Flexible Power

Transfer Solutions for


Commercial & Industrial
Applications

ASCO SERIES 300


Power Transfer Switches

ascopower.com
ASCO SERIES 300 SERIES 300 Automatic Transfer Switches
Automatic Transfer Switches Designed to Fit Anywhere

The ASCO SERIES 300 product line provides the most compact design of generator power transfer
switches in the industry. Power
Power outages impact small and large facilities alike. ASCO SERIES 300 Knowledge
Automatic Transfer Switches offer rugged design and reliable performance to
Product Available to mount on walls or floors, all models through 2000 amperes are designed to be completely

small and mid-size commercial and industrial facilities in packaged solutions


Details front-accessible. This permits installation flush against walls while allowing installation of cabling and Basic Automatic
connections from the front of the switch. Cable entrance plates are standard on 1600 and 2000 amperes Transfer Switch
that are easy to select, procure, install, and operate. Transfer Switch units; these allow use of optional side-mounted pull boxes for additional cable bending space. Functions
Overview
• 30 through 3000 amperes in compact designs • Optional Relay Expansion Module with extra
Every SERIES 300 generator transfer switch is engineered with ASCO's reliability expertise in a relays for accessory outputs
• Up to 600 VAC, single or three phase
package that makes backup power accessible for small and mid-size facilities. Leveraging knowledge • Soft keys for test function and time delay
• Listed to UL 1008 - Standard for Safety -
derived from a century of critical power transfer experience, each SERIES 300 is backed by the same bypass
Transfer Switch Equipment
ASCO technical support and service that solves the most demanding critical power challenges facing
• Emergency source failure alert indication
facilities today. • True double-throw operation: The single
solenoid design is inherently interlocked to • Optional Historical Event Log
prevent simultaneous connections of two
• Displays statistical ATS monitoring information
power sources.
• Built-in diagnostic functions
• Will not transfer to a dead source - single
solenoid operator derives power from the • Password protection to prevent unauthorized
destination source actions

• Easy-to-navigate 128x64 graphical LCD • Adjustable delay feature prevents nuisance


display with keypad provides LED indicators transfer due to momentary utility power
for switch position, source availability, not-in- outages and generator dips
auto mode, and alert conditions. • Auxiliary contacts signal position of main
• Integrated, multilingual, user interface for contacts - two for normal and two for
configuration and monitoring emergency position

• Available Delayed Transition operation • Standard solid neutral terminals

• Non-automatic operation can be selected • Restriction of Hazardous Substances (RoHS)


without opening enclosure door compliant controller
• Standard 2 year warranty. Optional 1, 2, and 3
year extensions

ASCO's SERIES 300 lineup offers


flexible backup power solutions for
businesses of every size. SERIES 300 Power
Transfer Switch
rated 200 amps

2 3
SERIES 300 Automatic Switching Solutions Open Transition Transfer Switching
Power
ASCO Transfer Switches are available with a standard, 2-position, open transition models that Knowledge
reliably transfer loads in less than 100 milliseconds. Open transition switches are suitable for a
Automatic and Non-Automatic Transfer Switching wide range of applications.
Power Transition Mode
Basics
ASCO Transfer Switches are available in both automatic and non-automatic types. Both are Knowledge • 30 to 3000 amps Tens of Seconds
electrically operated. For automatic transfer switches, the controller initiates transfer between Milliseconds to Minutes
• S
 ingle-operator switching mechanism Transferring
power sources . For non-automatic transfer switches, a user initiates transfer using local or Non-Automatic Motor Loads

VOLTAGE

VOLTAGE
remote controls. prevents simultaneous connection of
and Manual Emergency Normal Emergency
between
Normal
both sources
Transfer Switches Power Sources
SERIES 300 non-automatic transfer switches offer the following features: for Backup Power • Available In-Phase Monitor can be
TIME TIME

• Models range from 30 through 3000 • Source acceptability lights inform operator Applications activated for transferring motor loads
Open Transition Transferring
amperes, up to 600V when sources are available to accept load Loads with Zero
• Controller prevents inadvertent operation • Standard in-phase monitor for transferring Power Interruption
under low voltage conditions motor loads betweem live sources
Delayed Transition Transfer Switching

ASCO Delayed Transition Transfer Switches transfer loads between power sources using a timed
load disconnect position with an adjustable delay.

• 150 through 3000 amps


• R
 eliable, field-proven, dual-solenoid Tens of
Milliseconds
Seconds
to Minutes
<100
Milliseconds
operating mechanism

VOLTAGE

VOLTAGE

VOLTAGE
• Mechanical interlocks to prevent simultaneous
Emergency Normal Emergency Normal Emergency Normal
connection of both power sources
• Adjustable delay for load disconnect
TIME - TIME TIME

0 to 5 minutes
Delayed Transition
• Non-automatic models available in manual
operation configuration
• Automatic models available with load shed
feature

SERIES 300 Group G Controller


The SERIES 300 Group G Controller is reliable and field-proven. It provides all of the voltage,
frequency, control, timing, and diagnostic functions required for most emergency and standby Product
power applications. Details
Group G Controller

• Touch pad programming


• Displays active timers
• On-board diagnostics
400 Amp, Type 1 • Password protection
Enclosure
• Voltage and frequency sensing
• Status and control functions

4 5
Transfer Switch Communications and Metering
Options to Customize Functionality and Increase Value

Remote Annunciation Metering


Product Product
Monitor Power Equipment Status
Details from Anywhere
Transfer Switches are the Perfect Place to Details
Monitor Power Flow, Power Conditions,
5300 SERIES and Power Events 5210 Power Meter
Monitoring and control transfer switches from
Annunciators across the room, building, or from Internet. 5210 Power Meter – Provides deeper insight into
5310 – LED annunciator – Single ATS circuit status and conditions.

5350 – LED annunciator – up to 8 ATSs

Communication
Product
Turn Transfer Switches into Power
Details Information Portals

5140 Connectivity 5140 Connectivity Module – Makes status and


Module power information from a single switch available
to via ModBUS, SNMP, and web pages.

6 7
SERIES 300 Optional Accessories Withstand and Closing Ratings
Communications
11BE Feature Bundle. Programmable engine exerciser with seven independenct routines run the generator with or without loads,
on a daily, weekly, bi-weekly, or monthly basis. Controlled from the user interface keypad. FRAME
RATINGS
480V
CURRENT LIMITING FUSES

600V MAX. SIZE,


SPECIFIC BREAKER

240V 480V 600V


Power
AMPERES
• Event log display shows the event number, time and date, type and reason (if applicable). MAX. MAX. AMPS
CLASS
MAX. MAX. MAX. Knowledge
• Stores up to 300 events 100kA - 300 J
• RS485 Communication Port enabled common alarm output contact
• On three-phase systems, Accessory 11BE enables line-to-line voltage imbalance sensing and three-phase sensing
30 35kA 200kA 200 J 22kA 22kA 10kA UL 1008 Transfer
capabilities for the Emergency power source as well as the Phase Rotation checking for both power sources.
200kA 35kA 200 RK1
Switch Withstand
35kA 35kA 200 RK1
18RX Relay Expansion Module provides accessory relays and includes one Form C contact for normal source availability (18G), 70-100 150kA 85kA 25kA and Closing
D 200kA 35kA 200 J
and one Form C contact for emergency source availability (18B) (contact rating 5 amperes @ 30 VDC or @ 125 VAC Ratings
35kA 35kA 200 RK1
resistive) (100 ma, 4 VDC min) Additional output relay is provided the default is to indicate a common alarm. 150 150kA 85kA 25kA
200kA 35kA 200 J
72EE2 Connectivity module provides remote monitoring and control capabilities and includes accessory 11BE feature bundle Performance
200 200kA - 200 J 200kA 85kA 14kA
Environment and Power Testing for
230 100kA - 300 J 200kA 85kA 14kA
44A Strip heater with thermostat for cold environment to prevent internal condensation and icing. External 120-volt AC power Transfer Switches
E 260, 400 200kA - 600 J 65kA 42kA 35kA
source required.
600 J
44G Strip heater with thermostat, wired to load terminals on 208-240, 360-380, 460-480, 550-600 volt models. Contains wiring 150, 200, 260 200kA 200kA 200kA 200kA 42kA
800 L
harnesses for all transfer switch sizes.
600 J
1UP UPS back up power runs controller and LCD display for 30 seconds without AC power J 400 200kA 200kA 65kA 50kA 42kA
800 L
Extension Harness
600 J
600 200kA 200kA 65kA 85kA 42kA
37B Six-foot extension harness for open type units to accommodate customer mounting of controls and switch 800 L
37C Nine-foot extension harness for open type units to accommodate customer mounting of controls and switch H 800-1200* 200kA 200kA 1200 L 65kA 150kA 65kA
Indicators
1600-2000 200kA 200kA 2500 L 85kA 85kA 85kA
62W Audible alarm with silencing feature to signal transfers to emergency. (For D-frame models, may require oversize enclosure
depending on accessory combination). G 2600-3000 200kA 200kA 4000 L 100kA 100kA 100kA

Customer Control Circuits 4000 200kA 200kA 5000 L 100kA 100kA 100kA

30A Load-shed circuit initiated by opening of a customer-supplied contact (Open Transition model only)
Notes:
30B Load-shed circuit initiated by removal of customer-supplied control voltage (Open Transition model only)
* Front connection only
30AA Load-shed circuit initiated by opening of a customer-supplied contact (Delayed Transition model only)
30BA Load-shed circuit initiated by removal of customer-supplied control voltage (Delayed Transition model only) All units are RMS Symmetrical Amperes

Surge Protection All Withstand and Closing Rating values are tested in accordance with UL 1008.
See ASCO Publication 1128 for more information.
73 Surge suppressor rated 65 kA Application requirements may permit higher WCR for certain switch sizes.
Metering
23GA, Load Current Metering card measures either single or three-phase load current. Not available with Power Meter option
23GB 135L. Use 23GA for Single-Phase, 23GB for Three-Phase.
135L Power Meter on load side (includes shorting block and current transformers). Not available with Load Current Metering
options 23GA or 23GB.

