2.3 Status and Metering: 2.3.1 Overview
2.3 Status and Metering: 2.3.1 Overview
2.3.1 Overview
Port
Access Eth /
Register Size Description
Rights RS485
40101 1 Status Word 1 R Eth / RS485
40102 1 Status Word 2 R Eth / RS485
40103 1 Reserved R Eth / RS485
40104 1 Reserved R Eth / RS485
40105 1 Limiter Status Word R Eth / RS485
40106 1 Alarm/Protection Status Word R Eth / RS485
40107 1 Digital output Status Word R Eth / RS485
40108 1 Digital Input Status Word R Eth / RS485
40109 1 Virtual Digital Input Status Word (from AI) R Eth / RS485
40110 1 reserved R Eth / RS485
40111 … 40120 10 Read Setpoints R Eth / RS485
40121 … 30130 10 Read Analog IO R Eth / RS485
40131 … 40150 18 Read Metering R Eth / RS485
3 EXC ON 0: OFF; 1: ON na
5 PF Selected 0: OFF; 1: ON na
11 Standby 0: OFF; 1: ON na
0: OFF
13 PSS Active na
1: ON, PSS is contributing
10 FCB ON 0: OFF; 1: ON na
11 Reserved na
12 Reserved na
®
2-8 3BHS358281 E80 Rev. - UNITROL 1000 MODBUS Manual
7 Max Ie Active 0: OFF; 1: ON na
14 Reserved na
15 Reserved na
14 Reserved na
15 Reserved na
Digital output status shows status of signals that can also be routed to digital outputs.
40107; Digtial output status word
Bit Name Description Default
0 Boost 0: OFF; 1: ON na
7 reserved 0: OFF; 1: ON na
1 DI 2 0: OFF; 1: ON 0
2 DI 3 0: OFF; 1: ON 0
3 DI 4 0: OFF; 1: ON 0
4 DI 5 0: OFF; 1: ON 0
5 DI 6 0: OFF; 1: ON 0
6 DI 7 0: OFF; 1: ON 0
7 DI 8 0: OFF; 1: ON 0
8 DI 9 0: OFF; 1: ON 0
9 DI 10 0: OFF; 1: ON 0
10 DI 11 0: OFF; 1: ON 0
11 DI 12 0: OFF; 1: ON 0
12 reserved 0
13 reserved 0
14 reserved 0
15 reserved 0
40109; Virtual Input Status Word (Analog input used as digital inputs)
Bit Name Description Default
0: OFF (Ai1 = 0V)
0 DI13 0
1: ON (AI1 = above threshold)
®
2-10 3BHS358281 E80 Rev. - UNITROL 1000 MODBUS Manual
40109; Virtual Input Status Word (Analog input used as digital inputs)
Bit Name Description Default
0: OFF (Ai1 = 0V)
1 DI14 0
1: ON (AI1 = below threshold)
0: OFF (Ai2 = 0V)
2 DI15 0
1: ON (AI2 = above threshold)
0: OFF (Ai2 = 0V)
3 DI16 0
1: ON (AI2 = below threshold)
0: OFF (Ai3 = 0V)
4 DI17 0
1: ON (AI3 = above threshold)
0: OFF (Ai3 = 0V)
5 DI18 0
1: ON (AI3 = below threshold)
6 reserved 0
7 reserved 0
8 reserved 0
9 reserved 0
10 reserved 0
11 reserved 0
12 reserved 0
13 reserved 0
14 reserved 0
15 reserved 0
Remark:
If analog inputs AI1-3 are not configured as digital inputs, DI3-D18 are set to default value “0”.
Remark to PF setpoint:
Bit Value: -250 -500 -900 +/-1000 +900 +500 +250
PF: -0.25 -0.5 -0.9 1.0 +0.9 +0.5 +0.25
40124 reserved
40125 reserved
40128 reserved
40129 reserved
40130 reserved
®
2-12 3BHS358281 E80 Rev. - UNITROL 1000 MODBUS Manual