Professional Documents
Culture Documents
(GE) - AK Breakers Vol 2 of 2
(GE) - AK Breakers Vol 2 of 2
i 1
1 Manual #3-407 Selection &Application F-P Air Circuit Breakers
Page 1
Vi •v;':
iC a ?|0 t' ia •
V-" ''"r^'X
. v'^. ' •
I;
• ' •
.. iV :
.\>(Vf v. -tV
I i
'.;Vt''''.'-';''-,-'v
v.':."' V .•;,;
• •
•;',:5'.''
/'M
, Vv.i'^V'v '
..• i 'I ' . r.v
• -.-< ;A'
.jr: -
ti, kMyMi
, •p'lT':
'•: t '.
a'
V^r'.-;:ri:••
stei
i
t •• =
I , .-
• .; yy '-'y:0:';^icortwjiiptf
• !• '.j
• '•
->is!v;;:
page
Subject
Tripping Devices . . . . . . ..
Scries Overcurrent Tripping Device . . • * t • • • I
-IP-
Tripping Characteristics Produced . . • f I *
IP
Accessories for Federal Pacific Air,Circuit Breakers ^ •': r-: •
15'
• PPiiPp^K;-
/ "^ tt* Li '^- ^^ 4c« LJ ^
^:.• ''
'i .
V
.
V* ^ Li^:J;- •I w • 'v^-i<j ^v.;.;^*— i*
. ;^.. .
. •>..v ^ iU CM * Mii aj Li L>#<. L. ^^ / a • iT- »- .., ,/
• <•
Wa. -l'- -.iwal /-'..-A.L>LW. J-Vjairfti ii-iil»iik^ki*Li4ii.i5ilijliL-i«ltKWj^iaUrt'»V.r."; I Lia,Ua^:.*' /*.'1 j,.aLi -'...y/'' y
, -f;,
eral Pacific Electric Company (hereafter called the circuit to be used for verifying the ability of the cir
"Company). cuit breaker to interrupt the lotaLamperes (rms if al-.
ternating current) given by the interrtipting rating for
5. Locaf Electrical Codes the applicable operating duty shall be as follows;
Federal Pacific breakers are designed to comply
with the National Electrical Code. Where City or State A. RMS Total Amporos \i
Codes are more restrietive than the National Elec The rms total amperes shall be determined by ?}
trical Code, the Company should be consulted for its measuring the current flow in the test circuit dsi)
recommendations. Unless such recommendations art-
follows: . ^
The circuit breaker shall be short circuited W. -
obtained in advance of placing orders, the Company
omitted. . •
will notassume responsibility for compliance with such
codes.
In alternating-current circuits, the current mea-' •
6. Limits of Observable Temperature Rise sured shall be the rms total current including if any,
:( the direct-current component. It shall be measured
Federal Pacific air circuit breakers are designed in
accordance with "the NEMA Standards SG3-3.04 on
at an instant one-half cycle after the short circuit
Limits of ObservableTemperature Rise above the Am occurs and shall be calculated in accordance with
bient Temperature, the latter defined in the NEMA American Standard Methods for Determining the
Standard SG3-3.IS. Rms Value of Sinusoidal Current Wave a.nd a .
Normal-frequency Recovery Voltage. (For « i-
7. Unusual Service Conditions phase test circuit the rms total current 'sHcdl be'the}
When unusual environmental conditions or unusual
average of ihe currents in ail3 phases. For asingle-;:^
duty conditions are encountered, it is recommended phase test circuit, 3 successive tests shall be made
that these conditions be nullified at the site of the in to determine the average current in that circuit.)
stallation. Unusual conditions referred to are those The circuit constants for the test circuit, with the ?
considered by NEMA under SG3-2.02. When such required current flowing, shall be such that the i'•
action is not possible and standard equipment adaot- X/R ratio is at least 11.72,
able to the condition is not listed, recommendations
for special features necesshry to adapt standard equip In direct-current circuits, the current measured i
ment to the conditions should be obtained from the shall be the maximum value.
Company in advance of placing the order. The transient characteristicsof the testingcircuit
for a circuit breaker with delayed tripping in the
If^TEKRUPTING. RATEM.GS fault current range shall be such thai the 3-phase
The interrupting rating of a circuit breaker is the average current at the end of 30 cycles (based on
highest current (rms ifalternating current) at a speci-. a 60-cycle frequency) shall be not less than 75 per
fied operating voltage which the breaker is required cent of the average rms total current at the end of
to interrupt under the operating duty specified and the first half cycle. ' . •: "
with a normal frequency recover voltage equal to the
specified operaiing voltage. ^ . B. Performance <
Interrupting ratings of Federal Pacific air circuit At the end of any performance at or within its
breakers arc based on test prWediirci applicable op interrupting rating, the circuit breaker shall be
erating duty (dutycycle),^rtormance, and conditions the.foUowirig condition: ^ • • • A"•••
given in paragraphs SG3-3.07, SG3J.OS and SG3-3.19
01 the NEMA Standard for large air -ircui* brtaVc.7i 1, Mechanical—The circuit breaker shall be in
Tnese paragraphs read essentially as.follpws:—, substantially t',mechanical conditioii }C[^^ :,'
as at the beginnings - /
Short-Ciircult Interrupting Tests 2. Electrical—The circuit breaker shall.be co- -"'.
The ,iesi procedure and;characteristics of the. test .. pable of w///iy/anrf% rated
•jvjvSj
• isb^u-'K^ii-uue ^c:iL/;q£>
: J.V— ••
the rated continuous current of the circuit one-half second each, with d 15-secorid interval of
breaker. zero current between the one-half secondi perfods,'.
'rT
Short time ratings of Federal Pacific air circuit •rating shall be electrically operated from a remote
breakers are shown in Table No. 3, page 17. Appli- position only, to provide protection for the operator
c.%tion of bre.akers and series trip devices, where trip when closing against fault current.
ping is delayed to provide selective tripping, is further 1. Direct Monual-Oporatins Mechanism
discussed on pages 11 and 12.
Direct manual-operating mechanisms arc inte^al
MSCHAWSSMS
with the breaker, structure in DMB15, DMB25fl, .'•'I .
When the breaker is closed full contact should be DMB50 circuit breakers. The operating handle of '^e
established quickly and positively. This is required mechanism protrudes through the dead front panels'
since hesitation or slowness oil closing, particularly or the doors of the metal encldised drawout switchgear
when closing the circuit breaker against' a short cir units, depending on the enclosure.
cuit, causes excessive arcing, consequently burning of
the contacts, and other danjage to. the breaker. When
2. Electrica! Operuvlr.g Mechanisms
closing manually, the operator may hesitate or be un
certain m his efforts to close the breaker, giving rise Electrical Closing of DMB 15, 25-1 and 50 circuit
to the conditions described. breakers is accomplished by a solenoid actuated
mechanism. The solenoid is controlled by. closing
To insure greater safety, as well as ease of opera the control lelay provided for this purpose.'
tion, the following limitation recognized by the AIEE
and NEMA applies to manually operated breakers: COS^TKOL CLRCUJ7 POWER
The control circuit must have a reliable source of
Manually operated circuit breakers shall be limited power for successful operation of the control .cdmpo--
to applications where the interruptingrequirements do nents. The control circuit power source ^oiiild be
ot exceed 50000 amperes and where tripping is in independeni to the degree that the voltage is main
stantaneous for current above 15000 amperes for tained constant, particularly when fault conditions are
dead-front and enclosed breakers or where interrupt encountered, and should never be allowed to fall be
ing requirements do not exceed .10000 amperes for low the minimum value required for successful opera
live-front breakers and rated cpntinupus current idoes tion of the components.
not exceed 1600 amperes. For selective tripping, man
ually operated circuit breakers shall limited to ap The following table lists rated control voltages and
plication in which delayed tripping requirements do minimum and maximum ranges. These voltages are
not exceed 150*00 amperes. Allcircuit breakers sub to be measured at the terminals of the various control
jected to fault currents in excess of their interrupting mechanisms with full operating current flowing.
•• "
fr. f
hr'l ;
»cry- •' 9
r.*-* '>? i;. .•^•^ /
'•^ \'' t 'W Ww
, • i;..
:, <\.<,:::yyti!.'r -\ ./
hMii
ifj
• •. -
tMS
/-\
• •- V'
T. • •
.iS • ~-'^i"-
h-4ar" ^^
|l 'C
•• 'r
mm:
••i'iVV i' \r
V v»
v:iEp?^^^© Acljustmanis; .
Pa©DUeED Both the long-lime-delay pickup current and the
short-timc-dclay pickup current are field, adjustable by ,
1. Long-Tirae-Delay; adjusting the corresponding calibration knob to the .
Alone or in combination with the non-adjustable desired setting. Actual time delays corresponding to ,
instantaneous trip and/or short-time-delay. The long the three NEMA bands for both long-time-delay ^»d •
time-delay pickup is adjustable in the field at the short-timc-delay are factory set according to specifica-i-''
calibrated setting of 80, 100,'120, 140 and 160% of tion. Instantaneous tripping is.also factory set to speci
the ti^p-coil rating. Long-time-delay pickup adjust fication. Unless otherwise indicated on order, the in-i
ments in excess of 100% of the'trip coil rating do not stamaneous trip setting, will be at 10 times the con-
provide protection for.the brewer and should be used tinous current rating of the-&p coil. The armature
only on selective systems. Selection of time-current air gap is factory set and should not be changed.
characteristics should be made from Table A or ap The preceding characteristics produced arc the same
propriate curves. for the DMB-15, DMB-25-1, and.DMB-50 large air .
circuit breakers since the same type scries overcurrent
2. Short-Time-Delay; 5s^trip-device is used. However, the devices are not intcr->
Alone or in combination witli the non-adjustable O changeable from one interruptiiig rating to another,.;
instantaneous trip and/or long-time-delay for selective Table No. 3 shows permissible interrupting rating'''! } V»' ; ''
tripping. The short-time-delay is field adjustable at range of various series, trip coils.
the calibrated settings of 5, and 10 times the
trip coil rating. Selection of the time-current charac Time-Current Characteristic Curves
teristics should be made &om Table B or appropiiate The long-tirae.^elay curves am shown .as the sum-; Sir
curves. ' : v mation of the tripping device timing plufthe brisker
/
r
TABLE A
Lowor limit of bond ti
Typo of Broofcer TifflO Characteristic Pickup Toloronco
« 600% of Pickup Seftiho*
M!n. 5 seconds •
DMB-IS, 2S-t,S0 Inter. 15 seconds • . .
Max. ' 30 seconds
-T.
rr-T-^r...
i
.M:
•••',
' ::'jO
-Uii
•••
L.
NOTES—
/fii-
l.ong.time-doloy arid initontoneout
tripping (hown ore nofmolly
supptiod In oil DM& Air Clreto
Dreokeri. For lalocfiva tripping
appllcotiont, the chorl-time-deloy
shown it supplied oioner or in
SHORT TIME
combination with Ibhg-limo.delayi RESETT. OEUY
or In. combinotion with inttonto-
ncouj tripping) or in combinotion
with long-time-delay ohd instanto-
neoiit tripping. Type, of tripping
jk •ym'
// • • : f'-.-r"- •'(
j i: i.'jV ••..•«! • * . •[, ••
V*Xi<e4$U^vi«—L*
... . .
Ef^y
•C ,• »i;,.
.;^S INIEilM£dlA7£
.' •-: v:
'•'M • •'
< -
Long>Time Delay Curves um '.: * •
• "• .^..• *
_ -i";-. ••
• /
I
CUKVf
AXIMUM
NOTEi THE PJCK-Uf CURRENT SETTING FOP. EACH BAND IS ADJUSTABIE TO 5, ^Vj, and 10
TIMES THE RATING OF THE SERIES OVERCURRENT TRIPPING DEVICE,
suiTJ-nation of the timing of the tripping device plus device, resulting in the subsequent tripping of the cir-
the breaker clearing time. The broken line below the cuit breaker with which the trip device is associated.
operating curve indicates the reset time, i.e., the time Cajibravion: • • .
for which an overload may persistthrough the device
without ultimately tripping the breaker. the current Circuit breakers with adjustable overcurrent trip
is instantaneously reduced to and maintained at 20%
shall be calibrated at 80, 100, 120, 140, and 160 per
cent of their continuous current rating. The toleiaiicc
of the shoft-time-delay pickup current at or below this
line, the device will automatically reset. shall be plus or minus 10%.
Overcurrent trip coils shali be selected so as to
Both the long-time-deiay curves and the short-time- vide the minimum trip'setting required. v-
delay curves are average curves pnd include the varia
tions between individual units, the manufacturing tol Short Time Delay Pickup:' *
erances, and the differences between single phase and Shall be set at 5, 7'/z, and 10 times the ampere
three phase tripping. ' .- rating of the overcurrent trip coil.
Where palibratipn adjustment has been set so as Series Overcurrent Tripping:
to-co-ordinate devices properly in a selective system, Trip coil in series with main circuit! , "
the calibration-should not be disnirbed for. proper
operation of the system. ' " ; Instantaneous Overcurrent Trip:
Functions above a predetermined value orcurreni:!fepC
CONMUOyS CURRENT RATSNGS without any purposelydelayed action. • . i
Continuous current of circuit breakers and series
trip coils, in amperes, is iishovm. in Table. No. 2,, Delayed Overcurrent Trip: ^
page 16. ' • Functions above a predetermined value of Vr-
» current with a purposely delayed action. f'!*
DEFINSTI0N OF TERMS .
Dual Overcurrent Trip:,
SelecHve Qvercurrent Tripping: Combines the function of a delayed and an instan- '
The operation of circuit breakers in series so that, taneous overcurreni trip.
of the breakers carrying the fault current, only the
Selective Overcurrent Trip: •
breaker nearest the fault operates to remove the over-
current conditions and the breakers nearest the source Functions with a purposely delayed action at ali ' : '
shall remain closed and continue to carry the remaining values of current between a predetermined value and
,• load current. the rated interrupting current of the circuit breaker '
•with which it is associated, and which will automat- v .-
Cascading: ic^ly reset when tlie current is reduced within a pre- r-V ' -
The application of air circuit breakers in which the scribed time to a value within the rated continuous
current. . " -
.!. breakers nearest the source of power shall have intei-
:,: : rupting ratings equal to, or Inexcess of, theobtainable Dual Selective Overcurrent Trip: i i
fault current and where one or more breakers further
removed from the power source have interrupting rat Combines the function of adelayed overcurrent trip •
ings less than obtainable fault -it the point of a selective overciinent trip. ;' ; : •t
application. • '
Irtsfanfaneous: •
DETERMINATION OF SHbRT-CSRCUST ;
CURRENTS: .: '''V;-
_ A qualifying terra indicating that no delay is pur-
• posely introduced in the action of the device. Low-yoltagc air circuit brcakcrs'are toapplied '
i
'' ' ' -
?:
10"
(a) For d-z circuits, the current calculaicd shall be current component, i.s dcicrmined by multiplying -dz
the maximum value, taking into account all resistance symmetrical current as obtained from the preceding
up to thc 'source side of the circuit breaker but not method by a factor to account for the increase in the
A <'
including any of its own resistance. average three-ph.nsc current caused by the presence of
For d-c faults of 100,000 amperes and above, conr the direct-current component. While this factor de
sideratioh should be given to the rate of ri.se' of the pends on the X/R ratio of the total impedance to the
current as compared with the interrupting speed and point of fault, a good approximation is obtained by
rating of the circuit breakers. the use of a multiplying factor of 1.25. The use of
(b) For three-phase a-c circuits, the current cal this approximate factor, in preference to the determi , ,#•
culated shall be the average value of the three phases nation of the exact factor obtained for the specific
of the total current, including the d-c component, at
X/R ratio for each low voltage circuit breaker appli
an instant one-half cycle after the short circuit occurs.
cation, is generally accepted practice. This factor of ^
This value is computed by.first determining the total 1.25 corresponds to a ratio of 11.72.
symmetrical current from all sources, including syn (c) For single-phase a-c circuits, the current is cal
chronous motors and induction motors. .Then this, culated in the s.Tmc manner as that used for three-
total symmetrical current is multiplied by a factor to phase circuits, as tiic maximum asymmetrical current
determine the average three-phase current at an in-. in a single-phase circuit is identical with the current
in the highest phase of a three-phase circuit. (Sec '•f-G
stant one-half cycle after.&e short circuit occurs.
Determination of Symmetrical Current. The £y.m- American Standard on Low Voltage Ail' Circuit
Breakers C3 7.13)
metrical current consists of the sum of system and
motor contributions, calculated in the following .mari
ner: F '•
THH SELECtSVS" SYSTEM*" FV;
1. System contribution is determined for all sources .When service to a number of circuits'is to be
and all impedances up to the source side of the circuit maintained, despite a faiult in any one of the circuits
breaker, but. not including any of the circuit breaker and protection to all circuits must be provided, the
impedance. At 600 volts and below, even small im selective system is applicable. In Figure .1 the main
pedances should be taken into account as they may breaker A, the tie breakers B, and the feeder breakers
greatly affect the result. C are between the source and the loads. In the selec
2. Induction and synchronous motors connected to tive system, a fault at any load will trip the feeder
the bus act as generators, and at one-half cycle after breaker C which is bettveen the load and the circuit ,
the short circuit occurs, cphtributc current which may tie. breaker B, The remaining loads, however, will still
be calculated from the subtransient reactance of the^ GGGG:
/IF"'
..A
motor. Where the reactances of the motors are not
known, values are assumed for induction motors of 3.6
times motor full-load current, and for synchronous SOURCE A -A-y'U' •;
Determination of the /Symmetrical Current. The '* Selective trip and short time delay app'dcaticns limited to ' 'V ,i -.
asymmetrical or total rms current,^including the direct- inlcrruptins current ratines shown in table No. 3,. Page 17.^^ . ;
• -j;
.11 'V. , ,
/•""'V '
."i '•• .:
, • , '"n . » V y- ,
,• .i Ui<
(• result of an overload between it and the load, the re Examples of application of Federal Pacific air cir
maining tie circuit is being fed. All the breakers in cuit breakers on typical selective trip systems are
the system are timed so as to protect their associated given in Table No. 4, page 18. f .
circuits and to trip in suihcient time to protect the
breakers themselves within their respective interrupt
CASCADk system* •
ing capacities. The following arc requirements for
breakers in a selective arrangement, as outlined in the Although the selective system is the best recom
American Standard on Low Voltage Air Circuit mendation in all cases, there are applications where it
! Breakers:— is not feasible, economically, to use feeder breakers
with full interrupting, capacity at all loads. Iii such
Requirements for Circuit Breakers in Selective cases the cascade system may be employed. This
Trip Arrangement means that only the breakers nearest the source of
power must have interrupting ratings equal to the
Properly selected air circtiit .breakers may be ap
average total calculated rms current, &d stated for
plied to low voltage circuits to obtain selecUve trip
breakers between the source and the load.. Breakers
ping. The following requirements shall be observed:
further from the source may have lower interrupting
(a) Each air circuit breaker must have an in- ratings. The following are requirements for breakers, • /'V • ' •
O terrupting rating equal to or greater than the avail-
able fault current at the point of application.
in cascade as outlined by the American Standard on
Low Voltage Air Circuit Breakers:— .
