Steel Stair Design Based on AISC 360-10/16

INPUT DATA & DESIGN SUMMARY


COLUMN SECTION (Tube or Pipe) => HSS4X4X1/4
Tube A rmin t h
3.37 1.52 0.23 4.00
FLOOR BEAM - 1 => W16X26
A d Ix Sx Zx
7.68 15.70 301.00 38.40 44.20
STRINGER - 1 (Channel or Tube) => MC8X8.5
Channel A d Ix Sx Zx
2.50 8.00 23.30 5.82 6.95
STRINGER - 2 (Channel or Tube) => C12X20.7
Channel A d Ix Sx Zx
6.08 12.00 129.00 21.50 25.60
LANDING BEAM - 1 (Channel or Tube) => C8X18.75
Channel A d Ix Sx Zx
5.51 8.00 43.90 11.00 13.90
LANDING BEAM - 2 (Channel or Tube) => C8X18.75
Channel A d Ix Sx Zx
5.51 8.00 43.90 11.00 13.90

DIMENSIONS H = 16 ft, story Ht


L1 = 12 ft
L2 = 6 ft
L3 = 10 ft

NUMBER OF STORIES n = 2

GRAVITY LOAD DL = 50 psf


LL = 100 psf

THE STAIR DESIGN IS ADEQUATE.

ANALYSIS

STRINGER - 1

q = 33.69 deg, from horizontal


w = 0.25 (DL / Cos q + LL) L3 = 400 plf , projected
R = 0.5 w L1 = 2.40 kips
M = w L12 / 8 = 7.20 ft-kips
Fy = 36.00 ksi
Mn / Wb = Fy Zx / 1.67 = 12.49 ft-kips
> M [Satisfactory]
E = 29000 ksi
DLL = 5 (wLL Cos q) (L1 / Cos q)4 / (384 E I) = 0.46 in
< (L1 / Cos q) / 240 = 0.72 in [Satisfactory]

STRINGER - 2

w = 400 plf , projected, from STRINGER - 1


P = 6.00 kips, from LANDING BEAM - 2
RL = [w L1 (0.5 L1 + L2) + P L2] / (L1 + L2) = 5.20 kips
RR = [w L1 (0.5 L1) + P L1] / (L1 + L2) = 5.60 kips
X = RL / w = 12.00 ft, from left
Mmax = RL X - (0.5 w X2 ) = 33.61 ft-kips
Fy = 36.00 ksi
Mn / Wb = Fy Zx / 1.67 = 45.99 ft-kips
> M [Satisfactory]
DLL = 5 wLL (L1 + L2)4 / (384 E I) + PLL (L1 +L2)3 / (48 E I) = 0.29
< (L1 + L2) / 240 = 0.90 in [Satisfactory]
(cont'd)
LANDING BEAM - 1

w = 0.5 (DL + LL) L2 = 450 plf


R = 0.5 w L3 = 2.25 kips
M = w L32 / 8 = 5.63 ft-kips
Fy = 36.00 ksi
Mn / Wb = Fy Zx / 1.67 = 24.97 ft-kips
> M [Satisfactory]
DLL = 5 wLL L34 / (384 E I) = 0.05 in
< L3 / 240 = 0.50 in [Satisfactory]

LANDING BEAM - 2

L = 12 ft
w = 600 plf, floor gravity load
P = P1 + P2 = 4.80 kips, total point loads, from STRINGER - 1
R = 0.5 w L + 0.5 P = 6.00 kips
M = w L2 / 8 + P L 3 / 4 = 25.21 ft-kips
Fy = 50.00 ksi
Mn / Wb = Fy Zx / 1.67 = 110.28 ft-kips
> M [Satisfactory]
DLL = 5 wLL L4 / (384 E I) + PLL L3 / (48 E I) = 0.04 in
< L / 240 = 0.60 in [Satisfactory]

COLUMN

P = 7.85 kips
R =nP= 15.70 kips
KL = H = 16 ft
K = 1.0
Fy = 46.00 ksi
Kl/r= 126
Fe = 18 ksi
Fcr = 16 ksi
Pn / Wc = Fcr Ag / 1.67 = 31.80 kips
> R [Satisfactory]
Mc = Mn / Wb = 17.98 / 1.67 = 10.77 ft-kips, (AISC 360 F)
F= 0.18 W = 0.18 x( 50 psf x 45.0 ft2 ) = 0.41 kips, ASD
(If no landing seismic load, F shall be zero.)
Mr = F H / 4 = 1.62 ft-kips

 Pr 8  M r  P r  0.2
    , for
 Pc 9  M c  Pc
0.63 < 1.0 [Satisfactory]
 
 P r   M r  , for P r  0.2
 2P  M  Pc
 c  c

DF = F H3 / (48 E I) = 0.26 in
< H / 240 = 0.80 in [Satisfactory]
PROJECT : PAGE :
CLIENT : DESIGN BY :
JOB NO. : DATE : REVIEW BY :
Steel Stair Design Based on AISC Manual 9th

