water flow to
and helps provide protection against continue up to thirty minutes after
mechanical failure from improper termination of the machine dilution cycle.
operation. Table and Figures
Tables 12 and 13 provide electrical data
by voltage and unit size.
Table 14 identifies electrical devices and
their description.
Figures 32 to 35 illustrate typical machine
wiring and field connected wiring. These
schematics are typical, therefore, refer to
the schematic diagrams supplied with
the particular chiller control panel that
reflect the actual wiring “as built.”
Figures 36 to 40 illustrate connection
points of unit and control panel wiring.

66 ABS-M-10A
Unit Wiring
Diagrams

Table 12 – ABSD 500-1350 Ton – 50 Hertz Electrical Data


4B1 Refrigerant 4B2 Absorber Spray 4B3 Lt Solution Total Motor Control Minimum Maximum
Unit Pump Motor Pump Motor Pump Motor Rating Circuit Circuit Fuse
Size Voltage FLA HP KW FLA HP KW FLA HP KW FLA HP KW Amps Ampacity Size
190 12.0 3.0 2.3 25.0 5.0 3.7 25.0 5.0 3.7 62.0 13.0 9.7 10.5 79 80
500 220 10.4 3.0 2.3 21.0 5.0 3.7 21.0 5.0 3.7 52.4 13.0 9.7 9.1 67 70
380 6.0 3.0 2.3 12.0 5.0 3.7 12.0 5.0 3.7 30.0 13.0 9.7 5.3 38 40
415 5.5 3.0 2.3 11.0 5.0 3.7 11.0 5.0 3.7 27.5 13.0 9.7 4.8 35 35
190 12.0 3.0 2.3 25.0 5.0 3.7 25.0 5.0 3.7 62.0 13.0 9.7 10.5 79 80
600 220 10.4 3.0 2.3 21.0 5.0 3.7 21.0 5.0 3.7 52.4 13.0 9.7 9.1 67 70
380 6.0 3.0 2.3 12.0 5.0 3.7 12.0 5.0 3.7 30.0 13.0 9.7 5.3 38 40
415 5.5 3.0 2.3 11.0 5.0 3.7 11.0 5.0 3.7 27.5 13.0 9.7 4.8 35 35
190 12.0 3.0 2.3 30.0 7.5 5.6 25.0 5.0 3.7 67.0 15.5 11.6 10.5 85 90
700 220 10.4 3.0 2.3 26.0 7.5 5.6 21.0 5.0 3.7 57.4 15.5 11.6 9.1 73 80
380 6.0 3.0 2.3 15.0 7.5 5.6 12.0 5.0 3.7 33.0 15.5 11.6 5.3 42 45
415 5.5 3.0 2.3 14.0 7.5 5.6 11.0 5.0 3.7 30.5 15.5 11.6 4.8 39 40
190 12.0 3.0 2.3 30.0 7.5 5.6 25.0 5.0 3.7 67.0 15.5 11.6 10.5 85 90
800 220 10.4 3.0 2.3 26.0 7.5 5.6 21.0 5.0 3.7 57.4 15.5 11.6 9.1 73 80
380 6.0 3.0 2.3 15.0 7.5 5.6 12.0 5.0 3.7 33.0 15.5 11.6 5.3 42 45
415 5.5 3.0 2.3 14.0 7.5 5.6 11.0 5.0 3.7 30.5 15.5 11.6 4.8 39 40
190 25.0 5.0 3.7 25.0 5.0 3.7 30.0 7.5 5.6 80.0 17.5 13.0 10.5 98 100
975 220 21.0 5.0 3.7 21.0 5.0 3.7 26.0 7.5 5.6 68.0 17.5 13.0 9.1 84 90
380 12.0 5.0 3.7 12.0 5.0 3.7 15.0 7.5 5.6 39.0 17.5 13.0 5.3 48 50
415 11.0 5.0 3.7 11.0 5.0 3.7 14.0 7.5 5.6 36.0 17.5 13.0 4.8 44 45
190 25.0 5.0 3.7 30.0 7.5 5.6 30.0 7.5 5.6 85.0 20.0 14.9 10.5 103 110
1100 220 21.0 5.0 3.7 26.0 7.5 5.6 26.0 7.5 5.6 73.0 20.0 14.9 9.1 89 90
380 12.0 5.0 3.7 15.0 7.5 5.6 15.0 7.5 5.6 42.0 20.0 14.9 5.3 51 60
415 11.0 5.0 3.7 14.0 7.5 5.6 14.0 7.5 5.6 39.0 20.0 14.9 4.8 47 50
190 25.0 5.0 3.7 30.0 7.5 5.6 30.0 7.5 5.6 85.0 20.0 14.9 10.5 103 110
1225 220 21.0 5.0 3.7 26.0 7.5 5.6 26.0 7.5 5.6 73.0 20.0 14.9 9.1 89 90
380 12.0 5.0 3.7 15.0 7.5 5.6 15.0 7.5 5.6 42.0 20.0 14.9 5.3 51 60
415 11.0 5.0 3.7 14.0 7.5 5.6 14.0 7.5 5.6 39.0 20.0 14.9 4.8 47 50
190 25.0 5.0 3.7 30.0 7.5 5.6 30.0 7.5 5.6 85.0 20.0 14.9 10.5 103 110
1350 220 21.0 5.0 3.7 26.0 7.5 5.6 26.0 7.5 5.6 73.0 20.0 14.9 9.1 89 90
380 12.0 5.0 3.7 15.0 7.5 5.6 15.0 7.5 5.6 42.0 20.0 14.9 5.3 51 60
415 11.0 5.0 3.7 14.0 7.5 5.6 14.0 7.5 5.6 39.0 20.0 14.9 4.8 47 50

