Professional Documents
Culture Documents
Countries' I&N Elaborated By: Global Standard
Countries' I&N Elaborated By: Global Standard
Countries' I&N Elaborated By: Global Standard
GSH001
HV CIRCUIT-BREAKERS Rev. 02
03/08/2017
HV CIRCUIT-BREAKERS
This document is intellectual property of Enel SpA; reproduction or distribution of its contents in any way or by any means whatsoever
w is
subject to the prior approval of the above mentioned company which will safeguard its rights under the civil and penal codes.
GSH001
HV CIRCUIT-BREAKERS Rev. 02
03/08/2017
INDEX
GSH001
HV CIRCUIT-BREAKERS Rev. 02
03/08/2017
GSH001
HV CIRCUIT-BREAKERS Rev. 02
03/08/2017
ANNEX A………………………………………………………………………………………………………
A…………………………………………………………………………………………………………… ......... ….29
ANNEX B……………………………………………………
…………………………………………………………………………………………………………
……………………………………………………… ......... ….30
ANNEX C……………………………………………………
…………………………………………………………………………………………………………
……………………………………………………… .......... ….34
ANNEX D……………………………………………………
…………………………………………………………………………………………………………
……………………………………………………… ......... ….56
GSH001
HV CIRCUIT-BREAKERS Rev. 02
03/08/2017
1 SCOPE
Scope of this document is to provide technical requirements for the supply of three-poles Alternating
Current Circuit-Breakers with rated voltage from 72,5 kV to 245 kV to be used in Primary Substations of
the Enel Group Distribution companies, listed below:
• Ampla (Brazil)
• Chilectra (Chile)
• Codensa (Colombia)
• Coelce (Brazil)
• Edelnor (Perú)
• Edesur (Argentine)
• Endesa Distribución Eléctrica (Spain)
• Enel Distributie Banat (Romania)
• Enel Distributie Dobrogea (Romania)
• Enel Distributie Muntenia (Romania)
• Enel Distribuzione (Italy)
Note: the indication "Latam" refers to the Enel Group Distribution companies in South America.
Alternating Current Circuit-Breaker
Breakers (hereinafter CBs) are SF6 insulated (in alternative, non-fluorinated
non
greenhouse gases and vacuum circuit breakers are also acceptable), for outdoor installations
installation in Primary
Substations.
Some requirements are applicable only to one or more companies, therefore, depending on the
destination of the CBs,, the supplied equipment shall comply these
se specific requirements.
2 COMPONENTS LIST
The following CBs are covered by this global standard:
GSH001
HV CIRCUIT-BREAKERS Rev. 02
03/08/2017
3.1 Laws
3.1.1 Latam
3.1.1.1 Brasil
NR-10 - segurança em instalações e serviços em eletricidade
3.1.2 Italy
D.M. 1/12/1980 and subsequent modification D.M. 10/9/1981 “Disciplina dei contenitori a pressione di
gas con membrature miste di materiale isolante e di materiale metallico, contenenti parti attive di
apparecchiature elettriche”.
elettriche”
3.1.3 Spain
Real Decreto Riesgo Eléctrico 614/2001
Reglamento Electrotécnico para Baja Tensión,
Tensión Real Decreto 842/2002.
Reglamento de puntos de Medida Real Decreto 1110/2007.
Reglamento sobre condiciones técnicas y garantías
garantías de seguridad en instalaciones eléctricas de alta
tensión, Real Decreto 337/2014.
GSH001
HV CIRCUIT-BREAKERS Rev. 02
03/08/2017
3.2 Standards
3.2.1 Common standards
The below listed reference documents shall be intended in the in-force
force edition at the contract date
(amendments included).
For Latin America destinations the reference standard are the IEC/ISO, whilst for Europe destinations
the reference standard are the correspondent European standards (EN).
