Introduction
Thermostatic expansion valves regulate the Therefore the valves are especially suitable for
injection of refrigerant liquid into evaporators. liquid injection in ”dry“ evaporators where the
Injection is controlled by the refrigerant superheat at the evaporator outlet is proportional
superheat. to the evaporator load.
MOP-points
Refrigerant Range N Range NM Range NL Range B
-40 ® +10°C -40 ® -5°C -40 ® -15°C -60 ® -25°C
MOP-point in evaporating temperature te and evaporating pressure pe
+15°C/+60°F 0°C/+32°F -10°C/+15°F -20°C/-4°F
R 22 100 psig/6.9 bar 60 psig/4.0 bar 35 psig/3.5 bar 20 psig/1.5 bar
R 134a 55 psig/5 bar 30 psig/3.1 bar 15 psig/2.1 bar
R 404A/R 507 120 psig/9.3 bar 75 psig/6.2 bar 50 psig/4.4 bar 30 psig/3.1 bar
R 407C 95 psig/6.6 bar 50 psig/3.6 15 psig/1.1 bar
Example
Static superheat SS = 5 K
Opening superheat OS = 6 K
Total superheat SH = 5 + 6 = 11 K
A. The evaporating pressure pe is subtracted from Static pressure drop, Dp3 bar
Determination the condensing pressure pc. Values pe and pc Refrig- at height difference h
of pressure drop are determined by the values given for te and tc. erant between evaporator and receiver
These can be obtained from a refrigerant table 6m 12 m 18 m 24 m 30 m
or a Danfoss calculator.
pc - pe = 13.9 bar - 3.6 bar R 22 0.7 1.4 2.1 2.8 3.5
pc - pe = 10.3 bar R 134a 0.7 1.4 2.1 2.8 3.6
R 404A 0.6 1.3 1.9 2.5 3.2
To obtain the actual pressure drop across the
expansion valve, not only is it necessary to R 507 0.6 1.3 1.9 2.5 3.2
subtract pe from pc, but a series of other pres-
sure drops must also be subtracted
4. Pressure drop Dp4 in the liquid distributor:
1. Pressure drop Dp1 in the liquid line. Dp4 » 0.5 bar
For example: Dp1 » 0.1 bar
5. Pressure drop Dp5 in the distributor tubes:
2. The assumed pressure drop, p2, in filter drier, Dp5 » 0.5 bar
sight glass, manual shut-off valve and pipe
bends: Total pressure drop across expansion valve:
Dp2 » 0.2 bar. Dp = (pc - pe) - (Dp1 + Dp2 + Dp3 + Dp4 + Dp5)
Dp » 10.3 - (0.1 + 0.2 + 0.7 + 0.5 + 0.5)
3. Pressure drop Dp3 in the vertical liquid line Dp » 8.3 bar
(because of the height difference, h = 6 m).
This is given in the table below:
Dp3 = 0.7 bar
B.
Determination of capacity Qe
Orifice Pressure drop across valve Dp bar
Valve type no.
2 4 6 8 10 12 14 16
From the table for te = –10°C and Dp = 8.3 bar The table indicates that a TEX 2-2.3 with orifice
by interpolation: 04 should be used.
The table capacities are based on 4 K
Qe = 9.5 + 8.3 - 8 (10.1 - 9.5) subcooling ahead of valve.
10 - 8
Generally, the maximum capacity of a valve is
Qe = 9.6 kW approx. 20% higher than the figure given in the
table.
Thermostatic element, without orifice, filter cone, nuts, with sensor band
Connection Code no.
