Professional Documents
Culture Documents
Protection For Safety Fundamental
Protection For Safety Fundamental
Fundamental Principles
2.1 PROTECTION FOR SAFETY FUNDAMENTAL
PRINCIPLES
Electrical installations pose a number of inherent risks, which may result in
damage or injury to property or its intended users, either in the form of persons
or livestock. Regulations set out a number of fundamental principles that are
intended to protect against these risks, and it is essential that anyone involved in
electrical installation work should understand these principles.
The fundamental principles to be applied to an electrical installation are
covered in Chapter 13 of the IEE Wiring Regulations.
IEE Chapter 13 effectively ‘sets the scene’ and covers the principles to be
followed to provide protection for the safety of those that might be affected. It
also defines the process to be followed from the design of the installation,
through to the selection of the equipment, its installation, verification and
testing, to ensure that the requirements of the standard have been met.
More detail is covered in Part 4 of the IEE Regulations. IEE Chapters 41–44
refer to different aspects of the topic and the application of the measures listed
in the Regulations.
The areas covered are:
Protection against electric shock,
Protection against thermal effects,
Protection against overcurrent, both overload and short circuit and
Protection against voltage disturbances and electromagnetic disturbances.
Note: To enable the reader to refer to the relevant parts of the IEE Wiring
Regulations more easily, references to relevant parts of the Regulations are
enclosed within square brackets as [IEE Regulation 131.2].
25
26 PART j I Design of Electrical Installation Systems
normal service and in the case of a fault. These are referred to in the IEE
Regulations as basic protection (formally referred to in the 16th edition as
‘protection against ‘‘direct contact’’’) and fault protection (formally referred to
as ‘protection against ‘‘indirect contact’’’).
A number of the protective measures listed apply to both basic and fault
protection, and others apply to one of these only.
Basic protection can be achieved by either preventing the current from
passing through a body or by limiting the value of the current to a non-
hazardous level.
Fault protection can be achieved by similar methods, but also by reducing
the time the body is exposed to the fault, and therefore aiming to reduce the
time to a non-hazardous level.
The protective measures available consist of:
Automatic disconnection of supply (ADS),
Double or reinforced insulation,
Electrical separation,
Extra-low voltage and
Additional protection.
place live parts out of arms reach. This is defined in diagrammatic form in
Fig. 417 of the IEE Regulations. These two methods may only be applied in
industrial-type situations in areas which are controlled or supervised by skilled
persons. An example would be the exposed conductors for supply to overhead
travelling cranes.
Fault protection [IEE Regulation 411.3]: The object is to provide an area in
which dangerous voltages are prevented by bonding all exposed and extraneous
conductive parts. In the event of an earth fault occurring outside the installation,
a person in the zone concerned is protected by the exposed and extraneous
conductive parts in it being electrically bonded together and so having
a common potential. The same is not true when a fault occurs within the
installation.
The practicalities of the bonding requirements, calculation of the sizes of
bonding and protective conductors, and their installation are dealt with in
Chapter 4 of this book.
For the protection to be effective it is necessary to ensure that automatic
disconnection takes place quickly to limit the duration that a potentially
hazardous fault condition could exist. This aspect is covered in IEE Regulation
411.3.2. This is to be provided in accordance with the type of system earthing
used, i.e. TN, TT or IT. Tables 41.2–41.4 of the IEE Regulations give the values
of earth fault loop impedance for the different conditions and types of
protection used to achieve the required Disconnection times.
For TN and IT systems, disconnection times between 0.04 and 0.8s are
tabled (depending upon the nominal voltage to earth) for final circuits not
exceeding 32A, which includes not only socket outlets but also lighting circuits
and others.
The disconnection may be extended to 5s (TN) or 1s (TT) for distribution
circuits and other circuits not covered by the final circuits are not covered by the
table (IEE Regulation 411.3.2.2 and Table 41.1).
Automatic disconnection is generally brought about by the use of the
overload protection device. To achieve a sufficiently rapid disconnection the
impedance of the earth loop must be low enough to give the disconnection time
required. An alternative way of doing this is by the use of an RCD. The use of
an RCD is referred to in the IEE Regulations as Additional Protection.
