Variable-Area Flowmeter H 250/M9
Variable-Area Flowmeter H 250/M9
00
GR
Variable-area flowmeter
H 250/M9
H 250/F (food)
In the M9 indicator, the vertical position ● all-metal flowmeter, no blind spots
of the float is transmitted to the pointer/ ● surface roughness of wetted parts Ra ≤ 0.8 µm
magnet system, and the flow value ● CIP and SIP cleanability (200°C)
indicated directly on the scale. ● materials in conformity with FDA standards
● connections: Tri-Clamp, DIN 11851, flanges, etc.
● EHEDG tested / USA 3-A certified
Indicator
M9 indicator/modular standard and EEx e
● direct-reading flow indicator
● indicator with extension piece (HT version) for high process
temperatures
● electrical signal output (ESK II) with HART® communication in
2-wire technology (can also be retrofitted)
● communication interface PROFIBUS-PA, as an alternative to ESK II
● max. 2 limit switches (K) adjustable on the scale (can also be
retrofitted)
● flow totalizer ESK-Z in connection with current output ESK II
(can also be retrofitted, not for hazardous duty)
● multipole ring magnet with effective eddy-current brake
● optionally, seawater-proof indicator housing
● optionally, indicator housing of stainless steel 1.4404 (M9 SS)
2
H 250
● A module rack in the M9 indicator accommodates all electrical ● If process temperatures should exceed the max. allowable level for the
add-on functions and the scale plate. standard version, the indicator can be adapted to the new operating
conditions by way of an adapter (HT version).
● The modules of electrical options ESK II, ESK3-PA, ESK-Z,
K1 or K2 and the scale plate are plugged into the module rack ● Measuring sections made of various materials and with different liners
(plug-in technique). are available for the process products.
● Module replacement or retrofitting without interrupting the process ● The flowmeter can be supplied with magnetic filters and/or a float
and without dismantling the pointer. damper, or these can be retrofitted.
Measuring
section
optionally
with heating
Scale
Electrical
signal output
ESK II or
ESK3-PA
Limit switch
unit
K1/K2 or
KD1/KD2
Flow
totalizer
ESK-Z Module rack M9
Standard housing
of diecast aluminium Indicator housing
of stainless steel
The variable-area flowmeter The variable-area flowmeter H 250 M9 is approved for use in
type: H 250/M9/ESK II hazardous areas.
Physikalisch-Technische Bundesanstalt:
meets the requirements of the 89/336/EEC directive EEx ia IICT6...T3 and EEx ib IICT6...T3
in compliance with the following European standards: H 250/M9: PTB 01 ATEX 2181
Factory Mutual Research (FM) USA:
EN 61326 : 03/1997 Class I, Division 1, Groups A, B, C and D
+A1 : 04/1998 Class I, Division 2, Groups A, B, C and D
+A2 : 03/2001 J.I.3001672
and also the requirements of NAMUR recommendation NE 21/05/93. Canadian Standards Association (CSA)
Class I, Division 1, Groups A, B, C and D
Class I, Division 2, Groups A, B, C and D
LR 105802-7
H 250 3
H 250 Responsibility for these measuring devices as to suitability, designated use and corrosion resistance of the materials
used in relation to the process product rests solely with the operator.
Technical data
Inside thread, screwed (RR, HC) companion dimensions to ISO 228 G1/2" - 1",
(with insert and union nut) PN 40 - 50
ANSI B 1.20.1 1/2" - 1" NPT
4 H 250
H 250 Die Verantwortung hinsichtlich Eignung und bestimmungsgemässer Verwendung unserer Geräte liegt allein beim Besteller.
Max. process temperature TS H250/ .. / M9 (excl. built-in electrical equipment) (TS = temperature specified)
Float Liner
H250 / C PTFE PTFE 70 ≤ 70
H250 / C ceramics PTFE 150 ≤ 70
H250 / C ceramics TFM 250 ≤ 120
Max. process temperatures TS in non-hazardous area for H 250 / M9 with built-in electrical equipment
without heating jacket with heating jacket Version Max. allowable process temperatures in °C
Ta < 40°C Ta < 60°C
DIN ANSI DIN ANSI Tp °C Tp °C (1) Tp °C (2)
DN15/25 1/2", 1" DN15 1/2"
Code designations:
ESK II - signal output 4 ... 20 mA
ESK-Z - flow totalizer
HT - high-temperature version
K - switching contact / 2-wire
KD - switching contact / 3-wire
H 250 5
H 250 Die Verantwortung hinsichtlich Eignung und bestimmungsgemässer Verwendung unserer Geräte liegt allein beim Besteller.