Field Conversion Kits


Kit No. Description
Additional SERIES 300 Product Information
935147 Advanced Function Bundle Retrofit Kit (11BE) - See above accessory 11BE description for details.
935148 REX Module with Source Availability Contacts (Acc. 18RX) Transfer Switches and Panels Controls Technical Information
935149 UPS to allow controller to run for 30 seconds minimum without AC Power (Acc. 1UP)
Manual Transfer Switch Group G Controller Withstand and Closing Ratings
935150 1/3 Phase load current sensing card only (Acc. 23GA/GB)
K613127-001 Strip Heater (125 watt) 120 volt (Acc. 44A) Manual Transfer Switch with Quick Connects Weights and Dimensions and Ordering Info

K613127-002 Strip Heater (125 watt) 208-480 volt (Acc. 44G) Quick Connect Power Panel Drawings
948551 Quad-Ethernet Module (Acc. 72EE) Dual Purpose Quick Connect Power Panel Wiring Diagrams
K609027 Cable Pull Box (1600-2000 amperes)

8 9
SERIES 300 Manual Transfer Switching and
Quick Connection Solutions
ASCO SERIES 300 Manual Transfer Switching and Quick Connection Solutions offer reliable
service and application flexibility for a wide range of facilities. Power Power
Knowledge Knowledge
Manual Transfer Switches Quick Connect Panels
Differences NEC Requirement
• Three-position, easy-to-use center-off • Listed to UL 1008 Transfer Switch
Between Manual, for Permanent
switch Accessory standard
Non-Automatic, & Manual Switching
• Compact design - easy to install and Automatic Transfer • Utilizes standard Cam-Lok™ receptacles Means
maintain Switches for quick connections
• Designed to handle demands of motors • Standard Type 3R construction is
and inrush currents weatherproof with or without cable
Product • Utilizes standard Series 16 Single Pole Product
Details quick connect receptacles
Details
SERIES 300 SERIES 300
Manual Transfer Quick Connect
Switch Power Panel

Manual Transfer Switches with Quick Connects Dual-Purpose Manual Transfer Switches with Quick Connects
• The ASCO SERIES 300 Manual Transfer • Provides both supplemental backup
Switch with Integrated Quick Connects Product power and load testing connectivity Product
provides a total temporary power Details through a single device. Details
connection and transfer solution • Listed to UL 891 by ETL
• Enables connection and control of a SERIES 300 SERIES 300 Dual
• Utilizes standard Series 16 Single Pole
temporary or portable generator Manual Transfer Purpose Quick
quick connect receptacles
Switch with Quick Connect Power
• Provides a complete UL 1008-listed
Connects Panel
solution in a single unit

10 11
ASCO Power Technologies - Global Headquarters
160 Park Avenue www.ascopower.com
Florham Park, NJ 07932 customercare@ascopower.com
Tel: 800 800 ASCO

© 2021 ASCO Power Technologies. All Rights Reserved. Life Is On Schneider Electric is a trademark and the property of Schneider Electric SE, its subsidiaries and affiliated companies.
Publication 1195 R4. Printed in the U.S.A.
ASCO Series 300 Group G Controller
Standard Operational Features, Controls and Status Indicators

Standard Selectable Features

• Inphase monitor to transfer motor loads, without any intentional off time, to
prevent inrush currents from exceeding normal starting levels.
• Engine Exerciser to automatically test backup generator each week-with or
without load 20 minutes not adjustable.
• Commit to transfer
• Selective load disconnect control contacts (two provided) which operate with time
delay prior to and/or after load transfer and re-transfer.
• 60Hz or 50Hz selectable switch.
• Three – phase/single – phase selectable switch.

124* 64 Graphical LCD Display/LED Indicators

• Switch position green LED for normal


• Switch position red LED for emergency
• Source availability green LED for normal
• Source availability red LED for emergency
• “Not in Auto” amber LED
• Common Alarm amber LED
• Soft key for transfer test function
• Soft key for time delay bypass
• Set Engine Exerciser
• Selection of non – automatic operation
• Scroll, Up/Down Arrows
• Escape key
• Enter key

Voltage & Frequency Sensing

• Three phase under and over voltage sensing on normal, and single phase on
emergency
• True RMS voltage sensing with +/- 1% accuracy
• Selective settings: single or three phase voltage sensing on normal and single
phase sensing on emergency; 50 or 60Hz
• Frequency sensing accuracy is +/- 0.1Hz
• Under and over frequency settings on normal and emergency
• Voltage and frequency parameters adjustable in 1% increments
• Normal source pickup voltage adjustment range is 85 – 100%; drop - out voltage
adjustment range is 70 – 98% in 1% increments
• Emergency source pickup voltage adjustment range is 85 – 100%; drop - out
voltage adjustment range is 70 – 98% in 1% increments
• Normal source pickup frequency adjustment range is 86 – 100%; drop – out
adjustment range is 85 – 98% in 1% increments
• Emergency source pickup frequency adjustment range is 86 – 100%; drop – out
adjustment range is 85 – 98% in 1% increments
• Over voltage and over frequency reset is fixed at 2% below the trip setting

Time Delays

• Engine start time delay – delays engine starting signal to override momentary
normal source outages – adjustable 0 to 6 seconds (Feature 1C)
• Transfer to emergency time delay – adjustable 0 – 60 minutes (Feature 2B)
• Emergency source stabilization time delay to ignore momentary transients during
initial generator set loading – adjustable 0 to 4 seconds (Feature 1F)
• Re-transfer to normal time delay – adjustable 0 to 10 hours (Feature 3A)
• Unloaded running time delay for engine cooldown – adjustable 0 to 60 minutes
(Feature 2E)
• Pre and post signal time delay for selective load disconnect with a programmable
bypass on source failures – adjustable 0 to 5 minutes (Optional feature 31Z)
• Fully programmable engine exerciser seven independent routines to exercise the
engine generator, with or without loads, on a daily, weekly. Bi weekly or monthy
basis (Optional feature bundle 11BE)
• Delayed transition load disconnect time delay – adjustable 0 to 5 minutes

Standard Control Contacts

• Switch position indicating contacts (rated 10 amps 250VAC, 32VDC) (1) for
normal position (1) for emergency position

Remote Control Features – external inputs for connecting:

• Remote test switch


• Remote contact for test or for peak shaving applications. If emergency source
fails, switch will automatically transfer back to normal source if acceptable
• Inhibit transfer to emergency
• Remote time delay bypass switch emergency to normal
Electromagnetic Compliance Testing (EMC)

• IEC 61000 – 4 – 2 Electrostatic Discharge Immunity


• IEC 61000 – 4 – 3 Radiated RF Field Immunity
• IEC 61000 – 4 – 4 Electrical Fast Transient/Burst Immunity
• IEC 61000 – 4 – 5 Surge Immunity
• IEC 61000 – 4 – 6 Conducted RF Immunity
• CISPR 11 – Conducted RF Emissions and Radiated RF Emissions
• FCC CFR 47 Part 15

Additional Design Criteria

• NEMA ICS-109.21 Impulse Withstand Test


• Digital circuitry isolated from line voltages
• Isolated RS – 485 Serial Communications Port (Accessory 11BE Bundle)
• Connectivity Module for remote monitoring and control (Accessory 72EE)
Limited Warranty

Series 150, 200, 300 and 4000 SERIES


Power Transfer Switches
This Warranty is given ONLY to purchasers who buy for commercial or
industrial use in the ordinary course of each purchaser's business.

General:
ASCO Power Technologies, LP products and systems are in our opinion the finest available. We
take pride in our products and are pleased you have chosen them. Under certain circumstances
we offer with our products the following Twenty Four Month Limited Warranty Against
Defects in Material and Workmanship.

Please read your Warranty carefully. This Warranty sets forth our responsibilities in the unlikely
event of defect and tells you how to obtain performance under this Warranty.
TWENTY FOUR MONTH LIMITED WARRANTY AGAINST DEFECTS IN MATERIAL AND WORKMANSHIP ASCO PRODUCTS COVERED:

Series Product Description Catalog Codes


150, 200 1ATS, 2ATS
Standard Transfer Switches
3ATS, 3ADTS, 3NTS, 3NDTS
Manual Transfer Switches 3MTS, 3MTQ
Service Entrance Transfer Switches 3AUS, 3ADUS, 3APS, 3ARS,
300 (SEATS) 3MUS, 3MUQ, 3AGS

Power Transfer Load Centers (PTLC) 300L

Quick Connect Panels 3QC


4ATS, 4ADTS, 4ACTS, 4NTS,
Standard Transfer Switch
4NDTS, 4NCTS
4000
Electrically Operated Bypass-Isolation
4ATE, 4ADTE, 4NTE, 4NDTE
Transfer Switches

LIMITED WARRANTY:
ASCO warrants that the ATS will be free from defects in material and workmanship and
will conform to ASCO’s standard specifications for the ATS for a period of twenty four (24)
months from date of product shipment from ASCO (the “Warranty Period”). This Limited
Warranty does not extend to subsequent owners of the structure during the Warranty Period.

Terms of Warranty:
The foregoing Limited Warranty is conditioned upon User’s compliance with the following:

For sales or service 1-800-800-2726 (ASCO) 381339-331


1. The ASCO Power Transfer Switch is installed in accordance with ASCO specifications
and state and local codes and standards by an electrician licensed in the state of
installation.

2. The ASCO Power Transfer Switch is maintained in accordance with ASCO instructions
and used under normal conditions for the purposes intended by ASCO.

All warranty field-related repairs, replacements or adjustments must be


made by ASCO Power Services Inc. or its duly authorized representative.
Optional Available Extended Warranty
Optional extended warranty coverage may be purchased from ASCO for a specified fee at the
time of the original sale. If purchased, warranty period shall be extended up to an additional
thirty - six (36) months beyond the standard twenty - four (24) months to provide up to five (5)
year coverage applicable to the above referenced products, except for 3AUS, 3APS, 3AGS, and
3ARS products where the warranty period for the circuit breaker shall be limited to 24 months
from date of shipment from ASCO. The length of optional extended coverage shall be reflected
on the ASCO invoice and/or order acknowledgement document.

Warranty Extends to First Purchaser for Use, Non-transferable:


This Warranty is extended to the first person, firm, association or corporation for whom the
ASCO product specified herein is originally installed for use (the "User") in the fifty United
States or Canada. This Warranty is not transferable or assignable without the prior written
permission of ASCO.

Assignment of Warranties:

ASCO assigns to User any warranties which are made by manufacturers and suppliers of
components of, or accessories to, the ASCO product and which are assignable, but ASCO
makes NO REPRESENTATIONS as to the effectiveness or extent of such warranties, assumes
NO RESPONSIBILITY for any matters which may be warranted by such manufacturers or
suppliers and extends no coverage under this Warranty to such components or accessories.

Drawings, Descriptions:
ASCO warrants for the period and on the terms of the Warranty set forth herein that the
ASCO product will conform to the descriptions contained in the certified drawings, if any,
applicable thereto, to ASCO's final invoices, and to applicable ASCO product brochures and
manuals current as of the date of product shipment (“Descriptions”). ASCO does not control the
use of any ASCO product. Accordingly, it is understood that the Descriptions are NOT
WARRANTIES OF PERFORMANCE and NOT WARRANTIES OF FITNESS FOR A
PARTICULAR PURPOSE.