Pressure
Refri- Valve Capillary Inlet
equaliz- Range N Range NM Range NL Range B
gerant type tube ´
ation 1) –40 to +10°C –40 to –5°C –40 to –15°C –60 to –25°C
Outlet
m in. ´ in. mm ´ mm Without MOP With MOP With MOP With MOP Without MOP With MOP
TX 2 Int. 1.5 3¤8 ´ 1 ¤2 10 ´ 12 068Z3206 068Z3208 068Z3224 068Z3226 068Z3207 068Z3228
R 22
TEX 2 Ext. 1.5 3¤8 ´ 1 ¤2 10 ´ 12 068Z3209 068Z3211 068Z3225 068Z3227 068Z3210 068Z3229
TN 2 Int. 1.5 3¤8 ´ 1 ¤2 10 ´ 12 068Z3346 068Z3347 068Z3393 068Z3369
R 134a
TEN 2 Ext. 1.5 3¤8 ´ 1 ¤2 10 ´ 12 068Z3348 068Z3349 068Z3392 068Z3370
TS 2 Int. 1.5 3¤8 ´ 1 ¤2 10 ´ 12 068Z3400 068Z3402 068Z3406 068Z3408 068Z3401 068Z3410
R 404A/
R 507 TES 2 Ext. 1.5 3¤8 ´ 1 ¤2 10 ´ 12 068Z3403 068Z3405 068Z3407 068Z3409 068Z3404 068Z3411
1
) Valves with inch connections have 1¤4 inch pressure equalization.
Range B: – 60 to – 25°C
0X 0.15 0.11 0.5 0.38 068-2002
00 0.2 0.21 0.7 0.7 068-2003
01 0.3 0.45 1.0 1.6 068-2010
02 0.6 0.6 2.1 2.1 068-2015
03 0.8 1.0 2.8 3.5 068-2006
04 1.2 1.4 4.2 4.9 068-2007
05 1.5 1.7 5.2 6.0 068-2008
06 2.0 1.9 7.0 6.6 068-2009
Flare connections Connection for copper tubing Reducer for copper tubing
Code no.
with outside diameter with outside diameter
in. mm in. mm
1¤4 6 011L1101
3¤ 8 10 011L1135
1¤2 12 011L1103
1¤4 6 011L1107
Example
A TE 2 thermostatic expansion valve consists of When ordering one thermostatic expansion
two elements + flare nuts if required: valve, TEX 2 with orifice 01, five code numbers are
- 1 thermostatic element required:
- 1 orifice assembly and flare nuts - 1-off thermostatic element, 068Z3209
- 1-off orifice assembly 01, 068-2010
- 1-off 3¤8 in. flare nut, 011L1135
- 1-off 1¤2 in. flare nut, 011L1103
- 1-off 1¤4 in. flare nut, 011L1101
Thermostatic element, without orifice, filter cone, nuts, with sensor band
Connection Code no.
Pressure Capillary
Refrigerant Valve equaliz- tube Inlet Outlet Range N Range NL Range B
type ation 1) Flare ODF solder -40 to +10°C -40 to -15°C -60 to -25°C
m in. in. mm Without MOP With MOP With MOP Without MOP With MOP
TX 2 Int. 1.5 3¤ 8 1¤2 068Z3281 068Z3287 068Z3357 068Z3319
TX 2 Int. 1.5 3¤ 8 12 068Z3302 068Z3308 068Z3366 068Z3361 068Z3276
R 22 TEX 2 Ext. 1.5 3¤ 8 1¤2 068Z3284 068Z3290 068Z3359 068Z3320
TEX 2 Ext. 1.5 3¤ 8 12 068Z3305 068Z3311 068Z3367 068Z3363 068Z3277
TN 2 Int. 1.5 3¤ 8 1¤2 068Z3383 068Z3387
TN 2 Int. 1.5 3¤ 8 12 068Z3384 068Z3388
R 134a TEN 2 Ext. 1.5 3¤ 8 1¤2 068Z3385 068Z3389
TEN 2 Ext. 1.5 3¤ 8 12 068Z3386 068Z3390
TS 2 Int. 1.5 3¤ 8 1¤2 068Z3414 068Z3416 068Z3429 068Z3418 068Z3420
TS 2 Int. 1.5 3¤ 8 12 068Z3435 068Z3423 068Z3436 068Z3425 068Z3427
R 404A/
TES 2 Ext. 1.5 3¤ 8 1¤2 068Z3415 068Z3417 068Z3430 068Z3419 068Z3421
R 507 3¤ 8
TES 2 Ext. 1.5 12 068Z3422 068Z3424 068Z3437 068Z3426 068Z3428
1
) Valves with inch connections have 1¤4 inch pressure equalization. Valves with mm connections have 6 mm pressure equalization.
