Design Class Detail Overpressure Protection Project Date: Eccn Ear 99

You might also like

Download as docx, pdf, or txt
Download as docx, pdf, or txt
You are on page 1of 1

ECCN EAR 99

Design Class Detail


Overpressure Protection PROJECT Date

Capacity
Design Design Class
Item
Class 1 Class 2 Class 3
PRV Sizing Sizing of pressure relief valves (PRVs) shall be based on Sizing of PRVs shall be
unit nameplate capacity. Note: Operating units more than based on 110% of unit
10% above nameplate requires validation of relief system nameplate capacity.
capacity.
TIC is .05% greater than
Class 1 or 2. After
construction TIC is 0.25% to
0.30% greater than Class 1 or
2.
Specifying Design When designing equipment for containment (vs. relief), design pressures shall be based on
Pressure the installed impeller. For preliminary estimates, the pump deadhead pressure will be
expected pump suction pressure plus a specified multiplier of the rated total differential head
(TDH). The specified multiplier is intended to estimate the pump deadhead, provide limited
turndown capability, and cover pump manufacturing tolerances. In the event, the actual
deadhead of the pump exceeds the estimate, Shell will accept up to 16% overpressure.
Pump Deadhead 1.1 1.2 1.3
Multiplier TIC is 0.5% greater than TIC is 1% greater than
Class 1. Class 1.
Operability and Maintainability
Design Design Class
Item
Class 1 Class 2 Class 3
PRV Outlet Block No PRV outlet block PRV outlet block valves: and PRV bypass valves shall
Valves/PRV Bypass valves or PRV bypass conform to DEP 80.45.10.11-Gen.
Valves valves shall be provided. TIC is 0.1% greater than Class 1.
Option requires equipment shutdown and flare system entries.

DEP 00.00.07.84-Gen. September 2011 Page 1 of 1