Professional Documents
Culture Documents
Rizal Technological University College of Engineering, Architecture and Technology
Rizal Technological University College of Engineering, Architecture and Technology
BS ICE
First Semester 2021
Submitted to:
I. INTRODUCTION
Process industries have been growing steadily and advancing rapidly together with the
continuous advancement of technology. However, in connection to this, risk never ceases to exist. As
defined by Occupational Safety and Health (OSH), “risk is the likelihood that a person may be harmed
or suffers adverse health effects if exposed to a hazard.” To assess and determine the risks inside the
plant, during a process, engineers use many risk assessment methods such as Layers of Protection
Analysis (LOPA), Safety Integrity Level (SIL), and more. This allows and helps plants to create a
plan that will help in minimizing the risk to tolerable or desired level and keep employees safe and
avoid costly damages.
II. BACKGROUND
The figure above is an example of scenarios of layers of protection from DEKRA that is often
found through a qualitative hazard review, such as a Process Hazards Analysis (PHA) or a Hazard
and Operability study, which frequently involves a mix of equipment and human failures (HAZOP).
Probability of Failure
Safety Integrity Level Risk Reduction Factor
on Demand Reliability
(SIL) (RRF)
(PFD)
SIL 4 10,000 to 100,000 0.0001 to 0.00001 >99.99%
Identifying the System Integrity Level (SIL) of a safety system performance, techniques such
as Process Hazard Analysis (PHA) and Layers of Protection Analysis (LOPA) are used to
determine the Safety Instrumented System (SIS) and the Safety Instrumented Functions (SIF)
(Primatech Inc., 2009).
3. Probability of Failure Upon Demand (PFD) & Risk Reduction Factor (RRF)
Failure on demand occurs when a safety system is called upon to react following an initiating
event but fails to react. For example, the reactor system has an emergency quench water system
piped to the reactor in the event of a runaway. A runaway occurs, and the quench system is called
upon to act. This is considered a demand. Further, it is established, either by separate testing, or
plant history, that this quench system will successfully operate when demanded 9 times out of 10
times. This implies that it fails only one time out of 10. The risk reduction factor, RRF, is 10
(RRF=1/PFD). The PFD for this system will be 0.1. But the equation (RRF=1/PFD) only applies
to a narrow and specific set of circumstances. The Risk Reduction Factor is the number of times
that risk is reduced when comparing one situation against another (Marszal, 2020).
8|Page
4. SIL Assessment
According to General Electric Co. (2018), Safety Integrity Level is divided into four (4) discrete
ranks, levels 1 to 4 (as shown in the table above). Each level is determined by the reliability of
safety systems for equipment, units, and systems, and to create a plan of maintenance, operations,
monitoring and procurement. SIL uses numeric rating or value that represents the overall rating
for the instrumented function. This tells us the degree of the instrumented function to meet its
requirements to be able to mitigate the risk. After the value assignment to each instrumented
function, the combination of these values reflects the overall safety integrity of the safety
instrumented systems to which the functions belong.
There are several steps in performing an SIL Assessment:
• Assess the required SIL rating for an instrumented function using the created SIL Assessment
records from LOPA, risk matrix, PHA, or external.
• Associate the correct and appropriate SIL Assessment with the instrumented function.
5. SIL Determination
Safety Integrity Level (SIL) Determination is the process of determining the amount of risk
mitigation that is required to reduce the risk caused by a process to a tolerable and accepted level.
It represents the initial step in the development, design, commissioning, and operation of Safety
Instrumented System (SIS). SIL determination consists of the SIL for each Safety Instrumented
Function (SIF) within a SIS. This fundamental process is related to the overall risk from the
exposed hazard that can occur and is guided by the corporate standards to ensure that safety-related
systems acceptably performs the required safety functions under every stated condition within the
specified period.
Incomplete SIL Determination can affect the safety integrity of the process and even put the
integrity at risk. Properly defined SILs result in significant cost improvement across all operating
environments. To maintain SIL performance and optimize the ownership cost, performing regular
tests of SIFs for operational efficacy should be attained.
In every safety instrumented function, the average probability of failure on demand (PFDavg)
will be computed and the result will be compared with the PFDavg range for the targeted SIL. This
process involves reviewing the loop design and collecting the required information to calculate the
PFDavg for the loop.
The types of information required during the verification includes but is not limited to failure
rate of the hardware, common mode failure percentage, and the coverage of proof test. PFDavg
serves a simple function of instrument failure rates and test intervals for basic SIFs.
8. SIL Validation
Safety Integrity Level (SIL) Validation is implemented to build a “fit for purpose” design of
safety instrumented measures that has the capability of mitigating hazards with respect to safety
and consequences, in both the environment and economic loss. This aims to determine if the
specified requirements can be achieved as mentioned in the safety requirement specifications
through tests and inspections of the installed and commissioned SIS and its associated SIFs.
It is carried out prior to the operation phase of the IEC 61511 safety lifecycle to put forth a plan
for routine actions such as proof testing, maintenance override conditions, documentation of
system demand and failure rates consistent with the Safety Integrity Level (SIL), verification
calculations, audit and test documentation, and diagnostic and repair procedures. (Safeopedia Inc.,
2021)
12 | P a g e
C. SIL Calculation
Many automated processes are safety critical systems, these are process whose failure could
result in a loss of life, significant property damage or damage to the environment (J. C. Knight,
2002). An SIL Study or SIL Verification in the IEC standards is done to ensure that it meets a
minimum SIL.
A SIL Study helps to determine:
• Type of device
• Hardware architecture
• Voting logic
• Proof Test interval
These are all needed to meet the required Risk Reduction Factor or the Safety Integrity Level
of a Safety Instrumented Function.
Examaple:
A fail-closed PV-100 can lead to overpressure, a High-Pressure Shutdown was added as the
SIF in Figure 1. This consists of the sensor PIT-200, the logic controller PAH/ PAHH and the final
element PV-200. After conducting LOPA, the SIF must meet the requirements of SIL 2 to reduce
the risk by 100 (RRF at 100).
To determine the reliability of the (SIF), calculation of the PFD of each component is
necessary.
Figure 4
13 | P a g e
Note that this equation is for 1 out of 1 configuration (i.e. no redundancy), under low demand
operation. There are other equations for different voting logic such as: 1 out of 2 or 2 out of 3. There
are also other equations for safety functions used continuously that are considered as high demand
operations (Icarus-ORM Academy, 2015).
