Test Report issued under the responsibility of:

TEST REPORT
IEC 61727
Photovoltaic (PV) systems –
Characteristics of the utility interface

Report Number. .............................. : 200218043GZU-001


Date of issue ................................... : 20 Feb 2020
Total number of pages ................... 25 Pages

Name of Testing Laboratory Intertek Testing Services Shenzhen Ltd. Guangzhou Branch
preparing the Report ..................... : Block E, No.7-2 Guang Dong Software Science Park, Caipin
Road, Guangzhou Science City, GETDD, Guangzhou, China
Applicant’s name ........................... : Shenzhen SOFAR SOLAR Co., Ltd.
Address ........................................... : 401, Building 4, AnTongDa Industrial Park, District 68,
XingDong Community, XinAn Street, BaoAn District,
Shenzhen, China
Test specification:
Standard ......................................... : IEC 61727:2004
Test procedure ............................... : Type approval
Non-standard test method ............ : N/A
Test Report Form No. .................... : IEC61727B
Test Report Form(s) Originator .... : TÜ V SÜ D Product Service GmbH
Master TRF ..................................... : Dated 2017-11-03
Copyright © 2017 IEC System of Conformity Assessment Schemes for Electrotechnical
Equipment and Components (IECEE System). All rights reserved.
This publication may be reproduced in whole or in part for non-commercial purposes as long as the IECEE is acknowledged as
copyright owner and source of the material. IECEE takes no responsibility for and will not assume liability for damages resulting
from the reader's interpretation of the reproduced material due to its placement and context.
If this Test Report Form is used by non-IECEE members, the IECEE/IEC logo and the reference to the
CB Scheme procedure shall be removed.
This report is not valid as a CB Test Report unless signed by an approved CB Testing Laboratory
and appended to a CB Test Certificate issued by an NCB in accordance with IECEE 02.
General disclaimer:
The test results presented in this report relate only to the object tested.
This report shall not be reproduced, except in full, without the written approval of the Issuing CB Testing
Laboratory. The authenticity of this Test Report and its contents can be verified by contacting the NCB,
responsible for this Test Report.
Page 2 of 25 Report No. 200218043GZU-001

Test item description ....................... : Solar Grid-tied Inverter


Trade Mark ........................................ :

Manufacturer ..................................... : Same as applicant


Model/Type reference ...................... : SOFAR 11000TL-LV, SOFAR 13500TL-LV
SOFAR 16500TL-LV, SOFAR 18000TL-LV
Ratings .............................................. : Model SOFAR SOFAR SOFAR SOFAR
11000TL- 13500TL- 16500TL- 18000TL-
LV LV LV LV
Max.PV
1100Vdc
voltage
MPPT voltage 230-960Vdc
Max.input
2*24A 2*28A 2*30A
current
PV Isc 2*30A 2*35A 2*37.5A
Nominal
output
3W/N/PE 127/220 Vac
voltage

Nominal
output 60Hz
Frequency
Max.output
3*32A 3*40A 3*48A 3*53A
current
Nominal
11000 W 13500 W 16500 W 18000 W
output power
Max.output 11000 13500 16500 18000
power VA VA VA VA
Power factor
0.8Leading~0.8Lagging
range
Safety level Class I
Ingress
IP 65
Protection
Operation
Ambient -25℃ - +60℃
Temperature
Software
V2.00
version

TRF No. IEC 61727B


Page 3 of 25 Report No. 200218043GZU-001

Responsible Testing Laboratory (as applicable), testing procedure and testing location(s):

CB Testing Laboratory: Intertek Testing Services Shenzhen Ltd. Guangzhou


Branch
Testing location/ address ............................. : Block E, No.7-2 Guang Dong Software Science Park,
Caipin Road, Guangzhou Science City, GETDD,
Guangzhou, China
Associated CB Testing Laboratory: N/A
Testing location/ address ............................. : N/A

Tested by (name, function, signature) ........ : Sunny Lin


Engineer
Approved by (name, function, signature) ... : Jason Fu
Technical Team
Leader

