Electrical Power and Energy Systems: M. Giroletti, M. Farina, R. Scattolini

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 7

Electrical Power and Energy Systems 35 (2012) 194–200

Contents lists available at SciVerse ScienceDirect

Electrical Power and Energy Systems


journal homepage: www.elsevier.com/locate/ijepes

Short Communication

A hybrid frequency/power based method for industrial load shedding


M. Giroletti, M. Farina ⇑, R. Scattolini
Dipartimento di Elettronica e Informazione, Politecnico di Milano, Via Ponzio 34/5, 20133 Milano, Italy

a r t i c l e i n f o a b s t r a c t

Article history: This paper provides a systematic classification of existing Load Shedding (LS) methods and proposes a
Received 2 June 2011 novel LS algorithm, with specific reference to industrial systems power plants. The proposed technique
Received in revised form 26 September is based on a combination of the information provided by the measurement of the frequency, as in many
2011
frequency-based LS approaches, with the information available on the status of the generators, like in LS
Accepted 10 October 2011
power-based techniques. In this way, it is possible to guarantee fast response in front of generator trips
Available online 4 November 2011
together with the possibility to fully take advantage of the available spinning reserve. Simulation results
are reported to illustrate the performance of the proposed approach and to compare them to those guar-
Keywords:
Load shedding
anteed by consolidated techniques.
Industrial power plants Ó 2011 Elsevier Ltd. All rights reserved.
Frequency and power-based methods

1. Introduction is trivial. Therefore, the main issue is the frequency stability and
the LS action is aimed at restoring the power balance. For these
Power systems of industrial plants can be easily prone to the reasons, LS is usually based on:
occurrence of unpredictable circumstances, such as short-circuits,
generation losses or sudden breakdown of distribution lines. All (I) the measurements of the (grid) frequency and its derivative,
these events may result in emergency conditions where the load see e.g. [14–19]. In particular, methods based on the fre-
unbalance can cause dangerous cascade effects, such as the fre- quency derivative are frequently denoted adaptive, and
quency decay, the intervention of protection devices and the shut- allow the LS action to fit the size of the disturbance, in con-
down of one or more generators for safety reasons. In turn, this trast with previously developed methods, based on the fre-
yields an increase of the initial power deficiency and may even lead quency measurements solely, which require iterative
the entire power system to collapse. In order to prevent this dra- shedding procedures (see, e.g., [15]);
matic event, various Load Shedding (LS) strategies are adopted, (II) the comparison of the power supplied by generators and
all of them consisting of shedding a proper amount of load to de- absorbed by the loads, see e.g. [20–23] where fast and opti-
crease the overall power consumption and restore the power bal- mal solutions are proposed combining power-based distur-
ance between generated and absorbed power. bance detection methods with offline computation of maps
The selection of suitable LS strategies depends on the applica- for load selection (see also [24], where advanced load selec-
tion scenario. In large scale and wide area power systems the typ- tion methods are proposed).
ically adopted methods, see e.g. [1–13], are based on voltage
measurements, useful to determine the perturbation location, so Methods combining approaches (I) and (II) have been proposed
that the LS action can be confined to the area affected by the power in [25,26], where power-based methods are mostly used to provide
deficiency. Basic schemes are presented in [1,2], while more ad- a fast counter-action to generation trips, while frequency-based
vanced schemes based on predictive control and optimization are methods work on a slower time-scale, to provide auxiliary LS.
proposed in [3–5], and distributed implementations are described Application studies of various industrial load shedding architec-
in [6–9]. Comparisons and critical reviews of existent voltage- tures are described in [27–30].
based LS methods can be found in [10,11], while examples of appli- Techniques based on frequency (I) or on power (II) measure-
cation to real wide-area networks are provided in [12,13]. ments have their own advantages and drawbacks. Generally speak-
On the other hand, in case of local power systems, such as those ing, LS methods based on the detection of under frequency
of industrial plants, the detection of the location of the contingency conditions usually do not fully benefit from the available spinning
reserve. On the other hand, the performance of power-based meth-
ods can be hampered by the time required to complete the polling of
⇑ Corresponding author. Tel.: +39 0223993599; fax: +39 0223993412. a wide number of generators and loads and by the associated trans-
E-mail address: farina@elet.polimi.it (M. Farina). mission delays.

