RENDERING VICINITY MAP

VOLKMANN
A R C H I T E C T U R E
1601 North Main, Suite 202
Walnut Creek, CA 94596
925. 478. 2998 (office)
680 ContactUs@volmannarchitecture.com
www.volkmannarchitecture.com

Project Title:

Cobble Lane
RESIDENCES

2155 Overlook Drive


Walnut Creek CA

6 5 CN
94596

EL
Sheet Title:

ABBREVIATIONS PROJECT DATA DRAWING INDEX

Revisions:

CAL GREEN MANDATORY FEATURES CHECKLIST No. By Date

CalGreen 2013 RESIDENTIAL MANDATORY MEASURES CHECKLIST PROJECT DESCRIPTION GENERAL NOTES
SECTION A4.602 RESIDENTIAL OCCUPANCIES APPLICATION CHECKLIST

VERIFICATIONS ENFORCING AGENCY VERIFICATIONS ENFORCING AGENCY


TO SPECIFY VERIFICATION METHOD TO SPECIFY VERIFICATION METHOD
APPLICANT APPLICANT
FEATURE OR MEASUREMENT FEATURE OR MEASUREMENT
MANDATORY ENFORCING INSTALLER OR THIRD MANDATORY ENFORCING INSTALLER OR THIRD
MEASURES AGENCY DESIGNER PARTY MEASURES AGENCY DESIGNER PARTY

PLANNING AND DESIGN ALL ALL ALL PLANNING AND DESIGN ALL ALL ALL
SITE DEVELOPMENT ENVIRONMENTAL QUALITY (POLLUTANT CONTROL)
4.106.2 A PLAN IS DEVELOPED AND IMPLEMENTED TO MANAGE STORM WATER 4.504.1 DUCT OPENINGS AND OTHER RELATED AIR DISTRIBUTION COMPONENT OPENINGS
DRAINAGE DURING CONSTRUCTION
4.106.3 CONSTRUCTION PLANS SHALL INDICATE HOW SITE GRADING OR A DRAINAGE SYSTEM
SHALL BE COVERED DURING CONSTRUCTION.
PROJECT ROSTER
4.504.2.1 ADHESIVES, SEALANTS AND CAULKS SHALL BE COMPLIANT WITH VOC AND
WILL MANAGE ALL SURFACE WATER FLOWS TO KEEP WATER FROM ENTERING
OTHER TOXIC COMPOUND LIMITS.
BUILDINGS.
4.504.2.2 PAINTS, STAINS AND OTHER COATINGS SHALL BE COMPLIANT WITH VOC LIMITS.
ENERGY EFFICIENCY
4.504.2.3 AEROSOL PAINTS AND COATINGS SHALL BE COMPLIANT WITH PRODUCT WEIGHTED
GENERAL MIR LIMITS FOR ROC AND OTHER TOXIC COMPOUNDS.
4.201.1 BUILDING MEETS OR EXCEEDS THE REQUIREMENTS OF THE CALIFORNIA BUILDING 4.504.2.4 DOCUMENTATION SHALL BE PROVIDED TO VERIFY THAT COMPLIANT VOC LIMIT FINISH
ENERGY EFFICIENCY STANDARDS. 07/01/2014
MATERIALS HAVE BEEN USED.
WATER EFFICIENCY AND CONSERVATION (INDOOR WATER USE) 4.504.3 CARPET AND CARPET SYSTEMS SHALL BE COMPLIANT WITH VOC LIMITS.

4.303.1 PLUMBING FIXTURES (WATER CLOSETS AND URINALS) AND FITTINGS (FAUCETS AND 4.504.4 80 PERCENT OF FLOOR AREA RECEIVING RESILIENT FLOORING SHALL COMPLY WITH
SHOWERHEADS) INSTALLED IN RESIDENTIAL BUILDINGS SHALL COMPLY WITH THE THE VOC-EMISSION LIMITS DEFINED IN THE COLLABORATIVE FOR HIGH PERFORMANCE
PRESCRIPTIVE REQUIREMENTS OF SECTIONS 4.303.1.1 THROUGH 4.303.1.4.4. SCHOOLS (CHAPS) HIGH PERFORMANCE DATABASE OR BE CERTIFIED UNDER THE
RESILIENT FLOOR COVERING INSTITUTE (FOCI) FLOOR SCORE PROGRAM; OR MEET
4.303.2 PLUMBING FIXTURES AND FITTINGS REQUIRED IN SECTION 4.303.1 SHALL BE INSTALLED
CALIFORNIA DEPT. OF PUBLIC HEALTH. "STANDARD METHOD FOR THE TESTING AND
IN ACCORDANCE WITH THE CALIFORNIA PLUMBING CODE, AND SHALL MEET THE
EVALUATION OF VOLATILE ORGANIC CHEMICAL EMISSIONS FROM INDOOR SOURCES
APPLICABLE REFERENCED STANDARDS.
USING ENVIRONMENTAL CHAMBERS", VERSION 1.1, FEBRUARY 2010 (ALSO KNOWN AS
SPECIFICATION 01350.)
WATER EFFICIENCY AND CONSERVATION (OUTDOOR WATER USE)
4.504.5 PARTICLE BOARD, MEDIUM DENSITY FIBERBOARD (MDF) AND HARDWOOD PLYWOOD
Scale: AS NOTED
4.304.1 AUTOMATIC IRRIGATION SYSTEMS CONTROLLERS INSTALLED AT THE TIME OF FINAL
USED IN INTERIOR FINISH SYSTEMS SHALL COMPLY WITH LOW FORMALDEHYDE
INSPECTION SHALL BE WEATHER OR SOIL MOISTURE-BASED.
EMISSION STANDARDS.
Drawn By: ASM
ENHANCED DURABILITY AND REDUCED MAINTENANCE ENVIRONMENTAL QUALITY (INTERIOR MOISTURE CONTROL)

4.406.1 ANNULAR SPACES AROUND PIPES, ELECTRIC CABLES, CONDUITS OR OTHER OPENINGS
IN PLATES AT EXTERIOR WALLS SHALL BE PROTECTED AGAINST THE PASSAGE OF
4.505.2 VAPOR RETARDER AND CAPILLARY BREAK IS INSTALLED AT SLAB ON GRADE
FOUNDATIONS.
Approved: PCV
RODENTS BY CLOSING SUCH OPENINGS WITH CEMENT MORTAR, CONCRETE MASONRY
OR SIMILAR METHOD ACCEPTABLE TO THE ENFORCING AGENCY. 4.505.3 MOISTURE CONTENT OF BUILDING MATERIALS USED IN WALL AND FLOOR FRAMING IS
CHECKED BEFORE ENCLOSURE. Job No.: 21501.01
CONSTRUCTION WASTE REDUCTION, DISPOSAL AND RECYCLING ENVIRONMENTAL QUALITY (ENVIRONMENTAL COMFORT)