Warranty Claims Procedure:


Within a reasonable time, but in no case to exceed thirty (30) days, after User's discovery
of a defect, User shall contact ascopowerwarranty@ascopower.com. Subject to the
limitations specified herein, an ASCO Power Services field service representative will repair
For sales or service 1-800-800-2726 (ASCO) 381339-331
the non-conforming ASCO product warranted hereunder, without charge for parts, labor, or
travel expenses. Warranty coverage will apply only after ASCO's inspection discloses the
claimed defect and shows no signs of treatment or use that would void the coverage of this
Warranty . All defective products and component parts replaced under this warranty become the
property of ASCO.

Warranty Performance of Component Manufacturers:


It is ASCO's practice, consistent with its desire to remedy Warranty defects in the most prompt
and effective manner possible, to cooperate with and utilize the services of component
manufacturers and their authorized representatives in the performance of work to correct defects
in the product components. Accordingly, ASCO may utilize third parties in the performance of
Warranty work, including repair or replacement hereunder, where, in ASCO's opinion, such
work can be performed in less time, with less expense, or in closer proximity to the ASCO
product.

Items Not Covered By Warranty:


THIS WARRANTY DOES NOT COVER DAMAGE OR DEFECT CAUSED BY misuse,
improper application, wrong or inadequate electrical current or connection, negligence,
inappropriate on site operating conditions, repair by non-ASCO designated personnel, accident
in transit, tampering, alterations, a change in location or operating use, exposure to the elements,
water, or other corrosive liquids or gases, Acts of God, theft or installation contrary to ASCO's
recommendations or specifications, or in any event if the ASCO serial number has been altered,
defaced, or removed.

THIS WARRANTY DOES NOT COVER shipping costs, installation costs, external circuit
breaker resetting or maintenance or service items and further, except as may be provided
herein, does NOT include labor costs or transportation charges arising from the replacement of
the ASCO product or any part thereof or charges to remove or reinstall same at any premises of
User.
REPAIR OR REPLACEMENT OF A DEFECTIVE PRODUCT OR PART THEREOF DOES
NOT EXTEND THE ORIGINAL WARRANTY PERIOD.
THE PRODUCTS LISTED IN THIS WARRANTY ARE NOT FOR USE IN THE
CONTROL AREA OR ANY REACTOR CONNECTED OR SAFETY APPLICATIONS OR
WITHIN THE CONTAINMENT AREA OF A NUCLEAR FACILITY OR FOR
INTEGRATION INTO MEDICAL DEVICES.

Limitations:
THIS WARRANTY IS IN LIEU OF AND EXCLUDES ALL OTHER WARRANTIES,
EXPRESS OR IMPLIED, INCLUDING MERCHANTABILITY AND FITNESS FOR A
PARTICULAR PURPOSE.
USER'S SOLE AND EXCLUSIVE REMEDY IS REPAIR OR REPLACEMENT OF THE ASCO
PRODUCT AS SET FORTH HEREIN.

IF USER'S REMEDY IS DEEMED TO FAIL OF ITS ESSENTIAL PURPOSE BY A


COURT OF COMPETENT JURISDICTION, ASCO'S RESPONSIBILITY FOR PROPERTY
LOSS OR DAMAGE SHALL NOT EXCEED THE NET PRODUCT PURCHASE PRICE.

For sales or service 1-800-800-2726 (ASCO) 381339-331


IN NO EVENT SHALL ASCO ASSUME ANY LIABILITY FOR INDIRECT, SPECIAL,
INCIDENTAL, CONSEQUENTIAL OR EXEMPLARY DAMAGES OF ANY KIND
WHATSOEVER, INCLUDING WITHOUT LIMITATION LOST PROFITS, BUSINESS
INTERRUPTION OR LOSS OF DATA, WHETHER ANY CLAIM IS BASED UPON
THEORIES OF CONTRACT, NEGLIGENCE, STRICT LIABILITY, TORT, OR
OTHERWISE.

Miscellaneous:
NO SALESPERSON, EMPLOYEE OR AGENT OF ASCO IS AUTHORIZED TO ADD TO
OR VARY THE TERMS OF THIS
WARRANTY. Warranty terms may be modified, if at all, only in writing signed by an ASCO
officer.

ASCO obligations under this Warranty are conditioned upon ASCO timely receipt of full
payment of the product purchase price and any other amounts due. ASCO reserves the right to
supplement or change the terms of this Warranty in any subsequent warranty offering to User or
others.
In the event that any provision of this Warranty should be or becomes invalid and/or
unenforceable during the warranty period, the remaining terms and provisions shall continue in
full force and effect.

This Warranty shall be governed by, and construed under, the laws of the State of New Jersey,
without reference to the conflict of laws principles thereof.

This Warranty represents the entire agreement between ASCO and User with respect to the
subject matter herein and supersedes all prior or contemporaneous oral or written
communications, representations, understandings or agreements relating to this subject.

For sales or service 1-800-800-2726 (ASCO) 381339-331


ASCO Power Technologies

Engineering Application Information

WITHSTAND AND CLOSING RATINGS


FOR
TRANSFER SWITCH EQUIPMENT

ASCO products comply with all mandatory UL 1008 withstand


and closing ratings.

By using the information in this publication and calculating


available short circuit currents, the system designer can be assured
the transfer switches will be properly rated for the electrical system.

Internal
Introduction
This publication provides information on withstand and closing ratings (WCRs) for ASCO transfer switches and
related products, including compliance with the optional short time ratings and other revisions to UL 1008. Also
included are guidelines for special WCR applications and typical methods for specifying WCR requirements.

Guidelines for using the information in this publication


to verify suitability of switches for specific applications
based on withstand and closing ratings (WCR).

1. Determine the prospective fault current available (from each source) at the
location of the switch.
2. Determine the overcurrent protective devices (OPDs) that will be located ahead
of the switch.
3. If the OPD is a circuit breaker, refer to the “Time Based” rating column on
Table II of page 4. Select the switch rating necessary to handle the full load
current. Compare the fault current available at the switch source terminals to the
WCR shown in Table II for the applicable switch ampere size and voltage. If the
prospective fault current is equal to or less than the Time Based WCR from
Table II, the switch selected is suitable for the application.
4. If the prospective fault current is greater than the Time Based WCR obtained
from Table II, refer to the “Specific Breaker” list on Table III on pages 5-7.
Compare the fault current to the WCR shown in Table II. If the fault current is
equal to or less than the WCR shown in Table II, the switch is suitable for the
application when protected by any of the circuit breakers shown. If the specific
circuit breaker being used is not shown in the table, contact ASCO Power
Technologies.
5. If the prospective fault current is greater than the WCR listed in Table III, refer
to Special Application Considerations on page 8.
6. When the overcurrent protective devices are fuses refer to the “Current Limiting
Fuses” column of Table II on page 4. If there are any questions about the
suitability of the switch when protected by current limiting fuses contact ASCO
Power Technologies.

Internal
The Importance of Proper Ratings Consider a fault at point B on the load side of the
breaker feeding L1 as shown in Figure 1. If the system
The transfer switch is a unique and critical part of the breakers have been coordinated properly, the breaker
power system. It is the last distribution device feeding feeding L1 will trip before the upstream breaker or fuse.
the critical loads of a facility. For that reason, the The transfer switch must withstand this fault current
transfer switch should be located as close as possible to until the circuit breaker or fuse clears the fault. Most
the protected loads. In addition, after a fault (short automatic transfer switches available today have a
circuit) is cleared, the transfer switch must remain standard control circuit time delay of 0.5 seconds or
operable so that it can restore power to the critical loads more to override any momentary voltage transients.
from the alternate power source. This is ample time for any over current device to clear
In the design of an electrical power distribution system, the fault, allowing system voltage to return to normal
a coordination study should be conducted during the and avoiding any unnecessary operation of the transfer
design stage to determine the trip settings required for switch.
all circuit breakers. Proper trip settings will assure that a Now consider a fault at point A of Figure 1. The circuit
fault is cleared as close to its location as practical. The breakers on the load side of the transfer switch would
coordination study considers conductor sizes, quantities not see the fault current, but the upstream breaker (F2)
and lengths as well as any other relevant circuit would and the instantaneous trip element would be
impedance. The farther from the source a device is actuated. The transfer switch controller senses there is
located, the lower the fault current will be at that device. no voltage from the utility, signals a transfer operation
Referring to Figure 1, a fault at point A should be and the transfer switch is now required to close on the
cleared by the switchgear feeder breaker F2 and not by fault condition until the generator over current device
M. This would leave the other feeder circuits (F1 & F3 - clears the fault.
F7) in operation. A coordination study will determine the
magnitude of fault current at the load side of the transfer If a transfer switch does not have a sufficient withstand
switch and indicate the settings for F2. and closing rating, severe damage and a potential fire
hazard could result from the fault current. Over-rating
the transfer switch to achieve a sufficient WCR leads to
a less cost-effective design. Good engineering practice
requires adequately rated devices in the power
Utility Service distribution system. Therefore, the specified WCR for
Z = 5.75% the transfer switch should be equal to or greater than the
available fault current at the location of the transfer
M switch. Some recommended engineering practices to
assist in fault current calculations are referenced at the
end of this publication.
F1 F2 F3 F4 F5 F6 F7
How Codes Impact Ratings
Emergency Codes often require equipment to be approved for its
Generator intended use. For example, one of the most common
applications for automatic transfer switches is in
Emergency Systems per Article 700 of the National
Electrical Code (NEC) ANSI/NFPA 70. Section 700-3
Automatic and 700-6 require that all transfer equipment be
Transfer approved for use on Emergency Systems. How does a
Switch manufacturer obtain approval? There are several ways,
but perhaps the most common is via a third party
Fault A certification acceptable to the authority having
jurisdiction.