Testing procedure: TMP/CTF Stage 1: N/A


Testing location/ address ............................. : N/A

Tested by (name, function, signature) ........ : N/A


Approved by (name, function, signature) ... : N/A

Testing procedure: WMT/CTF Stage 2: N/A


Testing location/ address ............................. : N/A

Tested by (name + signature) ...................... : N/A


Witnessed by (name, function, signature) . : N/A
Approved by (name, function, signature) ... : N/A

Testing procedure: N/A


SMT/CTF Stage 3 or 4:
Testing location/ address ............................. : N/A

Tested by (name, function, signature) ........ : N/A


Witnessed by (name, function, signature) . : N/A
Approved by (name, function, signature) ... : N/A
Supervised by (name, function, signature) : N/A

TRF No. IEC 61727B


Page 4 of 25 Report No. 200218043GZU-001

List of Attachments (including a total number of pages in each attachment):


Appendix 1: photos (4 pages)

Summary of testing:

Tests performed (name of test and test Testing location:


clause): Intertek Testing Services Shenzhen Ltd.
All applicable tests Guangzhou Branch
Block E, No.7-2 Guang Dong Software Science
Park, Caipin Road, Guangzhou Science City,
GETDD, Guangzhou, China

Summary of compliance with National Differences:


List of countries addressed
N/A

The product fulfils the requirements of IEC 61727:2004

TRF No. IEC 61727B


Page 5 of 25 Report No. 200218043GZU-001

Copy of marking plate:


The artwork below may be only a draft. The use of certification marks on a product must be
authorized by the respective NCBs that own these marks.

TRF No. IEC 61727B


Page 6 of 25 Report No. 200218043GZU-001

Note:
1. The above markings are the minimum requirements required by the safety standard. For the
final production samples, the additional markings which do not give rise to misunderstanding
may be added.
2. Label is attached on the side surface of enclosure and visible after installation.

TRF No. IEC 61727B


Page 7 of 25 Report No. 200218043GZU-001

Test item particulars...................................................:


Classification of installation and use.......................: Fixed and outdoor use
Supply Connection .....................................................: Permanent connection
.......................................................................................:
Possible test case verdicts:
- test case does not apply to the test object ........... : N/A
- test object does meet the requirement.................. : P (Pass)
- test object does not meet the requirement ........... : F (Fail)
Testing.......................................................................... :
Date of receipt of test item ........................................ : 18 Feb 2020
Date (s) of performance of tests ............................... : 19 Feb 2020 to 20 Feb 2020

General remarks:
"(See Enclosure #)" refers to additional information appended to the report.
"(See appended table)" refers to a table appended to the report.
Throughout this report a comma / point is used as the decimal separator.

This report is based on and superseded original report No. 191122136GZU-001, 17 Dec 2019, have
following modification:
1, Added new models SOFAR 11000TL-LV and SOFAR 13500TL-LV, refer to page 9-10 for details.
After evaluation, the following clauses have to test in models SOFAR 11000TL-LV for this
modification
Clause 4.4 Direct current injection;
Clause 4.6 Harmonics and waveform distortion
Clause 4.7 Power factor;
This report shall be used together with the report 200218043GZU-002.

Manufacturer’s Declaration per sub-clause 4.2.5 of IECEE 02:


The application for obtaining a CB Test Certificate Yes
includes more than one factory location and a Not applicable
declaration from the Manufacturer stating that the
sample(s) submitted for evaluation is (are)
representative of the products from each factory has
been provided ............................................................... :

When differences exist; they shall be identified in the General product information section.

TRF No. IEC 61727B


Page 8 of 25 Report No. 200218043GZU-001

Name and address of factory (ies) .......................... : Dongguan SOFAR SOLAR Co., Ltd.
1F - 6F, Building E, No. 1 JinQi Road, Bihu
Industrial Park, Wulian Village, Fenggang Town,
Dongguan City, China

TRF No. IEC 61727B


Page 9 of 25 Report No. 200218043GZU-001

General product information:


The Solar converter is a three-phase type.
The unit is providing EMC filtering at the output toward mains. The unit does not provide galvanic
separation from input to output (transformerless). The output is switched off redundant by the high
-power switching bridge and two relays. This assures that the opening of the output circuit will
also operate in case of one error.

