Start Sequence: MLN Block 405, Algeria Operator Training
Start Sequence: MLN Block 405, Algeria Operator Training
START SEQUENCE
CX501KB Series
TRAINING GAS TURBINES
VENT FAN
AC LUBE OIL PUMP
STARTER MOTOR FUEL GAS OPEN
4,000
2,000 < 2000 RPM STARTER RE ENGAGE
0
5 15 25 35 45 55 165 175 185 195205 215 225 235 245 255 265 275 285 295 305 315 325 335 345 355 365 375 385 395
TIME (SECONDS)
CX501KB Series
TRAINING GAS TURBINES
READY TO START
Select "Start"
CX501KB Series
TRAINING GAS TURBINES
Confirm "Start"
FAULT CONDITION
ENCLOSURE VENTILATION FAULT:
No ventilation flow detected within
1 minute of start initiate. Check
enclosure doors; Vent fan failed;
Enclosure filters blocked ( high
delta P also indicated) or differential
pressure transmitter fault.
CX501KB Series
TRAINING GAS TURBINES
Main Programmable
Engine Control Unit Logic Controller
(ECU) (PLC)
FAULT CONDITIONS
CX501KB Series
TRAINING GAS TURBINES
FAULT CONDITIONS
PRIMING OIL PUMP MOTOR NOT
RUNNING :Motor requested but not
running. No feed back signal from
contactor. Contactor failed to operate
either tripped, isolated or failed
FAILED TO PRIME : Lube oil pressure <
0.68 bar g with standby pump running
and start/ cranking initiated. Priming Oil
Pump failure check AC supply to pump;
Oil pressure regulator fault or system
leaks.
FAULT CONDITIONS
ELECTRO-HYDRAULIC START MOTOR NOT
RUNNING: Motor requested but not running.
No feed back signal from contactor. Contactor
failed to operate either tripped, isolated or
failed
STARTER FAILED TO ENGAGE: Turbine failed
to reach 500rpm/ 20 secs after
hydraulic solenoid energised Check for
leaks in Hydraulic start system; insufficient
pump output or blocked hydraulic filter
CX501KB Series
TRAINING GAS TURBINES
R.P.M.
16,000
14,000
12,000
10,000
8,000
6,000
4,000
2,000
0
FAULT CONDITIONS
TURBINE FAILED TO CRANK: Turbine failed to reach 1800rpm/ 30 secs after
hydraulic solenoid energised. Check for leaks in Hydraulic start system; insufficient pump
output or blocked hydraulic filter
CX501KB Series
TRAINING GAS TURBINES
R.P.M.
16,000
14,000
12,000
10,000
8,000
6,000 PURGE
4,000
2,000
0
FAULT CONDITIONS
FAILED TO PURGE: Turbine failed to achieve 3000rpm/ 20 secs after hydraulic start system
energised or if speed drops below 3000rpm whilst purge timer is operating. Hydraulic Start
system failure; Start motor isolated or local stop switch operated.
R.P.M.
16,000
14,000
12,000
10,000
8,000
6,000
DECEL
4,000
2,000
0
CX501KB Series
TRAINING GAS TURBINES
FAULT CONDITIONS
IGNITER CHECK FAULT: Either main PLC or back Up PLC not requesting for
igniters to be turned on during the start sequence (both plcs must request igniters on
within 1 second of the other). Check for PLC fault; PLC sequencing fault; speed scaling
of either plc incorrect, fault seen by only one PLC. Plc programming fault.
GAS MANIFOLD/ P2 DP HIGH: Gas manifold pressure 0.6 bar > compressor delivery
pressure with Turbine Outlet Temperature < 180°C. Check gas regulator; or gas pressure
outside limits. Check setting of ECU gas ratio.
TURBINE FAILED TO LIGHT: CT temp. < 316°C or TOT <180°C 3seconds (10secs liquid
fuel) after fuel switched on and igniter energised. Check for igniter fault; - Insufficient
fuel :Fuel supply fault; gas-regulator or valve fault.; Compressor bleed valve position.
TURBINE OVER TEMP STARTING: CT temp. >871°C at turbine speed >13000 rpm ECU
fault (incorrect regulation by engine governor) FMV or fuel supply fault, check engine.
TURBINE STAGNATION: Turbine acceleration < 40rpm/sec speed<13000rpm.-
insufficient fuel. Check: Insufficient fuel :Gas regulator; Hydraulic start system;
Compressor bleed valve position
CX501KB Series
TRAINING GAS TURBINES
R.P.M.
16,000
14,000
12,000
10,000 ACCEL
8,000
6,000
4,000
2,000
0
CX501KB Series
TRAINING GAS TURBINES
A V
EXCITATION EXCITATION
CURRENT VOLTAGE
FAULT CONDITIONS
OIL COOLER FAN NOT RUNNING (ALARM): Motor requested but not running. No feed back signal from contactor.
Contactor failed to operate either tripped, isolated or failed
CX501KB Series
TRAINING GAS TURBINES
I I
Hz + - V
II
II
II I
I
I
V
Hz + -
II II
II I
CX501KB Series
TRAINING GAS TURBINES
+ -
II I
FAULT CONDITIONS
SYNCHROSCOPE
G
FAILED TO AUTOSYNCHRONISE (ALARM): Switch the auto synch off and then on again. If it fails a
second time set to Manual and synchronise using the volts and frequency raise/lower switches and
breaker close. If still not working switchgear problem.
7
6
5
POWER kW
4
3
2
1
0
TIME SEC