INPUT DATA & DESIGN SUMMARY


COLUMN SECTION (Tube or Pipe) => HSS4X4X1/4
Tube A rmin t h
3.37 1.52 0.23 4.00
FLOOR BEAM - 1 => W16X26
A d Ix Sx
7.68 15.70 301.00 38.40
STRINGER - 1 (Channel or Tube) => MC8X8.5
Channel A d Ix Sx
2.50 8.00 23.30 5.82
STRINGER - 2 (Channel or Tube) => C12X20.7
Channel A d Ix Sx
6.08 12.00 129.00 21.50
LANDING BEAM - 1 (Channel or Tube) => C8X18.75
Channel A d Ix Sx
5.51 8.00 43.90 11.00
LANDING BEAM - 2 (Channel or Tube) => C8X18.75
Channel A d Ix Sx
5.51 8.00 43.90 11.00

DIMENSIONS H = 16 ft, story Ht


L1 = 12 ft
L2 = 6 ft
L3 = 10 ft

NUMBER OF STORIES n = 2

GRAVITY LOAD DL = 50 psf


LL = 100 psf

THE STAIR DESIGN IS ADEQUATE.

ANALYSIS

STRINGER - 1

q = 33.69 deg, from horizontal


w = 0.25 (DL / Cos q + LL) L3 = 400 plf , projected
R = 0.5 w L1 = 2.40 kips
M = w L12 / 8 = 7.20 ft-kips
fb = M / Sx = 14.85 ksi
Fb = 0.6 Fy = 21.60 ksi > fb [Satisfactory]
E = 29000 ksi
DLL = 5 (wLL Cos q) (L1 / Cos q)4 / (384 E I) = 0.46 in
< (L1 / Cos q) / 240 = 0.72 in [Satisfactory]

LANDING BEAM - 1

w = 0.5 (DL + LL) L2 = 450 plf


P = 2.40 kips, from STRINGER - 1
R = 0.5 w L3 + P = 4.65 kips
M = w L32 / 8 + P L3 / 2 = 17.63 ft-kips
fb = M / Sx = 19.23 ksi
Fb = 0.6 Fy = 21.60 ksi > fb [Satisfactory]
DLL = 5 wLL L34 / (384 E I) + PLL L33 / (24 E I) = 0.14 in
< L3 / 240 = 0.50 in [Satisfactory]
(cont'd)
STRINGER - 2

w = 400 plf , projected, from STRINGER - 1


P = 4.65 kips, from LANDING BEAM - 1
RL = [w L1 (0.5 L1 + L2) + P L2] / (L1 + L2) = 4.75 kips
RR = [w L1 (0.5 L1) + P L1] / (L1 + L2) = 4.70 kips
X = RL / w = 11.87 ft, from left
Mmax = RL X - (0.5 w X2 ) = 28.21 ft-kips
fb = Mmax / Sx = 15.75 ksi
Fb = 0.6 Fy = 21.60 ksi > fb [Satisfactory]
DLL = 5 wLL (L1 + L2)4 / (384 E I) + PLL (L1 +L2)3 / (48 E I) = 0.24
< (L1 + L2) / 240 = 0.90 in [Satisfactory]

LANDING BEAM - 2

w = 450 plf, from LANDING BEAM - 1


R = 0.5 w L3 = 2.25 kips
M = w L32 / 8 = 5.63 ft-kips
fb = M / Sx = 6.14 ksi
Fb = 0.6 Fy = 21.60 ksi > fb [Satisfactory]
DLL = 5 wLL L34 / (384 E I) = 0.05 in
< L3 / 240 = 0.50 in [Satisfactory]

FLOOR BEAM - 1

L = 12 ft
w = 600 plf, floor gravity load
P = P1 + P2 = 4.80 kips, total point loads, from STRINGER - 1
R = 0.5 w L + 0.5 P = 6.00 kips
M = w L2 / 8 + P L 3 / 4 = 25.21 ft-kips
fb = M / Sx = 7.88 ksi
Fb = 0.66 Fy = 33.00 ksi > fb [Satisfactory]
DLL = 5 wLL L4 / (384 E I) + PLL L3 / (48 E I) = 0.04 in
< L / 240 = 0.60 in [Satisfactory]

COLUMN

P = 6.95 kips
R =nP= 13.90 kips
KL = H = 16 ft
K = 1.0
Fy = 46 ksi
Cc = (2p2Es/Fy)0.5 = 112
Kl/r= 126
F = (K l / r) / Cc = 1.13
(1-F2/2)Fy / (5/3+3F/8-F3/8) = N/A kis, for Cc > (Kl/r)
Fa = {
12p Es/[23(Kl/r) ] =
2 2
9.38 kis, for Cc < (Kl/r)
Rallow = A Fa = 31.60 kips > R [Satisfactory]