The internal control is redundant built. It consists of Main DSP(UC20) and slave DSP(UC73).
The Main DSP(UC20) can control the relays, measures voltage, and frequency, AC current with inje
cted, insulation resistance and residual current, in addition it tests the array insulation resistance an
d the RCMU circuit before each start up.
The slave DSP(UC73) is using for detecting residual current, also can open the relays independently
and communicate with Main DSP(UC20).
The unit provides two relays in series on Line conductors. When single fault applied to one relay,
alarm anerror code in display panel, another redundant relay provides basic insulation maintained
between the PV array and the mains. All the relays are tested before starting up. Both controllers
(Main DSP(UC20), Slave DSP(UC73) can open the relays

Difference of models:
Both models have identical mechanical and electrical construction except some parameter of the
software architecture in order to control the max output power. The detailed difference as following:

TRF No. IEC 61727B


Page 10 of 25 Report No. 200218043GZU-001

Other than special notice, the model SOFAR 18000TL-LV was as the representative test model in this
report.

TRF No. IEC 61727B


Page 11 of 25 Report No. 200218043GZU-001
IEC61727
Cl. Requirement - Test Result Verdict

4 UTILITY COMPATIBILITY P
The quality of power provided by the PV system for P
the on-site AC loads and for power delivered to the
utility is governed by practices and standards on
voltage, flicker, frequency, harmonics and power
factor.
Deviation from these standards represents out-of- P
bounds conditions and may require the PV system
to sense the deviation and properly disconnect from
the utility system.
4.1 Voltage, current and frequency P
The PV system AC voltage, current and frequency P
are compatible with the utility system.
4.2 Normal voltage operating range P
Utility-interconnected PV systems do not normally P
regulate voltage, they inject current into the utility.
Therefore, the voltage operating range for PV
inverters is selected as a protection function that
responds to abnormal utility conditions, not as a
voltage regulation function.
4.3 Flicker P
The operation of the PV system is not cause voltage P
flicker in excess of limits stated in the relevant
sections of IEC 61000-3-3 for systems less than 16
A or IEC 61000-3-5 for systems with current of 16 A
and above.
4.4 DC injection P
The PV system is not inject DC current greater than (See appended table) P
1 % of the rated inverter output current, into the
utility AC interface under any operating condition.
4.5 Normal frequency operating range P
The PV system operates in synchronism with the P
utility system, and within the frequency
trip limits defined in 5.2.2.
4.6 Harmonics and waveform distortion P
Total harmonic current distortion is less than 5 % at (See appended table) P
rated inverter output. Each individual harmonic is
limited to the percentages listed in Table 1.
Even harmonics in these ranges is less than 25 % of P
the lower odd harmonic limits listed.

TRF No. IEC 61727B


Page 12 of 25 Report No. 200218043GZU-001
IEC61727
Cl. Requirement - Test Result Verdict

4.7 The PV system has a lagging power factor greater P


than 0,9 when the output is greater than 50 % of the
rated inverter output power.
5 PERSONNEL SAFETY AND EQUIPMENT PROTECTION P
This Clause provides information and considerations P
for the safe and proper operation of the utility-
connected PV systems.
5.1 Loss of utility voltage P
To prevent islanding, a utility connected PV system Complied with IEC 62116, See P
ceases to energize the utility system from a de- the separate report for
energized distribution line irrespective of connected reference
loads or other generators within specified time limits.
A utility distribution line can become de-energized P
for several reasons. For example, a substation
breaker opening due to fault conditions or the
distribution line switched out during maintenance.
5.2 Over/under voltage and frequency P
The abnormal utility conditions of concern are P
voltage and frequency excursions above or below
the values stated in this Clause, and the complete
disconnection of the utility, presenting the potential
for a distributed resource island.
5.2.1 Over/under voltage P
When the interface voltage deviates outside the (See appended table) P
conditions specified in Table 2, the photovoltaic
system ceases to energize the utility distribution
system. This applies to any phase of a multiphase
system.