IEC 62271-1 High
High-voltage switchgear and controlgear - Part 1: Common specifications
IEC 62271-100 High-voltage switchgear and controlgear – Part 100: Alternating current
High
circuit
circuit-breakers
IEC/TR 62271-300 High
High-voltage switchgear and controlgear - Part 300:
300 Seismic qualification of
alternating current circuit-breakers
a
IEC/TR 62271-301 High-voltage switchgear and controlgear
High – Part 301: Dimensional
standardiz
standardization of high-voltage terminals
CLC/TR 62271-303 High-voltage switchgear and controlgear - Part 303: Use and handling of
High
sulphur hexafluoride (SF6)
IEC 60376 Specification of technical grade sulfur hexafluoride (SF6) for use
us in electrical
equipment
IEC 60073 Basic and safety principles for man-machine
man machine interface, marking and
identification – Coding principles for indicators and actuators
IEC 60447 Basic and safety principles for man-machine
man machine interface, marking and
identification - Actuating principles
IEC 61936-1 Power installations exceeding 1 kV a.c. - Part 1: Common rules
IEC/TS 60815-1 Selection and dimensioning of high-voltage
high voltage insulators intended for use in
polluted conditions – Part 1: Definitions, information and general principles
IEC/TS 60815-2 Selection and dimensioning of high-voltage
high voltage insulators intended for use in
polluted conditions – Part 2: Ceramic and glass insulators for a.c. systems
IEC/TS 60815-3 Selection and dimensioning of high-voltage
high insulators intended for use in
polluted conditions – Part 3: Polymer insulators for a.c. systems
IEC 62155 Hollow pressurized and unpressurized ceramic and glass insulators for use in
H
electrical equipment with rated
rated voltage greater than 1000 V
IEC 61462 Composite hollow insulators – Pressurized and unpressurized insulators for
use in electrical equipment with rated voltage greater than 1000 V –
Definitions, test methods, acceptance criteria and design recommendations
IEC 60332-3-24 Tests on electric and optical
optical fibre cables under fire conditions – Part 3-24:
Test for vertical flame spread of vertically-mounted
vertically mounted bunched wires or cables -
Category C
IEC 60947-7-1 Low-voltage switchgear and controlgear – Part 7-1:
Low 7 Ancillary equipment -
Terminal blocks for copper
copp conductors
IEC 60947-7-2 Low-voltage switchgear and controlgear – Part 7-2:
Low 7 Ancillary equipment -
Protective conductor terminal blocks for copper conductors
IEC 60068-2-17 Environmental testing – Part 2: Tests – Test Q: Sealing
ISO 1461 Hot dip galvanized coatings on fabricated iron and steel articles-
articles
Specifications and test methods
GSH001
HV CIRCUIT-BREAKERS Rev. 02
03/08/2017
4 SERVICE CONDITIONS
GSH001
HV CIRCUIT-BREAKERS Rev. 02
03/08/2017
Chilectra ETGI-1020
1020
Codensa AF3 (IEC/TR
IEC/TR 62271-300)
62271
Edelnor AF5 (IEC/TR
IEC/TR 62271-300)
62271
Enel Distributie AF5 (IEC/TR
IEC/TR 62271-300)
62271
Enel Distribuzione AF5 (IEC/TR
IEC/TR 62271-300)
62271
5 TECHNICAL CHARACTERISTICS
CHARACTERI
In addition to IEC 62271-100
100, the following requirements are prescribed.
1
In accordance with Prescriptia Energetica PE 101/85
2
This requirement can be verified by mean of type tests performed with O - 0,3 s - CO -3 min – CO operating sequence
and a declaration of the manufacturer about the CB compliance with O - 0,3 s - CO - 1 min – CO operating sequence.
GSH001
HV CIRCUIT-BREAKERS Rev. 02
03/08/2017
6 CONSTRUCTION CHARACTERISTIC
CHARACT
3
Applicable also to the Control Box and to the Operating Device Box(es).
GSH001
HV CIRCUIT-BREAKERS Rev. 02
03/08/2017
If interface plates and other accessories are necessary to o adapt the support to the civil works, they
shall be included in the supply of the support and shall be preliminary approved by Enel Group
Distribution companies.
The poles naming shall be A, B, C, from left to right, looking
looking the CB from the side with the main contact
position indicators.
The normal use, control and maintenance operations shall be performed with total workers safety.
6.2 Insulators
The insulators could be requested by Enel Group Distribution companies in ceramic or composite
materials.
In case of ceramic insulators,
insulators they shall be in brown color and compliant with IEC 62155.
In case of composite insulators,
insulators they shall be in light grey color and compliant with IEC 61462. The
envelope shall be made of silicone rubber, HTV type (High Temperature Vulcanized) or LSR type
(Liquid Silicone Rubber) and completely free of EPDM or other organic rubbers.
rubbers
Each SF6 circuit shall provide a connection elements (type DILO VK/BG-03/8
VK/BG or equivalent), with a
non-return valve, both for SF6 control device and for gas filling/replenishment, provided by not-
not
losable protection screw taps (located not higher than 1.800 mm from the ground level).
level)
GSH001
HV CIRCUIT-BREAKERS Rev. 02
03/08/2017
The SF6 circuit piping shall be performed using stainless steel or, in alternative, painted copper, in
order to reduce the stealing risk.