Pressure Transmitter:
𝜆𝐷𝑈 6.0 × 10−7 𝑓𝑎𝑖𝑙𝑢𝑟𝑒𝑠/ℎ𝑜𝑢𝑟
TI 48 months or TI = 35,040 hours
MTTR 8 hours
𝜆𝐷𝐷 1.5 × 10−7 𝑓𝑎𝑖𝑙𝑢𝑟𝑒𝑠/ℎ𝑜𝑢𝑟
35,040
𝑃𝐹𝐷𝑃𝑇 = 6.0 × 10−7 × ( + 8) + 1.5 × 10−7 × 8
2
𝑃𝐹𝐷𝑃𝑇 = 0.010518 or 1% chance in any given chance
Repeat the calculation on each component: PLC input, PLC main processor, PLC power
supply, PLC output, Solenoid, Actuator and Valve.
14 | P a g e
Step 3: Combine all the components PFDs to determine the SIL PFD
Element PFD
Pressure Transmitter 0.010518
PLC input 0.004388
PLC main processor 0.000051
PLC power supply 0.000002
PLC output 0.002194
Solenoid 0.010254
Actuator 0.005995
Valve 0.046975
𝑃𝐹𝐷𝑆𝐼𝐿 = 0.080376
Step 4: Convert SIL PFD to RRF and compare to the target RRF (which is at least 100)
The calculated RRF was far from the target of 100. From the SIL Table, the calculated RRF
still falls in the line of SIL 1 where the chances of failure are more than 1% and from our calculation
8%.
Consideration of other alternatives is needed when the SIL requirement is not met:
1. Look at the distribution of failure of the current setup, architectural constraints,
consideration of redundancy or adjustment of the proof test interval.
2. The designer must do a recalculation with another safer architecture (1oo2, 2oo3, etc.) to
meet the SIL requirement of a safety instrumented function (PLCdesign, 2016).
15 | P a g e
III. References
https://www.sciencedirect.com/book/9780080999975/marine-structural-design
https://www.aesolutions.com/post/independent-protection-layers-will-they-work- when-
needed?fbclid=IwAR3JglGGYEm6DNldvo_cAFOcTyP8U2D17sdqVObu-
LZzXizZqcfslxoV-30
https://www.crossco.com/resources/articles/determining-safety-integrity-levels-for- your-
process-application/
https://www.ge.com/digital/documentation/meridium/Help/V43060/IOTBmYjU3MW Yt
MWVhZC00YzQ2LTg3MDEtZmYxNzg4YmFlN2Nj.html
https://www.process-improvement-institute.com/consulting-services/sis-sil-sif-
services/?fbclid=IwAR1rtZAlTJbTwmcD69vWU4d20RQ8-
AmJYdCtNo9wTpjGkY4jem3UecpNCoE
https://webstore.iec.ch/publication/24241?fbclid=IwAR1IP_-QP-
4vBkp_AkNjOupMqN6DiX6N3JpBAwROgtGpTqtSdbAixOPUg8Q
https://www.isa.org/standards-and-publications/isa-standards/isa-standards-
committees/isa84?fbclid=IwAR1nLNLT9O5RVG_21GWkKCP9a2adVRYtw4JtUn
W6u++hh--JaRToXSpX8Lzyo
https://ieeexplore.ieee.org/document/1007998
https://www.linkedin.com/pulse/lopa-layer-protection-analysis-john-kingsley
www.dekra.com/en/layers-of-protection-analysis/ https://www.kenexis.com/risk-reduction-
factor/
https://www.icheme.org/media/9673/xxi-paper-045.pdf
https://processoperations.com/SafeInstrSy/SS_Chp01g.htm
https://www.processindustryinformer.com/application-of-the-sil-analysis-to-process- plant-
safety-systems
https://plcdesign.xyz/en/sil-requirement/
https://www.youtube.com/watch?v=IUe1DiybtMk
16 | P a g e
https://www.safeopedia.com/definition/4954/safety-integrity-level-study-sil-study- safety
https://www.safeopedia.com/definition/5009/sil-determination
https://www.safeopedia.com/definition/5010/sil-determination-methods
https://www.safeopedia.com/definition/5017/sil-validation-sil-v
https://forumautomation.com/t/independent-protection-layer- ipl/5877#google_vignette
https://blog.msasafety.com/what-safety-integrity-level-
means/?fbclid=IwAR2aq0_oAZ0K0mWGR64t98JiqtaqhGDmg-
5MDmyALlYinte7pjxZn18Hfu0
https://www.sciencedirect.com/science/article/pii/S1877705814017263
https://core.ac.uk/download/pdf/81971209.pdf
https://citeseerx.ist.psu.edu/viewdoc/download?doi=10.1.1.522.1335&rep=rep1&type
=pdf
http://www.primatech.com/images/docs/faq_s84_standard_for_safety_instrumented_s
ystems.pdf?fbclid=IwAR09mHoGt1zc-
UJn7UzN6yoE6FbZQtRH5MFS8DhIrNw8ORbYLd_VgWc7oBw
https://www.researchgate.net/profile/Philip-Henry/public
YouTube Link
https://www.youtube.com/watch?v=orZoS_GcxHE
https://www.youtube.com/watch?v=Af-CbZ7aTCY
Rizal Technological University
College of Engineering, Architecture and Technology
Department of Instrumentation and Control Engineering
BS ICE
First Semester 2021
Submitted to:
I. Introduction ............................................................................................................................. 1
History of HAZOP................................................................................................................... 1
IEC 61882 standard ................................................................................................................. 1
II. Hazard Operability .................................................................................................................. 2
A.Objectives of HAZOP.......................................................................................................... 2
B.Common mistakes when conducting a HAZOP .................................................................. 2
C.Types of HAZOP ................................................................................................................. 2
D.Basic team for a process plant may be: ............................................................................... 2
E.When and Where to use HAZOP? ....................................................................................... 3
III. HAZOP Procedure ............................................................................................................................. 3
A.HAZOP Worksheet and Flowchart .............................................................................................. 3
B.Definition of Terms and Flowchart .............................................................................................. 4
C.Structure of the HAZOP Study Procedure .................................................................................. 7
D.Flow Chart of the Study Method ................................................................................................ 10
IV. HAZOP Case Studies ............................................................................................................ 11
V. HAZOP Study Conclusion .................................................................................................... 11
VI. References ............................................................................................................................. 12
I. Introduction
HAZOP, or a Hazard and Operability Study, is a systematic way to identify possible hazards in
a work process. In this approach, the process is broken down into steps, and every variation in
work parameters is considered for each step, to see what could go wrong. HAZOP’s meticulous
approach is commonly used with chemical production and piping systems, where miles of pipes
and numerous containers can cause logistical headaches.
