MACLEAN

POWER
SYSTEMS
Suspension Information
Rev: A2, Date: 04/2004

The MPS “Complete Solution”

CR E-Glass Core – MPS uses “Boron Free” Corrosion Resistant E-Glass on all its insulators for its
High Electrical Integrity & High Resistance to acid corrosion. The Boron Free formulation of the
fiberglass core makes it resistant to Nitric Acid attacks. There has never been a brittle facture
failure of a CR E-glass insulator in over 30 years of use.

Silicone Rubber – MPS uses a Silicone formulation that has been utilized since 1984. The Si-O
Molecular Bonds (Inorganic Backbone of Silicone) are very stable and have Bond Strengths
higher than Sunlight, making the silicone resistant to UV degradation. In addition to providing
protection against ultraviolet radiation, electrical aging, and corona effect, silicone exhibits
hydrophobic properties; which provide excellent recovery characteristics to control leakage
currents in highly polluted or seacoast environments.
The MPS silicone rubber formulation has consistently outperformed other silicone formulations
in its hydrophobicity, its hydrophobicity recovery rate, and enhanced electrical properties in
contaminated environments

P-S-T End Fitting Seal – The P-S-T sealing system is a triple seal design with built-in redundancies.
Primary seal – rubber sheath compressed into chamfer of end fitting. Secondary seal – RTV
silicone applied to core / sheath / end fitting interface. Tertiary seal – Final external RTV seal
applied to sheath / end fitting interface. The P-S-T system has clearly shown its superiority to
withstand moisture penetration.

Stacked Shed – The MPS Stacked Shed configuration offers inherent protection against material aging in
critical areas of the sheath and resists the resultant material erosion when installed in highly
contaminated environments (resistance to Water Droplet Corona). In addition, stacked shed
profiles enhance the ability of the insulator to resist mechanical damage in these most critical
areas during transportation and installation.

Suspension Insulator Information – Page SI-I-1 of SI-I-3


USA - Tel: 847-455-0014 Fax: 847-451-0029 y Canada - Tel: 450-698-0520 Fax: 450-692-5670 y www.macleanpower.com
Product specifications are subject to continuous improvement and may be changed at any time without notification.
MACLEAN
POWER
SYSTEMS
Suspension Information
Rev: A2, Date: 04/2004

Catalog Number Definition


S 2 4 8 0 9 7 V A 01
INSULATOR TOWER LINE
TYPE MPS
END FITTING SECTION LENGTH CORONA
[ Specified INTERNAL
TYPE (Inches) RINGS
Mechanical Load ] USE

4 – Y-Clevis Tower Line Tower Line


S1 – 25k SML
5 – Tongue A- None 8” F- 17” 17”
S5 – 30k SML
6 – Clevis B- None 12” G- 8” 12”
S6 – 36k SML
7 – Socket C- None 17” H- 12” 17”
S2 – 50k SML
8 – Ball D- 8” 8” V- 8” 17”
S4 – 80k SML
9 – Eye E- 12” 12” X- None None

S 2 4 8 0 9 7 V A 0 1 MPS Catalog
To order a 97” 50k SML
Number Example Y-Clevis / Ball Insulator with an
MPS Identification
8" Corona Ring on the Line End 8” Corona Ring, the Catalog
Variable Leakage number would be
97" Insulator Section Length
Ball EF on Line End
Y-Clevis EF on Tower End S248097VA01
50k SML Insulator

SUSPENSION INSULATORS
AVAILABLE END FITTINGS

End Fitting
Type

Y-Clevis Tongue Clevis Socket Ball Eye


Insulators ANSI IEC ANSI IEC ANSI IEC ANSI IEC ANSI IEC ANSI IEC
25klb *Yes 52-6 52-6 52-5 52-5 *Yes
S1
120kN *Yes 16-C 16-C 16 16 *Yes

S5 30klb *Yes 52-6 52-6 52-5 52-5 *Yes


36klb *Yes 52-6 52-6 52-8 + 52-8 + *Yes
S6
160kN *Yes 16N 19-L 20 20 *Yes
30klb 52-5 52-5
S2 50klb *Yes 52-12 52-10 52-11 52-11 *Yes
210kN 22N 19-C/22-L 20/24 20/24 *Yes
80klb *Yes
S4
300kN 22-L 24+ 24+ *Yes
+ = Consult MPS for design availability
* = No ANSI or IEC classification available.
Suspension Insulator Information – Page SI-I-2 of SI-I-3
USA - Tel: 847-455-0014 Fax: 847-451-0029 y Canada - Tel: 450-698-0520 Fax: 450-692-5670 y www.macleanpower.com
Product specifications are subject to continuous improvement and may be changed at any time without notification.
MACLEAN
POWER
SYSTEMS
Suspension Information
Rev: A2, Date: 04/2004

Corona Rings for Suspension Insulators

High Voltages can result in unwanted noise (RIV)


and corona. To minimize the effects of corona,
coronar rings are applied to one or both ends of
the insulator (attached onto the end fittings).
Typically, for system voltages 230kV and above a
corona ring or combination of rings is necessary.
However, some applications may require rings at
lower system voltages. Refer to the Corona Ring
section of the Application Guide for detailed
information.

MPS corona rings are designed around the needs of the end user. It is easy to
install, unidirectional (not able to install in the wrong direction), and can be installed or
removed with hot stick tools. By making the ring a one piece design, we have
eliminated the problem of missing or lost parts. This was made possible by designing a
unique clamping mechanism that uses one captive bolt to secure the rinf to the
insulator. Additionally, the clamping section was designed such that the ring can only
be installed in one direction, which eliminates the problem of misapplied rings. As a
final step, the ring was designed with a split (opening) to allow installation with hot stick
tools.

Corona Ring Application Table


138kV 161kV 230kV 345kV 400kV 500kV
Line End None None 8" 12" 12" 17"
Tower End None None None None 8" 8"
Three Ring Diameters are available for use on all suspension insulator styles:
8” Ring, 12” Ring, and 17” Ring

For Insulators 230kV and above, MPS recommends use of Corona Rings. The
Application Table above depicts typical corona ring useage on MPS suspension
Insulators. For corona ring useage on special applications, environments, and
elevations; please contact MPS.

Suspension Insulator Information – Page SI-I-3 of SI-I-3


USA - Tel: 847-455-0014 Fax: 847-451-0029 y Canada - Tel: 450-698-0520 Fax: 450-692-5670 y www.macleanpower.com
Product specifications are subject to continuous improvement and may be changed at any time without notification.
MACLEAN
POWER
SYSTEMS
Suspension Insulators
Rev: A1, Date: 02/2004