6.4.2 Additional requirements for non-fluorinated greenhouse gases CBs
In alternative to the SF6,, non-fluorinated
non fluorinated greenhouse gases are also acceptable.
In case of single-poles
poles CB’s a distinct gas circuit and connection for each pole is required.
In case of three-pole
pole CB’s the number of gas circuits and consequent connections is the same of SF6
gas CBs (see table in 6.4.1).
6.4.1
Each gas circuit shall provide a connection elements (the the manufacturer will propose a suitable type
different from the one used for SF6, in order to avoid mistakes),
mistakes , with a non-return
non valve, both for gas
control device and for gas filling/replenishment, provided by not-losable
not losable protection screw taps
(located not higher than 1.800 mm from the ground level).
6.4.3 Gas (SF6 or non-fluorinated
fluorinated greenhouse gases) density control
The CB is a closed pressure system.
system The relative leakage rate shall all be Frel ≤ 0,5% per year. The
value for the time between replenishments shall be at least 10 years.
It shall be possible to perform the gas replenishment with the equipment in service, avoiding the
unwanted operation of the gas density control device.
Each gas circuit (1 or 3, see 6.4.1 or 6.4.2) shall have a device for the gas density control.
The alarm threshold calibration has to take into account the leakage rate. The block threshold
calibration shall be at least 0,02 MPa lower respect to the alarm threshold.
The gas density control device shall be:
• suitable to work in the provided temperature range;
• located in order to avoid the solar radiation influence on the external temperature measuring;
• insensitive to the vibration produced by the equipments operation;
• manufactured with stainless materials;
• realized in order to allow the functionality verify and the substitution with the poles
pol under
pressure;
• with the following scale(s) for a visible indication of gas density level:
Endesa Distribución Eléctrica,
Type of scale Enel Distributie and Enel Latam
Distribuzione
Colored Mandatory Mandatory
Graduated Forbidden Mandatory
The gas density control device shall provide 2 operating levels with contacts independently
adjustable:
•
st
1 minimum gas density level: alarm (replenishment necessary) with
with 1 contacts;
•
nd
2 minimum gas density level: block (to get out of service) with 2 contacts working separately
on 2 opening circuits (depending on specific requirements in chapter 7).
The contacts operating tolerance shall be lower than ± 1,5% (referring to the full scale) in the
provided temperature range; the contacts of each minimum gas density level shall have a difference
≤ 0,005 MPa between them.
6.4.4 Overpressure safety devices
Safety devices against the internal overpressure is mandatory only in case of ceramic insulators.
The devices shall be compliant with ISO 4126 and shall be properly calibrated over the maximum
operating pressure, in order to avoid improper operations.
GSH001
HV CIRCUIT-BREAKERS Rev. 02
03/08/2017
In case of overpressure safety valves operation, the expelled gas shall not run over people around
the equipment.
6.4.5 Gas filling/replenishment device (Optional)
At request the manufacturer shall supply a device for the gas replenishment.
replenishment
In case of SF6, the device shall be provided by female thread connection, W 21,7 x 1/14”
1/1 (UNI 11144
– only for Enel Distribuzione,)
Distribuzione, on gas bottle side and DILO VK/BG-03/8
03/8 or equivalent on pole junction
device side. The device will consist of:
• pressure regulator
• a safety valve (ISO
ISO 4126 compliant,
compliant calibrated at 8 bar rel);
• a pressure gauge 0÷1 MPa, 0,5 class, minim resolution ± 5 kPa, accompanied with a calibration
certificate;
• flexible tube 5 meters long, DN≥8.
DN
In case of non-fluorinated
fluorinated greenhouse gases,
gases, the manufacturer will propose a suitable solution
compliant, when applicable, with the above mentioned requirements for the SF6 version.
GSH001
HV CIRCUIT-BREAKERS Rev. 02
03/08/2017
2
The box internal wiring shall be performed with conductors with adequate section (always
( ≥ 1mm ),
flexible type, compliant
mpliant with IEC 60332-3-24
60332 and insulated at Uo/U = 450/750 V.
V
The cable ends shall be provided of pre-insulated
insulated compression type terminals, suitable for the clamps
where they have to be connected.