Hazard and Operability (HAZOP) is a well known and well documented study. The HAZOP
technique was initially developed to analyze chemical process systems, but has later been extended
to other types of systems and also to complex operations and to software systems. The purpose of
the HAZOP is to investigate how the system or plant deviate from the design intent and create risk
for personnel and equipment and operability problems.
History of HAZOP
The HAZOP technique was initially developed in the 1960s to analyze major chemical process
systems but has since been extended to other areas, including mining operations and other types
of process systems and other complex systems such as nuclear power plant operation and software
development. It is also used as the basis for reviewing batch processes and operating procedures.
Although a number of companies were addressing this issue, the technique is generally considered
to have originated in the Heavy Organic Chemicals Division of Imperial Chemical Industries (ICI),
which was then a major British and international chemical company. The history has been
described by Trevor Kletz. who was the company's safety advisor from 1968 to 1982, from which
the following is abstracted.
1
II. Hazard Operability
A. Objectives of HAZOP
1. Identify all deviations from the way a system is intended to function: their causes, and all the
hazards and operability problems associated with these deviations.
2. Decide whether actions are required to control the hazards and/or the operability problems,
and if so, identify the ways in which the problems can be solved.
3. Identify cases where a decision cannot be made immediately, and decide on what information
or actions are required.
4. Ensure that actions decided are followed up.
5. Make operator aware of hazards and operability problems.
C. Types of HAZOP
1. Process HAZOP
The HAZOP technique was originally developed to assess plants and process systems.
2. Human HAZOP
A “family” of specialized HAZOPs. More focused on human errors than technical failures.
3. Procedure HAZOP
Review of procedures or operational sequences Sometimes denoted SAFOP – SAFe
Operation Study.
4. Software HAZOP
Identification of possible errors in the development of software.
2
E. When and Where to use HAZOP?
Hazard and Operability Study should be accomplished in the design phase or during the early
stages of project development, as well as identifying the potential hazards in existing systems to
identify modifications that should be implemented to reduce risk and operability problems. As a
compromise, the HAZOP is usually carried out as a final check when the detailed design has been
completed. With an effective analysis, potential hazards may be discovered before they result in
injuries and loss.
HAZOP is best suited for assessing hazards in facilities, equipment, and processes and is
capable of assessing systems from multiple perspectives. In design, assessing system design
capability to meet user specifications and safety standards. In physical and operational
environments, assessing environment to ensure system is appropriately situated, supported,
serviced, contained, etc. In operational and procedural controls, assessing engineered controls (ex:
automation), sequences of operations, procedural controls.
3
Divide section
into nodes
NOT SURE
Design Intent
The design intent is a description of how the process is expected to behave at the node;
this is qualitatively described as an activity (e.g., feed, reaction, sedimentation) and/or
quantitatively in the process parameters, like temperature, flow rate, pressure, composition,
etc.
Node
A node is a specific location in the process in which (the deviations of) the design/process
intent are evaluated. Examples might be: separators, heat exchangers, scrubbers, pumps,
compressors, and interconnecting pipes with equipment.
Guideword
A short word to create the imagination of a deviation of the design/process intent. The
most commonly used guide-words are: no, more, less, as well as, part of, other than, and
reverse. The guidewords are applied, in turn, to all the parameters, in order to identify
unexpected and yet credible deviations from the design/process intent.
Guide-word + Parameter → Deviation
4
Other than (other) Complete substitution or miscellaneous - another activity
takes place or an unusual activity occurs or uncommon
condition exists
Parameter
The relevant parameter for the condition(s) of the process (e.g. pressure, temperature,
composition).
Process parameters may generally be classified into the following groups:
1. Physical parameters related to input medium properties
2. Physical parameters related to input medium conditions
5
3. Physical parameters related to system dynamics
4. Non-physical tangible parameters related to batch type processes
5. Parameters related to system operations
Deviation
A deviation is a way in which the process conditions may depart from their design/process
intent.
Cause
The reason(s) why the deviation could occur. Several causes may be identified for one
deviation. It is often recommended to start with the causes that may result in the worst possible
consequence.
Consequences
The results of the deviation, in case it occurs. Consequences may both comprise process
hazards and operability problems, like plant shut-down or reduced quality of the product.
Several consequences may follow from one cause and, in turn, one consequence can have
several causes
Relieve the process from the hazardous deviation
Safeguard
Facilities that help to reduce the occurrence frequency of the deviation or to mitigate its
consequences.
There are five types of Safeguard that can be used in HAZOP worksheets, including:
1. Identify the deviation
2. Compensate for the deviation
3. Prevent the deviation from occurring
4. Prevent further escalation of the deviation
5. Relieve the process from the hazardous deviation
6
C. Structure of the HAZOP Study Procedure
7. Pre-HAZOP Meeting
• Lead Process Engineer and HAZOP Study Leader
• Identify and Obtain Required Information
• Plan the Study Sequence
• Plan the Schedule
7
2. Identify the Project for the HAZOP Study
Based on the Safety Team meeting, the Safety Process route selected will specify whether
the project/process will undergo a HAZOP study. If a project is selected there will be some
indication of the time scheduling of the HAZOP because of the timing of the Project Planning
Program.
The decision to HAZOP or not to HAZOP is primarily the responsibility of this team and
will be based on several contributing factors:
• legislation - does local SHE legislation require a HAZOP;
• tradition - has the company a tradition of using HAZOP techniques process;
• conditions - hazardous chemicals, high/low temperatures, high/low pressures, chemical
reactions etc.;
• experience - does the company has wide HAZOP experience? and does the company
want it?
• cost - the project value may be low, in which case a small projects HAZOP group may
handle it.
8
subject process. Ideally, the team consists of 5 to 7 members, although a smaller team could
be sufficient for a simpler, less hazardous plant.