L1 L2 L3 L4
The Role of Underwriters Laboratories
Fault B Underwriters Laboratories (UL) is one of several
independent testing agencies and is perhaps the most
Critical loads well-known third party certifier. The Standard for Safety
Figure 1. Line diagram of a typical under which Underwriters Laboratories tests Transfer
emergency power system. Switch Equipment is UL 1008. Equipment which meets
UL requirements is listed in UL’s Electrical Construc-
1
tion Materials List. This list is frequently used by was the same as the short circuit testing in the standard,
electrical inspectors and other authorities having except the test sample was required to pass a
jurisdiction in conjunction with the device markings and temperature rise test at the conclusion of this new short
rating label to approve an electrical installation. time test. This meant the transfer switch main contacts
had to be virtually “like new” in order to minimize the
UL has issued several revisions to the UL 1008
increase in contact resistance in order to meet the
Standard, which clarify how a transfer switch is to be
temperature rise limits.
tested and marked for fault current withstand and
closing ratings. A major revision introduced in the 1989 The time duration of the short time test was up to the
version of UL 1008 allowed an optional rating category discretion of the manufacturer and could range from 0.1
for WCR and closing tests. Its purpose was to permit to 0.5 seconds. The amount of energy a transfer switch
transfer switch manufacturers to conduct tests without can withstand and close on is based on an I2T function,
overcurrent protective devices. For transfer switches which is a measurement of the energy handled by the
rated 400A and below for use on 10 kA circuit switch. Since the switch has to handle more energy with
maximum, the on time of the fault current must be at the longer time duration and also pass a temperature rise
least 25 ms (1½ cycles). For transfer switches rated test following this event, the short time ratings will be
above 400A or for use on circuits with available fault lower for an identical test sample compared to the short
currents above 10 kA, the on time of the fault current circuit ratings obtained for the requirements in UL1008
must be at least 50 ms (3 cycles). When this test is prior to 2002.
successful, the manufacturer may mark the switch for
use with any manufacturer’s circuit breaker within its
rating. Such umbrella ratings give the application The 7th Edition of UL 1008 became effective November
engineer more flexibility when specifying and 1, 2014 and resulted in significant changes to the short-
coordinating the transfer switch with overcurrent circuit ratings shown on all transfer switch products in
devices. the industry. First, the "Any" circuit breaker rating
Where a transfer switch manufacturer does not opt for added in 1989 was replaced with a “time based” rating
this test, the switch can only be marked to show the and marking shown in seconds rather than
specific manufacturer’s circuit breaker with which the cycles. Generally, these are time durations of 0.025 Sec
switch was tested, or circuit breakers approved by UL for short-circuit currents up to 10 kA on switch ratings
through extension from the original test data. The specific of 400 amp or less and 0.050 Sec for most other short-
breaker marking can limit the product’s application and circuit levels.
acceptance by the inspecting authority.
The most significant change is the way that specific
Other issues may develop when the transfer switch circuit breakers are permitted to be added to the label
WCR is limited to use with specific circuit breakers. markings. Specific circuit breakers must be short circuit
Even though a specific breaker is coordinated with the tested with the transfer switch per UL1008 requirements
transfer switch upon initial installation, the breaker or can be added based on comparing circuit breaker
could possibly be replaced at a later date with another maximum instantaneous clearing times to the actual time
type and/or rating which is not one of the breakers durations of short-circuit tests conducted on the transfer
approved by UL. Circuit breakers also change trip switch. UL has made this change to ensure all
characteristics as they age and the tripping time may be manufacturers utilize the criteria described in the 7th
become slower, allowing the transfer switch to be edition of UL1008 to qualify circuit breakers for use
subjected to energy above the original short circuit with transfer switches during short circuit testing of their
testing values. These issues would not be a concern to products.
the specifying engineer if a transfer switch rated for use
with “Time Based” were selected. Unfortunately, this limits the listed population of circuit
breakers on the WCR labels of many manufacturers’
Another significant change regarding short circuit switches and especially on smaller frame transfer
testing was made to UL1008 in June of 2002. Since the switches, because of the manner in which UL previously
requirement for selective coordination was added to evaluated adding circuit breakers to manufacturer’s
articles 700, 701 and 708 of the NEC, UL recognized markings. In the past, the listing of specific breakers
there would be situations where transfer switches would was based on a comparison of the “published”
be required to withstand and close on short circuit maximum instantaneous clearing time of the breaker
currents for time durations of 0.1 seconds (6 cycles for tested to non-tested circuit breakers maximum
60Hz systems). Consequently, UL added requirements instantaneous clearing times.
for a new optional short circuit test called “Short Time
Current Rating Test”. The criteria for a successful test

2
The format and appearance of the WCR label was also the electrical consultant when specifying these products.
changed significantly with the addition of more The ratings apply to the ASCO products shown in Table
descriptive statements regarding how the ratings should I and are specified in Tables II and III. The ratings apply
to single phase and three phase switches. The withstand
be applied in selecting appropriate over-current
& closing ratings of the overlapping neutral transfer pole
protection. An example of these labels is shown on page is identical to the WCR of the phase switching poles.
8.
See page 8, Special Application Considerations, if
ratings beyond those listed are required. Contact ASCO
ASCO Switches Meet and Exceed UL Power Technologies to determine if ratings have been
1008 Requirements increased or for ratings beyond three cycles which may
not be UL Listed, but which are based on other tests.
ASCO Power Technologies provides withstand current
ratings on its products to provide maximum flexibility to

Table I. Applicable Products (Refer to Specific Rating Tables for Each Products Rating)

ASCO Typical Product Description


Product Applications Automatic Transfer Switch Non-Automatic Transfer Switch
Series
Residential Automatic Manual
165, 185
Series 300 / Industrial / Light Automatic Transfer Switch Non-Automatic – Electrically Operated Transfer
386 Commercial (Light Commercial Applications) Switch
4000 TS 4NTS – Non-Automatic Transfer Switch
4000 Series Industrial, 4ATS – Automatic Transfer Switch
4NCTS – Non-Automatic Closed Transition Switch
Power Commercial, 4ACTS – Automatic Closed Transition Switch
4NDTS – Non-Automatic Delayed Transition
Transfer Institutional 4ADTS – Automatic Delayed Transition Switch
Switch
Switches
7000 TS 7NTS – Non-Automatic Transfer Switch
7ATS – Automatic Transfer Switch
7000 Series Health Care, 7NCTS – Non-Automatic Closed Transition Switch
7ACTS – Automatic Closed Transition Switch
Power Critical Power 7NDTS – Non-Automatic Delayed Transition
7ADTS – Automatic Delayed Transition Switch
Transfer Facilities Switch
7ASLS – Automatic Soft Load Transfer Switch
Switches 7MTS – Manually Operated Transfer Switch
7ATB – Automatic Transfer Switch with
7000 TB Bypass-Isolation 7NTB – Non-Automatic Transfer Switch with
7000 Series 7ACTB – Automatic Closed Transition Transfer Bypass-Isolation
Health Care,
Transfer Switch with Bypass-Isolation 7NCTB – Non-Automatic Closed Transition
Critical Power
Switches 7ADTB – Automatic Delayed Transition Transfer Switch with Bypass-Isolation
Facilities,
with Bypass- Transfer Switch with Bypass-Isolation 7NDTB – Non-Automatic Delayed Transition
Mission Critical
Isolation 7ASLB – Automatic Soft Load Transfer Switch Transfer Switch with Bypass-Isolation
Feature with Bypass-Isolation

3
Table II. UL1008 Withstand and Closing Ratings by Switch Frame

4
Table III. Withstand / Closing Ratings for Transfer Switches
Used with Specific Manufacturer’s Molded Case Circuit Breaker

Transfer Switch

Transfer Switch

Circuit Breaker

Circuit Breaker

Max) Per NEC


Rating (Amps)

Manufacturer
Frame Prefix

Rating (Amp
WCR/Closing
ASCO
Rating kA
Transfer Volts
RMS Circuit Breaker Type or Class
Switch Max
Symmetrical
Product
Amps

300 TS
D 30 22 480 GE THED 40
7000 TS

150 HR 250
125 HL 150
100 BJ, HJ 125
65 240 BG, HG 125
42 QG, QJ 90
150
HD
25 Square-D
BD 125
85 HL, HR 150
50 BJ 125
70 HG, HJ 150
35 480
BG 125
18 BD, HD 125
22 GE THED 90
HJ, HL, HR 150
25
BJ 125
300 TS
4000 TS D HG 150
18 600 Square-D
7000 TS BG 125
HD 150
14
BD 125
150 HR 250
125 HL 150
100 BJ, HJ 125
65 240 BG, HG 125
42 QG, QJ 125
HD 150
25 Square-D
100 BD 125
85 HL, HR 150
50 BJ 125
HG, HJ 150
35 480
BG 125
18 BD, HD 125
22 GE THED 150

5
HJ, HL, HR 150
25
BJ 125
HG 150
18 600 Square-D
BG 125
HD 150
14
BD 125
150 HR 250
125 HL 150
100 BJ, HJ 125
JG, JJ, JL, JR 200
65 240
BG, HG 125
42 QG, QJ 200
HD 150
25 Square-D
BD 125
85 HL, HR 150
150 50 BJ 125
HG, HJ 150
35 480 BG 125
25 JG, JJ, JL 200
18 BD, HD 125
22 GE THED 150
HJ, HL, HR 150
25
BJ 125
HG 150
18 600 Square-D
BG 125
HD 150
14
BD 125
200 JR 250
125 JL 250
100 JJ 250
240
65 JG 250
200 42 QG, QJ 225
Square-D
230 25 JD 250
85 JL, JR 250
30 480 JG, JJ 250
18 JD 250
14 600 JD, JG, JJ, JL, JR 250

65 240 GE THLC4 350

260 Cutler
300 TS E HMC 800
400 42 480 Hammer

GE THKM3F 1200

THQMV 225
GE SGL1, SGL4, SGL6, SGP1,
150 SGP4, SGP6
300 TS 200
Cutler
4000 TS 230 LDC, CLDC, HLD, CHLD 600
J 65 240 Hammer
7000 TS 260
Siemens
7000 TB 400 HLD6, HLXD6
/ ITE
600
QG, QJ 250
Square-D
LJ, LL, LR 600

6
Max) Per NEC
Switch Rating
Switch Frame

Manufacturer

Rating (Amp
WCR/Closing
ASCO

Transfer

Transfer

Breaker

Breaker
(Amps)
Rating kA

Circuit

Circuit
Prefix
Transfer Volts
RMS Circuit Breaker Type or Class
Switch Max
Symmetrical
Product
Amps