ABS-M-10A 67
Unit Wiring
Diagrams

Table 13 – ABSD 500-1350 Ton – 60 Hertz Electrical Data


4B1 Refrigerant 4B2 Absorber Spray 4B3 Lt Solution Total Motor Control Minimum Maximum
Unit Pump Motor Pump Motor Pump Motor Rating Circuit Circuit Fuse
Size Voltage FLA HP KW FLA HP KW FLA HP KW FLA HP KW Amps Ampacity Size
200 13.0 3.0 2.3 28.0 5.0 3.7 28.0 5.0 3.7 69.0 13.0 9.7 10.0 86 90
500 230 12.0 3.0 2.3 24.0 5.0 3.7 24.0 5.0 3.7 60.0 13.0 9.7 8.7 75 80
460 6.0 3.0 2.3 12.0 5.0 3.7 12.0 5.0 3.7 30.0 13.0 9.7 4.4 37 40
575 5.0 3.0 2.3 10.0 5.0 3.7 10.0 5.0 3.7 25.0 13.0 9.7 3.5 31 35
200 13.0 3.0 2.3 28.0 5.0 3.7 28.0 5.0 3.7 69.0 13.0 9.7 10.0 86 90
600 230 12.0 3.0 2.3 24.0 5.0 3.7 24.0 5.0 3.7 60.0 13.0 9.7 8.7 75 80
460 6.0 3.0 2.3 12.0 5.0 3.7 12.0 5.0 3.7 30.0 13.0 9.7 4.4 37 40
575 5.0 3.0 2.3 10.0 5.0 3.7 10.0 5.0 3.7 25.0 13.0 9.7 3.5 31 35
200 28.0 5.0 3.7 34.0 7.5 5.6 28.0 5.0 3.7 90.0 17.5 13.0 10.0 109 110
700 230 24.0 5.0 3.7 30.0 7.5 5.6 24.0 5.0 3.7 78.0 17.5 13.0 8.7 94 100
460 12.0 5.0 3.7 15.0 7.5 5.6 12.0 5.0 3.7 39.0 17.5 13.0 4.4 47 50
575 10.0 5.0 3.7 12.0 7.5 5.6 10.0 5.0 3.7 32.0 17.5 13.0 3.5 39 40
200 28.0 5.0 3.7 34.0 7.5 5.6 28.0 5.0 3.7 90.0 17.5 13.0 10.0 109 110
800 230 24.0 5.0 3.7 30.0 7.5 5.6 24.0 5.0 3.7 78.0 17.5 13.0 8.7 94 100
460 12.0 5.0 3.7 15.0 7.5 5.6 12.0 5.0 3.7 39.0 17.5 13.0 4.4 47 50
575 10.0 5.0 3.7 12.0 7.5 5.6 10.0 5.0 3.7 32.0 17.5 13.0 3.5 39 40
200 28.0 5.0 3.7 28.0 5.0 3.7 34.0 7.5 5.6 90.0 17.5 13.0 10.0 109 110
975 230 24.0 5.0 3.7 24.0 5.0 3.7 30.0 7.5 5.6 78.0 17.5 13.0 8.7 94 100
460 12.0 5.0 3.7 12.0 5.0 3.7 15.0 7.5 5.6 39.0 17.5 13.0 4.4 47 50
575 10.0 5.0 3.7 10.0 5.0 3.7 12.0 7.5 5.6 32.0 17.5 13.0 3.5 39 40
200 28.0 5.0 3.7 34.0 7.5 5.6 34.0 7.5 5.6 96.0 20.0 14.9 10.0 115 125
1100 230 24.0 5.0 3.7 30.0 7.5 5.6 30.0 7.5 5.6 84.0 20.0 14.9 8.7 100 110
460 12.0 5.0 3.7 15.0 7.5 5.6 15.0 7.5 5.6 42.0 20.0 14.9 4.4 50 60
575 10.0 5.0 3.7 12.0 7.5 5.6 12.0 7.5 5.6 34.0 20.0 14.9 3.5 41 45
200 28.0 5.0 3.7 34.0 7.5 5.6 34.0 7.5 5.6 96.0 20.0 14.9 10.0 115 125
1225 230 24.0 5.0 3.7 30.0 7.5 5.6 30.0 7.5 5.6 84.0 20.0 14.9 8.7 100 110
460 12.0 5.0 3.7 15.0 7.5 5.6 15.0 7.5 5.6 42.0 20.0 14.9 4.4 50 60
575 10.0 5.0 3.7 12.0 7.5 5.6 12.0 7.5 5.6 34.0 20.0 14.9 3.5 41 45
200 28.0 5.0 3.7 34.0 7.5 5.6 34.0 7.5 5.6 96.0 20.0 14.9 10.0 115 125
1350 230 24.0 5.0 3.7 30.0 7.5 5.6 30.0 7.5 5.6 84.0 20.0 14.9 8.7 100 110
460 12.0 5.0 3.7 15.0 7.5 5.6 15.0 7.5 5.6 42.0 20.0 14.9 4.4 50 60
575 10.0 5.0 3.7 12.0 7.5 5.6 12.0 7.5 5.6 34.0 20.0 14.9 3.5 41 45