The Process Engineer and the Operations or Commissioning Engineer, on the other hand,
should be very familiar with all the details of the plant under review so that they can answer
the questions which will be raised by the HAZOP team. In this case, the core team format will
comprise another specialist/s.
7. Pre-HAZOP meeting
In order to make the HAZOP run effectively a number of pre-HAZOP activities must be
carried out. The pre-HAZOP meeting is an essential component of these activities and
normally involves the following:
• Identifying the Obtaining the Required Information
• Planning the Study Sequence
• Planning the Schedule
Select deviation
e.g. more flow
Move on to next NO
Is more flow possible?
deviation
YES
Is it hazardous or does it Consider other
prevent efficient operation? causes of more
flow
YES
Will the operator know that
there is more flow?
YES
What change in plant or methods will Consider other
prevent the deviation or make it less changes or agree
likely or protect against the to accept hazard
consequences?
Agree change(s).
10
Agree who is responsible for the action
IV. HAZOP Case Studies
Reactor System
Exercise:
Perform HAZOP Study for Shell & Tube Heat Exchanger.
11
VI. References
A. Introduction
WHAT IS HAZOP
B. History of HAZOP
Hazard and Operability study
C. Objectives of HAZOP
Risk Assessment
D. Pros of Conducting a HAZOP Study
Hazard and Operability Study (HAZOP): Why It's Important for Safety Professionals
E. Cons of Conducting a HAZOP Study
Hazard and Operability Study (HAZOP): Why It's Important for Safety Professionals
F. Common mistakes when conducting a HAZOP
Common Mistakes When Conducting a HAZOP and How to Avoid Them
G. Types of HAZOP
Risk Assessment
H. Basic team for a process maybe:
Hazard and Operability Study (HAZOP): Why It's Important for Safety Professionals
Risk Assessment
I. HAZOP Worksheet and Flowchart
Risk Assessment 9. HAZOP (ntnu.edu)
J. Definition of Terms
Risk Assessment 9. HAZOP (ntnu.edu)
Risk Assessment
K. When and Where to perform HAZOP
Risk Assessment
WHAT IS HAZOP
Risk Assessment
Hazard & Operability Analysis (HAZOP)
L. HAZOP Study Procedure
Hazard and operability study (HAZOP) procedure | TÜV SÜD in India (tuvsud.com)
What Is HAZOP | Graphic Products
09.1 hazop studytrainingcourse (slideshare.net)
M. IEC 61882 Standard
Saiglobal OSH
Primatech_Comparison of HAZOP Application Guide
webstore.iec.ch
AS IEC 61882-2003 Hazard and operability studies (HAZOP studies)-Application guide
(saiglobal.com)
N. HAZOP Case Studies
PPT - HAZOP Case Studies – Example 1 PowerPoint Presentation, free download -
ID:2568493 (slideserve.com)
12
RIZAL TECHNOLOGICAL UNIVERISTY
COLLEGE OF ENGINEERING ARCHITECTURE AND TECHNOLOGY
INSTRUMENTATIO AND CONTROL ENGINEERING
TOPIC NO.3
INSTRUMENTATION ENGINEERING
CALMA, NORIELLE
AREA
CLASSIFICATION
MARIBAO, ALLYZA
PADRIGON, WILFREDO D.
VERGARA, BRYAN
Title page
I. INTRODUCTION ------------------------------------------------------------------------------- 1
II. HAZARDOUS AREA CLASSIFICATION ------------------------------------------------- 4
A. HAZARDOUS LOCATION STANDARDS
B. ZONE SYSTEM
C. CLASS/DIVISION SYSTEM
III. HAZARDOUS AREA CLASSFICATION MAPPING ------------------------------------12
IV. HAZARDOUS AREA CLASSIFICATION MARKINGS---------------------------------16
V. REFERENCES -----------------------------------------------------------------------------------20
I. Introduction
To prevent any risk of explosion or fire and improve safety of the process and employees, all
potentially hazardous areas must be classified according to the processes conducted in these
areas. It is in responsibility of the end user to define the Hazardous Areas Within the
operations.
Hazardous Area Classifications is the method of analyzing and classifying the environments
that may contain explosive gas atmospheres, as well as assisting in the right selection of
electrical equipment. The concept of analyzing potentially explosive locations is critical for
reducing the risk of electrical equipment installation in potentially explosive environments.
Appropriate areas classification allows preparation of safety procedures for plant operation and
maintenance. Classification varies across the world.
II. Hazardous Area Classification
Atmosphere Explosive
North America
Regulations established by NEC, CEC, OSHA and NFPA NEC 500 is most common and use
d for decades
Explosive Atmospheres Standards
The International Electrotechnical Commission has been adopted by countries around the
world (IEC) zoning is the name for this ideology, which is used throughout North America.
To determine the level of safety required, it is divided into Classes, Divisions, and Groups.
The boundaries of a particular hazardous zone are primarily defined by zone classification,
such as the release rate of gas or vapour and duration of release in normal condition.
zone 0, zone 1, and zone 2 can be present in any explosive atmosphere according to
IS 5572:2009 (concentration of flammable gas, vapour or mist in air) and IEC 60079-10
Hazardous Area Classification according to IEC 60097 and ATEX
Areas where there is the likelihood of the presence of gases, vapors, dust, and fibers are referred
to as zones. The higher the number in this ‘zonal classification’ the smaller is the risk of an
explosion.
Zones are classified as per IEC 60097 and ATEX shown below
B. Zone System
Hazardous areas are defined in DSEAR as "anywhere where explosive atmospheres are likely
to occur in such quantities that special precautions are required to protect worker safety. ". In
this context, it is better to take "special precautions" for the equipment's construction,
installation, and use, as indicated in BS EN 60079 101.
Hazardous areas are classified into zones based on an assessment of frequency and
duration of explosive gas atmospheres, as follows:
• Zone 0: An area in which an explosive gas atmosphere is present continuously or for long
periods;
• Zone 1: An area in which an explosive gas atmosphere is likely to occur in regular
operation;
• Zone 2: An area in which an explosive gas atmosphere is not likely to occur in regular
operation and, if it happens, will only exist for a short time.