(b) Except for the one farthest removed from
source of power, each air circuit breaker must have Requirements for CircuR Breakers in Cascade
a short-time rating equal to or greater than the Arrangement
available current at the point of application. Circuit breakers are considered lb be ..in cascade
(c) The iime-current characteristic of each air when a plurality of low voltage air circuit breakers are
circuit breaker, at all valu^ of avaflable overcur- connected in series in a distribution system, and the
ent, shall be such as to insure that-the circuit circuit breakers beyond those nearest to the source
breaker nearest the fault shall function to remove are applied in the following correlated manner.
the bvercurrent conditions. Hiose nearer the source
In this cascade arrangement, circuit breakers toward
shall remain closed and continue to carry the ro-
thesource arc provided with instantaneous tripping de
mainmg load current.
vices for current values which may occur for faults
(d) To insure that each circuit breaker shall beyond otlicr circuit breakers hearer the load. Hence,
function to meet these requirements, the time- circuit breakers in the series other than the circuit
currcn} characteristics of associated circuit breakers breaker closest to a fault may trip and interrapl loads
must no* tvviJap. The pickup settings and time de- on other than the faulty circuit. SaCL< hijraagements
Jay bands of ooth tbe long-time and short-time de- are used only where, the consequent jpossiblc sacrince.
. lay. elements must be properly selected. in service continuity is acceptable..
(e) Manually-operated circuit breakers shall be (a) ""Cascading shall be limited to two. or some
limited to applications La which delayed tripping times three steps of interrupting rating. •
requirements do not exceed 15,000 amperes or 15
1. The, interrupting rating of a circuit breaker or.
fees vvip-f.-i>i; mting, whichever is gre' ici, breakers nearest the source of powershall bo cqual to
(f) The time-current characteristic: of circuit at least 100 percent of the short-circuit current as calr".
breakers in a selective system shall be such that culatcd in accordance \vith preceding paragraphs of ;v...
four circuit breakers may be operated selectively in this guide. The circuit breaker or breakers in this
scries when required., One of these shall be a load . ii'i.'i
Cascading at 240v. and 4S0v. maximum intcmipling ratings
circuit breaker equipped with an instantaneous trip is limited to two steps of .intcmipting' ratinj.
t •?
- . I." •; •
step shall be equipped with instantaneous trips set to to voltage, current, and interrupting rating, previously,
trip at a value of current that will give back-up pro cited herein.
tection whenever the circuit breaker in the next lower Ser\'ice Ci.cuifs (Sections 2351, 2354, 2356,
step carries current greater thaix 80" percent of iis in 2357, 1953 Code) • 'I '.V
Feeder Circuits (Sections 2403 and 2405, "that where the overcun-ent protection' specified in
1953 Code) the table isnot sufficient for the starting current of the .
motor, it may be increased, but shall in no case ex- v
The general requirements' for circuit breakers and
cccd 400 percent of the motor full load current."
feeder circuits are that each ungrounded conductor be
disconnected when the breaker opens, and that the- For motor-feeders, (Section 4362, 1953 Code) the
rating of the overciirrent trip device be as follows: circuit breaker setting "shall not be greater than the ; ^
Adjustable-trip circuit breakers of the time-delay, largest rating or setting of the branch-circuit protcc- ! v !
magnetic-trip tj'pe, or of the instantaneous-lrip type,
live device, for any motor of the group (based on ;
shall have a setting of not more than 150 per cent of Tables 26 &27, Chapter 10), plus the sum of the
the allowable carrying capacity of the conductors.
full-load currents of the other motors of the group. '^i;
Motor circuits are exceptions to these requirements. "If two or more motors of equal horsepower rating
are the largest in the group, one of the motors should
Motor Circuits (Section 430, 1953 Code) be considered as the largest for the above calculations. .
"If two or more motors of a group must be started
Motor circuits are classified as "motor feeders" and
simultaneously, it may be necessary to install larger '
"motor-branch circuits." A motor-branch circuit may
feeder conductors and correspondingly larger ratings
serve only one motor or it may serve two or more or settings of feeder overcurrent protectibh."
motors.
Power and light loads. If a feeder supplies a motor i
For an individual motor, "the motorrbranch-circuit
load, and, in addition, a lifting or a lighting and
overcurrent device" (that is, circuit breaker) (Section
appliance load, the feeder circuit breaker should have ;
4342, 1953 Code) "shall be capable of carrying the
starting current of the.motor. Overcurrent protection
a rating or a setting sufficient to meet therequirements; f
of. the motors [a sin^ motor (Section 4342) br: ai
shall be considered as being obtained when this over-.
group of motors (Section. 4362)], plus the normal
current device has a rating or setting not exceeding
load current of the lighting and other loads. (Section
the values" given below:
4363, 1953 Code)
Single-phase "Code Letter A" (where the.
locked rotor current is not in excess of Motor controllers. From the Code "the term 'con
3.14 times the normal current)... 150% troller'-includes any switch or device normally used to
Single-phase "Code Letters B to E" (where start or stop the motor." (This.refers to devices con
the locked rotor current exceeds 3.14, but nected in the main circuit.) •
is not more than 4.99 times normal cur "A branch^;ircuit type circuit breaker may be used
rent) 200% as a controller. When this circuit breaker is also used
Single-phase—all other ; ; 250% for overcurrent protection, it shall conform to the
Polyphase squirrel-cage and synchronous appropriate provisions ... governing overcurrent pro
motors wito full-volmge, resistor or re tection." (Section 4383d, 1953 Code)
actor starting:
Section 4331 (1953)—^ RATING OF PROTEO^
"Code Letter A" (locked rotor current
not exceeding 3,14 times normal cur TIVE DEVICE. Motor-running ovefcuhrent de- •'
rent) 150% vices other'toan fuses shall have a rating of at V-
"Code Letters B to E" (ioclm(l rotor least 115 per cent.of toe full-load cuncni rating
current exceeds 3.14, but not more, of the motor. ^
than 4.99 times normd current) 200% Section 4347 '1953) —RATING OF CDUiJCJrr- ^
All others 250% BREAKER. Circuit-breakers for motor-branch-
Polyphase squirrel-cage and synchronous- circuit protection shall have a continouous cur-} ^
motors with auto-tiansformeis starting ' rent rating of not less than, 115 per cent; of the:
"Code I.etter A" (locked rotor current
not more than 3.14 times normal) ....150% ifuil-load current ratings of. the motors. ^
Section 4403 (1953)—CARRYING CAPACITY ' ;
All/others j 200%
AND INTE^-PTTNG f. •
Wound-rotor motors ; 150%
a. The disconnecting means shall have" a carry
Direct-current motors 150% ingcapacity of at lca:>t 115 per dcrlt ol the namc-
An exception to the settings specified above is plate current rating of the motoi*;: •.
14
.T, ''iX :•* *
/V. I* 1 ' - :A - '
^11= i-i-'iCia'siC.
(; •. • V • "-J; b.) i- - ..
L2ALc:ii!^s:. .
A large number of accessories arc available for use The following tables show standard and Optional
with both manually and. electrically operated Federal - accessories available with the various sizes of DMB
^ ''
Pacific DMB breakers.-^These-accesories are factory- breakers. These accc.ssories are available-with draw-
installed in the'breaker; aid .wired and tested to per out type or fixed mounted (stationary-type); breakers
form correctly their function within their rated ciper- used in metal enclosed switchgear and also witli indi-'
ating.range. Rated control voltages and ranges are vidual, wall mounted DMB circuit breakers.
tabulated on page 4.
I
STANDARD ACCESSORIES
1. D.Ma 75
FEDERAL PACIFIC CIRCUIT BREAKEKS . DMB IS DMB 25-t DMB 50 DMS'tOO
Operating Mcchanltms Man, Eloc. Man. Elec. Man. ' Elac. Elecincoi
.
)<^9>ptional accessories
' '. ... ^ c-;.5- -
—-y Auxiliary Switch 4 or 8 Circuit! ...... • X
Undervollage device—Initantoneoui
' X • • x - •' •' ..k . „ X,
or time deloy X X X X •'X:?" X 'X •
OvorcurrepI bell alarm—band reset X X - - X • •X ' X X X
OvercurrenI lockout device—lio.nd reset ™..... — X X x~ X • •' ^X-:- X X
Eleclricoi lockout device X X- X • X X - X X 1
Key lock .... . JJ —
X r ~ - X • ' X - • X X
Key Inlerlocfc X X X X X - X' X
Shunt Trip Device—4 circuit
•" ouxil.iory switch X __
X ^ _
'x .
(, OOT
Closing Swi^h (mounted or unmounted) ...... —
X _ !. X • X; •" • "X"'
• • Field discharge contact • X X X X X •• X •
Copacilor trip X , X X X X X .
X
X X k , •' 'X
long time delay and i
f
. 15
7 ; • •, •;• ; ,r
-"••• • •
V.
f • .• •, .• -• INTERRUPTING R<in(i« of
CASCADE SYSTEM
Maximum Shod ,
, SEIECTIVH SYSTEM •
. Mcixlmvm Shod i
Continuoui Ofcuil Current'
t .Ciicuit Srookcr Vollage • • BATING •
RotInQ in ot Which Breoke.
, 'Clreoit Cudtfn't ; .fe
(RMS. Ampt'vt) 'of Which Brcokof. \
Ampc... Con bo Appliod Con bo Apptiod
. (RMS Amporos) (BAIS Amperoi) ' \
(
1 OMSaS-l 34t«(80 35.000 100. 400 704500 25,000 .
0MB SO - 24).4S0 40,000 100,000 ..
400-1400 • .SOiOOO "
0M8 75 . 24t-480 ' 75,000 2CO0-300O 100,000 79,000
0MB too 24t.4«ti 100,000 400O • 100,000 100.060 ^4'
* Selpctive feeder breakers. Fioal load breakers may have higher ratings. See table 4.
NO. 2 15
-
. *
20
••iV- 1 ; : ;••
30
40 40
50 50
70 . 70
90 90
\ ' .100
125
t150 150
175 . 179 1 " '• • 1,1,'..
SHOi^T TIME AND SclKCriVE TRiP RATi:-viGS O? ?-:DlRAL ?ACmc CiuCUlT B^lEAKI^;;.:
These Currents Calculated in Accordance with AIEE and NEMA Standards.
Froquency—60 cytlat
Maxiffluffl Design Vai'n£|n~~^26 Volts
Dlotoctric Wilhiland Tost Voltage—2200 Volts
DMB 15 15000 15000 225 1510 225 100 to 225 125 to 225 . 150 to 225
DMB 25-1 25000 25000 600 40 to 600 175 to 600 200 to 600 . 250 to 600
DMB 50 50000 50000 1600 . 200 to 1600 350 to 1600 400 to 1600 500 to 1600 : . .'•••
DMB 75 75000 75000 3000 2000 to 3000 2000 to 3000 2000 to 3000 2000.1ft 2000' •
DMB 100 100000 100000 4000 4000 - 4000 4000 4000 ..
1. If ttripping instantaneous above 1500% coilrating for DMB 15, DMB 25-1 and DMB 50; 1200% for DMB 75 and DMB 100.
2. On currents above 1500% of coD rating for DMB 15, DMB25-1 and DMB 50; 1200% for DMB75 and DMB 100. •,
V
' .!
•ii:
V;
• • If •
•• , ''' i\
• • • v.. •.5- • -
•- • >>y -
C-
"'Wk
)7
'V;. *1 ' '
. . .y, ' ' ( p, . » <9 . . 6r"i f.
•L. -l.i- rrvfv^ 's** x' '< .
c;
nVV:-''
• V-
Shert^ircult C'J<'6r.l
,'• .. •. Tiemfftint)
' MoK-Stmrt. 1N«'me Tdia) PlMS A/v^e'et ;(ECo/a!iwDiD nma pacifk AiK Circuit Q9£AK{(t ~ J/lp Rooob H w)(h<A Por4r>t))e^:t ( 1
tfliifiBS-pfe - CrcvliKVA {Averaj^a 9*^hD» Acnp.
l»ed
KVi^ciuf
« Avo'Iol'la UATlU SYiyjM CASCADE SYSTfM 'rc'
SfLCUIVt STST(M
(rem PriiMiv hn«i«ui Molo
f*rt$nl Com* M f
Sr»>«m CvrrvAt fdrmtr l90& M«in Fwiiy.Relad
M • C M a F . 5 [ . ;
MetA Ctt^nd* Fv(ly*BA'rd
. Arnp* 'Alen# 50% Brveker Fe«d»p
Main Se'eet.'r*
Bf«al.er Feeder Fi"! -i-r
SXXXi 16690 20799
19600 21700 OMS DMB
3oa IMOM 194 200CO 2190 221CO 50 15
DMB
50
DMB DMB D«S DMB • '' '
IS 50 15 ?n
«% 2^0000 29990 22400 (30-225I (39225) ,(30.225}
jOOOCO 30500 22600
Unlim'ted 2080V 227CO
C"'^ •
31500 35000 DM6 DMB DMB DMB
DMB . 0M8 DMB
10» 13DOOO 32500 3500 36C90 M 25-1 50 15 50 . 25-1 50
s% 2i£000 93900 36600 . (150.909) (30.225) (1S0.6CO)
50OCKJO 34000 37600
UAllraTti j 34600 38100
ifiali.
.'• I
- '
18'
•' - •- v -^r i- -
'"-;r7.rT^rTTrTT'T-*! . •
. •t •... .
s
^ F f.
\ y" I'xiMVltd
50000
• 274O0
26600
33400
35600 DM3 15 {20-225) DMB 50
U04 02300 9000 41300 OMft .DM8 OMO DMB 14 {73 2231 DMB ' DMB . OMB 50
10C0CO
1500 150000 34600 45i03 75 30 73 0M6 14 CO 225) 73 50 DMB 50
5V^% 250000 37000 *6Wi (400.1600) PMt 14 (20224) (400.1600) DM8 53
47900 DMB 14 C9 723) OMB 50
500000 389G0
41100 501C0 0^3 25-) nOO 600) DMB 75
50COO 3)700 45700 DM8 59 <400.1600} DMB 14 129-324) DMB 50 (400-1600) DMB 50
1COOOO 2406 39400 12000 51400 0M3 DM8 50 (400.1600) DMB DMB 23.1 (lOO-fiCOj DMB DMB 50 (400.l6Ou) DMB 73
20G0 DMB 50 (400.1600/ 73 DMB 25-1 (1CO-630) 73 DMB 39 (400.1600) OMB 73
120000 44100 56100 73
5%% 250000 47700 59700 DM? 50 (400.1600) DMB 25-1 (100-6001 DMB50 (400-1609)' DMB 73
500000 50700 62700 0M8 73 tCCiM^SOOO) DMB 35-1 ,'100-6{>0| DMB 73 (2000.3000) DMB 73
54700 66700 DM? 73 (»yi.30»1 DM8 75-1 (100 403; DMB 73 (330O.50CO'; OMB73 '
v.
50000 6450 7900
0300 DM8 DM0- 0M8 DMB OMB DMB DMB
100000 2i7 6350 1450
300 150000 6950 B400 23.1 15 25.1 15 23-1 13 15
5% 250000 7050 6500 03.223) {)5.225) (13.235)
500000 : 7150 8609
7250 8700
SOOOO 25000 349C<3 DM6 40 (200.1600) OMB 24-1 |43 630) OMB 50 (200-1660) DMB so •'
* 1W4 31609 9600 41200 DM6 DMB 50 (200.1600) DMA 24-1 (43.600) D'AO 0M& 50 (W0.1690i DMB 50
/ 1 .
150000 35000 44900 • 73 . OMO 50COC UOC) 75 Da;&?4.1 (40-600) 73 DMB 4C (209-1600) DMA 50 •
! 5Vj% ?>3C0J .37560 ;• 47100 OMS 50 (200-16005 OMB 25-1 (49 6O0) DMB 50 (20O.)6OC« DMB 50
DMB 74 t20CC :-3Cr0' DM& !0 COO.I&CO) DMO 74 (200O-)0CO) Dr^8 73
19
P R O P O 5=^ A I
SPECIFIC PROCEDURES
Control coils, closing coils, shunt trip coils, charging motors, integral
control relays and auxiliary switches and relays are cleaned, lubri
cated, adjusted and inspected to be in proper working order. Contacts
are burnished or replaced as requij?ed.
The primary disconnect stabs on drawout circuit breakers are inspected
for wear, pitting or burning and cleaned and adjusted.
The circuit breaker frame, insulators, and main copper details are
cleaned of all extraneous foreign material (dust, dirt, carbon,
moisture, etc.). *
This quotation includes current vs. time calibration on all low voltage
drawout air circuit breakers.
SC:SP-LV-CB-2
11-17
PROPOSAL
SPECIFIC PROCEEDURES:
3. Instantaneous Pick-up.
SC:SP-LV-CB-3
11-17 -2-
.. .
''i'"r '::'.f^C'
,.••••.•)'--v, •
.••.:;•• •: •
' • *- f. .'fc '
•"' •• I
*• ' , ' I ' ''
; l.-, . , . '
<(A ''K*.' . .
::V- -•
. •" • w" •
• i •' • ,
.-v.-,-'.'I .•V •'
•.' . . ^ • 4 n^;< I
If
• '•C':S.-i't'-R : ,• • • •-•
; *
-a: "
' .'• . l!''-' '*•*'. . •«
•g-RV^vG^ncral
Refinishing
uf-j
,'vR;.V<;
•".I-'tBHU.-i HEC?iFIEi^ FO;^ GI:^CUi?- ^j-ica
. ^ . lUTEKi^mXT^TY
:Operation " .
Overloads •
2 -
, " i-:
SELSJIUH Ri;CTvpi:.:nS ?.:?i ClKCUI? BKiiy-m UPHtaTIOK
INTii;F^!XTTS5T VJTl
. a«. Fuses
•I
' .' • : Use current limitins fuses having rating of approximately
1/^ :dZ the inaxium d-c load current dram by the breaker
solenoid. Fuses, of this rating aro used in order •to
! protect the rectifying unit in case load should retrain : .. .
•I'.V- 'iii*
: i; connected, to the.; outfit for longer th^ the permissible
;• /bime,,;;. .0: > " ' , /X
bo. • Sectifier X- ' - v
3-'
SoiiiKIU}'! •R;:CTj:FIiaS FCR CIRCUIT BRI U. vR OPiCH^VTIO;
••k. ,;ijai :iCheck the a-c supply sobrcb'to^ see that ade^udte voltage
lislavraiiablQ when the I^ilrlo^ ds. being drawas k^ k k
Check the rectiiier-fuses to see that they are ;not blown-.
c. Inspect all ocnnectlons to see'.that none are open. •
d'. 'If .all of the above appear to be satisfactory then probably
.a rectifier, unit .has failed k^less. the breaker -mechani'sm
is.,.out of adjustmenlfi,. • ' • S.:' v ..-
A. The failed vinit ma.y be detected as foHows;
•' a. Disconnect the rectifier from ths a—c and d~c. circuits.
bo Appier 110. volts a~c if/ith, a 3.00 v;att lamp in seri.es to the a-"
temiinals of the rectifier for not .'more than one second^
•C» If ;the -lamp lights, one or more of .the individu^ stacks .have
failed. ' _
- 4
??SW|S5j<5?
