LT101-02-02 - 11KV 630a Outdoor (Icog) Type HT Panel

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 21

0 1 2 3 4 5 6 7 8 9

A
LEGEND DETAILS:-
x1
1) -H1 R-PHASE INDICATION LAMP (RED) 16) -XPT,X2,X3,X5 CONTROL TERMINALS 31) P1 DIGITAL VOLTMETER
x2
x1
2) -H2 Y-PHASE INDICATION LAMP (YELLOW) -XT1
17) C.T. SHORTING TERMINALS 32) P2 DIGITAL AMMETER
x2
x1 s1
3) -H3 B-PHASE INDICATION LAMP (BLUE) 18) -CT CURRENT TRANSFORMER 33) P3 DIGITALMULTIFUNCTION METER
x2 s2
x1
PT
B 4) -H4 ON INDICATION LAMP (RED) 19) POTENTIAL TRANSFORMER 34) P4 DIGITAL PF METER
x2
x1
5) -H5 OFF INDICATION LAMP (GREEN) 20) -H HOOTER 35) K51 IDMT NUMERICAL PROTECTION RELAY
x2
x1
6) -H6 TRIP INDICATION LAMP (AMBER) AN ANNUNCIATOR WINDOW 36) K86 LOCKOUT RELAY
21)
x2
x1
7) -H7 TCH INDICATION LAMP (YELLOW) 22) -SW SWITCH 37) K27,59 U/V & O/V RELAY
x2
x1
C
8) -H8 23) -TH THERMOSTAT 38) K97 PT FUSE FAILURE RELAY
SPRING CHARGE INDICATION LAMP (BLUE)
x2
x1
9) -H9 24) -SH SPACE HAEATER 39) K631 RELAY FOR TRAFO. FAULT
TEST POSITION INDICATION LAMP (WHITE)
x2
x1
x1 x2
10) -H10 SERVICE POSITION INDICATION LAMP (YELLOW) 25) -PL PANEL LIGHT HOLDER 40) R3,R1,R94 AUXILARY RELAY
x2

-HTF E1-E3 1
11) 1 2 HT FUSE 26) EARTHING

S6 2
T -PS
12) N TNC SWITCH 27)
POWER PACK
C
B

S5 B F2-F6
6A
DP MCB
13) L R LOCAL/REMOTE SELECTOR SWITCH 28) 1 3
A1 A2 DP MCB FOR AUX. SUPPLY
2 4
E

3
-FDC
-S4 10A
4 DP MCB
E.STOP PUSH BUTTON 29) 1 3
14) 1
DP MCB FOR DC SUPPLY
2 4
2

-FAC
16A -F1, F01
DP MCB
1 3 5 7
15) 1 3
30)
DP MCB FOR AC SUPPLY FP MCB
F 2 4 2 4 6 8

Next Page 2
ISSUE FOR:- APPROVAL
DRAWN TEJAS CLIENT:- M/S. Prozeal Infra Engineering Pvt. Ltd. JOB NO.:- LT102/1202/02-02 DWG NO.:- SS/LT102/321
CHECKED R.D.P PROJECT:- 2200 KW GRID CONNECTED SPV POWER PLANT AT DARI KONNUR NAME OF PANEL:- 11KV 630A OUTDOOR (1 ICOG) TYPE HT PANEL
R0 27.12.2021 AS PER PO NO:- PIEPL/PO/21-22/1214 TEJAS APPROVED R.D.P CONSULTANT:- LEGENDS DETAILS Current Page 1
REV. DATE DESCRIPTION NAME DATE CONTRACTOR:- Total Page 16
0 1 2 3 4 5 6 7 8 9

11kV INCOMING -PT1-3 -XPT


1n 1a E10 1 E11 F1 L1 T1 E12
SUPPLY
R Y B
1n 1a E30 2 E31 L2 T2 E32

A 1n 1a E50 3 E51 L3 T3 E52


A1 A2
E70 4 E71 7 8 E72
A1 A2 F01 Ir:250-320A

-XPT
A1 A2 1n 1a E110 5 E111 L1 T1 E211

-HTF CTR 1n 1a E130 6 E131 L2 T2 E231


1 2 1 + H1
CTR-R / 9.2:A
E150 7 E151 E251

230V AC
1n 1a L3 T3

SUPPLY
E170 8 E171 E271

E12

E32

E52

E72
B 7 8
1 2 2 - H2
CTR-B / 9.2:A Ir:250-320A
-K27,59 1 2 3 4 P1 R Y B N
/4.6:A
/7.2:A DIGITAL
-XT1 UNDER VOLTMETER DIGITAL VOLTMETER
1 OVER VOLTAGE RELAY U< U> WITH INBUILT
D1 D11 12 TRIP
SELECTOR SWITCH
14 11
P1 S1
-CT1 14 11 12 23 24 34 12 13
/3.0:A S2
2
P2 D2

K11

L11

L13
K1
C -XT1
3
D3 D31 13 15 23 24
P1 S1 4.6:A 4.6:B 7.2:A 7.2:B

-CT2 TO TO
CT /3.1:B S2 TRIP CKT. ANNUNCIATOR
4
CORE-1 P2 D4
E12
-XT1
5
D5 D51 E32
P1 S1 E52
D -CT3 E72
/3.1:C S2 6
P2 D6
1
-E
D11

D13

D31

D41

D51

D61

D13

D41

D61
E12

E32

E52

E72
-P3
MFM
-P2 -E1 1
1 2 3 4 5 6 8 9 10 11
DIGITAL
RS1 RS2 YS1 YS2 BS1 BS2
AMMETER
S1 S2 S1 S2 S1 S2 V1 V2 V3 VN DIGITAL AMMETER
WITH INBUILT -H1 -H2 -H3
SELECTOR SWITCH
E R x1 Y x1 B x1
MULTI FUNCTION METER 12 13
x2 x2 x2
1 FP2 1 FP3 1
PH N RS 485
FP1
63/63A 12 13 7 14 R PH. Y PH. B PH.
C.F 2 2 2
S1

