Mech 6181 Project Report
Mech 6181 Project Report
Project Report
Cooling load calculations of an office building
Submitted to:
Submitted by:
1
DESIGN CONSIDERATIONS ......................................................................................................................................4
PROBLEM STATEMENT ............................................................................................................................................5
FLOOR PLAN................................................................................................................................................................5
COOLING LOAD CALCULATIONS ..........................................................................................................................6
I. Station Incharge Room (SIC) .............................................................................................................................6
a) From roof: .......................................................................................................................................................6
b) From wall: ......................................................................................................................................................6
c) Window at east wall: ......................................................................................................................................7
d) Window at south wall: ....................................................................................................................................8
e) From lights: ....................................................................................................................................................8
f) From people:...................................................................................................................................................9
g) From appliances: ............................................................................................................................................9
h) Total Cooling Load for SIC Room ...............................................................................................................10
II. Total Cooling Load for CABIN – 1 Room .......................................................................................................12
III. Total Cooling Load for CABIN – 2 Room ...................................................................................................13
IV. Total Cooling Load for CABIN – 3 Room ...................................................................................................14
V. Total Cooling Load for CABIN – 4 Room .......................................................................................................15
VI. Total Cooling Load for Work Area – 1 Room .............................................................................................16
VII. Total Cooling Load for Work Area – 2 Room .............................................................................................17
VIII. Total Cooling Load for Dining and Recreation Room .................................................................................18
IX. Total Cooling Load for Conference Room ...................................................................................................19
X. Total Cooling Load for Record Room ..............................................................................................................20
XI. Total Cooling Load for Lounge ....................................................................................................................21
AREA OF DUCT CALCULATIONS ..........................................................................................................................22
COOLING MACHINE CAPACITY CALCULATIONS ............................................................................................23
FINAL DUCT DESIGN & AMOUNT OF AIR REQUIRED IN EACH ROOM .......................................................24
References ....................................................................................................................................................................25
2
Nomenclature
U – Overall heat transfer coefficient (W/ m2 o C)
TR – Required Temperature (o C)
To – Outside Temperature (o C)
SHGF – Sensible heat gain factor
CLF – Cooling load factor
SC – Solar attenuation Coefficients
Q – Heat transfer (W)
SHG – Sensible heat gain (W)
LHG – Latent heat gain (W)
SHF – Sensible heat Factor
– Mass flow rate (kg/s)
– Volume flow rate (m3/s)
ρ – Density (kg/m3)
h – enthalpy (Kj/kgda)
A – Area ( m2)
DBT – Dry Bulb temperature
Subscripts
o – Outside state
r – Room conditions
1 – State 1in Psychometric chart (i.e. State of fluid before entering room)
2 – State 2 in Psychometric chart ((i.e. State of mixed air before entering cooling machine)
W – Wall
Wi – Window
L – Lights
P – People
App – Appliances
stotal – sensible total
ltotal – latent total
3
DESIGN CONSIDERATIONS
Country India
City Vijayawada
Latitude 16.5
Longitude 80.5
Elevation 36 ft
Timelines 12:00PM,02:00 PM, 04:00 PM
Month May
Outside Temperature & Relative humidity 45o C DBT and 45%
Desired Temperature & Relative humidity 24o C DBT and 50%
Height of the building (in meters) 3.5
Number of hours in which each room is
12
occupied
Activity Level Seated, very light works
Roof Heavy weight roof
Type of the walls Light weight 8 in concrete block + air space
+ finish
Size of the window ( in meters) W1 = 3.6 x 1.5
and door W2 = 2.0 x 1.2
GD1 = 1.0 x 2.1
GD2 = 2.0 x 2.1(has no drapes)
Type of the Glass of the windows and doors Double Glazing 12.7 mm air space
Type of the frame of the windows Aluminum without thermal break
Shading / Curtain Yes
Type of Shading / Material of the Semiopen Weave - Medium Color
Curtain
Air Change per Hour 1
Velocity of air in the duct 7 m/s
Temperature of air supplied to cooling space 13o C DBT
4
PROBLEM STATEMENT
Compute the cooling load and cooling capacity in tons of an office building consisting
of only ground floor as shown in the architectural plan below. The location of the house
is 16° North Latitude.
The external walls are constructed of 8inch light weight aerated concrete blocks.
There is 0.75 inch of gypsum plaster on the inside. All external and internal walls are
Group D walls and they are dark colored.
