Bureau YeritastInciia) Prt Ltd.

(Construction Services Laboratory)


F-2/11, Road no: 9, IDA Nacharam. Ilyderabad
-500 076

To: The Deputy Executive Engineer, (P.R) Sub


- Division. Ichoda, Adilabad Telangana.

Work*: (PR) Department


- Package No. TS01 ICIIIBLB04-Construction of LSB at Km 1/830 on Road from MRL02
-NH44 Echoda to NH44 Raghuguda
BUREAU via Girjam & Mukra in Adilabad District.
VERITAS

TABLE 8A

SUGGESTED MIX (BY WEIGHT) FOR CONCRETE


Free
Water Compressive strength
Aggregate Cement Suggested Mix Slump
Cement used* Mix Max. size Content Cement Proportions Obtained (N/sq.mm)
Desi onation
t>
(mm) (Kg/cu.m)4 ratio C:FA:CA** (mm)
(max) 7 days 28 days
M20 40 341 0.48 1 : 2.15 : 3.68 50 19.5 28.7
Birla Gold, M25 20 403 0.41 1 : 1.76 : 3.02 45 24.3 34.8
OPC, 53 Grade M30 20 406 0.40 1 : 1.76 : 3.01 50 29.5 41.7
M40 20 430 0.38 1 : 1.60 : 2.85 40 39.5 50.6

This has to be verified at site. ** Cement: Fine Aggregate (100% NRS): Coarse Aggregate
Minimum and Maximum Cement Content as Specified by the Customer.
REMARKS: (1) Coarse aggregate shall satisfy the grading requirements as per IS: 383 -2016.
(2)Correction for water absorption of sand and coarse aggregate to be applied at site.
(3)Coarse aggregate of 20mm & 10mm shall be used in the ratio of 50:50 respectively
(4)The mix proportions recommended above should be tried in the field using the proposed materials and finalized by
observing the actual performance of the concrete mix. Suitable modifications may be necessary to suit field conditions
in the light of experience as well as for the particular materials used at the site in each case.
Note : 1. The results relate only to the items tested.
2. Report shall not be reproduced, except in full, without the written approval of the laboratory.
3. Any correction invalidates this report.

CH. SANTHOSH KUMAR


OucditvManager-