/ ESK 3-PA-EEx
Max. allowable process temperature Tp [°C]
Temperature class to EN 50014 T6 T5 T4 T3 T2, T1
Tamb [°C] ≤ 40 ≤ 60 ≤ 40 ≤ 60 ≤ 60 ≤ 40 ≤ 60 ≤ 40 ≤ 60
without with High- Heat-resistant
heating heating temperature cable required for
jacket jacket version Tp [°C] and higher
DN 15 DN 15 ---- 150 83 76 135 200 183 200 183
DN 25 x ---- 236 85 100 135 200 200 300 300
DN 50 DN 25 ---- 127 77 74 135 200 165 200 165
x ---- 171 85 91 135 200 200 300 300
DN 80 DN 50 ---- 109 71 72 135 200 150 200 150
DN 100 DN 80 x ---- 145 85 85 135 200 200 300 252
6 H 250
H 250 Die Verantwortung hinsichtlich Eignung und bestimmungsgemässer Verwendung unserer Geräte liegt allein beim Besteller.
H 250 7
H 250 Die Verantwortung hinsichtlich Eignung und bestimmungsgemässer Verwendung unserer Geräte liegt allein beim Besteller.
H 250/C CrNi steel 1.4571 CrNi-Stahl 1.4571 HC4, PTFE or Al2O3 or PTFE Al2O3
with PTFE liner ** with PTFE liner ** Al2O3 with gasket:
Kalrez KLR 6375 ***
H 250/F 2) CrNi steel 1.4435 CrNi steel 1.4435 CrNi steel 1.4435 CrNi steel 1.4435 -
The variable-area flowmeters within the meaning of the pressure equipment directive (PED) fall into three categories [Cat. I to Cat. III]:
Classification is according to Article 3, Item 1.2a), Diagram 6: pipelines for gases of fluid group 1.
For all categories, the Module H conformity assessment procedure is applied. Devices for low flows (cone 15.x) are not subject to a conformity
assessment. For these, Article 3.3 of the PED is applied.
For standard products (repeat jobs) the declaration of conformity can be issued in advance.
For customized products, the declaration is supplied on request together with the product.
In particular, devices fitted with flanges (EN-1092-1; ANSI B 16.5; JIS B 2238) are classified in Category III (suitability for unstable gases).
8 H 250
H 250
Limit switches
slave pointer
A total of two limit switches can be installed in the M9 indicator.
Switching point settings are indicated on the scale.
General mode of operation of the limit switches
The limit switches operate when the contact vane dips into the slot
sensor. Action is non-contacting. The switching point is hysteresis free. measured value
The switches operate when the setting pointer drops below the min. pointer
contact and rises above the max. contact. In connection with the
associated slave pointer system, the alarm can be switched on or
off in the switching point. terminals
slot sensor
The combination of sensor type and slave pointer version is the
deciding factor for whether or not open-circuit monitoring is additionally
possible.
H 250 9
H 250
Limit switches
Flow Flow Flow Flow Open-circuit
Signal trans- Type of less than more than less than more than monitoring Order No. Ex / ATEX
mitter/sensor contact Min. value Max. value possible
SC3,5-NO-Y min switched yes X251033100 yes
SC3,5-NO-Y max switched yes X251033200 yes
SC3,5-NO-Y min / max switched switched yes X251033300 yes
SJ3,5-SN min switched yes * X251033600 yes
SJ3,5-SN max switched yes * X251033700 yes
SJ3,5-SN min / max switched switched yes * X251033800 yes
SB3,5-E2 min switched no X251034200 no
SB3,5-E2 max switched no X251034300 no
SB3,5-E2 min / max switched switched no X251034400 no
SB3,5-E2 min switched yes X251033900 no
SB3,5-E2 max switched yes X251034000 no
SB3,5-E2 min / max switched switched yes X251034100 no
* fail-safe
Ident data
Built-in
equipment Ui[V] Ii[mA] Pi[mW] Ci[nF] Li[uH]
ESK II ≤ 30 ≤ 100 ≤ 1000 ≤ 20 =0
ESK3-PA ≤ 24 FISCO (1) =0 =0
4 ... 20 mA
= 0 ... 100% flow
* when metallically separated current evaluator modules (SPC) are used, the power supply (11/12) should not be grounded.
Technical data
Power supply 18 ... 30 V DC
Power consumption max. 70 mA
Input signal 4 ... 20 mA
Output sigal 0 ... 20 m-a
Rext. load impedance 0 ... 600 ohms
Ambient temperature -25°C to +65°C
Conversion error < 0.35%
Load effect < 0.1%
Temperature effect < 0.2%
H 250 11
H 250
PROFIBUS-PA connection
Connect the bus cable as shown on the right:
connect cable wires to D and D ⊥;
(polarity reversal has no effect).
The cable shield should be connected with minimum
length to the functional ground FE.
