Photovoltaic (PV) Systems - Characteristics of The Utility Interface
Photovoltaic (PV) Systems - Characteristics of The Utility Interface
TEST REPORT
IEC 61727
Photovoltaic (PV) systems –
Characteristics of the utility interface
Name of Testing Laboratory Intertek Testing Services Shenzhen Ltd. Guangzhou Branch
preparing the Report ..................... : Block E, No.7-2 Guang Dong Software Science Park, Caipin
Road, Guangzhou Science City, GETDD, Guangzhou, China
Applicant’s name ........................... : Shenzhen SOFAR SOLAR Co., Ltd.
Address ........................................... : 401, Building 4, AnTongDa Industrial Park, District 68,
XingDong Community, XinAn Street, BaoAn District,
Shenzhen, China
Test specification:
Standard ......................................... : IEC 61727:2004
Test procedure ............................... : Type approval
Non-standard test method ............ : N/A
Test Report Form No. .................... : IEC61727B
Test Report Form(s) Originator .... : TÜ V SÜ D Product Service GmbH
Master TRF ..................................... : Dated 2017-11-03
Copyright © 2017 IEC System of Conformity Assessment Schemes for Electrotechnical
Equipment and Components (IECEE System). All rights reserved.
This publication may be reproduced in whole or in part for non-commercial purposes as long as the IECEE is acknowledged as
copyright owner and source of the material. IECEE takes no responsibility for and will not assume liability for damages resulting
from the reader's interpretation of the reproduced material due to its placement and context.
If this Test Report Form is used by non-IECEE members, the IECEE/IEC logo and the reference to the
CB Scheme procedure shall be removed.
This report is not valid as a CB Test Report unless signed by an approved CB Testing Laboratory
and appended to a CB Test Certificate issued by an NCB in accordance with IECEE 02.
General disclaimer:
The test results presented in this report relate only to the object tested.
This report shall not be reproduced, except in full, without the written approval of the Issuing CB Testing
Laboratory. The authenticity of this Test Report and its contents can be verified by contacting the NCB,
responsible for this Test Report.
Page 2 of 25 Report No. 200218043GZU-001
Nominal
output 60Hz
Frequency
Max.output
3*32A 3*40A 3*48A 3*53A
current
Nominal
11000 W 13500 W 16500 W 18000 W
output power
Max.output 11000 13500 16500 18000
power VA VA VA VA
Power factor
0.8Leading~0.8Lagging
range
Safety level Class I
Ingress
IP 65
Protection
Operation
Ambient -25℃ - +60℃
Temperature
Software
V2.00
version
Responsible Testing Laboratory (as applicable), testing procedure and testing location(s):
Summary of testing:
Note:
1. The above markings are the minimum requirements required by the safety standard. For the
final production samples, the additional markings which do not give rise to misunderstanding
may be added.
2. Label is attached on the side surface of enclosure and visible after installation.
General remarks:
"(See Enclosure #)" refers to additional information appended to the report.
"(See appended table)" refers to a table appended to the report.
Throughout this report a comma / point is used as the decimal separator.
This report is based on and superseded original report No. 191122136GZU-001, 17 Dec 2019, have
following modification:
1, Added new models SOFAR 11000TL-LV and SOFAR 13500TL-LV, refer to page 9-10 for details.
After evaluation, the following clauses have to test in models SOFAR 11000TL-LV for this
modification
Clause 4.4 Direct current injection;
Clause 4.6 Harmonics and waveform distortion
Clause 4.7 Power factor;
This report shall be used together with the report 200218043GZU-002.
When differences exist; they shall be identified in the General product information section.
Name and address of factory (ies) .......................... : Dongguan SOFAR SOLAR Co., Ltd.
1F - 6F, Building E, No. 1 JinQi Road, Bihu
Industrial Park, Wulian Village, Fenggang Town,
Dongguan City, China
The internal control is redundant built. It consists of Main DSP(UC20) and slave DSP(UC73).
The Main DSP(UC20) can control the relays, measures voltage, and frequency, AC current with inje
cted, insulation resistance and residual current, in addition it tests the array insulation resistance an
d the RCMU circuit before each start up.
The slave DSP(UC73) is using for detecting residual current, also can open the relays independently
and communicate with Main DSP(UC20).
The unit provides two relays in series on Line conductors. When single fault applied to one relay,
alarm anerror code in display panel, another redundant relay provides basic insulation maintained
between the PV array and the mains. All the relays are tested before starting up. Both controllers
(Main DSP(UC20), Slave DSP(UC73) can open the relays
Difference of models:
Both models have identical mechanical and electrical construction except some parameter of the
software architecture in order to control the max output power. The detailed difference as following:
Other than special notice, the model SOFAR 18000TL-LV was as the representative test model in this
report.
4 UTILITY COMPATIBILITY P
The quality of power provided by the PV system for P
the on-site AC loads and for power delivered to the
utility is governed by practices and standards on
voltage, flicker, frequency, harmonics and power
factor.
Deviation from these standards represents out-of- P
bounds conditions and may require the PV system
to sense the deviation and properly disconnect from
the utility system.