68 ABS-M-10A
Unit Wiring
Diagrams

Figure 32 – ABSD Horizon Single-Stage Steam or Hot Water Absorption with Adjustable Frequency Drives
– Main Power Connection, Starter Control Module and Pump Motors
35A LINE VOLTAGE
460V-60HZ CONNECTION SHOWN
1 LINE VOLTAGE REFER TO TABLE "A"
FOR OTHER LINE VOLTAGE
1T4
34A H1 H2 CONNECTIONS
2 L1 L2 L3

1CB2
41A 37A 42A
3
20A X2 X1 GRN
J1 1U1 STARTER CONTROL MODULE
OPTIONAL 198B P1A
4 1U2 J1A-1 1 + 115 VAC
1CB1, 1S1 OR 1TB1
LINE 72 1T5
SEE NOTE 5
199B 1TB3-1 41B 1 2 42B 1TB3-5
5 1S1 1U2 J1A-2 2 -
LINE 73 INTER-PROCESSOR L1 L2
COMMUNICATION 42C
198A P1B 3 4 T1 T2 7 8
6 1U3 J1-3 BOT 3 +
LINE 92 5 6
199A
7 1U3 J1-4 BOT 4 - 24
1A 2A 3A
LINE 93 VAC
1B 2B
120A P1C WIRE 101D WIRE 102D
8 (19) MB 5 1U4 J2-4 1U4 J2-3
ABSORBER SOLUTION PUMP LINE 142 LINE 143
ADJUSTABLE FREQUENCY DRIVE J2
121A DRIVE FAULT P2B 101B
9 RED YEL BLK (20) MC 6 A 4 1U2 J2-4 WIRE 101G WIRE 102G
LINE 72 1U5 J2-4 1U5 J2-3
4U1 102B LINE 170 LINE 171
10 SEE NOTE 6 B 3 1U2 J2-3
LINE 73
1F1 J3 24 VAC
1B 34A ,B,C BLK 34B 1T6 124A P3B P2A 101A
11 3 A 2
OPTIONAL
35B 125A PHASE A-B VOLTS 102A
12 BLK 4 B 1