Range B: – 60 to – 25°C
0X 0.15 0.11 0.5 0.38 068-2002
00 0.2 0.21 0.7 0.7 068-2003
01 0.3 0.45 1.0 1.6 068-2010
02 0.6 0.6 2.1 2.1 068-2015
03 0.8 1.0 2.8 3.5 068-2006
04 1.2 1.4 4.2 4.9 068-2007
05 1.5 1.7 5.2 6.0 068-2008
06 2.0 1.9 7.0 6.6 068-2009
Solder adaptor The adaptor is for use with thermostatic The standard orifice in T 2 and TE 2 can be
expansion valves T 2 and TE 2 with flare ´ solder used with the solder adaptor when the
connections. When the adaptor is fitted correctly expansion valve filter is replaced with a
it meets the sealing requirements of DIN 8964. separately ordered filter.
The adaptor offers the following advantages: Only in this way can the sealing requirements of
· The orifice assembly can be replaced. DIN 8964 be fulfilled.
· The filter can be cleaned or replaced. A solder adaptor is also available for filter driers.
Solder adaptor without orifice assembly and Orifice assembly with filter for solder adaptor
filter
Orifice no. Code no.
Connection ODF solder Code no.
0X 068-2089
1¤4 in. 068-2062 00 068-2090
6 mm 068-2063 01 068-2091
3¤8 in. 068-2060 02 068-2092
10 mm 068-2061 03 068-2093
Filter for solder adaptor 04 068-2094
05 068-2095
Description Code no.
06 068-2096
Filter excl. orifice assembly 068-0015
Flare connections
See previous page.
Ordering
(continued) Thermostatic element R 22
Code no.
Valve Pressure Capillary
type equalization tube Range N Range NM Range NL Range B
–40 to +10°C –40 to –5°C –40 to –15°C –60 to –25°C
1¤4 in. / 6 mm m Without MOP With MOP With MOP With MOP Without MOP With MOP
TEX 5 Ext. 1) 3 067B3250 067B3267 067B3249 067B3253 067B3263 067B3251
TEX 12 Ext. 2) 3 067B3210 067B3227 067B3207 067B3213 067B3211
TEX 12 Ext. 2) 5 067B3209 067B3212
TEX 20 Ext. 2) 3 067B3274 067B3286 067B3273 067B3275 067B3276
TEX 20 Ext. 2) 5 067B3290 067B3287
TEX 55 Ext. 2) 3 067G3205 067G3220 067G3206 067G3207
TEX 55 Ext. 2) 5 067G3209 067G3217
1
) Pressure equalization with solder connector can be supplied on contacting Danfoss.
2
) Available as accessory: solder adapter for TE 12, TE 20 and TE 55. Code no. 068B0170.
Orifice assembly
Valve type Rated capacity Rated capacity Orifice no. Code no.
Range N: Range B:
–40 to 10°C –60/55 to –25°C
kW kW
TEX 5-3 19.7 11.9 01 067B2089
TEX 5-4.5 26.9 16.7 02 067B2090
TEX 5-7.5 38.8 24.8 03 067B2091
TEX 5-12 55.3 35.4 04 067B2092
TEX 12-4.5 26.8 17.2 01 067B2005
TEX 12-7.5 43.4 28.2 02 067B2006
TEX 12-12 64.0 41.4 03 067B2007
TEX 12-18 84.4 55.9 04 067B2008
TEX 20-30 108.0 70.0 01 067B2172
TEX 55-50 239.0 148.0 01 067G2005
TEX 55-85 356.0 228.0 02 067G2006
The rated capacity is based on:
Evaporating temperature te = +5°C for range N and te = –30°C for range B
Condensing temperature tc = +32°C
Refrigerant temperature ahead of valve tl = +28°C
Valve body
Connection
Code no.
