Minutes of meeting held between M/S Laxmi Associates and M/s CG Power & Industrial

Solutions Limited at National Institute of Biological, Sector 62, Noida Uttar Pradesh on dated
02/10/2021.

 TRF Detail: CG make 8 MVA, 33/11 KV Trf, Sr. No. M6058/01, Mfg. Year: 1997.
 Site: National Institute of Biological, Sector 62, Noida, UP.
 Members Present:
FROM CGPISL FROM Laxmi Associates
Mr. Vikrant Sharma (Territory Manager 1. Mr. Shad Khan (Testing Engineer)
North- After Sales Service) 2. Mr. Diwakar Rai (Testing Engineer)

 Minutes:
M/S Laxmi Associates testing team reported at above mentioned site on September 30, 2021
and performed the following tests on above mentioned transformer.
(A) Offline Test:
1. DIRANA Test- Moisture & Di-Electric.
2. Capacitance and Tan Delta Test of windings.
3. Ratio Test at all tap position.
4. Magnetizing Current Measurement Test at all tap position.
5. Magnetic balance Test.
6. IR & PI test.
7. Short circuit current and Impedance Measurement Test.
8. Winding resistance test (all taps).
9. SFRA Test.
10. DCRM Test of OLTC.

(B) Functional Test of protection Equipments:


1. OTI and WTI alarm and trip test.
2. Buchholz relay alarm and trip test.
3. OLTC OSR relay and PRD trip test.

 Note:
1. Insulation paper sample collected from inside of transformer main tank for Degree of
Polymerization test
2. Oil sample collected of Main tank for oil testing as mentioned in PO.
3. Online tests and Electrical Protection Relays (O/C, E/F differential, REF for Trip & Alarm
etc.) testing are pending.
All above work completed by team and left the site on 02-10-2021.

For M/S Laxmi Associates For M/S CGPISL

You might also like