The connection cable from the Control Box to the equipments
equipments shall be of adequate section (≥ 1,5
2
mm ), shielded, flexible, compliant with IEC 60332-3-24
60332 and insulated at Uo/U = 0,6/1 kV.
kV
2
Inside the Control Box an internal collector (in tin-plated
tin plated copper, section ≥ 60 mm
or nickel-plated
and with M5 regular interval threaded hole) shall be present for the grounding connection of all cable
shields; the manufacturer shall guarantee its effective connection to the CB grounding system.
The entrance of all cabless (both CB’s cables and control system cables) shall be from the Control Box
bottom side, where a removable loophole (in aluminum, with useful dimension of 150x100
150 mm) shall
be provided.
The Control Box shall include:
• remote/local selector switch
• control buttons for circuit breaker,
breaker with the following colors:
Chilectra, Codensa, Edelnor, Edesur,
Endesa Distribución Eléctrica, Enel Ampla, Coelce
Operation Distributie and Enel Distribuzione (according with NR10)
(according with IEC 60073)
Closing White White "L" on Red white background
Opening Black White "D" on Green white background
• magneto-thermic automatic circuit breakers for the supplies protection (motors, lighting lamp,
anti-condensation
condensation circuits – fuses are not admitted);
• interface terminal board for substation control system;
• anti-condensation circuit;
• internal lighting lamp, with automatic switching in case of open door;
door;
• only in case of three gas circuits, gas density signalization lamps (for each gas circuit, yellow
st nd
color about 1 minimum gas density level; red color about 2 minimum gas density level);
level
• only in case of three gas circuits, lamps testing button.
The signalization lamps and the internal lighting lamps shall not be incandescent type.
The grounding of a dc supply polarity is not admitted.
The terminal boards shall
shal be made with modular terminals. In particular, the terminals of control
system interface terminal board shall have section 4 mm² for control, signalization and anti- a
condensation circuits and section 10 mm² for the motors supply circuit.
It shall be provided
ded 2 bridged terminals couples for the anti-condensation
anti condensation circuit and 2 for the motor
supply circuit.
If diodes are used for the circuit separations or for the voltage return protection, they shall have
inverse voltage ≥ 3 kV.
The cable trucking systems for the internal wiring shall shave sufficient residual space (≥
( 10% of used
volume); the cables shall be anchored in some points on order to avoid their falling.
The cable trunks close to the interface terminal boards shall be used for the control system wiring and
cannot be used for the internal wiring.
6.5.1.1 Latam specific requirements
The remote/local selector switch shall have auxiliary contacts.
contacts
GSH001
HV CIRCUIT-BREAKERS Rev. 02
03/08/2017
The Control Box shall also include an electric socket output (Vac).
About the terminal boards, provision
p should be made for 20% of free terminals.
terminals
The control box shall also include auxiliary switch contacts to indicate CB position. The quantities
of auxiliary contacts available (NO-Normally
( Open or NC-Normally
Normally Closed)
Closed for the different
companies is indicated in Annex C.3.
C
6.5.1.2 Enel Distribuzione specific requirements
In alternative to IEC 60332-3-24,
60332 cables compliant with Italian standard CEI 20-22/2
20 and marked
with “CEI 20-22 II” can be accepted.
It’s necessary a space in the control box with a DIN bar width 150mm, height 200mm, depth
150mm for a device DV7203 (conversion
(conver digital signal in optical)
6.5.1.3 Endesa specific requirements
For Endesa the remote/local selector switch and the control buttons for opening and closing are
not required in the CB. Please check Annex C.1
During normal operation, with encloses and doors closed, the main contact position indicators and
the spring loading condition signalization shall be visible from ground level.
level
In order to allow the verification,
verification, during maintenance activity, of the unchanged characteristics of the
no-load
load travel curve (see note in 9.2.2-11b), manufacturer shall provide the measuring points,
properly machined.
In addition to the IP requirement of table at chapter 5, the box(es) protection degree with open doors
or when using hand-crank
crank (to charge CB’s springs) shall be minimum IP2X (unless the box can be
opened only using tools).
All mechanical organs (included the motion transmission rods for three-pole pole CBs) shall be enclosed
in metallic casings, IP2X,, in order to prevent the access to parts in movement (see par. 5.13.1 of IEC
62271-1).
The manufacturer shall provided the instruction for a safety access to mechanical organs.