The roof is made up of 152.4 mm Heavy weight concrete with 25.4 mm insulation with
suspended ceiling, dark colored and no attics are ducts space.
All windows are double glazed with 12.7 mm air gap and Aluminum without thermal
break. It has a reflective coating and the shading is medium colored and semi open weave
interior.
Type of work is seated, light work doing from 9 A.M to 9 P.M. Lights (30 W/m2 of
floor area), operating from 9 A.M. to 9 P.M. The space air is changing 1 times per hour.
The Outdoor Design Conditions are 45° C DBT and 45% humidity. Inside Design
Conditions are 24° C DBT and 50% humidity.
The calculations are based on 12 P.M., 2 P.M. and 4 P.M. in the month of May.
FLOOR PLAN
5
COOLING LOAD CALCULATIONS
a) From roof:
12 PM 2 PM 4 PM
CLTD 13 15 17
CLTDcorrected 30.1 32.1 34.1
Qroof (W) 1059.227 1140.272 1211.317
b) From wall:
16° N Latitude & May month; LM = -1 for East (∵ From Table 3.12)
K = 1 for dark color (∵ From Table 3.10)
6
12 PM 2 PM 4 PM
CLTD/1.8 15 17.77 18.33
CLTDcorrected 31.1 33.87 34.43
QEW (W) 429.449 467.698 475.431
16° N Latitude & May month; LM = -7 for South (∵ From Table 3.12)
K = 1 for dark color (∵ From Table 3.10)
12 PM 2 PM 4 PM
CLTD/1.8 5 8.89 13.33
CLTDcorrected 15.1 18.99 23.43
QSW (W) 239.58 301.229 371.745
i. Through conduction –
7
SHGF = 215 × 3.147 = 676.605 W/m2 (∵ From Table 3.25)
SC = 0.85 (∵ From Table 22)
12 PM 2 PM 4 PM
CLF 0.27 0.22 0.17
QEWi (W) 372.674 303.66 234.646
i. Through conduction –
Qs = A × SC × SHGF × CLF
SHGF = 41 × 3.147 = 129.027 W/m2 (∵ From Table 3.25)
SC = 0.85 (∵ From Table 22)
12 PM 2 PM 4 PM
CLF 0.83 0.68 0.35
QSWi (W) 491.554 402.719 207.281
e) From lights:
8
= 30 × 32.5 × 5
= 4875
Type “a” classification – ordinary furniture, no carpet and medium to high ventilation
rate So, a = 0.55 and Type “b” classification – 8 inch concrete floor with medium
ventilation rate So, b = Type D
12 PM 2 PM 4 PM
CLF 0.74 0.76 0.77
QL (W) 3607.5 3705 3753.75
f) From people:
Number of people = 5
moderately active office work
First entry starts at 9:00 AM
Sensible heat gain (SHG) = 73 W and Latent Heat Gain (LHG) = 59 W (∵ From Table
8.2)
g) From appliances:
9
Equipment Quantity Recommended Heat gain QSENSIBLE
Computers 3 65 195
Medium Monitor 3 70 210
Laser printer (small office) 2 320 640
QSTotal 1045
Time
12:00 PM 2:00 PM 4:00 PM
CLF = 0.73 CLF = 0.81 CLF = 0.5
QAppT = CLF × QSTotal QAppT = CLF × QSTotal QAppT = CLF × QSTotal
QSENSIBLE(W) QLATENT(W)
Roof 1059.227 -
Wall -1 (East Facing) 429.449 -
Wall -2 (South Facing) 239.58 -
Window -1(Conduction) 232.848 -
Window -1(Radiation) 372.674 -
Window -2(Conduction) 523.908 -
Window -2(Radiation) 491.554 -
Lights 3607.5 -
People 251.85 295
Appliances 762.85 0
Total 7971.44 295
QTOTAL = QSENSIBLE + QLATENT = 7971.44 + 295 = 8266.44W
10
ii. Time of the day – 02:00 PM
QSENSIBLE(W) QLATENT(W)
Roof 1140.272 -
Wall -1 (East Facing) 467.698 -
Wall -2 (South Facing) 301.299 -
Window -1(Conduction) 232.848 -
Window -1(Radiation) 303.66 -
Window -2(Conduction) 523.908 -
