Professional Documents
Culture Documents
Three-Point Hitch Dynamometer Design and Calibration: Assoc. Member Asae
Three-Point Hitch Dynamometer Design and Calibration: Assoc. Member Asae
Three-Point Hitch Dynamometer Design and Calibration: Assoc. Member Asae
and Calibration
X-CTg)
M--H
.-, i
#
* •-• i
o
at
o! o o I oS ;o
fu
1073.2-
25.4<£
tin y h~Tyn
20 40
70
60
50
o^ 40
Or 30
O
or 20
20 30
20
APPLIED FORCE (kN) APPLIED FORCE
Four loading patterns were used in the calibration and load cells.
these were: loads parallel to the assumed coordinates
axes x, y and z; and a combined or skewed load. Each CONCLUSIONS
run was performed by applying a load in small steps up
to 45 kN in tension and compression. Application of the The three-point hitch dynamometer was designed,
load in this manner gave a quasi-continuous set of data. constructed and calibrated. The calibration results
The 45 kN upper limit was imposed as the maximum showed that the instrument was accurate to within 5%
load which could be transmitted through the standard for draft forces ranging from 5 kN to 45 kN in any
cell. A larger standard cell with a greater load capacity direction. Errors in recovery of the applied load were
could be used to calibrate up to 60 kN in the x and y attributable to the alignment of the load cells and the
directions, as the reaction on the dynamometer would be friction in the ball end connections between the load cells
distributed over more than one load cell. and the supporting frame. The dynamometer performed
The data was sorted and coded before conducting a well in the field and satisfied the design requirements.
linear regression. The results of skewed loading in
tension and compression are shown in Fig. 3. Excellent References
1. ASAE S278.6. Attachment of implements to agricultural wheel
agreement between the applied load and the computed tractors equipped with quick-attaching coupler. Yearbook, 1983, pp.
load was exhibited. The fit of data was almost perfect, 151-153. ASAE Standards, ASAE, St. Joseph, MI 49085.
with R squared values close to 1.000. The percentage of 2. Barker, G. L., L. A. Smith and R. F. Colwick. 1981. Three-point
error in both the force and moment measurements was hitch dynamometer for direction force measurement. ASAE Paper
significant at small loads, as shown in Fig. 4. The error 81-1044, ASAE, St. Joseph, MI 49085.
3. Johnson, C. E. and W. B. Voorhees. 1979. A force dynamometer
in the calculated force and moment exceeded 5% below 5 for three-point hitches. TRANSACTIONS of the ASAE 22(2):226-228.
kN when the skewed load was applied. Thus, the 4. Morling. R. W. 1963. Soil force analysis as applied to tillage
dynamometer is not recommended for use with equipment. ASAE Paper 63-149, ASAE, St. Joseph, MI 49085.
implements requiring less than 5 kN draft if errors are to 5. Palmer, J. 1984. Evaluation of peak loads and load cycles of
implements in soil. ASAE Paper 84-1550, ASAE, St. Joseph, MI
be kept to within 5%. This error is thought to be due to 49085.
friction and alignment between the elements of the 6. Upadhyaya, S. K. 1984. Prediction of implement draft. ASAE
dynamometer, which causes cross interference between Paper 84-1518, ASAE, St. Joseph, MI 49085.