Caterpillar DCU Controller Page 1 of 10

Configuration Printout

http://192.168.0.101/File?selection=view 4/5/2018
Caterpillar DCU Controller Page 2 of 10

DCU
Firmware Version 2.11 P12
System Unit Metric
Selected Language French
Connected Hardware SDU 410

Main
Name Engine C9 AUX
Engine Manufacturer Caterpillar
Engine Hours J1939
Configuration Name CA900114_Gen1_YN555403_Final_config_Cat.ucfg (User Uploaded)
Operation Mode Locked to Input Yes

Communication
Network
IP Address 192.168.0.101
Modbus RTU
Id 1
Baudrate 19200
Databits 8
Stopbits 1
Parity Even
J1939
Source Address 0xf2
Allowed Source Addresses All
Allowed DM1 Source Addresses All
J1939:2 (inactive)
Source Address 0xf2
Allowed Source Addresses All
Allowed DM1 Source Addresses All
CANopen (active)
Node Id 0
Baudrate 125 kbit/s

Alarm Configuration
Primary Power Fail Alarm Enabled Yes
Secondary Power Fail Warning Enabled Yes
J1939 CANbus Broken Wire Alarm When Engine Not Running No
J1939 CANbus Amber Warning Lamp Enabled No
J1939 CANbus Red Lamp Severity Disabled

Standby Operation
Initial Start Delay 1 second(s)
Cranking Time 15 second(s)
Delay Between Start Attempts 10 second(s)
Number of Start Attempts 3
Delay Before Disconnecting Generator Breaker 180 second(s)
Cooling Time 3 minute(s)

Prelube
Oscillating No
Prelube Type None

Speed Sensor
Primary Pickup Source SDU
Secondary Pickup Source J1939
Third Pickup Source None
RPM Rounding 5
RUN Detected At 400 RPM
RPM setpoint 1 400 RPM
Ready To Take Load 1782 RPM
Nominal Speed 1800 RPM
Overspeed 2070 RPM (15 %)
Overspeed Shutdown Enabled
Overspeed Shutdown 100 millisecond(s)

Start Conditions
Ready to Start Signal

http://192.168.0.101/File?selection=view 4/5/2018
Caterpillar DCU Controller Page 3 of 10

None configured
Prevent Start
Ready to Start Signal Prevents Start Yes
Repair Mode Prevents Start No

Engine Load
Source channel None

GUI Information
Pages: 3
Page 1

1: Engine Oil Press.


2: Engine Speed
3: Coolant Temp.
4: Fuel Del. Pressure
5: Fuel Temperature
6: Fuel Rate
7: % Load
8: 4-20mA #1
9: Engine Intake Manifold #1 Pressure
Page 2

1: 4-20mA #3
2: Engine Speed
3: 4-20mA #4
4: Input Voltage
5: Coolant Pressure
6: Engine Hours
7: Total Fuel Used
8: None
9: Intake Manif. Temp.
Page 3

http://192.168.0.101/File?selection=view 4/5/2018
Caterpillar DCU Controller Page 4 of 10

1: PT100 #1
2: PT100 #2
3: PT100 #3
4: None
5: None
6: None
7: None
8: None
9: None
10: None
11: None
12: None

Signal Configuration
Switch Inputs
Switch Input #2
Signal Use DCU+RP+Event
Event Alarm
Delay Before Event 5 sec
Input State Normally Closed, Event on open
Requires Running Engine Yes
Requires In Gear No
Requires Engine Load No
Initial Delay 20 sec
Run Detection No
Switch Input #5
Signal Use DCU+RP+Event
Event Alarm
Delay Before Event 0 sec
Input State Normally Closed, Event on open
Requires Running Engine No
Requires In Gear No
Requires Engine Load No
Run Detection No
Switch Input #6
Signal Use DCU+RP+Event
Event Alarm
Delay Before Event 6 sec
Input State Normally Closed, Event on open
Requires Running Engine No
Requires In Gear No
Requires Engine Load No
Run Detection No
J1939 Inputs
Engine Oil Press.
Signal Use DCU+RP+Event
Sensor Min 0.00 kPascal
Sensor Max 1000.00 kPascal
Display US Metric
Display Unit psi kPascal
Display Range Min 0.00 0.00
Display Range Max 145.00 1000.00
Display Major Divider 36.00 250.00
Display Minor Divider 3.00 25.00
Display Multiplier 1 1

http://192.168.0.101/File?selection=view 4/5/2018
Caterpillar DCU Controller Page 5 of 10