TRF No. IEC 61727B


Page 13 of 25 Report No. 200218043GZU-001
IEC61727
Cl. Requirement - Test Result Verdict

5.2.2 Over/under frequency P


When the utility frequency deviates outside the (See appended table) P
specified conditions the photovoltaic system ceases
to energize the utility line. The unit does not have to
cease to energize if the frequency returns to the
normal utility continuous operation condition within
the specified trip time.
When the utility frequency is outside the range of ±1 P
Hz, the system ceases to energize the utility line
within 0,2 s. The purpose of the allowed range and
time delay is to allow continued operation for short-
term disturbances and to avoid excessive nuisance
tripping in weak-utility system conditions.
5.3 Islanding protection P
The PV system must cease to energize the utility P
line within 2 s of loss of utility.
5.4 Response to utility recovery P
Following an out-of-range utility condition that has (See appended table) P
caused the photovoltaic system to cease energizing,
the photovoltaic system is not energize the utility line
for 20 s to 5 min after the utility service voltage and
frequency have recovered to within the specified
ranges.
5.5 Earthing P
The utility interface equipment is earthed/grounded P
in accordance with IEC 60364-7-712.
5.6 Short circuit protection N/A
The photovoltaic system has short-circuit protection Should consider in the end N/A
in accordance with IEC 60364-7-712. use
5.7 Isolation and switching N/A
A method of isolation and switching is provided in Should consider in the end N/A
accordance with IEC 60364-7-712. use

TRF No. IEC 61727B


Page 14 of 25 Report No. 200218043GZU-001
IEC61727
Cl. Requirement - Test Result Verdict

4.3 TABLE: Flicker P


Model: SOFAR 18000TL-LV
Starting Stopping Running
Limit 4% 4% Pst = 1.0 Plt = 0.65

Test value L1-N 0.53 1.70 0.35 0.34

Test value L2-N 0.18 1.77 0.34 0.31

Test value L3-N 0.16 1.49 0.34 0.32

Supplementary information:

4.4 TABLE: Direct current injection P


Rated Ratio of Measured DC output current between terminals Isolated Limit
output rated transformer ?
L1-L2 L1-L3 L2-L3 L1-N L2-N L3-N (mA)
current output
(mA) (mA) (mA) (mA) (mA) (mA) (Yes/No)
(A) power
(VA)
Model: SOFAR 18000TL-LV
-- -- -- 191.9 141.2 112.2 No 472.4
47.24 25%
-- -- -- 206.3 169.7 128.4 No 472.4
47.24 50%
-- -- -- 196.9 186.9 131.0 No 472.4
47.24 100%
Supplementary information:

4.4 TABLE: Direct current injection P


Rated Ratio of Measured DC output current between terminals Isolated Limit
output rated transformer ?
L1-L2 L1-L3 L2-L3 L1-N L2-N L3-N (mA)
current output
(mA) (mA) (mA) (mA) (mA) (mA) (Yes/No)
(A) power
(VA)
Model: SOFAR 11000TL-LV
-- -- -- 30.60 41.54 27.19 No 288.7
28.87 25%
-- -- -- 33.90 40.52 27.29 No 288.7
28.87 50%
-- -- -- 33.64 47.16 31.07 No 288.7
28.87 100%
Supplementary information:

TRF No. IEC 61727B


Page 15 of 25 Report No. 200218043GZU-001
IEC61727
Cl. Requirement - Test Result Verdict

4.6 TABLE: Harmonics and waveform distortion P


Model: SOFAR 18000TL-LV
Harmonic % of % of % of Harmonic
fundamen fundamen fundamen
fundamen fundamen fundamen Current
tal L1 (A) tal L2 (A) tal L3 (A)
tal) tal) tal) Limits (%)
02 0.0679 0.1483 0.0408 0.0888 0.0907 0.1972 1.0%