4.408.1 RECYCLE AND/OR SALVAGE FOR REUSE A MINIMUM OF 50 PERCENT OF THE NON
4.507.2 DUCT SYSTEMS ARE SIZED, DESIGNED, AND EQUIPMENT IS SELECTED USING THE Date: 6/10/15
FOLLOWING METHODS:
HAZARDOUS CONSTRUCTION AND DEMOLITION WASTE IN ACCORDANCE WITH ONE OF
1.) ESTABLISH HEAT LOSS AND HEAT GAIN VALUES ACCORDING TO ANSI/ACCA
THE FOLLOWING:
2 MANUAL J-2004 OR EQUIVALENT.
1. COMPLY WITH A MORE STRINGENT LOCAL CONSTRUCTION AND DEMOLITION WASTE
2. SIZE DUCT SYSTEMS ACCORDING TO ANSI/ACCA 1 MANUAL D-2009 OR EQUIVALENT.
MANAGEMENT ORDINANCE; OR
2. A CONSTRUCTION WASTE MANAGEMENT PLAN; PER SECTION 4.408.2; OR
3. SELECT HEATING AND COOLING EQUIPMENT ACCORDING TO ANSI/ACCA 3 MANUEL Sheet No.:
S-2004 OR EQUIVALENT.
3. A WASTE MANAGEMENT COMPANY, PER SECTION 4.408.3; OR
4. THE WASTE STREAM REDUCTION ALTERNATIVE, PER SECTION 4.408.4.
INSTALLER & SPECIAL INSPECTOR QUALIFICATIONS

BUILDING MAINTENANCE AND OPERATION QUALIFICATIONS

A1
702.1 HVAC SYSTEM INSTALLERS ARE TRAINED AND CERTIFIED IN THE PROPER INSTALLATION
4.410.1 AN OPERATION AND MAINTENANCE MANUAL SHALL BE PROVIDED TO THE BUILDING
OF HVAC SYSTEMS.
OCCUPANT OR OWNER.

ENVIRONMENTAL QUALITY (FIREPLACES) 702.2 SPECIAL INSPECTORS EMPLOYED BY THE ENFORCING AGENCY MUST BE QUALIFIED
AND ABLE TO DEMONSTRATE COMPETENCE IN THE DISCIPLINE THEY ARE INSPECTING.
4.503.1 ANY INSTALLED GAS FIREPLACE SHALL BE A DIRECT-VENT SEALED-COMBUSTION TYPE. VERIFICATIONS
ANY INSTALLED WOOD STOVE OR PELLET STOVE SHALL COMPLY WITH US EPA PHASE
II EMISSION LIMITS WHERE APPLICABLE. WOOD STOVES, PELLET STOVES AND 703.1 VERIFICATION OF COMPLIANCE WITH THIS CODE MAY INCLUDE CONSTRUCTION
FIREPLACES SHALL ALSO COMPLY WITH APPLICABLE LOCAL ORDINANCES. DOCUMENTS, PLANS, SPECIFICATIONS BUILDER OR INSTALLER CERTIFICATION,
INSPECTION REPORTS, OR OTHER METHODS ACCEPTABLE TO THE ENFORCING 1 of 30
AGENCY WHICH SHOW SUBSTANTIAL CONFORMANCE.
FLOOR PLAN A SCALE: 1/4" = 1'-0" KEY NOTES FLOOR PLAN NOTES
VOLKMANN
A R C H I T E C T U R E
1601 North Main, Suite 202
Walnut Creek, CA 94596
925. 478. 2998 (office)
ContactUs@volmannarchitecture.com
www.volkmannarchitecture.com

Project Title:

Cobble Lane
RESIDENCES

2155 Overlook Drive


Walnut Creek CA
94596
Sheet Title:

UPPER LEVEL

Revisions:

No. By Date

UNDER FLOOR VENTILATION CALCS.

Scale: 1/4" = 1'-0"


Drawn By: ASM
Approved: PCV
FLOOR PLAN LEGEND
Job No.: 21501.01
Date: 6/10/15

A Sheet No.:
A5

A2
LOWER LEVEL 2 of 30
ELEC., MECH., & PLUMBING NOTES
VOLKMANN
A R C H I T E C T U R E
1601 North Main, Suite 202
Walnut Creek, CA 94596
925. 478. 2998 (office)
ContactUs@volmannarchitecture.com
www.volkmannarchitecture.com

Project Title:

Cobble Lane
RESIDENCES

2155 Overlook Drive


Walnut Creek CA
94596
Sheet Title:

UPPER LEVEL

ELEC., MECH., & PLUMBING LEGEND

Revisions:

No. By Date

Scale: 1/4" = 1'-0"


Drawn By: ASM
Approved: PCV
Job No.: 21501.01
Date: 6/10/15

Sheet No.:

LOWER LEVEL
A3
3 of 30
ELECTRICAL, MECHANICAL, & PLUMBING PLAN A SCALE: 1/4" = 1'-0"
ROOF DRAINAGE NOTES
VOLKMANN
A R C H I T E C T U R E
1601 North Main, Suite 202
Walnut Creek, CA 94596
925. 478. 2998 (office)
ContactUs@volmannarchitecture.com
www.volkmannarchitecture.com
ROOF DRAINAGE LEGEND
Project Title:

Cobble Lane
RESIDENCES

2155 Overlook Drive


Walnut Creek CA
94596
Sheet Title:

SECTION A-A SCALE: 1/4" = 1'-0" ROOF PLAN SCALE: 1/8" = 1'-0" ATTIC VENTILATION CALCS.

SECTION B-B SCALE: 1/4" = 1'-0" SECTION D-D SCALE: 1/4" = 1'-0"
Revisions:

No. By Date

Scale: AS NOTED
Drawn By: ASM
Approved: PCV
Job No.: 21501.01
Date: 6/10/15

Sheet No.:

A4
4 of 30
SECTION C-C SCALE: 1/4" = 1'-0"
ELEVATION NOTES
VOLKMANN
A R C H I T E C T U R E
1601 North Main, Suite 202
Walnut Creek, CA 94596
925. 478. 2998 (office)
ContactUs@volmannarchitecture.com
www.volkmannarchitecture.com

Project Title:

Cobble Lane
KEY NOTES RESIDENCES

2155 Overlook Drive


Walnut Creek CA
94596
Sheet Title:

RIGHT SIDE ELEVATION SCALE: 1/4" = 1'-0" REAR ELEVATION SCALE: 1/4" = 1'-0"

Revisions:

No. By Date

Scale: 1/4" = 1'-0"


Drawn By: ASM
Approved: PCV
Job No.: 21501.01
Date: 6/10/15

Sheet No.:

A5
5 of 30
FRONT AT SIDE ELEVATION SCALE: 1/4" = 1'-0" FRONT AT GARAGE ELEVATION SCALE: 1/4" = 1'-0"
FLOOR PLAN B SCALE: 1/4" = 1'-0"
VOLKMANN
A R C H I T E C T U R E
1601 North Main, Suite 202
Walnut Creek, CA 94596
925. 478. 2998 (office)
ContactUs@volmannarchitecture.com
www.volkmannarchitecture.com

Project Title:

Cobble Lane
RESIDENCES

2155 Overlook Drive


Walnut Creek CA
94596
Sheet Title:

Revisions:

No. By Date

UPPER LEVEL MAIN LEVEL BASEMENT LEVEL

KEY NOTES FLOOR PLAN NOTES FLOOR PLAN LEGEND

A
A5

UNDERFLOOR VENTILATION CALCS.