•••'•" • •' • •• ; •.' ^-••V -V
' ' 'bo Apply to"the a~c, teminals oif sich stack in turn the iiO;voit
a-c, mth the 100 vfatt lanp in . series as before;, • '
•• • ';.V. .* ' -vv:. ;
- r ' c, AI3. iinits v;hich light up the lainp..should be rem~/oa.
'r:- :. v''
^ .rifev'-N;.•. . ^
v.-;. V•
-yy
li/-' K
•.'••-•
''
T /-
' '''• 'At:-.-
..-.Av'-TT': • •;. ViGTiT
''
•SI "• :.. ;••• • . - nV:'' -
:A:r : •;
. i
•GTS'.'
.V,
:*
• :>•. ' V T. 'r'TA..''
•f\ .iV^o:--l::A."T ,• yf. >'•: ;• -."v
.•;. .•.=• ;.:-l ,.
' -g'-'
.: Jj., . . ; , .
'''•.'••i'V-'
A;<T^rrSjG:A?.vof
!• A?. Viiv fife;.' .• : Gsj
...•
.
;,TT:",T.:,
"...- "
-•V-vfc'V - • y:}' y4f':Mc0M
W.; Av"
. . .- . • . : .T'G-TT .-' . • • : U-T,.':, ";-A"-:.A,
. . A
/ • "...'•
i.yy- .. vl-l-'.
;ATs .T'TV:''
A;
1 •:
.ywrrnm^'Siyy
• ' h •
•;•
-... 7 'AS'
.
•
. • ..'aTT:
..A'-':'.-j, ..^T
••/ •. •" -•
••-•- VX' ;.: ;K;.,
• '• • ••*••-": >-'.
vA.. ; •^ ''ArTr'AT,;!
. ...-; ...
-•.Av' /G. •
• '.A.
..• 'tV'.
T-♦
TAG.'. G. •
- "5 -
!
- •INST.^ATION, SHEET ^
. ..V Push breaker iritp cubicle, until it'sxops and rabi'buttpn on, lower , .
ielt-hand side of breaker pops up.'f Breaker id "test" position'.
PraJnary discorniecting contacts are not engagedy but secondary dis-•
.: connecting contacts are in contact with similar .contacts in cubicle <,
Press dovsi on read ^ut+on end punh breaker in t5.ii .•' !•• resistance.
Release red button the moment breaker, starts to move in, .Insert 5/6"
i'ack3..ng-in handle-bar in right-hand side of levering-ix*. '''.urretat
bottom of carrj.age voider the breaker face pj-atei .. P\ish handle-bar to
''o evic; oi'.; •cii -
• •' . •- , -na ' V:.ori will i;-
C «-•- C •; '\ i* "'' "*:.^ . w^nCvS ':..o'..' '^n^/S'^ec
liocked end o:? handle-bar into turrebo
To remove breaker from cubicle, press red buttpii down, ,and pull
breaker forward and out 'of the cubicle.. ^ ^
Wbte that pressing down on the red button always: trips the bres.!-ev';
It is impossible to move from ."test" to "operating", or from "op-nr-
ating" to "test" vjithout first tripping the breaker.
After the above test operations, the face plate should be: adjusted
in the same manner as described under installation Fixed.
The breaker should nov7 be pushed into "test" position, and secondary
circuits checked. If it is a manual breaker vJith:,shunt-trip, or under-
voltage, or bell-alarm, the'control circuits can:~be energized and the,'
above accessories checked: If it is an electricallyvoperated breaker^"
the Control circuits can be energized, and the breaker operated several,
time-s to make sure that it functions correctly-.t .fc acces--
•series can be checked at the same time.,', S
V-: ' .
For description and maintenance see: IX'lB-15 and lIiB-25-1 Instruction Book
For details and characteristic curves of Manual 3-266 (.Selection and Application:.'
overcurrent devices refer to; • 'of Federal Pacific Air Circuit Breal<:ers) .y, l
v:>» .•
^11 i.iiii)Miu..iiiwii
-'i;, V : :
teEAL PACIFIC ^CTRlC COM?^ -f • ' vr. • • •
< • J
f- Eastern Switcbgear: hivisioh
•Meith Keyser Ayenua) P.; 0. Box 1510 •
. Scranton, Permsylvatiia •.'i':."-••V-..
•;
•-C." .}
• il^STRUCYIOM^ . ^ vrV •
•
for •
ElATSMGS: -m.
600 Voi ts A-C 250 Vol ts D-C
. '•••: -y
Type DMIJ-25' Type bMB-50
•y ..
• • • V- -y Mi
t .^..
•tf-i-y'yi
.;'i' ,
-V! '•y
.. ;
•• ;
CONTENTS
, . ' • • , Page.
General Description 5 ^
Standard Equipment 5
Optional Accessory Equipment ..y... 6
Shipment, Receiving, and Storing 7
Installation and Operating inspection 7
Inspection of Manual Operation 8
Connections 9
Drawout Mounting 9
Phase-isolating Batriers 10
Electrical-Operation Inspection 10
* N'
0, •!r<j--302 • f • ; ' •
.{•.jSiil, KS'l Federal Electric Products Compcny Pcge 3
•..'.Sr
The descriptions hereirr refer to 3-poie breakers. Two-pole breakers are the
same as 3-pole breakers except that the center pole Is omitted.
Note: This Instruction Manual does not necessarily describe oil late improvements •
in construction nor all details or variations. Conditions may arise during"
installation, operation,, or maintenance that are not covered herein. For
Information as to these or other points, .efer to.
Federal Electric Products Company
50 Paris St., Nework 5, N.J.
or to nearest brancrr office
•• "ft
' ^ ^ ' r;
i • • ii •
: p ! • • • •>
^ •
' I •'•'1 • • :- y
/•i« r:;" :V
f- -
^ ' , • i
Rev, I IN^302/.y
•V-" ^ i'WS'vv^f
' ii!) A/
1>-....- • , .'V •;
<'. ,''f;" .•
i'i ;* 77
' 1 •':'7 "": '."•*.i'.'>
•V.M'
•/ A • i "d- ^ i
/T '?• •I •V" .'.• '. •= y
fil .1 c; •
in .. I- J-iiiv
7:"
f
\r. 7?- S.f !•M=i-v A
^ . I -J li -:v .Si-:
H'y
" bF f' •••s f'-y-»;."
•'hf
{•>. V-.- t
,;l
...'
n • •-' "t '.r • ^ • ^ -N.! . =v"^
'^5 •
•[•'li-'.-'X
If .-. •}. Fig, 2 (above) ; j.;;
aA ''•••
h, (iv.,'
i? I' • -u.' :
••
• -ff-a Federal-Pacific Metni-Fhclosed :v7."'>
{• Switchgeor Uniii One Type
?;•
5 * • i;v. DMB-25 and two Type DMBr^ ;;
r\' 50's are shown with phose-
.%
: iA <4,
i ; >5i. isolating barriers in place.. uvrtx.
•> r • • V'-:-'•
• 7'.?« - •
;i '•;
"ilAAV/i •r7- '• i i;, .•••' 7' .7 ^ ,, V .as
-. i '.7\' "*/•' " i"' A ";iS.:
•• p.
,; tit'- .'•'iiifV;.'
•\
.'.*• ''•'.•"^f^'•^.*.
Ray. 0, ;iN-302-
^ ' '^s
. ' ' '
• •
FEDERAL-PACIFIC
GENERAL DESCRIPTION
These circuit breakers are of exceptionally sturdy design, built for long service of
frequent load switching and automatic interruption of overcurrents within rating. They
embody features thathave been field tested formany years In thousands of circuit break-
ers of this design. The circuit breakers ore electrically and mechanically trip free in .
any position of the closing stroke, end they will olso latch closed in the case of either
electrical or manual operation when they are closed against a sustained fault the current . '
of which does not exceed interrupting rating one-half cycle after contacts moke, Tho.
interrupting rating of the breaker is not affected by the selected standard.continuous
rating; that is,'the interrupting rating of rhe Type DMB-50, for example, is..50,000 amp
even though the overcurrent coils hove any of the standard continuous ratings from 100 ^
to 1600 amp. ' . : , A:
STANDARD EQUIPMENT"
The following operating features are regularly supplied with all circuit breakers ^
orranged for electrical control: ^ ^^^
2. Manual tripping and closing from the operating handle, with provisioh for pad- ' 'A
locking in open position. This padlocking prevents manual closing and it also maintoins
the breaker in trip-free condition so electrical closing cannot be completed. If the-. ,- .
breaker is mounted in a cell, the door cannot be opened when handle is padlocked.
3. Flec''r'''.al closing from solenoid. The control circuit energizes the operating A;
coil of a relay, the main contacts of which estoblish the circuit through tlit olenoid.
Seal-in and anti-pump features are provided for maintained contact control. ^
5, Fo'.'r-circuit auxiliary switch of which one ciiccit is required for switch oper
ation; the balance are available purchaser's use.
Suitable interlocking of operating and control functions ds de^crited herein, ore
provided to protect the breaker from the effects of mlsoperotion.
•; •l&ryV*
i; -/- « t>i CTj*
, j;/ .
3. Overcurrent bell alarm device—electrical and hand reset. Operates only when. ?•
tripping is the result of overcurrent. If required, provision is also made so thatelectrical •
or manual closing is prevented until the bell alarm device has been reset. .
4. Key interlock locks breakei in operj position and also opens the solenoid :
control circuit so electrical closing cannot be initiated. The breaker must be'in open „ :" •
position before the key can be removed. • .;;
9. Dead front, back box, and other met,!iuriicGl features that have to do with
housing the breaker ore considered a part of the breaker mounting, and are supplied as
specified. ' : ;•
* ^
10, Special overcurrent tripping devices. See Special Instruction or.referto factory :'
for description of these devices ^ Iiicii •• wi'ls- .'criety is available.
11.. " ...
Rectifier -•
for use "
when alternating current . -
is used for solenoid supply. Note; if ^0^':-
specified, a-c supply can be used for the shunt trip device without need of a rectifier.
sag
(:»!«. ¥ V-;;
Each circuit breaker before leaving the factory i^ carefully inspected, tested, and
packed. • It Is shipped in a wood crate. Hooks should not be used when handling. Ap
proximate net weights are as follows (with regular accessories). Add iO % for breakers
mounted on drawout platforms.
Upon receipt examine all equipment carefully for.indication of damage sustained v;. '-
in transit. If damage is found call for inspection by the delivering carrier at once, and
file claim with carrier. For assistance in filing claim it is odvisable that information os
to the extent of the damage be sent immediately to Traffic Manager, Federal Electric
Products Company, 50 Paris St., Newark 5, N. J., giving description of the damage, .Vr'^
identification of the breaker damaged, the delivering carrier's name, and if shipped by
rail, the car number, waybill reference, and any other information that will enable the '..-M-
manufaclurer to be of help in filing the claims \ ' S;!
When unpacking the circuit breakei, the crating or boxing must be removed care- ^ ' '^v
fully. Check all parts with packing list Avoid bending, breaking, or injuring any
parts. Do not leave screws, bolts, nuts, etc., in the packing material, Clean all. parts
befbf^ assembling them; use compressed air, if possible. See that instruction books, ^
drawings, and tags are kept with the breakers, -
^ When the circuit breaker can be Installed immediatel^y in its permanent location, it . •l.'^-v.-
is advisable TO do so even though it will not be placed in service for some time. When
set up in buildings under construction, it should be protected from dust/ dirt, and mols-
ture. 'v'. V'
• .'t '
If the circuit breaker cannot be installed in its permanent location irrimediately and
it IS necessary, to store it, it should be kep'- .r. u ciean, dry place. It must not be exposed
to dirt, to the action of corrosive gases, ur lo ^ussiblc .mechanical injury. Special care
should be taken to prevent injury to the apparatus through shocks or jars due to rough
handling. It is recommended that stored breakers be covered with paper instead of by
materiols-that may absorb or retain moisture. Do not lubricate the breaker. .Sufficient
lubricant was applied at the factory; additional amounts only attract d.irt,
>
to the operator clue to arcing or parrs movement during cutoniotic opening. Spoce must ; •
be provided for cleaning and inspection and for protection of adjacent apparatus from
flashover. Enclosed breakers should be placed in, cells or housings hoving minimum V":
2. Raise and lower the overcurrent trip shoft 52 (Figs. 12 and 13) to be sure it moves
freely.
3. Turn handle slowly in a clockwise direciloii to move the contacts tov/ord closed
position. Note that all ports move freely except for spring resistance. Note that con
tacts touch approximately simultaneously toward end of closing stroke. Continue closing
until completion of stroke. There should be o distinct drop-off of force required to turn
the handle as end of stroke is approached. This Is on Indication that the linkage has
properly moved "over toggle" so it is self-holding, sometimes referred to as "latched
closed". Return handle to neutral position. Are clearances Mand N (\/iew B, Fig. 9)
as specified? Is trip trigger 37 well clear of pin on end of trip lever 21 (Fig. 9) so
normal vibration will not be likely to cause unexpected tripping? Check jam nuts on : •
spring studs to see they ore tight (part 22, Fig. 9A), for example. Visually check but • t \: - '
dc not measure clearance P(F:g. 98). This clearance assures adequate pressure on lower
main contacts 13 in case of normal expected wear of contacts. Check cll compression
springs 10 and 11 (Fig. 9). None should have coils solid. • . 1 •.
4. Rotate handle counterclocky/ise until breaker trips. The mechanism assumes the.
position of View D, Fig. .9, for an instant, and then it returns to position of View A
becouse of pull of opening reset Spring 23, Return handle to neutral position. Did ports /
move freely? Check cotters, and all accessible screws, nuts, etc., for tightness. It is : i;. Vi"^
suggested that the section on Manual Operation on page,13be studied for explanation of
whot happens during the preceding closing and opening.
'y
5. So for as it rriay be done without electrical connections, check the action of "
the electrical devices and accessories. This will old in assuring proper operation of the /
linkage to \ ich they ore ttoched whe; electrical operotion can be effected. The . 1?:
explanation of how these ports normally operote os given in lover pages Will indicate
what should be done. For exomple, after again closing the breaker move'overcurrent
trip shaft 52 (Figs. 12 arid 13) in the tripping.direction to see if tripping occurs. Siml-
iariy try the action of the shunt trip and overvoitage release if used, etc. In these
cases trip trigger 37 moves clockwise sufflnlently to engage pin of trip.lever 21 so as to "
release the trip latch.nThe larch should always reset ouromaticoily so the tinal position ,A4
CONNECTIONS; -
Before making electrical connections every precowtion must be taken to see that all
leads that are to be connected to the circuit breaker are de-energized and will remain
so throughout the work. For ncn-drav/out connections be sure that all joints ore clean,
bright, and free from dents or burrs and that fostenings of the connection studs are tight..
All nuts on a current-carrying stud should turn freely; they should never be forced down
with a wrench. If they cannot be turned freely by hand, tap them lightly on the outer
surface with a hammer and turn by hand at the same .time, A nut that cannot be worked •M-
down in this manner will ruin the thread if an ortempt is mode to force it. ff the joints
are not correctly made, dangerous heotlng of the circuit breaker may result. •
Cables and connections should be properly supported so that the clrcuit breaker is
not subjected to unnecessary strains. Any strain v/hich at first has no apparent effect on
the stud alignment may. In time, force the studs to take up a new alignment due to
vibration during opening and closing of the circuit breaker, and poor contact may result.
To ovoid overheating of the circuit breaker, the connecting leads must hove a
current-carrying capacity at least equal to that of the current-carrying parts of the r. •
circuit breaker. Control wiring should be so installed that trouble on one circuit breaker
cannot be communicated to the control wiring of another breaker.
The control voltages and currents listed on the next page are a guide for determin
ing conductor sizes for the control circuits;
|n the case of drowout mountings, it is important that the non-movable parts of the
main and control terminals be located cccjrately in order that the contact springs of
the terminals will apply proper pressure. Even a slight variation of location rnay couse
a large variation of contact pressure. Do not use the approximate dimensions as shown
in Figs. 5 and 8 herein. Use only such dimensions as are shown on prints certified as
correct for construction applying to the particular circuit.breaker being installed. •
This Ifistructiori Manual shows several typical connection diagrams but hot all vari
ations ore included. In all caises, a certified print of the applicable diagram should be
used.
DRAWCIT MOUNTING. ^ : ^ ^
Figs. 3, 4, 5, and 8 show the circuit breaker mounted on drawout platform with
support and side-guide rollers for use in the cell. Adrowoul locking device is attached
to the lower^part of the deft si.de frame (Fig.. 16 shoves one form- —slightly modified on
some models). Cell^ Interlock, lover 58 shotilrl ho kept pushed down so the'- interlock rod
will not interfere with entry otthe circuit oreoker Into the ceii or cause it to be stopped
in test position. When lever 58 Is pushed dov/n, trip trigger 27 moves to such posiflon
that the breaker will be tripped if it is not already in open position. Ease of movement
complete to full-in position aga.inst the resistance of the springs of the termihdT contacts
•s assured by the leyerihg-in device (see the "turret" at front of platform in FlgdCS) that;-
' • • - •'7>
is used on circuit brrokers in cases where Federal-Pacific supplies the enclosures. Insert
a rod in the turret and turn it clockwise (looking down on tne turret) for the final move
ment to full-in position.
If the platform is equipped with cell-catch lever 61, the end of the lever will be
seen to move inwards slightly as a stop pin in bottom of cell is passed. When with-
drav/ing breaker from the cell it is necc^-u. y tc p-ish lever 61 irward near the end of the
withdrawal to release a catch before ct viute v/ithdrowal con be accomplished. Some
models have on equivalent device that is part of the side-frame Interlock assembly.
115v a-c MM
95 M M
3.5 95 3.5
230v o-c 190 190 50* 1.7 190 190 60* 1.7
460V o-c 380 380 25* -.8 380 380 36* .8
PHASE-ISOLATING BARRIERS:
As on aid for assuring complete isolating of phases and as an added precaution under
some conditions of installation, a barrier assembly, if supplied, is used to supplement
the effectiveness of the ore chutes (see breaker insrallotipii of Fig. 2).-- if a barrier u
supplied it is important that it be installed on the circuit breaker when it is ready for
use.
ELECTRICAL-OPERATION INSPECTION;
After it is certain that the wiring connections have been tested fcr possible grounds
or short circuits and that the circuits are correct in accordance v/ith the certified print,
the circuit breaker should be tested for electrical operation, but with the main leads
opened at the disconnecting switches or by having the breaker in "test position" in its
cell. This provides a complete check of the electrical control of the breaker.