Inlet ´ Outlet
Type Orifice no.
Flare Solder Solder Solder
in. mm angleway angleway straightway flanges
01 - 03 1¤2 ´ 5¤8 068B4013 068B4009 068B4007
TE 5 03 1¤2 ´ 7¤8 068B4010 068B4008
04 5¤8 ´ 7¤8 068B4011
01- 03 12 ´ 16 068B4013 068B4004 068B4002
TE 5 03 12 ´ 22 068B4005 068B4003
04 16 ´ 22 068B4012
01 - 02 5¤8 ´ 7¤8 068B4022 1) 068B4020 1) 068B4025 1)
TE 12 03 - 04 7¤8 ´1 068B4026 1)
03 - 04 7¤8 ´ 11¤8 068B4023 2) 068B4021 2)
01 - 02 16 ´ 22 068B4018 1) 068B4027 1)
TE 12 03 - 04 22 ´ 25 068B4015 1)
03 - 04 22 ´ 28 068B4017 2) 068B4016 2)
01 7¤8 ´ 11¤8 068B4023 2) 068B4021 2)
TE 20
01 22 ´ 28 068B4017 2) 068B4016 2)
01- 02 11¤8 ´ 13¤8 068G4004 3) 068G4003 3)
TE 55
01- 02 28 ´ 35 068G4002 3) 068G4001 3)
1
) ODF ´ ODF
2
) ODF ´ ODM
3
) ODM ´ ODM
ODF = Internal diameter
ODM = External diameter
Ordering
(continued) Thermostatic element R 134a
Code no.
Valve Pressure Capillary
type equalization tube Range N Range NM
–40 to +10°C –40 to –5°C
1¤4 in. / 6 mm m Without MOP With MOP With MOP
TEN 5 Ext. 1) 3 067B3297 067B3298 067B3360
TEN 12 Ext. 2) 3 067B3232 067B3233
TEN 12 Ext. 2) 5 067B3363
TEN 20 Ext. 2) 3 067B3292 067B3293
TEN 20 Ext. 2) 5 067B3370
TEN 55 Ext. 2) 3 067G3222 067G3223
TEN 55 Ext. 2) 5 067G3230
1
)Pressure equalization with solder connector can be supplied on contacting Danfoss.
2
) Available as accessory: solder adapter for TE 12, TE 20 and TE 55. Code no. 068B0170.
Orifice assembly
Valve type Rated capacity Orifice no. Code no.
kW
TEN 5-3.7 12.9 01 067B2089
TEN 5-5.4 19.1 02 067B2090
TEN 5-8.3 29.1 03 067B2091
TEN 5-11.2 39.6 04 067B2092
TEN 12-4.7 16.7 01 067B2005
TEN 12-7.7 27.2 02 067B2006
TEN 12-11.4 40.0 03 067B2007
TEN 12-15 53.0 04 067B2008
TEN 20-18 65.0 01 067B2170
TEN 55-41 145.0 01 067G2001
TEN 55-62 220.0 02 067G2002
The rated capacity is based on:
Evaporating temperature te = +5°C
Condensing temperature tc = +32°C
Refrigerant temperature ahead of valve tl = +28°C
Valve body
Connection
Code no.
Inlet ´ Outlet
Type Orifice no.
