Document Title: STANDARD IQ REMOTE CONTROL CIRCUITRY (24VDC)

THE BLUETOOTH® SETTING TOOL ENABLES ALL NOTE:


CONFIGURABLE ACTUATOR SETTINGS TO BE MADE. ACTUATOR REMOTE CONTROL SIGNALS MAY BE INTERNALLY OR
EXTERNALLY SUPPLIED.
BEFORE PUTTING THE ACTUATOR INTO SERVICE, IT MUST BE
INSTALLED AND COMMISSIONED IN ACCORDANCE WITH INTERNALLY SUPPLIED:
PUBLICATION PUB002-039 INSTALLATION AND MAINTENANCE
INSTRUCTIONS.
# FIT LINK '#' AS SHOWN AND CONNECT REMOTE CONTROL
CONTACTS TO INTERNAL SUPPLY ON TERMINAL 5.
UNLESS SPECIFIED WITH ORDER, THE ACTUATOR IS
DESPATCHED WITH DEFAULT SETTINGS AS LISTED IN EXTERNALLY SUPPLIED:
PUBLICATION PUB002-040. CONNECT CONTROL CONTACTS TO EXTERNAL SUPPLY LIVE/+VE.
CONNECT SUPPLY ZERO/-VE
FOR IQ CONTROL AND MONITORING FACILITIES, REFER TO TO TERMINAL 36 & 31 FOR SUPPLIES 20-60VDC OR 60-120VAC
PUBLICATION PUB002-041.
FOR CONTROL FORMS D & E, LINK '#' MUST BE FITTED.
CONNECT ZERO/-VE AS INDICATED ABOVE.

N
OW
CUSTOMER CONNECTION FOR
REMOTE CONTROL

TD
PLY

HU
+V PPL

YS
UP

DC L SU
C
OR 0VDC -VE
LS

NC
VA

E
AIN
120
-VE RNA

24V RNA
ON

GE
E

INT

ER
MM

60-

EN
OS
E

E
6
INT

INT

EM
MA

OP
CO

CL
20-

4 36 33 34 35 5 25
#
FORM A
OPEN/CLOSE PUSH TO RUN CONTROL Close Open
(LOCAL CONTROL REMAINS SELF MAINTAINED)
To external supply or terminal 5
(see 'Note:' above)

4 36 33 34 35 5 25 NOT APPLICABLE
# FOR IQM/IQML
FORM B
OPEN/CLOSE MAINTAINED CONTROL Close Open
WITH MID TRAVEL REVERSAL
To external supply or terminal 5
(see Note:' above)
NOT APPLICABLE
4 36 33 34 35 5 25
# To external supply or terminal 5
FOR IQM/IQML

FORM C (see 'Note:' above)


OPEN/STOP/CLOSE MAINTAINED CONTROL
Close Open Stop

NOT APPLICABLE
4 36 33 34 35 5 25
FORM D # FOR IQM/IQML

TWO WIRE CONTROL, ENERGISE TO OPEN


DE-ENERGIZE TO CLOSE. Close Open
(CONFIGURE FOR OPEN PRIORITY)
CUSTOMER TO LINK 5 - 33 To external supply or terminal 5
(see 'Note:' above)

4 36 33 34 35 5 25 NOT APPLICABLE
FORM E # FOR IQM/IQML

TWO WIRE CONTROL, ENERGISE TO CLOSE


DE-ENERGIZE TO OPEN Open Close
(CONFIGURE FOR CLOSE PRIORITY)
CUSTOMER TO LINK 5 - 35 To external supply or terminal 5
(see 'Note:' above)

4 31 33 34 35 5 25
FORM F # ESD
EMERGENCY SHUT-DOWN CIRCUIT. switch
THE ESD CIRCUIT CAN BE ADDED TO ANY OF THE CONTROL
CIRCUITS SHOWN ABOVE. (stayput)
AN ESD SIGNAL APPLIED TO THE ACTUATOR WILL OVERRIDE
To external supply or terminal 5
ANY EXISTING OPEN OR CLOSE CONTROL SIGNAL.
(see 'Note:' above)
THE DEFAULT ESD CONFIGURATION IS "STAY PUT", DERIVED
FROM A N/O CONTACT (SIGNAL APPLIED).
FOR OTHER CONFIGURABLE ESD SETTING OPTIONS, REFER TO
PUBLICATION PUB002-040 INSTALLATION AND MAINTENANCE
INSTRUCTIONS. THE BLUETOOTH® WORD MARK AND LOGOS ARE REGISTERED TRADEMARKS
OWNED BY SIG, INC AND ANY USE OF SUCH MARKS BY ROTORK IS UNDER LICENCE.

ROTORK CONTROLS LTD ROTORK CONTROLS INC Document No Issue No


This is an Associative Document that needs to be read in
www. .com BATH, BA1 3JQ
ENGLAND
ROCHESTER
NY 14624, USA
conjunction with the appropriate Rotork Wiring Diagram. RWS100 3