S1 Series Insulators
Insulator Strength Ratings
SML RTL
25 klb 12.5 klb
S1
120 kN 60 kN
ø16mm Rod
Electrical Flashover (kV)
Line
Voltage
"S1" Type Section
Length
Dry Arc Leakage
60 Hz CIFO
Weight
kV Catalog No. in [mm] in [mm] in [mm] Dry Wet Pos Neg lbs [kg]
S148040VX33 40.0 29.9 47.7 [1212] 6.5 [2.9]
69 S148040VX06 [1016] [759] 70.9 [1801] 299 270 519 556 8.3 [3.8]
S148040VX21 90.3 [2294] 9.8 [4.4]
S148048VX24 48.0 37.9 78.9 [2004] 8.6 [3.9]
115 S148048VX02 [1219] [963] 121.5 [3086] 375 338 648 690 11.9 [5.4]
S148048VX11 140.9 [3579] 13.9 [6.3]
S148052VX39 52.0 42.9 79.1 [2009] 8.4 [3.8]
115 S148052VX36 [1321] [1090] 117.8 [2992] 413 372 712 756 11.4 [5.2]
S148052VX37 144.9 [3680] 14.0 [6.4]
S148060VX35 60.0 49.9 94.8 [2408] 9.3 [4.2]
138 S148060VX04 [1524] [1267] 141.2 [3586] 490 437 837 886 12.9 [5.9]
S148060VX36 172.2 [4374] 15.3 [6.9]
S148064VX23 64.0 53.9 106.5 [2705] 10.1 [4.6]
161 S148064VX29 [1626] [1369] 168.5 [4280] 528 469 899 949 14.9 [6.8]
S148064VX26 202.0 [5131] 18.1 [8.2]
S148068VX14 68.0 57.9 106.7 [2710] 9.9 [4.5]
161 S148068VX15 [1727] [1471] 164.7 [4183] 566 500 960 1013 14.4 [6.5]
S148068VX17 206.0 [5232] 19.3 [8.8]
S148089VX03 89.0 78.9 150.9 [3833] 12.5 [5.7]
230 S148089VX04 [2261] [2004] 236.0 [5994] 766 657 1276 1335 19.1 [8.7]
S148089VX06 290.2 [7371] 24.2 [11.0]
S148096VX03 96.0 85.9 150.2 [3815] 12.1 [5.5]
230 S148096VX04 [2438] [2182] 239.2 [6076] 832 707 1379 1440 19.0 [8.6]
S148096VX06 293.3 [7450] 23.2 [10.5]
S148104VX07 104.0 93.9 150.4 [3820] 11.8 [5.4]
230 S148104VX08 [2642] [2385] 239.4 [6081] 909 774 1496 1559 18.7 [8.5]
S148104VX09 293.6 [7457] 22.9 [10.4]
S148120VX01 120.0 109.9 228.3 [5799] 17.2 [7.8]
345 S148120VX02 [3048] [2791] 356.0 [9042] 1039 893 1729 1795 27.1 [12.3]
S148120VX02 433.4 [11008] 34.5 [15.6]
S148165VX03 165.0 154.9 331.4 [8418] 23.3 [10.6]
500 S148165VX04 [4191] [3934] 517.1 [13134] 1368 1143 2374 2444 37.3 [16.9]
S148165VX06 613.9 [15593] 47.2 [21.4]
Notes: • Electrical Data is without Corona Rings. For Insulators 230kV & Higher, MPS recommends use of Corona Rings.
* For other ratings or custom insulator designs, contact your local MPS Sales Representative.

Suspension Insulators - Page SI-1 of SI-5


USA - Tel: 847-455-0014 Fax: 847-451-0029 y Canada - Tel: 450-698-0520 Fax: 450-692-5670 y www.macleanpower.com
Product specifications are subject to continuous improvement and may be changed at any time without notification.
MACLEAN
POWER
SYSTEMS
Suspension Insulators
Rev: A1, Date: 02/2004

S5 Series Insulators
Insulator Strength Ratings
SML RTL
30 klb 15 klb
S5
133 kN 66.5 kN

ø18mm Rod
Line Section Electrical Flashover (kV)
Voltage
"S5" Type Length
Dry Arc Leakage
60 Hz CIFO
Weight

kV Catalog No. in [mm] in [mm] in [mm] Dry Wet Pos Neg lbs [kg]
S548040VX05 40.0 28.0 45.6 [1158] 7.0 [3.2]
69 S548040VX07 [1016] [711] 72.7 [1847] 281 253 488 523 9.0 [4.1]
S548040VX08 88.2 [2240] 10.1 [4.6]
S548048VX03 48.0 36.0 76.9 [1953] 9.0 [4.1]
115 S548048VX09 [1219] [914] 119.4 [3033] 357 322 617 658 12.1 [5.5]
S548048VX10 155.3 [3945] 16.5 [7.5]
S548052VX03 52.0 40.0 77.0 [1956] 8.9 [4.0]
115 S548052VX05 [1321] [1016] 119.6 [3038] 395 356 681 725 12.0 [5.4]
S548052VX11 146.9 [3731] 14.9 [6.8]
S548060VX03 60.0 48.0 92.7 [2355] 9.8 [4.4]
138 S548060VX08 [1524] [1219] 143.0 [3632] 471 421 807 855 13.4 [6.1]
S548060VX10 173.6 [4409] 16.8 [7.6]
S548064VX13 64.0 52.0 108.3 [2751] 10.8 [4.9]
161 S548064VX14 [1626] [1321] 166.4 [4227] 509 453 869 819 15.0 [6.8]
S548064VX16 205.7 [5225] 19.2 [8.7]
S548068VX10 68.0 56.0 108.5 [2756] 10.7 [4.9]
161 S548068VX11 [1727] [1422] 166.5 [4229] 547 485 931 982 14.9 [6.8]
S548068VX12 209.7 [5326] 19.4 [8.8]
S548089VX01 89.0 77.0 152.7 [3879] 13.3 [6.0]
230 S548089VX02 [2261] [1956] 237.8 [6040] 747 643 1247 1306 19.4 [8.8]
S548089VX03 296.3 [7526] 25.5 [11.6]
S548096VX03 96.0 84.0 151.9 [3858] 13.1 [5.9]
230 S548096VX07 [2438] [2134] 237.1 [6022] 814 693 1351 1412 19.1 [8.7]
S548096VX09 293.9 [7465] 25.1 [11.4]
S548104VX03 104.0 92.0 152.2 [3866] 12.9 [5.9]
230 S548104VX06 [2642] [2337] 237.3 [6027] 890 759 1468 1531 18.9 [8.6]
S548104VX07 295.4 [7503] 23.1 [10.5]
S548120VX03 120.0 108.0 230.1 [5845] 18.0 [8.2]
345 S548120VX08 [3048] [2743] 357.8 [9088] 1025 879 1701 1767 27.1 [12.3]
S548120VX10 434.2 [11029] 35.4 [16.1]
S548165VX03 165.0 154.5 333.2 [8463] 24.1 [10.9]
500 S548165VX04 [4191] [3924] 518.9 [13180] 1354 1134 2346 2417 37.3 [16.9]
S548165VX05 625.3 [15883] 49.1 [22.3]
Notes: • Electrical Data is without Corona Rings. For Insulators 230kV & Higher, MPS recommends use of Corona Rings.
* For other ratings or custom insulator designs, contact your local MPS Sales Representative.

