Standard Factory Test
Standard Factory Test
1. Standard Conditions
Ambient temperature on test bench: <40°C (depending on actual outside ambient
temperature).
Generator Sets with air-to-air charge air cooled engines will be tested incl. the standard
set mounted mechanical radiator cooler.
Generator sets with air-to-water charge air cooling will be tested without optional cooling
equipment. The generator set will be connected to the cooling equipment of the test
bench.
The generator set will be filled with fluids and lubricants according to the engine
manufacturers fluids and lubricants specification.
The generator set will be operated with fuel according to the engine manufacturers fluids
and lubricants specification.
OER-DV-0003
Control Cabinet & Software
Parameterization of control panel.
Setting up and testing communication between engine controller and genset controller.
Checking and adjusting all control cabinet mounted components.
3. Test Run
Pre-Testing
Testing/ checking of (actual scope of testing depends on generator set configuration):
Manual start/stop
Emergency stop
Lube oil level
Coolant level
Alarms for low coolant level
Voltage adjustment via control panel
Speed adjustment via control panel
Idle Run
Testing of alarm & emergency shutoff in case of:
Low oil pressure
High engine temperature
Over frequency
OER-DV-0003
Load Run
Procedure
Protocolled Data
Measurement of the protocolled data will be carried out at the end of each operating period.
Frequency
Voltage
Current (3 phases)
Power factor
Active power
Fuel consumption
Lube oil pressure
Lube oil temperature
Coolant temperature
Air intake temperature before engine
Water temperature before charge air cooler
Intake air temperature before cylinder
Intake air pressure before cylinder
Engine speed
Requested torque
OER-DV-0003
Step Load Testing
Step load testing according to ISO 8528 performance class G3
4. Final Inspection
Check for the following items:
Automatic circuit breakers are tripped
Battery is disconnected
All covers are attached
Name plates are attached
Generator set is cleaned
Factory test procedure and specification are subject to change without notice.