HFDE, FDC, FDCE 225


NHH 250
JDC, JGU, JGX 350
Cutler HKD, CHKD, KDC, HKDB,
400
Hammer CHKDB, LHH
HLD, CHLD, LDC, CLDC,
600
LGH*, LGC*, LGU*, LGX*
HMDLB, CHMDLB 800
SEL, SEP 150
SFL, SFP, FEN, FEH 250
TBC4 400
GE TJL4V, TJL1S-6S, TBC6,
SGL1, SGL4, SGL6, SGP1,
600
SGP4, SGP6, FGN, FGH,
FGL, FGP
TB8 800
HDG, LDG 150
HFD, HFD6, HFXD, HFXD6,
480 HHFD6, HHFXD6, CFD6, 250
50
HFG, LFG
HJD, HJD6, HJXD, HJXD6,
Siemens
SHJD, SHJD6, HHJD6,
/ ITE 400
HHJXD6, CJD6, SCJD6,
HJG, LJG, LLG
HLD6, HLXD6, HHLD6,
300 TS HHLXD6, CLD6, SHLD6, 600
150 SCLD6, HLG
4000 TS
J 200 HJ, HL 150
7000 TS
230
7000 TB KC, KI, CF250L, NSF250 250
CK400N, CK400NN, CK400H,
400
CK400HH, CJ400L, NSJ400
LC, DJ, DL, LI, NSJ600 600
Square-D
MasterPact STR 28D, PK, PJ,
800
PL
65 JJ (Current Limiting)
100 JL (Current Limiting) 250
200 JR (Current Limiting)
JGU, JGX, JGH 250
Cutler
Hammer KDC 400
LDC,CLDC 600
TBC4 400
GE SGL1, SGL4, SGL6, SGP1,
600
SGP4, SGP6, FGP
HJ, HL, HG 150
KI, JJ, JL, JR, CF250L 250
42 600 Square-D CK400H, CK400HH, CJ400L 400
LI, MasterPact STR 28D, PK 600
HJD, CFD6 250
HHJD6, HHJXD6, CJD6,
400
Siemens SCJD6
/ ITE HHLD6, HHLXD6, CLD6,
600
SCLD6, LNG, LPG, LGC*,
LGU*, LGX*
7
Transfer Switch

Transfer Switch

Circuit Breaker

Circuit Breaker

Max) Per NEC


Rating (Amps)

Manufacturer
Frame Prefix

Rating (Amp
WCR/Closing
ASCO
Rating kA
Transfer Volts
RMS Circuit Breaker Type or Class
Switch Max
Symmetrical
Product
Amps

HFDE, FDCE, HFD, FDC,


225
LHH
JDC, JGH, JGC, JGU, JGX 250
HKD, HKDB, CHKD, CHKDB,
400
KDC
Cutler HLD, CHLD, LDC, CLDC,
Hammer LGH*, LGC*, LGU*, LGX*, 600
NHH
MDL, CMDL, HMDL, CHMDL,
NGS, NGH, NGC, MDLB, 800
CMDLB, HMDLB, CHMDLB
SFL, SFP, FEN, FEH 250
TBC4 400
TBC6, TJL4V, TJL1S-6S,
SGL1, SGL4, SGL6, SGP1,
600
GE SGP4, SGP6, FGN, FGH,
FGL, FGP
TBC8, TKL4V, TKH8S-12S,
TKL8S-12S, SKH8, SKL8, 800
SKP8, TB8
HFD6, HFXD6, HHFD6,
250
HHFXD6, CFD6, HFG, LFG
HJD6, HJXD6, SHJD6,
300 TS HHJD6, HHJXD6, CJD6, 400
4000 TS J 260 50 480 SCJD6, HJG, LJG, LLG
7000 TS HLD6, HLXD6, SHLD6,
7000 TB Siemens HHLD6, HHLXD6, CLD6, 600
/ ITE SCLD6, HLG
LMD, LMD6, LMXD, LMXD6,
HLMD, HLMD6, HLMXD,
HLMXD6, MD, MD6, MXD6,
800
HMG, HMD6, HMXD6, SMD6,
SHMD6, CMD6, SCMD6,
LMG, MG
KI, KC, CF250L, NSF250 250
CK400N, CK400NN, CK400H,
400
CK400HH, CJ400L, NSJ400
LC, DJ, DL, LJ, LL, LR, LI,
600
NSJ600
CK800N, CK800NN, CK800H,
CK800HH, MasterPact STR 800
Square-D 28D, MJ, PK, PJ, PL
CK1000HL 1000
CK1200NN, CK1200HH 1200

65 JJ (Current Limiting)

100 JL (Current Limiting)


250
200 JR (Current Limiting)

8
Max) Per NEC
Switch Rating
Switch Frame

Manufacturer

Rating (Amp
WCR/Closing
ASCO

Transfer

Transfer

Breaker

Breaker
(Amps)
Rating kA

Circuit

Circuit
Prefix
Transfer Volts
RMS Circuit Breaker Type or Class
Switch Max
Symmetrical
Product
Amps

JGU, JGX 250


Cutler
KDC 400
Hammer
LDC, CLDC 600
TBC4 400
TBC6, SGL1, SGL4, SGL6,
600
GE SGP1, SGP4, SGP6, FGP
TBC8, TKL4V, TKL8S-12S,
800
SKL8, SKP8
HJD, CFD6 250
300 TS HHJD6, HHJXD6, CJD6,
400
4000 TS SCJD6
J 260 42 600 HHLD6, HHLXD6, CLD6,
7000 TS Siemens 600
7000 TB SCLD6
/ ITE
HLMD6, HLMXD6, HMXD6,
SHMD6, HMD6, CMD6,
800
SCMD6, LMG, LNG, LPG,
LGC*, LGU*, LGX*
KI, JL, JR, JJ, CF250L 250
CK400H, CK400HH, CJ400L 400
Square-D LI 600
CK800H, CK800HH,
800
MasterPact STR 28D, PK

JGH, JGC, NHH 250


HKD, CHKD, KDC, HKDB,
400
CHKDB, LHH
CHLD, LDC, CLDC, LGH*,
Cutler 600
LGC*, LGU*, LGX*
Hammer
MDL, CMDL, HMDL, CHMDL,
NGS, NGH, NGC, MDLB, 800
CMDLB, HMDLB, CHMDLB
NGU 1600
TBC4 400
TBC6, TJL4V, TJL1S-6S,
SGL1, SGL4, SGL6, SGP1,
600
SGP4, SGP6, FGN, FGH,
300 TS GE
FGL, FGP
4000 TS
J 400 50 480 TBC8, TKL4V, TKH8S-12S,
7000 TS
TKL8S-12S, 800
7000 TB
SKH8, SKL8, SKP8, TB8
HFD6, HFXD6, HFG, LFG 250
HJD6, HJXD6, SHJD6,
HHJD6, HHJXD6, CJD6, 400
SCJD6, HJG, LLG, LJG
HLD6, HLXD6, SHLD6,
Siemens/ HHLD6, HHLXD6, CLD6, 600
ITE SCLD6, HLG
LMD6, LMXD6, HLMD6,
HLMXD6, MD6, MXD6,
HMD6, HMXD6, SMD6, 800
SHMD6, CMD6, SCMD6,
HMG, LMG

9
Max) Per NEC
Switch Rating
Switch Frame

Manufacturer

Rating (Amp
WCR/Closing
ASCO

Transfer

Transfer

Breaker

Breaker
(Amps)
Rating kA

Circuit

Circuit
Prefix
Transfer Volts
RMS Circuit Breaker Type or Class
Switch Max
Symmetrical
Product
Amps

CK400N, CK400NN, CK400H,


400
CK400HH, CJ400L, NSJ400
LC, DJ, DL, LJ, LL, LR, LI,
600
NSJ600
50 480 Square-D CK800N, CK800NN, CK800H,
800
CK800HH, MJ
CK1000HH 1000
PK, PJ, PL, MH, MasterPact
1200
STR 28D, CK1200HH
KDC 400
Cutler
LDC, CLDC, LGC*, LGU*,
Hammer 600
LGX*
TBC4 400
300 TS TBC6, SGL1, SGL4, SGL6,
4000 TS 600
J 400 GE SGP1, SGP4, SGP6, FGP
7000 TS TBC8, TKL4V, TKL8S-12S,
7000 TB 800
SKL8, SKP8
HHJD6, HHJXD6, CJD6,
400
SCJD6
42 600
HHLD6, HHLXD6, CLD6,
Siemens/ 600
SCLD6
ITE HLMD6, HLMXD6, HMXD6,
SHMD6, HMD6, CMD6, 800
SCMD6, LMG
LNG, LPG 1200
CK400H, CK400HH, CJ400L 400
LI 600
Square-D
CK800H, CK800HH 800
MasterPact STR 28D, PK 1200

JGH, JGC, HFG, LFG 250


HLD, CHLD, LDC, CLDC,
600
Cutler LGH*, LGC*, LGU*, LGX*
Hammer MDL, CMDL, HMDL, CHMDL,
NGS, NGH, NGC, NGU, 800
MDLB, CMDLB, NF
TBC6, TJL4V, TJL1S-6S,
300 TS
SGL1, SGL4, SGL6, SGP1,
4000 TS 600
SGP4, SGP6, FGN, FGH,
7000 TS
FGL, FGP
7000 TB GE
TBC8, TKL4V, TKH8S-12S,
J 600 50 480
TKL8S-12S, SKH8, SKL8, 800
SKP8, TB8
SKL12, SK12P 1200
HLD6, HLXD6, SHLD6,
HHLD6, HHLXD6, CLD6, 600
SCLD6, HLG LLG
Siemens/ LMD6, LMXD6, HLMD6,
ITE HLMXD6, MD6, MXD6,
HMD6, HMXD6, SMD6, 800
SHMD6, CMD6, SCMD6,
HMG, LMG

10
Max) Per NEC
Switch Rating
Switch Frame

Manufacturer

Rating (Amp
WCR/Closing
ASCO

Transfer

Transfer

Breaker

Breaker
(Amps)
Rating kA

Circuit

Circuit
Prefix
Transfer Volts
RMS Circuit Breaker Type or Class
Switch Max
Symmetrical
Product
Amps

HND6, HNXD6, SND6,


Siemens/
SHND6, ND6, NXD6, HNG, 1200
ITE
LNG, CND6

LC, DJ, DL, LI, NSJ600 600


300 TS
4000 TS
CK800N, CK800NN, MJ 800
7000 TS
7000 TB Square- MH, CK1200N, CK1200NN,
50 480
D CK1200H, CK1200HH, NT-H,
1200
NT-L1, NT-L, NT-LF, PK, PJ,
PL
CM2000HH 2000
CM2500HH 2500
7000 TB 85 PL1200 1200
JGC 250
Cutler
TBC4 400
Hammer
LDC, CLDC 600
J 600 TBC6, SGL1, SGL4, SGL6,
600
SGP1, SGP4, SGP6, FGP
GE
TBC8, TKL4V, TKL8S-12S,
800
SKL8, SKP8
SKL12, SKP12 1200
HHLD6, HHLXD6, CLD6,
600
300 TS SCLD6
4000 TS HLMD6, HLMXD6, HMXD6,
42 600 Siemens/
7000 TS SHMD6, HMD6, CMD6, 800
ITE
7000 TB SCMD6, LMG
HND6, HNXD6, HNG, LNG,
1200
SHND6
LI 600