Suspension Insulators - Page SI-2 of SI-5


USA - Tel: 847-455-0014 Fax: 847-451-0029 y Canada - Tel: 450-698-0520 Fax: 450-692-5670 y www.macleanpower.com
Product specifications are subject to continuous improvement and may be changed at any time without notification.
MACLEAN
POWER
SYSTEMS
Suspension Insulators
Rev: A1, Date: 02/2004

S6 Series Insulators
Insulator Strength Ratings
SML RTL
36 klb 18 klb
S6
160 kN 80 kN

ø18mm Rod
Line Section Electrical Flashover (kV)
Voltage
"S6" Type Length
Dry Arc Leakage
60 Hz CIFO
Weight

kV Catalog No. in [mm] in [mm] in [mm] Dry Wet Pos Neg lbs [kg]
S648040VX01 40.0 28.4 46.0 [1168] 6.9 [3.1]
69 S648040VX03 [1016] [721] 73.1 [1857] 284 257 494 529 8.8 [4.0]
S648040VX03 88.6 [2250] 9.9 [4.5]
S648048VX03 48.0 36.4 77.2 [1961] 8.9 [4.0]
115 S648048VX04 [1219] [925] 119.8 [3043] 360 325 623 665 11.9 [5.4]
S648048VX05 115.7 [2939] 16.3 [7.4]
S648052VX03 52.0 40.4 77.4 [1966] 8.8 [4.0]
115 S648052VX04 [1321] [1026] 119.9 [3045] 399 359 687 731 11.8 [5.4]
S648052VX05 147.2 [3739] 14.7 [6.7]
S648060VX04 60.0 48.4 89.2 [2266] 9.4 [4.3]
138 S648060VX05 [1524] [1229] 143.4 [3642] 475 424 813 861 13.2 [6.0]
S648060VX06 174.0 [475] 16.6 [7.5]
S648064VX05 64.0 52.4 108.7 [2761] 10.7 [4.9]
161 S648064VX06 [1626] [1331] 166.8 [4237] 513 456 875 925 14.8 [6.7]
S648064VX07 206.1 [5235] 19.0 [8.6]
S648068VX02 68.0 56.4 105.0 [2667] 10.3 [4.7]
161 S648068VX03 [1727] [1433] 166.9 [4239] 551 488 936 988 14.7 [6.7]
S648068VX05 210.1 [5337] 19.2 [8.7]
S648089VX05 89.0 77.4 153.1 [3889] 13.1 [5.9]
230 S648089VX06 [2261] [1966] 238.2 [6050] 751 646 1253 1312 19.2 [8.7]
S648089VX08 296.7 [7536] 25.4 [11.5]
S648096VX04 96.0 84.4 152.6 [3876] 12.9 [5.9]
230 S648096VX05 [2438] [2144] 237.7 [6038] 818 696 1356 1417 18.9 [8.6]
S648096VX07 291.9 [7414] 24.9 [11.3]
S648104VX01 104.0 92.4 152.6 [3876] 12.7 [5.8]
230 S648104VX02 [2642] [2347] 237.7 [6038] 894 762 1474 1536 18.7 [8.5]
S648104VX03 291.9 [7414] 22.6 [10.3]
S648120VX01 120.0 108.4 226.6 [5756] 17.5 [7.9]
345 S648120VX02 [3048] [2753] 358.2 [9098] 1028 881 1707 1772 26.9 [12.2]
S648120VX04 440.1 [11179] 35.7 [16.2]
S648165VX01 165.0 153.4 333.5 [8471] 23.9 [10.8]
500 S648165VX02 [4191] [3896] 519.3 [13190] 1357 1136 2352 2422 37.1 [16.8]
S648165VX03 625.7 [15893] 49.0 [22.2]
Notes: • Electrical Data is without Corona Rings. For Insulators 230kV & Higher, MPS recommends use of Corona Rings.
* For other ratings or custom insulator designs, contact your local MPS Sales Representative.

Suspension Insulators - Page SI-3 of SI-5


USA - Tel: 847-455-0014 Fax: 847-451-0029 y Canada - Tel: 450-698-0520 Fax: 450-692-5670 y www.macleanpower.com
Product specifications are subject to continuous improvement and may be changed at any time without notification.
MACLEAN
POWER
SYSTEMS
Suspension Insulators
Rev: A1, Date: 02/2004

S2 Series Insulators
Insulator Strength Ratings
SML RTL
50 klb 25 klb
S2
210 kN 105 kN

Ø24mm Rod

Line Section Electrical Flashover (kV)


Voltage
"S2" Type Length
Dry Arc Leakage
60 Hz CIFO
Weight

kV Catalog No. in [mm] in [mm] in [mm] Dry Wet Pos Neg lbs [kg]
S248056VX07 56.0 42.8 75.9 [1928] 12.5 [5.7]
115 S248056VX08 [1422] [1087] 118.0 [2997] 422 379 726 771 15.9 [7.2]
S248056VX09 144.9 [3680] 18.0 [8.2]
S248062VX13 62.0 48.8 93.4 [2372] 13.9 [6.3]
138 S248063VX14 [1575] [1240] 143.2 [3637] 479 428 820 869 17.9 [8.1]
S248063VX16 178.6 [4536] 21.1 [9.6]
S248068VX07 68.0 54.8 107.1 [2720] 13.9 [6.3]
161 S248068VX08 [1727] [1392] 168.3 [4275] 479 428 820 869 17.9 [8.1]
S248068VX09 187.5 [4763] 21.1 [9.6]
S248080VX10 80.0 66.8 107.6 [2733] 14.9 [6.8]
161 S248080VX02 [2032] [1697] 165.0 [4191] 536 476 913 964 19.5 [8.8]
S248080VX11 207.2 [5263] 22.8 [10.3]
S248092VX02 92.0 78.8 150.2 [3815] 18.2 [8.3]
230 S248092VX03 [2337] [2002] 238.3 [6053] 765 657 1275 1334 25.2 [11.4]
S248092VX05 289.6 [7356] 30.0 [13.6]
S248097VX05 97.0 83.8 151.4 [3846] 18.3 [8.3]
230 S248097VX06 [2464] [2129] 239.5 [6083] 813 692 1349 1409 25.3 [11.5]
S248097VX08 303.6 [7711] 31.1 [14.1]
S248106VX01 106.0 92.8 152.7 [3879] 18.3 [8.3]
230 S248106VX02 [2692] [2357] 237.0 [6020] 898 766 1481 1544 25.0 [11.3]
S248106VX03 294.4 [7478] 29.6 [13.4]
S248118VX02 118.0 104.8 226.0 [5740] 24.1 [10.9]
345 S248118VX03 [2997] [2662] 356.2 [9047] 1002 855 1656 1721 34.4 [15.6]
S248118VX05 444.7 [11295] 43.4 [19.7]
S248124VX02 124.0 110.8 228.2 [5796] 24.2 [11.0]
345 S248124VX03 [3150] [2814] 354.7 [9009] 1046 899 1742 1808 34.3 [15.6]
S248124VX05 438.6 [11140] 42.0 [19.1]
S248130VX02 130.0 116.8 226.5 [5753] 24.0 [10.9]
345 S248130VX03 [3302] [2967] 356.7 [9060] 1090 943 1829 1896 34.4 [15.6]
S248130VX05 444.6 [11293] 42.5 [19.3]
S248142VX06 142.0 128.8 334.3 [8491] 32.5 [14.7]
500 S248142VX07 [3607] [3272] 510.6 [12969] 1178 1017 2002 2070 47.8 [21.7]
S248142VX08 566.9 [14399] 53.5 [24.3]
Notes: • Electrical Data is without Corona Rings. For Insulators 230kV & Higher, MPS recommends use of Corona Rings.
* For other ratings or custom insulator designs, contact your local MPS Sales Representative.