6.5.2.1 Latam specific requirements
The operation counter can be mechanical or electromechanical.
6.5.3 Nameplates
Par. 5.10 of IEC 62271-100
62271 apply,, specifying that both CB nameplate and operating devices
nameplates shall include:
GSH001
HV CIRCUIT-BREAKERS Rev. 02
03/08/2017
6.6 HV terminals
6.6.1 Latam
The HV terminalss shall be manufactured with corrosion resistant copper or aluminum alloy, in order to
be interfaced with aluminum alloy connectors or clamps.
The terminals shall be rectangular shape with the following dimensions, according to fig. 3 (2x2 hole
pattern) or fig. 4 (2x3 hole pattern) of IEC/TR 62271-301:
• Hole diameters Ø 14.3mm
14
• Distance between holes 44.5mm
6.6.2 Endesa Distribución
The HV terminals shall be compliant with fig. 6 (2x4 hole pattern) of IEC/TR 62271-301.
62271
6.6.3 Enel Distributie and Enel Distribuzione
Distribu
The HV terminals shall be realized with corrosion resistant copper or aluminum alloy, in order to be
interfaced with aluminum alloy clamps.
For CBs up to 170 kV the HV terminals shall have Ø 40 ±0,25 X 80 min (mm) (fig. 1 of IEC/TR 62271-
301) dimensions.
For 245 kV CBs the HV terminals
terminals shall be suitable to be interfaced with standardized Enel clamps LM
1023 (double cable) and LM 1026 (single
(singl cable).
6.7 Grounding
The manufacturer shall ensure the equi-potentiality
equi potentiality between all parts forming the equipment.
At the base of each support upright two grounding points shall be provided, provided equipped with M12
stainless steel bolts (included in the supply).
supply)
If interface plates are necessary toto adapt the support to the civil works, they shall be designed taking
into account the position of the external grounding connections (see Annex B).
6.8 Anti-condensation
condensation circuit
Inside all boxes a proper anti-condensation
a system shall be provided in order to prevent humidity
damages and to ensure a proper air replacement.
GSH001
HV CIRCUIT-BREAKERS Rev. 02
03/08/2017
The anti-condensation
condensation circuit, controlled
controlled by a thermostat with fixed regulation at 25 °C (box internal
temperature), shall be unique for the overall equipment, supplied in a.c. (see table in chapter 5 for the
supply rated voltage) and protected with a magneto-thermic
magneto thermic automatic circuit breaker.
The heating elements shall be preferably connected in series in order to have the circuit opening in
case of failure of an element; a minimum current sensor shall detect and signal the anomaly.
In parallel connection case,
ase, the manufacturer
m shall assure a correct fault detection and distance
anomaly signaling in case of failure of an element, properly evaluating the tolerances of the supply
voltage and of the components resistance.
7 FUNCTIONAL CHARACTERISTIC
4
the words “remote” and “local” have to be translated in all documents as:
• Italian language: “Servizio” (S) and “Prova” (P)
• Spanish language: “Remoto” and “Local”
• Romanian language: “In functiune”
functi and “Probe”
• Portuguese language: “Remoto”
Remoto” and “Local”
GSH001
HV CIRCUIT-BREAKERS Rev. 02
03/08/2017
The selector is located in a centralized control box, for this reason it’s not necessary the local-
local
manual-remote
remote selector in the control box. For the same reason the open-close
open buttons are not
necessary. See Annex C.1.
5
with the CB closed the opening springs shall be always charged.
charged
GSH001
HV CIRCUIT-BREAKERS Rev. 02
03/08/2017
GSH001
HV CIRCUIT-BREAKERS Rev. 02
03/08/2017
Under-voltage
voltage releases consisting of energy storage systems (for example capacitors) are not
admitted.
The CB closing consensus shall be interdict in case of under-voltage voltage release drive circuit not
supplied or locked (only if “43LT” selector is in “T” position, see flowcharts in annex C.2).
7.1.3 Interlocking devices
7.1.3.1 General requirements
All operations shall be dependent to the internal CB interlockings.
The following interlocking circuits shall be provided,, depending on the monitored values (springs
status, gas pressure etc.):
• reclosing
• closing
• opening or, if required,
required automatic opening with open position blocking.
blocking
Further details are in the specific requirements.
7.1.3.2 Latam specific requirements
For the interlocking requirements refer to the annex C.3.
C
7.1.3.3 Endesa Distribución specific requirements
For the interlocking requirements refer to the annex C.1.