1F2 1T7 P3C


2B 35A ,B,C BLK 35C 126A
13 5 4U2
OPTIONAL SEE NOTE 6
PHASE B-C VOLTS J6 P6
36A 127A 43A
14 BLK 6 S1 (1)
3
1F3 1T8 P3D LOW TEMPERATURE
3B 36A,B BLK 36B 128A
15 7 SOLUTION PUMP
OPTIONAL START RELAY 2
BLK 34C 129A PHASE C-A VOLTS 44A 44A,B
16 8 SC (11)
1

17

P5A J5 J10 P10 4S3


WHT 130A 41D 44B BLK BLK 45A
18 1 S2 (3)
3 SPLICE SPLICE
1T1 PHASE A CURRENT
BLK 131A REFRIGERANT
19 2
PUMP START RELAY 2
1K1 1K11
WHT 132A P5B 48A 49A 42C
20 3 1K11-32,33,34
1 21 24 A1 A2
1T2 PHASE B CURRENT
BLK 133A
21 4

P5C J12 P12


WHT 134A 50A
22 5 S1 (1)
3
1T3 PHASE C CURRENT
BLK 135A ABSORBER SOLUTION
23 6
PUMP START RELAY 2
51A 51A,B
24 4U2 SC (11)
SEE NOTE 6 1
P7B J7
136A
25 (19) MB 3 LOW TEMPERATURE
SOLUTION PUMP
137A ADJUSTABLE FREQUENCY DRIVE 51B BLK 4S2 BLK 52A
1A 2A 3A
26 (20) MC 4 DRIVER FAULT S2 (3)
SPLICE SPLICE
1TB2 138B 138A,B P7C 4U1
27 L1 L2 L3 (13) FV 5 SEE NOTE 6
SEE NOTE 5 SOLUTION PUMP
ADJUSTABLE FREQUENCY DRIVE
139B 139A,B SPEED SIGNAL
28 (17) FC 6
1C 2C 3C
1D 2D 3D
138A
29 (13) FV WIRE 41D 1TB3-6
LINE 77 LINE 79
139A
30 RED YEL BLK (17) FC

4U1
31 SEE NOTE 6
1K11 1U11
1F4 T1
RED 1C 4A,B RED 4B RED 7A
32
L1 2
1F5 T2
YEL 2C 5A,B YEL 5B YEL 8A
33 4B1 1U11-81
L2 4
1F6 T3 TABLE "A"
BLK 3C 6A,B BLK 6B BLK 9A
34
L3 6
LINE VOLTAGE CONNECTIONS
35
4U1
190V H1 AND H2
RED 4A RED 10A T1
36 L1 T1
200V H1 AND H3
YEL 5A YEL 11A T2
37 L2 T2 4B2
220V H1 AND H4
BLK 6A BLK 12A T3
38 L3 T3
230V H1 AND H5
39
4U2
1F7 380V H1 AND H2
RED 1D RED 13A RED 16A T1
40 L1 T1

1F8 415V H1 AND H3


YEL 2D YEL 14A YEL 17A T2
41 L2 T2 4B3

1F9 460V H1 AND H2


BLK 3D BLK 15A BLK 18A T3
42 L3 T3
575V H1 AND H3

ABS-M-10A 69
Unit Wiring
Diagrams

Table 14

70 ABS-M-10A
Unit Wiring
Diagrams

Figure 33 – ABSD Horizon Single-Stage Steam or Hot Water Absorption with Adjustable Frequency Drives – Circuit and Chiller Control
(See Notes Page 70)
71
J1A
1U2 CIRCUIT CONTROL MODULE J2
1U1 J1-1 198B P1A P2B 101B
72 1 A 4 1U1 J2-4
LINE 6
INTER-PROCESSOR LINE 9
199B COMMUNICATION 102B
1U1 J1-2
73 2 B 3 1U1 J2-3
LINE 7
LINE 10
1K1 24 VAC
143A P1C
74 5 A 2
11 14 REFRIGERANT
144A PUMP ABNORMAL WIRE 41D 1TB3-5
75 6 B 1 LINE 18 LINE 5