Window -2(Radiation) 402.719 -
Lights 3705 -
People 281.05 295
Appliances 846.45 0
Total 8204.904 295
QTOTAL = QSENSIBLE + QLATENT = 8204.904 + 295 = 8499.904 W
QSENSIBLE(W) QLATENT(W)
Roof 1211.317 -
Wall -1 (East Facing) 475.431 -
Wall -2 (South Facing) 371.745 -
Window -1(Conduction) 232.848 -
Window -1(Radiation) 234.646 -
Window -2(Conduction) 523.908 -
Window -2(Radiation) 207.281 -
Lights 3753.75 -
People 302.95 295
Appliances 888.25 0
Total 8202.126 295
QTOTAL = QSENSIBLE + QLATENT = 8202.126 + 295 = 8497.126W
11
II. Total Cooling Load for CABIN – 1 Room
QSENSIBLE(W) QLATENT(W)
Roof 613.992 -
Wall -1 (East Facing) 542.1596 -
Wall -2 (South Facing) 212.721 -
Lights 1197 -
People 173.01 177
Appliances 373.1 0
Total 3111.983 177
QTOTAL = QSENSIBLE + QLATENT = 3111.983+ 177 = 3288.983 W
QSENSIBLE(W) QLATENT(W)
Roof 652.247 -
Wall -1 (East Facing) 551.055 -
Wall -2 (South Facing) 262.51 -
Lights 1212.75 -
People 183.96 177
Appliances 391.3 0
Total 3253.817 177
QTOTAL = QSENSIBLE + QLATENT = 3253.817+ 177 = 3430.817 W
12
III. Total Cooling Load for CABIN – 2 Room
QSENSIBLE(W) QLATENT(W)
Roof 575.737 -
Wall -2 (South Facing) 169.155 -
Lights 1165.5 -
People 153.3 177
Appliances 341.25 0
Total 2404.944 177
QTOTAL = QSENSIBLE + QLATENT = 2404.944 + 177 = 2581.944W
QSENSIBLE(W) QLATENT(W)
Roof 613.992 -
Wall -2 (South Facing) 212.721 -
Lights 1197 -
People 173.01 177
Appliances 373.1 0
Total 2569.823 177
QTOTAL = QSENSIBLE + QLATENT = 2569.823+ 177 = 2746.823 W
QSENSIBLE(W) QLATENT(W)
Roof 652.247 -
Wall -2 (South Facing) 262.51 -
Lights 1212.75 -
People 183.96 177
Appliances 391.3 0
Total 2702.767 177
QTOTAL = QSENSIBLE + QLATENT = 2702.767 + 177 = 2879.767 W
13
IV. Total Cooling Load for CABIN – 3 Room
QSENSIBLE(W) QLATENT(W)
Roof 287.868 -
Wall -1 (West Facing) 168.835 -
Partition Wall (Between 274.618 -
room and kitchen)
Lights 388.5 -
People 153.3 177
Appliances 341.25 0
Total 1614.373 177
QTOTAL = QSENSIBLE + QLATENT = 1614.373 + 177 = 1791.373W
QSENSIBLE(W) QLATENT(W)
Roof 306.996 -
Wall -1 (West Facing) 177.726 -
Partition Wall (Between 274.618 -
room and kitchen)
Lights 399 -
People 173.01 177
Appliances 373.1 0
Total 1704.451 177
QTOTAL = QSENSIBLE + QLATENT = 1704.451+ 177 = 1881.451 W
QSENSIBLE(W) QLATENT(W)
Roof 326.124 -
Wall -1 (West Facing) 208.844 -
Partition Wall (Between 274.618 -
room and kitchen)
Lights 404.25 -
People 183.96 177
Appliances 391.3 0
Total 1789.097 177
QTOTAL = QSENSIBLE + QLATENT = 1789.097 + 177 = 1966.097 W
14
V. Total Cooling Load for CABIN – 4 Room
QSENSIBLE(W) QLATENT(W)
Roof 287.868 -
Wall -1 (West Facing) 168.835 -
Wall -2 (South Facing) 169.156 -
Lights 388.5 -
People 153.3 177
Appliances 341.25 0
Total 1508.911 177
QTOTAL = QSENSIBLE + QLATENT = 1508.911+ 177 = 1685.911W
QSENSIBLE(W) QLATENT(W)
Roof 306.996 -
Wall -1 (West Facing) 177.726 -
Wall -2 (South Facing) 212.7207 -
Lights 399 -
People 173.01 177
Appliances 373.1 0
Total 1642.554 177
QTOTAL = QSENSIBLE + QLATENT = 1642.554 + 177 = 1819.554 W
QSENSIBLE(W) QLATENT(W)