Scale: 1/4" = 1'-0"


Drawn By: ASM
Approved: PCV
Job No.: 21501.01
Date: 6/10/15

Sheet No.:

A6
6 of 30
VOLKMANN
A R C H I T E C T U R E
1601 North Main, Suite 202
Walnut Creek, CA 94596
925. 478. 2998 (office)
ContactUs@volmannarchitecture.com
www.volkmannarchitecture.com

Project Title:

Cobble Lane
RESIDENCES

2155 Overlook Drive


Walnut Creek CA
94596
Sheet Title:

UPPER LEVEL FLOOR PLAN MAIN LEVEL FLOOR PLAN BASEMENT LEVEL FLOOR PLAN
Revisions:
ELEC., MECH., & PLUMBING NOTES ELEC., MECH., & PLUMBING LEGEND No. By Date

Scale: 1/4" = 1'-0"


Drawn By: ASM
Approved: PCV
Job No.: 21501.01
Date: 6/10/15

Sheet No.:

A7
7 of 30
ROOF NOTES
VOLKMANN
A R C H I T E C T U R E
1601 North Main, Suite 202
Walnut Creek, CA 94596
925. 478. 2998 (office)
ContactUs@volmannarchitecture.com
www.volkmannarchitecture.com

Project Title:

ROOF LEGEND Cobble Lane


RESIDENCES

2155 Overlook Drive


Walnut Creek CA
94596
Sheet Title:

ROOF PLAN SCALE: 1/8"= 1'-0" ATTIC VENTILATION CALCS

SECTION A-A SCALE: 1/4"= 1'-0"

Revisions:

No. By Date

SECTION D-D SCALE: 1/4"= 1'-0"

Scale: AS NOTED
Drawn By: ASM
Approved: PCV
Job No.: 21501.01
Date: 6/10/15

Sheet No.:

A8
8 of 30
SECTION B-B SCALE: 1/4"= 1'-0" SECTION C-C SCALE: 1/4"= 1'-0"
ELEVATION NOTES
VOLKMANN
A R C H I T E C T U R E
1601 North Main, Suite 202
Walnut Creek, CA 94596
925. 478. 2998 (office)
ContactUs@volmannarchitecture.com
www.volkmannarchitecture.com

Project Title:
KEY NOTES
Cobble Lane
RESIDENCES

2155 Overlook Drive


Walnut Creek CA
94596
Sheet Title:

RIGHT SIDE ELEVATION SCALE: 1/4" = 1'-0" REAR ELEVATION SCALE: 1/4" = 1'-0"

Revisions:

No. By Date

Scale: 1/4" = 1'-0"


Drawn By: ASM
Approved: PCV
Job No.: 21501.01
Date: 6/10/15

Sheet No.:

A9
9 of 30
FRONT AT SIDE ELEVATION SCALE: 1/4" = 1'-0" FRONT AT GARAGE ELEVATION SCALE: 1/4" = 1'-0"
4 4 1 VOLKMANN
A R C H I T E C T U R E
1601 North Main, Suite 202
Walnut Creek, CA 94596
2 925. 478. 2998 (office)
ContactUs@volmannarchitecture.com
www.volkmannarchitecture.com

Project Title:

3 Cobble Lane
1 2
4 RESIDENCES
5 5
INSIDE 3 OUTSIDE
CORNER CORNER 1 2 3 5 23
FRONT - 2155 Overlook Drive
1 CORNER WALL FLASHING 3 PAN FLASHING TO EAVE 4 RAKE END CAP 5 INSIDE CORNER TRIM Walnut Creek CA
- - 3"=1'-0"
NO SCALE
94596
Sheet Title:

9 PIPE PENETRATION AT WALL 10 ROOF @ PARALLEL WALL W/ SIDING 11 EXTERIOR CORNER @ SIDING 12 BELLY BAND
- N.T.S 3"=1'-0" -

13 STANDARD WINDOW INSTALLATION & FLASHING 16 ROOF @ PERPENDICULAR WALL W/ SIDING


N.T.S.

Revisions:

No. By Date

24

21 MECHANICAL PENETRATIONS 22 ROOF PENETRATION / PIPE 23 TYPICAL RAKE @ COMP. SHINGLE ROOFING 24 EAVE @ COMP SHINGLE ROOFING
- N.T.S.

Scale: AS NOTED
Drawn By: TKM
Approved: PCV
Job No.: 21501.01
Date: 6/10/15

Sheet No.:

23 24

25 DOOR FLASHING - THRESHOLD 28 RIDGE 29 VALLEY 30 PERIMETER FOOTING @ GRADE BEAM


D1
NO SCALE - 10 of 30
VOLKMANN
A R C H I T E C T U R E
1601 North Main, Suite 202
Walnut Creek, CA 94596
925. 478. 2998 (office)
ContactUs@volmannarchitecture.com
www.volkmannarchitecture.com

Project Title:

Cobble Lane
RESIDENCES
6 9
7
2155 Overlook Drive
1 GARAGE DOOR HEAD 2 HANDRAIL/GUARDRAIL 3 FURRED WINDOW @ HEAD 4 EXTERIOR DOOR HEAD - SIDING 5 SLIDING DOOR HEAD 6 WINDOW HEAD - SIDING Walnut Creek CA
- 3"=1'-0" - NO SCALE - 3"=1'-0" 3"=1'-0" 3"=1'-0" 3"=1'-0"
94596
Sheet Title:

21
13

7 GARAGE DOOR JAMB 8 HANDRAIL 9 FURRED WINDOW @ JAMB 10 DOOR JAMB - SIDING 11 SLIDING DOOR JAMB 12 WINDOW JAMB - SIDING
- 3"=1'-0" - - 3"=1'-0" 3"=1'-0" 3"=1'-0" 3"=1'-0"

13

13 GARAGE DOOR THRESHOLD 14 GUARDRAIL 15 FURRED WINDOW @ SILL 16 EXTERIOR DOOR THRESHOLD 17 SLIDING DOOR THRESHOLD 18 WINDOW SILL - SIDING
- 3"=1'-0" - 1 1/2"=1'-0" - 3"=1'-0" 3"=1'-0" 3"=1'-0" 3"=1'-0"

Revisions:

No. By Date

19 GABLE END VENT 20 STAIR STRINGER 21 POP OUT FLOOR/WALL CONNECTION


- - 3" = 1'-0" -

Scale: AS NOTED
Drawn By: TKM
Approved: PCV
Job No.: 21501.01
Date: 6/10/15

Sheet No.:

26 STAIR @ SLAB 27 STRINGER TO WALL


D2
- - 11 of 30
DIVISION 00 - PROCUREMENT & CONTRACTING DIVISION 06 - WOOD, PLASTICS, AND COMPOSITES 06 43 16 WOOD RAILINGS 07 27 13 WATER-RESISTIVE BARRIER 07 66 00 FLASHING AND SHEET METAL
REQUIREMENTS 01 74 00 CLEANING AND WASTE MANAGEMENT
06 10 00 ROUGH CARPENTRY A. Provide wood railings as shown on Drawings and as B. Provide 15 lb non-perforated asphalt-saturated building A. Provide flashing of 26 gauge galvanized sheet metal per VOLKMANN
01 00 00 PROJECT DIRECTORY A. Each Sub shall leave the Project area clean of debris and selected by Owner. paper at all exterior frame walls and as indicated on ASTM A525 Class 1.25 Commercial. Solder all joints in A R C H I T E C T U R E
scrap material upon the completion of the Subcontract. A. Provide and install wood framing as shown on the drawings chimney and skylight flashing (where applicable.) Lap
1601 North Main, Suite 202
A. OWNER: Byron Crowley B. All excess material is the property of the Contractor or the Drawings and as specified herein. Work includes all C. Provide 15 lb non-perforated asphalt-saturated building running trim 6 inches and seal between layers with butyl
Walnut Creek, CA 94596
256 Nob Hill Drive Sub. connectors, and related hardware and materials. 06 44 00 ORNAMENTAL WOODWORK paper at all exterior roofs below roofing material per base caulking. Coat sheet metal in contact with built-up
925. 478. 2998 (office)
Walnut Creek, CA 94596 C. The Contractor shall leave the Project area clean, ready B. All wood should be FSC (Forest Stewardship Council) Division 07 31 13 and 07 41 13 and as indicated on roofing in continuous bed of black plastic cement.
ContactUs@volmannarchitecture.com
(425) 317-9317 for occupancy. certified. A. Ornamental woodwork components, species and finishes drawings. Conform to roofing manufacturer's details; where
www.volkmannarchitecture.com
C. See structural drawings, calculations and specifications shall be as selected by Owner. Includes Knee braces, manufacturer has no specific instructions, conform to
01 40 00 QUALITY REQUIREMENTS - PERMIT AND FEES prepared by Dentils, Corbels, and others shown on exterior elevations 07 31 13.13 FIBERGLASS-REINFORCED ASPHALT NRCA details. Caulk joints, nail heads and wherever there
B. ARCHITECT: Volkmann Architecture, Inc. Cyrus Mashhoodi, PE B. All Ornamental woodwork to have one coat primer on all SHINGLES is a possibility of leakage with butyl base caulking.
Project Title:
1601 N. Main Street, Ste 202 A. The Contractor shall obtain and pay for all applicable 1825 Galindo Street, #406 sides and edges Endorse roofing warranty for roofing related sheet metal to
Walnut Creek, CA 94596 permits and fees. Concord, CA 94520 A. Roofing shall be "Landmark Plus" as manufactured by be free from defect and to be watertight for a period of 2
years.
Cobble Lane
(925) 478-2998 B. All Subs and Suppliers shall obtain permits and licenses (925) 818-0570 06 46 00 WOOD TRIM Certainteed, 2021 Las Positas Ct., Suite 129, Livermore,
for their operations as required by governing agencies. CA 94550, Mfr.. Representative: Darin Robinson, Ph (925) RESIDENCES
C. CONTRACTOR: to be determined 06 15 00 WOOD DECKING A. Interior woodwork components, species and finishes shall 371-6731. 40 Year warrantee. Colors to be selected by 07 65 26 FLEXIBLE FLASHING
DIVISION 02 - EXISTING CONDITIONS be as selected by Owner. Includes baseboards, door and Owner.
D. Subcontractors are herein referred to as SUBS
02 21 00 SITE SURVEYS
A. Wood decks to be 5/4 x 6 Pau Lope. Install and pre-drill window trim, aprons, stools, sills, crowns and/or handrails. B. Underlayment shall be: On standard slope roofs (4:12 to A. Provide W.R. Grace Vycor Plus self-adhere flexible 2155 Overlook Drive
(e.g. Framing Sub, Plumbing Sub, etc.) for Swaneeze # 7 2-1/4" Square Drive Stainless Steel trim 12:12) use one layer 15 lb. asphalt-saturated organic flashing. Apply as indicated on drawings and per
head screws. 06 61 00 PLASTIC LAMINATES, SOLID SYNTHETICS roofing felt; On low slope roofs (2:12 to 4:12 ) use 2 layers manufacturer's recommendations (not to be used as roof Walnut Creek CA
01 00 00 THE CONTRACT DOCUMENTS A. See Site Plan drawings and specifications prepared by B. All cuts should be sealed with Anchor Seal brand wax or 15 lb. asphalt-saturated organic roofing felt. Underlayment underlayment) 94596
DeBolt Civil Engineering equal to help prevent superficial checking. Spacing A. Plastic laminate or solid synthetic countertops, backsplash to meet ASTM D 4869 Type I. Install self-adhering sheet Sheet Title:
A. The Contract Documents consist of the Contract,including 811 San Ramon Valley Blvd. between deck boards should be approximately 1/8 inch. locations and countertop materials shall be as selected by flashing at eaves and valleys per drawings. All installation 07 71 23 GUTTER AND DOWNSPOUTS
any Subcontract agreements, the Drawings, and these Danville, CA 94526 C. Attach per details. Use Deck2Wall spacer to provide air Owner. of underlayments shall be per Manufacturers
Specifications. (925) 837-3780 space behind ledger recommendations. A. Gutters to be 5" K-Style Ogee with down spouts, including
B. The Contract, Drawings, and Specifications are intended D. Contact info: 06 65 00 PLASTIC SIMULATED WOOD TRIM C. Provide a complete roofing assembly, including all all related sheet metal accessories to be 24 gauge
to supplement each other. In case of conflict, the 02 30 00 EARTHWORK 69041 Chestnut Ave. necessary shingle shapes, installation components and galvanized sheet metal, with dimensions as shown on
Specifications shall control the Drawings and the Merchantville, NJ 08109. A. Provide flexible plastic trim per Drawings by Flex Trim (To accessories. Install per manufacturer's recommendations, Drawings. All joints shall be riveted and soldered. Gutter
A. Upon completion of the project, remove soil, which may be email: info@paulope.com and as detailed per Drawings. shall be installed per details. Gutter width should be
provisions of the Contract shall control both. be used at fascias at radial towers). 121" thick minimum.
excess because of excavation, trenching and backfilling. Phone # : (800)783-7220 D. Roofing shall conform to recommendations of the National installed with 1/2 inch minimum lateral clearance within
Install and finish per manufacturers recommendations.
Excess soil that may be adequate to support vegetation Roofing Contractors' Association "Roofing and supports.
Flex Trim
DIVISION 01 GENERAL REQUIREMENTS growth may be retained on site and distributed. Excess 06 20 13 EXTERIOR FINISH CARPENTRY Waterproofing Manual." B. Provide expansion joints per SMACNA guidelines. Provide
210 E Citrus Ave
soil that may not be adequate to support vegetation horizontal clearance from supports, gutter ends and