76 41D

J18 P18 1TB3-2


41E
77
3
41F
REFRIGERANT DUMP
78
VALVE RELAY 2
4RT1 J3 4B6
WHT P3A 65A 42E 1TB3-6
79 1
SENSING DETECTION 1 L1 L2
AND RECOVERY 42F
BLK TEMPERATURE
80 2
4RT23 1U11 1K1
WHT P3D 41F BLK 4S1 BLK 66A 67A 42F
STEAM CONDENSATE
81 7 HOT WATER TEMPERATURE 1K1-20,74
TEMPERATURE LEAVING 95 96 A1 A2
LEAVING LOW SPLICE SPLICE
LOW TEMPERATURE
BLK TEMPERATURE GENERATOR
GENERATOR
82 8 (HOT WATER UNITS)
(STEAM UNITS)

83
4RT22 J5
WHT P5C
84 5 HOT WATER TEMPERATURE
ENTERING LOW
BLK TEMPERATURE GENERATOR
85 6 (HOT WATER UNITS ONLY)

86 1TB3-3 1TB3-7
LINE 117 LINE 120

87
P1C
J1 TOP 1U3 CHILLER CONTROL MODULE J2
198G OR 198 P2B 101F OR 101
88 1 + A 4
SEE NOTE 5 SEE NOTE 5
199G OR 199 102F OR 102
89 2 - B 3
24 VAC
198D P1A P2A 101E
90 1U4 J1-1 1 + 3 + A 2 1U4 J2-2 115 VAC 15A
LINE 142 INTER-PROCESSOR LINE 144 CUSTOMER PROVIDED DEVICES AND WIRING
199D COMMUNICATION 102E MAXIMUM MODULE CONTACT RATINGS:
91 1U4 J1-2 2 - 4 - B 1 1U4 J2-1 2.88A INDUCTIVE, 1/3 HP
LINE 143 LINE 145
198A P1B
92 1U1 J1-3 3 +
LINE 6
J10 P10
199A
93 1U1 J1-4 4 -
LINE 7 HOT WATER PUMP 2
J1 BOTTOM RELAY 6K1
(HOT WATER UNITS ONLY)
94
1
4RT6 J3
WHT P3A
95 1
EVAPORATOR ENTERING
WATER TEMPERATURE J12 P12
BLK
96 2
CHILLED WATER 2
4RT7 6K2
WHT P3B PUMP RELAY
97 3 6K2-100,119
EVAPORATOR LEAVING 1
BLK WATER TEMPERATURE
98 4
4RT8 J14
WHT P3C P14
99 5
ABSORBER LEAVING CONDENSER-ABSORBER 2
6K2 6K3
BLK WATER TEMPERATURE WATER PUMP RELAY
100 6 6K3-123
1
4RT9
WHT P3D
101 7
CONDENSER LEAVING
WATER TEMPERATURE J16 P16
BLK
102 8
3
SOLUTION PUMP
103 RUNNING
STATUS RELAY 2
6K4
6S1 P5A J5
104 1
UNIT EXTERNAL AUTO STOP 1
W1 MUST BE JUMPERED
IF NOT USED
105 2

6S2 P5B J18 P18


106 3
UNIT EMERGENCY STOP 3
W2 MUST BE JUMPERED
MACHINE MANUAL
IF NOT USED
107 4 RESET ALARM
STATUS RELAY 2
5RT1 6K5
P5C
108 5 OUTDOOR AIR
TEMPERATURE SENSOR 1
PROVIDED BY TRANE
109 6 FIELD INSTALLED

J20 P20
110
LIMIT WARNING 2
4RT10 6K6
P7D J7 STATUS RELAY
WHT
111 7
ABSORBER ENTERING 1
BLK WATER TEMPERATURE
112 8

J22 P22
113
MACHINE AUTOMATIC 2
RESET ALARM 6K7
P9A J9
RED STATUS RELAY
114 1
1
BLK
115 2 1TB3-2 1TB3-6
LINE 77 LINE 79
+5 VDC SUPPLY STEAM
SHIELD PRESSURE TRANSDUCER
116 +DIF -DIF 3
(STEAM UNITS ONLY)
SEE NOTE 6
WHT 1TB3-3 41K
117 4R2 4