Flare Solder Solder Solder
in. mm angleway angleway straightway flanges
01 - 03 1¤2 ´ 5¤8 068B4013 068B4009 068B4007
TE 5 03 1¤2 ´ 7¤8 068B4010 068B4008
04 5¤8 ´ 7¤8 068B4011
01- 03 12 ´ 16 068B4013 068B4004 068B4002
TE 5 03 12 ´ 22 068B4005 068B4003
04 16 ´ 22 068B4012
01 - 02 5¤8´ 7¤8 068B4022 1) 068B4020 1) 068B4025 1)
TE 12 03 - 04 7¤8 ´1 068B4026 1)
03 - 04 7¤8 ´ 11¤8 068B4023 2) 068B4021 2)
01 - 02 16 ´ 22 068B4018 1) 068B4027 1)
TE 12 03 - 04 22 ´ 25 068B4015 1)
03 - 04 22 ´ 28 068B4017 2) 068B4016 2)
01 7¤8 ´ 11¤8 068B4023 2) 068B4021 2)
TE 20
01 22 ´ 28 068B4017 2) 068B4016 2)
01- 02 11¤8 ´ 13¤8 068G4004 3) 068G4003 3)
TE 55
01- 02 28 ´ 35 068G4002 3) 068G4001 3)
1
) ODF ´ ODF
2
) ODF ´ ODM
3
) ODM ´ ODM
ODF = Internal diameter
ODM = External diameter
Ordering
(continued) Thermostatic element R 404A/R 507
Code no.
Valve Pressure Capillary
type equalization tube Range N Range NM Range NL Range B
–40 to +10°C –40 to –5°C –40 to –15°C –60 to –25°C
1¤4 in. / 6 mm m Without MOP With MOP With MOP With MOP Without MOP With MOP
TES 5 Ext. 1) 3 067B3342 067B3357 067B3358 067B3344 067B3343
TES 12 Ext. 2) 3 067B3347 067B3345 067B3348 067B3349
TES 12 Ext. 2) 5 067B3346 067B3350
TES 20 Ext. 2) 3 067B3352 067B3351 067B3353 067B3354
TES 20 Ext. 2) 5 067B3356 067B3355
TES 55 Ext. 2) 3 067G3302 067G3303 067G3304 067G3305
TES 55 Ext. 2) 5 067G3301 067G3306
1)Pressure equalization with solder connector can be supplied on contacting Danfoss.
2
) Available as accessory: solder adapter for TE 12, TE 20 and TE 55. Code no. 068B0170.
Orifice assembly
Valve type Rated capacity Rated capacity Orifice no. Code no.
range N: range B:
–40 to 10°C –60/55 to –25°C
kW kW
TES 5-3.7 13.0 8.0 01 067B2089
TES 5-5.0 17.6 11.2 02 067B2090
TES 5-7.2 25.3 16.6 03 067B2091
TES 5-10.3 36.2 23.7 04 067B2092
TES12-4.2 14.8 11.6 01 067B2005
TES 12-6.8 23.9 18.9 02 067B2006
TES 12-10.0 35.2 27.7 03 067B2007
TES 12-13.4 47.1 37.5 04 067B2008
TES 20-16.5 59.0 41.0 01 067B2175
TES 55-37.0 130.0 95.0 01 067G2011
TES 55-56.0 197.0 144.0 02 067G2012
The rated capacity is based on:
Evaporating temperature te = +5°C for range N and te = –30°C for range B
Condensing temperature tc = +32°C
Refrigerant temperature ahead of valve tl = +28°C
Valve body
Connection
Code no.
Inlet ´ Outlet
Type Orifice no.
Flare Solder Solder Solder
in. mm angleway angleway straightway flanges
01 - 03 1¤2 ´ 5¤8 068B4013 068B4009 068B4007
TE 5 03 1¤2 ´ 7¤8 068B4010 068B4008
04 5¤8 ´ 7¤8 068B4011
01- 03 12 ´ 16 068B4013 068B4004 068B4002
TE 5 03 12 ´ 22 068B4005 068B4003
04 16 ´ 22 068B4012
01 - 02 5¤8´ 7¤8 068B4022 1) 068B4020 1) 068B4025 1)
TE 12 03 - 04 7¤8 ´1 068B4026 1)
03 - 04 7¤8 ´ 11¤8 068B4023 2) 068B4021 2)
01 - 02 16 ´ 22 068B4018 1) 068B4027 1)
TE 12 03 - 04 22 ´ 25 068B4015 1)
03 - 04 22 ´ 28 068B4017 2) 068B4016 2)
01 7¤8 ´ 11¤8 068B4023 2) 068B4021 2)
TE 20
01 22 ´ 28 068B4017 2) 068B4016 2)
01- 02 11¤8 ´ 13¤8 068G4004 3) 068G4003 3)
TE 55
01- 02 28 ´ 35 068G4002 3) 068G4001 3)
ODF ´ ODF
1)
ODF ´ ODM
2)
ODM ´ ODM
3)
ODF = Internal diameter
ODM = External diameter
The stated correction factors are to be multiplied In some cases it might therefore be necessary
with the valve capacities for R 12/ R 134A and to change to a lower valve capacity, either by
R 502/ R 404A respectively. changing the orifice or by replacing the com-
All service refrigerants give higher valve capacity plete valve with a smaller valve.