03 0.1761 0.3846 0.1338 0.2912 0.1870 0.4065 4.0%

04 0.0471 0.1029 0.0372 0.0809 0.0303 0.0659 1.0%

05 0.3756 0.8206 0.3273 0.7128 0.3376 0.7337 4.0%

06 0.0244 0.0534 0.0273 0.0596 0.0278 0.0605 1.0%

07 0.3786 0.8270 0.3845 0.8373 0.3389 0.7365 4.0%

08 0.0278 0.0607 0.0318 0.0692 0.0301 0.0653 1.0%

09 0.0457 0.0998 0.0554 0.1207 0.0773 0.1679 4.0%

10 0.0345 0.0754 0.0270 0.0589 0.0357 0.0776 0.5%

11 0.1654 0.3614 0.1900 0.4138 0.1207 0.2624 2.0%

12 0.0274 0.0599 0.0244 0.0531 0.0309 0.0673 0.5%

13 0.1099 0.2401 0.0947 0.2063 0.1194 0.2596 2.0%

14 0.0217 0.0474 0.0233 0.0507 0.0247 0.0538 0.5%

15 0.0297 0.0648 0.0320 0.0697 0.0298 0.0648 2.0%

16 0.0217 0.0473 0.0244 0.0532 0.0278 0.0605 0.5%


17 0.0738 0.1612 0.0585 0.1273 0.0508 0.1105 1.5%
18 0.0225 0.0491 0.0231 0.0504 0.0226 0.0491 0.5%
19 0.0592 0.1294 0.0480 0.1046 0.0531 0.1154 1.5%
20 0.0226 0.0494 0.0243 0.0529 0.0230 0.0500 0.5%
21 0.0269 0.0589 0.0244 0.0531 0.0265 0.0575 1.5%
22 0.0235 0.0512 0.0245 0.0533 0.0236 0.0513 0.5%
23 0.0452 0.0987 0.0510 0.1111 0.0443 0.0964 0.6%
24 0.0214 0.0468 0.0230 0.0500 0.0232 0.0504 0.5%
25 0.0396 0.0864 0.0387 0.0843 0.0438 0.0953 0.6%
26 0.0224 0.0490 0.0221 0.0481 0.0223 0.0486 0.5%
27 0.0222 0.0486 0.0235 0.0512 0.0213 0.0462 0.6%
28 0.0213 0.0465 0.0224 0.0487 0.0228 0.0496 0.5%

TRF No. IEC 61727B


Page 16 of 25 Report No. 200218043GZU-001
IEC61727
Cl. Requirement - Test Result Verdict

29 0.0333 0.0727 0.0356 0.0776 0.0293 0.0638 0.6%


30 0.0374 0.0817 0.0439 0.0956 0.0335 0.0728 0.5%
31 0.0311 0.0680 0.0329 0.0716 0.0332 0.0722 0.6%
32 0.0245 0.0534 0.0272 0.0593 0.0260 0.0566 0.5%
33 0.0232 0.0506 0.0232 0.0505 0.0232 0.0504 0.6%

THD 1.507% 1.434% 1.401% 5%


Supplementary information:

4.6 TABLE: Harmonics and waveform distortion P


Model: SOFAR 11000TL-LV
Harmonic % of % of % of Harmonic
fundamen fundamen fundamen
fundamen fundamen fundamen Current
tal L1 (A) tal L2 (A) tal L3 (A)
tal) tal) tal) Limits (%)
02 0.0087 0.0538 0.0152 0.0934 0.0167 0.1025 1.0%