Event Alarm
Threshold Type Low
Requires Running Engine Yes
Requires In Gear No
Requires Engine Load No
Initial Delay 8 sec
Alarm Threshold 250.00 kPascal
Delay Before Alarm 2 sec
Fuel Temperature
Signal Use DCU+RP+Event
Sensor Min -40.00 Celsius
Sensor Max 210.00 Celsius
Display US Metric
Display Unit Fahrenheit Celsius
Display Range Min 32.00 0.00
Display Range Max 212.00 100.00
Display Major Divider 45.00 25.00
Display Minor Divider 9.00 5.00
Display Multiplier 1 1
Event Alarm
Threshold Type High
Requires Running Engine No
Requires In Gear No
Requires Engine Load No
Alarm Threshold 66.00 Celsius
Delay Before Alarm 20 sec
Coolant Temp.
Signal Use DCU+RP+Event
Sensor Min -40.00 Celsius
Sensor Max 210.00 Celsius
Display US Metric
Display Unit Fahrenheit Celsius
Display Range Min 32.00 0.00
Display Range Max 302.00 150.00
Display Major Divider 45.00 25.00
Display Minor Divider 9.00 5.00
Display Multiplier 1 1
Event Alarm
Threshold Type High
Requires Running Engine Yes
Requires In Gear No
Requires Engine Load No
Initial Delay 5 sec
Alarm Threshold 103.00 Celsius
Delay Before Alarm 2 sec
Fuel Del. Pressure
Signal Use DCU+RP+Event
Sensor Min 0.00 kPascal
Sensor Max 1000.00 kPascal
Display US Metric
Display Unit psi kPascal
Display Range Min 0.00 0.00
Display Range Max 145.00 999.00
Display Major Divider 36.00 249.00
Display Minor Divider 7.00 49.00
Display Multiplier 1 1
Event Alarm
Threshold Type High & Low
Requires Running Engine Yes
Requires In Gear No
Requires Engine Load No
Initial Delay 20 sec
High Alarm Threshold 850.00 kPascal
Low Alarm Threshold 400.00 kPascal
Delay Before Alarm 5 sec
Total Fuel Used
Signal Use DCU+RP+Event
Sensor Min 0.00 liter
Sensor Max 2147483.65 liter
Display US Metric
Display Unit gallon liter
Display Range Min 0.00 0.00
Display Range Max 5673051.00 21474836.00

http://192.168.0.101/File?selection=view 4/5/2018
Caterpillar DCU Controller Page 6 of 10

Display Major Divider 0.00 0.00


Display Minor Divider 0.00 0.00
Display Multiplier 1 1
Event None
Engine Hours
Signal Use DCU+RP+Event
Sensor Min 0.00 hour
Sensor Max 21474836.47 hour
Display US Metric
Display Unit hour hour
Display Range Min 0.00 0.00
Display Range Max 21474836.00 21474836.00
Display Major Divider 0.00 0.00
Display Minor Divider 0.00 0.00
Display Multiplier 1 1
Event None
Fuel Rate
Signal Use DCU+RP+Event
Sensor Min 0.00 liters/hour
Sensor Max 3212.75 liters/hour
Display US Metric
Display Unit gallons/hour liters/hour
Display Range Min 0.00 0.00
Display Range Max 264.00 1000.00
Display Major Divider 13.00 50.00
Display Minor Divider 2.00 10.00
Display Multiplier 1 1
Event None
Fuel Level 1
Signal Use DCU+RP+Event
Sensor Min 0.00 Percent
Sensor Max 100.00 Percent
Display US Metric
Display Unit Percent Percent
Display Range Min 0.00 0.00
Display Range Max 100.00 100.00
Display Major Divider 0.00 0.00
Display Minor Divider 0.00 0.00
Display Multiplier 1 1
Event Alarm
Threshold Type High
Requires Running Engine No
Requires In Gear No
Requires Engine Load No
Alarm Threshold 50.00 Percent
Delay Before Alarm 6 sec
% Load
Signal Use DCU+RP+Event
Sensor Min 0.00 Percent
Sensor Max 250.00 Percent
Display US Metric
Display Unit Percent Percent
Display Range Min 0.00 0.00
Display Range Max 100.00 100.00
Display Major Divider 25.00 25.00
Display Minor Divider 5.00 5.00
Display Multiplier 1 1
Event None
Intake Manif. Temp.
Signal Use DCU+RP+Event
Sensor Min -40.00 Celsius
Sensor Max 210.00 Celsius
Display US Metric
Display Unit Fahrenheit Celsius
Display Range Min 32.00 0.00
Display Range Max 212.00 100.00
Display Major Divider 45.00 25.00
Display Minor Divider 9.00 5.00
Display Multiplier 1 1
Event Alarm
Threshold Type High
Requires Running Engine Yes