than their basic refrigerants.
Ordering (continued)
Components
PHT 85
Solder or weld flanges
4. Flange set
Weld flanges Solder flanges
Valve flange Flange type
in. Code no. in. Code no. mm Code no.
PHT 85 2 1 027N1025
PHT 85 2 11¤8 027L1029 28 027L1028
PHT 85 2 1 3 ¤8 027L1035 35 027L1035
PHT 125 3A 11¤4 027N1032
PHT 300 4A 11¤2 027N1040
PHT 300 4A 2 027N1050
Correction The evaporator capacities used must be dividing the required evaporator capacity by the
for subcooling Dtsub corrected if subcooling deviates from 4 K. correction factor below. Selections can then be
The corrected capacity can be obtained by made from the tables above.
Dtu 4K 10 K 15 K 20 K 25 K 30 K 35 K 40 K 45 K 50 K
Note:
Insufficient subcooling can produce Correction
1.00 1.06 1.11 1.15 1.2 1.25 1.3 1.35 1.39 1.44
flash gas. factor
Example
Refrigerant = R 22 Correction factor from table = 1.06
Evaporator capacity Qe = 5 kW Corrected capacity = 5 ¸ 1.06 = 4.72 kW
Subcooling = 10 K
Correction for subcooling The evaporator capacities used must be dividing the required evaporator capacity by the
Dtsub corrected if subcooling deviates from 4 K. correction factor below. Selections can then be
The corrected capacity can be obtained by made from the tables above.
Dtu 4K 10 K 15 K 20 K 25 K 30 K 35 K 40 K 45 K 50 K
Note:
Correction
Insufficient subcooling can produce 1.00 1.06 1.11 1.15 1.2 1.25 1.3 1.35 1.39 1.44
factor
flash gas.
Example
Refrigerant = R 22 Correction factor from table = 1.06
Evaporator capacity Qe = 5 kW Corrected capacity = 5 ¸ 1.06 = 4.72 kW
Subcooling = 10 K
Correction The evaporator capacities used must be the required evaporator capacity by the
for subcooling Dtsub corrected if subcooling deviates from 4 K. The correction factor below. Selections can then be
corrected capacity can be obtained by dividing made from the tables above.
Dtu 4K 10 K 15 K 20 K 25 K 30 K 35 K 40 K 45 K 50 K
Note:
Insufficient subcooling can produce Correction
1.00 1.06 1.11 1.15 1.2 1.25 1.3 1.35 1.39 1.44
flash gas. factor
Correction for subcooling The evaporator capacities used must be corrected required evaporator capacity by the correction
Dtsub if subcooling deviates from 4 K. The corrected factor below. Selections can then be made from
capacity can be obtained by dividing the the tables above.
Dtu 4K 10 K 15 K 20 K 25 K 30 K 35 K 40 K 45 K 50 K
Note:
Insufficient subcooling can produce Correction
1.00 1.08 1.13 1.19 1.25 1.31 1.37 1.42 1.48 1.54
flash gas. factor
Capacity in kW
(continued) Range N: –40°C to +10°C R 134a
Orifice Pressure drop across valve Dp bar Pressure drop across valve Dp bar
Valve type
no.
2 4 6 8 10 2 4 6 8 10
Correction for subcooling The evaporator capacities used must be the required evaporator capacity by the
Dtsub corrected if subcooling deviates from 4 K. The correction factor below. Selections can then be
corrected capacity can be obtained by dividing made from the tables above.
