2.3 Status and Metering

2.3.1 Overview

Port
Access Eth /
Register Size Description
Rights RS485
40101 1 Status Word 1 R Eth / RS485
40102 1 Status Word 2 R Eth / RS485
40103 1 Reserved R Eth / RS485
40104 1 Reserved R Eth / RS485
40105 1 Limiter Status Word R Eth / RS485
40106 1 Alarm/Protection Status Word R Eth / RS485
40107 1 Digital output Status Word R Eth / RS485
40108 1 Digital Input Status Word R Eth / RS485
40109 1 Virtual Digital Input Status Word (from AI) R Eth / RS485
40110 1 reserved R Eth / RS485
40111 … 40120 10 Read Setpoints R Eth / RS485
40121 … 30130 10 Read Analog IO R Eth / RS485
40131 … 40150 18 Read Metering R Eth / RS485

2.3.2 Status Words bit codings

40101; Status Word 1


Bit Name Description Default
0: Fieldbus access not granted
0 Modbus Request Selected na
1: Fieldbus access granted
0: Fieldbus not blocked
1 Fieldbus Blocked na
1: Fieldbus blocked
0: Remote setpoint not released
2 Setpoint Released na
1: Remote setpoint released

3 EXC ON 0: OFF; 1: ON na

4 Auto Selected 0: OFF; 1: ON na

5 PF Selected 0: OFF; 1: ON na

6 Var Selected 0: OFF; 1: ON na

7 Manual Selected 0: OFF; 1: ON na

8 Open Loop Selected 0: OFF; 1: ON na

9 VDC Selected 0: OFF; 1: ON na

10 Synchronize Selected 0: OFF; 1: ON na

11 Standby 0: OFF; 1: ON na

12 Limit Active 0: OFF; 1: ON na

0: OFF
13 PSS Active na
1: ON, PSS is contributing

2-7 3BHS358281 E80 Rev. - UNITROL® 1000 MODBUS Manual



40101; Status Word 1
Bit Name Description Default
14 SW Alarm 0: OFF; 1: ON na

15 Keep Alive Feedback 0: OFF; 1: ON na

40102; Status Word 2


Bit Name Description Default
0: Writing parameters are blocked
0 Parameter Change Released na
1: Write access to parameter area is granted
Parameter Change Not
1 Bit 0 Inverted na
Released
0: Values inside range
2 Values Outside Min-Max Limits 1: Parameter/signal value is out of range, bit is na
reset after reading
3 Gen CB Closed Status 0: open; 1: closed na
Status of digital input signal
4 Parallel with Grid Status na
0: OFF; 1: ON
No Load
5 0: OFF; 1: ON na
(Generator Status)
Internal status of AVR
6 Grid na
0: OFF; 1: ON