03 0.0197 0.1213 0.0153 0.0941 0.0083 0.0513 4.0%

04 0.0084 0.0514 0.0060 0.0368 0.0060 0.0368 1.0%

05 0.0175 0.1077 0.0385 0.2366 0.0391 0.2405 4.0%

06 0.0062 0.0379 0.0039 0.0240 0.0036 0.0224 1.0%

07 0.0129 0.0793 0.0187 0.1145 0.0281 0.1727 4.0%

08 0.0068 0.0418 0.0048 0.0293 0.0055 0.0338 1.0%

09 0.0373 0.2295 0.0109 0.0670 0.0310 0.1908 4.0%

10 0.0088 0.0544 0.0175 0.1074 0.0133 0.0818 0.5%

11 0.0076 0.0470 0.0123 0.0758 0.0082 0.0505 2.0%

12 0.0036 0.0220 0.0035 0.0215 0.0033 0.0203 0.5%

13 0.0079 0.0489 0.0063 0.0386 0.0112 0.0689 2.0%

14 0.0074 0.0454 0.0133 0.0814 0.0101 0.0624 0.5%

15 0.0053 0.0327 0.0046 0.0281 0.0043 0.0263 2.0%

16 0.0037 0.0225 0.0039 0.0238 0.0051 0.0314 0.5%


17 0.0122 0.0754 0.0082 0.0505 0.0147 0.0906 1.5%
18 0.0037 0.0225 0.0026 0.0161 0.0031 0.0192 0.5%
19 0.0066 0.0409 0.0112 0.0687 0.0097 0.0596 1.5%
20 0.0048 0.0294 0.0040 0.0244 0.0035 0.0214 0.5%

TRF No. IEC 61727B


Page 17 of 25 Report No. 200218043GZU-001
IEC61727
Cl. Requirement - Test Result Verdict

21 0.0046 0.0285 0.0036 0.0223 0.0031 0.0188 1.5%


22 0.0036 0.0221 0.0032 0.0195 0.0038 0.0235 0.5%
23 0.0116 0.0711 0.0113 0.0692 0.0144 0.0888 0.6%
24 0.0021 0.0129 0.0021 0.0129 0.0021 0.0131 0.5%
25 0.0087 0.0537 0.0128 0.0788 0.0134 0.0826 0.6%
26 0.0036 0.0219 0.0036 0.0220 0.0038 0.0235 0.5%
27 0.0034 0.0208 0.0043 0.0266 0.0037 0.0227 0.6%
28 0.0028 0.0172 0.0034 0.0209 0.0038 0.0233 0.5%
29 0.0118 0.0728 0.0131 0.0804 0.0135 0.0828 0.6%
30 0.0029 0.0177 0.0026 0.0161 0.0027 0.0167 0.5%
31 0.0098 0.0602 0.0124 0.0763 0.0140 0.0859 0.6%
32 0.0034 0.0209 0.0037 0.0225 0.0036 0.0221 0.5%
33 0.0033 0.0202 0.0026 0.0160 0.0036 0.0219 0.6%

THD 0.6530 0.6780 0.6590 5%


Supplementary information:

TRF No. IEC 61727B


Page 18 of 25 Report No. 200218043GZU-001
IEC61727
Cl. Requirement - Test Result Verdict

4.7 TABLE: Power factor P


Model: SOFAR 18000TL-LV
Input Output
Curre
Voltage Power Voltage Current Power Power Rated output
No nt (A
(V d.c.) (W) (V a.c.) (A a.c.) (W) factor (+/-) (V.A)
d.c.)
126.17 9.54
1 578.77 6.69 3872.22 126.92 9.57 3654.74 0.9980 (20±5)%
128.61 9.67
126.25 14.02
2 643.32 8.83 5675.55 126.98 14.10 5377.43 0.9989 (30±5)%
128.67 14.17
126.33 18.83
3 645.37 11.74 7578.03 127.03 18.90 7220.19 0.9992 (40±5)%
128.73 19.00
126.42 23.68
4 603.65 15.79 9527.94 127.10 23.74 9077.87 0.9994 (50±5)%
128.80 23.85
126.50 28.47
5 553.03 20.70 11440.96 127.15 28.53 10915.05 0.9994 (60±5)%
128.86 28.65
126.56 33.39
6 634.66 21.22 13462.17 127.19 33.51 12811.46 0.9994 (70±5)%
128.90 33.60
126.61 37.58
7 628.45 24.12 15157.00 127.22 37.71 14420.54 0.9994 (80±5)%
128.94 37.80
126.55 42.46
8 648.85 26.41 17132.76 127.20 42.63 16290.43 0.9993 (90±5)%
128.98 42.69
126.35 45.81
9 661.61 27.94 18487.50 127.05 45.96 17545.92 0.9992 (100±5)%
128.88 46.04
Supplementary information:
Power factor with “+” indicating leading and “-“ indicating lagging.