Various sources have attempted to establish time limits for these regions, but none have
been officially approved. The most commonly used values are:
A study of the extent and classification of a hazardous area involves reviewing and
documenting the following:
These factors allow the appropriate selection of the zone type, extent of the zone, and
as well as the equipment. The IP code provides a method for estimating the release rate of
small diameter holes with a pressurized source. It shows how the buoyancy and momentum of
a drop affect the extent of an area. Otherwise, it sums the values of a mixture of LPG, gasoline,
natural gas, and hydrogen from a refinery for pressures up to 100 bar.
Selection of Equipment:
The DSEAR ACOP describes the provisions concerning existing equipment. There are
different technical means (protection concepts) of building equipment to the other categories.
These, the standard current in mid-2003, and the letter giving the type of protection are listed
below.
Electrical
Type 'n' - EN
50021 1999
'd' - Flameproof Non-electrical
'ia' intrinsically safe enclosure EN 13463-1,
EN 50020, 2002 EN 50018 2000 2001
Ex s - Special protection if
specifically certified for Zone 'p' - Pressurized
0 EN 50016 2002
'q' - Powder
filling
EN 50017,
1998
'o' - Oil
immersion
EN 50015,
1998
'e' - Increased
safety
EN 50019,
2000
'ib' - Intrinsic
safety
EN 50020,
2002
'm' -
Encapsulation
EN 50028,
1987
's' - Special
protection
The correct selection of electrical equipment for hazardous areas requires the following
information:
• Hazardous area classification (as in the areas indicated in the table above);
• The temperature class or ignition temperature of the gas or vapor is mentioned
in the table below:
Maximum
Surface
Temperature Temperature, Ignition Temperature
Classification °C of gas or vapour, °C
T1 450 >450
T2 300 >300
T3 200 >200
T4 135 >135
T5 100 >100
T6 85 >85
Although several different combustible materials may be present in a particular area, the
material that gives the highest classification determines the overall type of the area. The IP
code specifically looks at the problem of hydrogen-containing process flows as commonly
found in refineries. Consideration should be given to combustible materials that may be
generated by chemical interactions.
C. CLASS/DIVISION SYSTEM
Hazardous locations per the Class/Division system are classified according to the
Class, Division, and Group.
▪ CLASS – The Class explains the general nature (or characteristics) of hazardous
substances that may or may not be present in sufficient quantities.
Class III – Locations where ignitable fibers may or may not be present in sufficient
amounts to form explosive or ignitable mixes.
CLASS DIVISION
Group definition
Group - define the type of hazardous material and (partly) the location of the surrounding
atmosphere. Group is divided in three groups where Group I is reserved for mining locations.
Group II is for explosive gases (Zone 0, 1 and 2) and Group III is for explosive dusts (Zone
20, 21 and 22).
Group Mines
I susceptible to firedamp (flammable mixture of gases naturally occurring
in a mine).
A potentially explosive atmospheres exist where there is a risk of explosion due to mixtures of
gas/air, vapor/air, dust/air or other flammable combinations. Any area that could have a
potentially explosive atmosphere is known as a Hazardous Area. The purpose of area
classification is to identify the extent of the area made hazardous as a result of the presence of
explosive atmosphere and to classify the identified hazardous area on the premise of likelihood
and kind of flammable release expected to be present.
Fig. 1 Area classification example according to International Electrotechnical Committee
(IEC)
Fig. 3 Tank with floating roof with or without protective cone roof
Fig. 4 Area Classification Diagram for a Class I Area (Flammable Liquid)
• A risk-based approach.
Grades of release
3 basic grades of release in order of decreasing frequency and likelihood of the explosive gas
atmosphere:
Release which is not expected to occur in normal operation and, if it does occur, is likely
to do so only infrequently and for short periods.
Release rate
The greater the release rate, the larger the extent of the zone.
• Geometry
• Release Velocity
• Concentration
• Liquid Temperature
Openness
• An enclosed area.
Ventilation
Natural or artificial movement of air and its replacement with “fresh air”.
• Fair: “Present at normal operation. Discontinuities are permitted for short period.”
Marking
The marking criteria for electrical equipment are uniformly given forth in general technical
requirements standards. The equipment must be clearly labeled in accordance with the
classified area in which it is permitted to be installed.
• Class
• Division
• Group
• The maximum safe operating temperature or temperature range, based on a 40°C
ambient.
• Any special conditions that have to be observed (such as NEC section 500-5(d))
SURROUNDING ATMOSPHERE
EX:
EX ic IIB T5 Gc
EXPLOSION PROTECTED
PROTECTION TYPE
EX:
• d- Flameproof
• Ia- Intrinsically Safe
• e- Increased safety
MATERIAL GROUP
EX:
• I - Mines
• II - Surface above
ground industries
SUB GROUP:
EX:
TEMPERATURE
CLASSIFICATION
EX:
• T1- 450ºC
• T2- 300ºC
• T3- 200ºC
• T4- 135ºC
• T5- 100ºC
• T6- 85ºC
AREA CLASSIFICATION
EX:
GROUP CLASSIFICATION
EX:
Gas :
• GROUP A- Acetylene
• GROUP B- Hydrogen Ethylene,
acrylonitrile, propylene oxide, ethyl oxide
• GROUP C- Cyclopropane, ethyl ether
• GROUP D - Acetone, methane, hexane,
propane
https://www.hse.gov.uk/comah/sragtech/techmeasareaclas.htm
https://www.worksafe.qld.gov.au/laws-and-compliance/compliance-and-enforcement/audits-
and-inspections/electrical-safety-audits/hazardous-area-installations-audits
https://www.emerson.com/documents/automation/product-bulletin-hazardous-area-
classifications-protections-en-123358.pdf
https://www.engineeringtoolbox.com/hazardous-areas-classification-d_345.html
https://www.grainger.com/know-how/safety/emergency-response/fire-protection/kh-
hazardous-locations-124-qt
https://www.slideshare.net/AniruddhaKulkarni6/hazardous-area-module-zones-
method-of-determination-of-hazardous-area-
radius#:~:text=Hazard%20radii%20may%20be%20determined,IP%20Code%2C%2
0Part%2015).
“UL and C-UL Hazardous Areas Certification for North America.” UL,
www.ul.com/services/ul-and-c-ul-hazardous-areas-certification-north-america.
“What Is Temperature Class (T Class) & Why Is It Important?” Pyroban, 17 Dec. 2019,
www.pyroban.com/temperature-class/.