C
7.1.3.4 Enel Distributie and Enel Distribuzione specific requirements
For the interlocking devices and for the automatic opening with open position blocking, blocking IEC
62271-100 applies with the clarifications in the following.
The following interlockings are requested:
a) Closing block (enabled in both positions
positions of the remote/local selector switch)
switch
b) Opening block (enabled in both positions of the remote/local selector switch) switch or in
alternative automatic opening with open position blocking (enabled only in remote position
of the remote/local selector switch)
switch
The refresh shall occur automatically only after the ending of the condition causing the block.
Both during normal CB working and during operations shall not be sent to the control system
temporary block signalizations.
7.1.3.4.a) Closing block
The closing block shall be activated if one of the following conditions occur:
occur
nd
a) 2 minimum gas density level (only in case of gas CBs);
b) discharghed closing springs (at least one of the three springs in case of single-polesingle
CBs).
In case of three-pole
pole CBs or single-pole
pole CBs with L/T selector switch in “T” position, the closing
block shall be activated also in the following conditions:
conditions
a) drive circuit of under-voltage
under release not supplied;
b) under-voltage
voltage release mechanically locked (at least one of the three releases in case of
single-pole
pole CBs).
CBs)
In case of single-pole
pole CBs with L/T selector switch in “L”
“ ” position, the closing block shall be
activated also in the following conditions:
a) at least st one of the three under-voltage
under releases mechanically locked.
locked
7.1.3.4.b) Opening block
pole gas CBs with L/T selector switch in “L” position, the
In case of single-pole t opening block shall
nd
be activated in case of 2 minimum gas density level intervention.
GSH001
HV CIRCUIT-BREAKERS Rev. 02
03/08/2017
GSH001
HV CIRCUIT-BREAKERS Rev. 02
03/08/2017
b) unlocked under-voltage
under release for three-pole CBs;
c) locked under-voltage
under releases for single-pole CBs.
7.2.4.2 Controls
The CBs operating logics are represented in the t flowcharts in Annex C.2 (where
( applicable in
case of vacuum CBs)..
It shall be reported in the terminal board the contacts referred to the following controls:
a) single-pole
pole CBs
a.1) drive circuit of shunt closing release control (CH-ABC)
st
a.2) 1 drive circuit of shunt opening release control (1° AP-A; A; 1°AP-
1°AP B; 1°AP-C)
nd
a.3) 2 drive circuit of shunt opening release control (2° AP-ABC)
ABC)
rd
a.4) 3 drive circuit of under-voltage
under release control (3° AP-ABC)
ABC)
b) three-pole CBs
b.1) drive circuit of shunt closing release control (CH-ABC)
st
b.2) 1 drive circuit of shunt opening release control (1° AP-ABC)
ABC)
rd
b.3) 3 drive circuit of under-voltage
under release control (3° AP-ABC)
ABC)
7.2.4.3 Signalizations
It shall be reported in the terminal board the contacts referred to the following signalizations:
a) single-pole
pole CBs
a.1) remote/local selector switch in local (P) position (43SP-Prova)
Prova)
a.2) intervention of motor protection device and/or auxiliary supply missing (42RT)
a.3) anti-condensation
condensation circuit anomaly (AnR152)
a.4) motor maximum operation time (BX)
a.5) discharged springs (P4 MOLLE)
st
a.6) 1 minimum gas density level (P1 GAS)
nd
a.7) 2 minimum
nimum gas density level (P4 GAS)
a.8) open position (caX152)
a.9) close position (ccX152)
a.10) poles discrepancy (DP)
a.11) incongruence of drive circuit of under-voltage
under voltage release control (3°AP-INC)
a.12) locking
ocking of drive circuit of under-voltage
under release control (BL3°AP-ABC)
(BL3°AP
a.13) open position (n° 3 152 NC)
a.14) close position (n° 3 152 NA)
b) three-pole CBs
b.1) remote/local selector switch in local (P) position (43SP-Prova)
Prova)
b.2) intervention of motor protection device and/or auxiliary supply missing (42RT)
b.3) anti-condensation
condensation circuit anomaly (AnR152)
b.4) motor maximum operation time (BX)
b.5) discharged springs (P4 MOLLE)
st
b.6) 1 minimum gas density level (P1 GAS)
nd
b.7) 2 minimum gas density level (P4 GAS)
b.8) open position (caX152)
b.9) close position (ccX152)
b.10) locking
ocking of drive circuit of under-voltage
under release control (BL3°AP-ABC)
(BL3°AP
GSH001
HV CIRCUIT-BREAKERS Rev. 02
03/08/2017
8 TESTING
GSH001
HV CIRCUIT-BREAKERS Rev. 02
03/08/2017
GSH001
HV CIRCUIT-BREAKERS Rev. 02
03/08/2017
GSH001
HV CIRCUIT-BREAKERS Rev. 02
03/08/2017
Functional tests (par. 7.2.2 of IEC 62271-1) shall be done only at rated voltage. About density meters,
the verification shall be performed at ambient temperature, in the real operating position, using
nitrogen and no SF6, with decreasing pressure values. The density meters verification can be also
performed using SF6, if precautions are taken to prevent SF6 dispersion in the environment.
