Professional Documents
Culture Documents
Selecting Control and Balancing Valves in A Variable Flow System - ASHRAe Journal - Jun 1997
Selecting Control and Balancing Valves in A Variable Flow System - ASHRAe Journal - Jun 1997
Selecting Control and Balancing Valves in A Variable Flow System - ASHRAe Journal - Jun 1997
The following article was published in ASHRAE Journal, June 1997. © Copyright 1997 American Society of Heating, Refrigerating and Air-Conditioning Engineers,
Inc. It is presented for educational purposes only. This article may not be copied and/or distributed electronically or in paper form without permission of ASHRAE.
This results in a differential temperature swing of 3-4°F, or An established practice is to select the valve size based upon the
more, that may be noticeable by the occupants in the space. Cv valve flow coefficient required. The Cv is defined as the flow in
Cycling the unit fan on-off in parallel with the coil valve will gpm through the wide open valve with a 1 psi pressure drop.
make this swing even more noticeable. The valve flow coefficient may be determined from the formula:
If the designer selects proportional control (P) (Figure 4) or
proportional-integral control,(PI) (Figure 5), there is an oppor- GPM
GPM = C v ∆P, or C v = ------------- (1)
tunity to control the space temperature conditions closer to the ∆P
load set point. This minimizes the temperature cycle with pro-
portional positioning of the control valve flow versus the load. where GPM is the load coil design flow in gpm,
In either of the control modes, two position, P, or PI, it is nec- ∆P is the pressure drop across the valve in psi,
essary that the designer properly select the control valve size
based upon design water flow requirements of the load terminal. See Hegberg, Page 56
Hegberg, From Page 56 system should be considered (Figure 10), since it reduces the
extreme pressure drops required.
that proceeds to the last terminal’s return and then returns to The designer must pay attention to what pipe sizes are
the source. The scaled pressure distribution diagram, reverse selected to keep the distribution main’s head-loss at an accept-
return, (Figure 10) not only shows the pump head required, but able level. For example, a direct return design might have a
shows a more uniform pressure distribution for each terminal large supply main pressure drop of 30 ft (9.14 m), and a 25-
than the direct return (Figure 9). Terminals near the pump have foot (7.62 m) drop across the last terminal’s sub-circuit and a
lower pressure drops. return main pressure drop of 30 ft.
The pump is selected to provide the system flow or sum of The high main loss in comparison to terminal sub-circuit
all the terminal’s design flows and the required foot head to loss will reduce the ability to proportionally distribute flow to
overcome the friction loss of the most resistant circuit. Each the terminals and especially a design flow in the last terminal.
circuit is analyzed for the total pressure loss from the pump This was pointed out in an ASHRAE Journal article1 by Gil
discharge, the supply main loss, the terminal, control valve, Carlson, Fellow ASHRAE. His article recommends higher
balancing device, the fittings, return main, and back to the pressure drop (p.d.) across the terminal sub-circuits compared
pump suction. to the distribution piping p.d.to increase the ability to obtain
Construction of pressure distribution diagrams or a spread- design flow in the end circuit. His article produced the table
sheet help the designer study the resistant losses in the mains shown in Figure 11.
and across each terminal. Notice that when the direct return In the case of a system design requiring 100 terminals of 10
design is selected (Figure 9), the high pressure drop across gpm (.631 L/s) each, then the main has to be capable of 1000
Terminal #1 compared to Terminal #100. The reverse return gpm (63.1 L/s), at full load, at the pump’s discharge. If we refer
Figure 16: Terminal heat output, valve flow and terminal output vs. control valve position.