Download as docx, pdf, or txt
Download as docx, pdf, or txt
You are on page 1of 13

(00:00)

The broadcast is now starting.

(00:02)
All attendees are in listen only mode.

(00:05)
Good afternoon everyone, and thank you for joining us on our call today.

(00:08)
My name is Nicole Daniel Quincy

(00:10)
from Trans Chat and I'll be your moderator this afternoon.

(00:13)
Our webinar topic is testing

(00:15)
and troubleshooting four to 20 million control loops.

(00:18)
The topic is presented by Jim Shields from Flute Corporation,

(00:23)
manager for the Process Calibration Group for Food Corporation.

(00:27)
He is in the Issa and has actively

(00:29)
supported and developed instrumentation curriculum throughout his career.

(00:34)
James worked in the field of calibration
(00:36)
and Metrology field and bench for over 40 years.

(00:40)
You can expect the presentation today

(00:42)
to last roughly 30 minutes and then we'll open it up for questions and answers.

(00:46)
Any time of the presentation, you can send questions through

(00:49)
the question box to the right in your webinar control.

(00:52)
I also want to mention that the webinar is being recorded.

(00:55)
You will each receive a follow up email

(00:57)
with a link to the recorded webinar and the slides of today's presentation.

(01:01)
I want to turn the presentation over to Jim.

(01:05)
Thank you, Nicole.

(01:06)
Welcome, everyone.

(01:08)
Today's topic, as Nicole mentioned,

(01:10)
testing and troubleshooting four to 20 million control loops.

(01:13)
Let's get started.

(01:16)
So we're going to cover what makes a four to 20 milliamp control

(01:20)
loop tick, things that can go wrong with four to 20

(01:25)
milliamp control loops and an in depth discussion on how do you

(01:30)
troubleshoot and what tools give you the answer.

(01:32)
They are the most useful.

(01:34)
Measuring milliamp signals, interpreting the measurements.

(01:37)
We're going to discuss multiple

(01:39)
measurement methods, testing the inputs and outputs of control

(01:43)
systems, PLCs DCs and indicators with milliamps signal sources,
(01:49)
and multiple methods and sourcing approaches will be addressed.

(01:53)
As well as testing one to five volt DC and zero to ten volt DCIO.

(02:01)
We're going to cover measuring loop power supplies, troubleshooting suspected power

(02:05)
supplies that are defective, testing and Isolating transmitter using

(02:10)
substitution power supply testing troubleshooting suspect transmitters

(02:15)
using milliamp simulate as a substitution method.

(02:20)
We're going to cover using a heart smart transmitter as a milliamp signal source,

(02:26)
something often overlooked and functionality built into hard smart

(02:29)
devices, testing an IDP using a four to 20 milliamp signal source and testing

(02:34)
a control valve with a four to 20 milliamp source.

(02:40)
So if we take a look at what makes

(02:44)
a loop tick, we've got a variety of devices in the loop.
(02:52)
A loop is a fairly consistent element in process control.

(02:57)
There's typically always going to be a 24 volts power supply, a transmitter,

(03:02)
of course, the signal wires to make the connection and the input to a control

(03:06)
system that's going to interpret the milliamp signal.

(03:09)
Most often that input to the control

(03:12)
system is going to be some value of resistance that converts the four to 20

(03:16)
milliamps signal to a one to five volt or zero to ten volt DC signal

(03:21)
that the controller or the control system then will decode into the actual value.

(03:28)
The milliamp signal represents a process value on the input to the transmitter.

(03:36)
That input can be a variety of different process parameters.

(03:39)
Temperature, pressure, flow, and PH are a number of common ones.

(03:43)
Virtually any process variable that can be measured and needs to be understood

(03:48)
by the control system can be converted by various types of transmitters.

(03:53)
We refer to this as a two way transmitter

(03:56)
because it is powered by the 24 volts power supply and does not have an external

(04:01)
connection to 120 or 240 volts to get its power.

(04:05)
The indicator controller, as I mentioned, interprets the milliamp signal.

(04:10)
It's scaled down the range of the transmitter and interpreting

(04:14)
the milliamp signal knows what the transmitter is actually measuring

(04:18)
based on its programming and configuration.

(04:35)
So the PV is the primary variable, sometimes referred to as the process

(04:41)
variable, and the example shown here, the process variable is pressure.

(04:47)
So there's pressure developed within the process vessel,
(04:51)
and that pressure needs to be sensed by a pressure transmitter.

(04:57)
In this case, the temperature transmitter.