Additional protection [IEE Regulation 411.3.3]: This is intended to
provide protection in the case of the failure of the basic or fault protection and
to account for the carelessness of users. Regulation 411.3.3 makes reference to
this by introducing additional protection (RCDs) for socket outlets not
exceeding 20A, unless for example it is under the supervision of skilled or
instructed persons, or it is identified for connection to a particular item of
equipment.
Other methods that fall under ADS are the use of Functional Extra-Low
Voltage (FELV) [IEE Regulation 411.7] and reduced low voltage systems [IEE
Regulation 411.8].
28 PART j I Design of Electrical Installation Systems
equipment being carried out in such a way as not to inhibit its intended heat
dissipation and in accordance with the manufacturer’s recommendations.
Luminaires and lamps shall be adequately ventilated, and spaced away from
wood or other combustible materials and any potential arcs or sparks that may
be emitted in normal services shall be dealt with accordingly.
Fixed equipment containing flammable dielectric liquids exceeding 25L
should have provision for safely draining any spilt or surplus liquid, and should
be placed in a chamber of fire resisting construction if within a building,
adequately ventilated to the external atmosphere.
Fault current is that which arises due to a fault in the circuit, as with a conductor
which has become disconnected, or in some other way shorted to another,
causing a very low resistance fault.
The IEE Regulations deal with overcurrent in Chapter 43 and overload and
fault currents are in Sections 433 and 434, respectively. When considering
circuit design both aspects of overcurrent have to be taken into account, and it is
often possible to use the same device to protect against overload and short
circuit. Before doing so it is necessary to determine the design current of the
circuit and also to ascertain the prospective short-circuit current which is likely
to arise, this is dealt with in IEE Regulations Section 435.
It should also be noted that the neutral conductor shall be protected against
short circuits although if the Cross-Sectional Area (CSA) of the neutral
conductor is at least equivalent to that of the line conductors, then it is not
necessary to provide overcurrent detection and a disconnection device [IEE
Regulation 431.2.1] unless it is likely that the current in the neutral conductor
may exceed that of the line conductors.
from a drop in voltage, or loss and subsequent reinstatement of supply, and this
may need to be done in conjunction with the user of the installation. Suitable
protection may be provided by the use of ‘no-volt’ or ‘low-volt’ relays and the
IEE Regulations lay down certain conditions for their operation.
FIGURE 2.1 TN-S system. Separate neutral and protective conductors throughout system. The
protective conductor (PE) is the metallic covering of the cable supplying the installations or
a separate conductor. All exposed-conductive-parts of an installation are connected to this
protective conductor via the main earthing terminal of the installation (E).
FIGURE 2.2 TN-C-S (PME) system. Neutral and protective functions combined in a single
conductor in a part of the system. The usual form of a TN-C-S system is as shown, where the
supply is TN-C and the arrangement in the installation is TN-S. The system is also known as PME.
The supply system PEN conductor is earthed at two or more points and an earth electrode may be
necessary at or near a consumer’s installation. All exposed-conductive-parts of an installation are
connected to the PEN conductor via the main earthing terminal and the neutral terminal, these
terminals being linked together.
36 PART j I Design of Electrical Installation Systems
Earthing (PME) and then separate in the rest of the system (usually the
installation).
TN-C system: As above but the neutral and protective conductors are combined
throughout the system and all exposed-conductive-parts of an installation
are connected to the PEN conductor. This system is only used in distribution
networks as The Electricity Safety, Quality and Continuity Regulations
prohibit combination of neutral and protective conductors in a consumer’s
installation.
TT system (Fig. 2.3): One point of the source of energy directly earthed, but the
exposed-conductive-parts of the installation being connected to earth elec-
trodes independent of the earth electrodes of the power system.
IT system: A system where the neutral point of the source of energy is either
isolated from earth or connected to earth through a high impedance. The
exposed-conductive-parts of the installation are earthed via an earth rod.
The electricity companies are not allowed to use this system on the low
voltage distribution network to the public.
Three systems are in general use in the United Kingdom at the present time.
These are the TN-S, TN-C-S and TT types. The supply undertaking may well
provide an earthing terminal at the consumer’s installation, and this constitutes
part of a TN system. In some cases the protective conductor is combined with
the neutral conductor, and in this arrangement the system is the TN-C-S type,
the supply being known as PME.