S2

-SPD R Y B -X3 1
-X3 2
-X3 3

SURGE PROTECTION DEVICE E12 E12


F R Y B N
R1 Y1 B1 E32 E32
3.0:A 3.1:A 3.1:A
E

Next Page 3
1 ISSUE FOR:- APPROVAL
DRAWN TEJAS CLIENT:- M/S. Prozeal Infra Engineering Pvt. Ltd. JOB NO.:- LT102/1202/02-02 DWG NO.:- SS/LT102/321
CHECKED R.D.P PROJECT:- 2200 KW GRID CONNECTED SPV POWER PLANT AT DARI KONNUR NAME OF PANEL:- 11KV 630A OUTDOOR (1 ICOG) TYPE HT PANEL
R0 27.12.2021 AS PER PO NO:- PIEPL/PO/21-22/1214 TEJAS APPROVED R.D.P CONSULTANT:- POWER & METERING DIAGRAM FOR INCOMER Current Page 2
REV. DATE DESCRIPTION NAME DATE CONTRACTOR:- Total Page 16
0 1 2 3 4 5 6 7 8 9

NUMERICAL RELAY[50,51,50N,51N,95]
2.0:F 2.0:F 2.0:F
R1 Y1 B1 -K51
-PS E
1
A
-XT1
7 IL1
C1 C11 C11 2 4
A3
P1 S1 C1 + K1
1 3 4D02 / 4.1:E
-CT1 A1 110V DC
/2.0:C S2
8
C3
- K2 AUX SUPPLY
P2 C2 4D03 / 4.1:F
A2

-XT1 IL2
9
C3 C10 C10 2 4 L1
B3 / 5.4:C
P1 S1 C4 D2
1 3
-CT2 A1 D3 TO TCH LAMP
B CT /2.0:C S2 C6
CORE-1 10 DO1
P2 C4 L10
A2
B4 / 5.4:C
D1

-XT1 IL3
11
C5 C31 C31 2 4
D6
C7
P1 S1 L11
1 3 B1 / 7.2:A
-CT3 A1 D5 O/C & E/F
C9
/2.0:D S2 12 DO2 WITH HIGHEST
P2 C6 L12 TO ANNUNCIATOR
A2
IE B2 / 7.2:B
D4
1 2 4
C -E C10

C51 1 3
C12 K1
A1 B6 / 4.7:B
D7
DO3
TO TRIP CKT
DI1 A2
K11 x1 x2 K13
4.6:B / D2 B5 / 4.7:A
I1 D8
TCH FUNCTION

I2
DI2
K12 x1 x2 X31 -X5 1
4.7:B / D3 D9
I3 A1
D
SPARE
K1 DO4
4.7:A / D1 A2 X32 -X5 2 1 2
I4 D10 -R1 -R1
/5.2:E 9 5 /5.2:E 10 6

-X3 4 S3 X33 -X5 3


RS485 COMM.

+
R1 D11
A1
PORT

RS-485 SPARE
-X3 5 S4 DO5.
R2
- A2 X34 -X5 4

-X3 6 D12

X11

X12

X13

X14

X15

X16
E 1 R3
1 3 5 -E -X6 1 -X6 2 -X6 3
-X6 4 -X6 5 -X6 6
-Q52
/4.2:C
/5.0:B 2 4 6
SPARE VCB SPARE VCB
/5.6:B
800A, 11kV,
MULTIPLYING CONTACT MULTIPLYING CONTACT
26.3kA FOR 3 SEC.,
3PH. 50Hz

R Y B

TO COMMON BUS

Next Page 4
2 ISSUE FOR:- APPROVAL
DRAWN TEJAS CLIENT:- M/S. Prozeal Infra Engineering Pvt. Ltd. JOB NO.:- LT102/1202/02-02 DWG NO.:- SS/LT102/321
CHECKED R.D.P PROJECT:- 2200 KW GRID CONNECTED SPV POWER PLANT AT DARI KONNUR NAME OF PANEL:- 11KV 630A OUTDOOR (1 ICOG) TYPE HT PANEL
R0 27.12.2021 AS PER PO NO:- PIEPL/PO/21-22/1214 TEJAS APPROVED R.D.P CONSULTANT:- POWER & CONTROL WIRING DIAGRAM FOR K51 RELAY Current Page 3
REV. DATE DESCRIPTION NAME DATE CONTRACTOR:- Total Page 16
0 1 2 3 4 5 6 7 8 9

K1 K1 K1
S5 1
A

K1

K1
L R K27,59 K51 K51
/2.6:B /3.3:A /3.3:A
A1 A2
K86 13 D1 B5

K3

K4
-K631A 1 -K631B 1 -K631C 1 -K631D 1
/10.3:A 2.6:C 3.3:D 3.5:C
S6 1 -X2 11 -S4 /6.1:D /6.2:D /6.3:D /6.3:D
S6 2
5 3
-X2 3 C 10.3:C TCH 9 5 9 5 9 5 9 5
REMOTE
T N TRIPPING
REMOTE 10.3:D 2.6:C 3.3:C 3.3:D 3.5:C
K1

N CLOSING T 4
6 -X2 12 15 D2 D3 B6
C -X2 4 A
B

K5

K11

K11

K11

K11

K11

K11

K12

K13

K13

K13

K13

K13
B
1
-S4
/1.1:E 2
/4.5:A K6
-X2
1
EXTERNAL
INTERLOCK
13
-X2 2
-R94
K86 14
K7

/10.3:A
1
C 9 10.3:B
-R94 10
10.3:B
/4.3:C 5 1
2 -R94
/4.3:C 6 2
K8

K10
K9

K11

K12
-X2 6 -X2 7 -X2 8 -X2 10

-Q52

K13
/3.0:E
24 11 22 23 21 08

VCB AUX.
OF1 OF2 OF3 CONTACT
D

12 10 09

K86
04 /10.3:A
03 9
A1 C1 10.6:C
XF MX1
A2 C2 10.6:C
16 15 10

-X2 9
-X2 5
E

K2 K2 K2
VCB VCB
K1

K2

AUX. SUPPLY
CLOSING COIL TRIPING COIL
FOR MASTER
4D02 / 3.5:A TRIP RELAY (K86)
AUX. SUPPLY
4D03 / 3.5:A TO K51 RELAY 5 9 /4.2:C
1 3 1
6 10 /4.3:C
-F2 2
6A 2 4
DP MCB
J3