(04:59)
Now that's highlighted has a temperature

(05:03)
sensor that goes into the process and measures temperature.

(05:06)
Thetransmitter.

(05:09)
The most common types of sensors used are

(05:12)
either thermocouples or RTDs, and they convert the low level nonlinear

(05:18)
signal from the temperature sensor into a four to 20 milliamp signal.

(05:23)
The transmitter in our example has a range of zero to 300 degrees C.

(05:28)
The relationship of the measured

(05:29)
temperature in milliamp is shown in the table at right

(05:33)
and a little bit easier to read in this example table here, you'll notice that as
(05:39)
the temperature increases by the sensor and interpreted

(05:44)
by the transmitter as that temperature increases, the milliamp signal increases.

(05:49)
So, by interpreting the milliamp signal

(05:51)
and knowing the range of the transmitter, you can approximate about what temperature

(05:56)
the transmitter is seeing as it's measuring the temperature in the process.

(06:01)
How accurately that relationship is

(06:04)
between temperature and milliamps is a function of the accuracy

(06:06)
of the calibration of the temperature transmitter itself.

(06:13)
The controller interprets the four to 20 milliamp signal.

(06:17)
As I mentioned,

(06:18)
it may have a 250 LM resistor on its input that converts that milliamp

(06:23)
signal into a one to five or a zero to ten volt DC signal.

(06:28)
That controller is programmed with the range of the transmitter.

(06:31)
So as the million amp signal changes, the temperature controller or the input

(06:36)
card to the control system is programmed to understand the relationship between

(06:41)
milliamps and temperature and then allows the controller to make decisions based

(06:45)
on the temperature that's related to the milliamps signal.

(06:50)
It can open up a control valve, for example, in this example,

(06:55)
applying more gas to a burner to heat the temperature up.

(06:58)
Of course, as the temperature goes up, the milliamp signal goes up.

(07:01)
The temperature control will recognize if the temperature is at or near a set point.

(07:06)
It can then open and close the control

(07:08)
valve that applies the heat to the process fluid in the vessel to keep the process
(07:13)
value for the temperature within allowable limits.

(07:18)
The input output of the control system is

(07:21)
typically going to have a 100 to 250 LM resistor on its input.

(07:28)
Sometimes in a broken loop.

(07:30)
Those input output cards can have fuses that will blow.

(07:33)
So if you have a dead loop you might check the input car to your control system.

(07:37)
There's a few other culprits that we'll talk about in a moment.

(07:43)
So in the example with a pressure transmitter that I started to talk about

(07:46)
a little bit earlier, pressure is the measured PV,

(07:49)
or primary variable that's being measured by the pressure transmitter.

(07:53)
There's a direct connection between the

(07:58)
process vessel and the input to the transmitter.
(08:01)
In a process vessel, the pressure is equal throughout the head space of the vessel.

(08:10)
So the pressure then that is being sent

(08:12)
by the transmitter itself is based on its location adjacent to the vessel.

(08:19)
The pressure then being sent

(08:21)
by the transmitter is the same pressure that's actually inside the vessel itself

(08:24)
via a capillary or some other form of piping or plumbing.

(08:31)
Our transmitter in this example has a range of zero to 100 PSI.

(08:36)
So the transmitter is in perfect adjustment and it's measuring zero PSI.

(08:41)
The milliamps signal being regulated

(08:44)
by the transmitter should be about four milliamps.

(08:46)
As the pressure increases from zero to 100 PSI, you'll see that milliamps signal

(08:51)
increase from four to 20 milliamps depending on the actual pressure that's

(08:56)
being sent on the input of the transmitter.

(08:59)
The indicator controller decodes the four to 20 milliamp signal.

(09:03)
As mentioned, same thing with temperature,

(09:06)
there's a resistance that develops a voltage drop as the four to 20 million

(09:10)
signal changes and the controller interprets that voltage via the D

(09:14)
and the programming that the controller has based on the range of the transmitter

(09:19)
to allow it to understand what the actual pressure is then in the vessel and then

(09:24)
based on a set point in this example, the controller can then close the control

(09:28)
valve to let pressure out of the vessel or close the relief valve if the pressure is

(09:34)
too low to allow the pressure to build to the appropriate pressure value

(09:41)
so things that can go wrong with 40 million control loops.
(09:45)
There's only a finite number of elements, but sometimes it can be interesting to try

(09:49)
to troubleshoot and identify which element is causing a problem.

(09:54)
One culprit that's quite common is wiring problems.

(09:58)
Most process applications.

You might also like