0142-0615/$ - see front matter Ó 2011 Elsevier Ltd. All rights reserved.
doi:10.1016/j.ijepes.2011.10.013
M. Giroletti et al. / Electrical Power and Energy Systems 35 (2012) 194–200 195

Nomenclature

Scalar variables P(t) ideal shed power or net shed power (W)
Ng number of generators Peff(t) load power eventually removed by shedding loads (W)
Nl number of loads Ta overall grid start-up time (s)
f(t) frequency (Hz) Tag start-up time of the generators (s)
fn nominal grid frequency Tal start-up time of motor loads (s)
df(t)/dt frequency derivative (Hz/s) Tag,i start-up time of the ith generator (s)
Pn(t) overall nominal generated power (W)
Pm(t) overall generated power (W) Array variables
Pc(t) overall power consumption (W) Bg(t) vector storing the status of the generators (array of
Pn,i(t) nominal real power of the ith generator, Pn ðtÞ ¼
P length Ng of booleans, the ith component is 1 if the ith
Ng
P ðtÞ (W)
i¼1 n;i generator is properly working) ()
Pg,i(t) power produced by the ith generator, P m ðtÞ ¼ Bl(t) vector storing the sampled status of the loads (array of
PN g
i¼1 P g;i ðtÞ (W) length Nl of booleans, the ith component is 1 if the ith
P l load is active) ()
Pl,i(t) power absorbed by the ith load, P c ðtÞ ¼ Ni¼1 P l;i ðtÞ (W)
R(t) spinning reserve (W) Pg(t) vector storing the (sampled) power supplied by the
D(t) power deficiency (D(t) = Pm(t)  Pc(t)) (W) generators (array of length Ng) (W)
A(t) gross shed power (power deficiency determined by the Pl(t) vector storing the (sampled) power absorbed by the
LS algorithm) (W) loads (array of length Nl) (W)

In general, all the LS strategies for islanded industrial plants can and the status of the loads, respectively. On the contrary, the status
be conceptually divided in three stages, namely the detection of of the generators, stored in vector Bg(t), is assumed to be acquired
the power deficiency (mismatch detection), the computation of at a much higher frequency (10 ms) by a dedicated system. This is
the power unbalance (deficiency estimation) and the selection necessary to guarantee an almost instantaneous intervention of the
of the loads to be removed (load selection). LS algorithm in case of production loss.
This paper mainly focuses on the phases of mismatch detection The amount of data to be collected and stored in Pg(t), Pl(t) and
and deficiency estimation and proposes a new hybrid method, Bl(t) can be very high (2Nl + Ng), and the sequential polling of all
which combines the most significant features of frequency-based the peripherals (generators and loads) can require a significant time.
(fLS) and power-based (PLS) LS approaches. The paper is organized Denote by Tpol (1–2 s) the time period required to complete the
as follows. In Section 2 the considered power system is described polling procedure, and by Tcom the associated computational time.
together with a sketch of the main features of the most common Then, letting
fLS and PLS methods. Section 3 is devoted to describe the new
T pol þ T com ¼ T cycle
hybrid technique denoted hLS, while in Section 4 a detailed simu-
lation example is reported and discussed to witness the advantages
of the proposed approach. Finally, Section 5 draws some conclu- It is apparent that possible variation of the status (on/off or
sions and hints for future research. power supplied/consumed) of a generator or a load can be detected
and stored in Pg(t), Pl(t) and Bl(t) with a delay in the range
2. Load shedding: structure and methods (0, Tpol + Tcycle), while its effect on the action taken by LS ranges be-
tween Tcom and 2Tcycle, see Fig. 1 for an illustration. These delays are
2.1. Power system: description and main assumptions comparable to the system dynamics and cannot be ignored in the
design of an efficient LS algorithm. Note however that they do
In the following, reference is made to a typical industrial power not affect the LS reaction time, but possibly only the appropriate-
system, characterized by a limited number of generators (Ng < 10), ness of LS action, which can be based on obsolete data.
possibly including the ‘‘infinite power’’ area grid, and hundreds or a 2.2. Dynamic model and general structure of LS algorithms
few thousands of loads (Nl = 100–5000). The phenomena of interest
associated to the transients of frequency and power flow in the grid Assuming a uniform frequency (all the generators and loads
are due to the dynamics of generators and loads. Primary and second- have the same angular velocity), the dynamics of the grid is
ary frequency regulation are assumed to be available (see [31]), described by the following equation
therefore the LS algorithm must be designed to compensate potential
generation losses, while load variations are considered as distur- df ðtÞ fn
¼  DðtÞ ð1Þ
bances to be rejected by frequency regulation, see [31]. This approach dt T a  Pn
is also aimed at minimizing the LS intervention when the system is where Ta (s) is the grid start-up time, fn and Pn are the nominal fre-
designed to properly supply the power required by the loads. quency (e.g. 50 Hz) and the power of the system, respectively, while
All the measurements, in particular of frequency and power, are D(t) = Pm(t)  Pc(t) is the power deficiency. The term Ta can be eval-
supposed to be affected by a negligible time delay, typically 10– uated as:
100 ms, while most significant delays are due to data acquisition  
and transmission from the peripherals to the central unit where T al Pc
T a ¼ T ag 1 þ ð2Þ
the LS algorithm is implemented. More specifically, these acquisi- T ag Pn
tion and transmission delays are of about 1–2 s depending on the where
number of peripherals (and hence on the amount of data to be
gathered), and are associated to the information stored in the vec-
PN g
i¼1 T ag;i  P n;i
tors Pg(t), Pl(t) and Bl(t) containing the sampled values of the T ag ¼ PNg ð3Þ
power produced by generators (Pg,i), absorbed by the loads (Pl,i) i¼1 P n;i
196 M. Giroletti et al. / Electrical Power and Energy Systems 35 (2012) 194–200