CK800H, CK800HH 800


Square-D CK1000HL 1000
CK1200H,CK1200HH, NT-H,
NT-L, NT-LF, NT-L1, 1200
MasterPact STR 28D, PK

HLD, CHLD, LGH, LGC, LGU,


600
LGX, LDC, CLDC
600
300 TS HMDL, CHMDL, HMDLB,
800 800
4000 TS H Cutler CHMDLB
960 65 480
7000 TS P** Hammer HND, CHND, NDC, CNDC,
1000 1200
7000 TB NF
1200
NGH, NGC, NGU 1600
RGH, RGC 2500
11
Max) Per NEC
Switch Rating
Switch Frame

Manufacturer

Rating (Amp
WCR/Closing
ASCO

Transfer

Transfer

Breaker

Breaker
(Amps)
Rating kA

Circuit

Circuit
Prefix
Transfer Volts
RMS Circuit Breaker Type or Class
Switch Max
Symmetrical
Product
Amps

TBC6, TJL4V, SGL, SGP6 600


GE
TBC8, SKL8, SKP8 800

SKL12, SKP12, TKL4V 1200


HLXD6, HHLXD6, HHLD6,
CLD6, SHLD6, SCLD6, HLG, 600
LLG
HMXD6, HMD6, SHMD6,
800
HMG, LMG, CMD6, SCMD6
Siemens/
ITE SHND6, CND6, HNXD6,
1200
HNG, LNG
HPG, LPG, HPD, HPD6,
300 TS CPD6, HPXD, HPXD6, 1600
4000 TS SHPD, SHPD6
7000 TS HRD6, HRXD6 2000
600
7000 TB 65 480 LI, LE LSI, LE LI, LX, LXI, LJ,
800 600
H LL, LR
960
P** MJ, ME, MX, CK800H,
1000 800
CK800HH
1200
CK1000HL 1000
NT-L1, NT-L, NT-LF, NE, NX,
Square- 1200
CK1200H, CK1200HH, PJ, PL
D NW, RJ, RL 1600
PE, PX 2500
SES, SE, SEH (LS or LSI
3000
TRIP)
SE (LI, LSI-E, and LI-E TRIP) 4000
MasterPact STR 28D 6300
7000 TB 150 MTZ2-16LF1 1600
TRI-PAC NB 800
Cutler
300 TS
Hammer RDC 2500
4000 TS 65 600
7000 TS Siemens/
7000 TB CND 1200
ITE

1600
2000
7000 TB 125 Master Pact NW-L 3000
2600
G 480 Square-D
3000

MTZ1-L1/L/LF
7000 TS 1600 MTZ2/3-L1/L1F
200 2000
7000 TB 2000 MTZ2/3-L/LF except MTZ2/3-
20L
n
*: With Digitrip 310+ LS or LSG Inst. Override set to 12X
**: P Frames only available as 7000TS and 7000TB
12
Marking Requirements
UL requires markings on each switch listing
the approved short circuit ratings for each
product and its ampacity. ASCO switches
display rating labels similar to the one shown
in Figure 2.

Special Application
Considerations
These are the “Time ASCO Power Technologies provides a line
Based” ratings for the of switches which are highly reliable, utilize
transfer switch. For
this switch the rating latest technology, include features most
is 35,000 RMS amps frequently used by the consulting engineer,
symmetrical at 480
volts and 22,000
and which are rated to meet a wide variety of
RMS amps at 600 requirements. For special applications, such
volts. as when higher ratings or longer withstand
times are needed, the system designer can
consider several rating alternatives:
1. Consider relocating the switch closer to
the load where the added impedance of
the feeder conductors will reduce the
This area indicates the available fault current to an acceptable
“Specific Breaker” ratings, level. This is consistent with good
maximum voltage, breaker engineering practice of locating transfer
manufacturer, breaker
type, and maximum frame switches as close to the load as possible
size. This switch is rated in order to minimize the risk of
either 65,000 RMS amps
at 240 volts or 42,000
conductor failures between the load side
RMS amps at 480 volts for of the switch and the utilization
the specific breakers equipment.
listed.
2. Use current limiting fuses or current
limiting circuit breakers to reduce fault
currents.
3. Use a larger ampacity switch with a
higher withstand/closing rating.
4. When the overcurrent protective device
Shown here is the rating ahead of the transfer switch has a
when used with current clearing time exceeding three cycles, a
limiting fuses of the Class
J maximum size indicated zone selective interlocking scheme may
on the label. This switch is be considered. Such a scheme permits
rated for 200,000 RMS intentional delays to be over-ridden and
amps when used with
Class J fuses 600 amps or the breaker to trip instantaneously
less. whenever the fault is within the breaker’s
zone of primary protection.
5. Contact ASCO Power Technologies to
determine if additional ratings are
available.

Figure 2. Typical rating label for ASCO 400 amp Transfer Switch.

13
How To Specify Withstand and unsafe practice or ratings which are too high (resulting
in unnecessarily higher costs).
Closing Ratings
Calculated values of available fault current should be A growing number of specifying professionals are
specified for each transfer switch based on its location in adding fault current withstand and closing current tables
the electrical system. This will assure that a properly to the electrical plans showing the calculated values for
rated switch will be applied and avoid specified ratings each switch. A typical arrangement is shown in Table
which are too low for the actual location (resulting in an IV.

Table IV. Typical Listings of Transfer Switch Fault Current Ratings on an Electrical Plan
Transfer Switched Transfer Calculated Fault Currents
No. of System Type of
Switch Neutral Switch RMS Sym.
Poles Voltage X/R Ratio OCD
Ident. No. Y/N Ampacity Amperes
ATS-E8 4 Y 260 480/277 29,000 2.3 MCCB
ATS-E9 3 N 400 480 33,000 2.3 MCCB
ATS-LS1 4 Y 100 480/277 7,300 2.1 MCCB
ATS-LS2 4 Y 150 480/277 8,900 2.4 MCCB
ATS-EQ1 3 N 1000 480 48,000 3.2 MCCB

Importance of X/R Ratio publication and calculating short circuit currents, the
system designer can be assured that the transfer switches
The circuit reactance to resistance ratio (X/R) is a will be properly rated for the electrical system.
determinant in preparing fault current studies.
Consideration should be given to the X/R ratio at each Table V. UL Maximum Test Factor
with Equivalent X/R Ratio
transfer switch location. The actual X/R ratio should not
exceed the X/R ratio at which the transfer switch was Available Fault Maximum Test Equivalent
tested. Table V shows the power factor test Current (amperes) Power Factor X/R Ratio
requirements of UL 1008 with equivalent X/R ratios. If 10,000 or less 0.50 1.73
an application requires higher X/R ratios, consider the 10,001 – 20,000 0.30 3.18
greater than 20,000 0.20 4.90
Special Application Considerations previously discussed
or consult ASCO Power Technologies for a
recommendation. By using the information in this

Suggested Fault Current Study Reference Guides


1. The Institute of Electrical and Electronics Engineers, Inc., IEEE Recommended Practice for Protection and Coordination of
Industrial and Commercial Power Systems, IEEE Buff Book, ANSI/IEEE Std. 242-1986, New York, N.Y., pp. 45-113.
2. The Institute of Electrical and Electronics Engineers, Inc., IEEE Recommended Practice for Electric Power Distribution for
Industrial Plants, IEEE Red Book, ANSI/IEEE Std. 141-1993, New York, N.Y., pp. 109-184.
3. The Institute of Electrical and Electronics Engineers, Inc., IEEE Recommended Practice for Power System Analysis, IEEE
Brown Book, ANSI/IEEE Std. 399-1990, New York, N.Y., pp. 171-194.
4. The Institute of Electrical and Electronics Engineers, Inc., IEEE Recommended Practice for Emergency and Standby Power
Systems for Industrial and Commercial Applications, IEEE Orange Book, ANSI/IEEE Std. 446-1995, New York, N.Y., pp. 175-
196.
5. The Institute of Electrical and Electronics Engineers, Inc., IEEE Recommended Practice for Electric Systems in Health Care
Facilities, IEEE White Book, ANSI/IEEE Std. 602-1996, New York, N.Y., pp. 50-51; 72-74.
6. Frank W. Kussy and Jack L. Warren, Design Fundamentals for Low-Voltage Distribution and Control, Marcel Dekker Inc., pp.
104-117, 1987.
7. Hermann W. Reichenstein, Applying Low-Voltage Fuses-Classes and Characteristics, McGraw-Hill Inc., 1979.
In addition to the above, most manufacturers of overcurrent protective devices can provide application data on calculating short
circuit currents. Various software packages are also available to assist the application engineer in performing calculations by
computer.

14
ASCO Power Technologies, Florham Park, New Jersey 07932 USA
800-800-2726 (ASCO) www.ascopower.com
©
Publication 1128 R29 ASCO Power Technologies 2021 Printed in U.S.A.