P.O. Box 2260
01 25 13 SUBSTITUTIONS PROCEDURES growth such as gravel, sand, and debris, shall be removed A. All wood to have one coat primer on all sides and edges. 07 46 23 WOOD SIDING corners. Maximum distance between expansion joint and
Redlands, CA 92373
from the site and discarded. B. All wood should be FSC (Forest Stewardship Council) downspout shall be 21 feet. Width a cross bottom of gutter
Phone: (800) 365-9874
A. Where products, materials and equipment are specified by B. Remove hummocks and depressions from site. Grade to certified. A. Provide siding and exterior trim as shown on Drawings shall be at least 4 inches.
manufacturer or trade name, they are intended to produce reasonably uniform surfaces, which will not trap C. Install wood per Drawings and include expansion space and as indicated herein. C. Continuously cleat gutter back edge using 6 inch minimum
establish quality and function. The Contractor is surface water. Surface backfill to structures; do not fill as needed. B. Install exterior siding over kraft waterproof building paper apron flashing. Provide waterproofing membrane that laps
higher than within 6 inches of wood wall sills nor higher DIVISION 07 - THERMAL AND MOISTURE PROTECTION
encouraged to seek substitutions and production options, D. Caulk joints at material intersections . or asphalt-saturated rag felt applied horizontally, with the the cleat and lies under the roof surface material, as
but the burden of proof that quality and function "or equal" than indicated on the drawings. E. Exterior wood siding shall be per Division 07 46 00. upper layer lapped over the lower layer not less than six detailed. Outlets shall be placed only in the bottoms of
C. Remove construction debris from site including excess 07 10 00 DAMP PROOFING AND WATERPROOFING
is upon the Contractor. Such requests shall be submitted F. Nail exterior trim & siding with double hot-dipped inches. Where vertical joints occur, felt or paper shall be gutters. Clearance shall be allowed around gutter outlets
to the Architect and shall include sufficient data, including materials, concrete and plaster washings, scrap, and galvanized nails by: lapped not less than six inches. Building paper or felt shall to allow for movement. Downspout shape shall be 2"x3"
rejected materials; do not bury on site. A. At slab as recommended in Geotechnical Investigation
cost differences, such that the Architect and Owner can Maze Stormguard be free from holes and breaks other than those created by rectangular, smooth. Gutter as shown on Drawings. All
Report; see "Site Work", Section 02 21 00 for contact
make a reasonable decision on acceptance. Where there 100 Church St. , fasteners. All manufactured siding products shall be exposed sheet metal components shall be etched and
02 32 00 GEOTECHNICAL DATA information.
are differences, the Contract Sum will be adjusted. Where Peru, Illinois 61345 installed per manufacturers recommendations. Fasteners painted, unless otherwise noted. See "Paint", Section 09
products, materials and equipment are specified "no Ph.800-435-5949. shall be corrosion-resistant per Div. 06 20 13 and meet 91 13 Exterior Painting.
Substitution", such products, materials and equipment A. Soils Report: See Geotechnical Investigation Report. www.mazenails.com or equal siding manufacturer's and code requirements.
Contact Owner for further information. 07 13 00 SHEET WATERPROOFING
shall be used. The Term "or equal" as used in these C. At board and batten exteriors, provide 3/8" thick APA 07 72 00 ROOF ACCESSORIES
Contract Documents shall mean "as accepted by the B. Contractor shall be familiar with existing conditions at the 06 20 23 INTERIOR FINISH CARPENTRY certified (resawn or smooth- see elevations for locations)
site to construct the work as described within these A. Provide Bituthene System 4000 by Grace Construction
Architect". A. Plumbing, Electrical or HVAC Subs shall provide and
constructions documents. Products between concrete topping and wood substrate.
A. Perform all work per details and applicable trade see elevations for locations) Spruce (Grade D & better install necessary vents and roof jacks to complete
01 45 00 QUALITY CONTROL standards; saw cuts straight and clean, tight fits without select) battens at 16" on center and at center of plywood installation of respective equipment.
02 62 00 SUBDRAINAGE per Manufacturer's recommendations.
gaps, splices tight and staggered (never side by side). end panel joints. B. Break all vents to rear of roof ridge.
Contact person: Scott Tyson
A. The Work shall conform in every part to the industry's Align and match miter joints at edges and corners. Install D. Provide exterior (Grade D & better select) Spruce trim C. Framing Sub shall install eave, gable and dormer vents as
A. Provide subdrain and perimeter drainage as required. All Phone: 800-354-5414 x 5675
accepted standards of good quality, and shall be free from running trim in maximum lengths; do not use short pieces resawn or smooth as shown on Drawings. All wood trim required by the Drawings.
faults defects. rain leaders shall be connected to a perimeter subsurface or splicing of scraps. shall be per details and elevations and pre-primed on all D. Provide galvanized metal louver vents as indicated on
B. The Work shall conform in every part to all applicable system. B. Keep number of joints to a minimum by consistently using sides where painted. All wood trims shall be continuous Drawings. Vents shall be primed for paint. Provide
07 13 26 SELF-ADHESIVE SHEET WATERPROOFING
codes, laws, ordinances, rules, regulations, and orders of DIVISION 03 - CONCRETE maximum size material. members for each span as indicated on drawings. galvanized insect screens.
any public authority covering building operations in the city C. Fasten all pieces straight, true, and secure. Coordinate E. Provide rain screen per Division 07 10 00. E. Provide Famco Roof Vent JV048 with net free ventilation
A. Provide W.R. Grace Ice & Watershield as indicated on
or county in which the real property is located. 03 00 00 CONCRETE backing and blocking with other trades with interfacing area of 38 sq. in. 26 ga GSM. Verify color with owner.
Drawings. Install per manufacturer's recommendations.
C. In carrying out his Work, each Sub shall take necessary work. 07 46 26 HARDBOARD SIDING Install per manufacturers recommendations at locations
Contact person: Scott Tyson
precautions to protect the work of other trades from A. See structural drawings, calculations and specifications D. All wood should be FSC (Forest Stewardship Council) shown on drawings.
Phone: 800-354-5414 x 5675
damage. prepared by: certified. A. Cement siding products shall be manufactured by James
D. Each Sub shall take all reasonable precautions to prevent Cyrus Mashhoodi. PE Hardie Building Products or equal and installed per 07 92 13 JOINT SEALANTS