Rizal Technological University
College of Engineering, Architecture and
Technology
Department of Instrumentation and Control Engineering
Submitted by:
BS ICE
CEAT-08-701P
CEAT-08-702E
CEAT-08-702P
Submitted to:
A. Fire and Gas System – It is a combined system of components and circuits designed to monitor
and report a fire or gas alarm condition or control devices that trigger an alarm and initiate an
appropriate response to these alarms.
Fire and gas safety (FGS) systems detects and reduce risk in hazardous environments and
industrial processes whether offshore oil platforms, onshore refineries and fuel storage sites,
pipeline compressor stations and liquefied natural gas (LNG) terminals, turbine enclosures and
more. These critical industrial facilities require compliant systems that detect flames or
combustible and toxic gases, identify faults in the equipment and activate notification and fire
suppression equipment in accordance with standards and codes. As a facility’s needs change or
expand, operators may require higher and more reliable risk mitigation risk levels.
A. Fire detector
1. Smoke Detectors
The two most commonly recognized smoke detection technologies are ionization smoke
detection and photoelectric smoke detection.
These detectors have an ionization chamber with an 8-particle radiator in the center that
ionizes the air inside the chamber with an Americium-241 foil. When the detector is in its usual
state, an electric voltage is applied to the needle electrode, and a known current pass through
the detection chamber as a result. Small aerosol particles (soot particles, combustion gases,
etc.) attach themselves to the ionized particles when a fire occurs. As a result, the resistance in
the chamber rises, and the current flow within the detecting chamber decreases. The electronics
in the detector register this change, and a fire signal is issued to the Control Panel. Generally,
more responsive to flaming fires.
A transmitter LED and a receiver photo-diode make up the sensor. These two devices are
positioned at an angle and separated by a screen so that light from the LED does not directly
impinge on the receiver diode. Infrared light is emitted by the transmitter LED into the
detection chamber. When a fire occurs, visible combustion products enter the chamber,
scattering some of the light emitted by the LED and causing it to impinge on the receiver diode.
This raises the signal level created by the receiver, which is detected by the detector electronics,
which then activates the alarm. Generally, more responsive to fires that begin with a long
period of smoldering.
2. Heat Detectors
The energy emitted by a fire in the form of heat is detected by thermal or heat detectors.
Conventional currents of heat air or combustion products, as well as radiation impacts, are the
most common ways for the detector to be activated. Thermal detectors are slower to respond to a
fire than other detecting systems since this method of activation takes time to establish.
Fixed temperature and rate of rise are the two most prevalent types of heat detectors. The signal
device is activated by the heat of a fire occurrence in both cases.
a. Fixed Temperature
Fixed-temperature detectors send out a signal or triggers automatically when the detection
element reaches a certain temperature.
b. Rate of Rise
When the temperature rises above a predetermined level, rate of rise detectors sends out a
signal. Rate of rise detection devices can be set to operate quickly, are effective over a wide
range of ambient temperatures, recycle rapidly, and can withstand a moderate rise in ambient
temperatures without sounding an alarm.
3. Flame Detectors
These detectors detect ultraviolet or infrared light and are mostly used to enhance heat and
smoke detectors or to provide broad surveillance of a big switchyard.
Flame detectors are commonly used in open areas outdoors, but they can also be used indoors.
Protects high-risk areas such as oil rigs, fuel stations, petrochemical factories, etc. They work by
analyzing the energy emissions (UV or IR) from a fire rather than the combustion products like
smoke and heat.
B. Gas Detectors
1. Flammable Gas Detectors
Detects the percentage by volume of flammable gas in air in terms of LFL and UFL.
a. Lower explosive limit (LEL) or lower flammable limit (LFL) - The lowest concentration
(the lowest percentage of substance in the air), which will create a fire when there is a
source of ignition (heat, arc or flame).
b. Upper explosive limit (UEL) or upper flammable limit (UFL) -The highest concentration
of a vapor or gas (the highest percentage of the substance in air) that will produce a flash
of fire when an ignition source (heat, arc, or flame) is present.
Disadvantages
• Catalysts can become poisoned or inactive due to contamination (chlorinated & silicone
compounds, prolonged exposure to H2S and other sulfur &/or corrosive compounds).
• The only means of identifying detector sensitivity loss is by checking with the appropriate
gas on a routine basis and recalibrating as required.
• Requires oxygen for detection.
• Prolonged exposure to high concentrations of combustible gas may degrade sensor
performance.
• If flooded with a very high gas concentration, may show erroneously low or no response,
and sensor may be damaged or rendered inoperable.
b. Infrared Gas Detectors - Infrared Gas Detectors make use of the property of Hydrocarbons
and other gases to absorb infrared energy at certain wavelengths but not others. For HCs
the absorption peak occurs around 3.4 µm. A reference measurement is normally made
close to the measurement wavelength that is not absorbed by expected gases. The ratio
from the two measurements gives the gas concentration free from variations in signal
intensity and detection sensitivity.
Disadvantages
• The initial higher cost per point. IR detectors typically are more expensive than catalytic
detectors at initial purchase.
• Higher spare parts cost.
• Gases that do not absorb IR energy (such as hydrogen) are not detectable.
• High humidity, dusty and/or corrosive field environments can increase IR detector
maintenance costs.
• Temperature range for detector use is limited compared to catalytic detectors.
• May not perform well where multiple gases are present.
c. Open Path (Line of Sight) Gas Detectors - Open path gas detectors make use of properties
of gases to absorb infrared energy at certain wavelengths but not others. This property
coupled with high energy sources enables open path detectors to sense gas over relatively
long distances, the wide-area coverage offered by Open Path Gas Detectors make them
excellent instruments for perimeter and cross-sectional monitoring around storage tanks,
off-shore platforms, along loading docks, and fence-line monitoring. Open Path Gas
Detectors provide a high speed of response, they operate in extreme conditions, and require
fewer instruments to monitor large areas.
Set Point: Open path detectors have a typical recommended minimum alarm setting of 0.5
LFL m (50 % LFL extended for one meter)
Advantage
• Much more efficient than fixed point detectors.
• Can be able to replace several fixed-point detectors.
• They require much less maintenance than do fixed point detectors.
• Well-suited for open spaces.
• Able to measure in large spaces.
Disadvantage
• The cost to install open path detectors may cost more than fixed point detectors.