15
ASCO Power Technologies, L.P. and ASCO Power Services, Inc. Standard Terms and Conditions of Sale
1. Contract Terms. These Standard Terms and Conditions of Sale (“Conditions of Sale”) shall apply to any purchase or procurement of Products or Services by the legal
entity procuring such Products or Services (“Purchaser”) from the legal entity (ASCO Power Technologies, L.P. or ASCO Power Services, Inc.) that provided the proposal or is
selling the Products and Services (“Seller”). To the extent that there is a conflict between these Conditions of Sale and a valid signed master agreement between the
Purchaser and Seller, the specific conflicting terms of the master agreement shall prevail. To the extent that there is a conflict between these Conditions of Sale and another
set of Seller terms and conditions issued to the Purchaser as part of the proposal or quotation process, the specific conflicting terms of the proposal or quotation document
shall prevail. Any other variation from these Conditions of Sale shall require the signed consent of an authorized Seller representative and these terms and conditions
supersede any prior or contemporaneous agreements or correspondence between the parties except as provided above. Seller’s acceptance of Purchaser’s purchase order
is expressly conditional on Purchaser’s assent to all of Seller’s Conditions of Sale, and Purchaser specifically acknowledges and agrees that any purchase order issued by
Purchaser shall operate only to establish payment authority for Purchaser’s internal accounting purposes. Any such purchase order issued by Purchaser shall not be
considered as a counteroffer, addition, amendment, modification or other revision these Conditions of Sale, and any terms or conditions contained in Purchaser’s purchase
order shall be of no force and effect. Purchaser’s acceptance of the Products or Services will manifest Purchaser’s assent to these Conditions of Sale.
2. Prices. Unless otherwise stated in an applicable quotation or proposal from Seller, the price quoted or specified by Seller for the Products or Services shall remain in
effect for thirty (30) days after the date of Seller's quotation provided Seller receives and accepts from Purchaser a purchase order and an unconditional release to
manufacture the Product and/or perform the Services within such time period. If such purchase order and release is not received by Seller within such thirty (30) day period,
Seller shall have the right to change the price for the Products and/or Services to Seller's price for the Products and/or Services then in effect at the time of shipment of the
Product and/or performance of the Services. All clerical errors are subject to correction. Services Terms: Additional charges will be billed to Purchaser at Seller’s then
prevailing labor rates for any of the following: (a) any Services not specified in Seller’s quotation, Seller’s order acknowledgement, Seller’s scope of work, or other documents
referenced herein and therein; (b) any Services performed at times other than Seller’s normal service hours; (c) if timely and reasonable site and/or equipment access is
denied the Seller service representative; (d) if it is necessary, due to local circumstances, to use union labor or hire an outside contractor, Seller Service personnel will provide
supervision only and the cost of such union or contract labor will be charged to Purchaser; (e) if Service or repair is necessary to return equipment to proper operating
condition as a result of other than Seller (i) maintenance, repair, or modification (including, without limitation, changes in specifications or incorporation of attachments or other
features), (ii) misuse or neglect, (including, without limitation, failure to maintain facilities and equipment in a reasonable manner), (iii) failure to operate equipment in
accordance with applicable specifications, and (iv) catastrophe, accident, or other causes external to equipment; (f) Seller’s performance is made more burdensome or costly
as a result of Purchaser’s failure to comply with its obligations herein; or (g) any additional obligations or requirements, including but not limited to those related to insurance
requirements, service delivery, building entry, or technical training. Seller is under no obligation to remove or dispose of parts or equipment unless specifically agreed upon in
Seller’s scope of work. Seller removed parts become the property of Seller. Purchaser shall not solicit, directly or indirectly, or employ any employee of Seller during the
period any Services are being provided to Purchaser and for a period of one (1) year after the last provision of Services.
3. Taxes. Unless otherwise set out in Seller’s proposal or quotation, prices do not include taxes, duties or any other governmental levies, all of which are payable by
Purchaser. Except as may be otherwise provided in the relevant Purchase Order, the price excludes all present or future sales taxes, revenue or excise taxes, value-added
taxes, import and export duties and any other taxes, surcharges or duties now existing or hereafter imposed by governmental authorities upon equipment and/or services
quoted by Seller. The Purchaser shall be responsible for all such taxes, duties and charges resulting from these Conditions of Sale or any associated purchase. Seller is
required to impose taxes on orders and shall invoice the Purchaser for such taxes and/or fees according to applicable law, statutes, or regulations, unless Purchaser furnishes
the Seller at the time of order with a properly completed exemption certificate(s) acceptable to the authorities imposing the tax or fees. Any changes in foreign exchange rates,
sales taxes, customs tariffs or other taxes shall be chargeable to the Purchaser.
4. Terms of Payment. Terms are net 30 days from date of invoice. Late payments will be subject to interest charges at the rate of two percent (2%) per month. If at
Purchaser’s request, shipments are delayed beyond the scheduled date, payments for the Products and Services completed to date will be invoiced to the Purchaser, as a
percentage of the total Purchase Order price when Seller was originally prepared to ship. Products held for the Purchaser shall be at the risk and expense of the Purchaser. If
shipment of Products and/or completion of Services is delayed more than 30 days after originally scheduled delivery date and not caused solely by Seller, Seller reserves the
right to ship all Products to the Purchaser who will accept responsibility for Products including payment. Failure to pay any applicable payment on its due date shall
automatically cause all installment amounts to become payable and in addition to Seller’s other lawful remedies, Seller reserves the right to suspend or cancel the PO. If
Purchaser fails to pay Seller for the Products and Services, Seller reserves the right to file in its sole discretion any liens, charges, security interests, or similar encumbrances
against the applicable property, building, land, or Products and Services and Purchaser consents to such filings and registrations. Purchaser shall be liable for all expenses,
including attorneys' fees, relating to the collection of past due amounts.
5. Delivery and Schedule. While Seller will use all reasonable commercial efforts to maintain the delivery date(s) and/or performance dates acknowledged or quoted by
Seller, all shipping dates and/or performance dates are approximate and not guaranteed.
6. Risk of loss. Unless otherwise specifically agreed by the Parties, the Products are delivered FCA Seller’s shipping point (Incoterms 2010) with Purchaser responsible for
all official export formalities, authorizations, risks and expenses as may be applicable for export from the country of shipment, and title and risk of loss or damage shall pass to
the Purchaser upon collection of the Products by the first carrier at Seller’s premises, plants or warehouses. Delivery of Products by Seller will be deemed to be made to the
Purchaser upon obtaining a signed receipt from the carrier showing receipt of the Products in good order.
7. Substitutions. Seller may furnish suitable substitutes for Products unobtainable because of priorities or regulations established by governmental authority or non-
availability of materials from suppliers, provided such substitutions do not adversely affect the technical soundness of the Products. Seller assumes no liability for deviation
from published dimensions and descriptive information not essential to proper performance of the Products.
8. Shortage. Claims for shortages or errors must be submitted to Seller within 30 days after invoice date, and failure to give such notice shall constitute unqualified
acceptance and a waiver of all such claims by the Purchaser.
9. Installments. Seller reserves the right to make shipments in installments, unless otherwise expressly stipulated in a specific Purchase Order; and all such installments
when separately invoiced shall be paid for when due per invoice without regard to subsequent shipments. Delay in shipment of any installment shall not relieve Purchaser of
its obligation to accept remaining shipments.
10. Force Majeure. Seller will be excused from and not be liable for any non-performance of a Purchase Order if such delay or non- performance is due to any cause
beyond the reasonable control of Seller, or which Seller could not reasonably foresee or reasonably provide against, and which prevents Seller from carrying out the terms of
the Purchase Order. This includes but is not limited to the following: war, revolution, insurrection or hostilities (whether declared or not), riot, economic upheaval, civil
commotion or uprising, flood, earthquake, tempest, hurricane, lightning or other natural disaster; fire or explosion; strike, lockout or other industrial disturbance whether at
Seller or one of its suppliers; sabotage, accident, embargo, car shortage, wrecks or delays in transportation, non-delivery of materials or order or action of government
authority. Any delay resulting from such cause shall extend the date of delivery accordingly. Seller reserves the right to cancel a Purchase Order, if in its opinion such
circumstances threaten or cause extended delay in the performance thereof.
11. Standard Warranty. Seller warrants: (a) Products manufactured by Seller under its own brands and supplied by Seller as part of the Purchase Order, are subject to
Seller's standard warranty that is applicable to the specific product at the time of purchase, and its terms, conditions and limitations are incorporated by reference herein (a
“Standard Warranty”). (b) Services performed by Seller’s personnel as part of the Purchase Order, if any, will be performed by qualified personnel with care, skill and
diligence, in accordance with the applicable generally accepted standards recognized by the industry, and shall be free from faulty workmanship for a period of thirty (30) days
from completion of the Services. For Services that include a Modification, the warranty for such Modification shall be one (1) year from the date of shipment of such by Seller.
A “Modification” is integrating new controls and/or switchgear components into existing switchgear or upgrading an automatic transfer switch with new components or
accessories. Exclusive Warranty Remedies: In the event of any warranty covered defects or deficiencies in Products in subsections (a) above, or Services in subs. (b) above,
the sole and exclusive obligation of Seller shall be to re-perform the Services, or repair or replace the defective Products or part of the Products, at Seller’s sole discretion.
Such warranty coverage is contingent on Purchaser providing prompt notification to Seller once such defect or deficiency is reasonably apparent to Purchaser. Exclusions &
Limitations: This warranty shall not apply (a) to Products not manufactured by Seller, (b) Services not provided directly by Seller, (c) to Products or Services that has been
repaired or altered by anyone other than Seller so as, in Seller’s judgment, affects the same adversely, (d) Seller’s conformance with Buyer’s design of the Products or Software;
or (e) to Products or Services that appear to be subjected to negligence, accident, or damage by circumstances beyond Seller’s control, or improper any non-Seller operation,
maintenance or storage, or to other than normal use or service. Unless specifically covered in a Standard Warranty, the foregoing warranties do not cover reimbursement for
labor, transportation, removal, installation, temporary power, or any other expenses that may be incurred in connection with repair or replacement. THESE WARRANTIES,
CONDITIONS, AND EXCLUSIONS ARE EXCLUSIVE AND IN LIEU OF ALL OTHER EXPRESS OR IMPLIED WARRANTIES, CONDITIONS, REPRESENTATIONS AND
GUARANTEES (EXCEPT WARRANTIES OF TITLE), INCLUDING, BUT NOT LIMITED, TO IMPLIED WARRANTIES OF MERCHANTABILITY, MERCHANTABLE QUALITY,
AND FITNESS FOR A PARTICULAR PURPOSE. EXCEPT AS MAY BE PROVIDED IN WRITING BY SELLER, SELLER SHALL NOT BE SUBJECT TO ANY OTHER
OBLIGATIONS OR LIABILITIES WHATSOEVER THAN AS STATED ABOVE WITH REGARD TO PRODUCTS AND SERVICES SOLD BY SELLER TO PURCHASER. Non-
Seller Products or Services: With respect to Products not manufactured by Seller, or Services provided by non-Seller providers, the warranty obligations of Seller shall in all
respects conform and be limited to the warranty actually extended to Seller by such non-Seller supplier.
12. Return of Products. No Products may be returned without first obtaining Seller’s written permission and a returned material identification tag. Returned Products must
be of current manufacture, in the original packaging, unused, undamaged and in saleable condition. Returned Products must be securely packed to reach Seller without