Fig. 1. Sampling of power data: graphic representation of the case of maximum delay between load variation and LS intervention.

Pn,i is the nominal real power of the ith generator, Tag,i. is the start- rithm is run when a generator is switched-off (recall that this infor-
up time of the ith generator, Pc (<Pn) is the power consumed by mo- mation is acquired at a high frequency). Actually, due to the
tor loads and Tal is the start-up time of motor loads, which can be acquisition and transmission delays described in Section 2.1 and
derived with a formula equivalent to the one used for Tag (Eq. (3)). to the associated sampled updates, the information available and
Usually, power systems are not operated at their maximum stored in the vectors Pg (t), Pl(t) and Bl(t) does not represent in gen-
power, so that they can respond to possible rises of power demand. eral the status of the system when the LS procedure is run. This can
The spinning reserve R(t) is defined as the overall surplus of real lead to an inadequate LS action with severe consequences, in par-
power that can be instantaneously produced by generators, and ticular in those critical cases when obsolete data are used to carry
is given by: out the LS action (see again Fig. 1).
Ng
X 2.4. Frequency-based load shedding
RðtÞ ¼ ðP n;i  P g;i ðtÞÞ ð4Þ
i¼1
The basic principle of fLS methods is to monitor the frequency
In normal working conditions, all the Ng generators are opera- and its derivative and to compare their values to specified thresh-
tive and R(t) varies continuously with Pg,i(t), which in turn depends olds. Many algorithms of this type have been proposed, see e.g.,
on the load variations. However, when one or more generators [20–23]; in the following only a prototypical algorithm, essentially
switch to fault conditions, their contribution is immediately set based on the frequency derivative, is described.
to zero and R(t) varies discontinuously. From Eq. (1), there is an immediate correspondence between
It is apparent that the proper use of the spinning reserve is cru- the derivative of the frequency and the amount of power defi-
cial for a correct management of the power system and can signif- ciency. Therefore, a fLS algorithm can be developed as follows. A
icantly reduce the intervention of LS algorithms. Indeed, LS can be pre-specified allowable range [dfmin, 0] for the variations of df(t)/
interpreted as an additional and emergency frequency control that dt due to load increments or generation trips is initially assumed.
must operate in case of an insufficient spinning reserve. Then, this range is uniformly quantized in nt levels dfi, i = 0, . . ., nt
A general LS algorithm must be conceptually organized in the  1, and a value Ai, i = 0, . . ., nt  1, of the gross shed power A(t) is
following steps. associated to each level according to the following expression de-
rived from (1):
 Mismatch detection: during this stage the non-null power defi-
ciency is detected and the estimate A(t) of D(t), named gross Ta
Ai ¼ P n dfiþ1 ; i ¼ 1; . . . ; nt  1 ð5Þ
shed power, is computed according to the selected strategy fn
(e.g., power based or frequency-based). Note that the finer is the quantization, i.e. the larger is the num-
 Deficiency estimation: during this stage the theoretical load ber nt of quantization levels, the better is the estimate A(t) of D(t).
power to be removed in order to restore standard operating In any case, due to discrete-effect of thresholds, A(t) P D(t), so as to
conditions is computed. It is referred in the following as ideal guarantee frequency restoration.
shed power, and denoted by P(t). An efficient LS method should When the power system is in operation and a generation loss
minimize the value of P(t) by using the spinning reserve to the occurs, the mismatch detection phase is completed by selecting
maximum possible extent. the quantization level corresponding to the current value of df(t)/
 Load selection: during this last stage the power Peff(t) dt and by assigning to A(t) the corresponding value Ai.
(Peff(t) P P(t)) to be actually removed from the power system The main advantages of using the fLS approach lie in the possi-
is computed and the loads to be shed are identified according bility to instantaneously detect under-frequencies, since the corre-
to a pre-defined criterion. In an ideal case, the LS procedure sponding measurements are not affected by delays, and in the fact
should lead to Peff(t)  P(t). that the computation of A(t) (see Eq. (5)) is affected by obsolete
knowledge of the grid status less severely than in case of PLS
2.3. Power-based load shedding (i.e., the value of Ta can be considered constant, to a first approxi-
mation). On the other hand, these methods do not use the available
In ideal PLS methods the mismatch detection and deficiency spinning reserve, so that the amount of power disconnected is
estimation phases are simply completed by computing the power greater than the minimum value strictly required. Moreover, since
deficiency D(t) and the load power to be removed based on the in Eq. (5) Ta is usually assumed to be time-invariant during power
instantaneous measurements, on the status of the generators and system operations, the method could not be properly tuned in crit-
on the available spinning reserve. More specifically, the LS algo- ical working conditions.
M. Giroletti et al. / Electrical Power and Energy Systems 35 (2012) 194–200 197