1. Repeat the manual operation tests described on page 8 but without checking
clearances, etc.. Check to see that ports move freely and have not become affected by
:th6 installation work of connecting. Leave.breaker in closed position* •77u:K'#r'
• 7": •
„ ^ f • '7
2. Momentarily close the shunt trip circuit. The breaker should open and the latch
should automatically reset. If the lotch did not resetmove handle to latch-reset position
(see Figs. 5 and 8) and make a note to check the reoson why it failed to reset (see oaae
19). . .
3. Momentarily close the closing-control circuit. The breaker should close from
operation of the solenoid. Check to see that clearance between trip trigger 37 (Fig, 9B)
and the pin on trip.lever 21 is the same as when the breaker is closed manually (tr^y.all
manual closing and compare the clearances).
4. Repeat shunt trip and electrical closing severe! times to make sure thatoperation
Is normal. Check clearance betv/een contact kickoff 64 of control relay and top of
collar 63 on stem 62 (see Fig. 17).to see if it is as specified. Place the mechanism in
trip-free condition by holding trip trigger 37 so it engages pin of trip lever. 21; mean
while move handle to closing position. The handle and shaft action should befree with
out evidence of binding. The handle parts will move tov/ard closed position but the
shaft parts will move only slightly.
• Bell Alarm; With breaker closed, move overcurrent trip shaft 52 (Figs. 12 and
13) in tripping direction. Breaker should open and alarm ring. Move handle to
tripping position; the alarm should stop. Again close breaker and trip by turning
shaft 52. Close shunt-trip circuit; the alarm should stop. This assumes that an
auxiliary-switch contact momentarily completes the circuit through the shunt
trip coil even though the breaker .is in open position. This description applies :
to the usual normally open bell-alarm switch installation (see Figs. 20 and 21).
Also trip by shunt trip and again ky manual trip. In neither case should the
alarm ring. -
Kirk Key Interlock; The electrical feature of this device is that the closing-
contro! relay circuit is opened when the breaker is key locked in the open
position. Lock the breaker in open position by the Kirk key lock and close the
closing-control circuit. There should be no operation of the control relay.
Undervoltoge Device; If facilities permit, arrange for applying-reduced voltage
to the coil of the device end note the voits at.which the breaker.is tripped. Did.
the mechanical reset rod extending from arm on main shaft (see Figs. .10.and. 11)
p^ooeriy reset the device? If the d<=yii_e is of the time-delay type, allow about
one minute for reseiting.
Other Accessoi ies; Perform such operotions as required to check the effective-
ness of any other accessories that embody electrical features.
With the breaker in open poi.lic.,., vicsu ihe disconnecting swii -h in the main leads
or move the breaket to full-in position if it is in c cell. Apply some load end repeat
manual and electrical closing and opening as a test of normal switching. Remove the
breaker from its cell and completely check connections,, bolts, and linkage to see that
nothing has become loosened or displaced during the test operotions. ;• Reicistb!!- circuit
breaker; it is now ready for service;. . • " • ' • • Art-'
f r :» <?/> <,r> •• -;••/:•
•i,.h
•'<^:'• '• . - Fecferal Electric Prob'ucii CoTipc •< - ""/.rr.'i, i9c '/
METHOD OF OPERATION!
Complete Information as to how the circuit breaker operates is of help v/hen tr/Ing
to locate the cause of improper operation. It oiso serves as a guide for understanding
the reasons for the adjustments and checks made during installation or maintenance in
spections,
CLOSING: V
Fig, 9A shows the position of the principal ports when the circuit breaker Is open.
To close the breaker^ main shaft i Is rotated clockwise by the closing solenoid or by the,
handle until the parts are ds shown in Fig. 9B. During this operation trip link 5arid,
strut 6move as one piece because they are latched iogerher by the trip latch (in trip'
link 5). Because links 7approach toggle position" as closed position is reached, a lorge
force is applied to turning square shaft 8. Contact springs 10 and_ 11 are thereby com
pressed to assure high pressure at main contacts 12 and 13, and moderate pressure at the
auxiliary arcing contocts 15-16. Ajumper 14 shunts contacts 13 and electrically con
nects qii moving contacts to the lower main terminal as is necessary during arcing when
opening. Contact 16 does not touch arcing horn 17 when in closed position. The arcing
horn is electrically connected to the upper terminal through a magnetic blowout coil
(^hown diagramatlcolly). On the Type DMB-50, jumper 36 shunts the main arc to ener
gize the blowout coil, but.there is on auxiliary air gap in the blowout-coil circuit (in
the arc chute) that opens the blowout-cpi! circuit when the main arc is extinguished.
It is not necessary to apply closing force after the breaker is fully closed because in
the final stage of closing, link 6, trip link 5, and main crank 48 are in a straight line;
in fact, they are "over center" so the mechanism is positively held in closed position by'
the force of springs 10 and 11. Such action is sometimes referred to as'"latching closed",
although there is no closing latch in the usual sense.
The Type DMB-25 circuit breaker has one complete moving-contact structure per - ••
pole (see Fig. 3). Type DMB-50 has two such complete structures per pole and eocb
structure also includes a shorter structure that comprises only an d^embly of main con
tacts 12 and 13 and associated contact springs 10. Thus there are four spring-applied r •
moving contact structures in parallel per pole in the larger circuit breaker (see Fig. 1)," '--r
Note fr'-ot neither electrical nor mon'.'s! closing can tqke.place unless trip link 5 ,
oiid strut 6move rigidly as one piece. Theretore ir tor any reason the trip latch is re
leased, or it did not^reset properly during the previous opening, the straight-line reld-:
tionship of the ports is no longer maintained and closing cannot occur. The breaker thus
cannot be closed if the shunt trip coil is energized, the low-voltage release operates,
_ or the breaker is not in its eel1at least as far as test posi; ion.' Also when closing against
° ''"c sul^f'cient to cause ii ifjpip.g , the breakerW.If trip as soon as
the circuit is established even before the breaker "iatci-cs cioaod" provided the over-
current
to CQUaedevice acts instontaneously.
The breaker to latch closedTheoven
closing
whenfcrces, hov/ever,
the fauii currentareissuffibiently Isvrge
as lorgeosrated
interruplmg current, provided the overcurrent device permits sufficient time, deldy for
complete closing to occur. •• • • ' • ;j ^
1-
r:;,.: ': ...
L Ir ' i- - ■♦•''
•;;;a
OPENING BY RELEASE OF TRIP LATCH:
;;
Current above pickup amount through the series trip coil In each main lead causes,
either time-delay or instantaneous tripping according to the type and setting.of the
overcurrent device (see Figs. 12 and 13 for tripping oction). Trip trigger 37 (Fig. 9B)
moves clockwise to move trip, lever 21 to release trip latch 38 (Fig. 9D), thereby col
lapsing the linkage and causing" the mechanism to move to the position of Fig. 9D as a
result of the force of contact springs 10, The upper main contacts 12 separate somewhat
before the parting of arcing contacts 15-16 (see Fig. 9C). The mechanism is then rapid
ly brought to the position shovyn In Fig.:9A by action of reset spring 23 which turns mqitt.
shaft 1 counterclockwise. The trip latch resets during this movement," thereby joining
link 5 and strut 6 so they act as one piece.
Opening by release of.the triplotch; as described, takes place in all cases of over-
current tripping as well as when tripping is the result of the action of the shunt trip"
device, no-voltage release, reverse-current device (d-c only), the drawout locking
device, or by any action that moves trip trigger 37 so it engages "pin on lever 21. Trip
ping takes place at any point of the closing stroke because trip trigger 37 extends Vferti-
':;r
cally alongside the path ofvertical travel of trip link 5, so engagement will occur when
ever trip trigger 37 is moved clockwise regardless of the position of trip link 5.
MANUAL OPENING:
The trip latch is not released during manual opening. Instead, the opening comes
about from handle movement which causes main shaft 1 to rptate counterclockwise
(viewed as in pig, 98) sufficiently to collapse the "over center" condition, of main crank
48, trip link 5, and strut 6. The force exerted by springs 10 and 11, supplemented by
the pull of spring 23 and other springs, completes the opening. The parts move directly
to their position as shown in Fig. 9A without need of going through the intermediate step
shown in Fig. 9D.
HANDLE-SHAFT ASSEMBLY:
The Operation of this assembly on the Type DMB-25 circuit breaker is exploined by
reference to Fig. 10. The parts and their connection to each other ate as follows:
Coupling crank 44 -- turns loosely on shaft 40. Clutch jews extend from the left hub of
the crank. Also pin 82 extends from the left flcnge as shown. This pin has a flat
surface that can be engaged by the clutch [aw of sliding-cqm clutch 42.
Main clutch 43 — fixed to shaft 40, Only a pert of this shown in Fig. 10 becouse it is
icgc:/ surrounded by siidir.j cc clutch 42, Jew projections extend from the right
of. main dutch 43, ' "
Sliding cam clutch 42 —concentric with and loosely turns on main clutch 42,. Avetti-
. .; col pin .(not shown in Fig., 10) extends through .shaft 40 and mQ'h clutch 43, into q, i
^Ibt.'n cam clutcK 42, This pin sei'ves to control pen t ofthe motion of slid.in9
'c (••1''? Fcclorcl tiocfiic r'i-oducts Cornpony • • April, 193-1
clutch 42 hccai:e the slot-cut thrcrj.;!'. h: bvi&n -.-d i-},© pin permit the cam to •/=.
move lengthwise along shaft 40 by a limited amount, ond also assures that cam
clutch 42 will rotate along with shaft 40 and main clutch 43. •
•. is a groove com recess•in its outer.surface,
The essential feature ofcam clutch 42 ^ — .S-
Fixed pin 50 extending from the frame into this groove cam holds cam clutch 42 •^ ^
without any movement lengthv/ise ofth" shui'r during ai) normal closing and .ripping ,'
movements of handle 3. . However, if handle 3 is moved to latch reset position (see . --^iv
Fig. 5), then cam clutch 42 moves to the front because of the curve in its recessed •
groove cam. " • • f. ', '';'nl'
Alarm cam 72 —attached to left end ofshaft 40,is bell-alarm accessory, if specified.
Position spring 41 and arm 83 and associated pins return handle assembly to neutral ,
position atend of either on opening or closing stroke. Coupling crank 44-f however, V.
will remain in either open or closed position. ;v?
• *' "r
The descriptiori of hdndle-shaft operation OS given In the preceding opplying 'to Vhe^ ^
Type DMB-25 circuit breaker also applies to, the Type DMB-50 circuit breaker except \
that ^in the latter breaker the general arrangement of the parts is reversed: The coupUng ^
crank is in back of the main clutch, and the sliding cam clutch moves toward theVear/of
the breaker when if engages fbr resetting of the trip latch. The alarm.com is located its
-i!, 1954 Federal Eiecfric ?fodi-ats Comrony •'090 V3
an Intermediate position instead of being on the end of the shcft. Also instead of there
being a pin attached to a flange of the coupling crank, the crank is of the two-arm
type, only one of which is engaged through a long pin by the sliding com clutch. Fig.
n identifies the parts with numbers that generally correspond to those of similar parts as
shown in Fig. 10.
HANDLE LOCKS;
Figs, 22, 23, and 24 show the overcurrent trip device, comprising a coll in the
main lead, atii armature moved by the magnetic force in the coil when current exceeds
pickup amount., an escapement-type mechanical time-delay device that deloys move
ment of the overcurrent trip shaft 52 (Figs, 12 and 13), and an. instantaneous magneti
cally operated element that moves the trip shaft immediately if current exceeds a sched
uled percent of pickup amount.
Modificoilwris of this basic device to meet various condiiioiv^ of service are avail
able, Information concerning them accompanies circuit breakers with which they are
supplied, or It is available on application to the factory.
CLOSING-CCNTROL RELAY:
Ci . '" order to relieve the electric closing contact of carrying the large current re-
quired^for the closing solenoid, the closing control circuit only energizes the operating
^ andcontacts
so enoid circuit is energized when the double the connection diagrams)/
of the control The clp^hg'?
relay close because
4i '>« *
of force exerted b/ the relay operating coll. Asea I-in of the" operating coil is provided
through a resistor connected between the two main contacts (see connection diagram). •'
IP-
As soon as the circuit breaker closes, the double main converts of the control relay
pre opened mechanically by upward movement of stem 62 (Fig. 17), which also de-
energizes the seal-in circuit of the operating coil. Blowout coils aid in extinguishing
the arc of interruption of the inductive current of the closing coil.
Should the breaker trip before the operator's finger is removed from the closing
control contact, the breaker will not reclose because the main contacts of the control
relay do not recouple to the armature of the relay operating coil after breaker opening
unless the coil is de-energized. This prevents "pumping" (successive open and close) if
the closing-control circuit remains energized under overcurrent conditions.
AUXILIARY SWITCH:
Interrupting Amp
Volts ' , Non—inductive Inductive
The drive shaft of the auxiliary switch is extended and connected to" the ON-OrF
circuit breaker. G.eeii ond red signal lamps, if required, are supplied
through auxiliary-switch contacts.
. , ^
•SHUNT.TRIP;'\ ;• - : •••A.
BELL ALARM:
UNDERVOLTAGE TRIP; / y
;• ••-.••• ^
The essential external features of the undervoltage trip device with mechanical
immediate reset Ore shown in Fig. 25 in their position when the breaker is closed. When
the coil is subject to line voltage above that for which the device is set, reset level 85 ' • ' .'niT
and trip lever 84 are in the solid-line positions. The slot in the end of reset bar 57. is
also positioned so that main shaft 1 con move between open and closed positions without -
1:"
lengthwise movement of bor 57.
By the means previously described, the upward movement of trip lever 84 causes the
circuit breaker to open with the result that the arm on main shaft 1 moves to the dotted-
line position which" again moves reset lever ,85 to its solid-line position. The under-
voltage device is thusreset ond trip lever 84 will remain down provided the voltage is
above that for which the device is ser. If the voltage is still too low, tr ip lever 84 will
remain up and the breaker will be trip free so it cannot be closed as long os thn und'?'- •
voltoge condition continues.
Connection to the. dndervoitage device should be.to the line side of the bredker if ]
-!•' ..
imrnediate reset is used,' and
. I . .1
to the I . I' « f
lood I .1*1
side if time-delay reset. Is
«
usedM-''
. '".•AAs' the uriden-
•"t 1 '''J.'J.i"'"''.'
yoltage device is" connected to the main leads, its coil must be suitable for the;
ohd kiiid of current interrupted by the circuit" brsoker (a-c or d-c, as the case may^be). ".v,.
• "v ; ,rT\ /.-1\ ••••^ ; :,Vl ,• ' -i « ' ' i" ' "
,i; • '•• ' • . '" • • -
enter handle shaft 40 (Fig. 11) of Type DMB-50, in either co.se locking them in the open
position of the breaker. At the same time linkage opens an electricaf contact in the
closing-control relay circuit. The device embodies mechanical means for preventing •.::;W
completion of locking when the breaker is in closed position. .
To lock; With breaker in open position/ handle neutral, key in place, turn key
counterclockwise 180® to lock breaker in open position—after which key can
be removed. The breaker is locked in open position.
To unlock; Insert key (unless already in place) and turn clockwise-to unlock.
The key connot be removed. The closing-control-relay interlocked contact will/
be closed. So closing of the breaker may proceed either electrically or manually.
':H';
OTHER ACCESSORIES:
Instructions relating to accessories other than those described herein ore supplied
with all circuit breakers using such devices. '
The safety and successful operation of connected apparatus depends on the proper
action of the circuit breaker. Therefore the circuit breaker must have systematic care
and inspection. The following points require special attention:
K Be sure that the circuit breaker is in test position in its cell for all inspections
in which it is necessary to have control current available, or disconnect the main leads
if the breaker is not in on enclosure. Adjustments that can be rriade when the control
circuits are energized may be performed when the breaker is in the test position, but if
there is any doubt remove the breaker entirely from the cell —or disconnect control
leads if the breaker is not mounted in an enclosure.
2. Inspect the operating mechanism periodically and keep it clean.
3. Examine the-contacts frequently. See that they are aligned and that contact "
surfaces bear with r firm, uniform pressure. Replace badly pitted Or burned contacts •
before tl.'-y are burned away so far as to prevent full contact or are likely to ^uuse ;..v
damage to other parts of the circuit breaker. All main and control leads should be dis-
connected wheri working on the contacts-.
4. All contact members, both main and control, must be kept clean and bright to
insure maximum
^
operating^ efficiency.
/
If has been found by experience that operatina
liiui upcrurmg
rhe circui.t oreaker several times at intervals
the ".'i. of not* over two.
. weeks
i. v/ill
•!< reduce
< the
. '" V
effects.or oxidation and materially prolong the effective life of the circuit breaker. It -"•
15 recommended that this practice be followed excppt vhct a circuit breaker which is f ''
regulorly operated every few days will not require such oitention.
5. See that bolts, nuts,- washers, cotter pins and all terminal connections are in
place and tight. .
6. Clean the circuit breaker at more frequent intervals than usual where abnormal
conditions prevail, such as when near salt spray, cement dust, or acid fumes —to ovoid
flashovers as a result of the accumulation of foreign substances on the surfaces of the
circuit breaker.
, • • ' V
CONTACT MECHANISM:
Perform steps 2, 3, and 4 of the Inspection for Manual Operation (see page 8 )
including check of clearances M, N, and P(Fig. 9B) and adjust if required. When the ;• s-,.
circuit breaker is in closed position, the pressure of the contact springs should be main
tained at 50 lbs for the upper main.contacts 12 (Fig. 9) and at 32 lbs for arcing contacts
9. Pressure should be measured by fish scale and pull-away sling attached to straddle
the contact surface so the pull will represent average pressure at center of contact. The
scale should be read just as the contacts part..
The contact surfaces should be dressed with a fine file or sandpaper^ Each contact
assembly is removable after disconnecting jumperand releasing the springs by unsdrewing
holding nuts. The lower end of the assembly has only a pin-in-slot connection*
The amount of effective toggle when handle moves to closed position is adjusted by
the jam nut on the right-^and link of toggle links 7(Fig. 9), but as this is carefully adr
justed ot the factory, it is unlikely that further adjustment will be required. •
Failure of Trip Latch to Reset: If there is frequent failure of the trip latch to reset
so it is found necessary to move handle to reset position to reset the latch more i
often than occasional intervals, the ports and linkage that produce "tripping through
movement of trip trigger 37(Fig. 9) should be examined in detail. Check all clear-
^ # ' • • • I fx \m • i I & I
.
ances betw.-en parts where there should be clearance. Check fastenings for "tight •: -i-:
ness, Check any condition m the mounting of the circuit breaker that would be .. '«•*
likely to cause abnormal vibration during opening. Particularly see that trip trigger
37 is well clear of pin on trip lever 21 at all points of the stroke. Check condition
of reset spring 23 (Fig. 9) and its fastenings.
If nothing can be found that would cause the latch failures, check th"^ condition
of the latch itself by inspecting the latching surfaces of trip latch 38 and latch prop
86(Fig. 9). If the surfaces are worn or indicate the possibility of not holding firmly iffi*
when reset, replace trip link 5 entirely; it includes the latch assembly. The re
moved trip link may then be repaired if practicable.