damage and labeled with the return authorization number. For any returns, Seller will be pay the carrier and deduct the freight charges from the credit unless if returns result from
Seller error, freight charges will be paid by Seller. Any cost incurred by Seller to put Products in first class condition will be charged to the Purchaser. Returns must originate from
Dec 2020 Page 1 of 2
the original Purchaser account number. Returns will be credited at the original price paid as indicated on the invoice or Purchase Order associated to the Products being returned
as provided by the Purchaser. If no invoice number or Purchase Order number is provided, then credit will be issued based on the into stock price in effect 12 months prior to
date of return authorization and will also have an additional 25% processing fee applied. Seller Products, which are listed in the current product list as returnable and which are
accepted for credit, not involving a Seller error, shall be assessed a restocking fee of 25% of the invoice price.
13. Intellectual Property. Seller retains ownership of all right, title and interest (including copyright and patent rights) in and to the intellectual property relating to Products
and Services and work product relating to thereto, including, but not limited to, documentation, prints, and drawings. Nothing in these Conditions of Sale constitutes a transfer
or conveyance of any right, title or interest in such intellectual property, including without limitation any software or firmware contained in those, except the limited right
to use it as provided in the documentation. As to Products proposed and furnished by Seller, Seller shall defend any suit or proceeding brought against Purchaser so far as
based on a claim that such Products constitute an infringement of any copyright, trademark or patent in the United States or Canada. This obligation shall be effective only if
Purchaser shall have made all payments then due hereunder and if Seller is notified promptly in writing and given authority, information, and assistance at Seller’s expense for
the defense of the same. In the event the use of such Products by Purchaser is enjoined in such a suit, Seller shall, at its expense, and at its sole option, either (a) procure for the
Purchaser the right to continue using such Products, (b) modify such Products to render them non-infringing, or (c) replace such Products with non-infringing Products. Seller
will not be responsible for any compromise or settlement made without its written consent. The foregoing states the entire liability of Seller for patent, trademark or copyright
infringement, and in no event shall Seller be liable if any infringement charge is based on the use of Seller Products for a purpose other than that for which it was sold by Seller. As
to any Products or Services furnished by Seller to Purchaser and manufactured or provided in accordance with designs proposed by Purchaser, the Purchaser shall indemnify
Seller against any award made against Seller for patent, trademark, or copyright infringements.
14. Software. Any software or computer information, in whatever form that is provided with Products manufactured by Seller or as part of Services, is licensed to Purchaser
solely pursuant to standard licenses of Seller or its supplier of such software or computer information which licenses are hereby incorporated by reference and are available upon
request. Seller does not warrant that such software or computer information will operate error-free or without interruption, and warrants only that during the warranty period
applicable to the Products that the software will perform its essential functions. If such software or computer information fails to conform to such warranty, Seller will, at its
option, provide an update to correct the non-conformance or replace the software or computer information with the latest available version containing a correction. Seller shall
have no other obligation to provide updates or revisions.
15. LIMITATION OF LIABILITY. NOTWITHSTANDING ANY PROVISION OF THESE CONDITIONS OF SALE OR ANY OTHER CONTRACT DOCUMENT TO THE
CONTRARY, IN NO EVENT SHALL EITHER PARTY, ITS OFFICERS, DIRECTORS, AFFILIATES OR EMPLOYEES BE LIABLE FOR ANY FORM OF INDIRECT,
SPECIAL, CONSEQUENTIAL OR PUNITIVE DAMAGES, INCLUDING, BUT NOT LIMITED TO, LOSS OF USE, LOSS OF PRODUCTION, LOSS OF PRODUCT, LOSS OF
REVENUE, PROFITS OR LOSS OF DATA DAMAGES WHETHER SUCH DAMAGES ARISE IN CONTRACT OR TORT, IRRESPECTIVE OF FAULT, NEGLIGENCE OR
STRICT LIABILITY OR WHETHER SUCH PARTY HAS BEEN ADVISED IN ADVANCE OF THE POSSIBILITY OF SUCH DAMAGES. NOTWITHSTANDING ANY OTHER
PROVISION OF THESE CONDITIONS OF SALE OR ANY OTHER CONTRACT DOCUMENT TO THE CONTRARY, AND TO THE EXTENT PERMITTED BY APPLICABLE
LAW, THE MAXIMUM LIABILITY OF SELLER FOR DAMAGES HEREUNDER SHALL NOT EXCEED THE AMOUNTS ACTUALLY PAID BY THE PURCHASER TO
SELLER FOR THE PRODUCTS AND/OR SERVICES GIVING RISE TO A CLAIM. SELLER SHALL NOT BE LIABLE FOR DAMAGES CAUSED BY DELAY IN
PERFORMANCE AND THE REMEDIES OF PURCHASER SET FORTH IN THIS AGREEMENT ARE EXCLUSIVE.
16. Insurance. Seller shall maintain reasonable insurance coverage (e.g., commercial general liability, worker’s compensation, automobile) in such amounts as Seller
deems appropriate in accordance with industry practice. Certificate of insurance evidencing this may be provided on request.
17. Import and Export. Purchaser agrees that all Products and Services require proper compliance with import and export laws and administrative requirements including
the payment of all associated duties, taxes and fees.
18. Health and Safety; Compliance. Seller employees shall not perform Services that, in their sole opinion, are not free of reasonably foreseeable harm. This includes
working on any equipment, whether provided by Seller, Purchaser or otherwise, that in such Seller employees’ sole opinion has not been placed in an electrically safe working
condition. Purchaser warrants that site and working conditions shall meet or exceed those specified by applicable Occupational Health and Safety Act and Regulations.
Purchaser shall inform Seller of: (a) Known hazards, or reasonably foreseeable hazards, that are related to Seller’s scope of Services and the site where the Services will be
performed; and (b) Information about the worksite necessary to identify hazards and assess risk for the protection of the health and safety of Seller personnel. This information
might include, but is not limited to: (i) Providing an accurate up-to-date single line diagram of the electrical distribution system; (ii) Providing relevant Workplace Hazardous
Materials Information System (WHMIS) information such as Material Safety Data Sheets (MSDS) and floor plans indicating areas where hazardous materials are located and
emergency exits for service rooms and other areas of operation; and (iii) Other site specific information relative to the Purchaser’s operation, process and safety systems. Any
hazardous materials requiring remediation in Seller’s sole opinion will be separately chargeable to Purchaser and will be a condition precedent to Seller’s performance of such
Services. If the Purchaser has concerns related to ethics, compliance or ASCO Power/Schneider Electric’s Principles of Responsibility, and/or any potential violations of
these policies, Purchaser is welcome to make use of Schneider Electric’s GreenLine. The GreenLine is Schneider Electric’s global helpline for external stakeholders. It is a
confidential channel through which Purchasers can ask questions and raise concerns. Reports can be made using the following link:
https://secure.ethicspoint.eu/domain/media/en/gui/104677/index.html
19. Witness of Tests & Factory Inspections. Normal production schedules do not provide the opportunity for Purchaser to witness routine factory tests on Products or
make factory inspections. Witnessing of tests or factory inspections by the Purchaser may result in delays of production for which Seller will not be responsible and which may
result in additional charges and delayed scheduling to Purchaser. Witness testing and factory inspections must be requested at time of quotation, are subject to additional
costs and must be confirmed at Purchase Order entry. Standard Seller factory testing and inspection will apply. Seller will notify Purchaser fourteen (14) calendar days prior to
scheduled witness testing or inspection. In the event Purchaser is unable to attend, the Parties may mutually agree on a rescheduled date. However, Seller, at its sole option,
may consider the witness tests or inspection waived, and ship and invoice the Products and the witness testing charges. Purchaser will be responsible for paying for all
scheduled witness testing, whether or not Purchaser attends.
20. Patterns and Tools. Notice will be given if special patterns or tools are required to complete any Purchase Order. Charges for such patterns or tools do not convey title
thereto or the right to remove them from Seller’s plant. If patterns or tools are not used for a period of two years, Seller shall have the right to scrap them without notice.
21. Nuclear Applications. Unless otherwise agreed in writing by a duly authorized representative of Seller, Products sold hereunder are not intended for use in or in
connection with any nuclear facility or activity. Purchaser hereby represents and warrants that such Products shall not be used in or in connection with any nuclear facility or
activity. If so used, Seller disclaims all liability for any damage, injury or contamination; and Purchaser agrees and indemnifies Seller against any such liability, whether arising
as a result of breach of contract, warranty or tort (including negligence) or otherwise.
22. Nature of Relationship. Purchaser agrees that Seller is an independent contractor and nothing in these Conditions of Sale creates between Seller and Purchaser a
relationship of partners, joint venturers, or agents of each other, and no Party may so represent itself any of these manners.
23. Termination. Any Purchase Order may be terminated by the Purchaser only upon 30 days’ notice to Seller and upon payment of reasonable and proper termination
charges based on the price of the terminated Purchase Order and reimbursement of all costs and expenses associated with the order caused by such termination and shall
include a reasonable profit. Special or custom ordered Products is not cancelable after final acceptance or approval of drawings for the commencement of manufacturing.
24. Cancellation. Seller shall have the right to cancel any Purchase Order at any time by written notice for any material breach of these Conditions of Sale by the
Purchaser, including material delays by Purchaser or its authorized representatives in releasing Products for manufacture or approval drawings and excessive changes to
specifications or drawings.
25. Amendments. No amendment, supplement, modification, waiver or termination of the Purchase Order or these Conditions of Sale is binding unless executed in writing
by both parties.
26. Applicable Laws. All matters arising out of or relating to the execution, construction, interpretation or breach thereof, are to be governed by the laws of the
state of New Jersey, excluding (i) such jurisdiction’s rules regarding conflicts of laws, and (ii) the provisions of the United Nations Convention on Contracts for the International
Sale of Goods. Seller agrees to bring any action claims or legal proceedings in any way pertaining to this Purchase Order, or the execution, construction, interpretation or
breach thereof in the courts of the jurisdiction specified above and in no other court or tribunal whatsoever. No action, regardless of form, arising out of transactions relating
to this contract, may be brought by either party more than two (2) years after the cause of action has accrued.
27. Indemnity. Each party shall indemnify and hold the other party harmless from loss, damage, liability or expense resulting from damage to personal property of a third
party, or injuries, including death, to third parties to the extent caused by a negligent act or omission of the party providing indemnification or a party’s subcontractors, agents
or employees during performance of services hereunder. Such indemnification shall be reduced to the extent damage or injuries are attributable to others. The indemnifying
party shall defend the other party in accordance with and to the extent of the above indemnification, provided that the indemnifying party is: (i) promptly notified by the other
party, in writing, of any claims, demands or suits for such damages or injuries; (ii) given all reasonable information and assistance by the other party; (iii) given full control over
any resulting negotiation, arbitration or litigation, including the right to choose counsel and settle claims, or the indemnifying party’s obligations herein shall be deemed waived.
DISCLAIMER: The Purchaser acknowledges that the products or part thereof are produced in, or otherwise sourced from, or will be installed areas already affected by, or that
may be affected in the future by, the prevailing COVID-19 epidemics/pandemic and that the situation may trigger stoppage, hindrance or delays in Seller’s (or its
subcontractors) capacity to produce, deliver, install or service the products, irrespective of whether such stoppage, hindrance or delays are due to measures imposed by
authorities or deliberately implemented by the Seller (or its subcontractors) as preventive or curative measures to avoid harmful contamination exposure of Seller’s (or its
subcontractors’) employees. The Purchaser therefore recognizes that such circumstances shall be considered as a cause for excusable delay not exposing the Seller to
contractual sanctions including without limitation delay penalties, liquidated or other damages or termination for default.
Dec 2020 Page 2 of 2