GRN
118 5
GND
J26 1TB3-9 6S5 6K2
RED P9B P26 86A 1TB3-10
119 6
CHILLED WATER 2
OPTO INPUT
BLK FLOW SWITCH 42L 1TB3-7
120 7
LOW TEMPERATURE 1
+5 VDC 42M
SHIELD GENERATOR STEAM
121 +DIF -DIF 8 PRESSURE TRANSDUCER
(STEAM UNITS ONLY)
WHT SEE NOTE 6
122 4R3 9

J28 1TB3-12 6S6 6K3


GRN P28 87A 1TB3-11
123 10
GND CONDENSER-ABSORBER 2
OPTO INPUT
WATER FLOW SWITCH 42M
124
1

125

126 1TB3-4 1TB3-8


LINE 148 LINE 149

ABS-M-10A 71
Unit Wiring
Diagrams

Figure 34 - ABSD Horizon Single-Stage Steam or Hot Water Absorption – Purge and Stepper Control Modules and Local Clear Language Display Panel
141
1U4 PURGE CONTROL MODULE
(See Notes Page 70)
P1A J1 J2 P2B
198D 101D
142 1U3 J1-1 BOT 1 + SEE NOTE 6 A 4 1T5-3
LINE 90 LINE 6
199D 102D
143 1U3 J1-2 BOT 2 - B 3 1T5-8
LINE 91 INTER-PROCESSOR LINE 6
24 VAC
198E P1B COMMUNICATION P2A 101E
144 3 + A 2 1U3 J2-2
LINE 90
199E 102E
145 4 - B 1 1U3 J2-1
LINE 91

146 1TB3-3 1TB3-7


LINE 117 LINE 120

147
J6
P6 41T 1TB3-4
148
PURGE PUMPOUT 2 41L,M,N,U,V
RELAY 4L19 1TB3-8
95A BLK BLK 42R
149
1
42N,T,AM,AN
150 4JB3
4RT11 J3 J8
RED RED P3B P8 41L
151 3
PURGE REFRIGERANT 2
COMPRESSOR SUCTION TANK VALVE RELAY 4L18 4TB4-3
BLK BLK TEMPERATURE 94A 94B BLK YEL 42P 42N
152 4
1 SPLICE SPLICE
4TB4-1
4S16 RED RED P3C
153 5
LIQUID LEVEL SENSOR J10
BLK BLK P10 41M
154 6
PURGE REFRIGERANT 2
4B9
COMPRESSOR RELAY 96A 96B BLK WHT 42S
155
1 SPLICE SPLICE
4TB4-2

156
1K6 4B10
41U 98A 42T
157
11 14 1 2
J12 P12 41N
158
2
PURGE VACUUM 1K6
PUMP RELAY 97A 42AM
159
1 A1 A2

160

J14 P14 41V


161
2
ABSORBER 4L20
VALVE RELAY 99A BLK YEL 42AN
162
1 SPLICE SPLICE

163

164 115 VAC 15A


CUSTOMER PROVIDED DEVICES AND WIRING
J16 P16 MAXIMUM MODULE CONTACT RATINGS:
165 2.88A INDUCTIVE, 1/3 HP
3

166 ALARM RELAY


2 6DS1

167
1
PURGE ALARM
168

169

J1 1U5 STEPPER CONTROL MODULE J2


198E P1A P2B 101G
170 1 + A 4 1T5-4
LINE 6
199E 102G
171 2 - B 3 1T5-7
INTER-PROCESSOR LINE 6
24 VAC
198F P1B COMMUNICATION P2A 101H
172 3 + A 2

199F 102H
173 4 - B 1

174
4RT12 J5
WHT P5A
175 1
SATURATED EVAPORATOR
BLK REFRIGERANT TEMPERATURE
176 2
4RT13
WHT P5B
177 3
ABSORBER
BLK SPRAY TEMPERATURE
178 4
4RT14
WHT P5C
179 5
SOLUTION TEMPERATURE
BLK LEAVING ABSORBER
180 6
4RT15 4B11
WHT P5D
181 7
SOLUTION TEMPERATURE
ENTERING ABSORBER J8 3
BLK P8 113A RED
182 8 4