7 Prim. Net 0: OFF; 1: ON na

8 Sec. Net 0: OFF; 1: ON na

9 Remote SP Enable (AI) 0: OFF; 1: ON na

10 FCB ON 0: OFF; 1: ON na

11 Reserved na

12 Reserved na

Can communication status


13 CAN Double Channel Status na
0 OFF; 1: ON

14 Parameters Saved 0: OFF; 1: ON na

15 System OK Do not use, only for production test purpose na

2.3.3 Limiters status word bit coding

40105; Limiter Status word


Bit Name Description Default
0 Limit Active 0: OFF; 1: ON na

1 V/Hz Limit Active 0: OFF; 1: ON na

2 SP Limit Reached 0: OFF; 1: ON na

3 Sp Minimum Reached 0: OFF; 1: ON na

4 SP Maximum Reached 0: OFF; 1: ON na

5 Operational Limit Active 0: OFF; 1: ON na

6 Min Ie Active 0: OFF; 1: ON na

®
2-8 3BHS358281 E80 Rev. - UNITROL 1000 MODBUS Manual

7 Max Ie Active 0: OFF; 1: ON na

8 Min PQ Active 0: OFF; 1: ON na

9 Min UM Active 0: OFF; 1: ON na

10 Max UM Active 0: OFF; 1: ON na

11 Max IM Active 0: OFF; 1: ON na

12 Min IM Active 0: OFF; 1: ON na

13 Voltage Relay Active 0: OFF; 1: ON na

14 Reserved na

15 Reserved na

2.3.4 Alarm/Protection status

40106; Alarm/Protection word


Bit Name Description Default
0 SW Alarm 0: OFF; 1: ON na

1 Diode Alarm 0: OFF; 1: ON na

2 Diode Trip 0: OFF; 1: ON na

3 SW Alarm or Diode Trip 0: OFF; 1: ON na


Loss Of Modbus Communication
4 0: OFF; 1: ON na
Keep alive signal was not toggled
5 FCB Alarm 0: OFF; 1: ON na

6 External Alarm 0: OFF; 1: ON na

7 Supervision Alarm 0: OFF; 1: ON na

8 Supervision Trip 0: OFF; 1: ON na

9 Switch Over 0: OFF; 1: ON na

10 Supervission Alarm 1 0: OFF; 1: ON na

11 Supervission Alarm 2 0: OFF; 1: ON na

12 Monitor Alarm 1 0: OFF; 1: ON na

13 Monitor Alarm 1 0: OFF; 1: ON na

14 Reserved na

15 Reserved na

2.3.5 Digital output status

Digital output status shows status of signals that can also be routed to digital outputs.
40107; Digtial output status word
Bit Name Description Default
0 Boost 0: OFF; 1: ON na

1 Field Flashing 0: OFF; 1: ON na

2 Voltage Relay 0: OFF; 1: ON na

2-9 3BHS358281 E80 Rev. - UNITROL® 1000 MODBUS Manual



3 Close CB Command 0: OFF; 1: ON na

4 Sync Check 0: OFF; 1: ON na

5 Close FCB Command 0: OFF; 1: ON na

6 Open FCB Command 0: OFF; 1: ON na

7 reserved 0: OFF; 1: ON na

8 DO5 (digital output state) 0: OFF; 1: ON na

9 DO6 (digital output state) 0: OFF; 1: ON na

10 DO7 (digital output state) 0: OFF; 1: ON na

11 DO8 (digital output state) 0: OFF; 1: ON na

12 DO1 (digital output state) 0: OFF; 1: ON na

13 DO2 (digital output state) 0: OFF; 1: ON na

14 DO3 (digital output state) 0: OFF; 1: ON na

15 DO4 (digital output state) 0: OFF; 1: ON na

2.3.6 Digital inputs readings

40108; Dgital Input Status Word


Bit Name Description Default
0 DI 1 (digital input state) 0: OFF; 1: ON 0

1 DI 2 0: OFF; 1: ON 0

2 DI 3 0: OFF; 1: ON 0

3 DI 4 0: OFF; 1: ON 0

4 DI 5 0: OFF; 1: ON 0

5 DI 6 0: OFF; 1: ON 0

6 DI 7 0: OFF; 1: ON 0

7 DI 8 0: OFF; 1: ON 0

8 DI 9 0: OFF; 1: ON 0

9 DI 10 0: OFF; 1: ON 0

10 DI 11 0: OFF; 1: ON 0

11 DI 12 0: OFF; 1: ON 0

12 reserved 0

13 reserved 0

14 reserved 0

15 reserved 0

40109; Virtual Input Status Word (Analog input used as digital inputs)
Bit Name Description Default
0: OFF (Ai1 = 0V)
0 DI13 0
1: ON (AI1 = above threshold)

®
2-10 3BHS358281 E80 Rev. - UNITROL 1000 MODBUS Manual

40109; Virtual Input Status Word (Analog input used as digital inputs)
Bit Name Description Default
0: OFF (Ai1 = 0V)
1 DI14 0
1: ON (AI1 = below threshold)
0: OFF (Ai2 = 0V)
2 DI15 0
1: ON (AI2 = above threshold)
0: OFF (Ai2 = 0V)
3 DI16 0
1: ON (AI2 = below threshold)
0: OFF (Ai3 = 0V)
4 DI17 0
1: ON (AI3 = above threshold)
0: OFF (Ai3 = 0V)
5 DI18 0
1: ON (AI3 = below threshold)
6 reserved 0