Dtu 4K 10 K 15 K 20 K 25 K 30 K 35 K 40 K 45 K 50 K
Note:
Insufficient subcooling can produce Correction
1.00 1.08 1.13 1.19 1.25 1.31 1.37 1.42 1.48 1.54
flash gas. factor
Correction The evaporator capacities used must be corrected required evaporator capacity by the correction
for subcooling Dtsub if subcooling deviates from 4 K. The corrected factor below. Selections can then be made from
capacity can be obtained by dividing the the tables above.
Dtu 4K 10 K 15 K 20 K 25 K 30 K 35 K 40 K 45 K 50 K
Note:
Insufficient subcooling can produce Correction
1.00 1.08 1.13 1.19 1.25 1.31 1.37 1.42 1.48 1.54
flash gas. factor
Correction The evaporator capacities used must be the required evaporator capacity by the
for subcooling Dtsub corrected if subcooling deviates from 4 K. The correction factor next page. Selections can then
corrected capacity can be obtained by dividing be made from the tables above.
Correction The evaporator capacities used must be the required evaporator capacity by the
for subcooling Dtsub corrected if subcooling deviates from 4 K. The correction factor below. Selections can then be
corrected capacity can be obtained by dividing made from the tables above.
Note: Dtu 4K 10 K 15 K 20 K 25 K 30 K 35 K 40 K 45 K 50 K
Insufficient subcooling can produce
flash gas. Correction
1.00 1.1 1.2 1.29 1.37 1.46 1.54 1.63 1.7 1.78
factor
T2
1. Thermostatic element
(diaphragm)
2. Interchangeable orifice
assembly
3. Valve body
4. Superheat setting spindle
(see instructions)
5. Ext. pressure equalizing TE 5
connection with 1¤4 in./6 mm flare
Design
Function
(Continued)
TE 12 / TE 20
TE 55
1. Thermostatic element
(diaphragm)
2. Interchangeable orifice assembly
3. Valve body
4. Superheat setting spindle
(see instructions)
5. Ext. pressure equalizing
connection with 1¤4 in./6 mm
flare nut
6. Pilot connection
7. Insert in main valve
8. Main spring PHT 85
9. Bottom plug
X = R 22
N = R 134a
S = R 404A/ R507
· On TE 20 and TE 55
the upper stamp (N/B 50/35 TR) indicates
the rated capacity in the two evaporating
temperature ranges N and B, and the
refrigerant.
(50/35 TR = 175 kW in range N and 123 kW in Orifice assembly marking
range B). for TE 20 and TE 55
The lower stamp (TEX 55) refers to the valve
type for which the assembly can be used.
Ædi
in. mm
1/ 6
4
3/ 10
8
TE 5
Inlet side L1
ÆD1 mm
1¤2 in./12 mm ODF 10
5¤8 in./16 mm ODF 10
Outlet side L1
ÆD2 mm
5¤8 in./16 mm ODF 12
7¤8 in./22 mm ODF 17
Bracket for TE 5
Type TE 12 and TE 20
Inlet side L1
ÆD 1 mm
5 ¤8 in./16 mm ODF 12
7 ¤8 in./22 mm ODF 17
Outlet side L1
ÆD 2 mm
TE 12 Weight
7 ¤8 in./22 mm ODF 17 Solder flanges, straightway Without filter: 2.3 kg
11¤8 in./28 mm ODF 25 With filter: 3.2 kg
Bracket
for TE 12 and TE 20
Type TE 55
Inlet side L1
ÆD1 mm
7¤8 in./22 mm ODF 17
11¤8 in./28 mm ODM 25
Outlet side L1
ÆD2 mm
11¤8 in./28 mm ODF 22 TE 55 Weight TE 55 Weight
Solder, straightway 1.7 kg Solder, straightway 1.6 kg
13¤8 in./35 mm ODM 27
PHT 85 Weight
Solder or weld flanges 4.5 kg