5
115A WHT
183 STEAM OR HOT WATER 3
ENERGY VALVE
4RT16 J7 1
WHT P7B STEPPER 111A BLK
184 5 SEE NOTE 5 2
SOLUTION TEMPERATURE
ENTERING LOW 4
BLK TEMPERATURE GENERATOR 114A YEL
185 6 1

186

187

188
4RT18 J9
WHT P9B
189 3
SOLUTION TEMPERATURE
LEAVING LOW
BLK TEMPERATURE GENERATOR
190 4

191

192

193

4RT19 J11
WHT P11B
194 3
SATURATED CONDENSER
BLK REFRIGERANT TEMPERATURE
195 4

196

197

J1 1U6 LOCAL CLEAR LANGUAGE DISPLAY PANEL J2


198F P1 P2 101H
198 1 + A 2
INTER-PROCESSOR
24 VAC
199F COMMUNICATION 102H
199 2 - CHASSIS GROUND B 1

200
GRN
201

72 ABS-M-10A
Unit Wiring
Diagrams

Figure 35 – ABSD Horizon Single-Stage Steam or Hot Water Absorption – Options Control Module and/or Communication Control Modules
(See Notes Page 70)

ABS-M-10A 73
Unit Wiring
Diagrams

Figure 36 – Connections: Main Unit Control Panel (Left Side)

74 ABS-M-10A
Unit Wiring
Diagrams

Figure 37 – Connections: Unit Control Panel (Right Side)

ABS-M-10A 75
Unit Wiring
Diagrams

Figure 38 – Connections: Unit Control Panel

76 ABS-M-10A
Unit Wiring
Diagrams

Figure 39 – Connection Diagram – Unit Mounted Controls

ABS-M-10A 77
Unit Wiring
Diagrams

Figure 40 – Connection Diagram – Unit Mounted Controls

78 ABS-M-10A
Unit Wiring
Diagrams

Sensors
The table below Indicates unit sensors, primary function control or monitor,
connection points, and the normal operation temperature range.
Control sensor abnormal will cause a diagnostic shutdown. Monitor sensor abnormal
will generate an informational warning message only, allowing chiller operation to
continue.

Table 15
Sensor Application Sensor Primary Function Module
1 Evap. Entering Water Temp LCWT Control Chiller
2 Evap. Leaving Water Temp LCWT Control Chiller
3 Absorber Ent. Water Temp ELWT-Fdfwd & Low Tower Limit Chiller
4 Absorber Leaving Water Temp Monitor Chiller
5 Cond Leaving Water Temp Monitor Chiller
6 Solution Temp Leaving LTG Concentration Calc (LTG) Stepper
7 Saturated Evap. Rfgt Temp Evap Limit Stepper
8 Saturated Cond. Rfgt Temp Concentration Calc (LTG) Stepper
9 Diff Evap Wtr Pressure (Optional) Monitor TBD
10 Diff Tower Wtr Pressure (Optional) Monitor TBD
11
12
13
14
15 Solution Temp Entering Absorber Control T-Margin Stepper
16 Solution Temp Leaving Absorber Monitor Stepper
17 Solution Temp entering LTG Monitor Stepper
18 Absorber Spray Temp Monitor Stepper
19
20 SDR Temperature SDR Logic Circuit
21* Supply Steam Pressure (4R2) Control Chiller
22* High Temperature Steam Pressure (4R3) Control Chiller
23 Entering Steam Temperature or Hot Water Entering Monitor Circuit
24 Steam Condensate Leaving CHX Or Hot Water Leaving Monitor Circuit

ABS-M-10A 79
Literature Order Number ABS-M-10A
File Number SV-RF-ABS-ABSD-M-10A-0401
Supersedes Supersedes ABS-M-10-0500
The Trane Company
An American Standard Company Stocking Location La Crosse
www.trane.com
For more information contact Since The Trane Company has a policy of continuous product and product data improvement, it reserves the
your local district office or right to change design and specifications without notice. The installation and servicing of the equipment
e-mail us at comfort@trane.com referred to in this booklet should be done by qualified, experienced technicians.

You might also like