, •. V- v> •
" . • '.'F-
1 „
... .
CLOSING SOLENOID;
The solenoid is designed for intermittent duty. To remove the Solenoid: Hove
breaker in open position. Disconnect leads to control relay and to terminal block. Re
move pin in link that connects to the core.. On Type DM3-50 remove three hex head
cap screws at bock of coil/ and pull out horizontally. On Type"DMB-25 remove four
bolts underneath the coil. The disassembly of the device after removal from the circuit
breaker is obvious. However, o list should be kept of the parts and of the order of re
moval so replacement may be made in the correct opposite manner., " ^
Each device is removable after withdrawing six bolts from bock frome of the circuit,
breaker. The series coil and the overcurrent-device assembly are withdrawn as a unit.
Do not remove the tripping unit from the coil.
There are several forms of ovet current devices available, and suitable instructions
accompany any that differ from Form A (see Figs. 22 and 24) to which the foilowirig In ifi • • -i--- a"-'".
structions apply:
Pickup Adjustment: The percent of coil rating at which pickup takes ploce (the current
at which timer starts its operation) is altered by turning the exposed knob. A pointer on
a calibrated dial controls this adjustment, •f:A
"AA, :
Time-Delay Adjustment: Remove molded cose, to expose the escapement timer at bottom
of assembly. On the opposite side from that shown in Fig. 24 is a circular disk that has
thin metal projections which can be altered by rotation so they may be brought near to
or moved owoy from adjacent thick bosses. To increase the time of pickup', move the •
thin metal projections "toward the thick bosses; to decrease the time, move them away
from the thick bosses. ' .
Instantaneous Adjustment; Refer to Fig. 24. Place spring end in slot No. 4 for greatest,
percent of coir rating at which the device changes from time-delay to instantarieous:
operation. Place spring in slot No. 1 for the smallest pertent of coil rating at'which • AfcH
the instantaneous eieme/.t becorhes effettive,
CONTROL RELAY; ;•
.
With oil control circuits and main leads open, remove cover from relay'housing/
dress contacts, clean the interior, end check all connections for tightness. Reconnect
the control leads.
With the circuit breaker in test position in the cell, or with main leads otherwise
disconnected, momentarily energize the closing-control circuit. The-breaker should
close. Trip the breaker. Again energize the closing-control circuit, but this time keep
it continually energized during both tbe closing ofthe breokerand a following trip. The
breaker should ^not close after the tripping, thereby showing that the anti-pump,feature *
of the reloy is in operating condition. It v/iil also show that the resistor which ifupplibs
the seol-in contact is intact. ' • • -A
•*
/,p,-ll,/l' 54 • Federol ElecJ/ic Prodych Compony Pogo 21
• • •
^ Remove cover from front of control relay. Disconnect leads from the relay contacts
that go to the closing solenoid and the terminal block. Energize the relay operating
;> coil and close breaker slowly by handle. Note the point in the closing srroks at v/hich
'44 the relay contacts are opened because of engagement of coMar 63 with kickoff bar 64
(Fig. 17) • The contacts should not open until it Is no longer necessary to apply strong
force to move the handle. The breaker is then {ust beyond the "sncp-^over" point very : r\ : •
near the end of its stroke. If the condition is incorrect/ adjust at jam nuts dt top of stem
62 until it is correct. HoweveV/ be careful to see that the contacts will open each time H
aff®'" several closings are made, because it is very important that enough leeway be left
*: so there will never be an instance in which the contacts fail to open at the end of the
a'asing stroke of the breaker, yet it must also be certain that the solenoid willremain
®nergized as long as any force is required from it for breaker closing;
After being sure that the preceding adjustment is correct, trip the Isreakerand again
energize the relay operating coil and keep it energized throughout a manual closing
followed by manual tripping. With the operating coil still energized, check to see that
coupling link that connects the operating coil plunger to the relay contacts remains
uncoupled. De-energize the operating coil and note that the link now couples the
. t .
plunger to the contact frame. Again energize the operating coil, which should result in
closing of the relay contacts. • If an incorrect condition is found make such adjustment
as is necessary..
AUXILIARY SWITCH;
Remove front cover and inspect contacts. Dress or replace as required-. The switch
is designed so that contacts close somewhat before the end of the stroke. This insures
complete engagement even if there is some rebound of contocts.of the circuit breaker
during opening. The auxiliary-switch contacts should be so arranged on the shaft that
they are squarely and firmly applied to the contact fingers ofthe switch when the circuit
breaker is fully closed or open, as the case may be.
With breaker open, move the core of the coil against the trip frame assembly and
slowly try tp close the breaker manually. The breaker should not close because of being
trip free. When the shunt trip is not energized there should be 1/32" minirnum clear
ance between the small trip lever that extends from the bottom of the shunt trip assembly
and the frome thot it engages during tripping. "
BELLALARM,.UNDERVpLTAQEr.D?VICE, KEY INTERLOCK,
AND OTHER ACCESSORIES:
The inspection of these accessories is made by performing the work described in the •s\-: - • ^
oDnlicobie pr-agraphs of the section, F'ectrlcal-Operotlon Inspection (page 10), after
which remove covers of the devic.is, dress contacts, clean "all ports, check for loose
connections. The undervoltage trip lever 84 (Fig. 25) should have clearance at" least . ;.
1/32" from the tripping frame that It engages. Ameasured undervoltage source should '/
be available to make certain that the undervoltage device operates when the voltage is
reduced to the omquht at which the device is supposed to operate. / 4.
. • ..
P^ey Lock 67
Celt interlock
Rod 59"'
Adjusting
Screw 60
Aidrm
Beit Crank 75 H I l9(®
Switch 74 •i
Locking
Ljotch 69 —^ 1' ' iciiDj I f, I .
dosed'pr^iti:
y • . . i block 7!
Pin 78 J U Accessory Trip Frame 55 Handle Shott 40 Locking Piote 70 in suplh d.i'^<
thaf-ldc^^:;
cpn^fibe^^:
brddHer0W
Alarm Sv/itch 74 Drive Rod for cl6sed}pcish^
Alarm Switch r.
'V
Plunger 76 —
\-Manual-Trip
Lockout Lever 80
. !
t •
Fija.j7;^><#
ActuOl Cli uy KICKOFPfc
.Cam on Hondto
21- Bel] ALARVi ASSEMBLY Drive Bar 81 TACTS :
Shaft for LAan-
TYPE DMB-50 ual Lockout END of'.Cki.
Shown reody for tripping Accessory-Trip Lockout Rod 79 Type 0MB,!4
• sV'
: >•.
• .t' *>i - *?f •
Closing
Solenoid 4 - •
'y-fdis Bar omitted on Type Dt^B-ZS,
\^;:land Trigger 37 moved by direct contoc; 1
I ; of Wifbdroival Trip Lug 53 ( see Fig. tZ )
O El) O (lli)
— — —Main Shaft I
TYPE DMB-25
AWWWmWWTO!
Spring 65
Clearance R
Vis"' minimum
Plunger 66
Lower Shaft of
Type DMB-Z5
twain
Shaft I
Note: The action is simlliar ' ' ••• • ' •" sii®
in Type DMB-50
S^KE. except for method of upward FEDERAL ELECTRIC PRODUCTS CO. DATE
M PARIS STlIEET. NCVrARK. N, J.. U. S' *. '
movement, for which see Fig. It
TYPES DMB and DS CIRCUIT BREAKERS^-:;
CLOSING COi'L ar:d hVTcPLOCKtNC ClETAltS-'.
im
yj.»
' .»
• R'-'/orr. Srnng -'i! FixocJ Coupling Crank r\<7 Blowout Cr,tl 2'i-
Pin 50 j ( Schematic '} —-
Trip Link 5 —
in- MANUAL DRIVE for TYPE 0MB-25
- - 'CF- 'h—-
Main Crank 4is . Latch Prop
• ft:-
Fig. 9A^BplAKgR
Fixed Pin 50
Coupling Crank 44 (loose on. shaft)
Handle Shaft 40. ^ Handle Return Spring 4!
• * • . •• -3 vi;^.
Oilite Bearing
Fia. 12-TRIGGER TRIPRti>.G- LlNKA%:j^y^
— . ''N.-,,,*-
KicHpff Spindle 51
ir>i-
. • / .V -1 •
•'r U~ manual drive TYRE DMB-50 ; Trip Frame 54 Wilddrawa! Trip;Lr^^^^^
.'''CjCt l€. Ciecrance N- '/iq '
•J'Brj.'.'-O'j! Coil,
supplied
^ l^Arcino Contact
Spring ft
i Arcing Contact
Stop Nut 22
E-K
Y^Contact
Clearance M -
'Tnrp'\. (tO-^
lY Spring to Tnp txrtch 33
h\ \
•yJ Square
j , Shafts
Fig. 9C ( above )
K
I .' ^^Toggle Links 7
ARCING CONTACT ASSEMBLY
Clearance
[ :^~'7'r/p
tt
min
.
,0 otter start of Opening
i ; Trigger 37, r
•y^J\
V
'> Trip Lever 2!
5.EUUENCE
s^Main Shaft I
OPERATIONS
—Overcurrenr Device 20
Overcurrent
Device 20
—Trip Trigger 37 . \
-Trip Trigger 37
Ta Shunt Trip, Undervoitage Device,
•^Ta Bell ana Bell Alarm Lockout
Alarm Lockout
•\ ier~
^ftage Device £) FEDERAL ELECTRIC PRODUCTS CO
Trip Frame 54 ' DATE • err
y 50 PAHIS STREET RfWAHK h J USA \ - •> . .
~iTp Shunt Ttip
TYPE DMB CIRCUIT BREAKERS.
_
S- : hi-'-"-'.!
OPERATING and TRIPPING DETAILS
- •' • '.* ,T. -I L '•
CHUTE-S
; !• :: L
• PLACE -^.Tr ;:=1 , ;• • : • vt
li.r!
•.|•r;jl4 —SVg ' ^4S7
\ 1, -
N •'PI
IV;
•
?r
j
.
i .='••
1 » »
L— -1-^ -T—:—I—
V
ij ",y-—'
t 'Jxfcv For Co// 25" Min, C. td
y ^1-'
rir
r-f
— —
y;'L
Extra Aux. Sw.,
if Supplied ^
\ i'vi^ )'f-'
Auxiliary Swirch n n n
1 1 1 1 1 1 1 1
•1 •1
30
Ceil
Alarm Switch,
if Supplied ——
HO" to Close
1^ I
Shunt Trip —H
; Vr ) -.Pi , ..
tr. f'V,. r. .V *n* j - uh . I
I—I
Underuoltoge
Device, if
:':i.' ' '•• '•^(x P • -^-AS-V . • • P"."plied
• , -,s,..,, •
o:;-
•-; * '
!>•/ • .ti
• (• }. ',i
FR0N1 ELEVATi^f^
• ••""'7 • - ^
•"''W -"^'irl -f'®if^
iii
Far Cell IB
•<• •-•'• : Vi - ••ly -..
ir, -••'•• , .| j. '..y .•'•• "'
I'-
='
-"ll'-,, =•-/
!'•' • • .4 J.Iv- . !•' /
• ' - 1^-Ua
n i rrv ,>i ;
••: f T
^"" .•.•i'.:4.•••;s"! •r?u
!•• • .. • •• '-in
4j'-
-.--v'
' ,« • HT ' • . _
• -M
KTfF^*' ^
• .r'Nfr Device, if z%\
Supplied
.. • 2^4 ^
£ Handle Snaft^- •—-i.
if supplied i '
'/Zr
Cell and Door not included J ^ ^-Breaker
in Breaker Style Numoer L...
Cell Depth 23 " V"* -
V.
a-
•••i
•1)
—Barrier Assembly,
[fir
j if supplied y^^Barrier Assembly, if supplied
/Key Interlock, Controi Terminals
if supplied
Electrical Lockout,. to Bottocn
n
'4i-
If supplied — 1 Extra CI's, if supplied of.
Matching
/
Contact
^fo ^podioc.'^ , Padlock Supplied
--to ^ by Purchaser j Alternate
\ \ location of
Control Termma is, .
if supplied-' ' .... .f
£ Handle rri;
—Solenoid
Trip-"—
i
d 1
T
^4
23% -
Grounding Terminal
SIDE ELEVATION
TYPE DMB-50
S--Z8-5''
••it • CIRCUIT BREAKER
Approx. pirnensions ->.A'ot for Construction
DOOR OPENINGS
€ Handle Shaft -
' ^6 "^»a for i
Kay ipck^ 'i '-
if Supplied
H
C.to C. Cell Depth 20" MIn.
Yy
Bonier Assembly, If Supplied
^^•'Barrier Assembly,
if Supplied
1 Control Terminals
Cell Door-—>-J|
ifti
i
II
II Extra C.T.'s,
1 • '/q
/« Min. " if Supplied 237/q
I
Auxiliary
~r^ /c. to bottom of "v/y '!
Switch
/
/ 4 7/.gJi Matching
»1
11 y Contact
5"
eO I—^ Hari.dle 3/4—
OP
,CK
dio
Alternate Location
of Control Term
•Extra Aux. Sw. inals, if Supplied IV; ./:t» »ii-
if Supplied
Electrical
Lockout, if
Solenoid
Supplied Mi
—Alarm Switch,
if Supplied
Overcurrent
Key Interlock,
if Supplied
to. Trip
•i" ;^".. ilf,'j
v Vj
m::3
•Grounding Terminal
y ATI ON t: rviiioN
qOHTROL
(£r-
terminal
assembly
nn
t4 t4
---I •••'if
terminal
BLOCK
auxiliary
SWi'YCH RES 400A:
CONTROL
RELAY OVERCURRENT
SERIES COILS
Key Interlock
N-C Contact in
this lead, if
used.
CONTROL CONNECTIONS
POWER
SCHEfwATIC
To line side it
OV is immcd'Qie
Shunt
reseT", but to lood
side it time deloy
voltoge
250 V
^ 11
CONTROL SCHEMATIC
ADDlTlf^^f/.
DUALOVERCUR- ,J I
RENT TRIP DEVICE
E25 omp -f:
.<• .--•
O O O. O O '0 — K,.
900000
DUALOVERCURRENT
I.I 20 19 ID 17 16 IS 14
aOTTOM •
TRIP DEVICE- 600 crfip
TERMINAL
assembly Y4.4,. I'.'!
4''
»• •
BOTTOM
AUXILIARY •4 ' r.ef
SWITCH t 'i
1-i-.P 0'-
dualOVERCURRENt
ofOropout VoUoge ^Device Normal . »''• .•.'.-/.•a.
raise dropout TRIP DEViCF-600 omp
' vice rsrso)
-Reset Lever 85
•v
^''^•••1 i-l-
Wit/] Cover removed, showing
I
instanraneous pickup
adjustment
Oevits
/ ' Open
Peleoseti Jr^ '
. Positfon
Undervolioge Device 31
.
federal electric PRODUCTS CO DATE "t'
y SD PARIS STHEET wewxan HI USA...
'VOtTAGF orvirr ArronQement for Trip ond Reset,
^—T— Solid lines of De^rice shQw Reset Position • TYPE DMB CIRCUIT BREAKER ;
SrJt.-S', W'-
''?,'£s -ao\'tjrc'ioN niAGRAMs
Rt^EWAL PART^'&ATALoe APJD
M'AINTENANCE INSTRUCTiONS
Federal Pacific
TYPE DM3 15-T
Air Circuit Breakers
January I960
-I
-• "'If li'- t.
^
U-yrl:
.rQ--
'"T7T.
/V Hi-
i „•
- - '-..-I* '1 "
if.
9-^:
RENEWAL PARTS DAtA •v-'f:>
Renewal F^rts Data wi ll provide you witli the proper Wentificatiphrof those Ren^^ which you
..•. ^•V;..'',v >' may require in the maititif^ance of your Federal Pacific eQuipmE^t ' . . ., •
i . 't 'S desirable to forecast as accurately as possible yoUr requirema^ts for Renewal Parts to -^s-ur-^ fhrt ^
' • SiSSs'S.S'S"' - oniricManS
The recommendations .or stock are tiic minimum quantities that should be.a^liabie for servici'io thi'
equipm^L f^el Lrot you are in a better position tlian v/e to decide how much you wish b inv^s!
Renewal Par.s. ine importance of minimizing shut-dovro Urnedue to possible break-down^ no -/t n .
(ogefiier. with uw- dislarice from source of supply and transportation facriities; should bo c^ot .d.n'ed Ion,
ed by'
you when orcienng renewai parts. i^s-.co.-i.,.i...ied i
r'
1. Obtain the complete'namepla'te feadirig of the
, apparahis for whfch the part is deslrea. jSh'/yo"-'}
-. • .1^, • 2. Turn to tiie Apparatus index and with the name-'- SiMil
plate reading find the page' humbe'r. of the
Renewal Parts Data sheet, ' '
3.
' '* y.*> '*• •• •.
where tlie desired part is d^cribed and
IdcnL'fied.
y^t -
•:S^y
ordering INSTRUCTIONS
,nd adrnt tho p,,,. Oivi it. cmolct, ddmcpte, ll lu apparafus.
" t" '' ''-i''"; W""'- F«' -.d.=d,L Scvu. llL ,= (iKt your
ilEifJwS, ;;Fl^'iJiS ••-' '•'I "a„, C.d c„„.p,,d..c,, Sdi l„, p,p. ,, ,p.
•v^i i i - ' • r'-'yi'
.^ S'^ces. sr...cHa,i •
; . ° Alarm,.seeBreak^ shoul(?
item ll. trip• V
'-*.'•"iV^iV-:".,
Rated Control
Voltage
. ; Control Devices ^'endidjJ^- ; UndervoltogO
trip Reset
24 volt DC
'48 volt DC • ' 14-30 • I '. -_','u> •
•;V-.
'"• '-0 'fuii r.?-;ai-;;,ui rinc^ "'rCna-.iC^r.or eiecfrk faiiuro. Special aUenii: ,j v:> ,i(.
"- '• '(M one end and cotter pins"are bpenfi°"' are in place, springs are net
•lit- ..
. W) Trip roo insulation shouifinotsiip . ": • i-'. ;.?>•
v'"
•^^.-SetcurrehUt9S%ic£unXS^^
lii''
; 3- Reset calibration positioh of overCuWent
r,v<.v •; .•-^-9:^r,.ass othe^^especified-betWe tuml^ : ii'/T •
V
(10) Kirk-Key Interlock •; ;' • -. ' ': ' ' • • •'' '•••\''^'?' V.h';^^ • o"
Alarm-
(11) Bell Alarm ' ' :' "' •' ;y •- .^r- •- V.'.- J
f >
.j|)v?&ip:brpakerWitivb»e^u„^
... •y:i-.'V,sk
.,'u • .•-•.; .••••"•.' •^ci!
\; A-"i
..I.. .1-^ . .
.'rv'-'.V..;"
:\-s'
TABLc 1
•' :>=•
• •• V.