2. Toxic Gas Detectors - Detects the concentration in ppm of toxic gas in terms of TLV.
a. Threshold Limit Value (TLV) - Refers to airborne concentrations of substances, and
represent conditions under which nearly all workers may be repeatedly exposed day after
day without adverse health effects.
Parts Per Million (PPM) - The mass of a chemical or contaminate per unit volume of water
1. Mechanical Considerations
a. Mounting Locations
o Solid and robust mounting location
o Good structure and clearly marked
A. Fire Detection
All workplaces should have arrangements for detecting fire. IS 3218 gives a basis for assessing
what type of detection system will be appropriate for a workplace and will also give guidance of
its installation. Consideration must be given to any parts of the workplace where a fire could start
and spread undetected. This could be a storage area or a basement that is not visited on a regular
basis, or a part of the workplace that has been temporarily vacated, for example at mealtimes. Fires
that start and develop unnoticed can pose a serious danger to people in the workplace.
1. Fire Warning
In almost all buildings, a suitable electrically operated fire warning system, with manual
call points positioned both on exit routes and adjacent to final exits should be installed. This
should have sufficient sounders for the warning to be clearly heard throughout the workplace.
The sound used as a fire warning should be distinct from other sounds in the workplace and,
where background noise levels are high or an employee has a hearing impairment, it may also
be necessary to install a visual alarm such as a distinctive flashing or rotating light.
2. Nuclear Power Plant
Traditionally, nuclear power plant designers have utilized a combination of fire codes, test
standards, fire consultant recommendations, insurance agency requests, and detector vendor
suggestions to formulate the design of fire detection systems. Proceeding in this manner,
designers often apply detection principles to nuclear power plants which have been proven in
residential and commercial installations. However, because the ventilation conditions, ceiling
heights, ceiling construction, and types of combustibles existing in nuclear power plants can
differ from those used elsewhere, it is difficult to show that traditional detection system design
approaches will be adequate for 9 nuclear power plants. Also, it is doubtful whether any theory
can be developed and proven in the near future to describe the effects of different installation
conditions on detection system operation.
B. Gas Detection
Gas sensors are critical for monitoring and detecting hazardous inert gases, and ensuring
safety, air quality, or analyzing environments throughout many different industries.
3. Power Plant
The coal-fired power plant is a highly engineered complex of material handling,
combustion, electrical generation and pollution reduction equipment, all designed for
continuous operation. Power plants have many safety hazards, some of which are addressed
by fixed gas detection. Major plant systems include coal handling, combustion controls,
feedwater and boiler, cooling towers, electrical generators, flue gas cleanup and stacks,
emissions monitoring and the control system. Most areas of the plant have sub-systems or
operations with the potential for personnel exposure to dangerous levels of Combustible and
Toxic gases, plus Oxygen Deficiency, not to mention fire.
4. Boiler Room
Industrial buildings and facilities commonly use natural gas for heating. In these facilities
an undetected gas leak or incomplete combustion could present an explosive hazard or an
influx of carbon monoxide resulting in loss of life, structural damage, or expensive waste of
fuel. Since the boiler is not frequently occupied, leaks often remain undetected. Continuous
gas monitoring and detection system will provide early warning of a gas release and prevent
potentially catastrophic events.
V. REFERENCES
Principle of operation:
Fire and Gas System - instrumentationtools.com
Gas detectors - www.instrumart.com
Fire detector - www.firetrace.com
Types of equipment
Smoke detector - Honewellprocess.com
Three types of flammable Gas detector - instrumentationtools.com
Upper Falmmable Limit - www.archie.org
Catalys Gas Detector - instrumentationtools.com
Infrared Gas Detection - instrumentationtools.com
Open Path Gas Detector - sensidynegasdetection.com
PELS TLVS - gasdetection.com
Electrochemical - sciencedirect.com
Toxic Gas detector- instrumentationtools.com
H2S Detector- sciencedirect.com
Design considerations
https://www.youtube.com/watch?v=A2MGMo0suqM
Fire, Smoke & Gas Detection – 6:20
Heat Detection – 7:13
Smoke Detection – 11:06
Schematic Representation of Ionization Detector – 12:18
Photoelectric – 13:45
Gas Detector – 14.27
Flame Detector – 23:05
Fire Detector – 24:18
Rizal Technological University
College of Engineering, Architecture and Technology
Department of Instrumentation and Control Engineering
Instrumentation Engineering
TOPIC 5:
INSTRUMENT ENCLOSURE/NEMA RATING/ IP RATING
Submitted by:
Submitted to:
Engr. John Yasay
Instructor
I. INSTRUMENT ENCLOSURE
Enclosures are commonly known as „protective housing‟ for a variety of products and
items. According to Oxford Dictionaries, an enclosure is an „artificial or natural barrier that seals
off an area‟ and they are commonly used for electronics product.
Electrical Enclosures are core safety features of a robust electrical system. They have a
two-pronged purpose of not only protecting users from live parts of an electrical system but are
also designed to protect electrical wiring and /or equipment from harsh environments, related to
severe weather conditions or industrial hazards. Today‟s enclosures are built to provide a lifetime
of service when the correct enclosure is used to meet the specific needs for a service or
application (Automation Direct).
Enclosures are designed in a range of shapes and sizes to offer various solutions and
serve various applications. The following enclosure types are the most used enclosures.
10. Flush-Mount Enclosures: this enclosure has an external frame that allows to be
sunken/recessed in wall. Most typically used in applications where external space
is limited or in high traffic area.
II. SELECTION CONSIDERATION
When selecting enclosures, correct size and adequate protection are the priorities. When
considering quality of protection, material type and professional rating systems are the deciding
factors. Additional features such as ventilated sections or insulation may be important depending
on the application.
B. Material Types
The amount of protection and durability an enclosure depends largely on its material
composition. Most electronic and instrument enclosures are made from materials classified as
either metals or polymers.
1. Metals generally exhibit higher conductivity to both heat and electricity than other
material types. Steel is widely used to form enclosures because of its strength and malleability.
Stainless steel is used rather than standard steel in environments requiring corrosion resistance
and lightweight materials. Aluminum is a less expensive, lightweight, and more conductive
metal that exhibits good resistance to oxidation.