Suspension Insulators - Page SI-4 of SI-5


USA - Tel: 847-455-0014 Fax: 847-451-0029 y Canada - Tel: 450-698-0520 Fax: 450-692-5670 y www.macleanpower.com
Product specifications are subject to continuous improvement and may be changed at any time without notification.
MACLEAN
POWER
SYSTEMS
Suspension Insulators
Rev: A1, Date: 02/2004

S4 Series Insulators
Insulator Strength Ratings
SML RTL
80 klb 40 klb
S4
300 kN 150 kN

Ø32mm Rod

Line Section Electrical Flashover (kV)


Voltage
"S4" Type Length
Dry Arc Leakage
60 Hz CIFO
Weight

kV Catalog No. in [mm] in [mm] in [mm] Dry Wet Pos Neg lbs [kg]
S499097VX05 97.0 78.7 149.4 [3795] 30.0 [13.6]
230 S499097VX06 [2464] [1999] 138.7 [3523] 764 656 1272 1332 35.8 [16.2]
S499097VX07 296.4 [7529] 39.6 [18.0]
S499106VX03 106.0 87.7 153.2 [3891] 30.7 [13.9]
230 S499106VX04 [2692] [2228] 237.2 [6025] 849 719 1405 1467 36.2 [16.4]
S499106VX05 294.9 [7490] 40.0 [18.1]
S499118VX04 118.0 99.7 228.2 [5796] 36.3 [16.5]
345 S499118VX05 [2997] [2532] 354.2 [8997] 964 817 1581 1645 44.5 [20.2]
S499118VX06 432.9 [10996] 49.7 [22.5]
S499124VX06 124.0 105.7 228.9 [5814] 36.6 [16.6]
345 S499124VX07 [3150] [2685] 354.9 [9014] 1008 862 1668 1733 44.9 [20.4]
S499124VX08 444.2 [11283] 50.7 [23.0]
S499130VX03 130.0 111.7 229.7 [5834] 37.0 [16.8]
345 S499130VX04 [3302] [2837] 355.7 [9035] 1052 906 1755 1821 45.3 [20.5]
S499130VX05 439.7 [11168] 50.8 [23.0]
S499142VX02 142.0 123.7 330.9 [8405] 44.3 [20.1]
500 S499142VX03 [3607] [3142] 414.9 [10538] 1140 989 1927 1995 49.8 [22.6]
S499142VX05 540.9 [13739] 58.1 [26.4]
S499152VX05 152.0 133.7 335.7 [8527] 45.2 [20.5]
500 S499152VX06 [3861] [3396] 414.9 [10538] 1213 1042 2071 2140 50.3 [22.8]
S499152VX07 587.7 [14928] 61.7 [28.0]
S499165VX10 165.0 146.7 332.9 [8456] 45.7 [20.7]
500 S499165VX11 [4191] [3726] 416.9 [10589] 1308 1106 2257 2327 51.2 [23.2]
S499165VX12 642.7 [16325] 66.0 [29.9]
S499182VX06 182.0 163.7 334.2 [8489] 46.7 [21.2]
500 S499182VX07 [4623] [4158] 418.2 [10622] 1432 1179 2498 2569 52.2 [23.7]
S499182VX08 643.9 [16355] 67.0 [30.4]
Notes: • Electrical Data is without Corona Rings. For Insulators 230kV & Higher, MPS recommends use of Corona Rings.
* For other ratings or custom insulator designs, contact your local MPS Sales Representative.

Suspension Insulators - Page SI-5 of SI-5


USA - Tel: 847-455-0014 Fax: 847-451-0029 y Canada - Tel: 450-698-0520 Fax: 450-692-5670 y www.macleanpower.com
Product specifications are subject to continuous improvement and may be changed at any time without notification.
MACLEAN
POWER
SYSTEMS
Line Post Information
Rev: A1, Date: 02/2004

This Page of the


MacLean Power Systems
On-Line Catalog is currently
Under Construction

We expect this page to be active in the near future.


Please check again soon.

Line Post Information – Page LP-I-1 of LP-I-1


USA - Tel: 847-455-0014 Fax: 847-451-0029 y Canada - Tel: 450-698-0520 Fax: 450-692-5670 y www.macleanpower.com
Product specifications are subject to continuous improvement and may be changed at any time without notification.
MACLEAN
POWER Line Post Insulators
SYSTEMS
Rev: A2, Date: 04/2004

H1-C1 Series Insulators: [2.0” Rod Dia.]

Fixed Gain Base


Drop Tongue – Fixed Gain Base
Line Section Electrical Flashover (kV)
Voltage
MDCL * Catalog No. Length
Dry Arc Leakage
60 Hz CIFO
Weight

kV lbs [kN] in [mm] in [mm] in [mm] Dry Wet Pos Neg lbs [kg]
1721 H1C1029VX01 29.0 21.7 49.5 [1257] 38.2 [17.3]
69 [7.7] H1C1029VX02 [737] [551] 74.5 [1892]
219 198 371 462
42.2 [19.1]
1401 H1C1034VX01 34.0 26.8 44.6 [1133] 37.8 [17.1]
69 [6.2]
H1C1034VX02
[864] [681]
74.6 [1895] 265 243 452 547 42.6 [19.3]
H1C1034VX03 89.6 [2276] 45.1 [20.5]
1152 H1C1040VX01 40.0 32.9 45.8 [1163] 38.4 [17.4]
69 [5.1]
H1C1040VX02
[1016] [836]
70.8 [1798] 321 296 549 642 42.5 [19.3]
H1C104VX03 90.8 [2306] 45.8 [20.8]
1042 H1C1044VX01 44.0 37.0 79.9 [2029] 44.3 [20.1]
115 [4.6]
H1C1044VX02
[1118] [940]
119.9 [3045] 358 331 614 702 50.8 [23.0]
H1C1044VX03 144.9 [3680] 54.9 [24.9]
913 H1C1049VX01 49.0 42.1 80.0 [2032] 44.7 [20.3]
115 [4.1]
H1C1049VX02
[1245] [1069]
120.0 [3048] 403 373 695 771 51.2 [23.2]
H1C1049VX03 150.0 [3810] 56.1 [25.4]
821 H1C1054VX01 54.0 47.2 95.1 [2416] 47.6 [21.6]
138 [3.7]
H1C1054VX02
[1372] [1199]
145.1 [3686] 449 415 776 836 55.7 [25.3]
H1C1054VX03 180.1 [4575] 61.4 [27.9]
728 H1C1060VX01 60.0 53.4 106.2 [2697] 49.9 [22.6]
161 [3.2]
H1C1060VX02
[1524] [1356]
166.2 [4221] 503 464 873 920 59.6 [27.0]
H1C1060VX03 206.2 [5237] 66.1 [30.0]

Notes: • STL (Specified Tensile Load) – 3,500 Lbs. [15.6 kN]


• Electrical Data is without Corona Rings. For Insulators 230kV & Higher, MPS recommends use of Corona Rings.
* For other ratings or custom insulator designs, contact your local MPS Sales Representative.

Line Post Insulators – Page LP-1 of LP-9


USA - Tel: 847-455-0014 Fax: 847-451-0029 y Canada - Tel: 450-698-0520 Fax: 450-692-5670 y www.macleanpower.com
Product specifications are subject to continuous improvement and may be changed at any time without notification.
MACLEAN
POWER Line Post Insulators
SYSTEMS
Rev: A2, Date: 04/2004

H1-C2 Series Insulators: [2.0” Rod Dia.]