WiV, ;*•'.• v-i-J: » •
•C- .:•
V•}, '[J-yr-:-:
.;;.*v. .'
.yi.' \ •-
'\l
;• [y-'Ai - Vi":
• i'
•: -i,/.
-V,••:.:• . r-'.- t: .
i;}-: .• •; . - " •" r' -
iRgore 1)
>•';
••'•••VVv
., V -,». -.- --rj^.-^v- ^^J.,... .g-.r. .•^•.... . _•- .„.;
' ' ' ...•«• ' .*.'«* .*:• • • . ..• -*2
. i .v'- 'i
'•V. .•-;
^ • '»
':
>
.
I • '
i, ' • •
-> »
I I Iq •
••
V
...
• r
'
-
.t..
•>"
^ 'M
, fi^ V:.
e«— . -.vnm
'^w--isi
Jj ur YI 9 ^ ^
!l •
{] ' Ix 0
fl tl
I
' i.
' ?
t" A
';
-
••
-.
1
aa • ['
. ^:s"£?sat ISA
'fr '•fMlfri'r
•••• J'f ' •
" .M'l ':12^'
. - r'^; ^ ''i
iA /lO
'E • r •
E''i ^
J '' X '"^y •' \ " •^ ' vt'*—«- '-^
•:- ",1V
"(Flcure 2V ;. •.•••'.';•••-t^li.;..
t." i"^rr C'f; ; , on vhis (is? VnoScr .:! Mcni.:- c-JvI;
Ciccii^ ♦
•
f vd" V• 1151-0631 • •
.. Vy,
13 ; - Undervoltage Device 115V AC Instantaneous . • . .- '• d'; 1151-0952'.
.1 t|ndervoltage.OeVicf 125V D^ . '. i;.' ;• #"V • V--V^-1152-0952^v:V;:j •i'*> "i f*
-
O"
I'
>
.* . .*$ ,•<
FOR 'Di>,-
r% -.[101:1: ' or'ic :: :."r-.-no'vai 'ptj.-ts civs type ''V V.'e-1.!;,- -wr.a sc-rini
r.l'ov.T, on nopcplcte of brooker. . . , i -.'.'
'MiRy ®?R«coiiH.iGn<:iL"d'Spore Ports,'See Page 7-,. - .' ',
JTEM DESCRIPTION . / i . PART NUMBER
• V '
• Hansie •
2 Closing Plate , -
' I-''' '.s '" • '. 'Moiried Escutchecn
3 1101-0960
:;"• ,^;., vrr'--r,W
"4 Retainer 1101-1186.
5 ,. Indicalbf Wameplate. Assembly •li:51rl3T2
V •••••. =r ^ -vr
6 Intllcalor Pivot Shaft. .IIOI7IO43
" • • V-'V.w. '• 7 Coil Spring mWl74
:•.: ••^
Ind'oa'or Pvelainer • 1101-1188
9 Negator Spring r.:: .110V0S24.
10 • Connacttng Strap . y;
1102-1033
11 • Connc'ctino Strap 1101-1038
12 V Moldecl Faceplate
••-. , . Auxiliary Shaft Support . •, ;• : . t •:; ? 1101-0836
M-.-; vr-i;-,;'
F::Rf9i:::F%o- 14 Shaft Auxiliary, 1101-0487 " :"V - ;• •
•••;>^:e
• : >/..-iV;,
..v.- •
•{•V - •../•»-I'
1? •I-?''!' • s"
V:tr '.'i 20 ... Ass'emb
, Coup!ing Lever ............
ly J;,..: . ..
•21 Ramp Assembly
*'a'v
22 Bell Crank Assembly
23 Rod
'':v: ! - •: • •-. • . > , - ;
8-
I'vv'; V" '
V r ./.• iP'; .
''..'iF/l:
-- .-I -r
?.n?.C:viPT10.-; • HUhlgtR
• 1101:0315 .v.
' "'V: 48 - Stop Ring
. 'V
.;ii0l-0316'
' ,/•• 1 . '^• •49
v'
, Lower Shaft 1101-0543 :r
50 C Scrfew . .. • • 1101-0338
P«.!V- 51
52
Sleeve '. • 1101^336 . yy,.
;• :.Mlameplate .1101-0564
> . ; 1 •
fe'/; •
- s.*
lU.r - •
:r,.
wmimM
•T
V.
-•iiSCRiPTIOM PART
/../rXA
ni^ 81
82
., Arc Chute.
Arc Chute Cover
>
. -i-
•V X-Vt':vAA
• •'i., ; • • •-• •• •".. ' XxMxX1WL0589' ^ - yX-Xi'ifT'XX
V!?v .••• -•;.•• ;'.
.
. 83.
84
Steel Screw
V •;••'
/ 1' A.'^^iT'Xli01-b343 ':;Ax'
Steei.Ser.ew •
85 Rea r Ro j.ler V/eI Ass embly' 'V •.••»• XT"- •-. ..Iipi;;034.4 ,v •>'. .-V-
• X X .1151-0612 •.; • .• ;.;T
86 Guide Roller V/elded Assembly •1151-0613 , - ^ •-•XyXX-
. Lever Base Assembly « •I'l ».*-. i .
vvLv;-
>•": n
• 88 'Retaining Ring ; X; , . A .. -1101-0018
89 Lever Base Spring X"X X110L0019 • , T---:xm
90 Carriage Lever rS/Vx
: • 1101-0,021 •
91 Washer .• ' • :'
1101-0465 X
Guide Rail
93 . 1101-0881
iv'ain Stab ,. ., ' "' ' 1101-0499. • • •
( . 94
•x- Clip-. • • v'"' •;
:*.
•i/;T-llOl-0504 XXXf X
' 95 . Can-iage Plate V/elded Assembly •"• . 115i-0918 X
96 Release Rod
'•••"xT,X
• ' . .1101-1111- . •
-K;-:-•.
. Trip Rod Gutder • > 1101rl0.il ... , v.,A.
98
'"•'washer .'.J-X'.';- .. r 1101-1022
• .-T-iXT'
. " '•* '- 99 Spring. ' 1101-102.5
100 V, ; Locking Pin • .. .•. • X ilOirto •X::3X AX-X-' .••••XXr
rnSmSfi 101 -••y^p Pin -,4¥S xXX' S' iibLte \tt:|XXa
102 Pin . 1101-1023 ••;-.XtA.;-.
103 • ;; ^rip Rod-V/eld Asisembly Ii5i4qp8v,-.XTXXTXXA vxX,3|f
104 . yyL Spring Support . • v .' XX-'X'XAX..
-'• -i- '
U01X1029AX-X--;XX:X
105 Spring
106 •
\'- r;:'
id2-ob6:' .•'•'X-^ ••
' :v::/ • • Basket Washer ' X. 1101^0173 •XO.r -
;; V•. :',y 107 .: . X' yShdulder Screw ' '
iidLKspXXiA'XL^
^ 108 ' Spring^ • 'x', ^ llpl-0192V XA X- r
*n09
•.XxT:'''Xv,
Basket Assembly .X-X Xuis^imXx'T -x • •
-110 . Brass Tubing '-'XT;AX'; •.n-'r.
•i' 111 •. Trip Trigger. v rr-T15MC^'
•., -.XXA .toi-iuj/ ^•' . X • • ^ ^
IIZ
6 't .* '. V'i • '
• ••. .• V1 V . '• • •'
Secondary Contact Support Weld;. Assembly : • . 1151-0756 '
^ni3' • X tii^oVabfe.Contact Assembly AX;XA X; • ..X ^ • jlsLos^L ' ^
"A V-. X'L' AX
''i'Ax: •
••••;..
AhxP'-At- -.'x-xv • .-..'•x 'i ,• . .. • •
•Xv;«aat-:A. . ' •A.x.X:
•a: vX'-;-.
-X
X .'T-'-'L
./AT;; ' •--^•:XASXX..AAXX---X.;T.:X^i
• X'A X- • -A':,.. X.--'--'XAT'..XX,...X.' ? .A--'-' •:-'••• A-. ."A--
.... . , .X-.'' •' \ •
-• * : • XX XX^'X•'X-.'-AXAX;- •
XXxX:Xxx-x-:,x' • . y -• -••X.'; -X'. ' •iXXXyA^i .. uX' i-;''
.,Xx--a;x':x,.xx ^ x,^a::::;ax
.XX.0Xy
xXxfxxxxnA''
/-vv- -- ry;v- .
'."x. .'^XXi-
:x ,at:A:a ^ -• XX AXA" -x:-
vX'. X--.X.:.,. ' X.'
«X -.a' / • • X. -'.L" . •'/. 'r X'- ' • • . •
• A ;V • ; .
,. ,: ••• -.'•^••X^AXXX
T.'X' X .'xfexXxXxxXgxA;'#
:«h:& ..xAX-X.
..X'X.
IxFIX
A'. -•-A'T;-A ;'.
..x:x::''a;X:xx'xx • XiAXxAAi
.x'.vXA'
:XxpXx:AAiiiii^lli|
» ;V'
FUSLiJ OFFiiC
-'si
Akron, Ohio Hafrisburg. Ponnsylvariia ' ' Peoria, lllitiols,.':
Albiiqusrque.'Nev; Me^Jco l-!artford, Connecticut Philadelphiai Pennsylvania
Armdale, Halifax. Nova Sco' ia Havana, Cuba Phoeriix, Arizona
A'Jr'r.ia, Georgia Houston, Texas Pittsburgh, Pennsylvania
Baltimore, Maryland Indianapolis, Indiana- Portland, Oregon
Birmirigh'am, Alabama Kansas City, Missouri ' Readirtgi Pennsylvania .
Boca Raton, Florida, Knoxvilie, Tennessee; ; -. Rich.mpnd, Virginia. .
•,/Mf Boise, Idaho' Little .Rock. Arkansas v. • . i c ,Rocherfer,"Newj^Yor^
. Boston, Massachusetts Long island City, New, York ^Saginaw, Wlchi^n;: ,
Buffalo, New York Longmeadow, Massachusetts St. Louisvii^issourj' ••jf
Calgary, Alberta. Canada Los Angeles, California ;St. pkersburg,'Flbri'da . '
Charlotte, North Carolina Lo.uisviUe, Kentucky - ' , . : SaitLake City, Utah . , •* f
• .Vf:VO' ; i.
RATINiCS. DIMENSIONS, PACKAGING—STANDARD SIZES
[ p- - - 2M VOITS MO votrs
Olwsntmn'.
Oversil ] CfiO r.JftWl L6S. Catalog , "oiJiritrr" T r'p Cartcii
Unglh I Clamttr Quanlll)' prrlCU Hamber. • • Cmxin ( UhmcW Qoa'r.tTto
ECN.l ECS.i •'
ECN.IS ECS.lS- .
ECN.2 10 , , 5 ECSJ.. 4- .'W." 10
ECN.3 ECS.3
tCN.« ECS.« -
ECN.S '£CS.».
• 6CS-6"
ECN.e ,
E^N.a
ECNI'.O
2* , 10 • ,. Efis-'e •: '•
ECSl.O :
"s-"' I -'V- I w
ECN'.tZS ECS1;I2V
"EfNlVr' ECSl.23"^
ECM • ECSl.S
Ef":; 'i K.- 10 ' I 'S ECS! S
ECM.3 costs
KN?^ f-CSg.D
ECNZ.2S ECS2,2S
eCS2-5 CCS2.5 -
ECM2.8 «.• 1 »• , 5 ECS2.3 %- • »
ECS3.9 ECS3.0..
EeK3.2, 6CS3.2-
FERRULE
TYPE ECN3.5 ECS3.S
ECh4.0 ECS4.0
ECNtf.S 2-. •" 10 . S ECS<.5'":. 10
ECNS'.O. BCS5.0' • ;
ecus.6 . •tCS5.6 • -
ECNS.2S :6«B.25 ^
ECN7 ECS?
ECNa 2''". 1 -Hi' L-.i'ii'"':. s,; ECSS . •Kt" 10
ECNU ECSS
tCHIO • ECSIO
ECNU ECSI2
ECNLS ECSIS .
ECN17.S w to , s. ECSn.S 10
ECN20- 6CS20
ECN2S , CCS25 •
ECH30 . CCS3Q ,,
ECN3S ECS3S'
ECMO . ECS40
Ecms y - 'Ki- I 10 [ u-- EC$4S life' 10
ECN50 ECS50 .
ECNSO ECS6Q
BLUE •
ECS7G ' WIOTK I
ecssD .
«•. 8 30
30 ecs90
CCS200
.14" I S
Ecsno
ECS125
Hi" • I 60 ECSISO 9K-;V-( Hi". I ,-1
Ecsns
ECS2D0
EC$225
ECS2S0
IK- I no
170 ECS300 UK- ;f- IK* I I
eCS350
Ecs«oa.
- r ECSSSO
290 ' ' ESS500 13«- • 2- 1
ECSEOO
MIDGET FUSES—Dimensions! Overall length, 1Vi"j Cap diameter 13/32". Carton quantity; 10
Caiflicj I ^ ^ r c.'
AmfM/to I Wu.Tiber I Ameoffs J I 3\i.
32 V'lLTJ 240 VOLTS 240 VOITS 21<0 VOLTS
MEN.l 1.25 . MEm.2S -j .-,v
.VEN.15 I.« MEftl.t ME:
MEN.2 1.0, MENl.O ..ME.
MEN.3 1.8 MEM.B ' MFI
MCN.« 2.0 Wff!2.0 _ . Mf
MEK.S 2,25 M"tH2.25 •«£!
MEN.S' 2,5 MEN2.S ' •«E
MEN.8 2.8 . .'MEN2.8 ME.
MFNl.O 3-2 • MEK3.2 , ME;
V;N:.;25 8.5 UCH3.S
i£Nl,125
u.vi.zs"
lISSO.U/i
LtSUO
LES12S
LESISQ
US175
CES20fl
IES235
US2SQ
LES300
US35I3
LESiOO
LES/.W
I.ESjCfl - 13«t
LESSSO
SSWSEH^.-.V: ? yv.]:
'^.-CONO^
.(• "•»: : = ••i'.. r • it I , • • :: i: o'.m P%h .'.:••,•••
9
V- •.. l-zy:. '- • •
\
- , '• . '. - •• •-: *.•
.- •• . • '.< : r • '. • .
>
i !.
MiMLx
^ - ,J
L
c,
"D O 0
-•, Uw '5:<wi.r ^ &miSM -1 fl) 'X
¥ I; 01 o O, /• 'M
Ci) i n: :x
mmm'mVemmtmgisMf> •,i-•«•: v^Sr: Sho (>y '-
.'1".
•Z -••:-•
-v. •
RENEWAL PARTS DATA..
;; This Renewal Parts' Datg will provide you with the proper WentificaUpn of thoseAReheMi^Par
. may require in the maintenaiice of your Federal Pacific equipment.- .if; ' : • . , ^-
i- ' dejsirabic b forecast as nccurateiy as possible your requirements;for Renewal Part^'to assure thial
• ^ the necessary parts and materials will be available when heeded to keep your equipmen'b^^^^^
continuous
• Ai
operating
r*;l Mm i"i
cohditio;i
rt' i • ' , ' • \
Tiie reconiinendalions for si'.'"', are 'he minimum quantities that should be available for servicing this
.., eqiJtpmcni. Wo fee! Ihal yc.: in e l -.Lter position lhan we to decide how much ycu.wi.Hh to ihv-esl in
Renewal Parts. Tiis iniporlanco of miniinizing s.hul-Jown Jme due to possible ijren.k-clowns in operation,
v.t.t together witii the distance fmim source of supply nnd transportation faciiitics, should be cdnsiclereri by
.. .. you v/hen ordering renev/arparts. • .•
; -pt; .-Maintain the maximum operating characteristics of your apparatus anddts dependability by using genuine
Federal Pacific Renev/ai Parts. .t
The s«-vices of FPE engineers and Customer Service Centers are available to help v/ith your maintenance
problems. •
ORDERING INSTRUCTIONS .
Give the Pnrf // or other iricntifyin^ itcrrnxrp end name-tlio port. Givo'the complefc numcplatc redding 6f:the cipparotus.
State wh'^ i'T shiprnent is dosircH l;y f-eicjhl, cxprc?ir», or by pcrce! post. For mainrenoncc Service contact your
noorest Fi £ oalcs Office to whorn you should iicnd all orders and correspondence:- See last pogc of hook for
addresser, of FPE Solos Office-
: -
• b' •
',f". •
;• .•
•w.S',
v :"V-,' «/
r . * '
\.
. '•
i'Qlx iViM-> .•,.1 - ! ; Avl'>' aLIJi i i"i'iM::.f:,A:~f<':> , ;>
•^ Voltages wi ll .be applied for one(1) minute without arcing.. .'• • C.'
V ' coniacis ciosea voltage 10 be appjied between phase and ground and between phases. YYYy
'• y-.y.. 2- with contacts open voltage to be applied between line and load termihWls,ahd:^^^ line
; • and load terminafs and ground. ' ; ^ -
3 - voltage to be applied between controrcircuits and ground, and line.tenainals Ay^^^
.-./closed. V/,;" ,••//' •' • V-t'j;'.' ''frf
•'. . •- * ' •' ' •
(2) Manuel Opuration ;' "• • ' '
(a) -Bre?.!.?.: will be msnually closed and opened no less than iv/snty-five (25) b'lties,- BrGa!- r not
b'tnri, .•landle sho'i'ri .'eiurii to pcsiticn.
(b) I'V-lts btsake-f is supplleci wiln a Bell Aiar.-.i, see item 11. • •'
lY.
(c) 1rip breaker by ninnijally activating shunt trip. Breaker should trip before plunger reaches end of
its travel.
(a) V/itiV trip bar pushed upward breaker should not close. - t , /V
;; y ;, (b); ,lf drawout breaker carriage locking handle is depressed the breaker should trip ffee;-before%e;
/:r';«!;'Pln'-releas.es' tj^.ker-.jfrdm.cell. . : f-p,
Ccl.' Tnp breaker wJth' tfip lever, movirrg itVery gentlyhr . r ' sYY/ y:-.'
. ,(4) ElectircaI Operation • • • ' • . i', • . Y\''
Yi; •' Electrical accessorieswill operate satisfactony for at ledst five (5) operations with maximum and
minimum voltages as given in following chart. = /-f , , • v' ;/
-''ypY tb) Items to be checked are solenoid control relay, shunt trip and underydltage trip.whlth should •
; operate satisfaclpry in the rangedf voltages shown. • -
Control Devices Solenoid .;iShprit ^Trlp ' '' - Undorv oltogc '.
-Voliago- V'Reset'//./
• "v'c
(c) Adjustshle lints (maie) shoulcj not bind on crank on main shaft,
v .- (d) Trip rod insulation should not slip. ;. •
Insulation.on shafts.should not be scratched. } h:'''''':i /
vX';.'