J4

4D00 4D01
9.4:F 9.4:F
110V DC
AUX SUPPLY Next Page 5
3 ISSUE FOR:- APPROVAL
DRAWN TEJAS CLIENT:- M/S. Prozeal Infra Engineering Pvt. Ltd. JOB NO.:- LT102/1202/02-02 DWG NO.:- SS/LT102/321
CHECKED R.D.P PROJECT:- 2200 KW GRID CONNECTED SPV POWER PLANT AT DARI KONNUR NAME OF PANEL:- 11KV 630A OUTDOOR (1 ICOG) TYPE HT PANEL
R0 27.12.2021 AS PER PO NO:- PIEPL/PO/21-22/1214 TEJAS APPROVED R.D.P CONSULTANT:- CLOSING & TRIPPING CONTROL WIRING DIAGRAM FOR INCOMER Current Page 4
REV. DATE DESCRIPTION NAME DATE CONTRACTOR:- Total Page 16
0 1 2 3 4 5 6 7 8 9

M1
B
L1

L1

L1

L1

L1
-X2 13 -X2 15 -X2 17 -X2 21

-Q52 -Q52
/3.0:E 13 01 07 /3.0:E
18 -R3
B1 4
/9.6:E
OF4
K86 K51 B2 B3 8 12
/10.3:A /3.3:A
B3
C 19 20 7 3.5:B
SERVICE TEST 10.3:D
POS. SW. POS. SW.
10.3:D 3.5:B M
8 B4

14 02 06 05

-X2 14 -X2 16 -X2 18 -X2 19 -X2 22 -X2 23


D

M2

M3
L3

L4

L5

L6

L7

L8
x1 x1
-H10 -H11
x2 x2
x1 x1 A1 x1 x1 x1 x1

M1

M2
-H4 -H5 -R1 -H6 -H7 -H8 -H9
TCH VCB SPRING SPRING DC FAIL
x2 x2 A2 x2 x2 x2 x2
L2 CHARGE MOTOR CHARGE
E
L1

L2

VCB IN VCB IN AUX. VCB ON VCB OFF VCB TRIP TCH LAMP
SERVICE TEST RELAY
1 3 5
-F3 9 1 /3.7:D
6 1 3
6A 20
2 4
10 2 /3.9:D -X2
DP MCB
EARTHING TB -F4
6A 2 4
J3

J4

DP MCB

M1

M2
H3

H4
EARTHING TB

4D04 4D05
F 9.5:F 9.5:F 3A02 3A03
3A00 3A01 7.2:F 7.2:F
110V DC 9.1:C 9.2:C
AUX SUPPLY 230V AC AUX SUPPLY 230V AC TO
FROM INCOMER ANNUNCIATOR
WINDOW
Next Page 6
4 ISSUE FOR:- APPROVAL
DRAWN TEJAS CLIENT:- M/S. Prozeal Infra Engineering Pvt. Ltd. JOB NO.:- LT102/1202/02-02 DWG NO.:- SS/LT102/321
CHECKED R.D.P PROJECT:- 2200 KW GRID CONNECTED SPV POWER PLANT AT DARI KONNUR NAME OF PANEL:- 11KV 630A OUTDOOR (1 ICOG) TYPE HT PANEL
R0 27.12.2021 AS PER PO NO:- PIEPL/PO/21-22/1214 TEJAS APPROVED R.D.P CONSULTANT:- CONTROL WIRING DIAGRAM FOR INDICATING LAMP & SPRING Current Page 5
REV. DATE DESCRIPTION NAME DATE CONTRACTOR:- CHARGE MOTOR FOR INCOMER Total Page 16
0 1 2 3 4 5 6 7 8 9

K21

K21

K21

K21
3 3 3

-X4 1 -X4 3 -X4 5 -X4 7 -K631A -K631B -K631C


/6.1:D 11 6 /6.2:D 11 6 /6.3:D 11 6
B

-FIELD

X17

X18

X19

X20

X21

X22

X23

X24

X25
BUCHHOLZ WTI OTI PRV -X6 7 -X6 8 -X6 9 -X6 13 -X6 14 -X6 15 -X6 19 -X6 20 -X6 21
TRIP TRIP TRIP TRIP

SPARE CONTACT SPARE CONTACT SPARE CONTACT


C

-X4 2 -X4 4 -X4 6 -X4 8


K23

K24

K25

K26

D 3 1
-K631D -K632
/6.3:D 11 6 /6.4:D 9 5

A1 A1 A1 A1 A1
-K631A -K631B -K631C -K631D -K632
A2 A2 A2 A2 A2

X26

X27

X28

X29

X30

X31
-X6 10 -X6 11 -X6 12 -X6 16 -X6 17 -X6 18

E
5 1 /4.8:A 5 1 /4.8:A 5 1 /4.9:A 5 1 /4.9:A 5 SPARE CONTACT SPARE CONTACT
9 9 9 9 9 1 /6.8:D
6 2 /7.3:A 6 2 /7.3:A 6 2 /7.4:A 6 2 /7.5:A
K22
K21

10 10 10 10
6 6 6 6
11 3 /6.5:B 11 3 /6.7:B 11 3 /6.8:B 11 3 /6.6:D
1 3
-F5
6A 2 4
DP MCB
J3

J4

TRANSFORMER
FAULT AUX. RELAY[K631]

F 4D06 4D07

110V DC
AUX SUPPLY

Next Page 7
5 ISSUE FOR:- APPROVAL
DRAWN TEJAS CLIENT:- M/S. Prozeal Infra Engineering Pvt. Ltd. JOB NO.:- LT102/1202/02-02 DWG NO.:- SS/LT102/321
CHECKED R.D.P PROJECT:- 2200 KW GRID CONNECTED SPV POWER PLANT AT DARI KONNUR NAME OF PANEL:- 11KV 630A OUTDOOR (1 ICOG) TYPE HT PANEL
R0 27.12.2021 AS PER PO NO:- PIEPL/PO/21-22/1214 TEJAS APPROVED R.D.P CONSULTANT:- CONTROL WIRING DIAGRAM FOR TRANSFORMER AUX. RELAY (K632 ) Current Page 6
REV. DATE DESCRIPTION NAME DATE CONTRACTOR:- OG-1 TRAFO FEEDER Total Page 16
0 1 2 3 4 5 6 7 8 9