4.1 Voltage, current and frequency P
The PV system AC voltage, current and frequency P
are compatible with the utility system.
4.2 Normal voltage operating range P
Utility-interconnected PV systems do not normally P
regulate voltage, they inject current into the utility.
Therefore, the voltage operating range for PV
inverters is selected as a protection function that
responds to abnormal utility conditions, not as a
voltage regulation function.
4.3 Flicker P
The operation of the PV system is not cause voltage P
flicker in excess of limits stated in the relevant
sections of IEC 61000-3-3 for systems less than 16
A or IEC 61000-3-5 for systems with current of 16 A
and above.
4.4 DC injection P
The PV system is not inject DC current greater than (See appended table) P
1 % of the rated inverter output current, into the
utility AC interface under any operating condition.
4.5 Normal frequency operating range P
The PV system operates in synchronism with the P
utility system, and within the frequency
trip limits defined in 5.2.2.
4.6 Harmonics and waveform distortion P
Total harmonic current distortion is less than 5 % at (See appended table) P
rated inverter output. Each individual harmonic is
limited to the percentages listed in Table 1.
Even harmonics in these ranges is less than 25 % of P
the lower odd harmonic limits listed.
Supplementary information:
126.10 5.82
1 696.04 3.31 2301.54 127.05 5.71 2235.45 0.9881 (20±5)%
127.02 5.78
127.17 8.66
2 701.49 4.92 3452.42 127.13 8.59 3369.43 0.9952 (30±5)%
127.08 8.63
126.23 11.56
3 700.71 6.57 4601.30 127.20 11.47 4499.81 0.9975 (40±5)%
127.12 11.49
127.29 14.43
4 701.32 8.20 5750.78 126.24 14.34 5629.26 0.9984 (50±5)%
127.16 14.36
127.35 17.32
5 701.25 9.84 6900.87 127.27 17.23 6756.26 0.9989 (60±5)%
127.20 17.22
127.32 20.23
6 700.34 11.49 8049.53 126.31 20.07 7880.60 0.9992 (70±5)%
127.23 20.08
126.34 23.08
7 701.55 13.12 9200.59 127.34 22.95 9013.20 0.9994 (80±5)%
128.25 22.95
127.37 25.95
8 701.88 14.74 10348.53 127.39 25.81 10134.17 0.9995 (90±5)%
127.30 25.80
127.41 28.86
9 701.08 16.40 11495.99 127.42 28.65 11251.27 0.9996 (100±5)%
127.34 28.64
Supplementary information:
Power factor with “+” indicating leading and “-“ indicating lagging.
5.2.1 & 5.4 TABLE: Under-and over-voltage trip settings and reconnection test P
(1) Under voltage disconnection procedure
Rated Output Required Value of Ratio of Interva Measured Measured
output power min. voltage PCE trip decreased l time tripped disconnectio
voltage (VA) (V) settings (V / s) (s) voltage n time (s)
(V) (V) (V)
127 18000 107.95 107.95 0.22 4 108.60 1.510
Rated Output Required Value of Ratio of Interval Measured Measured
output power min. voltage PCE trip decreased time tripped voltage disconnection
voltage (VA) (V) settings (V / s) (s) (V) time (s)
(V) (V)
127 18000 63.50 63.50 0.22 0.1 64.10 0.076
(2) Under voltage reconnection procedure
Ratio of voltage rapidly Reconnection voltage (V) Reconnection time (s)
decreased
(V / s)
0.22 110.10 71.52
(3) Over voltage disconnection procedure
Rated Output Required Value of Ratio of Interva Measured Measured
output power max. voltage PCE trip increased l time tripped disconnectio
voltage (VA) (V) settings (V / s) (s) voltage n time (s)
(V) (V) (V)
127 18000 139.70 139.70 0.22 4 139.54 1.510
Rated Output Required Value of Ratio of Interval Measured Measured
output power max. voltage PCE trip increased time tripped voltage disconnection
voltage (VA) (V) settings (V / s) (s) (V) time (s)
(V) (V)
127 18000 171.45 171.45 0.22 0.1 171.26 0.040
(4) Over voltage reconnection procedure
Ratio of voltage rapidly Reconnection voltage (V) Reconnection time (s)
decreased
(V / s)
0.22 138.06 70.97
Supplementary information:
5.2.2 & 5.4 TABLE: Over/under frequency trip settings and reconnection test P
(1) Under frequency disconnection procedure
Rated Output Required Value of Ratio of Interva Measured Measured
output power min. PCE trip decreased l time tripped disconnectio
frequency (VA) frequency settings (Hz / s) (s) frequency n time (s)
(Hz) (Hz) (Hz) (Hz)
60 18000 59 59 0.01 0.3 59.00 0.080
Supplementary information:
For test condition A:
If any of the recorded run-on times are longer than the one recorded for the rated balance condition, then
the non-shaded parameter combinations also require testing.
For test condition B and C:
If run-on times are still increasing at the 95 % or 105 % points, additional 1 % increments is taken until
run-on times begin decreasing.