• :x. it'n-
'••c
•'• • "'• •'•
- • .-
; . •, iV-
-
. -V.'.i 1•
Coil RoHr.j No Trip Three (3) Minutes Coil Rating No Trip Tnrea {^} f.iinutes
100 72 • 88 ..V25fr'„., ; /; 180 220
• 125 90 • •^ 110 :30b:^ 216 264
150 108 132 • ;,350.-;/ •.•::252 , 308
175 126 154 400:: ^ 288:. 352
200 144 176 500 • : , v36o:; ViO
' "225 172 198 600 . :..432't; 528
A ^
• ••V?'
WpW^'- . .
•v;A;
/•ritftili#
J'T,
.•:-
HHB- .* • */ •'• =
H'v:;-
. ' v ' V, •
•-,
j1 ••''•' '
• iv'.,
=<•
,- -W;:
-i':
x0§i
.>J .v^-.V.' .,'••• -. \\ M > \
^ w. DMB 25-IT
J
CONTACT DATAVi'-
'h •
"-• • fV •• • vV .
•M • : •'
• • •-• • • • •.
s 3 •:
• -T'-'y • • •'"- •A'. T-k
'-vT^;
••:?•>- rY'Yli;'
J.
(Figure 1)
-3-: .•:;"/•
•>.-
. ,'. .V-{;•;••'/ .'• v .-''jIV I J*-":". IVV^V. 't. • , r..
;QfV .u
.'
• I--
. :.1.••v.H i- V; «
4r/r..:
r -V '. 5. - •,••4 ".
• i.: - I - .
i •• t )
;
;-:1
'v-- ^ •4 4' ^ "' •-•
(•'
2C 2B 2 •?
.1 - V
•.ij.' i - 4^*
T.? «•• ivl ^v-!i..
?.4 4^-;
./
'•• •« u
fi • •
'••;4v:'4y
'. /
4- 5 6 ;4"7 I ;
8 9
•'.; •Y/yiil*'- I'i.' 'r''-''
V> • V' - •••
•••Ur:-,';,
•44144. ;• -..4- - A
44;-:• •; t
<^4
?r *' ''
/•"!
"^4
•4- • . •;.
•i^l'-?vf;-'.»S \U.
• • t-'f -.y-^v
-. . • ... 7
7 ',134-001:;
3A —Arc Chute Cover
: H0'l.0589
.4 - Basket assembly 600 Amp. (6 fingers) -77.:.
..•1151-li0&
.5 Break^ Grounding Contact •
• \'-V
-1101-049^7;. H'. A,"
1151-0670 mm
•;'•.= ^-* 'f\K " •^ " 12 :, - 4-Point Secondary Contacts (breaker) ' •
: •
- • . ••. .i'-: . •' • • •.• • •
• 13 - Undervoltage Device 115V AC Instantaneous '
V • undsrvoitage.DeVice230V AC Instantaneous 115il-d952
•• • • undervoitage Device 125V DC Instantaneous 1152-0952
• .v;
::7;:'7.7--f7,
i
•'-'-••A.
v.A'--''..--- y'-.'-" •• >. •
•"••'^ x:; ' ; ..• •
r, f • H fU-' ;;i
••• n; r.-.X'ji siitiwi; -.-j i>.;,.>i• '-r type c.; •
bsx-nker. undXorioI
*' Re=c<iiMC-n(ied Sparc Parts (3e.; pqgi^ 7J
."..V-XX
STEM DESeRlPTION
vXX'-'X-':. v^RARf NUMBER
1 •Handle X X
• •
! •;.• •
. jllOl-OSSO
••'Closin^pfate •-• "• - •• ••-X*- • - :iidi^96f
Molded Escutcheon Xf:'
,X 1101^0960 ' • •T'/K
Retainer , •'Xh • •- :vfp
•x;xiioirii88-''; •iXX:
•IndiCutor.NaniepIate Assembly ;/X}ii5i^ii72'" .•Xv'X
. Indicator Pivot Shaft ' , '-w
^xxiioi^i()43: •
Coil Spring . .•viXll()l-il74X^ Mrl
Indicator Retainer
. Negator Spring , X110I.0824.
Connscling St'np . .•1102-1038;
Connecting Strap
1101-1038; .
Molded Faceplate . ' 1B2-0708-X
Auxiliary Shaft Support Xxiiot0836:::..-
. Shaft Auxiliary 1101-0487;/•'
; Cfu'tch Tubing X .kX'XX'
;.Gam V/elded Xssembly
Xvx-x=:i7
:XX;-XX-..
18. Link Rdd-X
19 Latcil-.
rlldiT0503;x /"^" '• •••.Xv-XXr'-'X)^,
•20 Coupling Lever Assembly . 1151-0659^
21
Ix^XfX' Ramp Assembly • X; X;^51-67^''x, :•
,22 .. Bell Crank Assembly
X •il51-06^:/;-',
-•
.1*
23 Rod
24 Spring ' '
.2701-0()8i t / •-
'.V®'
•••X ,- .:,X
, •1101-0544 X. V,.
25 ^Unk^ • X^ , 2701-p68(i"-/; •:/
26
1. •..
'•'i-''- '.-- -x'", '. '
Link
; 2702-0080 X .•/:
• ^ '.•v.'-,. • ••M • •
27 'Pin X xx-,-X:XX---:.;-X xl
'^•v,'V :;••?;-f ,-...- ,XvX;I1014)334x;'
28
"MarkAssembly (complete) x^/'^X'y-xx.yy#^
29 ^Crank-Assembly
•-:;'x;?V.d65-oo6v X- xXXx'- Xlx'XX-rxX-
30 Rod ;
;v;3iX;:;il5i-p698:'/
:, 1101-0476
31 Link
/: .•V110^1223 • • '• Xv..X:.; 'X;;XX'
32, ••'Pin' '
33 ^Pin- 'x. Xv i:: :Xlblr6335; X /Xl-X-
34
Reset Coupling Tube . ^;'.X''ll01-b542X;/
35 Pin (9/16 dia.)
36 ' , 1/1101-0311
Drav/back Spring .; ,• 1101-0131-1
37 Washer
38
X XilOl-0171X
Bali Bearing for Lower Sq. Shaft •xliidl-d328l/-
. Vi;
-.• /X'X
'.X-X-rXXX'X- • lxl''.:",:xx'
'V M 0 • i i;! i- I'
ji-.
; ..... ,
i«, ,*C^
1:.
'•Ak.
C. 'V-'"
•
igj e E.N ERAL OFFI,C ES: S O PA,R 1S :s T'R EET, ,N, EV"/A RK:,. i",. "N;^ W, J E R. ,'E y
••t.'-- -xv-'r--
.V <••'* .
: S'
• •• •' •M'
I • •': •:;••
?.•
Federal Pacific
TYPE DMB 50-T
Air Circuit Breakers
January 19©0
;VA--M ,•
-. •,
i;, -
li
"•• •
- *' .* .• . '••
:
-•
'S: • r • '
, ^ xx-xXx
•-M
: 1
•i.
/ ? .
\:.'
^ "T; :
••s •
roT • •^
•'
r'• • K.
i :• •••:.•
•' " A
• • '-1. ,'. . '• . i •
r •
. ixSX<.^ •
•s -rKy.''-:
RENEWAL PARTS DATA
This Renewal Parts Data will provide you with the proper identirication of those Renev^al Parts wnich vou .i.
may require in the maintenance of your Federal Pacific equipment. '
It Is desirable to forecast as accurately as possible your requirements for Renev/al Parts to assure that
the necessary parts and materials will be available when needed to keep your equipment in efficient and
continuous operating condition.
The recommendations for stock are the minimum quantities that should be available for servicing this
equipment We feel that you are in a better position than we to decide how much you wish to invest in
Renewal Parts. The importance of miniini^iiig shut-dGv\n time due to possible break-downs in operation
together witli the distance from source of supply and transportation facilities, should be considered by'
you when ordering renewal parts.
Maintain the maximum operating characteristics of your appaialus and its dependability by using genuine
Federal Pacific Renewal Parts.
The services of FPE engineers and Customer Service Ceniets areavaiiabie to help with your main
tenance problems. •••
ORDERING INSTRUCTIONS
Give the Port » ot other identifying number ond nome rhe port. Give the eomplcre namcploro reading ofthe oppoiorua. • • ; -r-y-'-
toto vvhether shipment is desired by freight, express, or by parcel post. For mointononce Service contoct your neoreat
Sales Office to whom you should send all orders end correspondence. Sec lost page of book foroddress uf
FPE Solos Office. ' ,
••
.;y
*
'..1
(c) Undervoltage trip shall operate betwee.n 30-60% of voltage rating aiid mechanically resetunder
voltage trips shall seal in at 80% of rated voltage (see table 4 b).
(1) T'r.c delay 3 to 4 seconds.
(d) Anti-pump feature of breaker shall be checked by operating closing sv/itch 3 or 4 times while
breaker is closed. • •.
(e) If Bell Alarm is supplied refer to item 11.
r;;'
, -r':'
Vir.:JoI inspection . . ,
(a) Breaker will be inspected for signs of incchanical or electricai Special attention shoulfl
be given to see that retaining rings and £-,rings on cqnLacls, etc., are in place, springs are not
•unhooked on one end and colter pins are opened. ' .' • • *
<b) Arcing top on movable contacts should not touch arcing tip oii snuffer when arcing top is
pressed forward.
(c) Adjustable link (male) should not bind on crank on main siiafL
(d). Trip reel insulation should not slip. ... ......
(e) insulation on sRafts shouldnot be scratcheo. " "
|2toZ
• J';''
20 LBS.
• . f-'.
•50 LBS.
8° CLOSED
35° OPEN
xA-'V 'j
)/ 2_
V>.n'
-
'.Mi
(Figure 1) , '.vV*
•nlSr
'• • ..:.r
"7 - ''iV; •, ,,
?'
,•;!
V '
/ •;
I
t
.- t
SN f
?:•
• J
5r ^
., ..^ .
-/•:• 'it *
. .' ..• .i\
Ui... kw-
-* V • -v, 1 •
/
•~v:
^• "SX^-
' :\ • rr-it
i
\.
• \
'A 3^
,'/ 'V •'i
3C 3B
J
•» *--
f
t
A '
::3
rrrn'fii
. • • m" i'
! 1';
: I
U , j ; ^ : 1 si 'V <V X""-
^ l.^ Ud tj ?•
9 10 ..; f«i ••' ^-r^tsrs'.
8 1O
¥ ''***
i3-.i
15 V.
V.'Jv::, ; ;
(Figure 2)
Sv",-'--
1
. RENEWAL PARTS FOR DMB 50-T
NOTE: WKon ordering rencv/o! parts give type of breaker and serial
• number whown on namcplatc of breaker.
•''^Recommended Spore Ports, See Page 7
'' ' . :
- 82 Pivot Pin 'IOK'87 . • ;-K.-
83 Pivot Pin for Movable Arcing Contact 1101-0088
84 Movable Contact Shunt Brazing 1151-0625
• '• V7 - ••:.•:?'•
: r;-
i^£i\!:'.,AL PARTS FOR DMB 50-T (. cr.; <• r. u0d)
':*•' -Vi;
.description
•* '' o5 .. NUMBER
Braid Assembly Sbuni
86 Pivot Pin 1151-0624
87 Special Screv< 1101-0088
88 Pivot 1101-0104
.. ... .89. •Spring •; •• . ... 1101-0101
90 1101-0100 •
Conlact Arm Holder
91 Nut for Spring Adjustable 1151-0719
92 . Contact Guide Pin 1101-0103 .
-v . .
93 Washer 110H3530
94 Arc Chamber Bracket 1101-0175
95 Main Shaft Assembly 1151-0750'
96 Spacer ' 1151-0718"
97 1101-0135
Connector
98 1101-0527
99
Filler DMB 50 Arc Chamber 1101-0531
Cover .
100 1101-0532
Washer
101 . 1101-0171
Trip Lever
102 1101-0829
Latch Assembly
103 Plate Assembly 1151-0701
104 Spring • 1151-0702
105 Hinge Plywooo Assembly 1101-0492 •
024-014
105 .
107
Arm Assembly
1151-9207
o
Bolt
1101-9210
108 Switchette Cat. CR-1070A-102E G.E. Co.
109 Carriage Plate Assembly
110 1151-0745
Rear Roll & Stud
111 . Retaining Ring 1151-0612
112 Lever Base Spring 1101-0018
113 Front Roller 1101-0019.
114 1101-0020
Carriage Lever Arm
115 Washer
1101-0021
116 Lever Base Assembly 1101-0465
117 1151-0b97
V pin.Support- . . .... ..
118 - ' • Front Roller Shaft
4101-0022 •
««119 1101-0023 .
Main Stab Plug In Switch
120 KL Klip Main Stab 1101-0499
121 1101-0504
Trip Lever Stop Assembly - - 1151-0711
122 . Brace
123 1101-0507
Trip Bar Assembly
124 Screw (Trip Bar Pivot) 1151-0713
125 1101-0055
Pivot Screw (Trip Bar Slop) 1101-0056
126
Washer(Lock Pjn)
127 Spring Trip Lever Stop 1101-0057
128 102-0i-.>
Washer
1101-0059
-V.
•DO .Spring ...a... . _ 1101-0062.
"Bl Lock Pin 1101-0063 •
132 Pin Support fot Spring. 1101-0065
133 Spring 1101-0093
*«134 Basket Assembly 1151-0632
D5 Basket Washer 1101-0173,
• 136 •Shouldered Screv/ 1101-0193
137 Spring ilOi-0192 -I'mi
" • V^:v:.-
v-
ii'. • '
v'- •
• . ' OA--.
i • ' ' »
Atianta, Gcoigia Long Island City, N«.w VorK Santa Clara, California
Boston, Massachusetts l.ns Angeles, California Scranton, Pennsylvania
Chicago, lllirois.. - ... . Newark, New Jersey •. Seattle, Washincton
Cleveland, Ohio Pittsburgh, Pennsylvania Toronto, Ontario, Canada
Dallas, Texjs St. Louis, Missouri Vancouver, B. C., Canada
Granby, Quetjec, Canada
FIELD OFFICES
Akron, Ohio Harrisburg. Pennsjlraniu Peorla, Illinois
Albuquerque, New Mexico Hartiord, Conueciiicut Philadelphia, Pennsylvania
Armdale, Halifax, Nova Scotiaa Havana, Cuba Phoenix, Arizona
Atlanta, Georgia Houston, Texas Pittsburgh, Pennsylvania
Baltimore. Ma.'yisnd Indianapolis, lndiai><, Portland, Oregon
Birmingham, Alabama Kansas City, Missouri Reading, Pennsylvania
Boca Raton, Florida Knoxvllle, Tennessee Richmond, Virginia
Boise. Idaho Little Rock; Arkansas Rcchsster, New York
Boston, Massachusetts Long island City, New York Ssginaw, Michigan
' Buffalo, New York Lcngnioadov/, Massacnusctts 'St. Louis, Missouri -
Calgary, Alberta, Canada Los Angeles. California St. Petersburg, Florida
Charlotte, North Carolina Lx)uisviUe, Kentucky Salt Lake City, Utah
Chicago. Illinois LubbocK. Texas San Antonio. Tex.as
Cincinnati, Ofiic Memphis, "en.-.esseu San Francisco, California
Cleveland, Ohio Mexico City, D.F., Mexico Santiago, Chile
Columbia, South Carolina Miami, Florida Sanlurce, Puerto Rico
Columbus, Ohio Milwaukee, Wisconsin Scranton, Pennsylvania
Corpus Chrlsti, Texas Minneapolis, Minnesota Seattle. Washington
Dallas, Texas Montreal, Quebec, Canada Shreveport. Louisiana
Dayton, Ohio Nashville, Tennessee Spokane, V/ashlngton
^ Dp.nvBr, Colorado. ., Newark,. New.Jersey . Syracuse, New. Yqrk . Lv' » s.
Detroit, Michigan New Orleans, Louisiana Toronto, Ontario, Canada
Edmonton, Alberta, Canada New York, New York Tulsa, Oklahoma
El Paso, Texas Norfolk, Virginia Vancouver, B, C.. Canada
Eltham, London, England i
Oklahoma City, Oklahoma V^asliington. D, C.
•^ort Worth, Texas i
Omaha. N^hrosK^ Wicnita, Kansas
Grand Rapids, Michigan (Ormoncj Beacn, rTunua V/innipeg, Manitoba, Canada
Greensboro. Nortr: Carolina 1Pensacola, Florida
1 ELHCTR8C
.jjQENERAL OFPICES: oO PARIS STREET. NEWARK 1, NEW JERSEY
INSTRUCTION MANUAL
TYPE DST-2 SKV & 15KV
MAGNETIC AIR CIRCUIT BREAKER
IN-820.11 DATED APRIL, 1972
PRINTED IN U,8.A.
TABLE OF CONTENTS
PART I- GENERAL INFORMATION O
1. Introduction 3
1.1 Foreword 3
1.2 General Description 4
1.3 Construction 4
1.4 Features 4
2. Shipping 4
3. Inspection 5
4. Storage Prior to Installation 5
5. Installation 5
5.1 Preliminary Operations 5
5.2 Safety Precautions 5
5.3 Mechanical Checking 5
5.4 Installation S
5.4.1 Lifting 5
5.4.2 Arc-chute Fitting 5
5.5 Racking Operations 6
5.6 Manual Checking of Operating Mechanism 7
5.7 Electrical Checking of Operating Mechanism 7
PART II - GENERAL MAINTENANCE
6.1 Periodical Inspection 7
6.1.1 Arc-chute Inspection 7
6.1.2 Arcing Contact Inspection 7
6.1.3 Replacement and Adjustmentof Arcing Contacts 7
6.1.4 Main Contact Inspection 8
6.1.5 Main Contact Replacement 8
62 Operating Mechanism Maintenance 8
PART III - DETAILED MAINTENANCE PROCEDURES
7. Operating Mechanism 9
7.1 Characteristics 8
72 Principles of Operation 8-11
7.2.1 Breaker Open-ClosingSprings Discharged 9
7.2.2 Breaker Open-Closing Springs Charged 8
7.2.3 Breaker Closed with Closing Springs Discharged 11
7.2.4 Breaker Closedwith Springs Charged 11
7.3 Troubleshooting 11
7.3.1 The Breaker Cannot be Closed 11
7.3.2 Problem with the Spring Charging Motor or inthe Chain 11
7.3.3 The BreakerCannot be Opened Electrically 11-12
7.4 Checksand Adjustments 12
7.4.1 Adjustmentof the Closing SpringMechanical Lock 12
7.4.2 Checkingthe Trip Bar for Breaker Opening 12
7.4.3 Checking the Closing Release for Closing the Breaker 12
7.4.4 Adjustment of the Clearance between the Ratchet Pawl and
the Sprocket Wheel to Prevent Overstressing the Pitch Chain 12
PART IV - APPENDIX
7.5 Fitting, Replacement and Adjustment of the Trip Latch 13
7.6 Replacement of the Closing Spring 13
7.7 Hydrauiic Shock Absorber 13
7.8 Fitting the Operating Mechanism to the Breaker 14
8. Schedule of Maintenance 14
9. Operating Time & Contact Velocities IS
10. Control Power Requirements IS
11. Wiring Diagrams: ACclose;DCclose 16
12. Accessories 17-19
13. Spare Parts 19-23 o
Refer to IN-820.4A for metal-clad switchgear installation, operation and maintenance instructions.