2. Polymers are nonmetal materials with varying properties. ABS is a hard, rigid,
inexpensive thermoplastic polymer that has good chemical and creep resistance, but is prone to
cracking under stress. Fiberglass is a strong, durable, reinforced polymer that is resistant to many
caustics and extreme temperatures. Polycarbonate exhibits excellent impact strength and can be
molded to tight tolerances, but has only moderate resistance to chemical corrosion. Polystyrene
is used for its rigidity, hardness, heat, and dimensional stability and because of its ease of
fabrication.
III. NATIONAL ELECTRICAL MANUFACTURERES ASSOCIATION
A. NEMA
B. NEMA RATING
New NEMA ratings are published every fifth year and are used to protect electrical
equipment from damage due to liquids, dust, and/or corrosive chemicals.
It is not mandatory for all electrical components to be designed or built with a NEMA
enclosure. Instead, NEMA ratings are merely used as an industry standard and are completely
voluntary. At PSI Control Solutions, our electrical equipment is custom-built using NEMA
standards.
Nema Enclosures designs and manufactures electrical enclosures in the following NEMA
standards:
NEMA 3, 3X: This enclosures rain-tight, sleep-tight and dust-tight and are made for both indoor
and outdoor. It designates added protection against dust beyond a NEMA 3R or 3RX enclosure.
NEMA 4, 4X: This enclosures are intended for indoor and outdoor
use and provides the same protections as NEMA 3 enclosure with
additional protection against water ingress and/or hose-directed
water. Also, you need not worry about damaging your electrical
components.
NEMA 6, 6P: It has the same protection as NEMA 4 but has a
protection from temporary or prolonged water submersion up to a
designated depth.
NEMA 7: This is built for hazardous locations, explosion proof and made for indoor use
NEMA 8: It offers the same protection as NEMA 7 enclosure and can be used indoor and
outdoor.
NEMA 13: NEMA 13 enclosures are for general purposes and for indoor use. It provides the
same protection as the NEMA 12 enclosures and has added protection against dripping and
sprayed oils and coolants.
The reason for having a universal IP rating system is so that buyers and users can be
confident of how safe it is to use certain electrical or mechanical goods in specific environments
and applications.
Unlike more vague marketing terms such as “waterproof” - which don‟t necessarily give
a clear definition of precisely where and to what extent an item can resist moisture ingress - an IP
rating is designed to provide a far more specific account.
The numbers that follow IP each have a specific meaning. The first indicates the degree
of protection (of people) from moving parts, as well as the protection of enclosed equipment
from foreign bodies. The second defines the protection level that the enclosure enjoys from
various forms of moisture (drips, sprays, submersion etc.)
The first digit indicates the level of protection that the enclosure provides against access
to hazardous parts (e.g., electrical conductors, moving parts) and the ingress of solid foreign
objects.
Protection of the equipment inside the enclosure against harmful ingress of water.
In this section, we‟ll look more closely at some of the more common IP ratings you‟ll find on a
majority of everyday item types.
The ratings widely accepted as „waterproof‟ for most general purposes are IP65, IP66 and
IP67. However, one common misconception regarding weatherproofing is that items intended for
prolonged outdoor use require the highest numerical IP ratings for moisture resistance.
B. IP rated enclosures
There‟s a vast range of different IP-rated enclosure types available across all sectors and
industries, including a great many options for all manner of electronics and mechanical systems
aimed at both home and industrial settings.
Enclosure IP ratings are assigned to everything from mobile phone housings to junction
boxes, bathroom/outdoor lighting setups, and instrument cases intended for robust protection in
harsh marine or chemical environments. In the following sections, we‟ll examine some of the
more widely used enclosure types, and consider some of the demanding IP standards each
enclosure type might require to make it suitable for a range of specific applications.
When looking into the myriad configurations of enclosures and system housings on the
market, you‟ll find that there‟s an equally wide range of IP-rated enclosure accessories and
optional extra fittings available for most types of housing. IP ratings for these types of add-ons
usually mirror those of the enclosures they‟re designed to be used with.
The majority offer various tweaks and specialisations, each designed to make a generic
enclosure more ideally suited to one particular application or another. These are usually focused
around component-specific mounting solutions, attachment methods or additional security
features, aimed at a particular type of application or enclosure contents.
Instrument cases are another widely used housing type, most often found protecting every
day electrical products from damage by dirt, dust or moisture ingress. Typical IP ratings for
instrument cases might start from around IP40, indicating resistance to particulates only (i.e. not
intended for outdoor use), but it‟s also common to see ratings up to IP67+ for full immersion
resistance.
Instrument cases are usually available in both heavy-duty and more lightweight
configurations, depending on the level of protection and portability required. They can be used
for anything from outdoor LED power supply casings to industrial camera housings, desktop
electronics and measuring/control equipment.
E. Electrical IP ratings
As with all other types of enclosures, IP numbers for electrical applications follow the
same universal coding system for clarity and ease of understanding. However, it‟s even more
important with electrical IP ratings to fully consider the potential exposure types and resistance
protection you might need for any electronic components or systems, as ingress from either
particulates or moisture of any kind can often result in damage or increase hazard risk.
REFERENCES
EE News Europe. NEMA Type 9 Enclosures for Electronics in Hazardous Locations .Retrieved
from https://www.eenewseurope.com/news/nema-type-9-enclosures-electronics-
hazardous-locations
Global Specs. Electronic and Instrument Enclosures Selection Guide: Types, Features,
Applications | Engineering360. (n.d.). Engineering360. Retrieved September 30, 2021,
from
https://www.globalspec.com/learnmore/electrical_electronic_components/enclosures/elec
tronic_instrument_enclosures
NEMA Power. ETI offers units that meet NEMA Type 3S Requirement. Retrieved from
https://www.nemapower.com/nema_type_3s.php
OCC Fiber. Enterprise Fiber Optic Enclosures and Adapter Plates. Retrieved from
https://www.occfiber.com/product/nema-3-enclosures/
RSP Supply. (n.d.). Disconnect Enclosures: Free-Standing, NEMA 3R-4X & Stainless Steel or
Fiberglass. Retrieved September 29, 2021, from https://www.rspsupply.com/c-1675-
disconnect-enclosures.aspx
E-Book
Youtube Video
https://www.youtube.com/watch?v=z935clBMJYU
https://www.youtube.com/watch?v=aP0aXuqyiwE