L11

L11

L11

L11

L11

L11

L11

L11
A
K51 K27,59
/3.3:A /2.6:B -X4 11 -X4 13
B1 23
3.5:B 2.6:C -K631A 2 -K631B 2 -K631C 2 -K631D 2
/6.1:D /6.2:D /6.3:D /6.3:D
BUCHHOLZ WTI
10 6 10 6 10 6 10 6
ALARM ALARM
3.5:C 2.7:C
B2 24
-X4 12 -X4 14

L12

L13

L14

L15

L16

L17

L18

L19
B
-AN
/8.1:C 3
1 2 4 5 6 7 8 COM

O/C & E/F U/V&O/V BUCHHOLZ WTI OTI PRV BUCHHOLZ WTI
WITH HIGHEST TRIP TRIP TRIP TRIP TRIP ALARM ALARM
TRIP

POWER ON

C
8 WINDOW ANNUNCIATOR TEST

ACCEPT

RESET
P N C NO T A R E
L33

L34

L35
1
D 8.1:E / 1D00 E

8.2:E / 1D01

1 2
-X4 9
-R3 -R3
/9.6:E 5 9 /9.6:E 6 10
+OG1-H1
8.2:E
L31

L32

8.3:E
E
+OG1-H2

-X4 10
L31

L32

M1

M2

1 3
-F6
x1
6A 2 4
DP MCB
-H
J3

J4

x2
F
4D08 4D09 -3A02 -3A03
9.6:F 9.6:F 5.7:F 5.7:F
L34

230V DC 230V AC
AUX SUPPLY AUX SUPPLY
HOOTER
Next Page 8
6 ISSUE FOR:- APPROVAL
DRAWN TEJAS CLIENT:- M/S. Prozeal Infra Engineering Pvt. Ltd. JOB NO.:- LT102/1202/02-02 DWG NO.:- SS/LT102/321
CHECKED R.D.P PROJECT:- 2200 KW GRID CONNECTED SPV POWER PLANT AT DARI KONNUR NAME OF PANEL:- 11KV 630A OUTDOOR (1 ICOG) TYPE HT PANEL
R0 27.12.2021 AS PER PO NO:- PIEPL/PO/21-22/1214 TEJAS APPROVED R.D.P CONSULTANT:- CONTROL WIRING DIAGRAM FOR ANNUNCIATOR CIRCUIT FOR Current Page 7
REV. DATE DESCRIPTION NAME DATE CONTRACTOR:- INCOMER Total Page 16
0 1 2 3 4 5 6 7 8 9

L11

L11

L11

L11

L11

L11

L11
B
-X4 15 -X4 17 -X4 19 -X4 22 -X4 25 -X4 27 -X4 29

-R3 3
/9.6:E
OTI MOG SPARE SPARE SPARE SPARE SPARE
ALARM ALARM 7 11

-X4 16 -X4 18 -X4 20 -X4 23 -X4 26 -X4 28 -X4 30


L20

L21

L22

L23

L24

L25

L26

L27

L11
C -AN
/7.2:B 4
1 2 3 5 6 7 8 COM

OTI MOG DC
SPARE SPARE SPARE SPARE SPARE SUPERVISION
ALARM ALARM

POWER ON

8 WINDOW ANNUNCIATOR-2
TEST
D

ACCEPT

RESET
P N C NO T A R E

1
E
L36

L37

E
L33

L34

-X4 21 -X4 24

7.0:D 7.1:D 7.4:E +OG1-H2


1D00 1D01 +OG1-H1 7.4:E

110V DC/230V AC
AUX SUPPLY TO HOOTER

Next Page 9
7 ISSUE FOR:- APPROVAL
DRAWN TEJAS CLIENT:- M/S. Prozeal Infra Engineering Pvt. Ltd. JOB NO.:- LT102/1202/02-02 DWG NO.:- SS/LT102/321
CHECKED R.D.P PROJECT:- 2200 KW GRID CONNECTED SPV POWER PLANT AT DARI KONNUR NAME OF PANEL:- 11KV 630A OUTDOOR (1 ICOG) TYPE HT PANEL
R0 27.12.2021 AS PER PO NO:- PIEPL/PO/21-22/1214 TEJAS APPROVED R.D.P CONSULTANT:- CONTROL WIRING DIAGRAM FOR ANNUNCIATOR CIRCUIT FOR Current Page 8
REV. DATE DESCRIPTION NAME DATE CONTRACTOR:- INCOMER Total Page 16
0 1 2 3 4 5 6 7 8 9

2.2:B 2.2:B
CTR-R CTR-B

H1

H2
1 3
-FAC
16A 2 4
DP MCB

H3

H4
-XAC
1
230V AC
2

230V AC SUPPLY
H3

H4

H3

H4
1 3
-F9
6A 2 4
DP MCB
1 1
-F7 -F8

H10

H11
3A00 3A01 NL
C
5.6:F 5.6:F 6A 2 6A 2

TO VCB SPRING

H9
-PS

H8
CHARGE MOTOR

H6
POWER PACK
230V AC
-XSH 1

DLS 13
PS TH

J1

J2
H12
1
3 14 1 3

H7
2 -FDC
x1
x1 x1 10A 2 4
DP MCB
-PL -SH1 -SH2
D 80W 80W
x2 x2
x2
-XSH 2

PLUG PANEL SPACE


SOCKET LIGHT HEATER
HOLDER 5
9 1 /7.2:D
A1 6
-R3 10 2 /7.2:D
7
A2
11 3 /8.5:B
8
E
12 4 /5.8:C

DC SUPERVISION

J3

J4
RELAY
110V DC SUPPLY
J3

J4

J3

J4

J3

J4
F

4D00 4D01 4D04 4D05 4D08 4D09


4.1:F 4.1:F 5.0:F 5.1:F 7.1:F 7.1:F

TO CLOSING TO INDICAION TO ANNUNCIATOR


CIRCUIT CIRCUIT CIRCUIT
Next Page 10
8 ISSUE FOR:- APPROVAL
DRAWN TEJAS CLIENT:- M/S. Prozeal Infra Engineering Pvt. Ltd. JOB NO.:- LT102/1202/02-02 DWG NO.:- SS/LT102/321
CHECKED R.D.P PROJECT:- 2200 KW GRID CONNECTED SPV POWER PLANT AT DARI KONNUR NAME OF PANEL:- 11KV 630A OUTDOOR (1 ICOG) TYPE HT PANEL
R0 27.12.2021 AS PER PO NO:- PIEPL/PO/21-22/1214 TEJAS APPROVED R.D.P CONSULTANT:- AC & DC VOLTAGE CIRCUIT FOR INCOMER Current Page 9
REV. DATE DESCRIPTION NAME DATE CONTRACTOR:- Total Page 16
0 1 2 3 4 5 6 7 8 9

MASTER TRIP RELAY (K86)


-K86

K8
4.2:C / 1
B 1
1

TO CLOSING COIL
2

4.2:C / 2 K9
2

X5 X35
5 3
3

SPARE T.B.
4

C X5 X36 K13
6 4 9 / 4.7:D
9

K1 K2
4.4:A / 5 10 / 4.7:E
5 10
5

TO TRIPING COIL
6
K11
4.4:B / 6
6

L1
5.4:C / 7
D 7
7

TO TRIP LAMP
8
L9
5.4:C / 8
8

Next Page 11
9 ISSUE FOR:- APPROVAL
DRAWN TEJAS CLIENT:- M/S. Prozeal Infra Engineering Pvt. Ltd. JOB NO.:- LT102/1202/02-02 DWG NO.:- SS/LT102/321
CHECKED R.D.P PROJECT:- 2200 KW GRID CONNECTED SPV POWER PLANT AT DARI KONNUR NAME OF PANEL:- 11KV 630A OUTDOOR (1 ICOG) TYPE HT PANEL
R0 27.12.2021 AS PER PO NO:- PIEPL/PO/21-22/1214 TEJAS APPROVED R.D.P CONSULTANT:- MACRO FOR MASTER TRIP RELAY (K86) Current Page 10
REV. DATE DESCRIPTION NAME DATE CONTRACTOR:- Total Page 16
0 1 2 3 4 5 6 7 8 9

Terminal diagram HT STANDARD

Strip
External targets
=+IC-X2 Internal targets

Target designation Wiring Jumper Function text Jumper Wiring Target designation Placement

-S4:2 K6 1 EXTERNAL INTERLOCK

-R94:9 K7 2 EXTERNAL INTERLOCK


B
A2 K4 3 REMOTE CLOSE CMD

-S4:1 K5 4 REMOTE CLOSE CMD

-Q52-16 5 VCB CLOSING COIL CONTACT K2 -F2:3 /4.1:F

-Q52-11 6 CLOSING CIRCUIT K9 -K86-2 /10.3:B

-Q52-22 7 CLOSING CIRCUIT -R94:14 /4.3:C

-Q52-21 8 TRIPPING CIRCUIT K11 -K86-6 /10.3:D


C

-R94:6 9 TRIPPING CIRCUIT -Q52-15 /4.4:E

-Q52-08 10 TCH K12 -K51-I3 /3.4:D

-K86-5 K1 11 REMOTE TRIP CMD

-K86-6 K11 12 REMOTE TRIP CMD

-Q52-13 13 VCB IN SERVICE POSITION L1 -F3:1 /5.0:E

D -H4:x1 L3 14 VCB IN SERVICE POSITION -Q52-14 /5.1:C

-Q52-01 15 VCB IN TEST POSITION

-H5:x1 L4 16 VCB IN TEST POSITION -Q52-02 /5.1:C

-Q52-07 17 VCB ON L1 -K86-7 /10.3:D

-H6:x1 L5 18 VCB ON -Q52-19 /5.2:C

-H7:x1 L6 19 VCB OFF -Q52-20 /5.3:C


E
20 EARTHING TB

-Q52-18 21 SPRING CHARGE MOTOR M1 -F4:1 /5.6:E

-F4:3 M2 22 SPRING CHARGE MOTOR -Q52-06 /5.6:C

-H10:x1 M3 23 SPRING CHARGE -Q52-05 /5.7:C

12
10 C:\Users\Public\EPLAN\Data\Images\Company name\swati_switch_gears.jpg
C:\Users\Public\EPLAN\Data\Images\Company name\swati logo.jpg

DRAWN TEJAS CLIENT:- CLIENT:- M/S. Prozeal Infra Engineering Pvt. Ltd. JOB NO.:- LT102/1202/02-02 DWG NO.:- SS/LT102/321
CHECKED R.D.P PROJECT:- PROJECT:- 2200 KW GRID CONNECTED SPV POWER PLANT AT DARI KONNUR NAME OF PANEL:- 11KV 630A OUTDOOR (1 ICOG) TYPE HT PANEL
R0 27.12.2021 AS PER PO NO:- PIEPL/PO/21-22/1214 TEJAS APPROVED R.D.P MEP CONSULTANT:-
CONSULTANT:- Switchgears Pvt Ltd. Terminal diagram =+IC-X2 Page 11
REV. DATE DESCRIPTION NAME DATE CONTRACTOR:- CONTRACTOR:- An ISO 9001-2008 Tele/Fax: 02717-645195,96/251160 Email: design@swatiswitchgears.com Page 16
0 1 2 3 4 5 6 7 8 9

Terminal diagram HT STANDARD

Strip
External targets
=+IC-X3 Internal targets

Target designation Wiring Jumper Function text Jumper Wiring Target designation Placement

1 MFM RS-485 -P3-7: /2.4:E

2 MFM RS-485 -P3-14 /2.5:E


B
3 MFM RS-485

-K51-R1 S3 4 RS 485 FOR RELAY

-K51-R2 S4 5 RS 485 FOR RELAY

6 RS 485 FOR RELAY

C
Strip
External targets
=+IC-X4 Internal targets

Target designation Wiring Jumper Function text Jumper Wiring Target designation Placement

1 BUCHHOLZ TRIP FROM FIELD K21 -F5:1 /6.0:E

2 BUCHHOLZ TRIP FROM FIELD K23 -K631A:A1 /6.1:D

3 WTI TRIP FROM FIELD


D

4 WTI TRIP FROM FIELD K24 -K631B:A1 /6.2:D

5 OTI TRIP FROM FIELD

6 OTI TRIP FROM FIELD K25 -K631C:A1 /6.3:D

7 PRV TRIP FROM FIELD

8 PRV TRIP FROM FIELD K26 -K631D:A1 /6.3:D

E 9 HOOTER CMD FROM OG-1

10 HOOTER CMD FROM OG-1 -H:x1 /7.4:F

11 BUCHOLZ ALARM FROM FIELD L11 -K631D:2 /7.5:A

12 BUCHOLZ ALARM FROM FIELD

13 WTI ALARM FROM FIELD

14 WTI ALARM FROM FIELD


F

13
11 C:\Users\Public\EPLAN\Data\Images\Company name\swati_switch_gears.jpg
C:\Users\Public\EPLAN\Data\Images\Company name\swati logo.jpg

DRAWN CLIENT:- JOB NO.:- DWG NO.:-


CHECKED PROJECT:- NAME OF PANEL:- 11KV 630A OUTDOOR (1 ICOG) TYPE HT PANEL
APPROVED MEP CONSULTANT:- Switchgears Pvt Ltd. Terminal diagram =+IC-X3 =+IC-X4 Page 12
REV. DATE DESCRIPTION NAME DATE CONTRACTOR:- An ISO 9001-2008 Tele/Fax: 02717-645195,96/251160 Email: design@swatiswitchgears.com Page 16
0 1 2 3 4 5 6 7 8 9

Terminal diagram HT STANDARD

Strip
External targets
=+IC-X4 Internal targets

Target designation Wiring Jumper Function text Jumper Wiring Target designation Placement

15 OTI ALARM FROM FIELD

16 OTI ALARM FROM FIELD -1 /8.1:C


B
17 MOG ALARM FROM FIELD

18 MOG ALARM FROM FIELD L21 -2 /8.2:C

19 SPARE ANNUNCIATION

20 SPARE ANNUNCIATION L22 -3 /8.2:C

21 HOOTER CMD TO INCOMER

22 SPARE ANNUNCIATION
C

23 SPARE ANNUNCIATION L23 -4 /8.3:C

24 HOOTER CMD TO INCOMER

25 SPARE ANNUNCIATION

26 SPARE ANNUNCIATION L24 -5 /8.4:C

27 SPARE ANNUNCIATION

D 28 SPARE ANNUNCIATION -6 /8.4:C

29 SPARE ANNUNCIATION -R3:3 /8.5:B

30 SPARE ANNUNCIATION L26 -7 /8.5:C

Strip
External targets
=+IC-X5 Internal targets
E

Target designation Wiring Jumper Function text Jumper Wiring Target designation Placement

1 K51 RELAY SPARE CONTACT -K51-D9 /3.5:D

2 K51 RELAY SPARE CONTACT X32 -K51-D10 /3.5:D

3 K51 RELAY SPARE CONTACT -K51-D11 /3.5:D

4 K51 RELAY SPARE CONTACT X34 -K51-D12 /3.5:E


F

14
12 C:\Users\Public\EPLAN\Data\Images\Company name\swati_switch_gears.jpg
C:\Users\Public\EPLAN\Data\Images\Company name\swati logo.jpg

DRAWN CLIENT:- JOB NO.:- DWG NO.:-


CHECKED PROJECT:- NAME OF PANEL:- 11KV 630A OUTDOOR (1 ICOG) TYPE HT PANEL
APPROVED MEP CONSULTANT:- Switchgears Pvt Ltd. Terminal diagram =+IC-X4 =+IC-X5 Page 13
REV. DATE DESCRIPTION NAME DATE CONTRACTOR:- An ISO 9001-2008 Tele/Fax: 02717-645195,96/251160 Email: design@swatiswitchgears.com Page 16
0 1 2 3 4 5 6 7 8 9

Terminal diagram HT STANDARD

Strip
External targets
=+IC-X5 Internal targets

Target designation Wiring Jumper Function text Jumper Wiring Target designation Placement

-K86-3 5 K86 RELAY SPARE DO

-K86-4 X36 6 K86 RELAY SPARE DO


B

Strip
External targets
=+IC-X6 Internal targets

Target designation Wiring Jumper Function text Jumper Wiring Target designation Placement

1 SPARE VCB MULTIPLYING CONTACT X11 -R1:1 /3.7:D

C
2 SPARE VCB MULTIPLYING CONTACT X12 -R1:9 /3.7:D

3 SPARE VCB MULTIPLYING CONTACT -R1:5 /3.7:D

4 SPARE VCB MULTIPLYING CONTACT X14 -R1:2 /3.9:D

5 SPARE VCB MULTIPLYING CONTACT X15 -R1:10 /3.9:D

6 SPARE VCB MULTIPLYING CONTACT X16 -R1:6 /3.9:D

7 SPARE VCB MULTIPLYING CONTACT X17 -K631A:3 /6.5:B


D

8 SPARE VCB MULTIPLYING CONTACT X18 -K631A:11 /6.5:B

9 SPARE VCB MULTIPLYING CONTACT X19 -K631A:6 /6.5:B

10 SPARE VCB MULTIPLYING CONTACT X26 -K631D:3 /6.6:D

11 SPARE VCB MULTIPLYING CONTACT X27 -K631D:11 /6.6:D

12 SPARE VCB MULTIPLYING CONTACT X28 -K631D:6 /6.6:D

E 13 SPARE VCB MULTIPLYING CONTACT X20 -K631B:3 /6.7:B

14 SPARE VCB MULTIPLYING CONTACT X21 -K631B:11 /6.7:B

15 SPARE VCB MULTIPLYING CONTACT X22 -K631B:6 /6.7:B

16 SPARE VCB MULTIPLYING CONTACT X29 -K632:1 /6.8:D

17 SPARE VCB MULTIPLYING CONTACT X30 -K632:9 /6.8:D

18 SPARE VCB MULTIPLYING CONTACT X31 -K632:5 /6.8:D


F

15
13 C:\Users\Public\EPLAN\Data\Images\Company name\swati_switch_gears.jpg
C:\Users\Public\EPLAN\Data\Images\Company name\swati logo.jpg

DRAWN CLIENT:- JOB NO.:- DWG NO.:-


CHECKED PROJECT:- NAME OF PANEL:- 11KV 630A OUTDOOR (1 ICOG) TYPE HT PANEL
APPROVED MEP CONSULTANT:- Switchgears Pvt Ltd. Terminal diagram =+IC-X5 =+IC-X6 Page 14
REV. DATE DESCRIPTION NAME DATE CONTRACTOR:- An ISO 9001-2008 Tele/Fax: 02717-645195,96/251160 Email: design@swatiswitchgears.com Page 16
0 1 2 3 4 5 6 7 8 9

Terminal diagram HT STANDARD

Strip
External targets
=+IC-X6 Internal targets

Target designation Wiring Jumper Function text Jumper Wiring Target designation Placement

19 SPARE VCB MULTIPLYING CONTACT X23 -K631C:3 /6.8:B

20 SPARE VCB MULTIPLYING CONTACT X24 -K631C:11 /6.8:B


B
21 SPARE VCB MULTIPLYING CONTACT X25 -K631C:6 /6.8:B

Strip
External targets
=+IC-XAC Internal targets

Target designation Wiring Jumper Function text Jumper Wiring Target designation Placement
C
1 230V AC TO OG1 CIRCUIT

2 230V AC TO OG1 CIRCUIT

Strip
External targets
=+IC-XPT Internal targets

D
Target designation Wiring Jumper Function text Jumper Wiring Target designation Placement

-PT1-3:1a E10 1 PT TERMINAL FOR METERING E11 -F1:L1 /2.6:A

-PT1-3:1a E30 2 PT TERMINAL FOR METERING E31 -F1:L2 /2.6:A

-PT1-3:1a E50 3 PT TERMINAL FOR METERING E51 -F1:L3 /2.6:A

-PT1-3 E70 4 PT TERMINAL FOR METERING E71 -F1:7 /2.6:A

-PT1-3:1a E110 5 PT TERMINAL FOR PROTECTION E111 -F01:L1 /2.5:A


E
-PT1-3:1a E130 6 PT TERMINAL FOR PROTECTION E131 -F01:L2 /2.5:A

-PT1-3:1a E150 7 PT TERMINAL FOR PROTECTION E151 -F01:L3 /2.5:A

-PT1-3 E170 8 PT TERMINAL FOR PROTECTION E171 -F01:7 /2.5:A

16
14 C:\Users\Public\EPLAN\Data\Images\Company name\swati_switch_gears.jpg
C:\Users\Public\EPLAN\Data\Images\Company name\swati logo.jpg

DRAWN CLIENT:- JOB NO.:- DWG NO.:-


CHECKED PROJECT:- NAME OF PANEL:- 11KV 630A OUTDOOR (1 ICOG) TYPE HT PANEL
APPROVED MEP CONSULTANT:- Switchgears Pvt Ltd. Terminal diagram =+IC-X6 =+IC-XAC =+IC-XPT Page 15
REV. DATE DESCRIPTION NAME DATE CONTRACTOR:- An ISO 9001-2008 Tele/Fax: 02717-645195,96/251160 Email: design@swatiswitchgears.com Page 16
0 1 2 3 4 5 6 7 8 9

Terminal diagram HT STANDARD

Strip
External targets
=+IC-XSH Internal targets

Target designation Wiring Jumper Function text Jumper Wiring Target designation Placement

-TH:13 1 SPACE HEATER T.B. H6 -F8:2 /9.3:C

-PL:x2 2 SPACE HEATER T.B. -SH1:x2 /9.3:D


B

Strip
External targets
=+IC-XT1 Internal targets

Target designation Wiring Jumper Function text Jumper Wiring Target designation Placement

1 CT SHORTING T.B. FOR METERING -CT1:S1 /2.0:C

C
-P3-1 D11 2 CT SHORTING T.B. FOR METERING -E:1 /2.1:D

3 CT SHORTING T.B. FOR METERING -CT2:S1 /2.0:C

-P3-3 D31 4 CT SHORTING T.B. FOR METERING -E:1 /2.1:D

-P2-RS2 D51 5 CT SHORTING T.B. FOR METERING -CT3:S1 /2.0:D

-P3-5 D51 6 CT SHORTING T.B. FOR METERING -E:1 /2.1:D

7 CT SHORTING T.B. FOR METERING -CT1:S1 /3.0:A


D

-K51-C1 8 CT SHORTING T.B. FOR METERING -E:1 /3.1:C

9 CT SHORTING T.B. FOR METERING -CT2:S1 /3.1:B

-K51-C4 10 CT SHORTING T.B. FOR METERING -E:1 /3.1:C

-K51-C12 11 CT SHORTING T.B. FOR METERING -CT3:S1 /3.1:C

-K51-C12 12 CT SHORTING T.B. FOR METERING -E:1 /3.1:C

15 C:\Users\Public\EPLAN\Data\Images\Company name\swati_switch_gears.jpg
C:\Users\Public\EPLAN\Data\Images\Company name\swati logo.jpg

DRAWN CLIENT:- JOB NO.:- DWG NO.:-


CHECKED PROJECT:- NAME OF PANEL:- 11KV 630A OUTDOOR (1 ICOG) TYPE HT PANEL
APPROVED MEP CONSULTANT:- Switchgears Pvt Ltd. Terminal diagram =+IC-XSH =+IC-XT1 Page 16
REV. DATE DESCRIPTION NAME DATE CONTRACTOR:- An ISO 9001-2008 Tele/Fax: 02717-645195,96/251160 Email: design@swatiswitchgears.com Page 16
BILLS OF MATERIAL / BILLS OF QUANTITY
Client:-M/S. Prozeal Infra Engineering Pvt. Ltd. Job. No. :- LT101/1202/02-02 Rev.:-R0
Project:- 2200.0 kW GRID CONNECTED SPV POWER
Drg. No. :- SS/LT101-02-02/421 Date:-27.12.2021
PLANT AT DARI KONNUR, MH (EESL)
Consultant:- AS PER PO NO . :- PIEPL/PO/21-22/1214