4.7 TABLE: Power factor P


Model: SOFAR 11000TL-LV
Input Output
Curre
Voltage Power Voltage Current Power Power Rated output
No nt (A
(V d.c.) (W) (V a.c.) (A a.c.) (W) factor (+/-) (V.A)
d.c.)

TRF No. IEC 61727B


Page 19 of 25 Report No. 200218043GZU-001
IEC61727
Cl. Requirement - Test Result Verdict

126.10 5.82
1 696.04 3.31 2301.54 127.05 5.71 2235.45 0.9881 (20±5)%
127.02 5.78
127.17 8.66
2 701.49 4.92 3452.42 127.13 8.59 3369.43 0.9952 (30±5)%
127.08 8.63
126.23 11.56
3 700.71 6.57 4601.30 127.20 11.47 4499.81 0.9975 (40±5)%
127.12 11.49
127.29 14.43
4 701.32 8.20 5750.78 126.24 14.34 5629.26 0.9984 (50±5)%
127.16 14.36
127.35 17.32
5 701.25 9.84 6900.87 127.27 17.23 6756.26 0.9989 (60±5)%
127.20 17.22
127.32 20.23
6 700.34 11.49 8049.53 126.31 20.07 7880.60 0.9992 (70±5)%
127.23 20.08
126.34 23.08
7 701.55 13.12 9200.59 127.34 22.95 9013.20 0.9994 (80±5)%
128.25 22.95
127.37 25.95
8 701.88 14.74 10348.53 127.39 25.81 10134.17 0.9995 (90±5)%
127.30 25.80
127.41 28.86
9 701.08 16.40 11495.99 127.42 28.65 11251.27 0.9996 (100±5)%
127.34 28.64
Supplementary information:
Power factor with “+” indicating leading and “-“ indicating lagging.

TRF No. IEC 61727B


Page 20 of 25 Report No. 200218043GZU-001
IEC61727
Cl. Requirement - Test Result Verdict

5.2.1 & 5.4 TABLE: Under-and over-voltage trip settings and reconnection test P
(1) Under voltage disconnection procedure
Rated Output Required Value of Ratio of Interva Measured Measured
output power min. voltage PCE trip decreased l time tripped disconnectio
voltage (VA) (V) settings (V / s) (s) voltage n time (s)
(V) (V) (V)
127 18000 107.95 107.95 0.22 4 108.60 1.510
Rated Output Required Value of Ratio of Interval Measured Measured
output power min. voltage PCE trip decreased time tripped voltage disconnection
voltage (VA) (V) settings (V / s) (s) (V) time (s)
(V) (V)
127 18000 63.50 63.50 0.22 0.1 64.10 0.076
(2) Under voltage reconnection procedure
Ratio of voltage rapidly Reconnection voltage (V) Reconnection time (s)
decreased
(V / s)
0.22 110.10 71.52
(3) Over voltage disconnection procedure
Rated Output Required Value of Ratio of Interva Measured Measured
output power max. voltage PCE trip increased l time tripped disconnectio
voltage (VA) (V) settings (V / s) (s) voltage n time (s)
(V) (V) (V)
127 18000 139.70 139.70 0.22 4 139.54 1.510
Rated Output Required Value of Ratio of Interval Measured Measured
output power max. voltage PCE trip increased time tripped voltage disconnection
voltage (VA) (V) settings (V / s) (s) (V) time (s)
(V) (V)
127 18000 171.45 171.45 0.22 0.1 171.26 0.040
(4) Over voltage reconnection procedure
Ratio of voltage rapidly Reconnection voltage (V) Reconnection time (s)
decreased
(V / s)
0.22 138.06 70.97
Supplementary information:

TRF No. IEC 61727B


Page 21 of 25 Report No. 200218043GZU-001
IEC61727
Cl. Requirement - Test Result Verdict

5.2.2 & 5.4 TABLE: Over/under frequency trip settings and reconnection test P
(1) Under frequency disconnection procedure
Rated Output Required Value of Ratio of Interva Measured Measured
output power min. PCE trip decreased l time tripped disconnectio
frequency (VA) frequency settings (Hz / s) (s) frequency n time (s)
(Hz) (Hz) (Hz) (Hz)
60 18000 59 59 0.01 0.3 59.00 0.080