Chapter j 2 Fundamental Principles 37
The majority of new systems coming into use are of the TN-C-S type, but
before use can be made of the PME type of supply, stringent conditions must be
met. Special requirements may apply and the supply undertaking must be
consulted. If no earth terminal can be provided by the supply undertaking or the
supply does not comply with the conditions for PME, then the TT system must
be used.
Another form of TN-C-S is a Protective Neutral Bonding (PNB) arrange-
ment (Fig. 2.4), this generally occurs where the source of supply is provided by
the consumer, the District Network Operator (DNO) providing an HV supply
only and the transformer being provided by the consumer. The consumer is
required to provide the earth, in which case the PNB arrangement allows more
flexibility as to where the consumer makes the connection to earth.
Each of the systems described demands different design characteristics and
the designer must take such factors into consideration when planning the
installation.
The IT system is rarely encountered and will not be found in the United
Kingdom as part of the public supply. However, it does have particular appli-
cation in some continuous process industries, where an involuntary shutdown
would cause difficulties with the process concerned. A private supply is
necessary and the Regulations require a means of monitoring system faults so
that they cannot be left undetected [IEE Regulation 411.6.3].
FIGURE 2.4 TN-C-S (PNB) system. Another form of TN-C-S is a Protective Neutral Bonding
(PNB) arrangement. This occurs where the District Network Operator (DNO) provides an HV
supply only, the transformer being provided by the consumer.
38 PART j I Design of Electrical Installation Systems
FIGURE 2.5 An isolating transformer supplying extra-low voltage socket outlets for use of
portable tools in an industrial installation.
the demand both daily and yearly and what future demand is to be expected.
There also needs to be a consideration for the control and similar requirements
as well as any special conditions such as harmonics.
Most of these considerations will need to be addressed when tackling the
requirements for the calculation of the maximum demand and diversity.
The Purpose and Intended Use of the Building and the Type
of Construction [IEE Regulation 31]
The construction and use of the building will inevitably dictate the type of
equipment to be installed, the impact of this is dealt with in Chapter 31 of the
IEE Wiring Regulations.
sets or a separate feeder from the supply network which are independent of
each other (such as supplies taken from different primary sub-stations).
When calculating any characteristics associated with these systems, both the
normal and stand-by sources need to be considered, and must have adequate capacity
and rating plus reliably changeover in the required time [IEE Regulation 313.2].
The specific requirements for stand-by systems are not covered by the IEE
Wiring Regulations, but their impact needs to be considered, which is dealt
with in Chapter 56 of the IEE Wiring Regulations, further guidance can be
obtained from the relevant standards and regulations for the particular system.
Consideration for the continuity of such systems is coved in Chapter 36 of
the Regulations.
Chapter 52 of the IEE Wiring Regulations covers the majority of the consid-
erations and requirements when determining the size of the conductors including
the minimum sizes to be utilised, which is listed Table 52.3 of the Regulations.
Starting currents,
Harmonic currents (e.g. from fluorescent lighting),
Mutual inductance,
d.c. feedback,
High-frequency oscillations,
Earth leakage currents and
Need for additional earth connections.
FIGURE 2.6 IEE Regulation 513 requires that every item of equipment be arranged so as to
facilitate its operation, inspection and maintenance. This switchboard is installed in a room
provided for the purpose, with access space both in front and behind the equipment. This situation
will allow access for proper maintenance (W.T. Parker Ltd).
44 PART j I Design of Electrical Installation Systems
TABLE 2.1 An Extract from IEE Table 53.2 Showing Some Switching and
Other Devices Permissible for the Purposes Shown. IEE Regulations
Section 537 gives additional information on this topic
required, and it is often the practice to provide stop buttons in suitable positions
which control a contactor.
Every installation must be provided with means of isolation but the
requirement for the other two categories is dependent upon the nature of the
equipment in use. In all but small installations it will be necessary to provide
more than one isolator so that the inconvenience in shutting down the whole
installation is avoided when work is required on one part of it. If insufficient
isolators are provided or if they are inconveniently placed then there may be
a temptation to work on equipment whilst it is still live (Table 2.1).