The Critical path studied is from the ETS room up to FAHU-1 which has the highest coil pressure drop and the highest flow rate
compared with other air handling units
Fittings losses
pipe size Flow Friction rate velocity Pipe Length Total length(Pipe Total pressure
Section (Inches) (GPM) (Ft/100Ft) (Ft/sec) (Ft)
length+equivalent
drop (Ft)
length)
Equivalent length
Item Quantity (ft) per item
90˚ Elbow 4 25
ETS Room 10 1322 0.85 5.38 84 280 2.38
piping Branch Tee 6 16
Total equivalent length 196
90˚ Elbow 6 25
AB 10 1322 0.85 5.38 Branch Tee 2 16 560 742 6.307
Total equivalent length 182
90˚ Elbow 2 25
BC 10 1287.3 0.8 5.23 Branch Tee 2 16 14 96 0.768
Total equivalent length 82
90˚ Elbow 0 20
CD 10 1081.3 0.58 4.4 Branch Tee 2 16 20 52 0.3016
Total equivalent length 32
Reducer 0 23
DE 8 906 1.29 5.8 Branch Tee 2 13 20 46 0.5934
Total equivalent length 26
Reducer 0 13
EG 6 634.8 2.6 7 Branch Tee 2 10 20 40 1.04
Total equivalent length 20
90˚ Elbow 8 13
Branch Tee 2 8.2
GH 5 433.5 3.16 6.95 Gate valve 2 6 295 451.4 14.26424
Reducer 2 12
Total equivalent length 156.4
90˚ Elbow 0 20
HI 5 389 2.6 6.24 Branch Tee 2 8.2 79 95.4 2.4804
Total equivalent length 16.4
90˚ Elbow 2 10
IJ 4 289.9 4.58 7.31 Branch Tee 4 6.7 145 191.8 8.78444
Total equivalent length 46.8
Heat
Exchanger & Refer to the HEX calculation detail 30.08
Hook up
Total pressure drop in all piping sections and various equipment (Ft) 103.21908
Final pump Head after applying a 10% factor of safety (Ft) 113.541
Pump hook up is according to this detailed
drawing