07 21 16 BLANKET INSULATION
damage or loss to all materials and equipment during 1825 Galindo Street, #406 06 26 13 BOARD PANELING manufacturer's requirements
delivery, storage and installation. Concord, CA 94520 B. Install exterior siding over kraft waterproof building paper A. Provide caulking or sealant at the following locations:
A. Insulation R-values and locations per Title 24 Energy
E. Tolerances where not specified in the Drawings shall A. All wood panels to have one coat primer on all sides and or asphalt-saturated rag felt applied horizontally,with the Finish material intersections where mildew
(925) 818-0570 Calculations. "C" type shall be used at cathedral
conform to the industry's accepted standards. Where edges. upper layer lapped over the lower layer not less than six resistance is required.
roof/ceiling assemblies. All batt insulation to be fiberglass
tolerances more critical than industry accepted standards B. Install wood per Drawings and include expansion space inches. Where vertical joints occur, felt or paper shall be Locations where movement is anticipated.
B. Provide reinforced concrete landings as shown on with vapor retarder face except where used in acoustical
are specified, they shall supersede industry standards. as needed. lapped not less than six inches. Building paper or felt shall Intersections of dissimilar exterior materials. Revisions:
Drawings. applications it shall be unfaced. Owens-Corning or equal.
F. Details shown are typical; similar details shall apply at C. Do not begin installation until substrates have been be free from holes and breaks other than those created by Joints and cracks around windows, thresholds, and
C. See Foundation drawings, calculations and specifications Consider Knauf Eco-Batts as green alternative (see No. By Date
similar conditions. properly prepared. fasteners. All manufactured siding products shall be door frame, wall and roof penetrations.
prepared by: Resources Div 7). Installation per manufacturers
G. Contractor shall verify all existing conditions and D. Install in accordance with LP smartside panel siding installed per manufacturers recommendations. Fasteners All joint locations necessary to make the building
Cyrus Mashhoodi, PE recommendations.
dimensions at the job site. Any conditions requiring manufacturer's instructions. shall be corrosion-resistant per CRC R602. Meet siding water or vapor.
1825 Galindo Street, #406 B. Install all fiberglass batt insulation with foil or Kraft-facing
construction different from that shown on the Drawings 1. Read warranty and comply with all terms necessary manufacturer's and code requirements. B. Caulking and sealant materials shall be selected as
Concord, CA 94520 toward interior living spaces.
shall be brought to the attention of the Architect. to maintain warranty coverage. C. All trim shall be per details and elevations and pre-primed appropriate to each application, based on
(925) 818-0570 C. Floor insulation at crawl space.
H. Dimensions shall refer to rough concrete surfaces, face of 2. Install in accordance with conditions stated in on all sides where painted. All trims shall be continuous manufacturer's recommendations. Color shall blend with
D. All plumbing walls adjacent to interior living spaces shall
studs, face of concrete block, top of sheathing, or top of DIVISION 04 - MASONRY ICC-ES NER-124 or ICC-ES ER-5905. members per each span as indicated at drawings. adjacent materials.
be sound insulated with unfaced R-13 acoustic batts.
slab, unless otherwise noted. E. Allow products to adjust to ambient conditions before D. Provide corner trim as shown on Drawings C. Subs shall provide all caulking.
E. Provide radiant barrier as required per T-24 Energy
I. Contractor shall be solely responsible for all excavation 04 20 00 UNIT MASONRY starting installation. E. Provide "ARTISAN" Lap Siding as manufactured by
Calculations.
procedures including: lagging, shoring, and the protection F. Do not install to green wood or crooked structural framing. James Hardie, Cedarmill 5/8" thick w/ 7" exposure.
of adjacent property, structures, streets and utilities. A. See structural drawings, calculations and specifications Do not install over rain soaked or buckled materials. Do F. Provide "Hardisoffit" Panel as manufactured by James
07 26 16 BELOW GRADE VAPOR RETARDERS
J. Contractor shall be solely responsible for providing prepared by: not install if excessive moisture is present in the interior, Hardie. 1/8 " thick non-vented
adequate shoring and bracing as required for the Cyrus Mashhoodi, PE including that from curing concrete and plaster.
A. Provide vapor retarder (membrane) under interior slabs on
protection of life and property during the construction of 1825 Galindo Street, #406 G. Do not cut siding to fabricate trim; use trim components
grade per Geotechnical Engineers Report
the structure. Shoring and bracing shall remain in place Concord, CA 94520 manufactured for that purpose.
until the floors, roof and wall sheathing have been entirely (925) 818-0570 H. After installation, seal all joints except the overlapping
constructed. horizontal lap joints. Seal around all penetrations. See
K. Any conflicting information found in the Contract DIVISION 05 - METALS special requirements if an Open Joint Rain Screen
Documents shall be brought to the attention of the technique is utilized.
Architect. 05 05 23 METAL FRAMING AND FASTENING I. Protect installed products until completion of project. Scale: AS NOTED
L. Contractor and Subs shall furnish all labor, materials and Touch-up, repair or replace damaged products
tools necessary to perform the Work shown on the A. See structural drawings, calculations and Drawn By: TKM
Drawings, specified herein, or reasonably implied. specifications prepared by: 06 41 00 ARCHITECTURAL WOOD CASEWORK
M. Supervision shall be provided by the Contractor and each Approved: PCV
Cyrus Mashhoodi, PE
Sub to assure satisfactory results to the Contractor. 1825 Galindo Street, #406 A. The Work shall include all labor, tools, and materials Job No.: 21501.01
Concord, CA 94520 necessary to fabricate all cabinets and cases as per the
01 50 00 TEMPORARY FACILITIES AND CONTROLS (925) 818-0570 drawings, including all hardware necessary for proper Date: 6/10/15
operation.
A. The Contractor shall provide at no cost to the Subs or 05 50 00 METAL FABRICATIONS B. Cabinet construction shall be Custom Grade as defined by
Sheet No.:
Owner the following temporary facilities and services: the Woodworking Institute of California.
sanitary A. Provide metal railings as shown on Drawings and as C. Owner to select cabinet construction type ( face-fame or
electrical power selected by Owner. frameless), door/ drawer style, and finishes. Submit shop