http://192.168.0.101/File?selection=view 4/5/2018
Caterpillar DCU Controller Page 7 of 10

Requires In Gear No
Requires Engine Load No
Initial Delay 20 sec
Alarm Threshold 70.00 Celsius
Delay Before Alarm 5 sec
Engine Intake Manifold #1 Pressure
Signal Use DCU+RP+Event
Sensor Min 0.00 kPascal
Sensor Max 500.00 kPascal
Display US Metric
Display Unit psi kPascal
Display Range Min 0.00 0.00
Display Range Max 72.00 350.00
Display Major Divider 14.00 100.00
Display Minor Divider 7.00 50.00
Display Multiplier 1 1
Event Alarm
Threshold Type High
Requires Running Engine No
Requires In Gear No
Requires Engine Load No
Alarm Threshold 340.00 kPascal
Delay Before Alarm 10 sec
Coolant Pressure
Signal Use DCU+RP+Event
Sensor Min 0.00 kPascal
Sensor Max 500.00 kPascal
Display US Metric
Display Unit psi kPascal
Display Range Min 0.00 0.00
Display Range Max 72.00 500.00
Display Major Divider 14.00 100.00
Display Minor Divider 3.00 25.00
Display Multiplier 1 1
Event Alarm
Threshold Type Low
Requires Running Engine Yes
Requires In Gear No
Requires Engine Load No
Initial Delay 20 sec
Alarm Threshold 70.00 kPascal
Delay Before Alarm 5 sec
4-20 mA Inputs
4-20mA #1
Signal Use DCU+RP+Event
Sensor Min 0.00 Celsius
Sensor Max 800.00 Celsius
Display US Metric
Display Unit Fahrenheit Celsius
Display Range Min 32.00 0.00
Display Range Max 1472.00 800.00
Display Major Divider 360.00 200.00
Display Minor Divider 90.00 50.00
Display Multiplier 1 1
Event Alarm
Threshold Type High
Requires Running Engine No
Requires In Gear No
Requires Engine Load No
Alarm Threshold 400.00 Celsius
Delay Before Alarm 10 sec
4-20mA #4
Signal Use DCU+RP+Event
Sensor Min -100.00 kPascal
Sensor Max 1000.00 kPascal
Display US Metric
Display Unit psi kPascal
Display Range Min 0.00 0.00
Display Range Max 72.00 500.00
Display Major Divider 14.00 100.00
Display Minor Divider 3.00 25.00
Display Multiplier 1 1

http://192.168.0.101/File?selection=view 4/5/2018
Caterpillar DCU Controller Page 8 of 10