Roof 326.124 -
Wall -1 (West Facing) 208.844 -
Wall -2 (South Facing) 262.51 -
Lights 404.25 -
People 183.96 177
Appliances 391.3 0
Total 1776.987 177
QTOTAL = QSENSIBLE + QLATENT = 1776.987 + 177 = 1953.987 W
15
VI. Total Cooling Load for Work Area – 1 Room
QSENSIBLE(W) QLATENT(W)
Roof 1069.227 -
Wall -1 (South Facing) 239.58 -
Windows(South) 1015.462 -
Lights 2886 -
People 306.6 354
Appliances 1338.75 0
Total 6855.619 354
QTOTAL = QSENSIBLE + QLATENT = 6855.619 + 354 = 7209.619 W
QSENSIBLE(W) QLATENT(W)
Roof 1140.272 -
Wall -1 (South Facing) 301.282 -
Windows(South) 926.627 -
Lights 2964 -
People 346.2 354
Appliances 1463.7 0
Total 7141.901 354
QTOTAL = QSENSIBLE + QLATENT = 7141.901 + 354 = 7495.901W
QSENSIBLE(W) QLATENT(W)
Roof 1211.317 -
Wall -1 (South Facing) 371.798 -
Windows(South) 731.19 -
Lights 3003 -
People 367.92 354
Appliances 1535.1 0
Total 7220.326 354
QTOTAL = QSENSIBLE + QLATENT = 7220.326 + 354 = 7574.326 W
16
VII. Total Cooling Load for Work Area – 2 Room
QSENSIBLE(W) QLATENT(W)
Roof 1315.972 -
Wall -1 (North Facing) 516.451 -
Windows(North) 1192.41 -
Lights 3552 -
People 306.6 354
Appliances 1338.75 0
Total 8222.184 354
QTOTAL = QSENSIBLE + QLATENT = 8222.184 + 354 = 8576.184 W
QSENSIBLE(W) QLATENT(W)
Roof 1403.412 -
Wall -1 (North Facing) 550.897 -
Windows(North) 1169.876 -
Lights 3648 -
People 346.2 354
Appliances 1463.7 0
Total 8581.905 354
QTOTAL = QSENSIBLE + QLATENT = 8581.905 + 354 = 8935.905 W
QSENSIBLE(W) QLATENT(W)
Roof 1490.852 -
Wall -1 (North Facing) 585.342 -
Windows(North) 1087.252 -
Lights 3696 -
People 367.92 354
Appliances 1535.1 0
Total 8762.467 354
QTOTAL = QSENSIBLE + QLATENT = 8762.467 + 354 = 9116.467 W
17
VIII. Total Cooling Load for Dining and Recreation Room
QSENSIBLE(W) QLATENT(W)
Roof 1398.2203 -
Wall -1 (North Facing) 556.442 -
Windows(North) 1192.41 -
Partition Wall (kitchen) + door 618.4098 -
Lights 7548 -
People 511 590
Appliances 840 0
Total 12664.482 590
QTOTAL = QSENSIBLE + QLATENT = 12664.482+ 590 = 13254.482W
ii. Time of the day – 02 :00 PM
QSENSIBLE(W) QLATENT(W)
Roof 1491.125 -
Wall -1 (North Facing) 593.555 -
Windows(North) 1169.876 -
Partition Wall (kitchen)+ door 618.4098 -
Lights 7752 -
People 576.7 590
Appliances 918.4 0
Total 13120.066 590
QTOTAL = QSENSIBLE + QLATENT = 13120.066+ 590 = 13710.066 W
QSENSIBLE(W) QLATENT(W)
Roof 1584.03 -
Wall -1 (North Facing) 630.6676 -
Windows(North) 1087.252 -
Partition Wall (kitchen)+ door 618.4098 -
Lights 7854 -
People 613.2 590
Appliances 963.2 0
Total 13350.76 590
QTOTAL = QSENSIBLE + QLATENT = 13350.76+ 590 = 13940.76W
18
IX. Total Cooling Load for Conference Room
QSENSIBLE(W) QLATENT(W)
Roof 1644.965 -
Wall -1 (North Facing) 553.014 -
Wall -2 (East Facing) 344.128 -
Windows(North-2,East-1) 3747.2448 -
Lights 11100 -
People 1226.4 1416
Appliances 472.5 0
Total 19088.252 1416
QTOTAL = QSENSIBLE + QLATENT = 19088.252+ 590 = 20504.252W
QSENSIBLE(W) QLATENT(W)
Roof 1754.265 -
Wall -1 (North Facing) 589.8985 -
Wall -2 (East Facing) 374.8647
Windows(North-2,East-1) 3546.896 -