Fixed Gain Base

Trunnion – Fixed Gain Base


Line Section Electrical Flashover (kV)
Voltage
MDCL * Catalog No. Length
Dry Arc Leakage
60 Hz CIFO
Weight

kV lbs [kN] in [mm] in [mm] in [mm] Dry Wet Pos Neg lbs [kg]
1720 H1C2029VX02 29.0 21.4 49.2 [1250] 38.3 [17.4]
69 [7.7] H1C2029VX04 [737] [544] 74.2 [1885]
216 195 367 457
42.4 [19.2]
1400 H1C2034VX03 34.0 26.5 44.3 [1125] 38.0 [17.2]
69 [6.2]
H1C2034VX05
[864] [673]
74.3 [1887] 263 240 447 542 42.8 [19.4]
H1C2034VX04 89.3 [2268] 45.3 [20.5]
1152 H1C2040VX01 40.0 32.6 45.5 [1156] 38.6 [17.5]
69 [5.1]
H1C2040VX02
[1016] [828]
70.5 [1791] 318 293 545 638 42.7 [19.4]
H1C2040VX03 90.5 [2299] 45.9 [20.8]
1041 H1C2044VX01 44.0 36.7 79.6 [2022] 44.5 [20.2]
115 [4.6] H1C2044VX02 [1118] [932] 119.6 [3038]
355 328 609 697
51.0 [23.1]
912 H1C2049VX03 49.0 41.8 79.7 [2024] 44.9 [20.4]
115 [4.1]
H1C2049VX04
[1245] [1062]
119.7 [3040] 401 371 691 767 51.4 [23.3]
H1C2049VX06 149.7 [3802] 56.3 [25.5]
821 H1C2054VX04 54.0 46.9 94.8 [2408] 47.8 [21.7]
138 [3.7]
H1C2054VX05
[1372] [1191]
144.8 [3678] 446 413 772 833 55.9 [25.4]
H1C2054VX06 179.7 [4564] 61.6 [27.9]
728 H1C2060VX01 60.0 53.1 105.9 [2690] 50.1 [22.7]
161 [3.2]
H1C2060VX02
[1524] [1349]
165.9 [4214] 500 462 869 915 59.8 [27.1]
H1C2060VX03 205.9 [5230] 66.3 [30.1]

Notes: • STL (Specified Tensile Load) – 5,000 Lbs. [22.2 kN]


• Electrical Data is without Corona Rings. For Insulators 230kV & Higher, MPS recommends use of Corona Rings.
* For other ratings or custom insulator designs, contact your local MPS Sales Representative.

Line Post Insulators – Page LP-2 of LP-9


USA - Tel: 847-455-0014 Fax: 847-451-0029 y Canada - Tel: 450-698-0520 Fax: 450-692-5670 y www.macleanpower.com
Product specifications are subject to continuous improvement and may be changed at any time without notification.
MACLEAN
POWER Line Post Insulators
SYSTEMS
Rev: A2, Date: 04/2004

H1-91 Series Insulators: [2.0” Rod Dia.]

Bendable Gain Base

Drop Tongue – Bendable Gain Base


Line Section Electrical Flashover (kV)
Voltage
MDCL * Catalog No. Length
Dry Arc Leakage
60 Hz CIFO
Weight

kV lbs [kN] in [mm] in [mm] in [mm] Dry Wet Pos Neg lbs [kg]
1760 H191029VX01 29.0 22.2 50.1 [1273] 36.1 [16.4]
69 [7.8]
H191029VX02
[737] [564]
75.1 [1908] 224 203 380 471 40.1 [18.2]
H191029VX03 80.1 [2035] 41.0 [18.6]
1433 H191034VX01 34.0 27.3 50.2 [1275] 36.5 [16.6]
69 [6.4]
H191034VX03
[864] [693]
75.2 [1910] 270 248 460 555 40.6 [18.4]
H191034VX04 90.2 [2291] 43.0 [19.5]
1174 H191040VX01 40.0 33.5 46.3 [1176] 36.4 [16.5]
69 [5.2]
H191040VX03
[1016] [851]
71.3 [1811] 326 301 558 650 40.4 [18.3]
H191040VX03 91.3 [2319] 43.7 [19.8]
1051 H191044VX01 44.0 37.5 80.4 [2042] 42.2 [19.1]
115 [4.7]
H191044VX02
[1118] [953]
120.4 [3058] 362 335 623 709 48.7 [22.1]
H191044VX03 145.4 [3693] 52.8 [23.9]
923 H191049VX01 49.0 42.7 80.5 [2045] 42.7 [19.4]
115 [4.1]
H191049VX02
[1245] [1085]
120.5 [3061] 408 378 704 778 49.1 [22.3]
H191049VX03 150.5 [3823] 54.0 [24.5]
828 H191054VX01 54.0 47.8 95.6 [2428] 45.5 [20.6]
138 [3.7]
H191054VX02
[1372] [1214]
145.6 [3698] 453 420 785 843 53.6 [24.3]
H191054VX03 180.6 [4587] 59.3 [26.9]
736 H191060VX01 60.0 53.9 106.7 [2710] 47.8 [21.7]
161 [3.3]
H191060VX02
[1524] [1369]
166.7 [4234] 507 469 882 928 57.6 [26.1]
H191060VX03 206.7 [5250] 64.0 [29.0]

Notes: • STL (Specified Tensile Load) – 7,000 Lbs. [31.1 kN]


• Electrical Data is without Corona Rings. For Insulators 230kV & Higher, MPS recommends use of Corona Rings.
* For other ratings or custom insulator designs, contact your local MPS Sales Representative.

Line Post Insulators – Page LP-3 of LP-9


USA - Tel: 847-455-0014 Fax: 847-451-0029 y Canada - Tel: 450-698-0520 Fax: 450-692-5670 y www.macleanpower.com
Product specifications are subject to continuous improvement and may be changed at any time without notification.
MACLEAN
POWER Line Post Insulators
SYSTEMS
Rev: A2, Date: 04/2004

NPKG Series Insulators: [2.5” Rod Dia.]

Fixed Gain Base


[To change from a gain
base to a flat base,
Change the “G” to a “F” as
per catalog definition]

Trunnion – Fixed Gain Base


Line Section Electrical Flashover (kV)
MDCL Catalog No. Dry Arc Leakage Weight
Voltage Length 60 Hz CIFO
kV lbs [kN] in [mm] in [mm] in [mm] Dry Wet Pos Neg lbs [kg]
2500 35.0 25.8 72.4 45.3
69 [11.1]
NPKG30XH016S0
[889] [655] [1839]
256 234 436 530
[20.5]
2417 40.9 31.8 90.7 49.4
69 [10.8]
NPKG30XH020S0
[1039] [808] [2304]
311 287 532 626
[22.4]
2140 45.4 36.4 104.5 52.4
115 [9.5]
NPKG30XH023S0
[1153] [925] [2654]
352 325 604 692
[23.8]
115 1790 52.8 44.0 127.5 57.5
NPKG30XH028S0 419 388 724 795
138 [8.0] [1341] [1118] [3239] [26.1]
1573 58.7 50.0 145.9 61.5
138 [7.0]
NPKG30XH032S0
[1491] [1270] [3706]
473 438 821 869
[27.9]
138 1495 61.7 53.1 155.1 63.6
NPKG30XH034S0 500 462 868 915
161 [6.7] [1567] [1349] [3940] [28.8]
1337 67.6 59.1 173.5 67.6
161 [5.9]
NPKG30XH038S0
[1717] [1501] [4407]
553 510 964 1006
[30.7]
1280 70.6 62.1 182.6 69.6
161 [5.7]
NPKG30XH040S0
[1793] [1577] [4638]
579 533 1011 1051
[31.6]
1201 75.0 66.7 196.4 72.7
230 [5.3]
NPKG30XH043S0
[1905] [1694] [4989]
618 567 1082 1118
[33.0]
1055 83.9 75.8 224.0 78.8
230 [4.7]
NPKG30XH049S0
[2131] [1925] [5690]
696 635 1222 1251
[35.7]

Notes: • STL (Specified Tensile Load) – 5,000 Lbs. [22.2 kN]


• Electrical Data is without Corona Rings. For Insulators 230kV & Higher, MPS recommends use of Corona Rings.
* For other ratings or custom insulator designs, contact your local MPS Sales Representative.