Equipotential bonding conductor must be connected to the device
(if necessary via the external U-clamp terminal for grounding bus
the M9 indicator part). connection
Technical data
Hardware Software
Physical to IEC 1158-2 GSD supplied on disk
and the FISCO model. (device master file) or via internet www.krohne.com
Supply voltage
via 2-wire bus connection: Device profile full implementation of profile B, V3.0
non-“Ex” application 9 ... 32 V DC
Use in hazardous areas 9 … 24 V DC Function blocks
Flow (AIO) optionally for volumetric or mass flow rate,
Current consumption selectable via channel parameters, default
Base current 12 mA units Qv [m3/h]; Qm [kg/h]
Starting current < base curent
FDE < 18 mA Totalizer (TOT0) volume totalizer
default unit: [m3]
Accuracy
in connection with H250/M9 Totalizer (TOT1) mass totalizer
to VDI/VDE 3513 Class 1.6 default unit: [kg]
Measured value resolution < 0.1% of full-scale value
Temperature effect < 0.05%/K of measured value Address range 0-126, default 126
set slave address is supported
EC type approval certificate SAP’s
11 2 G EEx ia IIC T6 PTB 00 ATEX 2063 Service_Access_Points 1
DD
Device Description DD for PDM
Operation via Profibus-PA
(no local operator control at device)
12 H 250
H 250
Optional equipment
Magnetic filter Damping system
If the process product contains ferromagnetic particles, install a (also available as retrofit kit)
magnetic filter upstream of the flowmeter. The filter contains bar
magnets in helical arrangement for optimum efficiency at low
pressure loss. All magnets are individually coated with PTFE as damping cylinder of ceramics,
protection against corrosion.
PEEK or stainless steel
Two versions are available:
damping tube
Type F - flange adapter for all
nominal sizes, overall
length 100 mm, material
float
1.4571 and others
Pointer cylinder
H 250 13
H 250
Flow tables
Float shape Reference conditions
Water CIV, DIV Water at 20°C
Air TIV, DIV Air at 20°C; 1.013 bar abs.
100% flow values, turndown ratio 10:1
H 250/RR, H 250/HC (Hastelloy C4)
Nominal size Cone No. Water Air Max. pressure drop mbar
DIN ANSI l/h m3/h
DN inches CIV DIV TIV * DIV CIV TIV DIV
15 1/2" K 15.1 25 - 0.65 - 26 21 -
K 15.2 40 - 1.0 - 26 21 -
K 15.3 63 - 1.5 - 26 21 -
K 15.4 100 - 2.2 - 26 21 -
K 15.5 160 - 3.6 - 26 21 -
K 15.6 250 - 5.5 - 26 21 -
K 15.7 400 - 10 18 28 21 38
K 15.8 630 1000 14 28 32 22 50
25 1" K 25.1 630 - 14 - 32 24 -
K 25.2 1000 - 22 - 33 24 -
K 25.3 1600 - 35 - 34 25 -
K 25.4 2500 - 50 110 38 26 78
K 25.5 4000 6300 80 170 45 30 103 **
50 2" K 55.1 6300 - 80 230 74 13 60
K 55.2 10000 - 110 350 77 13 69
80 3" K 85.1 25000 - 350 - 68 16 -
K 85.2 40000 - 400 - 89 16 -
100 4" K105.1 63000 100000 - 120 - 220
* not for flowmeters with heating (M9 indicator) ** 300 mbar with damper (gas service)
A float damper is recommended: The specified pressure losses apply to water and air at max. flow rate.
for TIV floats with an operating (inlet) pressure < 0.3 bar [DN 15, Conversion to other process products or operating data (pressure,
DN 25 (1/2", 1")] ≤ 0.2 bar [DN 50 (2")] and generally when temperature, density, viscosity) can be carried out with the aid of the
CIV and DIV floats are used on gas service. calculation method to VDE/DVI Code 3513.
14 H 250
H 250
150
M16x1.5
ød
300
250
250
Weights Weights
H 250 with screw connection to DIN 11851 H 250/C (ceramic/PTFE)
Nominal size Max. allowable Approx. weight Meter size to Approx. weight
of flow operating DIN 2501 ANSI B 16.5 DIN 2501 ANSI B 16.5
pressure in
150 lbs 300 lbs
DN mm inches bar psig kg lbs
DN PN inches lbs kg lbs kg lbs kg lbs
15 1/2" 40 580 2.0 4.4 15 40 1/2" 150/300 3.5 7.7 3.2 7.0 3.5 7.7
25 1" 40 580 3.5 7.7 25 40 1" 150/300 5 11.0 5.2 11.5 6.8 15.0
50 2" 25 363 5.0 11.0 50 40 2" 150/300 10 22.1 10 22.1 11 24.3
80 3" 25 363 7.6 16.8 80 16 3" 150/300 13 28.7 13 28.7 15 33.0
100 4" 25 363 10.3 22.7 100 * 16 4" 150/300 15 33.1 16 35.3 17 37.5
* PTFE only
overall height 3" / 300 lbs and more: 300 mm
H 250 15