7 reserved 0

8 reserved 0

9 reserved 0

10 reserved 0

11 reserved 0

12 reserved 0

13 reserved 0

14 reserved 0

15 reserved 0

Remark:
If analog inputs AI1-3 are not configured as digital inputs, DI3-D18 are set to default value “0”.

2.3.7 Read Setpoint

Bit values range Scaling


Reg. Description
Default Min Max Bits Value Unit
40111 Read Setpoint - Auto Absolute 0 0 32000 1000 1 kV

40112 Read Setpoint - Manual Absolute 0 0 10000 10 1 A

40113 Read Setpoint - PF Absolute 0 -1000 1000 1000 1

40114 Read Setpoint - VAR Absolute 0 -32000 32000 100 1 MVAr

40115 Read Setpoint - reserved 0 0 0

40116 Read Setpoint - Auto Relative 0 0 24576 16384 100 %

40117 Read Setpoint - Manual Relative 0 0 24576 8192 100 %

40118 Read Setpoint - VAR Relative 0 -16384 16384 8192 100 %


-32768 32676
40119 Read Setpoint - Open Loop Relative 0 32768 50 %
(0%) (100%)
40120 Read Setpoint - reserved 0 0 0

Remark to PF setpoint:
Bit Value: -250 -500 -900 +/-1000 +900 +500 +250
PF: -0.25 -0.5 -0.9 1.0 +0.9 +0.5 +0.25

2-11 3BHS358281 E80 Rev. - UNITROL® 1000 MODBUS Manual



2.3.8 Read Analog I/O

Bit values range Scaling


Reg. Description
Default Min Max Bits Value Unit
40121 Analog Input 1 (-10V to +10V) 0 -16384 16383 16383 10 V

40122 Analog Input 2 (-10V to +10V) 0 -16384 16383 16383 10 V

40123 Analog Input 3 (-10V to +10V) 0 -16384 16383 16383 10 V

40124 reserved

40125 reserved

40126 Analog Output 1 (-10V to +10V) 0 0 32676 16383 10 V

40127 Analog Output 2 (-10V to +10V) 0 0 32676 16383 10 V

40128 reserved

40129 reserved

40130 reserved

Remark to analog output


Output is reflecting +/- 10V

2.3.9 Read Metering

Bit values range Scaling


Reg. Description
Default Min Max Bits Value Unit
40131 Phase R to S rms Generator Voltage 0 0 32000 1000 1 kV

40132 Phase S to T rms Generator Voltage 0 0 32000 1000 1 kV

40133 Phase T to R rms Generator Voltage 0 0 32000 1000 1 kV

40134 Average of all 3 Phases 0 0 32000 1000 1 kV

40135 Network voltage 0 0 32000 1000 1 kV

40136 Machine frequency 0 0 20000 100 1 Hz

40137 Network frequency 0 0 20000 100 1 Hz

40138 Generator phase current 0 0 32000 1000 1 kA

40139 Real power 0 0 32000 100 1 MW

40140 Reactive power 0 -32000 32000 100 1 MVAr

40141 Power factor (1 0 -1000 1000 1000 1

40142 Excitation current 0 0 10000 10 1 A

40143 Excitation voltage 0 0 4000 10 1 V

40144 Power Electronics Supply 0 0 4000 10 1 V


Network to machine voltage
40145 0 -32000 32000 1000 1 kV
difference
Network to machine phase angle
40146 0 -1800 1800 10 1 Deg
difference
Network to machine frequency
40147 0 -10000 10000 100 1 Hz
difference

®
2-12 3BHS358281 E80 Rev. - UNITROL 1000 MODBUS Manual