Line Post Insulators – Page LP-4 of LP-9


USA - Tel: 847-455-0014 Fax: 847-451-0029 y Canada - Tel: 450-698-0520 Fax: 450-692-5670 y www.macleanpower.com
Product specifications are subject to continuous improvement and may be changed at any time without notification.
MACLEAN
POWER Line Post Insulators
SYSTEMS
Rev: A2, Date: 04/2004

NBKG Series Insulators: [2.5” Rod Dia.]

Bendable Gain Base


[To change from a gain base to
a flat base, Change the “G” to
a “F” as per catalog definition]

Trunnion – Bendable Gain Base


Line Section Electrical Flashover (kV)
MDCL Catalog No. Dry Arc Leakage Weight
Voltage Length 60 Hz CIFO
kV lbs [kN] in [mm] in [mm] in [mm] Dry Wet Pos Neg lbs [kg]
2500 35.2 25.8 72.4 57.1
69 [11.1]
NBKG30XH016S0
[894] [655] [1839]
256 234 436 530
[25.9]
2492 41.1 31.8 90.7 61.1
69 [11.1]
NBKG30XH020S0
[1044] [808] [2304]
311 287 532 626
[27.7]
2191 45.6 36.4 104.5 64.2
115 [9.7]
NBKG30XH023S0
[1158] [925] [2654]
352 325 604 692
[29.1]
115 1826 53.0 44.0 127.5 69.2
NBKG30XH028S0 419 388 724 795
138 [8.1] [1346] [1118] [3239] [31.4]
1598 58.9 50.0 145.9 73.3
138 [7.1]
NBKG30XH032S0
[1496] [1270] [3706]
473 438 821 869
[33.2]
138 1521 61.9 53.1 155.1 75.3
NBKG30XH034S0 500 462 868 915
161 [6.8] [1572] [1349] [3940] [34.2]
1364 67.8 59.1 173.5 79.4
161 [6.1]
NBKG30XH038S0
[1722] [1501] [4407]
553 510 964 1006
[36.0]
1299 70.8 62.1 182.6 81.4
161 [5.8]
NBKG30XH040S0
[1798] [1577] [4638]
579 533 1011 1051
[36.9]
1220 75.2 66.7 196.4 84.4
230 [5.4]
NBKG30XH043S0
[1910] [1694] [4989]
618 567 1082 1118
[38.3]
1070 84.1 75.8 224.0 90.5
230 [4.8]
NBKG30XH049S0
[2136] [1925] [5690]
696 635 1222 1251
[41.1]

Notes: • STL (Specified Tensile Load) – 5,000 Lbs. [22.2 kN]


• Electrical Data is without Corona Rings. For Insulators 230kV & Higher, MPS recommends use of Corona Rings.

Line Post Insulators – Page LP-5 of LP-9


USA - Tel: 847-455-0014 Fax: 847-451-0029 y Canada - Tel: 450-698-0520 Fax: 450-692-5670 y www.macleanpower.com
Product specifications are subject to continuous improvement and may be changed at any time without notification.
MACLEAN
POWER Line Post Insulators
SYSTEMS
Rev: A2, Date: 04/2004
* For other ratings or custom insulator designs, contact your local MPS Sales Representative.
NBSG Series Insulators: [2.5” Rod Dia.]

Bendable Gain Base


[To change from a gain base to
a flat base, Change the “G” to
a “F” as per catalog definition]

Drop Tongue – Bendable Gain Base


Line Section Electrical Flashover (kV)
MDCL Catalog No. Dry Arc Leakage Weight
Voltage Length 60 Hz CIFO
kV lbs [kN] in [mm] in [mm] in [mm] Dry Wet Pos Neg lbs [kg]
3125 34.8 25.8 72.4 54.4
69 [13.9]
NBSG30XH016S0
[884] [655] [1839]
256 234 436 530
[24.7]
2540 40.7 31.8 90.7 59.3
69 [11.3]
NBSG30XH020S0
[1034] [808] [2304]
311 287 532 626
[26.9]
2223 45.2 36.4 104.5 61.1
115 [9.9]
NBSG30XH023S0
[1148] [925] [2654]
352 325 604 692
[27.7]
115 1847 52.6 44.0 127.5 67.4
NBSG30XH028S0 419 388 724 795
138 [8.2] [1336] [1118] [3239] [30.6]
1619 58.5 50.0 145.9 71.4
138 [7.2]
NBSG30XH032S0
[1486] [1270] [3706]
473 438 821 869
[32.4]
138 1535 61.5 53.1 155.1 73.5
NBSG30XH034S0 500 462 868 915
161 [6.8] [1562] [1349] [3940] [33.3]
1380 67.4 59.1 173.5 77.5
161 [6.1]
NBSG30XH038S0
[1712] [1501] [4407]
553 510 964 1006
[35.2]
1308 70.4 62.1 182.6 79.5
161 [5.8]
NBSG30XH040S0
[1788] [1577] [4638]
579 533 1011 1051
[36.1]
1230 74.8 66.7 196.4 82.6
230 [5.5]
NBSG30XH043S0
[1900] [1694] [4989]
618 567 1082 1118
[37.5]
1076 83.7 75.8 224.0 88.7
230 [4.8]
NBSG30XH049S0
[2126] [1925] [5690]
696 635 1222 1251
[40.2]

Notes: • STL (Specified Tensile Load) – 15,000 Lbs. [66.7 kN]


• Electrical Data is without Corona Rings. For Insulators 230kV & Higher, MPS recommends use of Corona Rings.
* For other ratings or custom insulator designs, contact your local MPS Sales Representative.

Line Post Insulators – Page LP-6 of LP-9


USA - Tel: 847-455-0014 Fax: 847-451-0029 y Canada - Tel: 450-698-0520 Fax: 450-692-5670 y www.macleanpower.com
Product specifications are subject to continuous improvement and may be changed at any time without notification.
MACLEAN
POWER Line Post Insulators
SYSTEMS
Rev: A2, Date: 04/2004

H2-91 Series Insulators: [2.5” Rod Dia.]

Bendable Gain Base

Drop Tongue – Bendable Gain Base

Line Section Electrical Flashover (kV)


MDCL Catalog No. Dry Arc Leakage Weight
Voltage Length 60 Hz CIFO
kV lbs [kN] in [mm] in [mm] in [mm] Dry Wet Pos Neg lbs [kg]
1095 H291081VX06 81.0 73.3 152.8 [3881] 71.6 [32.5]
230 [4.9]
H291081VX05
[2057] [1862]
238.8 [6066] 675 617 1184 1215 83.6 [37.9]
H291081VX03 279.6 [7102] 89.3 [40.5]
1019 H291086VX09 86.0 78.4 153.3 [3894] 72.9 [33.1]
230 [4.5]
H291086VX10
[2184] [1991]
239.4 [6081] 719 654 1262 1289 84.8 [38.5]
H291086VX11 298.3 [7577] 93.0 [42.2]
979 H291090VX15 90.0 82.5 152.9 [3884] 73.7 [33.4]
230 [4.4]
H291090VX16
[2286] [2096]
239.0 [6071] 753 683 1324 1348 85.7 [38.9]
H291090VX17 297.9 [7567] 93.9 [42.6]
907 H291097VX07 97.0 89.7 155.5 [3950] 75.7 [34.3]
230 [4.0]
H291097VX08
[2464] [2278]
241.6 [6137] 813 733 1431 1450 87.7 [39.8]
H291097VX09 296.0 [7518] 95.2 [43.2]

Notes: • STL (Specified Tensile Load) – 15,000 Lbs. [66.7 kN]


• Electrical Data is without Corona Rings. For Insulators 230kV & Higher, MPS recommends use of Corona Rings.
* For other ratings, designs with corona rings, or custom insulator designs, contact your local MPS Sales Representative.