Dielectric tests (par. 7.2.4 of IEC 62271-1) shall be done applying 1 kV for 1 s.
Electronic devices, motors etc. can be excluded by dielectric test only if agreed during the conformity
assessment (homologation
homologation, certification etc.) process.
8.3.3 Measurement of the resistance of the main circuit
(IEC 62271-100 par. 7.3)
It shall be performed after mechanical operating tests.
tests
The ambient temperature influence can be neglected.
neglected
The test can be performed without HV terminals, specifying it in the test report.
8.3.4 Tightness test
(IEC 62271-100 par. 7.4)
nd
It shall be performed at least at 2 minimum gas density level (block).
8.3.5 Design and visual checks
(IEC 62271-100 par. 7.5)
The checks shall be performed referring to conformity assessment (homologation
homologation, certification etc.)
documents and verifying damage absence.
8.3.6 Mechanical operating tests
(IEC 62271-100 par. 7.101 101)
It shall be recorded:
a. at Vmax, Vn, Vmin, closing (C) and opening (O) times, time spread (on each release);
a1. at Vmax, Vn, Vmin,
Vmin opening (O) times, time spread of under-voltagevoltage release(if
release present –
see 8.2.11)) and it shall be verified its compliance with IEC 62271-1
62271 par. 5.8.4;
b. at Vn, close-open
open (CO) time and open-close-open
open (O – t - CO) cycle;
c. att Vn, the operation time of one of each type (make and break) of auxiliary contacts,
contacts respect to
the operation of main contacts on closing and on opening of CB;
d. no-load
load travel curves.
The spring recharging time of the motor after a closing operation and its absorption (maximum value,
inrush excluded) shall be measured only at Vn. Vn
8.3.7 Protective treatments
The thickness of the protective coatings shall be verified according with 8.2.20.
8.2.20
8.3.8 Specific routine tests
8.3.8.1 Enel Distribuzione
8.3.8.1.a) Tests to verify the encloses
enclose endurance to gas internal pressure
Only in case of gas CBs.
Manufacturer shall provide the “Certificazione di rispondenza” (see D.M. 1/12/1980).
1/12/1980)
GSH001
HV CIRCUIT-BREAKERS Rev. 02
03/08/2017
GSH001
HV CIRCUIT-BREAKERS Rev. 02
03/08/2017
9 SUPPLY REQUIREMENTS
GSH001
HV CIRCUIT-BREAKERS Rev. 02
03/08/2017
GSH001
HV CIRCUIT-BREAKERS Rev. 02
03/08/2017
GSH001/2 6792645
GSH001/6
GSH001/7 150186
GSH001/8 150187
GSH001/9 150196
GSH001/11 0103-0303
GSH001/12
GSH001
HV CIRCUIT-BREAKERS Rev. 02
03/08/2017
Figure 1
GSH001
HV CIRCUIT-BREAKERS Rev. 02
03/08/2017
Figure 2
GSH001
HV CIRCUIT-BREAKERS Rev. 02
03/08/2017
Ref.
Company A B C D E F G H I
figure
6
Ampla 2 - ≥ 3100 ≥ 790 ≤ 4300 - ≥2250 ≥1700 - -
6
Coelce 2 - ≥ 3100 ≥ 790 ≤ 4300 - ≥2250 ≥1700 - -
6
Edelnor ≥2250
7 7
Endesa 2 - ≥ 3130 ≥630 - - ≥2300 - ≥1400
Ref.