Fig. 2. Frequency derivative trend after a load disturbance and subsequent power Fig. 3. Frequency derivative trend after power deficiency and consequent LS
deficiency. intervention.

2.5. A critical scenario of one or more generators even in critical cases, such as in the
scenario depicted in Section 2.5.
In order to evaluate the performance provided by the PLS and  Corrective interventions: in order to trigger possible corrective
fLS methods, consider the case where one or more loads are acti- interventions after a first load shed, an error signal efd(t),
vated just before the disservice of one or more generators or when defined as the difference between the frequency derivative after
the plant is disconnected from the area grid due to the breakdown and before the first corrective action is computed. The rationale
of a distribution line. This has different effects on the performance of this choice is illustrated in Fig. 3, where it is assumed that a
provided by the two approaches. generator trip is occurred at time td and the subsequent load
shed has not been sufficient to restore the frequency derivative
 PLS: When the LS algorithm is activated by the generator trip, at its value taken at t d . The amount of a second load shed
the information stored in the vectors Pg(t), Pl(t) and Bl(t) is depends on efd(t).
obsolete, and D(t) is underestimated by A(t). Moreover the spin-  Update of the grid start-up time: the parameter Ta is considered
ning reserve is overestimated; as a consequence, the ideal shed time varying and its value is periodically updated according to
power value is underestimated and the grid power balance is the available information on the operating generators (provided
not restored. by Bg(t)). Consequently the gross shed power in hLS becomes a
 fLS: The effect of the generator loss is overestimated, since a sig- time varying variable, i.e.,
nificant contribution to the frequency variation is due to the
increased load. A simple graphical representation is shown in
T a ðtÞ
Fig. 2, which illustrates the df(t)/dt trend after a load variation Ai ðtÞ ¼ Pn dfiþ1 ; i ¼ 1; . . . ; nt  1 ð6Þ
fn
at time tl and a subsequent power deficiency at time td due to
generation trip. Recall that in our assumptions (see Section
2.1) primary and secondary frequency regulation is available in this way, the parametric uncertainty of Ta(t) is removed.
and the LS method is in charge to compensate for power unbal-  Use of the spinning reserve (as in [32]): the value of the spinning
ance only due to generation losses, i.e., only when the status of a reserve is periodically updated, with period Tcycle or is subject to
generator changes (an element of vector Bg). Then, it is apparent asynchronous variations in case of generator loss.
 
that, being df td =dt different from its nominal zero value, the
estimation of the power deficiency A(t) due to the switch-off Note that in the hLS method, like in the power-based approach,
of  the
 generator calculation and based on the analysis of the value of the spinning reserve is unavoidably based on data
df tþ d =dt would be significantly wrong. which could be obsolete. However, since the main actions are re-
lated to the measurement of the frequency and its derivative, a
continuous-time monitoring of the power system status is per-
3. Hybrid frequency/power based load shedding formed as in the fLS approach, and there is the possibility to per-
form a corrective action in the case of previous insufficient LS.
In order to overcome the main drawbacks of the PLS and fLS Therefore, in case of concomitant generator trip and rise in power
methods, a new hybrid algorithm is proposed. It is referred to as consumption (the critical scenario of Section 2.5), hLS acts as
hLS and basically combines the advantages of the two approaches, follows:
i.e. the robustness and insensitivity to measurement delays of fLS
methods and the possibility to use the spinning reserve of the  in the first intervention, the load computed from the measure-
PLS techniques. hLS is essentially based on the fLS approach sup- ment of Ddf(t)/dt is shed, however this action could be insuffi-
plemented by the information on the instantaneous status of the cient due to a wrong evaluation of the spinning reserve;
generators (stored in the vector Bg(t)) and on the sampled informa-  in the second intervention, additional load is removed, corre-
tion on the status of the generators (stored in the vector Pg(t)) to sponding to a shed power value computed according to efd(t),
properly estimate and use the available spinning reserve. The main in order to finally achieve frequency recovery. Specifically, for
characteristics of hLS are: the value of efd(t) different levels must be defined and a given
level of LS is to be defined for each level.
 Rejection of load perturbation effects in the computation of the
frequency derivative variations: the mismatch detection phase Furthermore, Tcycle can be significantly reduced since, unlike the
is performed by analyzing the variation Ddf(t)/dt of the power-based approach, hLS does not use load measurements and,
frequency derivative instead of the derivative df(t)/dt itself. This consequently, the polling procedure is only referred to generators
allows one to properly estimate the effect of the generation trip (recall that Nl  Ng). This is very effective in decreasing the obso-
198 M. Giroletti et al. / Electrical Power and Energy Systems 35 (2012) 194–200