Line Post Insulators – Page LP-7 of LP-9


USA - Tel: 847-455-0014 Fax: 847-451-0029 y Canada - Tel: 450-698-0520 Fax: 450-692-5670 y www.macleanpower.com
Product specifications are subject to continuous improvement and may be changed at any time without notification.
MACLEAN
POWER Line Post Insulators
SYSTEMS
Rev: A2, Date: 04/2004

H3-91 Series Insulators: [3.0” Rod Dia.]

Bendable Gain Base

Drop Tongue – Bendable Gain Base


Line Section Electrical Flashover (kV)
Voltage
MDCL * Catalog No. Length
Dry Arc Leakage
60 Hz CIFO
Weight

kV lbs [kN] in [mm] in [mm] in [mm] Dry Wet Pos Neg lbs [kg]
3263 H391051VX06 51.0 39.3 75.9 [1928] 76.0 [34.5]
115 [14.5]
H391051VX07
[1295] [998]
119.5 [3035] 378 350 651 734 84.7 [38.4]
H391051VX08 148.5 [3772] 90.5 [41.1]
2674 H291060VX14 60.0 48.7 95.0 [2413] 82.9 [37.6]
138 [11.9]
H391060VX15
[1524] [1237]
143.4 [3642] 462 427 800 854 92.6 [42.0]
H391060VX16 177.3 [4503] 99.4 [45.1]
2239 H391069VX05 69.0 58.2 109.2 [2774] 88.8 [40.3]
161 [10.0]
H391069VX09
[1753] [1478]
167.3 [4249] 544 502 949 992 100.4 [45.5]
H391069VX10 206.0 [5232] 108.2 [49.1]
2060 H391075VX08 75.0 64.4 110.7 [2812] 91.2 [41.4]
161 [9.2]
H391075VX06
[1905] [1636]
168.8 [4288] 599 550 1047 1085 102.8 [46.6]
H391075VX07 207.5 [5271] 110.5 [50.1]
1852 H391082VX04 82.0 71.8 151.9 [3858] 101.8 [46.2]
230 [8.2]
H391082VX05
[2083] [1824]
239.0 [6071] 662 605 1160 1192 119.2 [54.1]
H391082VX01 287.4 [7300] 128.9 [58.5]
1726 H391087VX06 87.0 77.0 152.3 [3868] 103.6 [47.0]
230 [7.7]
H391087VX07
[2210] [1956]
239.4 [6081] 706 643 1240 1268 121.0 [54.9]
H391087VX08 297.5 [7557] 132.6 [60.1]
1671 H391090VX25 90.0 80.1 155.4 [3947] 105.2 [47.7]
230 [7.4]
H391090VX26
[2286] [2035]
237.7 [6038] 733 666 1288 1313 121.7 [55.2]
H391090VX27 295.8 [7513] 133.3 [60.5]
1414 H391104VX07 104.0 94.8 228.1 [5794] 124.5 [56.5]
345 [6.3]
H391104VX08
[2642] [2408]
358.8 [9114] 856 767 1505 1522 150.7 [68.4]
H291104VX09 387.8 [9850] 156.5 [71.0]

Notes: • STL (Specified Tensile Load) – 20,000 Lbs. [89.0 kN]


• Electrical Data is without Corona Rings. For Insulators 230kV & Higher, MPS recommends use of Corona Rings.
* For other ratings or custom insulator designs, contact your local MPS Sales Representative.

Line Post Insulators – Page LP-8 of LP-9


USA - Tel: 847-455-0014 Fax: 847-451-0029 y Canada - Tel: 450-698-0520 Fax: 450-692-5670 y www.macleanpower.com
Product specifications are subject to continuous improvement and may be changed at any time without notification.
MACLEAN
POWER Line Post Insulators
SYSTEMS
Rev: A2, Date: 04/2004

NBSG40XV Series Insulators: [3.5” Rod Dia.]

Bendable Gain Base


[To change from a gain base to
a flat base, Change the “G” to
a “F” as per catalog definition]

Drop Tongue – Bendable Gain Base

Line Section Electrical Flashover (kV)


MDCL Catalog No. Dry Arc Leakage Weight
Voltage Length 60 Hz CIFO
kV lbs [kN] in [mm] in [mm] in [mm] Dry Wet Pos Neg lbs [kg]

5612 48.5 36.4 95.6 110.1


115 NBSG40XV023S0 352 326 605 693
[25.0] [1232] [925] [2428] [49.9]
115 4672 55.8 44.0 116.5 118.0
NBSG40XV028S0 420 389 725 796
138 [20.8] [1417] [1118] [2959] [53.5]
138 3888 64.6 53.1 141.5 127.5
NBSG40XV034S0 500 462 869 916
161 [17.3] [1641] [1349] [3594] [57.8]
3505 70.4 59.2 158.2 133.8
161 NBSG40XV038S0 553 510 964 1006
[15.6] [1788] [1504] [4018] [60.7]

Notes: • STL (Specified Tensile Load – 15,000 lbs. [66.8 kN] MDCL = Max. Design Cantilever Load
• Electrical Data is without Corona Rings. For Insulators 230kV & Higher, MPS recommends use of Corona Rings.
• NBSG40 Series Insulators for use in North American Market Only
* For other ratings or custom insulator designs, contact your local MPS Sales Representative.

Line Post Insulators – Page LP-9 of LP-9


USA - Tel: 847-455-0014 Fax: 847-451-0029 y Canada - Tel: 450-698-0520 Fax: 450-692-5670 y www.macleanpower.com
Product specifications are subject to continuous improvement and may be changed at any time without notification.
MACLEAN
POWER
SYSTEMS
Station Post Information
Rev: A1, Date: 02/2004

This Page of the


MacLean Power Systems
On-Line Catalog is currently
Under Construction

We expect this page to be active in the near future.


Please check again soon.

Station Post Information – Page SP-I-1 of SP-I-1


USA - Tel: 847-455-0014 Fax: 847-451-0029 y Canada - Tel: 450-698-0520 Fax: 450-692-5670 y www.macleanpower.com
Product specifications are subject to continuous improvement and may be changed at any time without notification.
MACLEAN
POWER High Voltage Station Posts – SP200
SYSTEMS
Rev: A1, Date: 02/2004

NAA100XH Series Station Posts


For Systems from…
69kV to 315kV
B.I.L.: 350kV --- 1050kV
• “A” End Fittings = 5” Bolt Circle w/ 4 tapped holes
• “P” End Fittings = 5” Bolt Circle w/ 4 through holes
• Class “100” = 2.5” Solid Rod
• HTV Silicone Rubber housing
• Meets or Exceeds the ANSI C29.9 Electrical requirements
• Tensile Strength = 17,500 lbs
• Torsional Strength = 32,000 in-lbs
• S1 = 12” Corona Ring (S0 = No Corona Ring)

Corona (grading) Ring: Recommended for most


applications with BIL ≥ 900kV. At lower voltages,
corona rings may be considered for areas of high local
contamination, and/or with altitudes > 3300 ft. Where
MPS considers them necessary, corona rings will be
included.

