Partial Strengthening of R.C Square Columns Using CFRP: HBRC Journal
Partial Strengthening of R.C Square Columns Using CFRP: HBRC Journal
HBRC Journal
http://ees.elsevier.com/hbrcj
KEYWORDS Abstract In some buildings, when quality control is poor, the upper parts of columns have a weak
Fiber; compressive strength, especially in floor zone. Low compressive strength for upper part of the col-
Column; umn will lead to a reduction in bearing capacity of column. Strengthening of this part using tradi-
Strengthening; tional methods such as R.C jackets and steel jackets will not satisfy the architectural conditions.
CFRP; Also the Egyptian code for design and construction of fiber reinforced polymers prevents partial
Concrete strengthening of rectangular columns with fiber laminates.
This study is carried out to investigate the overall behavior of R.C square columns with poor con-
crete at upper part, strengthened with CFRP. The wrapped part of column was the upper part only.
An experimental program was undertaken testing ten square columns 200 · 200 · 2000 mm. One
of them was a control specimen and the other nine specimens were strengthened with CFRP. The
main parameters studied in this research were the compressive strength of the upper part, the height
of the upper poor concrete part, and the height of CFRP wrapped part of column. The experimental
results including mode of failure, ultimate load, concrete strain, and fiber strains were analyzed. The
main conclusion of this research was, partial strengthening of square column using CFRP can be
permitted and gives good results of the column carrying capacity.
ª 2014 Production and hosting by Elsevier B.V. on behalf of Housing and Building National Research
Center.
1687-4048 ª 2014 Production and hosting by Elsevier B.V. on behalf of Housing and Building National Research Center.
http://dx.doi.org/10.1016/j.hbrcj.2014.01.001
280 A.S. Abdel-Hay
The behavior of twelve R.C columns with poor concrete jacket. It was also concluded that the compressive strength
strength at upper part was experimentally investigated by M. of the original column is the main factor which significantly
Rabie [2]. This study concluded that, the ultimate column load affects the ultimate load capacity, and the use of reinforced
decreases as the concrete strength of upper part decreases, concrete jacket with length equal to the length of defected part
while the ultimate column load increases as the height of poor improves the column properties.
concrete part decreases. This research also presents a proposed Mohamed [4] suggested a general mathematical model to
equation for calculating the ultimate load of column taking describe the stress–strain relationship of FRP confined con-
into consideration the effect of poor concrete strength at upper crete. This relationship is applicable to both circular and rect-
part. angular columns, and accounts for the main parameters that
Usama [3] carried out an experimental investigation on influence the stress–strain response.
strengthening of the defected part in the column. The main Yu-Fei wu et al. [5] investigated the effect of cross-sectional
conclusions were that the ultimate load of defected part of a aspect ratio on the strength of CFRP-confined rectangular
column is increased by wrapping its cross section by concrete concrete columns by testing forty-five reinforced concrete
282 A.S. Abdel-Hay
1) Increasing the CFRP jacket height will cause a signifi- The measured CFRP strain was plotted against load as shown
cant increase in both ductility and total energy of in Figs. 12–14. It is clear that, the fiber tensile strain increased
wrapped column. as the upper concrete strength decreased at the same load level.
2) Increasing the top concrete height will cause an increase Also increasing the jacket height will cause an increase in fiber
in ductility and total energy for the same wrapped height strain but there is no effect of upper part height on tensile
of column. strain of carbon fiber laminate.
286 A.S. Abdel-Hay
Conclusions and recommendations [4] Mohamed H. Harajli, Axial stress–strain relationship for FRP
confined circular and rectangular concrete columns, Cem.
Concr. Compos. 938 (2006) 928–948.
The following conclusions are drawn from this work. [5] Yu-Fei Wu, you-Yi Wei, Effect of cross-sectional aspect ratio on
the strength of CFRP-confined rectangular concrete columns,
1) Partial strengthening of square columns with poor con- Eng. Struct. 32 (2010) 32–45.
crete at upper part can be used. It is significant to wrap [6] Manuel A.G. Silva, Behavior of square and circular columns
the poor part only using one layer of CFRP. strengthened with amidic or carbon fibers, Construct. Build.
2) Increasing the jacket height (hj/ht) will provide a higher Mater. 3222 (2011) 3225–3228.
ductility for wrapped columns without significant [7] Lei-Ming Wang, Yu-Fei Wu, Effect of corner radius on the
performance of CFRP-confined square concrete columns: Test,
increase in ultimate load of columns.
Eng. Struct. 493 (2008) 505–530.
3) The corner radius of confined part must be increased as
[8] Baris Binici, Khalid M. Mosalam, Analysis of reinforced
the concrete strength of upper part decreases. concrete columns retrofitted with fiber reinforced polymer
4) The ultimate load of wrapped column increases as the Lamina, Compos. B 265 (2007) 238–276.
concrete strength of upper part increases, while the duc- [9] Okan Ozcan, Baris Binici, Guney Ozcebe, Seismic strengthening
tility decreases. of rectangular reinforced concrete columns using fiber
5) Increasing the top concrete height (ht) causes an increase reinforced polymers, Eng. Struct 964 (2010) 932–973.
in ductility, but the failure load decreases. [10] M. Maalej, S. Tanwongsval, P. Paramasivam, Modelling of
6) Ductile failure mode achieved in specimens of top con- rectangular RC columns strengthened with FRP, Cem. Concr.
crete height of 500 mm, while in case of 350 mm top con- Compos. 263 (2003) 225–276.
[11] Mark F. Green, Luke A. Bisby, Amir Z. Fam, Venkatesh K.R.
crete height, the failure mode was brittle.
Kodur, FRP confined concrete columns: behaviour under
extreme conditions, Cem. Concr. Compos. 928 (2006) 928–937.
[12] J.F. Berthet, E. Ferrier, P. Hamelin, Compressive behavior of
References concrete externally confined by composite jacket, part A:
experimental study, Construct. Build. Mater. 223 (2005) 219–
[1] Ahmed F.A. Ali. Strengthening of rectangular reinforced 232.
concrete columns using fiber glass reinforced polymers. Master [13] M.N.S. Hadi, Behaviour of FRP wrapped normal strength
of Science in structural engineering, faculty of Engineering, concrete columns under eccentric loading, Compos. Struct. 503
Cairo University, 2009. (2006) 511–572.
[2] M. Rabie, Behavior of RC columns with poor concrete strength [14] The Egyptian code for design and construction of fiber
at upper part, Life Sci. J. 9 (2) (2012) 1159–1165. reinforced polymers. ECP 208–2005.
[3] Usama M. Abdel Hameed. Behavior of partially strengthened
reinforced concrete columns under axial loads. Master of science
in structural Engineering, Faculty of Engineering, Cairo
University, 1999.