lescence of power measurements and in the reliability of the spin- Table 1


ning reserve estimation. Normalized values of estimated gross shed power a, spinning reserve r, and ideal shed
power p in the three cases, for the three LS methods, in face of a normalized
perturbation d = 28.33%.

Case 1 2 3
4. A simulation example
LS f P h f P h f P h
In order to test the performance of the hLS approach and to a 37 28.3 29 30 28 32 29 33.8 33
compare it with frequency and power-based approaches, a proto- r – 10 10 – 10 10 – 6.2 6.2
p 37 19.3 20 + 9 30 19 23 + 6 29 28.6 27.8
typical industrial power plant has been considered, simulated
and tested in the critical scenario described in Section 2.5.
The power system is equipped with primary and secondary fre-
quency regulation, the nominal frequency is fn = 50 Hz, there are 55
three generators with nominal power Pn,i = 24 MW, i = 1, 2, 3 (over-
all power Pn = 72.0 MW) and start-up time Tag,i = 10 s, i = 1, 2, 3. The

f(t) [Hz]
simulations reported in the following are characterized by initial 50
equilibrium conditions with an initially supplied power provided
X
by each generator Pg,i = 20.4 MW, i = 1, 2, 3, which corresponds, in
steady state, to the overall produced and absorbed power 45
Pc = 61.2 MW. Correspondingly, the initial spinning reserve for 0 5 10 15 20 25 30 35 40

each generator is Ri = 3.6 MW, i = 1, 2, 3, and the total one is R = t [s]


10.8 MW. Consequently, the grid start-up time is Ta = 10 s. The 0.5
value of Tcycle is 2 s.
0

df(t)/dt [Hz/s]
In the example below the following two subsequent events are X
−0.5
simulated:
−1
 t = tl = 4.2 s: load variation of +6 MW (8.33% of the nominal gen- −1.5
erated power);
−2
 t = td (td > tl): loss of generator 3, correspondingly the power 0 5 10 15 20 25 30 35 40
deficiency is D(t) = 20.4 MW. t [s]

Note that, in view of the previous assumptions, the initial load Fig. 4. Frequency (top) and frequency derivative (bottom) in Case 1. Trajectories:
hLS (solid line), fLS (dashed line), PLS (dotted line). Vertical lines: tl (black dashed
variation at tl is dynamically compensated by the frequency regu- line), td (gray line), occurrence of LS (dotted line(s)). The symbol X indicates crossing
lation. Therefore, it is worth remarking that the power deficiency is by PLS of the security threshold (f = 47.5 Hz).
variable with td. In fact, after the rise of the load, the power sup-
plied undergoes a transient approximately of ten seconds and the
closer is td to tl, the lower is the power deficiency. 55
The most critical situation arises when Dt = td  tl is small. If
Dt P 4 s, the power data are updated to their correct values (recall
f(t) [Hz]

that the maximum updating delay is 2Tcycle = 4 s, see Section 2.1); 50


if Dt < 4 s, power consumption and power generation data can be
obsolete and if td < 6 s, they are obsolete with probability 1; there- X
fore, if td < 8 s, a second LS intervention may be necessary.
45
In line with this remark, three scenarios are tested in simula- 0 5 10 15 20 25 30 35 40
tion, namely: t [s]

0.5
1. Dt = 0.2 s (td = 4.4 s).
0
df(t)/dt [Hz/s]

2. Dt = 3.6 s (td = 7.8 s).


X
3. Dt = 4.3 s (td = 8.5 s). −0.5

−1
In the simulations reported below, the levels of intervention of
−1.5
the LS algorithm applied have been properly defined for f(t), df(t)/
dt and Ddf(t)/dt. Moreover, the transients of the power deficiency −2
0 5 10 15 20 25 30 35 40
D(t), of the gross shed power A(t), of the ideal shed power P(t) t [s]
and spinning reserve R(t) have been normalized with respect to
the nominal power Pn and the corresponding values d(t), a(t), Fig. 5. Frequency (top) and frequency derivative (bottom) in Case 2. Trajectories:
p(t), and r(t), respectively, have been reported (in per unit) in the hLS (solid line), fLS (dashed line), PLS (dotted line). Vertical lines: tl (black dashed
line), td (gray line), occurrence of LS (dotted line(s)). The symbol X indicates crossing
following figures. by PLS of the security threshold (f = 47.5 Hz).
Notably, in Cases 1 and 2, the polling procedure is not com-
pleted in the interval Dt between the first perturbation (load in- the amount of load to be removed by hLS is 29% of the nominal
crease) and the second one (loss of a generator). power, while fLS disconnects 37%.
Table 1 reports the values a, r, p in the three cases, for the three LS The transients (t 6 40 s) of the main variables f(t) and df(t)/dt, in
methods, in face of a normalized perturbation d = 28.33%. Remark the three considered scenarios, are shown in Figs. 4–6, while a
that, for hLS and PLS, the first LS action provides p = a  r + 1%. The more detailed illustration (4 6 t 6 11 s) of the initial responses is
addition of 1% is due for allowing perfect frequency regulation. given in Figs. 7–9.
In all considered scenarios, the shedding action required by hLS As it is apparent from Figs. 4 and 5, the LS actions provided by
is the least dramatic, in terms of shed load. Remarkably, in Case 1, both hLS and fLS prevent the system to collapse, while PLS cannot
M. Giroletti et al. / Electrical Power and Energy Systems 35 (2012) 194–200 199

55 55

f(t) [Hz]
f(t) [Hz]

50
50

45
45 tl td tLS
0 5 10 15 20 25 30 35 40
t [s] 0.5

df(t)/dt [Hz/s]
0
0.5
−0.5
0
df(t)/dt [Hz/s]

−1
−0.5
−1.5
−1 −2
4 5 6 7 8 9 10 11
−1.5 t [s]
−2
0 5 10 15 20 25 30 35 40 Fig. 9. Frequency (top) and frequency derivative (bottom) in Case 3 (detail:
t [s] 4 6 t 6 11 s). Trajectories: hLS (solid line), fLS (dashed line), PLS (dotted line).
Vertical lines: tl (black dashed line), td (gray line), occurrence of LS (dotted line(s)).
Fig. 6. Frequency (top) and frequency derivative (bottom) in Case 3. Trajectories:
hLS (solid line), fLS (dashed line), PLS (dotted line). Vertical lines: tl (black dashed
line), td (gray line), occurrence of LS (dotted line(s)). 0.2

r [pu]
0.1

0 X
55 0 5 10 15 20 25 30 35 40
t [s]
f(t) [Hz]

50 0.2
r [pu]

X 0.1
45
t t t t ’ 0 X
l dLS LS 0 5 10 15 20 25 30 35 40
t [s]
0.5
df(t)/dt [Hz/s]

0 0.2
X
−0.5
r [pu]

0.1
−1
−1.5 0
0 5 10 15 20 25 30 35 40
−2
4 5 6 7 8 9 10 11 t [s]
t [s]
Fig. 10. Transients of the available normalized spinning reserve for Case 1 (top),
Fig. 7. Frequency (top) and frequency derivative (bottom) in Case 1 (detail: Case 2 (middle), and Case 3 (bottom). Trajectories: hLS (solid line), fLS (dashed line),
4 6 t 6 11 s). Trajectories: hLS (solid line), fLS (dashed line), PLS (dotted line). PLS (dotted line). Vertical lines: tl (black dashed line), td (gray line), occurrence of LS
Vertical lines: tl (black dashed line), td (gray line), occurrence of LS (dotted line(s)). (dotted line(s)). The symbol X indicates the instant when PLS crosses the security
The symbol X indicates crossing by PLS of the security threshold (f = 47.5 Hz). threshold (f = 47.5 Hz) in Cases 1 and 2.

provide a sufficient shed, so that the system crashes. For hLS, the
second LS intervention is crucial to recover normal operating con-
55 ditions. In Case 3 only one intervention of the LS algorithms is nec-
essary because power data are updated on time, and both PLS and
f(t) [Hz]

hLS can guarantee good performances, as shown in Fig. 6, where


50
the transients of the frequency and its derivative are reported. Note
that the LS algorithms are triggered only after the generation trip.
45 In Figs. 7–9, we clearly show the sequence of events occurring in
t td tLS tLS’ time: specifically, while the load variations occur at instant tl and
l
the generation trips arise at instant td, the instants when the load
0.5
shedding actions are exerted are indicated with tLS.
df(t)/dt [Hz/s]

0
Fig. 10 shows the corresponding transients of the available nor-
−0.5 malized spinning reserve.
−1 To conclude, in view of Table 1 and Figs. 4–10, it is apparent
−1.5 that, while PLS can be critical in certain circumstances, hLS pro-
−2 vides safe operation, while requiring a minimal amount of load
4 5 6 7 8 9 10 11
t [s] shedding with respect to other methods such as fLS. For this rea-
son, it is believed that hLS can be a promising approach, combining
Fig. 8. Frequency (top) and frequency derivative (bottom) in Case 2 (detail: safety and performance.
4 6 t 6 11 s). Trajectories: hLS (solid line), fLS (dashed line), PLS (dotted line).
Vertical lines: tl (black dashed line), td (gray line), occurrence of LS (dotted line(s)).
The symbol X indicates crossing by PLS of the security threshold (f = 47.5 Hz).
200 M. Giroletti et al. / Electrical Power and Energy Systems 35 (2012) 194–200

5. Conclusions [8] Otomega B, Glavic M, Van Cutsem T. Distributed undervoltage load shedding.
IEEE Trans Power Syst 2007;22(4):2283–4.
[9] Otomega B, Van Cutsem T. Local vs. wide-area undervoltage load shedding in
In this paper a critical review of available load shedding algo- the presence of induction motor loads. In: Proceedings of the IEEE power tech
rithms is provided, and a novel method is proposed, specifically conference; 2009. p. 1–7.
[10] Van Cutsem T, Vournas CD. Emergency voltage stability controls: an overview.
tailored for power plants of industrial systems. This method com-
In: Proceedings of the IEEE PES general meeting; 2007. p. 1–10.
bines the advantages of the algorithms based on the grid frequency [11] Moors C, Lefebvre D, Van Cutsem T. Load shedding controllers against voltage
measurements, i.e. prompt intervention in case of generation instability: a comparison of designs. In: Proceedings of the IEEE power tech
conference, vol. 2; 2001.
losses, with those guaranteed by the approaches based on the anal-
[12] Lefebvre D, Bernard S, Van Cutsem T. Undervoltage load shedding scheme for
ysis of the unbalance between the produced and consumed power, the Hydro-Quebec system. In: Proceedings of the IEEE PES general meeting,
i.e. the possibility to use the available spinning reserve to reduce vol. 2; 2004. p 1619–24.
the amount of load to be shed. [13] Nikolaidis VC, Vournas CD, Fotopoulos GA, Christoforidis GP, Kalfaoglou E,
Koronides A. Automatic load shedding schemes against voltage instability in
The main characteristic of the proposed approach, named hLS, is the Hellenic system. In: Proceedings of the IEEE PES general meeting; 2006. p.
to compute the LS action on the basis of (a) the spinning reserve, 1–7.
(b) the dynamic update of the grid start-up time information, (c) [14] Anderson PM, Mirheydar M. An adaptive method for setting underfrequency
load shedding relays. IEEE Trans Power Syst 1992;7(2):647–55.
the difference between the values taken by the frequency deriva- [15] Huang SJ, Huang CC. An adaptive load shedding method with time-based
tive just before and after the disconnection of a generator to com- design for isolated power systems. Electr Power Energy Syst 2000;22(1):51–8.
pute an initial LS, (d) the possibility of carrying out corrective LS [16] Villamediana HJ, Neira AC. Dynamic stability improving at industrial electrical
systems through the use of variable load shedding schemes. In: Proceedings of
actions. Simulation results have demonstrated that this approach the transmission & distribution conference and exposition: Latin America;
is able to cope with critical situations where significant perturba- 2006. p. 1–5.
tions (load increase, breakdown of a generator) occur in rapid se- [17] Ford JJ, Bevrani H, Ledwich G. Adaptive load shedding and regional protection.
Electr Power Energy Syst 2009;31:611–8.
quence. With respect to frequency based approaches, hLS gives
[18] Hirodontis S, Li H, Crossley PA. Load shedding in a distribution network. In:
also the possibility to fully take advantage of the available spinning Proceedings of the international conference on sustainable power generation
reserve, so reducing the amount of load to be shed even in critical and supply; 2009. p. 1–6.
[19] Rudez U, Mihalic R. Monitoring the first frequency derivative to improve
situations.
adaptive underfrequency load-shedding schemes. IEEE Trans Power Syst
In the paper, minor attention has been given to the final step of 2011;26(2):839–46.
