Verification of temperature-rise to IEC 61439

Customer/order: Red cárnica 220VAC


Enclosure type: Part of a bayed enclosure suite
Decisive dimensions Height: 2000 mm Siting type: First or last enclosure in a
for temperature rise suite, free-standing
Width: 1600 mm Air inlet openings: No

Depth: 600 mm Number of horizontal divider panels: 0

Dimensions A0 Area factorb Ae


acc. to table 3 (Sp. 3) x (Sp. 4)

mxm m2 m2
Effective cooling
surface 2 3 4 5
Roof 1,60 x 0,60 0,96 1,40 1,34
Front 1,60 x 2,00 3,20 0,90 2,88
Rear 1,60 x 2,00 3,20 0,90 2,88
Left side 0,60 x 2,00 1,20 0,50 0,60
Right side 0,60 x 2,00 1,20 0,90 1,08
Ae= Σ(Ao - b) = 8,78

with effective cooling surface Αe


2
> 1,25 m ≤1,25 m2
ƒ = h 1,35 ÷ Α b = 2,66 (see 5.2.3) g = h ÷w = (see 5.2.3)

Air inlet openings [cm 2] 0


Enclosure constant k 0,109
Factor for horizontal divider panels d 1,00
Effective power loss [W] 300
x ***
P =P 98,09
. . x
Δt 0,5 = k d P [K] 10,69
Temperature distribution factor c 1,27
.
Δt 1,0 = c Δt 0,5 [K] 13,58
Temperature-rise characteristic curve: