YK Optiview (Rev K 03)

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 24

9/24/2010

YK OptiView w/ Standard Starter Section 1 ELINK YORK TALK 3 Micro Board: 031-01730 or 031-02430
Item Version Rev Date Part Number Cksum Baud COMMENTS
1 C.MLM.01.00 031-01797-000 19.2K If data is requested in Metric mode, must use version C.MLM.01.05d.203 or later
2 C.MLM.01.05D.203 031-01797-000 425C 19.2K Temporary fix for Metric mode requirement. Problem was with digital points.
3 C.MLM.01.06.200 031-01797-000 B918 19.2K Adds missing data points and status codes; supports the Property Data Units feature.
4 C.MLM.01.14.111 031-02474-001 19.2K Has overlapping warning code defects. Chiller engineering is corrrecting
5 C.OPT.01.15.100 031-02474-001 19.2K Medium Voltage (4160V) VSD introduced. Requires 031-02430-001 microboard (Standard Volt VSD = "Low" =208-480 Volts)
6 C.OPT.01.16.100 031-02474-001 19.2K Overlapping warning code defects fixed.
7 C.OPT.01.18.307 031-02474-001 19.2K Flash based on 02430 Microboard
8 C.OPT.01.21.307 18-Sep-09 031-02474-001 19.2K Heat Recovery Objects added. SCR -758
9 C.OPT.01.23.307 031-02474-001 19.2K BV.10 Command discontinued (SCR 802.v23)
10

ENG GPIC BACnet BACnet LON LON N2 ENG


MODBUS ENG Units
PAGE Object Object & Object Profile SNVT Metasys POINT LIST CODE: S = STANDARD O = OPTIONAL N = NOT AVAILABLE PAGE
REF Type Instance Name Name Type Address Address Scale IMP SI POINT LIST DESCRIPTION 1 2 3 4 5 6 7 8 9 10 REF
see note 1 see notes 2, 3 see note 4
P03 AV.1 AV1 REM LEAVING CHW TEMP SP nviCoolSetPt SNVT_temp_p (105) ADF 1 0001 Div 10 °F °C Leaving Chilled Liquid Setpoint-Selected S S S S S S S S S P03
P04 AV.2 AV2 MOTOR CURRENT REMOTE SP nviCapacityLimit SNVT_lev_percent (81) ADF 2 0002 Div 10 % % Motor Current Limit Setpoint S S S S S S S S S P04
P05 AV.3 AV3 HOT WATER REMOTE SP nviHeatSetPt SNVT_temp_p (105) ADF 3 0003 Div 10 °F °C Remote Leaving Cond Liquid SP (Heat Recovery Duty) N N N N N N N O O P05
P06 A AV4 ADF 4 0004 Div 10 P06
P07 BV.1 BV1 REM START STOP CMD nviChillerEnable SNVT_switch (95) BD 1 0061 N/A 0/1 0/1 Remote Start/Stop [Stop/Start] S S S S S S S S S P07
P08 B BV2 BD 2 0062 N/A P08
P09 B BV3 BD 3 0063 N/A P09
P10 B BV4 BD 4 0064 N/A P10
P11 AI.1 AV5 LEAVING CHW TEMP nvoLvgCHWTemp SNVT_temp_p (105) ADF 5 0005 X10 °F °C Leaving Chilled Liquid Temperature S S S S S S S S S P11
P12 AI.2 AV6 ENTERING CHW TEMP nvoEntCHWTemp SNVT_temp_p (105) ADF 6 0006 X10 °F °C Return Chilled Liquid Temperature S S S S S S S S S P12
P13 AI.5 AV7 EVAPORATOR PRESSURE nvoEvapPress SNVT_press (30) ADF 7 0007 X10 PSI kPA Evaporator Pressure (PSIG) S S S S S S S S S P13
P14 AI.6 AV8 CONDENSER PRESSURE nvoCondPress SNVT_press (30) ADF 8 0008 X10 PSI kPA Condenser Pressure (PSIG) S S S S S S S S S P14
P15 AV.14 AV9 OIL DIFERENTIAL PRESSURE nvoOilDiffPress SNVT_press (30) ADF 9 0009 X10 PSI kPA Oil Pressure Differential (PSID) S S S S S S S S S P15
P16 AI.4 AV10 ENTERING COND WATER TEMP nvoEntCNDTemp SNVT_temp_p (105) ADF 10 0010 X10 °F °C Return Condenser Liquid Temperature S S S S S S S S S P16
P17 AI.3 AV11 LEAVING COND WATER TEMP nvoLvgCNDTemp SNVT_temp_p (105) ADF 11 0011 X10 °F °C Leaving Condenser Liquid Temperature S S S S S S S S S P17
P18 AI.11 AV12 MOTOR CURRENT PCT FLA nvoActualCapacit SNVT_lev_percent (81) ADF 12 0012 X10 % % Motor Current Percent FLA S S S S S S S S S P18
P19 A AV13 ADF 13 0013 X10 P19
P20 A AV14 ADF 14 0014 X10 P20
P21 A AV15 ADF 15 0015 X10 P21
P22 A AV16 ADF 16 0016 X1 * P22
P23 A AV17 ADF 17 0017 X1 * P23
P24 A AV18 ADF 18 0018 X10 P24
P25 AV.1 AV19 LEAVING CHW TEMP ACT SP nvoActiveSetpt SNVT_temp_p (105) ADF 19 0019 X10 °F °C Active Leaving Chilled Liquid Setpoint S S S S S S S S S P25
P26 AV.20 AV20 MOTOR CURRENT ACTUAL SP nvoCapacityLimit SNVT_lev_percent (81) ADF 20 0020 X1 % % Active Motor Current Limit Setpoint S S S S S S S S S P26
P27 AV.6 AV21 EVAP SATURATION TEMP nvoEvapSatTemp SNVT_temp_p (105) ADF 21 0021 X10 °F °C Evaporator Saturation Temp S S S S S S S S S P27
P28 AV.7 AV22 COND SATURATION TEMP nvoCondSatTemp SNVT_temp_p (105) ADF 22 0022 X10 °F °C Condenser Saturation Temp S S S S S S S S S P28
P29 AI.7 AV23 DISCHARGE TEMP nvoDischTemp SNVT_temp_p (105) ADF 23 0023 X10 °F °C Discharge Temperature S S S S S S S S S P29
P30 AI.32 AV24 OIL SUMP TEMPERATURE nvoOilSumpTemp SNVT_temp_p (105) ADF 24 0024 X10 °F °C Oil Sump Temperature S S S S S S S S S P30
P31 AI.35 AV25 REFRIGERANT LEVEL POS nvoRefLvlPos SNVT_lev_percent (81) ADF 25 0025 X1 * % % Refrigerant Level Position S S S S S S S S S P31
P32 AV.15 AV26 ACCUM OPERATING HOURS nvoRunHours SNVT_time_hour (124) ADF 26 0026 X1 * hr hr Unit Operating Hours S S S S S S S S S P32
P33 AV.16 AV27 ACCUM SYSTEM STARTS nvoSystemStarts SNVT_count (8) ADF 27 0027 X1 * count* count* Unit System Starts S S S S S S S S S P33
P34 AI.30 AV28 OIL SUMP PRESSURE nvoOilSumpPress SNVT_press (30) ADF 28 0028 X10 PSI kPA Oil Sump Pressure (PSIG) S S S S S S S S S P34
P35 AI.31 AV29 OIL PUMP PRESSURE nvoOilPumpPress SNVT_press (30) ADF 29 0029 X10 PSI kPA Oil Pump Pressure (PSIG) S S S S S S S S S P35
P36 BO.1 BV5 COMPR MOTOR STATUS nvoOnOff SNVT_switch (95) BD 5 0065 N/A 0/1 0/1 Motor Run Contacts S S S S S S S S S P36
P37 BO.14 BV6 LIQUID LINE SOLENOID nvoLiqLineSolnd SNVT_switch (95) BD 6 0066 N/A 0/1 0/1 Liquid Line Solenoid S S S S S S S S S P37
P38 BO.2 BV7 CHW PUMP STAT nvoCHLPump SNVT_switch (95) BD 7 0067 N/A 0/1 0/1 Chilled Liquid Pump S S S S S S S S S P38
P39 BI.4 BV8 STOP SWITCH STATUS nvoPanelStopSw SNVT_switch (95) BD 8 0068 N/A 0/1 0/1 Panel Stop Switch [Start enabled/Stop] S S S S S S S S S P39
P40 BI.1 BV9 CHW FLOW SWITCH STAT nvoCHFlowSwitch SNVT_switch (95) BD 9 0069 N/A 0/1 0/1 Chilled Liquid Flow Switch S S S S S S S S S P40
P41 B BV10 BD 10 0070 N/A P41
P42 B BV11 BD 11 0071 N/A P42

NOTE: The Appropriate YK Status Code Tables Should Accompany this Document

Revision: YK Optiview (Rev K_03) Tab: Standard Property of Johnson Controls, Inc. Page: 1 of 24
9/24/2010

ENG GPIC BACnet BACnet LON LON N2 MODBUS ENG Units ENG
PAGE Object Object & Object Profile SNVT Metasys POINT LIST CODE: S = STANDARD O = OPTIONAL N = NOT AVAILABLE PAGE
REF Type Instance Name Name Type Address Address Scale IMP SI POINT LIST DESCRIPTION 1 2 3 4 5 6 7 8 9 10 REF
see note 1 see notes 2, 3 see note 4
P43 B BV12 BD 12 0072 N/A P43
P44 B BV13 BD 13 0073 N/A P44
P45 B BV14 BD 14 0074 N/A P45
P46 B BV15 BD 15 0075 N/A P46
P47 B BV16 BD 16 0076 N/A P47
P48 B BV17 BD 17 0077 N/A P48
P49 B BV18 BD 18 0078 N/A P49
P50 B BV19 BD 19 0079 N/A P50
P51 B BV20 BD 20 0080 N/A P51
P52 B BV21 BD 21 0081 N/A P52
P53 B BV22 BD 22 0082 N/A P53
P54 B BV23 BD 23 0083 N/A P54
P55 B BV24 BD 24 0084 N/A P55
P56 SC.1 MV1 /AV401 UNIT OPERATION CODE nvoOperCode SNVT_count (8) ADI 1 0030 X1 enum* enum* Operation Code S S S S S S S S S P56
P57 SC.2 MV2 /AV402 UNIT SAFETY FAULT CODE nvoSafetyCode SNVT_count (8) ADI 2 0031 X1 enum* enum* Unit Safety Fault Code S S S S S S S S S P57
P58 SC.3 MV3 /AV403 UNIT CYCLING FAULT CODE nvoCyclingFault SNVT_count (8) ADI 3 0032 X1 enum* enum* Unit Cycling Fault Code S S S S S S S S S P58
P59 SC.4 MV4 /AV404 UNIT WARNING FAULT CODE nvoWarnFault SNVT_count (8) ADI 4 0033 X1 enum* enum* Unit Warning Fault Code S S S S S S S S S P59
P60 SC.5 MV5 /AV405 UNIT CONTROL SOURCE nvoUnitCtrlSrce SNVT_count (8) ADI 5 0034 X1 enum* enum* Unit Control Source [0=Local, 1 = ISN, 2= Analog, 3 = Digital, 4 = Modem] S S S S S S S S S P60
P61 SC MV6 /AV406 ADI 6 0035 X1 P61
P62 SC MV7 /AV407 ADI 7 0036 X1 P62
P63 SC MV8 /AV408 ADI 8 0037 X1 P63
P64 SC MV9 /AV409 ADI 9 0038 X1 P64
P65 SC MV10 /AV410 ADI 10 0039 X1 P65
P66 AI.33 AV30 PROX SENSOR ACT POS nvoBearingPos SNVT_length_mil (20) ADF 30 0040 X1 no units* no units* High Speed Thrust Bearing Proximity Position (mils ) O O O O O O O O O P66
P67 AV.40 AV31 PROX SENSOR REF POS nvoBearingRef SNVT_length_mil (20) ADF 31 0041 X1 no units* no units* High Speed Thrust Bearing Proximity Reference (mils ) O O O O O O O O O P67
P68 A AV32 ADF 32 0042 X1 P68
P69 A AV33 ADF 33 0043 X1 P69
P70 AO.49 AV34 HEATREC HEADPRES CTL VLV nvoHRHPCtlVlv SNVT_lev_percent (81) ADF 34 0044 X10 % % Heat Recovery/Head Pressure Control Valve (Heat app only) N N N N N N N O O P70
P71 AV.19 AV35 ANTI RECYCLE TIME REMAIN nvoAntiRecycle SNVT_time_min (123) ADF 35 0045 X1 * mins mins Anti-Recycle Time Remaining S S S S S S S S S P71
P72 AI.50 AV36 PRE ROTATIONAL VANE POS nvoPRVPosition SNVT_lev_percent (81) ADF 36 0046 X1 * % % Pre Rotation Vanes Position (Future or special quote only) N N N N N O O O O P72
P73 A AV37 ADF 37 0047 X1 * P73
P74 A AV38 ADF 38 0048 X1 * P74
P75 A AV39 ADF 39 0049 X1 * P75
P76 A AV40 ADF 40 0050 X1 P76
P77 A AV41 ADF 41 0051 X1 P77
P78 A AV42 ADF 42 0052 X1 P78
P79 A AV 43 ADF 43 0053 X1 P79
P80 B BV25 BD 25 0085 N/A P80
P81 B BV26 BD 26 0086 N/A P81
P82 B BV27 BD 27 0087 N/A P82
P83 B BV28 BD 28 0088 N/A P83
P84 B BV29 BD 29 0089 N/A P84

NOTES
LON SNVTS Used: SNVT_count (8), SNVT_lev_percent (81), SNVT_temp_p (105), SNVT_switch (95) , SNVT_time_minute (123) , SNVT_freq_hz (76) , SNVT_amp (01) , SNVT_elec_kwh (13) , SNVT_power_kilo (83) , SNVT_volt (44) ,
1
SNVT_volt_ac (138), SNVT_press_p (87)
2 Modbus Scaling indicated in BOLD with an (*) asterisk are User Configurable, if necessary, through the USER's Report. See a qualified JCI technician for details.
Modbus Function Types Supported (ENG P03-P06 = Types 03, 06, 16) , (ENG P07- P10 = 01, 03, 05, 15, 06, 16), (ENG P11-P35, P56-P79 = 03, 04) , (ENG P36-P55, P80 -P84 = 01, 02, 03).
3
All Modbus values are of the type SIGNED with the exception of the User Configurabale values that are all UNSIGNED.
4 BACnet Engineering Units shown with an (*) Asterisk will be assigned a BACnet Eng Unit type of (95) ie NO UNITS.
5 Status Codes: Special Display characters such as (, ), [, ], {, },/,\,%,< and > are not compatible with Elink N2 formats. Substitute text strings , "-", PCT, GTN will be used .
6 Status Codes: Status Code Text string lengths are limited to 60 total characters (including spaces)
7
8
9
10

NOTE: The Appropriate YK Status Code Tables Should Accompany this Document

Revision: YK Optiview (Rev K_03) Tab: Standard Property of Johnson Controls, Inc. Page: 2 of 24
9/24/2010

YK OptiView with Standard Starter Section 2 ELINK YORK TALK 3 Micro Board: 031-01730 or 031-02430
ENG GPIC BACnet BACnet LON LON N2 ENG
MODBUS ENG Units
PAGE Object Object & Object Profile SNVT Metasys POINT LIST CODE: S = STANDARD O = OPTIONAL N = NOT AVAILABLE PAGE
REF Type Instance Name Name Type Address Address Scale IMP SI POINT LIST DESCRIPTION 1 2 3 4 5 6 7 8 9 10 REF
see note 1 see notes 2, 3 see note 4
P03 A ADF 44 0101 Div 10 P03
P04 A ADF 45 0102 Div 10 P04
P05 A ADF 46 0103 Div 10 P05
P06 A ADF 47 0104 Div 10 P06
P07 B BD30 0161 N/A P07
P08 B BD31 0162 N/A P08
P09 B BD32 0163 N/A P09
P10 B BD33 0164 N/A P10
P11 AI.38 AV105 MTR SHAFT END VIBR nvoMBrgShftVibr SNVT_count (8) ADF 48 0105 X10 count* count* Motor Bearing Shaft End Vibration N N N N N N N O O P11
P12 AI.39 AV106 MTR OP SHAFT END VIBR nvoMBrgOpShfVib SNVT_count (8) ADF 49 0106 X10 count* count* Motor Bearing Opposite Shaft End Vibration N N N N N N N O O P12
P13 AI.40 AV107 MTR SHAFT END TEMP nvoMBrgShftTemp SNVT_temp_p (105) ADF 50 0107 X10 °F °C Motor Bearing Shaft End Temperature N N N N N N N O O P13
P14 AI.41 AV108 MTR OP SHAFT END TEMP nvoMBrgOpShfTemp SNVT_temp_p (105) ADF 51 0108 X10 °F °C Motor Bearing Opposite Shaft End Temperature N N N N N N N O O P14
P15 AI.48 AV109 MTR WINDING AVG TEMP nvoAvgMWindTemp SNVT_temp_p (105) ADF 52 0109 X10 °F °C Average Winding Temperature N N N N N N N O O P15
P16 A AV110 ADF 53 0110 X10 P16
P17 A AV111 ADF 54 0111 X10 P17
P18 AI.50 AV112 PRE ROTATIONAL VANE POS nvoPRVPosition SNVT_lev_percent (81) ADF 55 0112 X10 % % Pre Rotation Vanes Position S S S S S S S S S P18
P19 A AV113 ADF 56 0113 X10 P19
P20 AV.42 AV114 REFRIGERANT LEVEL SP nvoRefLvlSP SNVT_lev_percent (81) ADF 57 0114 X10 % % Refrigerant Level Setpoint S S S S S S S S S P20
P21 AI.10 AV115 DROP LEG REFRIG TEMP nvoDropLegTemp SNVT_temp_p (105) ADF 58 0115 X10 °F °C Drop Leg Refrigerant Temperature O O O O O O O O O P21
P22 AI.36 AV116 LEAVING COND HW TEMP nvoLvgCndHWLTmp SNVT_temp_p (105) ADF 59 0116 X1 * °F °C Leaving Heating Condenser Liquid Temperature ( Heat App Only) N N N N N N N O O P22
P23 AV.34 AV117 LEAV COND HW TEMP ACT SP nvoHWActiveSP SNVT_temp_p (105) ADF 60 0117 X1 * °F °C Active Hot Water Setpoint (Heat Recovery or HP app only) N N N N N N N O O P23
P24 AO.49 AV118 HEATREC HEADPRES CTL VLV nvoHR_HP_CtlVlv SNVT_lev_percent (81) ADF 61 0118 X10 % % Heat Recovery/Head Pressure Control Valve ( Heat app only) N N N N N N N O O P24
P25 A AV119 ADF 62 0119 X10 P25
P26 A AV120 ADF 63 0120 X1 P26
P27 A AV121 ADF 64 0121 X10 P27
P28 A AV122 ADF 65 0122 X10 P28
P29 A AV123 ADF 66 0123 X10 P29
P30 A AV124 ADF 67 0124 X10 P30
P31 A AV125 ADF 68 0125 X1 * P31
P32 A AV126 ADF 69 0126 X1 * P32
P33 A AV127 ADF 70 0127 X1 * P33
P34 A AV128 ADF 71 0128 X10 P34
P35 A AV129 ADF 72 0129 X10 P35
P36 B BV105 BD 34 0165 N/A P36
P37 B BV106 BD 35 0166 N/A P37
P38 B BV107 BD 36 0167 N/A P38
P39 B BV108 BD 37 0168 N/A P39
P40 B BV109 BD 38 0169 N/A P40
P41 B BV110 BD 39 0170 N/A P41
P42 B BV111 BD 40 0171 N/A P42

NOTES
11
12
13
14
15
16
17
18
19
20

NOTE: The Appropriate YK Status Code Tables Should Accompany this Document

Revision: YK Optiview (Rev K_03) Tab: Standard Property of Johnson Controls, Inc. Page: 3 of 24
9/24/2010

ENG GPIC BACnet BACnet LON LON N2 ENG


MODBUS ENG Units
PAGE Object Object & Object Profile SNVT Metasys POINT LIST CODE: S = STANDARD O = OPTIONAL N = NOT AVAILABLE PAGE
REF Type Instance Name Name Type Address Address Scale IMP SI POINT LIST DESCRIPTION 1 2 3 4 5 6 7 8 9 10 REF
see note 1 see notes 2, 3 see note 4
P43 B BV112 BD 41 0172 N/A P43
P44 B BV113 BD 42 0173 N/A P44
P45 B BV114 BD 43 0174 N/A P45
P46 B BV115 BD 44 0175 N/A P46
P47 B BV116 BD 45 0176 N/A P47
P48 B BV117 BD 46 0177 N/A P48
P49 B BV118 BD 47 0178 N/A P49
P50 B BV119 BD 48 0179 N/A P50
P51 B BV120 BD 49 0180 N/A P51
P52 B BV121 BD 50 0181 N/A P52
P53 B BV122 BD 51 0182 N/A P53
P54 B BV123 BD 52 0183 N/A P54
P55 B BV124 BD 53 0184 N/A P55
P56 SC MV101 /AV411 ADI 11 0130 X1 P56
P57 SC MV102 /AV412 ADI 12 0131 X1 P57
P58 SC MV103 /AV413 ADI 13 0132 X1 P58
P59 SC MV104 /AV414 ADI 14 0133 X1 P59
P60 SC MV105 /AV415 ADI 15 0134 X1 P60
P61 SC MV106 /AV416 ADI 16 0135 X1 P61
P62 SC MV107 /AV417 ADI 17 0136 X1 P62
P63 SC MV108 /AV418 ADI 18 0137 X1 P63
P64 SC MV109 /AV419 ADI 19 0138 X1 P64
P65 SC MV110 /AV420 ADI 20 0139 X1 P65
P66 A AV130 ADF 73 0140 X1 P66
P67 A AV131 ADF 74 0141 X1 P67
P68 A AV132 ADF 75 0142 X1 P68
P69 A AV133 ADF 76 0143 X1 P69
P70 A AV134 ADF 77 0144 X10 P70
P71 A AV135 ADF 78 0145 X1 * P71
P72 A AV136 ADF 79 0146 X1 * P72
P73 A AV137 ADF 80 0147 X1 * P73
P74 A AV138 ADF 81 0148 X1 * P74
P75 A AV139 ADF 82 0149 X1 * P75
P76 A AV140 ADF 83 0150 X1 P76
P77 A AV141 ADF 84 0151 X1 P77
P78 A AV142 ADF 85 0152 X1 P78
P79 A AV143 ADF 86 0153 X1 P79
P80 B BV125 BD 54 0185 N/A P80
P81 B BV126 BD 55 0186 N/A P81
P82 B BV127 BD 56 0187 N/A P82
P83 B BV128 BD 57 0188 N/A P83
P84 B BV129 BD 58 0189 N/A P84

NOTES
21
22
23
24
25
26
27
28
29
30

NOTE: The Appropriate YK Status Code Tables Should Accompany this Document

Revision: YK Optiview (Rev K_03) Tab: Standard Property of Johnson Controls, Inc. Page: 4 of 24
9/24/2010

YK Status Codes
ENG YK Operational Code ENG YK Safety Fault ENG YK Safety Fault
PAGE SC.1 PAGE SC.2 PAGE SC.2
P56 OPER.CODE P57 SAFETY.FLT P57 SAFETY.FLT
0 Unit Stopped - Ready to Start 0 No Safety Faults Present 52 Evaporator - Low Pressure - Smart Freeze
1 Unit Stopped - Local Shutdown 1 Evaporator - Low Pressure 53 Surge Protection - Excess Surge
2 Unit Stopped - Remote Shutdown 2 Evaporator - Transducer Or Leaving Liquid Probe 54 Reserved
3 Unit Stopped - Warning Active 3 Evaporator - Transducer Or Temperature Sensor 55 Reserved
4 Unit Stopped - Cycling Shutdown 4 Condenser - High Pressure Contacts Open 56 Thrust Bearing - Proximity Probe Clearance
5 Unit Stopped - Safety Shutdown 5 Condenser - High Pressure 57 Thrust Bearing - Limit Switch Open
6 Unit Start Inhibit 6 Condenser - Pressure Transducer Out Of Range 58 Motor - Phase Rotation
7 Unit Starting 7 Auxiliary Safety - Contacts Closed 59 Motor - High Temperature
8 Unit Running - No Abnormal Condition 8 Discharge - Low Temperature 60 Discharge - High Pressure
9 Unit Running - Warning Active 9 Discharge - High Temperature 61 Motor - High Winding Temperature
10 Unit Running - Chiller Unload Before Shutdown 10 Oil - High Temperature 62 Motor - High Bearing Temperature
11 Unit Coastdown 11 Oil - Low Differential Pressure 63 Reserved
12 Unit Running - Modified Run 12 Oil - High Differential Pressure 64 Reserved
13 Unit Stopped - Internal Shutdow 13 Oil - Pump Pressure Transducer Out Of Range 65 Reserved
14 Reserved 14 14 Oil - Sump Pressure Transducer Out Of Range 66 Reserved
15 Reserved 15 15 Oil - High Pressure 67 Condenser - High Pressure - Stopped
16 Oil - Clogged Filter 68 Motor - Ground Fault
17 Oil - Low Differential Seal Pressure 69 Excessive Bearing Vibration
18 Oil - Differential Pressure Calibration 70 Excessive Low Discharge Superheat
19 Oil Separator - Low Level 71 Reserved 71
20 Oil - Variable Speed Pump - Setpoint Not Achieved 72 Reserved 72
21 Control Panel - Power Failure 73 Reserved 73
22 Reserved 22 74 Motor - Lack Of Bearing Lubrication (By custom SQ only)
23 Motor Or Starter - Current Imbalance 75 Reserved 75
24 Thrust Bearing - Proximity Probe Clearance 76 Reserved 76
25 Thrust Bearing - Proximity Probe Uncalibrated 77 Reserved 77
26 Thrust Bearing - Proximity Probe Out Of Range 78 Reserved 78
27 Thrust Bearing - High Oil Temperature 79 Reserved 79
28 Thrust Bearing - Oil Temperature Sensor 80 Reserved 80
29 Reserved 29 81 Reserved 81
30 Reserved 30 82 Reserved 82
31 Reserved 31 83 Reserved 83
32 Reserved 32 84 Reserved 84
33 Reserved 33 85 Reserved 85
34 Reserved 34 86 Reserved 86
35 Reserved 35 87 Reserved 87
36 Reserved 36 88 Reserved 88
37 Reserved 37 89 Reserved 89
38 Reserved 38 90 Reserved 90
39 Reserved 39 91 Reserved 91
40 Reserved 40 92 Reserved 92
41 Reserved 41 93 Reserved 93
42 Reserved 42 94 Reserved 94
43 Reserved 43 95 Motor – High Winding Temperature (text by SQ only)
44 Reserved 44 96 Motor – High Bearing Temperature (text by SQ only)
45 Reserved 45 97 Motor – High Bearing Vibration (text by SQ only)
46 Reserved 46 98 Motor – Cooling Coil Leak (text by SQ only)
47 Reserved 47
48 Reserved 48
49 Starter - Invalid Motor Selection
50 Oil Or Condenser Transducer Error
51 Evaporator - Low Pressure

Revision: YK Optiview (Rev K_03) Tab: Standard Property of Johnson Controls, Inc. Page: 5 of 24
9/24/2010

YK Status Codes
ENG YK Cycling Fault ENG YK Warning Fault
PAGE SC.3 PAGE SC.4
P58 CYCLING.FLT P59 WARNING.FLT
0 No Cycling Faults Present 0 No Warnings Present
1 Multiunit Cycling - Contacts Open 1 Real-Time Clock Failure
2 System Cycling - Contacts Open 2 Setpoint Override
3 Oil - Low Temperature Differential 3 Condenser Or Evaporator Transducer Error
4 Oil - Low Temperature 4 Evaporator - Low Pressure Limit
5 Control Panel - Power Failure 5 Condenser - High Pressure Limit
6 Leaving Chilled Liquid - Low Temperature 6 Condenser Transducer Error
7 Leaving Chilled Liquid - Flow Switch Open 7 Freeze Threat From Operating Chiller
8 Condenser - Flow Switch Open 8 Refrigerant Level Out Of Range
9 Motor Controller - Contacts Open 9 Standby Lube - Low Oil Pressure
10 Motor Controller - Loss Of Current 10 Purge - High Pressure
11 Power Fault 11 Purge - Float Switch Error
12 Control Panel - Schedule 12 Purge - Excess Purge
13 Starter - Low Supply Line Voltage 13 Oil - High Temperature
14 Starter - High Supply Line Voltage 14 Oil - Low Pressure Limit
15 Proximity Probe - Low Supply Voltage 15 Vanes Uncalibrated
16 Oil - Variable Speed Pump - Drive Contacts Open 16 Vanes Uncalibrated - Fixed Speed
17 Reserved 17 17 Reserved 17
18 Reserved 18 18 Reserved 18
19 Reserved 19 19 Reserved 19
20 Reserved 20 20 Oil - Dirty Filter
21 Reserved 21 21 Discharge - High Pressure Limit
22 Reserved 22 22 Vanes Uncalibrated
23 Reserved 23 23 Low Discharge Superheat Limit
24 Reserved 24 24 Low Discharge Superheat Detected
25 Reserved 25 25 Seal Lubrication In Process
26 Reserved 26 26 External I/O - Serial Communications
27 Reserved 27 27 Slide Valve Uncalibrated
28 Reserved 28 28 Freeze Threat - Condenser Flow Switch
29 Reserved 29 29 Surge Protection - Excess Surge Limit
30 Reserved 30 30 Excess Surge Detected
31 Reserved 31 31 Purge - Canister #1 Full
32 Reserved 32 32 Oil Recovery Limit
33 Reserved 33 33 KW Meter Not Calibrated
34 Reserved 34 34 Condenser Or Vgd Sensor Failure
35 Reserved 35 35 Conditions Override Vgd
36 Reserved 36 36 Motor Bearing Lube Suggested
37 Reserved 37 37 Motor Bearing Lube Required
38 Reserved 38 38 Motor Bearing Lube Not Done
39 Reserved 39 39 Reserved 39
77 Motor - High Winding Temperature (text by SQ only) 40 Motor – High Winding Temperature (By custom SQ only)
41 Motor – High Bearing Temperature (By custom SQ only)
42 Motor – High Bearing Vibration (By custom SQ only)
43 Motor – Bearing Vibration Baseline Not Set (By custom SQ only)
44 Condenser- High Refrigerant Level (By custom SQ only)
45 Condenser- Low Refrigerant Level (By custom SQ only)
46 Condenser- Unstable Refrigerant Level (By custom SQ only)

Revision: YK Optiview (Rev K_03) Tab: Standard Property of Johnson Controls, Inc. Page: 6 of 24
9/24/2010

This Page Intentionally Left Blank

Revision: YK Optiview (Rev K_03) Tab: Standard Property of Johnson Controls, Inc. Page: 7 of 24
9/24/2010

This Page Intentionally Left Blank

Revision: YK Optiview (Rev K_03) Tab: Standard Property of Johnson Controls, Inc. Page: 8 of 24
9/24/2010

YK OptiView with SSS Section 1 ELINK YORK TALK 3 Micro Board: 031-01730 or 031-02430
Item Version Rev Date Part Number Cksum Baud COMMENTS
1 C.MLM.01.00 031-01797-000 19.2K If data is requested in Metric mode, must use version C.MLM.01.05d.203 or later
2 C.MLM.01.05.203 031-01797-000 425C 19.2K Temporary fix for Metric mode requirement. Problem was with digital points.
3 C.MLM.01.06.200 031-01797-000 B918 19.2K Adds missing data points and status codes; supports the Property Data Units feature.
4 C.MLM.01.14.111 031-02474-001 19.2K Has overlapping warning code defects. Chiller engineering is corrrecting
5 C.OPT.01.15.100 031-02474-001 19.2K Medium Voltage (4160V) VSD introduced. Requires 031-02430-001 microboard (Standard Volt VSD = "Low" =208-480 Volts)
6 C.OPT.01.16.100 031-02474-001 19.2K Overlapping warning code defects fixed.
7 C.OPT.01.18.307 031-02474-001 19.2K Flash based on 02430 Microboard
8 C.OPT.01.21.307 18-Sep-09 031-02474-001 19.2K Heat Recovery Objects added. SCR -758
9 C.OPT.01.23.307 031-02474-001 19.2K BV.10 Command discontinued (SCR 802.v23)
10

ENG GPIC BACnet BACnet LON LON N2 ENG


MODBUS ENG Units
PAGE Object Object & Object Profile SNVT Metasys POINT LIST CODE: S = STANDARD O = OPTIONAL N = NOT AVAILABLE PAGE
REF Type Instance Name Name Type Address Address Scale IMP SI POINT LIST DESCRIPTION 1 2 3 4 5 6 7 8 9 10 REF
see note 1 see notes 2, 3 see note 4
P03 AV.1 AV1 REM LEAVING CHW TEMP SP nviCoolSetPt SNVT_temp_p (105) ADF 1 0001 Div 10 °F °C Leaving Chilled Liquid Setpoint-Selected S S S S S S S S S P03
P04 AV.2 AV2 MOTOR CURRENT REMOTE SP nviCapacityLimit SNVT_lev_percent (81) ADF 2 0002 Div 10 % % Motor Current Limit Setpoint S S S S S S S S S P04
P05 AV.3 AV3 HOT WATER REMOTE SP nviHeatSetPt SNVT_temp_p (105) ADF 3 0003 Div 10 °F °C Remote Leaving Cond Liquid SP (Heat Recovery Duty) N N N N N N N O O P05
P06 A AV4 ADF 4 0004 Div 10 P06
P07 BV.1 BV1 REM START STOP CMD nviChillerEnable SNVT_switch (95) BD 1 0061 N/A 0/1 0/1 Remote Start/Stop [Stop/Start] S S S S S S S S S P07
P08 B BV2 BD 2 0062 N/A P08
P09 B BV3 BD 3 0063 N/A P09
P10 B BV4 BD 4 0064 N/A P10
P11 AI.1 AV5 LEAVING CHW TEMP nvoLvgCHWTemp SNVT_temp_p (105) ADF 5 0005 X10 °F °C Leaving Chilled Liquid Temperature S S S S S S S S S P11
P12 AI.2 AV6 ENTERING CHW TEMP nvoEntCHWTemp SNVT_temp_p (105) ADF 6 0006 X10 °F °C Return Chilled Liquid Temperature S S S S S S S S S P12
P13 AI.5 AV7 EVAPORATOR PRESSURE nvoEvapPress SNVT_press (30) ADF 7 0007 X10 PSI kPA Evaporator Pressure S S S S S S S S S P13
P14 AI.6 AV8 CONDENSER PRESSURE nvoCondPress SNVT_press (30) ADF 8 0008 X10 PSI kPA Condenser Pressure S S S S S S S S S P14
P15 AV.14 AV9 OIL DIFERENTIAL PRESSURE nvoOilDiffPress SNVT_press (30) ADF 9 0009 X10 PSI kPA Oil Pressure Differential S S S S S S S S S P15
P16 AI.4 AV10 ENTERING COND WATER TEMP nvoEntCNDTemp SNVT_temp_p (105) ADF 10 0010 X10 °F °C Return Condenser Liquid Temperature S S S S S S S S S P16
P17 AI.3 AV11 LEAVING COND WATER TEMP nvoLvgCNDTemp SNVT_temp_p (105) ADF 11 0011 X10 °F °C Leaving Condenser Liquid Temperature S S S S S S S S S P17
P18 AI.11 AV12 MOTOR CURRENT PCT FLA nvoActualCapacit SNVT_lev_percent (81) ADF 12 0012 X10 % % Motor Current Percent FLA S S S S S S S S S P18
P19 AI.16 AV13 PHASE A MOTOR CURRENT nvoCurrent_A SNVT_amp (1) ADF 13 0013 X10 amps amps Solid State Starter Phase A Current S S S S S S S S S P19
P20 AI.17 AV14 PHASE B MOTOR CURRENT nvoCurrent_B SNVT_amp (1) ADF 14 0014 X10 amps amps Solid State Starter Phase B Current S S S S S S S S S P20
P21 AI.18 AV15 PHASE C MOTOR CURRENT nvoCurrent_C SNVT_amp (1) ADF 15 0015 X10 amps amps Solid State Starter Phase C Current S S S S S S S S S P21
P22 AI.13 AV16 PHASE A_B LINE VOLTS nvoVoltage_A SNVT_volt (44) ADF 16 0016 X1 * volts volts Solid State Starter Phase A Voltage S S S S S S S S S P22
P23 AI.14 AV17 PHASE B_C LINE VOLTS nvoVoltage_B SNVT_volt (44) ADF 17 0017 X1 * volts volts Solid State Starter Phase B Voltage S S S S S S S S S P23
P24 AI.15 AV18 PHASE C_A LINE VOLTS nvoVoltage_C SNVT_volt (44) ADF 18 0018 X10 volts volts Solid State Starter Phase C Voltage S S S S S S S S S P24
P25 AV.1 AV19 LEAVING CHW TEMP ACT SP nvoActiveSetpt SNVT_temp_p (105) ADF 19 0019 X10 °F °C Leaving Chilled Liquid Setpoint-Selected S S S S S S S S S P25
P26 AV.20 AV20 MOTOR CURRENT ACTUAL SP nvoCapacityLimit SNVT_lev_percent (81) ADF 20 0020 X1 % % Motor Current Limit Setpoint-Selected S S S S S S S S S P26
P27 AV.6 AV21 EVAP SATURATION TEMP nvoEvapSatTemp SNVT_temp_p (105) ADF 21 0021 X10 °F °C Evaporator Saturation Temp S S S S S S S S S P27
P28 AV.7 AV22 COND SATURATION TEMP nvoCondSatTemp SNVT_temp_p (105) ADF 22 0022 X10 °F °C Condenser Saturation Temp S S S S S S S S S P28
P29 AI.7 AV23 DISCHARGE TEMP nvoDischTemp SNVT_temp_p (105) ADF 23 0023 X10 °F °C Discharge Temperature S S S S S S S S S P29
P30 AI.32 AV24 OIL SUMP TEMPERATURE nvoOilSumpTemp SNVT_temp_p (105) ADF 24 0024 X10 °F °C Oil Sump Temperature S S S S S S S S S P30
P31 AI.35 AV25 REFRIGERANT LEVEL POS nvoRefLvlPos SNVT_lev_percent (81) ADF 25 0025 X1 * % % Refrigerant Level Position S S S S S S S S S P31
P32 AV.15 AV26 ACCUM OPERATING HOURS nvoRunHours SNVT_time_hour (124) ADF 26 0026 X1 * hr hr Unit Operating Hours S S S S S S S S S P32
P33 AV.16 AV27 ACCUM SYSTEM STARTS nvoSystemStarts SNVT_count (8) ADF 27 0027 X1 * count* count* Unit System Starts S S S S S S S S S P33
P34 AI.30 AV28 OIL SUMP PRESSURE nvoOilSumpPress SNVT_press (30) ADF 28 0028 X10 PSI kPA Oil Sump Pressure S S S S S S S S S P34
P35 AI.31 AV29 OIL PUMP PRESSURE nvoOilPumpPress SNVT_press (30) ADF 29 0029 X10 PSI kPA Oil Pump Pressure S S S S S S S S S P35
P36 BO.1 BV5 COMPR MOTOR STATUS nvoOnOff SNVT_switch (95) BD 5 0065 N/A 0/1 0/1 Motor Run Contacts S S S S S S S S S P36
P37 BO.14 BV6 LIQUID LINE SOLENOID nvoLiqLineSolnd SNVT_switch (95) BD 6 0066 N/A 0/1 0/1 Liquid Line Solenoid S S S S S S S S S P37
P38 BO.2 BV7 CHW PUMP STAT nvoCHLPump SNVT_switch (95) BD 7 0067 N/A 0/1 0/1 Chilled Liquid Pump S S S S S S S S S P38
P39 BI.4 BV8 STOP SWITCH STATUS nvoPanelStopSw SNVT_switch (95) BD 8 0068 N/A 0/1 0/1 Panel Stop Switch [Start enabled/Stop] S S S S S S S S S P39
P40 BI.1 BV9 CHW FLOW SWITCH STAT nvoCHFlowSwitch SNVT_switch (95) BD 9 0069 N/A 0/1 0/1 Chilled Liquid Flow Switch S S S S S S S S S P40
P41 B BV10 BD 10 0070 N/A P41
P42 B BV11 BD 11 0071 N/A P42

NOTE: The Appropriate YK Status Code Tables Should Accompany this Document

Revision: YK Optiview (Rev K_03) Tab: with SSS Property of Johnson Controls, Inc. Page: 9 of 24
9/24/2010

ENG GPIC BACnet BACnet LON LON N2 MODBUS ENG Units ENG
PAGE Object Object & Object Profile SNVT Metasys POINT LIST CODE: S = STANDARD O = OPTIONAL N = NOT AVAILABLE PAGE
REF Type Instance Name Name Type Address Address Scale IMP SI POINT LIST DESCRIPTION 1 2 3 4 5 6 7 8 9 10 REF
see note 1 see notes 2, 3 see note 4
P43 B BV12 BD 12 0072 N/A P43
P44 B BV13 BD 13 0073 N/A P44
P45 B BV14 BD 14 0074 N/A P45
P46 B BV15 BD 15 0075 N/A P46
P47 B BV16 BD 16 0076 N/A P47
P48 B BV17 BD 17 0077 N/A P48
P49 B BV18 BD 18 0078 N/A P49
P50 B BV19 BD 19 0079 N/A P50
P51 B BV20 BD 20 0080 N/A P51
P52 B BV21 BD 21 0081 N/A P52
P53 B BV22 BD 22 0082 N/A P53
P54 B BV23 BD 23 0083 N/A P54
P55 B BV24 BD 24 0084 N/A P55
P56 SC.1 MV1 /AV401 UNIT OPERATION CODE nvoOperCode SNVT_count (8) ADI 1 0030 X1 enum* enum* Operation Code S S S S S S S S S P56
P57 SC.2 MV2 /AV402 UNIT SAFETY FAULT CODE nvoSafetyCode SNVT_count (8) ADI 2 0031 X1 enum* enum* Unit Safety Fault Code S S S S S S S S S P57
P58 SC.3 MV3 /AV403 UNIT CYCLING FAULT CODE nvoCyclingFault SNVT_count (8) ADI 3 0032 X1 enum* enum* Unit Cycling Fault Code S S S S S S S S S P58
P59 SC.4 MV4 /AV404 UNIT WARNING FAULT CODE nvoWarnFault SNVT_count (8) ADI 4 0033 X1 enum* enum* Unit Warning Fault Code S S S S S S S S S P59
P60 SC.5 MV5 /AV405 UNIT CONTROL SOURCE nvoUnitCtrlSrce SNVT_count (8) ADI 5 0034 X1 enum* enum* Unit Control Source [0=Local, 1 = ISN, 2= Analog, 3 = Digital, 4 = Modem] S S S S S S S S S P60
P61 SC MV6 /AV406 ADI 6 0035 X1 P61
P62 SC MV7 /AV407 ADI 7 0036 X1 P62
P63 SC MV8 /AV408 ADI 8 0037 X1 P63
P64 SC MV9 /AV409 ADI 9 0038 X1 P64
P65 SC MV10 /AV410 ADI 10 0039 X1 P65
P66 AI.33 AV30 PROX SENSOR ACT POS nvoBearingPos SNVT_length_mil (20) ADF 30 0040 X1 no units* no units* High Speed Thrust Bearing Proximity Position (mils ) S S S S S S S S S P66
P67 AV.40 AV31 PROX SENSOR REF POS nvoBearingRef SNVT_length_mil (20) ADF 31 0041 X1 no units* no units* High Speed Thrust Bearing Proximity Reference (mils ) S S S S S S S S S P67
P68 A AV32 ADF 32 0042 X1 P68
P69 A AV33 ADF 33 0043 X1 P69
P70 AO.49 AV34 HEATREC HEADPRES CTL VLV nvoHRHPCtlVlv SNVT_lev_percent (81) ADF 34 0044 X10 % % Heat Recovery/Head Pressure Control Valve ( Heat app only) N N N N N N N O O P70
P71 AV.19 AV35 ANTI RECYCLE TIME REMAIN nvoAntiRecycle SNVT_time_min (123) ADF 35 0045 X1 * mins mins Anti-Recycle Time Remaining S S S S S S S S S P71
P72 AI.50 AV36 PRE ROTATIONAL VANE POS nvoPRVPosition SNVT_lev_percent (81) ADF 36 0046 X1 * % % Pre Rotation Vanes Position (Future or special quote only) N N N N N O O O O P72
P73 A AV37 ADF 37 0047 X1 * P73
P74 A AV38 ADF 38 0048 X1 * P74
P75 A AV39 ADF 39 0049 X1 * P75
P76 A AV40 ADF 40 0050 X1 P76
P77 A AV41 ADF 41 0051 X1 P77
P78 A AV42 ADF 42 0052 X1 P78
P79 A AV 43 ADF 43 0053 X1 P79
P80 B BV25 BD 25 0085 N/A P80
P81 B BV26 BD 26 0086 N/A P81
P82 B BV27 BD 27 0087 N/A P82
P83 B BV28 BD 28 0088 N/A P83
P84 B BV29 BD 29 0089 N/A P84

NOTES
LON SNVTS Used: SNVT_count (8), SNVT_lev_percent (81), SNVT_temp_p (105), SNVT_switch (95) , SNVT_time_minute (123) , SNVT_freq_hz (76) , SNVT_amp (01) , SNVT_elec_kwh (13) , SNVT_power_kilo (83) , SNVT_volt (44) ,
1
SNVT_volt_ac (138), SNVT_press_p (87)
2 Modbus Scaling indicated in BOLD with an (*) asterisk are User Configurable, if necessary, through the USER's Report. See a qualified JCI technician for details.
Modbus Function Types Supported (ENG P03-P06 = Types 03, 06, 16) , (ENG P07- P10 = 01, 03, 05, 15, 06, 16), (ENG P11-P35, P56-P79 = 03, 04) , (ENG P36-P55, P80 -P84 = 01, 02, 03).
3
All Modbus values are of the type SIGNED with the exception of the User Configurabale values that are all UNSIGNED.
4 BACnet Engineering Units shown with an (*) Asterisk will be assigned a BACnet Eng Unit type of (95) ie NO UNITS.
5 Status Codes: Special Display characters such as (, ), [, ], {, },/,\,%,< and > are not compatible with Elink N2 formats. Substitute text strings , "-", PCT, GTN will be used .
6 Status Codes: Status Code Text string lengths are limited to 60 total characters (including spaces)
7
8
9
10

NOTE: The Appropriate YK Status Code Tables Should Accompany this Document

Revision: YK Optiview (Rev K_03) Tab: with SSS Property of Johnson Controls, Inc. Page: 10 of 24
9/24/2010

YK OptiView with SSS Section 2 ELINK YORK TALK 3 Micro Board: 031-01730 or 031-02430
ENG GPIC BACnet BACnet LON LON N2 ENG
MODBUS ENG Units
PAGE Object Object & Object Profile SNVT Metasys POINT LIST CODE: S = STANDARD O = OPTIONAL N = NOT AVAILABLE PAGE
REF Type Instance Name Name Type Address Address Scale IMP SI POINT LIST DESCRIPTION 1 2 3 4 5 6 7 8 9 10 REF
see note 1 see notes 2, 3 see note 4
P03 A ADF 44 0101 Div 10 P03
P04 A ADF 45 0102 Div 10 P04
P05 A ADF 46 0103 Div 10 P05
P06 A ADF 47 0104 Div 10 P06
P07 B BD30 0161 N/A P07
P08 B BD31 0162 N/A P08
P09 B BD32 0163 N/A P09
P10 B BD33 0164 N/A P10
P11 AI.38 AV105 MTR SHAFT END VIBR nvoMBrgShftVibr SNVT_count (8) ADF 48 0105 X10 count* count* Motor Bearing Shaft End Vibration N N N N N N N O O P11
P12 AI.39 AV106 MTR OP SHAFT END VIBR nvoMBrgOpShfVib SNVT_count (8) ADF 49 0106 X10 count* count* Motor Bearing Opposite Shaft End Vibration N N N N N N N O O P12
P13 AI.40 AV107 MTR SHAFT END TEMP nvoMBrgShftTemp SNVT_temp_p (105) ADF 50 0107 X10 °F °C Motor Bearing Shaft End Temperature N N N N N N N O O P13
P14 AI.41 AV108 MTR OP SHAFT END TEMP nvoMBrgOpShfTemp SNVT_temp_p (105) ADF 51 0108 X10 °F °C Motor Bearing Opposite Shaft End Temperature N N N N N N N O O P14
P15 AI.48 AV109 MTR WINDING AVG TEMP nvoAvgMWindTemp SNVT_temp_p (105) ADF 52 0109 X10 °F °C Average Winding Temperature N N N N N N N O O P15
P16 A AV110 ADF 53 0110 X10 P16
P17 A AV111 ADF 54 0111 X10 P17
P18 AI.50 AV112 PRE ROTATIONAL VANE POS nvoPRVPosition SNVT_lev_percent (81) ADF 55 0112 X10 % % Pre Rotation Vanes Position S S S S S S S S S P18
P19 A AV113 ADF 56 0113 X10 P19
P20 AV.42 AV114 REFRIGERANT LEVEL SP nvoRefLvlSP SNVT_lev_percent (81) ADF 57 0114 X10 % % Refrigerant Level Setpoint S S S S S S S S S P20
P21 AI.10 AV115 DROP LEG REFRIG TEMP nvoDropLegTemp SNVT_temp_p (105) ADF 58 0115 X10 °F °C Drop Leg Refrigerant Temperature O O O O O O O O O P21
P22 AI.36 AV116 LEAVING COND HW TEMP nvoLvgCndHWLTmp SNVT_temp_p (105) ADF 59 0116 X1 * °F °C Leaving Heating Condenser Liquid Temperature ( Heat App Only) N N N N N N N O O P22
P23 AV.34 AV117 LEAV COND HW TEMP ACT SP nvoHWActiveSP SNVT_temp_p (105) ADF 60 0117 X1 * °F °C Active Hot Water Setpoint (Heat Recovery or HP apps Only) N N N N N N N O O P23
P24 AO.49 AV118 HEATREC HEADPRES CTL VLV nvoHR_HP_CtlVlv SNVT_lev_percent (81) ADF 61 0118 X10 % % Heat Recovery/Head Pressure Control Valve ( Heat app only) N N N N N N N O O P24
P25 AV.25 AV119 SSS MOTOR INPUT POWER nvoSSSMtrInptPwr SNVT_power_kilo (28) ADF 62 0119 X10 kW kW SSS Motor Input Power N N N N N N N O O P25
P26 AV.26 AV120 SSS INPUT KWH nvoSSSKWH SNVT_elec_kwh ADF 63 0120 X1 kWh kWh SSS Motor Kilowatt Hours (Future or special quote only) O O O O O O O O O P26
P27 A AV121 ADF 64 0121 X10 P27
P28 A AV122 ADF 65 0122 X10 P28
P29 A AV123 ADF 66 0123 X10 P29
P30 A AV124 ADF 67 0124 X10 P30
P31 A AV125 ADF 68 0125 X1 * P31
P32 A AV126 ADF 69 0126 X1 * P32
P33 A AV127 ADF 70 0127 X1 * P33
P34 A AV128 ADF 71 0128 X10 P34
P35 A AV129 ADF 72 0129 X10 P35
P36 B BV105 BD 34 0165 N/A P36
P37 B BV106 BD 35 0166 N/A P37
P38 B BV107 BD 36 0167 N/A P38
P39 B BV108 BD 37 0168 N/A P39
P40 B BV109 BD 38 0169 N/A P40
P41 B BV110 BD 39 0170 N/A P41
P42 B BV111 BD 40 0171 N/A P42

NOTES
11
12
13
14
15
16
17
18
19
20

NOTE: The Appropriate YK Status Code Tables Should Accompany this Document

Revision: YK Optiview (Rev K_03) Tab: with SSS Property of Johnson Controls, Inc. Page: 11 of 24
9/24/2010

ENG GPIC BACnet BACnet LON LON N2 ENG


MODBUS ENG Units
PAGE Object Object & Object Profile SNVT Metasys POINT LIST CODE: S = STANDARD O = OPTIONAL N = NOT AVAILABLE PAGE
REF Type Instance Name Name Type Address Address Scale IMP SI POINT LIST DESCRIPTION 1 2 3 4 5 6 7 8 9 10 REF
see note 1 see notes 2, 3 see note 4
P43 B BV112 BD 41 0172 N/A P43
P44 B BV113 BD 42 0173 N/A P44
P45 B BV114 BD 43 0174 N/A P45
P46 B BV115 BD 44 0175 N/A P46
P47 B BV116 BD 45 0176 N/A P47
P48 B BV117 BD 46 0177 N/A P48
P49 B BV118 BD 47 0178 N/A P49
P50 B BV119 BD 48 0179 N/A P50
P51 B BV120 BD 49 0180 N/A P51
P52 B BV121 BD 50 0181 N/A P52
P53 B BV122 BD 51 0182 N/A P53
P54 B BV123 BD 52 0183 N/A P54
P55 B BV124 BD 53 0184 N/A P55
P56 SC MV101 /AV411 ADI 11 0130 X1 P56
P57 SC MV102 /AV412 ADI 12 0131 X1 P57
P58 SC MV103 /AV413 ADI 13 0132 X1 P58
P59 SC MV104 /AV414 ADI 14 0133 X1 P59
P60 SC MV105 /AV415 ADI 15 0134 X1 P60
P61 SC MV106 /AV416 ADI 16 0135 X1 P61
P62 SC MV107 /AV417 ADI 17 0136 X1 P62
P63 SC MV108 /AV418 ADI 18 0137 X1 P63
P64 SC MV109 /AV419 ADI 19 0138 X1 P64
P65 SC MV110 /AV420 ADI 20 0139 X1 P65
P66 A AV130 ADF 73 0140 X1 P66
P67 A AV131 ADF 74 0141 X1 P67
P68 A AV132 ADF 75 0142 X1 P68
P69 A AV133 ADF 76 0143 X1 P69
P70 A AV134 ADF 77 0144 X10 P70
P71 A AV135 ADF 78 0145 X1 * P71
P72 A AV136 ADF 79 0146 X1 * P72
P73 A AV137 ADF 80 0147 X1 * P73
P74 A AV138 ADF 81 0148 X1 * P74
P75 A AV139 ADF 82 0149 X1 * P75
P76 A AV140 ADF 83 0150 X1 P76
P77 A AV141 ADF 84 0151 X1 P77
P78 A AV142 ADF 85 0152 X1 P78
P79 A AV143 ADF 86 0153 X1 P79
P80 B BV125 BD 54 0185 N/A P80
P81 B BV126 BD 55 0186 N/A P81
P82 B BV127 BD 56 0187 N/A P82
P83 B BV128 BD 57 0188 N/A P83
P84 B BV129 BD 58 0189 N/A P84

NOTES
21
22
23
24
25
26
27
28
29
30

NOTE: The Appropriate YK Status Code Tables Should Accompany this Document

Revision: YK Optiview (Rev K_03) Tab: with SSS Property of Johnson Controls, Inc. Page: 12 of 24
9/24/2010

YK Status Codes
ENG YK Operational Code ENG YK Safety Fault ENG YK Safety Fault
PAGE SC.1 PAGE SC.2 PAGE SC.2
P56 OPER.CODE P57 SAFETY.FLT P57 SAFETY.FLT
0 Unit Stopped - Ready to Start 0 No Safety Faults Present 52 Evaporator - Low Pressure - Smart Freeze
1 Unit Stopped - Local Shutdown 1 Evaporator - Low Pressure 53 Surge Protection - Excess Surge
2 Unit Stopped - Remote Shutdown 2 Evaporator - Transducer Or Leaving Liquid Probe 54 Reserved
3 Unit Stopped - Warning Active 3 Evaporator - Transducer Or Temperature Sensor 55 Reserved
4 Unit Stopped - Cycling Shutdown 4 Condenser - High Pressure Contacts Open 56 Thrust Bearing - Proximity Probe Clearance
5 Unit Stopped - Safety Shutdown 5 Condenser - High Pressure 57 Thrust Bearing - Limit Switch Open
6 Unit Start Inhibit 6 Condenser - Pressure Transducer Out Of Range 58 Motor - Phase Rotation
7 Unit Starting 7 Auxiliary Safety - Contacts Closed 59 Motor - High Temperature
8 Unit Running - No Abnormal Condition 8 Discharge - Low Temperature 60 Discharge - High Pressure
9 Unit Running - Warning Active 9 Discharge - High Temperature 61 Motor - High Winding Temperature
10 Unit Running - Chiller Unload Before Shutdown 10 Oil - High Temperature 62 Motor - High Bearing Temperature
11 Unit Coastdown 11 Oil - Low Differential Pressure 63 Reserved 63
12 Unit Running - Modified Run 12 Oil - High Differential Pressure 64 Reserved 64
13 Unit Stopped - Internal Shutdow 13 Oil - Pump Pressure Transducer Out Of Range 65 Reserved 65
14 Reserved 14 14 Oil - Sump Pressure Transducer Out Of Range 66 Reserved 66
15 Reserved 15 15 Oil - High Pressure 67 Condenser - High Pressure - Stopped
16 Oil - Clogged Filter 68 Motor - Ground Fault
17 Oil - Low Differential Seal Pressure 69 Excessive Bearing Vibration
18 Oil - Differential Pressure Calibration 70 Excessive Low Discharge Superheat
19 Oil Separator - Low Level 71 LCSSS - Phase A Open Scr
20 Oil - Variable Speed Pump - Setpoint Not Achieved 72 LCSSS - Phase B Open Scr
21 Control Panel - Power Failure 73 LCSSS - Phase C Open Scr
22 (Reserved) 74 Motor - Lack Of Bearing Lubrication (By custom SQ only)
23 Motor Or Starter - Current Imbalance 75 Reserved 75
24 Thrust Bearing - Proximity Probe Clearance 76 Reserved 76
25 Thrust Bearing - Proximity Probe Uncalibrated 77 Reserved 77
26 Thrust Bearing - Proximity Probe Out Of Range 78 Reserved 78
27 Thrust Bearing - High Oil Temperature 79 MVSSS - Phase Rotation
28 Thrust Bearing - Oil Temperature Sensor 80 MVSSS - Motor Or Starter - Current Imbalance
29 Reserved 29 81 MVSSS - 105% Motor Current Overload
30 Reserved 30 82 MVSSS - High Instantaneous Current
31 Reserved 31 83 MVSSS - Failed Scr
32 Reserved 32 84 MVSSS - High Heatsink Temperature - Running
33 Reserved 33 85 MVSSS - Ground Fault
34 Reserved 34 86 MVSSS - Contactor Fault
35 Reserved 35 87 MVSSS - Motor Drive Fault
36 Reserved 36 88 MVSSS - Disconnect
37 Reserved 37 89 Reserved 89
38 LCSSS - Phase Rotation 90 Reserved 90
39 LCSSS - Motor Or Starter - Current Imbalance 91 Reserved 91
40 LCSSS - 105% Motor Current Overload 92 Reserved 92
41 LCSSS - High Instantaneous Current 93 Reserved 93
42 LCSSS - Open Scr 94 Reserved 94
43 LCSSS - Phase A Shorted Scr 95 Motor – High Winding Temperature (text by SQ only)
44 LCSSS - Phase B Shorted Scr 96 Motor – High Bearing Temperature (text by SQ only)
45 LCSSS - Phase C Shorted Scr 97 Motor – High Bearing Vibration (text by SQ only)
46 LCSSS - High Phase A Heatsink Temperature - Running 98 Motor – Cooling Coil Leak (text by SQ only)
47 LCSSS - High Phase B Heatsink Temperature - Running
48 LCSSS - High Phase C Heatsink Temperature - Running
49 Starter - Invalid Motor Selection
50 Oil Or Condenser Transducer Error
51 Evaporator - Low Pressure

Revision: YK Optiview (Rev K_03) Tab: with SSS Property of Johnson Controls, Inc. Page: 13 of 24
9/24/2010

YK Status Codes
ENG YK Cycling Fault ENG YK Cycling Fault ENG YK Warning Fault
PAGE SC.3 PAGE SC.3 PAGE SC.4
P58 CYCLING.FLT P58 CYCLING.FLT P59 WARNING.FLT
0 No Cycling Faults Present 52 Reserved 52 0 No Warnings Present
1 Multiunit Cycling - Contacts Open 53 Reserved 53 1 Real-Time Clock Failure
2 System Cycling - Contacts Open 54 Reserved 54 2 Setpoint Override
3 Oil - Low Temperature Differential 55 Reserved 55 3 Condenser Or Evaporator Transducer Error
4 Oil - Low Temperature 56 LCSSS Initialization Failed 4 Evaporator - Low Pressure Limit
5 Control Panel - Power Failure 57 LCSSS Shutdown - Requesting Fault Data... 5 Condenser - High Pressure Limit
6 Leaving Chilled Liquid - Low Temperature 58 LCSSS - Low Phase A Temperature Sensor 6 Condenser Transducer Error
7 Leaving Chilled Liquid - Flow Switch Open 59 LCSSS - Low Phase B Temperature Sensor 7 Freeze Threat From Operating Chiller
8 Condenser - Flow Switch Open 60 LCSSS - Low Phase C Temperature Sensor 8 Refrigerant Level Out Of Range
9 Motor Controller - Contacts Open 61 LCSSS - Phase Locked Loop 9 Standby Lube - Low Oil Pressure
10 Motor Controller - Loss Of Current 62 LCSSS - Power Fault 10 Purge - High Pressure
11 Power Fault 63 LCSSS - High Supply Line Voltage 11 Purge - Float Switch Error
12 Control Panel - Schedule 64 LCSSS - Low Supply Line Voltage 12 Purge - Excess Purge
13 Starter - Low Supply Line Voltage 65 LCSSS - Invalid Current Scale Selection 13 Oil - High Temperature
14 Starter - High Supply Line Voltage 66 LCSSS - Run Signal 14 Oil - Low Pressure Limit
15 Proximity Probe - Low Supply Voltage 67 LCSSS - Serial Communications 15 Vanes Uncalibrated
16 Oil - Variable Speed Pump - Drive Contacts Open 68 LCSSS - Stop Contacts Open 16 Vanes Uncalibrated - Fixed Speed
17 Reserved 17 69 LCSSS - Invalid Full Load Amps Setting 17 Harmonic Filter - Operation Inhibited
18 Reserved 18 70 LCSSS - Logic Board Processor 18 Harmonic Filter - Data Loss
19 Reserved 19 71 LCSSS - Logic Board Processor 19 Harmonic Filter - Input Frequency Range
20 Reserved 20 72 LCSSS - Logic Board Power Supply 20 Oil - Dirty Filter
21 Reserved 21 73 Reserved 73 21 Discharge - High Pressure Limit
22 Reserved 22 74 LCSSS - Serial Communications 22 Vanes Uncalibrated
23 Reserved 23 75 LCSSS - Phase Loss 23 Low Discharge Superheat Limit
24 Reserved 24 76 Reserved 76 24 Low Discharge Superheat Detected
25 Reserved 25 77 Motor - High Winding Temperature 25 Seal Lubrication In Process
26 Reserved 26 78 Reserved 78 26 External I/O - Serial Communications
27 Reserved 27 79 Reserved 79 27 Slide Valve Uncalibrated
28 Reserved 28 80 Reserved 80 28 Freeze Threat - Condenser Flow Switch
29 Reserved 29 81 Motor Controller - Contacts Open 29 Surge Protection - Excess Surge Limit
30 Reserved 30 82 Reserved 82 30 Excess Surge Detected
31 Reserved 31 83 Reserved 83 31 Purge - Canister #1 Full
32 Reserved 32 84 Reserved 84 32 Oil Recovery Limit
33 Reserved 33 85 Reserved 85 33 KW Meter Not Calibrated
34 Reserved 34 86 Reserved 86 34 Condenser Or Vgd Sensor Failure
35 Reserved 35 87 MVSSS - Initialization Failed 35 Conditions Override Vgd
36 Reserved 36 88 MVSSS Shutdown - Requesting Fault Data... 36 Motor Bearing Lube Suggested
37 Reserved 37 89 MVSSS - Power Fault 37 Motor Bearing Lube Required
38 Reserved 38 90 MVSSS - High Supply Line Voltage 38 Motor Bearing Lube Not Done
39 Reserved 39 91 MVSSS - Low Supply Line Voltage 39 Harmonic Filter - Data Loss
40 Reserved 40 92 MVSSS - Run Signal 40 Motor – High Winding Temperature (By custom SQ only)
41 Reserved 41 93 MVSSS - Serial Communications 41 Motor – High Bearing Temperature (By custom SQ only)
42 Reserved 42 94 MVSSS - Stop Contacts Open 42 Motor – High Bearing Vibration (By custom SQ only)
43 Reserved 43 95 MVSSS - Logic Board Power Supply 43 Motor – Bearing Vibration Baseline Not Set (By custom SQ
44 Reserved 44 96 MVSSS - Phase Loss 44 Condenser- High Refrigerant Level (By custom SQ only)
45 Reserved 45 97 MVSSS - Serial Communications (Panel) 45 Condenser- Low Refrigerant Level (By custom SQ only)
46 Reserved 46 98 Reserved 98 46 Condenser- Unstable Refrigerant Level (By custom SQ only)
47 Reserved 47 99 Reserved 99
48 Reserved 48 100 Reserved 100
49 Reserved 49 101 Reserved 101
50 Reserved 50 102 Reserved 102
51 Reserved 51 103 Reserved 103

Revision: YK Optiview (Rev K_03) Tab: with SSS Property of Johnson Controls, Inc. Page: 14 of 24
9/24/2010

This Page Intentionally Left Blank

Revision: YK Optiview (Rev K_03) Tab: with SSS Property of Johnson Controls, Inc. Page: 15 of 24
9/24/2010

This Page Intentionally Left Blank

Revision: YK Optiview (Rev K_03) Tab: with SSS Property of Johnson Controls, Inc. Page: 16 of 24
9/24/2010

YK OptiView with VSD Section 1 ELINK YORK TALK 3 Micro Board: 031-01730 or 031-02430
Item Version Rev Date Part Number Cksum Baud COMMENTS
1 C.MLM.01.00 031-01797-000 19.2K If data is requested in Metric mode, must use version C.MLM.01.05d.203 or later
2 C.MLM.01.05.203 031-01797-000 425C 19.2K Temporary fix for Metric mode requirement. Problem was with digital points.
3 C.MLM.01.06.200 031-01797-000 B918 19.2K Adds missing data points and status codes; supports the Property Data Units feature.
4 C.MLM.01.14.111 031-02474-001 19.2K Has overlapping warning code defects. Chiller engineering is corrrecting
5 C.OPT.01.15.100 031-02474-001 19.2K Medium Voltage (4160V) VSD introduced. Requires 031-02430-001 microboard (Standard Volt VSD = "Low" =208-480 Volts)
6 C.OPT.01.16.100 031-02474-001 19.2K Overlapping warning code defects fixed.
7 C.OPT.01.18.307 031-02474-001 19.2K Flash based on 02430 Microboard
8 C.OPT.01.21.307 18-Sep-09 031-02474-001 19.2K Heat Recovery Objects added. SCR -758
9 C.OPT.01.23.307 031-02474-001 19.2K BV.10 Command discontinued (SCR 802.v23)
10

ENG GPIC BACnet BACnet LON LON N2 ENG


MODBUS ENG Units
PAGE Object Object & Object Profile SNVT Metasys POINT LIST CODE: S = STANDARD O = OPTIONAL N = NOT AVAILABLE PAGE
REF Type Instance Name Name Type Address Address Scale IMP SI POINT LIST DESCRIPTION 1 2 3 4 5 6 7 8 9 10 REF
see note 1 see notes 2, 3 see note 4
P03 AV.1 AV1 REM LEAVING CHW TEMP SP nviCoolSetPt SNVT_temp_p ADF 1 0001 Div 10 °F °C Leaving Chilled Liquid Setpoint-Selected S S S S S S S S S P03
P04 AV.2 AV2 MOTOR CURRENT REMOTE SP nviCapacityLimit SNVT_temp_p ADF 2 0002 Div 10 % % Motor Current Limit Setpoint S S S S S S S S S P04
P05 AV.3 AV3 HOT WATER REMOTE SP nviHeatSetPt SNVT_temp_p ADF 3 0003 Div 10 °F °C Remote Leaving Cond Liquid SP (Heat Recovery Duty) N N N N N N N O O P05
P06 A AV4 ADF 4 0004 Div 10 P06
P07 BV.1 BV1 REM START STOP CMD nviChillerEnable SNVT_switch BD 1 0061 N/A 0/1 0/1 Remote Start/Stop [Stop/Start] S S S S S S S S S P07
P08 B BV2 BD 2 0062 N/A P08
P09 BV.10 BV3 VSD FIXED SPEED SELECT nviVSDFixedSpd SNVT_switch BD 3 0063 N/A 0/1 0/1 Variable Speed Drive Fixed Speed [Auto / Fixed] S S S S S S S S N P09
P10 B BV4 BD 4 0064 N/A P10
P11 AI.1 AV5 LEAVING CHW TEMP nvoLvgCHWTemp SNVT_temp_p ADF 5 0005 X10 °F °C Leaving Chilled Liquid Temperature S S S S S S S S S P11
P12 AI.2 AV6 ENTERING CHW TEMP nvoEntCHWTemp SNVT_temp_p ADF 6 0006 X10 °F °C Return Chilled Liquid Temperature S S S S S S S S S P12
P13 AI.5 AV7 EVAPORATOR PRESSURE nvoEvapPress SNVT_press_p ADF 7 0007 X10 PSI kPA Evaporator Pressure S S S S S S S S S P13
P14 AI.6 AV8 CONDENSER PRESSURE nvoCondPress SNVT_press_p ADF 8 0008 X10 PSI kPA Condenser Pressure S S S S S S S S S P14
P15 AV.14 AV9 OIL DIFERENTIAL PRESSURE nvoOilDiffPress SNVT_press_p ADF 9 0009 X10 PSI kPA Oil Pressure Differential S S S S S S S S S P15
P16 AI.4 AV10 ENTERING COND WATER TEMP nvoEntCNDTemp SNVT_temp_p ADF 10 0010 X10 °F °C Return Condenser Liquid Temperature S S S S S S S S S P16
P17 AI.3 AV11 LEAVING COND WATER TEMP nvoLvgCNDTemp SNVT_temp_p ADF 11 0011 X10 °F °C Leaving Condenser Liquid Temperature S S S S S S S S S P17
P18 AI.11 AV12 MOTOR CURRENT PCT FLA nvoActualCapacit SNVT_lev_percent ADF 12 0012 X10 % % Motor Current Percent FLA S S S S S S S S S P18
P19 AI.53 AV13 PHASE A MOTOR CURRENT nvoCurrent_A SNVT_amp ADF 13 0013 X10 amps amps VSD Phase A Current S S S S S S S S S P19
P20 AI.54 AV14 PHASE B MOTOR CURRENT nvoCurrent_B SNVT_amp ADF 14 0014 X10 amps amps VSD Phase B Current S S S S S S S S S P20
P21 AI.55 AV15 PHASE C MOTOR CURRENT nvoCurrent_C SNVT_amp ADF 15 0015 X10 amps amps VSD Phase C Current S S S S S S S S S P21
P22 A AV16 ADF 16 0016 X1 * P22
P23 A AV17 ADF 17 0017 X1 * P23
P24 A AV18 ADF 18 0018 X10 P24
P25 AV.1 AV19 LEAVING CHW TEMP ACT SP nvoActiveSetpt SNVT_temp_p ADF 19 0019 X10 °F °C Leaving Chilled Liquid Setpoint-Selected S S S S S S S S S P25
P26 AV.20 AV20 MOTOR CURRENT ACTUAL SP nvoCapacityLimit SNVT_temp_p ADF 20 0020 X1 % % Motor Current Limit Setpoint-Selected S S S S S S S S S P26
P27 AV.6 AV21 EVAP SATURATION TEMP nvoEvapSatTemp SNVT_temp_p ADF 21 0021 X10 °F °C Evaporator Saturation Temp S S S S S S S S S P27
P28 AV.7 AV22 COND SATURATION TEMP nvoCondSatTemp SNVT_temp_p ADF 22 0022 X10 °F °C Condenser Saturation Temp S S S S S S S S S P28
P29 AI.7 AV23 DISCHARGE TEMP nvoDischTemp SNVT_temp_p ADF 23 0023 X10 °F °C Discharge Temperature S S S S S S S S S P29
P30 AI.32 AV24 OIL SUMP TEMPERATURE nvoOilSumpTemp SNVT_temp_p ADF 24 0024 X10 °F °C Oil Sump Temperature S S S S S S S S S P30
P31 AI.35 AV25 REFRIGERANT LEVEL POS nvoRefLvlPos SNVT_lev_percent ADF 25 0025 X1 * % % Refrigerant Level Position S S S S S S S S S P31
P32 AV.15 AV26 ACCUM OPERATING HOURS nvoRunHours SNVT_time_hours ADF 26 0026 X1 * hr hr Unit Operating Hours S S S S S S S S S P32
P33 AV.16 AV27 ACCUM SYSTEM STARTS nvoSystemStarts SNVT_count ADF 27 0027 X1 * count* count* Unit System Starts S S S S S S S S S P33
P34 AI.30 AV28 OIL SUMP PRESSURE nvoOilSumpPress SNVT_press_p ADF 28 0028 X10 PSI kPA Oil Sump Pressure S S S S S S S S S P34
P35 AI.31 AV29 OIL PUMP PRESSURE nvoOilPumpPress SNVT_press_p ADF 29 0029 X10 PSI kPA Oil Pump Pressure S S S S S S S S S P35
P36 BO.1 BV5 COMPR MOTOR STATUS nvoOnOff SNVT_switch BD 5 0065 N/A 0/1 0/1 Motor Run Contacts S S S S S S S S S P36
P37 BO.14 BV6 LIQUID LINE SOLENOID nvoLiqLineSolnd SNVT_switch BD 6 0066 N/A 0/1 0/1 Liquid Line Solenoid S S S S S S S S S P37
P38 BO.2 BV7 CHW PUMP STAT nvoCHPump SNVT_switch BD 7 0067 N/A 0/1 0/1 Chilled Liquid Pump S S S S S S S S S P38
P39 BI.4 BV8 STOP SWITCH STATUS nvoPanelStopSw SNVT_switch BD 8 0068 N/A 0/1 0/1 Panel Stop Switch [Start enabled/Stop] S S S S S S S S S P39
P40 BI.1 BV9 CHW FLOW SWITCH STAT nvoCHFlowSwitch SNVT_switch BD 9 0069 N/A 0/1 0/1 Chilled Liquid Flow Switch S S S S S S S S S P40
P41 B BV10 BD 10 0070 N/A P41
P42 B BV11 BD 11 0071 N/A P42

NOTE: The Appropriate YK Status Code Tables Should Accompany this Document

Revision: YK Optiview (Rev K_03) Tab: with VSD Property of Johnson Controls, Inc. Page: 17 of 24
9/24/2010

ENG GPIC BACnet BACnet LON LON N2 MODBUS ENG Units ENG
PAGE Object Object & Object Profile SNVT Metasys POINT LIST CODE: S = STANDARD O = OPTIONAL N = NOT AVAILABLE PAGE
REF Type Instance Name Name Type Address Address Scale IMP SI POINT LIST DESCRIPTION 1 2 3 4 5 6 7 8 9 10 REF
see note 1 see notes 2, 3 see note 4
P43 B BV12 BD 12 0072 N/A P43
P44 B BV13 BD 13 0073 N/A P44
P45 B BV14 BD 14 0074 N/A P45
P46 B BV15 BD 15 0075 N/A P46
P47 B BV16 BD 16 0076 N/A P47
P48 BV.42 BV17 ACC VALVE SURGE MAP nvoACCVSM SNVT_switch BD 17 0077 N/A 0/1 0/1 Adaptive Capacity Control VSM [False/True] (Low Voltage VSD only) S S S S O O O O O P48
P49 BV.43 BV18 ACC NEW SURGE POINT nvoACCNSP SNVT_switch BD 18 0078 N/A 0/1 0/1 Adaptive Capacity Control NSP [False/True] (Low Voltage VSD only) S S S S O O O O O P49
P50 BO.30 BV19 VSD COOL PUMP RUN RELAY nvoVSDWtrPumpRly SNVT_switch BD 19 0079 N/A 0/1 0/1 Variable Speed Drive Water Pump Relay (Low Voltage VSD only) S S S S O O O O O P50
P51 BV.46 BV20 VSD HARMONIC FILTER INST nvoHarmonicFltr SNVT_switch BD 20 0080 N/A 0/1 0/1 Harmonic Filter Installed [False/True] (Low Voltage VSD only) S S S S O O O O O P51
P52 BV.44 BV21 ACC SURGE DETECTION TYPE nvoACCSurgeType SNVT_switch BD 21 0081 N/A 0/1 0/1 ACC Surge Type [Delta P/Current] (Low Voltage VSD only) S S S S O O O O O P52
P53 B BV22 BD 22 0082 N/A P53
P54 B BV23 BD 23 0083 N/A P54
P55 B BV24 BD 24 0084 N/A P55
P56 SC.1 MV1 /AV401 UNIT OPERATION CODE nvoOperCode SNVT_count ADI 1 0030 X1 enum* enum* Operation Code S S S S S S S S S P56
P57 SC.2 MV2 /AV402 UNIT SAFETY FAULT CODE nvoSafetyCode SNVT_count ADI 2 0031 X1 enum* enum* Unit Safety Fault Code S S S S S S S S S P57
P58 SC.3 MV3 /AV403 UNIT CYCLING FAULT CODE nvoCyclingFault SNVT_count ADI 3 0032 X1 enum* enum* Unit Cycling Fault Code S S S S S S S S S P58
P59 SC.4 MV4 /AV404 UNIT WARNING FAULT CODE nvoWarnFault SNVT_count ADI 4 0033 X1 enum* enum* Unit Warning Fault Code S S S S S S S S S P59
P60 SC.5 MV5 /AV405 UNIT CONTROL SOURCE nvoUnitCtrlSrce SNVT_count ADI 5 0034 X1 enum* enum* Unit Control Source [0=Local, 1 = ISN, 2= Analog, 3 = Digital, 4 = Modem] S S S S S S S S S P60
P61 SC MV6 /AV406 ADI 6 0035 X1 P61
P62 SC MV7 /AV407 ADI 7 0036 X1 P62
P63 SC MV8 /AV408 ADI 8 0037 X1 P63
P64 SC MV9 /AV409 ADI 9 0038 X1 P64
P65 SC MV10 /AV410 ADI 10 0039 X1 P65
P66 AI.33 AV30 PROX SENSOR ACT POS nvoBearingPos SNVT_length_mil (20) ADF 30 0040 X1 no units* no units* High Speed Thrust Bearing Proximity Position (mils ) S S S S S S S S S P66
P67 AV.40 AV31 PROX SENSOR REF POS nvoBearingRef SNVT_length_mil (20) ADF 31 0041 X1 no units* no units* High Speed Thrust Bearing Proximity Reference (mils ) S S S S S S S S S P67
P68 A.19 AV32 ANTI RECYCLE TIME REMAIN nvoAntiRecycle SNVT_time_minute ADF 32 0042 X1 mins mins Anti-Recycle Time Remaining S S S S S S S S S P68
P69 AV.79 AV33 ACC MAP PRV POS nvoACCMapPRVPos SNVT_lev_percent ADF 33 0043 X1 % % ACC Map PRV Position (Low Volt VSD only) S S S S S S S S S P69
P70 AI.51 AV34 VSD OUTPUT VOLTAGE nvoVSDOutputVolt SNVT_volt_ac ADF 34 0044 X10 volts volts Variable Speed Drive Output Voltage (Low Voltage VSD only) S S S S S S S S S P70
P71 AV.71 AV35 VSD INPUT KW nvoVSDInputPwr SNVT_power_kilo ADF 35 0045 X1 * kw kw Variable Speed Drive Input Power S S S S S S S S S P71
P72 AV.72 AV36 VSD INPUT KWH nvoVSDKWH SNVT_elec_kwh ADF 36 0046 X1 * kwh kwh Variable Speed Drive Kilowatt Hours S S S S S S S S S P72
P73 AI.56 AV37 VSD DC LINK VOLTAGE nvoVSDDCBusVolt SNVT_count ADF 37 0047 X1 * volts volts Variable Speed Drive DC Bus Voltage (Low Voltage VSD only) S S S S S S S S S P73
P74 AI.57 AV38 VSD DC LINK CURRENT nvoVSDInvertCur SNVT_amp ADF 38 0048 X1 * amps amps Variable Speed Drive Inverter Link Current (Low Voltage VSD only) S S S S S S S S S P74
P75 AV.75 AV39 VSD SURGE COUNT nvoACCSurgeCnt SNVT_count ADF 39 0049 X1 * count* count* ACC Surge Count (Low Volt VSD only) S S S S O O O O O P75
P76 AI.52 AV40 VSD OUTPUT FREQUENCY nvoVSDOutFreq SNVT_freq_hz ADF 40 0050 X1 hz hz Variable Speed Drive Output Frequency S S S S S S S S S P76
P77 AV.83 AV41 VSD MAX VOLTAGE THD nvoHFltrMaxVTHD SNVT_lev_percent ADF 41 0051 X1 % % Harmonic Filter Max Voltage Total Harmonic Distortion (Low Volt VSD only) S S S S O O O O O P77
P78 AV.84 AV42 VSD MAX CURRENT TDD nvoHFltrMaxATDD SNVT_lev_percent ADF 42 0052 X1 % % Harmonic Filter Max Current Total Demand Distortion (Low Volt VSD only) S S S S O O O O O P78
P79 AV.82 AV43 VSD HFILTER SUPPLY KVA nvoHFltrTotSKVA SNVT_count ADF 43 0053 X1 kVA kVA Harmonic Filter Total Supply KVA (Low Voltage VSD only) S S S S O O O O O P79
P80 B BV25 BD 25 0085 N/A P80
P81 B BV26 BD 26 0086 N/A P81
P82 B BV27 BD 27 0087 N/A P82
P83 B BV28 BD 28 0088 N/A P83
P84 B BV29 BD 29 0089 N/A P84

NOTES
LON SNVTS Used: SNVT_count (8), SNVT_lev_percent (81), SNVT_temp_p (105), SNVT_switch (95) , SNVT_time_minute (123) , SNVT_freq_hz (76) , SNVT_amp (01) , SNVT_elec_kwh (13) , SNVT_power_kilo (83) , SNVT_volt (44) ,
1
SNVT_volt_ac (138), SNVT_press_p (87)
2 Modbus Scaling indicated in BOLD with an (*) asterisk are User Configurable, if necessary, through the USER's Report. See a qualified JCI technician for details.
Modbus Function Types Supported (ENG P03-P06 = Types 03, 06, 16) , (ENG P07- P10 = 01, 03, 05, 15, 06, 16), (ENG P11-P35, P56-P79 = 03, 04) , (ENG P36-P55, P80 -P84 = 01, 02, 03).
3
All Modbus values are of the type SIGNED with the exception of the User Configurabale values that are all UNSIGNED.
4 BACnet Engineering Units shown with an (*) Asterisk will be assigned a BACnet Eng Unit type of (95) ie NO UNITS.
5 Status Codes: Special Display characters such as (, ), [, ], {, },/,\,%,< and > are not compatible with Elink N2 formats. Substitute text strings , "-", PCT, GTN will be used .
6 Status Codes: Status Code Text string lengths are limited to 60 total characters (including spaces)
7
8
9
10

NOTE: The Appropriate YK Status Code Tables Should Accompany this Document

Revision: YK Optiview (Rev K_03) Tab: with VSD Property of Johnson Controls, Inc. Page: 18 of 24
9/24/2010

YK OptiView with VSD Section 2 ELINK YORK TALK 3 Micro Board: 031-01730 or 031-02430
ENG GPIC BACnet BACnet LON LON N2 ENG
MODBUS ENG Units
PAGE Object Object & Object Profile SNVT Metasys POINT LIST CODE: S = STANDARD O = OPTIONAL N = NOT AVAILABLE PAGE
REF Type Instance Name Name Type Address Address Scale IMP SI POINT LIST DESCRIPTION 1 2 3 4 5 6 7 8 9 10 REF
see note 1 see notes 2, 3 see note 4
P03 A ADF 44 0101 Div 10 P03
P04 A ADF 45 0102 Div 10 P04
P05 A ADF 46 0103 Div 10 P05
P06 A ADF 47 0104 Div 10 P06
P07 B BD30 0161 N/A P07
P08 B BD31 0162 N/A P08
P09 B BD32 0163 N/A P09
P10 B BD33 0164 N/A P10
P11 AI.38 AV105 MTR SHAFT END VIBR nvoMBrgShftVibr SNVT_count (8) ADF 48 0105 X10 count* count* Motor Bearing Shaft End Vibration N N N N N N N O O P11
P12 AI.39 AV106 MTR OP SHAFT END VIBR nvoMBrgOpShfVib SNVT_count (8) ADF 49 0106 X10 count* count* Motor Bearing Opposite Shaft End Vibration N N N N N N N O O P12
P13 AI.40 AV107 MTR SHAFT END TEMP nvoMBrgShftTemp SNVT_temp_p (105) ADF 50 0107 X10 °F °C Motor Bearing Shaft End Temperature N N N N N N N O O P13
P14 AI.41 AV108 MTR OP SHAFT END TEMP nvoMBrgOpShfTemp SNVT_temp_p (105) ADF 51 0108 X10 °F °C Motor Bearing Opposite Shaft End Temperature N N N N N N N O O P14
P15 AI.48 AV109 MTR WINDING AVG TEMP nvoAvgMWindTemp SNVT_temp_p (105) ADF 52 0109 X10 °F °C Average Winding Temperature N N N N N N N O O P15
P16 AI.58 AV110 VSD INTERNAL AMBIEN TEMP nvoVSDInternalT SNVT_temp_p (105) ADF 53 0110 X10 °F °C VSD Internal Ambient Temp (Low voltage VSD only) S S S S O O O O O P16
P17 AI.59 AV111 VSD CONVERTER HSINK TEMP nvoVSDHeatSinkT SNVT_temp_p (105) ADF 54 0111 X10 °F °C VSD Converter Heatsink Temp (Low voltage VSD only) S S S S O O O O O P17
P18 AI.50 AV112 PRE ROTATIONAL VANE POS nvoPRVPosition SNVT_lev_percent (81) ADF 55 0112 X10 % % Pre Rotation Vanes Position S S S S S S S S S P18
P19 AV.78 AV113 ACC MAP OUTPUT FREQ nvoACCMapOutFreq SNVT_freq_hz (76) ADF 56 0113 X10 hz hz ACC Map Output Frequency (Low Voltage VSD only) S S S S O O O O O P19
P20 AV.42 AV114 REFRIGERANT LEVEL SP nvoRefLvlSP SNVT_lev_percent (81) ADF 57 0114 X10 % % Refrigerant Level Setpoint S S S S S S S S S P20
P21 AI.10 AV115 DROP LEG REFRIG TEMP nvoDropLegTemp SNVT_temp_p (105) ADF 58 0115 X10 °F °C Drop Leg Refrigerant Temperature O O O O O O O O O P21
P22 AI.36 AV116 LEAVING COND HW TEMP nvoLvgCndHWLTmp SNVT_temp_p (105) ADF 59 0116 X1 * °F °C Leaving Heating Condenser Liquid Temperature ( Heat App Only) N N N N N N N O O P22
P23 AV.34 AV117 LEAV COND HW TEMP ACT SP nvoHWActiveSP SNVT_temp_p (105) ADF 60 0117 X1 * °F °C Active Leaving Cond Liq Setpoint (Heat Recovery Only) N N N N N N N O O P23
P24 AO.49 AV118 HEATREC HEADPRES CTL VLV nvoHR_HP_CtlVlv SNVT_lev_percent (81) ADF 61 0118 X10 % % Heat Recovery/Head Pressure Control Valve ( Heat app only) N N N N N N N O O P24
P25 A AV119 ADF 62 0119 X10 P25
P26 A AV120 ADF 63 0120 X1 P26
P27 A AV121 ADF 64 0121 X10 P27
P28 A AV122 ADF 65 0122 X10 P28
P29 A AV123 ADF 66 0123 X10 P29
P30 A AV124 ADF 67 0124 X10 P30
P31 A AV125 ADF 68 0125 X1 * P31
P32 A AV126 ADF 69 0126 X1 * P32
P33 A AV127 ADF 70 0127 X1 * P33
P34 A AV128 ADF 71 0128 X10 P34
P35 A AV129 ADF 72 0129 X10 P35
P36 B BV105 BD 34 0165 N/A P36
P37 B BV106 BD 35 0166 N/A P37
P38 B BV107 BD 36 0167 N/A P38
P39 B BV108 BD 37 0168 N/A P39
P40 B BV109 BD 38 0169 N/A P40
P41 B BV110 BD 39 0170 N/A P41
P42 B BV111 BD 40 0171 N/A P42

NOTES
11
12
13
14
15
16
17
18
19
20

NOTE: The Appropriate YK Status Code Tables Should Accompany this Document

Revision: YK Optiview (Rev K_03) Tab: with VSD Property of Johnson Controls, Inc. Page: 19 of 24
9/24/2010

ENG GPIC BACnet BACnet LON LON N2 ENG


MODBUS ENG Units
PAGE Object Object & Object Profile SNVT Metasys POINT LIST CODE: S = STANDARD O = OPTIONAL N = NOT AVAILABLE PAGE
REF Type Instance Name Name Type Address Address Scale IMP SI POINT LIST DESCRIPTION 1 2 3 4 5 6 7 8 9 10 REF
see note 1 see notes 2, 3 see note 4
P43 B BV112 BD 41 0172 N/A P43
P44 B BV113 BD 42 0173 N/A P44
P45 B BV114 BD 43 0174 N/A P45
P46 B BV115 BD 44 0175 N/A P46
P47 B BV116 BD 45 0176 N/A P47
P48 B BV117 BD 46 0177 N/A P48
P49 B BV118 BD 47 0178 N/A P49
P50 B BV119 BD 48 0179 N/A P50
P51 B BV120 BD 49 0180 N/A P51
P52 B BV121 BD 50 0181 N/A P52
P53 B BV122 BD 51 0182 N/A P53
P54 B BV123 BD 52 0183 N/A P54
P55 B BV124 BD 53 0184 N/A P55
P56 SC MV101 /AV411 ADI 11 0130 X1 P56
P57 SC MV102 /AV412 ADI 12 0131 X1 P57
P58 SC MV103 /AV413 ADI 13 0132 X1 P58
P59 SC MV104 /AV414 ADI 14 0133 X1 P59
P60 SC MV105 /AV415 ADI 15 0134 X1 P60
P61 SC MV106 /AV416 ADI 16 0135 X1 P61
P62 SC MV107 /AV417 ADI 17 0136 X1 P62
P63 SC MV108 /AV418 ADI 18 0137 X1 P63
P64 SC MV109 /AV419 ADI 19 0138 X1 P64
P65 SC MV110 /AV420 ADI 20 0139 X1 P65
P66 A AV130 ADF 73 0140 X1 P66
P67 A AV131 ADF 74 0141 X1 P67
P68 A AV132 ADF 75 0142 X1 P68
P69 A AV133 ADF 76 0143 X1 P69
P70 A AV134 ADF 77 0144 X10 P70
P71 A AV135 ADF 78 0145 X1 * P71
P72 A AV136 ADF 79 0146 X1 * P72
P73 A AV137 ADF 80 0147 X1 * P73
P74 A AV138 ADF 81 0148 X1 * P74
P75 A AV139 ADF 82 0149 X1 * P75
P76 A AV140 ADF 83 0150 X1 P76
P77 A AV141 ADF 84 0151 X1 P77
P78 A AV142 ADF 85 0152 X1 P78
P79 A AV143 ADF 86 0153 X1 P79
P80 B BV125 BD 54 0185 N/A P80
P81 B BV126 BD 55 0186 N/A P81
P82 B BV127 BD 56 0187 N/A P82
P83 B BV128 BD 57 0188 N/A P83
P84 B BV129 BD 58 0189 N/A P84

NOTES
21
22
23
24
25
26
27
28
29
30

NOTE: The Appropriate YK Status Code Tables Should Accompany this Document

Revision: YK Optiview (Rev K_03) Tab: with VSD Property of Johnson Controls, Inc. Page: 20 of 24
9/24/2010