the LS procedure (the load selection phase), i.e. the best choice of [20] Delfino B, Croce F, Fazzini PA, Massucco S, Morini A, Silvestro F, et al. Operation
the loads to be selected once the total amount of LS has been com- and management of the electric system for industrial plants: an expert system
prototype for load-shedding operator assistance. IEEE Trans Ind Appl
puted. To this regard, a dynamic algorithm has been developed 2001;5:3260–7.
with the aim to minimize both the number of loads to be removed [21] Pinceti P. Emergency load-shedding algorithm for large industrial plants.
and the difference between the ideal and the effective power to be Control Eng Pract 2002;10(2):175–81.
[22] Shokooh S, Khandelwal T, Shokooh F, Tastet J, Dai JJ. Intelligent load shedding.
shed. Due to the limited available computational time, the minimi- Need for fast and optimal solution. In: Proceedings of the IEEE PCIC Europe;
zation is performed with an heuristic approach, which also con- 2005. p. 1–10.
sider the priority levels associated to the loads; further details on [23] Shokooh F, Dai JJ, Shokooh S, Tastet J, Castro H, Khandelwal T, et al. An
intelligent load shedding (ILS) system application in a large industrial facility.
these aspects can be found in [33]. In: Proceedings of the industry applications conference, vol. 1; 2005. p. 417–
25.
Acknowledgment [24] Mostafa MA, El-Hawary ME, Mbamalu GAN, Mansour MM, El-Nagal KM, El-
Arabaty AM. Effects of prioritizing demand on optimal load shedding policy.
Electr Power Energy Syst 1996;18(7):415–24.
The authors are indebted to A. Miotti and E. Brambilla, Siemens [25] Schiefen M, Schauerman G, Adamiak M, Cable B. Design & implementation of
Italia, for posing the problem and for many helpful discussions. an industrial facility islanding and load shed system. In: 61st Annual
conference for protective relay engineers; 2008. p. 573–83.
[26] Jethwa K, Bansal RK, Date N, Vaishnav R. Comprehensive load-shedding
References system. IEEE Trans Ind Appl 2010;46(2):740–9.
[27] Tzeng YM, Chen CS, Hsu CT, Chen JK, Chang WH. Design of load shedding
[1] Begovic M, Novosel D, Karlsson D, Henville C, Michel G. Wide-area protection scheme for a cogeneration facility: a case study. Electr Power Energy Syst
and emergency control. Proc IEEE 2005;93(5):876–91. 1996;18(7).
[2] Mechenbier J, Ellis A, Curtner R, Ranade S. Design of an under voltage load [28] Qiu B, Liu Y, Chan EK, Cao LL. LAN-based load shedding controller (LSC) for the
shedding scheme. In: Proceedings of the IEEE PES general meeting, vol. 2; oil refinery facility. In: Proceedings of the IEEE power engineering society
2004. p. 1611–8. winter meeting, vol. 2; 2001. p. 835–40.
[3] Glavic M, Van Cutsem T. Some reflections on model predictive control of [29] Zhao Q, Chen C. Study on a system frequency response model for a large
transmission voltages. In: Proceedings of the IEEE 38th North American power industrial area load shedding. Electr Power Energy Syst 2005;27(3):233–7.
symposium, NAPS; 2006. p. 625–32. [30] Mihirig A, Nguyen H, Allen AJ. On-line fast load shedding to maintain system
[4] Larsson M, Karlsson D. Coordinated system protection scheme against voltage stability and operation for isolated oil field power system. In: Proceedings of
collapse using heuristic search and predictive control. IEEE Trans Power Syst the IEEE petroleum and chemical industry conference; 2006. p. 1–7.
2003;18(3):1001–6. [31] Machowski J, Bialek J, Bumby J. Power system dynamics: stability and
[5] Van Cutsem T, Moors C, Lefebvre D. Design of load shedding schemes against control. Wiley; 2008.
voltage instability using combinatorial optimization. In: Proceedings of the [32] Chuvychin VN, Gurov NS, Venkata SS, Brown RE. An adaptive approach to load
IEEE PES winter meeting, vol. 2; 2002. p. 848–53. shedding and spinning reserve control during underfrequency conditions. IEEE
[6] Glavic M, Van Cutsem T. Adaptive wide-area closed-loop undervoltage load Trans Power Syst 1996;11(4):1805–10.
shedding using synchronized measurements. In: Proceedings of the IEEE PES [33] Giroletti M. Metodi di Load Shedding nei Sistemi di Potenza Industriali. Master
general meeting; 2010. p. 1–8. Thesis, Politecnico di Milano; 2011 [in Italian].
[7] Otomega B, Van Cutsem T. Undervoltage load shedding using distributed
controllers. IEEE Trans Power Syst 2007;22(4):1898–907.

You might also like