Name of Panel :- 11KV 630A OUTDOOR (ICOG) TYPE HT


Project:-
PANEL -
SR. NO. TAG NO. RATING DISCRIPTION QTY MAKE TYPE/PART NO.
11kV HT VCB ICOG Feeder 1
[A] VACCUM CIRCUIT BREAKER
Q52 800A 11kV Drawout Type VCB (STR: 26.3kA for 3 Sec.) 1 No. Schneider EASY PACT
1 4C/O Contact With inbuilt Mechanical Anti -
Pumping Feature
2 230V AC Spring Charging Motor 1 No. Schneider
3 110V DC Closing Coil 1 No. Schneider
4 110V DC Tripping Coil 1 No. Schneider
[B] CURRENT TRANSFORMER & POTENTIAL TRANSFORMER
CT1-3 300/1/1A Core-1, Class-0.2S, 15VA 3 Nos.
SEI/ECS/Precise/Schneider
Core-2, Class-5P10, 15VA Resin cast
1 Approved Vendor
CT Secondary Termination on P1 Side

EI/ECS/Precise/Schneider
2 500VA Control Transformer with HT Fuse , Ratio-11000V/230V 1 No. Resin cast
Approved Vendor
60VA Single Phase gun type PT,
PT1-3 3 Nos. SEI/ECS/Precise/Schneider
PTR: 11000V/√3/110V/√3/110V/√3 Resin Cast
3 Approved Vendor
Core-1 Class-0.2
Core-2 Class-3P
[C] RELAYS
Numerical Communicable INST- IDMT 2O/C + 1E/F Relay With
1 K51 110V DC 1 No. CSPC/Schneider/Eq
Highset (51/50+51N/50N,95) CTR-/5A, Flush Mounting
Electromechanical Type Master Trip Relay with 3NO+1NC Conatct,
2 K86 110V DC 1 No. Alstom/CSPC(C&S)/Schneider
Flush Mounting
[D] METERS

1 P3 110V AC Digital MFM Meter,Class-0.2, 96X96, CTR-/5A 1 No. Secure/Eq.

2 P4 110V AC Digital Ammeter with inbuilt Selector switch, 96X96, CTR-/5A 1 No. Secure/Eq.

3 P5 110V AC Digital Voltmeter with inbuilt Selector switch, 96X96, CTR-/5A 1 No. Secure/Eq.

[E] INDICATING LAMP


1 H1 63.5V AC R-Phase Indicating Lamp (Red), LED Type 1 No. L&T (Esbee)
2 H2 63.5V AC Y-Phase Indicating Lamp (Yellow), LED Type 1 No. L&T (Esbee)
3 H3 63.5V AC B-Phase Indicating Lamp (Blue), LED Type 1 No. L&T (Esbee)
4 H4 110V DC ON Indicating Lamp (Red) , LED Type 1 No. L&T (Esbee)
5 H5 110V DC OFF Indicating Lamp (Green), LED Type 1 No. L&T (Esbee)
6 H6 110V DC TRIP Indicating Lamp (Amber), LED Type 1 No. L&T (Esbee)
7 H7 110V DC TCH PB With 1NO+1NC Contact (Yellow), LED Type 1 No. L&T (Esbee)
8 H8 230V AC Spring Charge Indicating Lamp (Blue), LED Type 1 No. L&T (Esbee)
9 H9 110V DC VCB In Test Indicating Lamp (White), LED Type 1 No. L&T (Esbee)
10 H10 110V DC VCB in Service Indicating Lamp (Yellow), LED Type 1 No. L&T (Esbee)
11 H11 110V DC DC FAIL 1 No. L&T (Esbee)
[F] PUSH BUTTON
Em. Stop Push Button (Red) With 1NO+1NC Contact, Mushroom
1 S4 1 No. L&T (Esbee)
head Type
2 S5 6A 1Pole, 2Ways, Without Off L/R Selector Switch, Rotary Type 1 No. Salzer
[G] OTHER CONTROL COMPONENTS
TNC, 1 Pole, 3 Ways, Spring Return to Neutral, Pistol Grip Handle,
1 S6 32A 1 No. Switron/Salzer
Angular Movement : 45+45°, Rotary Type

2 R3 110V DC 4 C/O Aux. Relay for DC Fail 1 No. Omron/PLA /Salzer/Phoenix

3 R94 110V DC 4 C/O Aux. Relay for Antipumping Application 1 No. Omron/PLA /Salzer/Phoenix

4 K631 110V DC 4 C/O Aux. Relay for X'Mer Fault 4 No. Omron/PLA /Salzer/Phoenix

5 F1 6A FP Control MCB for PT Secondary 2 Nos.


Schneider/ABB
6 F2-F7 6A DP Control MCB 6 Nos.
8 Window Annunciator With Accept, Reset ,Test Push Button With
7 AN 90-270V AC/DC 2 No. EAPL/GIC
RS485
8 H 90-270V AC Hooter, 96X96mm 1 No. Esbee/Eq.
9 SPD Surge Protection Device 1 No. Meco/Nelsion/Eq.
Alan/Nuteck
10 PS Power Pack, Input: 230V AC, Output: 110V DC 1 No.
/Micro Power/Gogate
[H] MICELENIOUS ITEMS
1 PS 230V AC 3 Pin Plug Socket 1 No. Anchor
1 PL 230V AC Panel Light Holder 1 No. Anchor
2 SH Space Heater 2 No. Girishego
3 TH Thermostate 1 No. Girishego
4 F8-9 6A SP Control MCB 2 Nos. Schneider/ABB
5 X2-X6,XSH Control Terminals Lot Connectwell
6 End Plate with End Clamp for Control Terminals Lot Connectwell
7 XT1,XPT C.T. & P.T. Terminals Lot Connectwell
Havell's/Polycab/KEI/
PVC Copper Flexible Wire Lot
8 Finolex/RR Cable/Equi.
[I] VCB TROLLEY
1 VCB TROLLEY 1 No.

You might also like