Lights 11400 -
People 1384.08 1416
Appliances 516.6 0
Total 19566.605 1416
QTOTAL = QSENSIBLE + QLATENT = 19566.605+ 1416 = 20982.605 W
QSENSIBLE(W) QLATENT(W)
Roof 1863.565 -
Wall -1 (North Facing) 626.782 -
Wall -2 (East Facing) 381.012
Windows(North-2,East-1) 3226.367 -
Lights 11550 -
People 1471.68 1416
Appliances 541.8 0
Total 19661.207 1416
QTOTAL = QSENSIBLE + QLATENT = 19661.207+ 1416 = 21077.207 W
19
X. Total Cooling Load for Record Room
QSENSIBLE(W) QLATENT(W)
Roof 575.737 -
Wall -1 (West Facing) 233.45 -
Wall -2 (South Facing) 169.14 -
Window -1 1051.863 -
Lights 1165.5 -
People 153.3 177
Total 3349.032 177
QTOTAL = QSENSIBLE + QLATENT = 3349.032 + 177 = 3526.032W
QSENSIBLE(W) QLATENT(W)
Roof 613.992 -
Wall -1 (West Facing) 245.62 -
Wall -2 (South Facing) 212.60 -
Window -1 2169.884 -
Lights 1197 -
People 173.01 177
Total 4612.379 177
QTOTAL = QSENSIBLE + QLATENT =4612.379 + 177 = 4789.379 W
QSENSIBLE(W) QLATENT(W)
Roof 652.247 -
Wall -1 (West Facing) 288.77 -
Wall -2 (South Facing) 262.44 -
Window -1 3070.513 -
Lights 1212.75 -
People 183.96 177
Total 5670.783 177
QTOTAL = QSENSIBLE + QLATENT = 5670.783+ 177 =5847.783W
20
XI. Total Cooling Load for Lounge
QSENSIBLE(W) QLATENT(W)
Roof 2187.803 -
Wall -1 (East Facing) 77.328 -
1
Through Glass door(GD-2) 564.909 -
Lights 8857.8 -
People 511 590
Total 12198.842 590
QTOTAL = QSENSIBLE + QLATENT = 12198.842+ 590 = 12788.842W
QSENSIBLE(W) QLATENT(W)
Roof 2333.172 -
Wall -1 (East Facing) 97.243 -
Through Glass door(GD-2) 536.459 -
Lights 9097.2 -
People 576.7 590
Total 12640.776 590
QTOTAL = QSENSIBLE + QLATENT = 12640.776+ 590 = 13230.776 W
QSENSIBLE(W) QLATENT(W)
Roof 2478.541 -
Wall -1 (East Facing) 120.004 -
Through Glass door(GD-2) 473.868 -
Lights 9216.9 -
People 613.2 590
Total 12902.514 590
QTOTAL = QSENSIBLE + QLATENT = 12902.514+ 590 = 13492.514 W
1
The main glass door has no drapes so value of SC for radiation calculation is taken as 0.35 from table 22
21
AREA OF DUCT CALCULATIONS
22
COOLING MACHINE CAPACITY CALCULATIONS
The total air quantity required for entire building is by energy balance
equation of space:
= Qtotal / (hr h1) (kg/s)
Amount of fresh air required from outside is calculated by assuming
Ventilation and infiltration by ACH method. So, ACH for the entire building is
taken as 1 change per hour.
Infiltration rate of fresh air is calculated by following formula:
= (Volume of total building x ACH) / 3600 (m3/s)
Mass of fresh air required = x ρo (kg/s)
Amount of recirculated air will be =
State 2 (properties of mixed air) is determined by doing mass balance of the
mixed sections (i.e. recirculated air from space and fresh air from outside) gives
following
Above table shows cooling load calculations of entire building at 04:00 PM.
23
FINAL DUCT DESIGN & AMOUNT OF AIR
REQUIRED IN EACH ROOM
Below image shows the floor plan along with duct dimensions and amount of air required
for each room.
24
References
1. McQuiston, F. C., Parker, J. D., & Spitler, J. D. (2019). Heating, Ventilating, and Air