Electrical Characteristics Mechanical


Typical Line

Porcelain TR

Leakage
Dry Arc

Compression
Weight
Voltage

Deflection
Test Voltage
Height

BIL Rating

Low Freq.
withstand

@ TR MWL
Max. RIV

to ground
@ 1 MHz

CIFO +

MDCL
SCL
Catalog No.
kV inch inch inch lbs. kV kV µV kV kV lbs lbs lbs inch

69 NAA100XH16S0 278 30.0 26.8 72.0 38 350 145 200 44 390 4400 2770 25k 0.7

286 1.9
115 NAA100XH23S0 45.0 37.4 106.1 46 550 230 200 73 610 2800 1750 12k
287 2.9
288 2.6
138 NAA100XH29S0 54.0 46.5 133.7 49 650 275 200 88 710 2300 1440 8k
289 4.0
291 3.1
161 NAA100XH34S0 62.0 54.1 156.7 60 750 315 200 103 810 2000 1260 6k
295 4.8
304 4.6
230 NAA100XH46S1 80.0 68.0 211.8 52 900 385 500 146 1010 1600 990 3.4k
308 7.0
312 4.8
315 NAA100XH54S1 92.0 80.1 248.6 57 1050 455 500 146 1210 1400 870 2.5k
316 8.6
Notes: • SCL = Specified Cantilever Load, MDCL = Max. Design Cantilever Load
• For “P” end fittings, replace the “A” with the “P”
• To order Station Posts, contact your local MPS Sales Representative.
• Station Posts for use in North American Market Only.

Station Post Insulators – Page: SP200-1 0f SP200-3


USA - Tel: 847-455-0014 Fax: 847-451-0029 y Canada - Tel: 450-698-0520 Fax: 450-692-5670 y www.macleanpower.com
Product specifications are subject to continuous improvement and may be changed at any time without notification.
MACLEAN
POWER High Voltage Station Posts – SP200
SYSTEMS
Rev: A1, Date: 02/2004

NAA200XV Series Station Posts


For Systems from…
69kV to 500kV
B.I.L.: 350kV --- 1470kV
• “A” End Fittings = 5” Bolt Circle w/ 4 tapped holes
• Class “200” = 3.5” Solid Rod
• HTV Silicone Rubber housing
• HIGH STRENGTH
• Meets or Exceeds the ANSI C29.9 Electrical requirements
• Tensile Strength = 25,500 lbs
• Torsional Strength = 54,000 in-lbs
• S1 = 12” Corona Ring (S0 = No Corona Ring)

Adaptor Plate
To comply with ANSI standards on 7” Bolt Circle fittings,
MPS has adopted the use of 1” adapter plates 5”-7”
shown here. The top adapter plate, when needed, has
integral slotted holes to facilitate alignment during erection
of bus supports.

The use of adaptor plates increases the height of the


insulators by 1” or 2”. For retrofitting, it is possible to
adjust the total height to the original TR value.

Electrical Characteristics Mechanical


Typical Line

Porcelain TR

Leakage
Dry Arc

Compression
Weight
Voltage

Deflection
Test Voltage
Height

BIL Rating

Low Freq.
withstand

@ TR MWL
Max. RIV

to ground
@ 1 MHz

CIFO +

MDCL
SCL
Catalog No.
kV inch inch inch lbs. kV kV µV kV kV lbs lbs lbs inch
216SP 0.1
69 NAA200XV15S0 30.0 25.0 62.0 53 350 145 200 44 390 10k 7150 100k
278 0.2
286 0.5
115 NAA200XV24S0 45.0 38.0 99.0 69 550 230 200 73 610 7100 4470 40k
287 0.7
288 0.7
138 NAA200XV28S0 54.0 44.7 117.5 77 650 275 200 88 710 6000 3630 35k
289 1.1
291 0.9
161 NAA200XV33S0 62.0 52.3 138.3 86 750 315 200 103 810 5160 3120 25k
295 1.4
304 4.6
230 NAA200XV45S1 80.0 66.2 188.4 110 900 385 500 146 1010 4000 2370 16k
308 7.0
Notes: • SCL = Specified Cantilever Load, MDCL = Max. Design Cantilever Load
• For custom Station Posts, contact your local MPS Sales Representative.
• Station Posts for use in North American Market Only.

Station Post Insulators – Page: SP200-2 0f SP200-3


USA - Tel: 847-455-0014 Fax: 847-451-0029 y Canada - Tel: 450-698-0520 Fax: 450-692-5670 y www.macleanpower.com
Product specifications are subject to continuous improvement and may be changed at any time without notification.
MACLEAN
POWER High Voltage Station Posts – SP200
SYSTEMS
Rev: A1, Date: 02/2004

NAA200XV Series Station Posts (cont’d)


• “A” End Fittings = 5” Bolt Circle w/ 4 tapped holes
• Class “200” = 3.5” Solid Rod
• HTV Silicone Rubber housing
• HIGH STRENGTH
• Meets or Exceeds the ANSI C29.9 Electrical requirements
• Tensile Strength = 25,500 lbs
• Torsional Strength = 54,000 in-lbs
• S1 = 12” Corona Ring (S0 = No Corona Ring)

Corona (grading) Ring: Recommended for most


applications with BIL ≥ 900kV. At lower voltages,
corona rings may be considered for areas of high local
contamination, and/or with altitudes > 3300 ft. Where
MPS considers them necessary, corona rings will be
included.

Electrical Characteristics Mechanical


Typical Line

Porcelain TR

Leakage
Dry Arc

Compression
Weight
Voltage

Deflection
Test Voltage
Height

BIL Rating

Low Freq.
withstand

@ TR MWL
Max. RIV

to ground
@ 1 MHz

CIFO +

MDCL
SCL

Catalog No.
kV inch inch inch lbs. kV kV µV kV kV lbs lbs lbs inch
312 2.3
315 NAA200XV53S1 316 92.0 78.3 221.8 122 1050 455 500 146 1210 3475 2020 12k 3.5
362 6.5
324 3.9
345 NAA200XV62S1 367 106.0 91.9 259.3 137 1300 525 1000 220 1410 3000 1760 8.5k 5.7
369 8.0
330 5.4
500 NAA200XV73S1 371 122.0 108.6 305.2 154 1470 590 1000 220 1610 2600 1480 6.5k 7.1
373 10.6

Notes: • SCL = Specified Cantilever Load, MDCL = Max. Design Cantilever Load
• For custom Station Posts, contact your local MPS Sales Representative.
• Station Posts for use in North American Market Only.

Station Post Insulators – Page: SP200-3 0f SP200-3


USA - Tel: 847-455-0014 Fax: 847-451-0029 y Canada - Tel: 450-698-0520 Fax: 450-692-5670 y www.macleanpower.com
Product specifications are subject to continuous improvement and may be changed at any time without notification.
MACLEAN
POWER
SYSTEMS
Braced Post Information
Rev: A1, Date: 02/2004

This Page of the


MacLean Power Systems
On-Line Catalog is currently
Under Construction

We expect this page to be active in the near future.


Please check again soon.

Braced Post Information – Page BP-I-1 of BP-I-1


USA - Tel: 847-455-0014 Fax: 847-451-0029 y Canada - Tel: 450-698-0520 Fax: 450-692-5670 y www.macleanpower.com