(2) Under frequency reconnection procedure


Ratio of frequency rapidly Reconnection frequency (Hz) Reconnection time (s)
decreased (Hz / s)
0.01 >59 70.03
(3) Over frequency disconnection procedure
Rated Output Required Value of Ratio of Interva Measured Measured
output power max. PCE trip increased l time tripped disconnectio
frequency (VA) frequency settings (Hz / s) (s) frequency n time (s)
(Hz) (Hz) (Hz) (Hz)
60 18000 61 61 0.01 0.3 61.00 0.104
(4) Over frequency reconnection procedure
Ratio of frequency rapidly Reconnection frequency (Hz) Reconnection time (s)
decreased (Hz / s)
0.01 <61 70.16
Supplementary information:

TRF No. IEC 61727B


Page 22 of 25 Report No. 200218043GZU-001
IEC61727
Cl. Requirement - Test Result Verdict

5.3 TABLE: tested condition and run-on time P


Model: SOFAR 18000TL-LV
No. PEUT (% Reactiv PAC QAC Run-on PEUT Actual VDC Which
of EUT e load time(ms) (KW) Qf (V) load is
rating) (% of (Var) selected
normal) to be
adjusted
(R or L)
Test condition A
1 100 100 0 0 399.5 17.9 1.00 827 /
2 100 100 -5 -5 183.5 17.9 0.98 827 /
3 100 100 -5 0 270.5 17.9 0.96 827 /
4 100 100 -5 +5 217.0 17.9 0.94 827 /
5 100 100 0 -5 223.5 17.9 1.02 827 /
6 100 100 0 +5 228.5 17.9 0.98 827 /
7 100 100 +5 -5 213.0 17.9 1.07 827 /
8 100 100 +5 0 257.0 17.9 1.06 827 /
9 100 100 +5 +5 199.5 17.9 1.03 827 /
Test condition B
10 66 66 0 0 350.0 10.8 1.00 726 /
11 66 66 0 -5 209.0 10.8 1.02 726 L
12 66 66 0 -4 239.5 10.8 1.01 726 L
13 66 66 0 -3 220.0 10.8 1.01 726 L
14 66 66 0 -2 313.5 10.8 1.01 726 L
15 66 66 0 -1 300.7 10.8 1.00 726 L
16 66 66 0 1 207.0 10.8 0.99 726 L
17 66 66 0 2 185.5 10.8 0.99 726 L
18 66 66 0 3 182.0 10.8 0.98 726 L
19 66 66 0 4 172.5 10.8 0.98 726 L
20 66 66 0 5 160.7 10.8 0.97 726 L
Test condition C
21 33 33 0 0 342.5 5.4 1.00 605 /
22 33 33 0 -5 72.3 5.4 1.03 605 L
23 33 33 0 -4 84.5 5.4 1.02 605 L
24 33 33 0 -3 91.3 5.4 1.02 605 L
25 33 33 0 -2 92.5 5.4 1.01 605 L
26 33 33 0 -1 104.0 5.4 1.01 605 L
27 33 33 0 1 213.5 5.4 1.00 605 L
28 33 33 0 2 201.0 5.4 0.99 605 L
29 33 33 0 3 172.5 5.4 0.99 605 L
30 33 33 0 4 215.5 5.4 0.99 605 L
31 33 33 0 5 190.0 5.4 0.98 605 L

TRF No. IEC 61727B


Page 23 of 25 Report No. 200218043GZU-001
IEC61727
Cl. Requirement - Test Result Verdict

Supplementary information:
For test condition A:
If any of the recorded run-on times are longer than the one recorded for the rated balance condition, then
the non-shaded parameter combinations also require testing.
For test condition B and C:
If run-on times are still increasing at the 95 % or 105 % points, additional 1 % increments is taken until
run-on times begin decreasing.

TRF No. IEC 61727B


Page 24 of 25 Report No. 200218043GZU-001

Appendix 1: Photos

Overview

Rear view

TRF No. IEC 61727B


Page 25 of 25 Report No. 200218043GZU-001

Appendix 1: Photos

Connection view

Internal view

--- End of test report---