KTA Caracteristicas Tecnicas
KTA Caracteristicas Tecnicas
Canalis KTC 3L + PE
Canalis KTC
Conductor characteristics
Phase conductors
Average resistance at an ambient temperature of 20 °C R20 m:/m 0.041 0.029 0.024 0.018 0.014 0.012 0.009 0.007
Average resistance at Inc and at 35 °C R1 m:/m 0.049 0.035 0.029 0.022 0.018 0.015 0.012 0.009
Average reactance at Inc and at 35 °C and at 50 Hz X1 m:/m 0.022 0.016 0.015 0.013 0.011 0.008 0.007 0.007
Average impedance at Inc and at 35 °C and at 50 Hz Z1 m:/m 0.054 0.039 0.033 0.026 0.021 0.017 0.014 0.012
PE = casing
Average resistance at an ambient temperature of 20 °C m:/m 0.203 0.178 0.164 0.143 0.126 0.113 0.093 0.080
Casing mm² 120 130 140 155 165 180 190 200
(Equivalent copper cross-section)
Average weight
3L + PE kg/m 19 25 29 36 44 51 66 82
Conductor characteristics
Phase conductors
Average resistance at an ambient temperature of 20 °C R20 m:/m 0.041 0.029 0.024 0.018 0.014 0.012 0.009 0.007
Average resistance at Inc and at 35 °C R1 m:/m 0.049 0.035 0.029 0.022 0.018 0.015 0.012 0.009
Average reactance at Inc and at 35 °C and at 50 Hz X1 m:/m 0.022 0.016 0.015 0.013 0.011 0.008 0.007 0.007
Average impedance at Inc and at 35 °C and at 50 Hz Z1 m:/m 0.054 0.039 0.033 0.026 0.021 0.017 0.014 0.012
PE = casing
Average resistance at an ambient temperature of 20 °C m:/m 0.203 0.178 0.164 0.143 0.126 0.113 0.093 0.080
Casing mm² 120 130 140 155 165 180 190 200
Equivalent copper cross-section
Average weight
3L + N + PE kg/m 25 33 39 49 60 71 92 114
Canalis KTC
Conductor characteristics
Phase conductors
Average resistance at an ambient temperature of 20 °C R20 m:/m 0.041 0.029 0.024 0.018 0.014 0.012 0.009 0.007
Average resistance at Inc and at 35 °C R1 m:/m 0.049 0.035 0.029 0.022 0.018 0.015 0.012 0.009
Average reactance at Inc and at 35 °C and at 50 Hz X1 m:/m 0.022 0.016 0.015 0.013 0.011 0.008 0.007 0.007
Average impedance at Inc and at 35 °C and at 50 Hz Z1 m:/m 0.054 0.039 0.033 0.026 0.021 0.017 0.014 0.012
PE = internal copper protective conductor
Average resistance at an ambient temperature of 20 °C m:/m 0.050 0.039 0.034 0.026 0.022 0.019 0.014 0.012
Copper cross-section mm² 210 300 360 480 600 720 960 1200
Average weight
3L + N + PER kg/m 25 33 39 49 60 71 92 114
Fire load value
kWh / m 2.5 3.6 4.1 5.9 7.3 8.0 11.5 14.4
Radiated magnetic field
Radiated magnetic field strength 1 metre from the B µT 0.4 0.5 0.75 0.9 1.3 1.6 2.1 3.0
trunking
Choice of products when harmonics are present (see “harmonic currents” for more details).
Rated current according to THD3 (3rd order THD < 15 % 1000 1350 1600 2000 2500 3200 4000 5000
distortion) 15 % < THD < 33 % - 1000 1350 1600 2000 2500 3200 4000
THD > 33 % - - 1000 1350 1600 2000 2500 3200
Performance criteria
Fire integrity Thermal
insulation
Without external fire barrier 120 mn 30 mn
With external fire barrier 120 mn 120 mn