YK Status Codes
ENG YK Operational Code ENG YK Safety Fault ENG YK Safety Fault
PAGE SC.1 PAGE SC.2 PAGE SC.2
P56 OPER.CODE P57 SAFETY.FLT P57 SAFETY.FLT
0 Unit Stopped - Ready to Start 0 No Safety Faults Present 52 Evaporator - Low Pressure - Smart Freeze
1 Unit Stopped - Local Shutdown 1 Evaporator - Low Pressure 53 Surge Protection - Excess Surge
2 Unit Stopped - Remote Shutdown 2 Evaporator - Transducer Or Leaving Liquid Probe 54 VSD - High Inverter Baseplate Temperature
3 Unit Stopped - Warning Active 3 Evaporator - Transducer Or Temperature Sensor 55 VSD Harmonic Filter - High Baseplate Temperature
4 Unit Stopped - Cycling Shutdown 4 Condenser - High Pressure Contacts Open 56 Thrust Bearing - Proximity Probe Clearance
5 Unit Stopped - Safety Shutdown 5 Condenser - High Pressure 57 Thrust Bearing - Limit Switch Open
6 Unit Start Inhibit 6 Condenser - Pressure Transducer Out Of Range 58 Motor - Phase Rotation
7 Unit Starting 7 Auxiliary Safety - Contacts Closed 59 Motor - High Temperature
8 Unit Running - No Abnormal Condition 8 Discharge - Low Temperature 60 Discharge - High Pressure
9 Unit Running - Warning Active 9 Discharge - High Temperature 61 Motor - High Winding Temperature
10 Unit Running - Chiller Unload Before Shutdown 10 Oil - High Temperature 62 Motor - High Bearing Temperature
11 Unit Coastdown 11 Oil - Low Differential Pressure 63 VSD / MVVSD - High Phase A Inverter Baseplate Temp
12 Unit Running - Modified Run 12 Oil - High Differential Pressure 64 VSD / MVVSD - High Phase B Inverter Baseplate Temp
13 Unit Stopped - Internal Shutdow 13 Oil - Pump Pressure Transducer Out Of Range 65 VSD / MVVSD - High Phase C Inverter Baseplate Temp
14 Reserved 14 14 Oil - Sump Pressure Transducer Out Of Range 66 VSD Motor Or Starter - Current Imbalance
15 Reserved 15 15 Oil - High Pressure 67 Condenser - High Pressure - Stopped
16 Oil - Clogged Filter 68 Motor - Ground Fault
17 Oil - Low Differential Seal Pressure 69 Excessive Bearing Vibration
18 Oil - Differential Pressure Calibration 70 Excessive Low Discharge Superheat
19 Oil Separator - Low Level 71 Reserved 71
20 Oil - Variable Speed Pump - Setpoint Not Achieved 72 Reserved 72
21 Control Panel - Power Failure 73 Reserved 73
22 Reserved 22 74 Motor - Lack Of Bearing Lubrication (By custom SQ only)
23 Motor Or Starter - Current Imbalance 75 VSD / MVVSD - Low Frequency Detected
24 Thrust Bearing - Proximity Probe Clearance 76 MVVSD- Feedback Sensor
25 Thrust Bearing - Proximity Probe Uncalibrated 77 MVVSD - Control Fault
26 Thrust Bearing - Proximity Probe Out Of Range 78 MVVSD - Drive Boot Failure
27 Thrust Bearing - High Oil Temperature 79 Reserved 79
28 Thrust Bearing - Oil Temperature Sensor 80 Reserved 80
29 VSD - High Heatsink Temperature 81 Reserved 81
30 VSD / MVVSD - 105% Motor Current Overload 82 Reserved 82
31 VSD - High Phase A Inverter Heatsink Temperature 83 Reserved 83
32 VSD - High Phase B Inverter Heatsink Temperature 84 Reserved 84
33 VSD - High Phase C Inverter Heatsink Temperature 85 Reserved 85
34 VSD - High Converter Heatsink Temperature 86 Reserved 86
35 VSD - Precharge Lockout 87 Reserved 87
36 Harmonic Filter - High Heatsink Temperature 88 Reserved 88
37 Harmonic Filter - High Total Demand Distortion 89 VSD - Power Transformer High Temperature
38 Reserved 38 90 VSD - High Output Frequency
39 Reserved 39 91 MVVSD - Ground Fault
40 Reserved 40 92 VSD - Main Control Board Fault
41 Reserved 41 93 MVVSD - Contactor Fault
42 Reserved 42 94 MVVSD - Interlock Fault
43 Reserved 43 95 Motor – High Winding Temperature (text by SQ only)
44 Reserved 44 96 Motor – High Bearing Temperature (text by SQ only)
45 Reserved 45 97 Motor – High Bearing Vibration (text by SQ only)
46 Reserved 46 98 Motor – Cooling Coil Leak (text by SQ only)
47 Reserved 47
48 Reserved 48
49 Starter - Invalid Motor Selection
50 Oil Or Condenser Transducer Error
51 Evaporator - Low Pressure

Revision: YK Optiview (Rev K_03) Tab: with VSD Property of Johnson Controls, Inc. Page: 21 of 24
9/24/2010

YK Status Codes
ENG YK Cycling Fault ENG YK Cycling Fault ENG YK Cycling Fault
PAGE SC.3 PAGE SC.3 PAGE SC.3
P58 CYCLING.FLT P58 CYCLING.FLT P58 CYCLING.FLT
0 No Cycling Faults Present 52 VSD Harmonic Filter - Logic Board Power Supply 104 MVVSD DC Bus Voltage Imbalance _ CL
1 Multiunit Cycling - Contacts Open 53 VSD Harmonic Filter - Run Signal 105 MVVSD - Precharge - DC Bus Voltage Imbalance - AU
2 System Cycling - Contacts Open 54 VSD Harmonic Filter - DC Current Transformer 1 106 MVVSD - Precharge - DC Bus Voltage Imbalance - AL
3 Oil - Low Temperature Differential 55 VSD Harmonic Filter - DC Current Transformer 2 107 MVVSD - Precharge - DC Bus Voltage Imbalance - BU
4 Oil - Low Temperature 56 LCSSS Initialization Failed 108 MVVSD - Precharge - DC Bus Voltage Imbalance - BL
5 Control Panel - Power Failure 57 reserved 109 MVVSD - Precharge - DC Bus Voltage Imbalance - CU
6 Leaving Chilled Liquid - Low Temperature 58 reserved 110 MVVSD - Precharge - DC Bus Voltage Imbalance - CL
7 Leaving Chilled Liquid - Flow Switch Open 59 reserved 111 MVVSD - High DC Bus Voltage - AU
8 Condenser - Flow Switch Open 60 reserved 112 MVVSD - High DC Bus Voltage - AL
9 Motor Controller - Contacts Open 61 reserved 113 MVVSD - High DC Bus Voltage - BU
10 Motor Controller - Loss Of Current 62 reserved 114 MVVSD - High DC Bus Voltage - BL
11 Power Fault 63 reserved 115 MVVSD - High DC Bus Voltage - CU
12 Control Panel - Schedule 64 reserved 116 MVVSD - High DC Bus Voltage - CL
13 Starter - Low Supply Line Voltage 65 reserved 117 MVVSD - Gate Driver - ANU
14 Starter - High Supply Line Voltage 66 reserved 118 MVVSD - Gate Driver - ANL
15 Proximity Probe - Low Supply Voltage 67 reserved 119 MVVSD - Gate Driver - AMU
16 Oil - Variable Speed Pump - Drive Contacts Open 68 reserved 120 MVVSD- Gate Driver - AML
17 VSD / MVVSD - Initialization Failed 69 reserved 121 MVVSD - Gate Driver - BNU
18 VSD / MVVSD Shutdown - Requesting Fault Data... 70 reserved 122 MVVSD - Gate Driver - BNL
19 VSD - High Phase A Instantaneous Current 71 reserved 123 MVVSD- Gate Driver - BMU
20 VSD - High Phase B Instantaneous Current 72 reserved 124 MVVSD - Gate Driver - BML
21 VSD - High Phase C Instantaneous Current 73 VSD - Serial Communications 125 MVVSD - Gate Driver - CNU
22 VSD - Phase A Gate Driver 74 reserved 126 MVVSD - Gate Driver - CNL
23 VSD - Phase B Gate Driver 75 reserved 127 MVVSD - Gate Driver - CMU
24 VSD - Phase C Gate Driver 76 VSD - Low Inverter Baseplate Temperature 128 MVVSD - Gate Driver - CML
25 VSD / MVVSD - Single Phase Input Power 77 Motor - High Winding Temperature 129 MVVSD - Input Power Supply
26 VSD - High DC Bus Voltage 78 VSD - Low Phase A Inverter Baseplate Temperature
27 VSD - Logic Board Power Supply 79 VSD - Low Phase B Inverter Baseplate Temperature
28 VSD - Low DC Bus Voltage 80 VSD - Low Phase C Inverter Baseplate Temperature
29 VSD - DC Bus Voltage Imbalance 81 reserved
30 VSD - High Internal Ambient Temperature 82 MVVSD - Serial Communications
31 VSD - Invalid Current Scale Selection 83 MVVSD - Input Power Transformer
32 VSD - Low Phase A Inverter Heatsink Temperature 84 MVVSD - Input Over-Voltage
33 VSD - Low Phase B Inverter Heatsink Temperature 85 MVVSD - Loss Of Cooling Fan
34 VSD - Low Phase C Inverter Heatsink Temperature 86 MVVSD - High Instantaneous Current
35 VSD - Low Converter Heatsink Temperature 87 reserved
36 VSD - Precharge - DC Bus Voltage Imbalance 88 reserved
37 VSD / MVVSD- Precharge - Low DC Bus Voltage 89 reserved
38 VSD - Logic Board Processor 90 reserved
39 VSD / MVVSD - Run Signal 91 reserved
40 VSD - Serial Communications 92 reserved
41 VSD / MVVSD - Stop Contacts Open 93 reserved
42 VSD Harmonic Filter - Logic Board Or Communications 94 reserved
43 VSD Harmonic Filter - High DC Bus Voltage 95 reserved
44 VSD Harmonic Filter - High Phase A Current 96 reserved
45 VSD Harmonic Filter - High Phase B Current 97 reserved
46 VSD Harmonic Filter - High Phase C Current 98 VSD - Serial Communications Vyper
47 VSD Harmonic Filter - Phase Locked Loop 99 MVVSD DC Bus Voltage Imbalance _ BU
48 VSD Harmonic Filter - Precharge - Low DC Bus Voltage 100 VSD - Serial Communications Raptyr
49 VSD Harmonic Filter - Low DC Bus Voltage 101 MVVSD DC Bus Voltage Imbalance _ BU
50 VSD Harmonic Filter - DC Bus Voltage Imbalance 102 MVVSD DC Bus Voltage Imbalance _ BL
51 VSD Harmonic Filter - Input Current Overload 103 MVVSD DC Bus Voltage Imbalance _ BU

Revision: YK Optiview (Rev K_03) Tab: with VSD Property of Johnson Controls, Inc. Page: 22 of 24
9/24/2010

YK Status Codes
ENG YK Warning Fault
PAGE SC.4
P59 WARNING.FLT
0 No Warnings Present
1 Real-Time Clock Failure
2 Setpoint Override
3 Condenser Or Evaporator Transducer Error
4 Evaporator - Low Pressure Limit
5 Condenser - High Pressure Limit
6 Condenser Transducer Error
7 Freeze Threat From Operating Chiller
8 Refrigerant Level Out Of Range
9 Standby Lube - Low Oil Pressure
10 Purge - High Pressure
11 Purge - Float Switch Error
12 Purge - Excess Purge
13 Oil - High Temperature
14 Oil - Low Pressure Limit
15 Vanes Uncalibrated
16 Vanes Uncalibrated - Fixed Speed
17 Harmonic Filter - Operation Inhibited
18 Harmonic Filter - Data Loss
19 Harmonic Filter - Input Frequency Range
20 Oil - Dirty Filter
21 Discharge - High Pressure Limit
22 Vanes Uncalibrated
23 Low Discharge Superheat Limit
24 Low Discharge Superheat Detected
25 Seal Lubrication In Process
26 External I/O - Serial Communications
27 Slide Valve Uncalibrated
28 Freeze Threat - Condenser Flow Switch
29 Surge Protection - Excess Surge Limit
30 Excess Surge Detected
31 Purge - Canister #1 Full
32 Oil Recovery Limit
33 KW Meter Not Calibrated
34 Condenser Or Vgd Sensor Failure
35 Conditions Override Vgd
36 Motor Bearing Lube Suggested
37 Motor Bearing Lube Required
38 Motor Bearing Lube Not Done
39 Harmonic Filter - Data Loss
40 Motor – High Winding Temperature (By custom SQ only)
41 Motor – High Bearing Temperature (By custom SQ only)
42 Motor – High Bearing Vibration (By custom SQ only)
43 Motor – Bearing Vibration Baseline Not Set (By custom SQ only)
44 Condenser- High Refrigerant Level (By custom SQ only)
45 Condenser- Low Refrigerant Level (By custom SQ only)
46 Condenser- Unstable Refrigerant Level (By custom SQ only)

Revision: YK Optiview (Rev K_03) Tab: with VSD Property of Johnson Controls, Inc. Page: 23 of 24
9/24/2010

This Page Intentionally Left Blank

Revision: YK Optiview (Rev K_03) Tab: with VSD Property of Johnson Controls, Inc. Page: 24 of 24