Professional Documents
Culture Documents
Uso Del Factor de Redundancia
Uso Del Factor de Redundancia
Use of the
Redundancy
Factor
The redundancy factor, ρ, is used in association with the seismic load com-
binations that are specified in Section 12.4. In particular, in accordance with
Eq. (12.4-3):
Fig. G13-1
Evaluation of the * * * *
redundancy factor for
various buildings * *
* *
* *
(D) (E) (F)
35’
B V D
20’ G H
Y
25’ 20’ 35’ 20’ 25’
X
60
40
20
0
0.0 0.5 1.0 1.5 2.0 2.5 3.0 3.5
Deformaon (in.)
each, the total lateral capacity of the system is 400 kip. Recall that the force-
displacement plot for this four-wall system is shown by the upper curve in
Fig. G13-4. The displacement shown in the figure is the y direction displace-
ment δ2. The first change of slope in the curve occurs when walls C and D
yield, and the second change occurs when walls A and B yield.
When wall C is removed, the center of rigidity moves 9.375 ft to the
left. When an elastic analysis is performed, the system can resist a lateral
load of only 230 kip because wall D reaches its 100-kip capacity. At this
point, walls A and B resist 65 kip each. Additionally, the ratio of the displace-
ment at point δ2 with respect to the displacement at point δ1 is 1.35. Hence,
a torsional irregularity, but not an extreme irregularity, exists. The ratio of
the resisting force of the three-wall system to that of the four-wall system is
230/370 or 0.621. On this basis, the system must be designed with ρ = 1.3
because it loses more than 33% of its strength.
From the perspective of an inelastic analysis, the three-wall system can
resist a total of 300 kip. This is shown by the force-displacement diagram
(the lower curve) in Fig. G13-4. The ratio of the inelastic resisting force of
the three-wall system to that of the four-wall system is 300/400 = 0.75. In
this case, the system could theoretically be designed with ρ = 1.0 because it
passes both the strength and the nonextreme torsion irregularity tests.
Two final points are made regarding the use of the redundancy factor:
1. When it is determined that ρ = 1.3 in a given direction, the factor
of 1.3 applies only to load combinations where seismic forces are
applied in that direction. Also, the load combination with ρ = 1.3
is used for all components and connections developing seismic
forces when the load is applied in that direction. This includes
elements and component from the bottom to the top of the struc-
ture and is not limited to those elements and components in levels
resisting more than 35% of the seismic base shear.
2. The condition (a) test of Section 12.3.4.2 applies for buildings with
different types of lateral load–resisting elements in a given direc-
tion. For example, for a dual moment-frame shear wall system, the
test would be performed with a single wall removed and then with
a single beam removed from the moment frame.
Seismic Loads: Guide to the Seismic Load Provisions of ASCE 7-10 87
This page intentionally left blank