SP-1
water drawings for approval.
material storage D. Owner to select countertop materials. Coordinate
dumpster/debris removal substrate requirements of tile or slab materials.
telephone E. Verify appliance sizes with Owner and Supplier.
e-mail 12 of 30
DIVISION 08 - OPENINGS DIVISION 09 - FINISHES 09 91 13 EXTERIOR PAINTING DIVISION 11 - EQUIPMENT For PEX (cross-linked polyethlene) tubing systems: DIVISIONS 26 - ELECTRICAL
A. Provide Uponor (Wirsbo) AquaPEX system ASTM F876,
08 05 00 COMMON WORK RESULTS FOR OPENINGS A. Paint shall be selected by Owner. Brush-outs of each 11 31 13 RESIDENTIAL KITCHEN APPLIANCES F877 and F1960, or equal. Follow manufacturer's 26 05 00 COMMON WORK RESULTS FOR ELECTRICAL VOLKMANN
09 29 00 GYPSUM BOARD selected color and sheen shall be submitted for approval installation guidelines. System shall be IAPMO certified or A R C H I T E C T U R E
A. Provide fixed and operable windows as shown on prior to application. A. Install all appliances per manufacturer's other approved certification agency approval. Uponor A. The Work includes all labor, materials and equipment 1601 North Main, Suite 202
Drawings. Contractor shall coordinate framed openings A. Gypsum board shall be 1/2 inch on all walls, and ceilings B. Exterior Paint Wood: 1 coat 100% exterior acrylic latex recommendations. Coordinate with the work of other contact: 5925 148th Street West, Apple Valley, MN 55124, necessary to properly complete electrical system as Walnut Creek, CA 94596
as required for specific window manufacturer. Confirm unless otherwise noted. primer, 2 coats 100% exterior acrylic latex. trades as required. 800 321-4739, www.uponor-usa.com. per the Drawings. This includes all necessary 925. 478. 2998 (office)
windows with Owner prior to ordering. B. Nailing shall be according per CRC R702.3.5 C. Exterior Paint: Non-Ferrous Metal: Prior to priming B. Provide appliances as shown here as selected by B. If manifold is used, mount plumbing manifold in a installation and/or hook-up of built-in appliances and ContactUs@volmannarchitecture.com
B. Windows shall be installed per manufacturer instructions requirements. Galvanized metal must be cleaned with a degreasing Owner. Verify with Owner and Friedman's Appliance. convenient, accessible location to allow access for shut equipment, but excludes utility hook-ups provided by
www.volkmannarchitecture.com
per CRC 303, set in a level, plumb and square position, C. Provide moisture-resistive "green" wallboard at all wet cleaner to remove all oils prior to etching. Surface should off to individual fixtures. Label valves as to fixture location. the utility company.
without distortion. locations except behind tile. then be etched with Galva-etch by Dunn Edwards or 1. 30" Double Oven C. Provide minimum clearances of 36-inches (vertical) and B. Underground service shall be 200 Amp (minimum) as
C. All window & door details indicated are generic. Windows D. Gypsum board on all walls and ceilings shall be taped, equal. After etching apply 1 coat epoxy ester primer Manufacturer: By Owner 18-inches (horizontal) between thermoplastic manifold (if per CEC 230.31 through 230.33 requirements. Project Title:
& doors shall be installed in accordance with approved three coats putty unless otherwise specified, sanded and D. Sealant color shall be appropriate to the installation. 2. 30" Warming Drawer, Wood Front used) and the water heater. C. The Electrical Sub shall provide trench and backfill for
manufacturer's instruction. Fastener size and spacing free from seam lines or defects in workmanship. Manufacturer: By Owner D. Provide hangers and supports as necessary to properly electric underground service, except when furnished by Cobble Lane
E. Metal corners per Owner shall be installed and finished 3. 30" 4-burner Gas Cooktop secure system at code-required grades in such a manner utility company.
shall be provided in such instructions and shall be
calculated based on maximum loads and spacing used in per manufacturer standards.
09 91 23 INTERIOR PAINTING
Manufacturer: By Owner as to insure a quiet system. D. The Electrical Sub shall provide conduit and wiring for RESIDENCES
the tests, per CRC TABLE R602.3(1) F. Provide metal "J"-mold wherever board abuts exposed A. Paint shall be selected by Owner. Brush-outs of each 4. 30" Hood Exhaust E. Provide hose bibbs as per Drawings, with tee fittings underground service, as required for a proper
D. Provide flashing at rough openings prior to window wood. selected color and sheen shall be submitted for approval Manufacturer: By Owner above ground for future landscape sprinkler installation at installation.
installation per manufacturer instructions. Units shall be G. Interior face of 1hr Fire-Resistant wall construction shall prior to application. 5. 30" Built-in Microwave with 30" Trim front and rear of house, unless otherwise specified. E. The Electrical Sub shall provide all required can-outs, 2155 Overlook Drive
properly caulked with sealant to prevent water leakage receive 5/8 inch Type 'X' gypsum wallboard, fire-taped. B. Unless otherwise noted, paint at wet rooms and finish Kit sweeps and sleeves, stubs, etc., prior to concrete pour.
around frame. H. Gypsum board finish texture shall be as selected by Manufacturer: By Owner 22 13 16 SANITARY WASTE AND VENT PIPING F. Cable television outlets shall be provided by Electrical Walnut Creek CA
woodwork shall be semi-gloss, and paint at all other
E. Windows shall be dual-glazed. See Title 24 Energy Owner. rooms shall be flat latex. 6. 36" Refrigerator with Overlay Contractor. 94596
Calculations for requirements. Provide tempered safety I. Unless otherwise specified, gypsum board shall be nailed C. Sealant color and type shall be appropriate to the Manufacturer: By Owner A. Provide sanitary waste and vent piping as required, and G. Aluminum wire smaller than No. 6 A.W.G. shall not be Sheet Title:
glazing where shown on drawings and per CRC R308.3 & at all studs, top and bottom plates and blocking as follows: installation. 7. Dishwasher, Panel Ready per state and local requirements having jurisdiction over used in electrical wiring.
R308.4 requirements. Manufacturer: By Owner this project. H. Electrical equipment:
GYPSUM BOARD 09 93 13 EXTERIOR STAINING & TRANSPARENT 8. Disposal with Air Switch B. All soil piping, vent piping and jacks are required to extend - Light fixtures as shown on Drawings:
NAILING FINISHES Manufacturer: By Owner 2'-0" minimum outside of foundation wall. Provide Sewer Manufacturer: Owner to select.
08 16 13 COMPOSITE DOORS connection. - Provide allowance for Landscape lighting.
1/2" thick, edges unblocked 5d cooler nails @ A. Stain and transparent finishes shall be selected by Friedman's Appliance, C. Provide trenching, back fill and compaction as required. Manufacturer: Owner to Select.
A. Exterior Doors: 7" o.c. Owner. Brush-outs of each selected color shall be 2304 Monument Blvd., - General lighting:To be selected by Owner.
22 23 13 INSTANTANEOUS TANKLESS FUEL-FIRED
1. 1-3/4" solid core fiberglass doors submitted for approval prior to application. Pleasant Hill, CA 94523, DOMESTIC WATER HEATER - Owner to select trim kit for all recessed
Manufacturer: Therma tru 1/2" thick, edges blocked, two-ply Base ply: 5d 925-602-1360, Harold. lighting.
Model: as selected by owner. cooler nails @ 7" 09 93 23 INTERIOR STAINING & TRANSPARENT - Exhaust fans:
A. Water heater shall be per Title-24 Calculations tankless as
2. 1-3/4" solid core fiberglass Dutch Door w/ insulated o.c. Face ply: 8d FINISHES Manufacturer: Panasonic
selected by Owner or as noted otherwise on Drawings.
tempered high performance glazing cooler nails @ 8" 11 31 23 RESIDENTIAL LAUNDRY APPLIANCES Model: Whisper Green
B. Provide all plumbing piping, service shut-off, connections
Manufacturer: Simpson o.c. A. Stain and transparent finishes shall be selected by Model #: FV-08VKM1
and venting.
Model: to be selected by owner. Owner. Brush-outs of each selected color shall be A. Provide appliances as shown on Drawings. Products shall C. Comply with all codes having jurisdiction over this project. - Recessed cans at vaulted ceilings to be
3. 1-3/4" solid core fiberglass Single-Lite French 5/8" thick, edges unblocked 6d cooler nails @ submitted for approval prior to application. be selected by Owner. Install all appliances per cathedral style cans
insulated tempered high performance 7" o.c. B. Nailing shall be according per CRC R702.3.5 manufacturer's recommendations. Coordinate with the 22 41 00 RESIDENTIAL PLUMBING FIXTURES Manufacturer: Halo
glazing. requirements. work of other trades as required. - Switching:
Manufacturer: 5/8" thick, edges blocked, two-ply Base ply: 6d cooler A. Provide plumbing fixtures as noted in Section 22 06 40 or Manufacturer: Lutron
nails @ 9" o.c. DIVISION 10 - SPECIALTIES DIVISION 12 - FURNISHINGS as selected by Owner. Model: Maestro - Owner to select finish
Model: .
4. Garage doors: Overhead sectional roll-up doors. Face ply: 8d cooler B. Install fixtures per CPC Chapter 4 & Table 4-1, and local and color.
nails @ 7" o.c. 10.28.16.13 BATH ACCESSORIES 12 36 00 COUNTERTOPS requirements having jurisdiction over this project.
Manufacturer: Garage Doors Inc.
Model: Craftsman Style, Paint grade. C. All soil piping, vent piping and jacks are required to extend I. Bonding water pipes and above-ground metal gas
G. Membrane Penetrations shall comply per CRC 302.4.2 A. Provide residential bath accessories as noted: A. Provide countertops as selected and approved by owner. 2'-0" minimum outside of foundation wall. Provide Sewer piping to the service ground shall be installed per CEC
B. Interior Doors:
(Exception 1) where located in a maximum two-hour Towel Bars/rings, hooks: Baldwin Verify substrate requirements. Coordinate with associated connection. 250.104
fire-resistance-rated walls and partitions by steel electrical Recessed Medicine Cabinets: Robern or as selected by trades. D. Provide trenching, back fill and compaction as required. J. Underground service laterals that are not encased in
1. 1-3/8" solid core Redi Prime 8882 traditional.
boxes shall not exceed 16 square inches in area, provided Owner. E. Mount shower heads at 72" above drain inlet. concrete and that are buried at least 18 inches or more
2. 'Safe-N-Sound' 1-3/8" solid-core
the aggregate area of the openings through the B. Provide solid backing at each location. DIVISION 21 - FIRE SUPPRESSION under grade to have their location identified by a
Manufacturer: Masonite.
Style: smooth, 2-panel, paint grade. membrane does not exceed 100 square inches in any 100 DIVISION 23 - HEATING, VENTILATING, AND warning ribbon that is placed at least 12 inches above
square feet of wall area. The annular space between the 10 28 19.16 SHOWER DOORS 21 13 13 WATER-BASED FIRE SUPPRESSION AIR-CONDITIONING (HVAC) the underground installation.
Prime all surfaces
C. At pocket doors use heavy-duty pocket frame set 1500 by wall membrane and the box shall not exceed 1/8 inch.
A. Unless otherwise specified, shower door and tub A. Provide domestic fire sprinklers per state and local 23 05 00 COMMON WORK RESULTS FOR HVAC
JOHNSON COMPANY.
D. Door hardware per Div 08 71 00. 09 30 00 TILING enclosures shall be frameless, 72 inches tall, 3 8" clear, authorities having jurisdiction over this project.
tempered glass; polish and ease edge. Color and B. Coordinate with other trades for specific system A. The Work includes all labor, materials and equipment
E. Provide 20 min. rated 1 3/8" thick solid wood, or
A. Locations of tile shall be as selected by Owner. Manufacturer to be selected by Owner. requirements. necessary to install, test, adjust and guarantee forced air
honeycombed steel, self-closing & self-latching door with
B. Tile materials, colors, and patterns shall be as selected by B. Tub/shower enclosure with sliding doors shall have nylon heating and/or air conditioning system as per the
smoke seal from garage to habitable space as shown on
Owner . rollers. Enclosures shall be securely installed, caulked DIVISION 22 - PLUMBING Drawings.
Drawings per CRC 302.4
C. Install tile according to the methods from the current Tile with silicone rubber caulk to prevent leakage through B. The Work includes all labor, materials and equipment
F. All door details indicated are generic. Doors shall be
Council of North America Handbook for Tile Installation. frames, and be plumb, true, and free of distortion. 22 05 00 COMMON WORK RESULTS FOR PLUMBING necessary to install, test, adjust and guarantee forced air
installed in accordance with approved manufacturer's
D. Provide matching splash tile, base tile, corner and edge C. Shower enclosures shall have integral walls and receptor heating and/or air conditioning system as per Drawings.
instruction. Fastener size and spacing shall be provided in
trim shapes as required for a complete installation. with clear tempered glass door and size per Drawings as A. The Work includes all labor, materials, tools and C. Ductwork routing shall not destroy or adversely affect the
such instructions and shall be calculated based on
Provide matching accessories as specified by Owner (e.g. selected by Owner. equipment necessary to install complete rough and finish structural integrity of any part of the rough framing.
maximum loads and spacing used in the tests, per CRC
soap dishes, shampoo niches, etc.). D. Shower receptor / compartment shall have a min. of 1,024 plumbing systems as per the Drawings, and as required D. The forced air heating furnace shall be as per Drawings
TABLE R602.3(1)
E. At all tile, provide grout with integral color to match tile; sq.. in. interior area and accommodate 30" dia. circle. All per CPC guidelines. and Title 24 Energy Calculations.
obtain Owner approval of grout color prior to installation. dimensions to be maintained to a point 70" above shower B. The Work includes, but is not limited to, the following: E. Thermostatic regulating devices shall be located as shown
08 53 13 VINYL WINDOWS
Type of grout shall be as indicated in TCNA Method used drain outlet except for valves, shower head, soap dishes, All soil piping, vent piping and jacks at drawings.
for each type of application. Grout joints shall be 1/8 inch and grab bars. Waste piping required to extend 2'-0" minimum F. Ductwork, Grills and registers shall be located as shown
A. Provide fixed and operable vinyl windows as shown on
wide maximum. Thoroughly compact grout. Thoroughly E. Shower doors shall open so as to maintain a 22" wide outside of foundation wall, porch, or deck, or to on Drawings.
Drawings. Contractor to confirm with Owner the
clean grout from face of tile; use no acids. Finished grout unobstructed opening for egress. septic tank G. Duct insulation shall be provided in accordance with Revisions:
manufacturer for the windows and shall coordinate framed
openings as required for specific window manufacturer. shall be slightly concave with no voids. Hot and cold water piping requirements at title 24 Energy Calculations.
10 57 23 CLOSET SHELVING No. By Date
Confirm windows with Owner prior to ordering. Gas piping H. Condenser shall be as shown on Drawings and per Title
09 60 00 FINISH FLOORING Water heaters 24 Energy Calculations.
A. Provide Elfa shelving at Walk-In Closet. Shelving shall Plumbing fixtures and fittings, to be selected by I. Flatwork Sub shall provide concrete condenser pad as
08 71 00 HARDWARE
A. Floor finish materials shall be as selected by Owner and include all components required for installation: 'Easy Owner shown on drawings.
Architect. Hang' Top Tracks, 'Easy Hang' Standards, ventilated Water and gas service piping from meters J. All cutting of framing to be performed by Contractor.
A. Provide door, window and special function hardware.
B. The Subcontractor shall fully prepare subfloor surface shelves, shelf brackets, closet rod and closet rod holder Stubs and elbows for foundation, driveways and
Manufacturer, finish, operation to be determined by
before installation of finish material, including sanding and and wall anchors for 1/2" drywall installation. sidewalks as per Site and Foundation Plans 23 11 23 NATURAL GAS PIPING
Owner.
filling of subfloor if required to insure finish surface is free B. Owner to select style and special components (i.e., Individual fixture shut-off at fixture or manifold.
08 83 13 MIRROR GLASS GLAZING of unreasonable distortion. drawers, etc.). C. All service locations shall be as per the Drawings. A. All below grade gas piping and beyond the building line
C. Seams in all finish floor materials shall be located to C. Install per manufacturer's recommendation. D. In running piping, Plumbing Sub shall not destroy or shall be steel, Schedule 40, black with polyethylene
A. Provide mirrors as determined by owner. minimize the number of seams, and to provide the best adversely affect the structural integrity of any part of the jacket, welded joints.
possible appearance. rough framing. B. Natural gas pipe above grade and within the building line
08 91 19 FIXED LOUVERS E. Plumbing Sub shall provide and install necessary vents shall be steel, Schedule 40 black, malleable iron or forged
and roof jacks to complete installation of respective steel with screwed fittings.
A. Provide fixed GSM venting gable end louvers where equipment. C. Gas piping shall be installed according to code
indicated on drawings. F. Break all vents to rear of roof ridge. requirements as specified in CPC 1211 and local
regulations.
08 95 13 SOFFIT VENTS 22 06 40 PLUMBING FIXTURE SCHEDULE D. Provide clearly marked, easily accessible, and tested shut
off valves as required by the building code.
A. Framing Sub shall install eave, roof vents as required by A. Provide plumbing fixtures as selected by Owner: Scale: AS SHOWN
the Drawings. 23 54 00 CENTRAL HEATING EQUIPMENT
B. Eave vents shall be as noted on the Attic Ventilation 22 11 16 DOMESTIC WATER PIPING Drawn By: TKM
Calculations. A. The forced air heating furnace shall be as per Drawings
Approved: PCV
C. Provide O'Hagin 'cloaked' vents, or equal at roof as shown A. Water service piping from meter to foundation shall be as and Title 24 Energy Calculations.
on Drawings. Install per manufacturers' requirements. per code, one inch minimum or larger as per load and B. Thermostatic regulating devices shall be located as shown Job No.: 21501.01
Vents to match tile color and profile. System to comply pressure requirements. Provide shut-off valve at on the Drawings.
with ICC ES Report # 9650A foundation wall. C. Ductwork, grills and registers shall located as shown on Date: 6/10/15
B. Hot and cold water supply shall be as per code. Tubing Drawings. Color to match adjacent finish.
shall be installed so that no fittings occur under concrete D. Duct insulation shall be provided in accordance with
Sheet No.:
slabs. All runs shall be made so that branch connections requirements per Title 24 Energy Calculations.
occur at fixture locations where fittings can be installed. E. Venting shall be as per CMC 904 requirements.
Systems shall be as free as possible from fittings and
sharp turns. 23 62 00 PACKAGED COMPRESSOR AND CONDENSER
UNITS
A. Condenser shall be as shown on Drawings and per Title
24 Energy Calculations.
B. Flatwork Sub shall provide concrete condenser pad at
SP-2
13 of 30
location shown on Drawings.