Company A B C D E F G H I
figure
6
Ampla 2 - ≥3600 ≥1630 ≤5200 - ≥2250 ≥2530 -
6
Chilectra ≥ 3500 ≥ 1750 ≤ 7000 400 ≥2250
370 x 6
Codensa 2 ≥ 5180 ≥ 3630 ≥ 1750 ≥ 5480 ≥2250 2530
230
6
Edesur ≥3700 ≥2250
7
7 ≥2000
Endesa 2 - ≥ 3800 ≥1300 - - ≥2300 -
Enel 4500 6
1 ≤6500 2000 ≤6500 500 ≥2250 ≥2000
Distributie ±30
Enel 4500 6
1 ≤6500 2200 ≤6500 500 ≥2250 ≥2000
Distribuz. ±30
6
In accordance with par. 7.2.4 of IEC 61936-1
61936
7
In accordance with Real Decreto Riesgo Eléctrico 614/2001 and NNM001.- Normas de operación definiciones. This
distance is mandatory unless there is a physical barrier allowing distance I to be shorter.
8
Blank cell means that there isn’t a mandatory requirement for that characteristic
GSH001
HV CIRCUIT-BREAKERS Rev. 02
03/08/2017
Ref.
Company A B C D E F G H I
figure
Enel 4500 ≥2250
6
1 ≤6500 2200 ≤6500 500 ≥2000
Distribuz. ±30
Ref.
Company A B C D E F G H I
figure
6
Chilectra 1 ≥4600 ≥3500 ≤8500 400 ≥2250
6
Codensa ≥2250
6
Edelnor ≥2250
6
Edesur ≥4600 ≥2250
GSH001
HV CIRCUIT-BREAKERS Rev. 02
03/08/2017
GSH001
HV CIRCUIT-BREAKERS Rev. 02
03/08/2017
C.2 – ENEL DISTRIBUTIE AND ENEL DISTRIBUZIONE ELECTRICAL SCHEMES AND FLOWCHARTS
GSH001
HV CIRCUIT-BREAKERS Rev. 02
03/08/2017
Figure 4 (72,5
72,5 ÷ 170 kV single-pole CBs electricall scheme)
GSH001
HV CIRCUIT-BREAKERS Rev. 02
03/08/2017
GSH001
HV CIRCUIT-BREAKERS Rev. 02
03/08/2017
THREE
THREE-POLE CIRCUIT BREAKERS FLOWCHARTS:
GSH001
HV CIRCUIT-BREAKERS Rev. 02
03/08/2017
GSH001
HV CIRCUIT-BREAKERS Rev. 02
03/08/2017
GSH001
HV CIRCUIT-BREAKERS Rev. 02
03/08/2017
GSH001
HV CIRCUIT-BREAKERS Rev. 02
03/08/2017
SINGLE
SINGLE-POLE CIRCUIT BREAKERS FLOWCHARTS:
GSH001
HV CIRCUIT-BREAKERS Rev. 02
03/08/2017
GSH001
HV CIRCUIT-BREAKERS Rev. 02
03/08/2017
GSH001
HV CIRCUIT-BREAKERS Rev. 02
03/08/2017
GSH001
HV CIRCUIT-BREAKERS Rev. 02
03/08/2017
GSH001
HV CIRCUIT-BREAKERS Rev. 02
03/08/2017
COELCE:
GSH001
HV CIRCUIT-BREAKERS Rev. 02
03/08/2017
GSH001
HV CIRCUIT-BREAKERS Rev. 02
03/08/2017
AMPLA
GSH001
HV CIRCUIT-BREAKERS Rev. 02
03/08/2017
GSH001
HV CIRCUIT-BREAKERS Rev. 02
03/08/2017
GSH001
HV CIRCUIT-BREAKERS Rev. 02
03/08/2017
CODENSA
GSH001
HV CIRCUIT-BREAKERS Rev. 02
03/08/2017
MOTOR CIERRE Y ANTIBOMBEO APERTURA 1 APERTURA 2 CONTACTOS AUXILIARES SEÑALES Y CONTROL SF6 CALEFACCION
HV CIRCUIT-BREAKERS
GLOBAL STANDARD
EDELNOR
INFORMACION DEL FABRICANTE INFORMACION DEL FABRICANTE
GSH001
Page 55 of 57
03/08/2017
Rev. 02
GLOBAL STANDARD Page 56 of 57
GSH001
HV CIRCUIT-BREAKERS Rev. 02
03/08/2017
CHILECTRA:
GSH001
HV CIRCUIT-BREAKERS Rev. 02
03/08/2017