Event Alarm
Threshold Type High & Low
Requires Running Engine Yes
Requires In Gear No
Requires Engine Load No
Initial Delay 10 sec
High Alarm Threshold 200.00 kPascal
Low Alarm Threshold 40.00 kPascal
Delay Before Alarm 5 sec
4-20mA #3
Signal Use DCU+RP+Event
Sensor Min 0.00 Celsius
Sensor Max 150.00 Celsius
Display US Metric
Display Unit Fahrenheit Celsius
Display Range Min 32.00 0.00
Display Range Max 302.00 150.00
Display Major Divider 45.00 25.00
Display Minor Divider 9.00 5.00
Display Multiplier 1 1
Event Alarm
Threshold Type High
Requires Running Engine No
Requires In Gear No
Requires Engine Load No
Alarm Threshold 104.00 Celsius
Delay Before Alarm 5 sec
PT100 Inputs
PT100 #3
Signal Use DCU+RP+Event
Sensor Min 0.00 Celsius
Sensor Max 800.00 Celsius
Display US Metric
Display Unit Fahrenheit Celsius
Display Range Min 32.00 0.00
Display Range Max 302.00 200.00
Display Major Divider 45.00 25.00
Display Minor Divider 9.00 5.00
Display Multiplier 1 1
Event Alarm
Threshold Type High
Requires Running Engine No
Requires In Gear No
Requires Engine Load No
Alarm Threshold 160.00 Celsius
Delay Before Alarm 10 sec
PT100 #2
Signal Use DCU+RP+Event
Sensor Min 0.00 Celsius
Sensor Max 800.00 Celsius
Display US Metric
Display Unit Fahrenheit Celsius
Display Range Min 32.00 0.00
Display Range Max 302.00 200.00
Display Major Divider 45.00 25.00
Display Minor Divider 9.00 5.00
Display Multiplier 1 1
Event Alarm
Threshold Type High
Requires Running Engine No
Requires In Gear No
Requires Engine Load No
Alarm Threshold 160.00 Celsius
Delay Before Alarm 10 sec
PT100 #1
Signal Use DCU+RP+Event
Sensor Min 0.00 Celsius
Sensor Max 800.00 Celsius
Display US Metric
Display Unit Fahrenheit Celsius
Display Range Min 32.00 0.00
Display Range Max 302.00 200.00

http://192.168.0.101/File?selection=view 4/5/2018
Caterpillar DCU Controller Page 9 of 10

Display Major Divider 45.00 25.00


Display Minor Divider 9.00 5.00
Display Multiplier 1 1
Event Alarm
Threshold Type High
Requires Running Engine No
Requires In Gear No
Requires Engine Load No
Alarm Threshold 160.00 Celsius
Delay Before Alarm 10 sec
Special Inputs
Engine Hours
Signal Use DCU+RP
Sensor Min 0.00 hour
Sensor Max 21474836.47 hour
Display US Metric
Display Unit hour hour
Display Range Min 0.00 0.00
Display Range Max 10000.00 10000.00
Display Major Divider 1000.00 1000.00
Display Minor Divider 500.00 500.00
Display Multiplier 1 1
Event None
Input Voltage
Signal Use DCU+RP+Event
Sensor Min 0.00 Volt
Sensor Max 40.00 Volt
Display US Metric
Display Unit Volt Volt
Display Range Min 0.00 0.00
Display Range Max 40.00 40.00
Display Major Divider 10.00 10.00
Display Minor Divider 2.00 2.00
Display Multiplier 1 1
Event Alarm
Threshold Type High & Low
Requires Running Engine No
Requires In Gear No
Requires Engine Load No
High Alarm Threshold 30.00 Volt
Low Alarm Threshold 22.00 Volt
Delay Before Alarm 20 sec

Functional Outputs
User Config Output #1 Ready To Take Load
User Config Output #2 Active Faults
User Config Output #3 New Alarm Pulse
User Config Output #4 Alarm or Ack Button or Remote Acknowledge
On Board Relay #1 Ready State
On Board Relay #2 Alarm in Alarm List

Functional Inputs
User Config Switch Input #1 Remote Mode

Speed Relays
Speed Relay 1
Activate Speed 400 RPM
Event Log No
Delay Before Event 0 sec

http://192.168.0.101/File?selection=view 4/5/2018
Caterpillar DCU Controller Page 10 of 10

SDU 410

Signal Configuration
Switch Inputs
SDU Switch #1
Signal Use Event
Event Shutdown
Delay Before Event 2 sec
Input State Normally Open, Event on Closed
Requires Running Engine Yes
Requires In Gear No
Requires Engine Load No
Initial Delay 2 sec
Run Detection No
SDU Switch #2
Signal Use Event
Event Shutdown
Delay Before Event 2 sec
Input State Normally Open, Event on Closed
Requires Running Engine No
Requires In Gear No
Requires Engine Load No
Run Detection No
SDU Switch #3
Signal Use Event
Event Shutdown
Delay Before Event 1 sec
Input State Normally Open, Event on Closed
Requires Running Engine No
Requires In Gear No
Requires Engine Load No
Run Detection No
SDU Switch #4
Signal Use Event
Event Shutdown
Delay Before Event 1 sec
Input State Normally Open, Event on Closed
Requires Running Engine No
Requires In Gear No
Requires Engine Load No
Run Detection No

http://192.168.0.101/File?selection=view 4/5/2018