\
PART I — General Information
1 INTRODUCTION
1.1 FOREWORD Metal Clad Switchgeaf, and othertype Electrical Apparatus
Federal Pacific Electric Company apparatus is built to the are as follows;
highest standard of quality to insure continuous reliable (a) Cleaning of cells with low pressure air or vacuum.
service with a minimum of maintenance. Some routine
(b) Inspection of cell bushings, cable connections and
preventative maintenance is, however, required on semi
bus joint connections.
annual or annual basis in accordance with the various uses
of the product It is suggested that, due to the precision (c) General inspection of control wiring, and
craftsmanship involved in the construction of this appa components.
ratus, no attempts (with the exception of few minor (d) 2500 Volt DC M^erTests and DC Hi-pot Tests for,
adjustments) should be made by the customer to fix or Insulation Reliability.
adjust clearances. (e) Protective Relay Calibration Tests for Response and
Should the need occur, the Field Service Department of the Time Delay.
Power Equipment Systems Division of Federal Pacific (f) 5KV and I5KV circuit breaker electrical and mech
Electric Company is equipped to assist you with any anical operating checks coordinated with relay
maintenance or repair which may be required throughout response.
the anticipated longlifeof this equipment. (g) Transformer oil or askarel dielectric Hi-pot Tests
FPE "On-Site Test Facilities" are available to you. This (also on minimum oil breakers and tank typo oil
service includes engineering inspection and testing of elec breakers).
trical equipment planned to supplement yourregular main For further information regarding service, please contact
tenance program, to improve equipment reliability and to the Manager of Field Service Department at Newark, New
protect your investment. Such services, for MetalEnclosed, Jersey.
5 INSTALLATION
5.1 PRELIMINARY OPERATIONS
Before setting a breaker into operation, the following
operations should be carried out:
(a) Carefully clean all parts of the breaker with a dry
cloth.
(b) Check the condition of contacts and terminals. The
main contacts are coated with a thin layer of
contact lubricant. If the main contacts are dirty
they should be cleaned with acetone and sparingly
relubricated with FPE #1551 A 5853 contact
grease. The terminals and arcing contacts should be
cleaned with acetone. The three moving arcing
contacts must dose and open simultaneously. See
section 6.13, Page 7 for adjustment specification.
Tighten all the parts listed in Appendix 8 under
"Maintenance to be carried out."
VWastier
Wadwr
Nuts adjustod to
Front Are
Chute Support
width of support
plates.
o
Are Chute
return
Figure 2b connection
Front Arc
Chute support Arc Chute
return
Figure 2e connection
Figure 3c
dTiriiiiT'iit-inVi'
6.1 PERIODIC INSPECTION Appendix No. 8 indicates the maximum number of oper
A schedule for maintenance of a breaker in service is ations the breaker should be expected to perform without
included in Appendix No. 8. In addition to the listed replacement of the contacts.
operation it is recommended to carefully clean the breaker
at least every six months. 6.1.3 Replacement anil Adjusting of Arcing
The contacts and arc chutes should be frequently and Contact (Figure 4}
carefully inspected, as instructed in 6.1.1 — 6.1.5, if the Draw the breaker out, remove the interphase barrier and arc
breaker has been subjected to frequent operations on short- chutes (Fig. 2). Replace the arcing contacts as followsr
circuits or overload. (a) Open the breaker and discharge the closing springs.
The breaker, and in particular the operating mechanism, (b) 5kV 250, 350 and 15kV 750 MVA - Remove nut
should be ^quently inspected if the breaker has been from contact pivot pin and remove pin. Remove
subjected to dust or corrosive industrial atmospheres. spring pin retainer and spring pin. Remove 2 shunt
screws and remove moving arcing contact. Install
new contact in reverse procedure.
6.1.1 Arc Chute Inspection (Figure!) ISkV 500 - Remove 3 studs securing moving arcing
Draw the breaker out, remove the safety barrier (1) as contact to the blades. Install new contact making
instructed in 5.4.2, loosen the nuts of studs (7), rotate the certain that nuts are securely tightened.
arc chutes approximately 45° backward one at a time by (c) Remove stationary arcing contact springs (5) (Fig.
rotating aroimd pins (3) then check the conditions of the 4b and 4c) by removing adjusting nuts and stud.
arc chute plates. Remove upper shunt screw. Remove arcing contact
If any breakages or flaws on arc chutes or ceramicplatesor assembly, remount shunt onto new arcing contacts
burning on blow-out coils are found, it is advisable to and install in reverse procedure.
replace the arc chute. Replacement arc chutes may be (d) Adjust the moving arcing contact, makingsure that
ordered direct from the factory, by contacting Switchgear all 3 poles close simultaneously and fixed to moving
Marketing, Newark, New Jersey. main contact gap as arcing contacts touch: 5kV 250
= 8 ± I'mm (.32 ± .04 in.); 5kV 350 = 4 ± 1mm
(.160 ± .04 in.); 15 kV = 11 if mm (.44 in.).
6.1.2 Arcing Contact Inspection Contacts may be slowly closed using the mainte
Draw the breaker out, remove the interphase barrier and arc nance bar (23, Fig. 1) for the 5kV breaker, and
diutes. "Maintenance Close De^" (Page 19) for the 15kV
The arcing contacts should be reasonably clean, without breaker. '
pits and deformations. Small pits can be filed without (e) Close the breaker (Fig. 4c) and adjust the length of
modifying the shape of the contacts. In normal use, when springs (5) to 11mm (.44 inch) for 15kV 500 and
cunents of approximately the rated value are being inter 14.5mm (37 inch) for other ratings.
rupted, the arcing contacts might be slightly worn; replace (f) Open and close the breaker several times to check
ment, however, is uimecessary. mechaiucal operation.
In more severeservice when appreciable wear is noticed, the (g) Remount the arc chutes and the interphase barrier
arcing contacts should be replaced as described in 6.13. as instructed in 5.4.2.
o
FIguraS
0000Q ©000
© • /
0
FigunSa
©
BREAKER OPEN: CLOSING a>RINGS CHARGED BREAKER CLOSED: CLOSING SPRINGS CHARGED
© ©
FIguraSb FIguraSd
10
BREAKER CLOSED: CLOSING SPRINGS DISCHARGED
3 0.5mm
0 0© —.00mm
("•-«£) ® 0© ©
(0 to .04 in.!
nguraOe Figum?
At the end of this motion the trip latch assumes the 7.2.4 Breaker Closed with Springs Charged
latch position. (Figure6d)
When fully chaiged, the primaiy closing latch (13) is This is the usual operating position of the dosed breaker.
held rixed by the secondary closing latch (IS) on shaft The trip operation can be performed as follows:
(16) by means of bearing (14) assuring the springs aie (a) Manually, by rotating knob (23).
kept charged. The sprocket wheel(17) is then free from (b) Remote, through the shunt trip.
ratchet (18) and idles. The breaker will not close if
springs(1) are not completely charged.
Although the ^ring charging can be done manually as 7.3 TROUBLE SHOOTING
described above, the usual procedure is to perform this 7.3.1 When the Breaker Cannot be Closed
operation by means of a motor. This may be due to the following:
(b) Motor Charging. (a) Looseness of the eccentric (6, Fig. 7) - adjust as
When motor (19) is energized, it rotates camshaft (20) instructed in 7.4.1.
through the reduction gear (21); the clutches (22) are (b)Warpage of the trip rod (8, Fig. 7) — check as
actiuted in sudi a way as to charge the springs in the instructed in 7.42.
same way it is done manually (see 6a). (c) Wear of lever (7, Fig. 7, Page 10). —This trouble is
If during the operation, the voltage supply fails, the very uncommon and may occur after a number of
motor is always in a position to continue charging once operations much greater than that recommended.
the power is restored. Charging can of course be The lever (7) is to be replaced at our plant or by an
continued manually, if necessary. FPE Field Service Engineer.
7.2.3 Breaker Closed with Closing Springs (d) Clearance between the ratdiet pawl (3, Fig. 8) and
the sprocket wheel (4, Fig, 8) is different from the
Discharged (Figfare6c)
prescribed dearance. —See 7.4.4 for adjustment.
This is a transient state for the breaker. It occurs whenever
the breaker is closed and before the springs are recharged.
7.3.2 Problem with the Spring Cherging Motor or
The breaker mechanism is changed to this position as
follows:
in the Chain (16) (Figures)
This happens if the clearance between the ratchet pawl (3)
The shaft (16) is rotated either by the electrical close and the sprodcet wheel is incorrect. See 7.4.4 for
operation or manuaUy with knob (23). adjustment.
The latch(13) is released and springs (1) rotate the lever
(6) counter-clockwise. This drives the shaft (25)
dockwise through lever(11) and trip link and doses the 7.3.3 The Breaker Cannot be Opened Electrically
breaker. This may be due to the auxiliary circuit not being dosed.
11
Verify the circuits and their connection to the switchgear 7.4.3 Checking the Closing Release (7) for Closing
termina] blocks. the Breaker (Figure 8J
With breaker open and sprinp discharged:
(a) Check for free movement of closing release bar (7)
and make sure that when it is in the stop position,
O
7.4 CHECKS AND ADJUSTMENT
the right end of lever (6) is stopped by the slot (9)
7.4.1 Adjustment of the Closing Spring Mechani
in the dividing plate.
cal Lock (Figure 7)
(b) Roller (5) should engage lever (6) with a minimum
Since this adjustment is to be made with the breaker closed, overlap of l.Smm (.06 inch).
the eccentric (6, Fig. 7) should first be locked by tightening
screw (I) in such a way as to position the lobe opposite the 7.4.4 Adjustment of the Clearance between the
pin (7); then, with the breaker closed and springs Ratchet Pawl (3) and the Sprocket Wheel (4)
discharged, perform the following operations:
to prevent undue stresses to the Chain or to
(a) Loosen screw (1) slightly. the Spring Charging Motor (Figure8)
(b) Turn knob (2) counter-clockwise until the clearance Starting horn spring "Discharged" (1) position, rotate the
between the lever (3) and the pin (4) of trip bar (S) diaft (2) half a turn clockwise, whii^ corresponds to the
is between 0 and .04 inch (0 and .1 mm). full closiiig spring charging.
(c) Rotate the eccentric (6) until it is touching pin (7) The ratchet, pawl (3) must clear the sprocket wheel (4) at
of knob (2); lock it in this position by tightening the the instant when ^e bearing (5) presses against the upper
screw (t). part of lever (6) of closing release bar (7), thus assuring the
spriitg"Charged" position.
If the ratchet pawl (3) clears the sprodcet wheel (4) before
7.4.2 Checking the Trip Bar (8) for Opening the the bearing (5) presseson the lever (6), the closing springs
Breaker (Figure 7) (1) are not completely charged and the breaker carmot be
When the breaker is closed, the clearance between the pin dosed.
(9) of the trip lever (10) and the trip rod (8) actuated by If, on the other hand, the ratchet pawl (3) clears the
the knob (2) is to be 3 to 4mm (.12 to .16 in.). Should thh ^rocket vdieel (4) after the bearing (S) has pressedon the
^^clearance be less, the pin (9) would hit the trip bar (8) thus lever (6), the pitch chain (16) would be subjected to undue
tripping the breaker. stresses and the motor would be excessively overloaded.
Therefore, it is necessary to check that: Therefore, with the springs in "Charged" position, the o
dearance between the ratchet pawl (3) and the sprodcet'
(a) The trip bar (8) is not warped and is not held vdieel (4) must be 4 ±.Smm(.16 ±.02 inch). This is set by
upward by foreign matter. adjusti^ the eccentric (8) fixed tothe base plate toget the
(b)That the pins (11) are provided with washers and dearance required.
split rinp. The mwual diarge crank will override if an operator
(c) That the lever (12) is not warped and moves freely. continues to charge after the mechariism is fiiUy <toged.
(d) That the spring (13) is fastened securely. This prevents possible damage to the mechanisitL
®4±.G«nm |
{.netJgln.) 1
® ®
FilpireS
12
PART IV —Appendix
^ APPENDIX 7.5
Fitting, Replacement and Adjustment of the Trip Latch
(Fig. 10).
(a) Open the breaker and discharge the springs.
^ /-A
(b) De-energize the auxiliary circuits.
(c) Charge the closing springs until the Trip Linkage
system latchesin the position shown. Fig. 10.
(d) Remove the split washer (2) and slip out the pin (3).
(e) Lift the lever(4) by operating on latch (5).
(f) Remove the clips and washers from pin (6).
(g) Disengage the trace reset springs (9).
(h) Remove the trace.
Adjustment of linkage length is made by screwing, in or
out, of the right part into the left part of the assembly
(item 7 and 8).
(i) Adjust the new assembly length (L) to equal the 9 (8
length of the one removed. figun to
(j) To reassemble, reverse the above steps.
APPENDIX 7.7
APPENDIX 7.6 Hydraulic Shock Absorber
Check Shock Absorber for any signs of leakage and for
(Type "AEM" Mechanism Only)
moving contact stopping without rebound^
Emplacement of Closing Springs (Fig. 8 ).
An accurate check could only be madb using a travel
The closing springs can be fitted with the help of a hook analyzer. Rebound is adjusted by shifting mounting
(Fig. 11) which will be supplied on request, as follows; brackets as shown. 1
(a) Insert a Srrun (.20 inch) dia. pin into hole (A) of
closing spring support (IS).
(b) Fit the hook to the pin and insert the threaded
portion of the hook into the hole drilled in the left
part of the operating mechanism housing.
(c) By means of the nut supplied with the hook, charge
the springs until pin (IS) can be fitted. Rgura 12a
(d) Remove the hook and check the ^ring chafing
operation. (1i i
. \h 2
VO ^
t.OOSEN (4)
SCREWS AND
ADJUST
SkV Excapt SkV 350,3000A
LOOSEN (
SCREWS AND
Rpara 12b
KO.Z ADJUST
MOREDAMRENINO
© ®
Figure 8b
APPENDIX 8
RECOMMENDED MAINTENANCE SCHEDULE FOR THE DST-2TYPE BREAKER
NUMBER OF OPERATIONS
5kV 250& ISkV 500= 10.000 max.
MAINTENANCE TO BE CARRIED OUT 5kV 350 & 15kV 750 = 5,000 max.
Every Every
2000 4000
Or Once Annually, If Less
Arc chutes (1)
Z Main contacts
o
Arcingcontacts (2) X
H Main contact lubrication X
U Tightening of nuts, screws, etc. X
U
o. Tightening of connections, shunt trip X
m Operating mechanism chain.' X
Z Auxiliary contacts on the operating mechanism
Closing release latch X
(1) The arc chutes can withstand without (2) The lifetime of arcing crmtacts depend on the nature
being serviced: of operations. Their comlition is to be inspected:
Interruptions replacement is required when their wear is noticeable,
Interruptions Numbers of operations tliat the arcing contacts can
with the full
Medianical with rated current withstand without being rep]aced are indicated below.
short-circuit
Operations rated voltage
cos 0=0.8
current at rated Interruptions
voltage cos 0=0.15 Interruptions with the full
with in with in number with in with rated current short-circuit
number spection number spection replace
every every ment
spection
after
at rated voltage
cos 0=O.8
current at
rated voltage o
2,000 5,000 2,000 1 duty cos 0=0.15
10,000 as re
quired cycle 5,000 1 duty cycle
14
^ x i = - f c . . . •.f.
APPENDIX 9
OPERATING TIME & CONTACT VELOCITIES OF DST-2 - 5 & ISkV
Note: Closif^ velocity measured in area IH inch before "arc contact touch" to "arc contact touch".
Opamgvelocity measured hi area from "arc contact touch" to IK inch from "arc contact touch".
APPENDIX 10
DST-2 AIR CIRCUIT BREAKER CDNTROL POWER REQUIREMENTS
AVAILABLE TRIPPING VOLTAGE
Current Required
(Intermittent) 12.5 6.25 2.4 1.2 0.1 max. 0.1 max.
At Nominal Voltage
Voltage, Nominal 48 VDC 125 VDC 250 VDC 115 VAC 230 VAC
* Recommended Fuse
(FPEECN250V 8 33 1.6 3.2 1.6
Dual Element)
Voltage, Nominal 24 VDC 48 VDC 125 VDC 250 VDC 115 VAC 230 VAC
Special
Voltage Range 18-30 36-60 90-130 180 - 260 95 - 125 190 - 250
Cunent Requhed
12.5 6.25 2.4 1.2 4.4 2.2
At Nominal Voltage
Reconunended Fuse
(FPEECO®250V 10 10 10 10 10 10
One-time Cartridge)
* Use fuse recommended for motorcircuit when close andmotorcircuit have common power supply.
15
91
Mooa
O 0U9U3ftJS Zjsei
9*^ ^ d«^9A1KZr»
••P9-W w'wSi ^wuu
ja,^AMm'm»^
#9>vg 9w •nay
.3lf«¥
fw75^7*e5i#ii»
snon
« t v w «aM«» jOJBUf
.'3 ^4""
9/«4 --J
9tO f/9
n
^9«7i9 ArfMf 0f>^>W7aMt 9U 'J«
wtfvA/ry
OMOOV
g^o0'9'00^\
iw<«<
MOrfftvO 3UVU3ftX ZJSO
l>co«rg<jy«w> '9K9fim*m'i ^9MmfU^^9CT JOmMS ywffit/WP
•r nTfir^T
xarM4»-^^r Itayg^'ai^gy
ortf 00 •»« *0 90 e»9 vtd '>19 o:
M> MUfM Mf VM*
• 'wewwuw
1 t#f
'jiwa'amia'jy^
(•II til iiagw»»^m»w
'"T Xm i
!••♦ ^ ;iff
0/W < . u
sf^»mm •JMW w a w *9 w
umnwufy ww .mil
wa»»t "OW
<--S«!SV«S5^
a/wiryytr
•SSTfiiaS
ps/XM^Hsr 90 Atiefr*^ 0Mr A»
'---7 I I
. ArafJWa^M*^ a««M ,J, # I A, *^\
St079 U**nNf X *»-«»' «^; ^'j" '.»,' rf.
*^9lt^/99999 ;«99 ^•099 AYtMr 2w%*«0»#0 M 0/^ '!»
0I0>09^J^ 0/ 09^7 •*» %09IOt*^
Qf^9997 .•>0/0A'
ravu9via ONiuim
o
w
II XIQNSddV
APPENDIX 12
(2)
CRANK
RACKING HANDLE,
DWG. NO. 2251 B 5412 (Standard)
1. With circuit breaker on rails of cell, attach racking handle 2. If circuit breaker is in either test or operating position,
in accordance with above diagram. depress pedal (14, Fig. 1) and rack. Rackingfrom other
positions does not require depressing of the pedaL
HANDLING DOLLY
DWG. NO. 2254 C 4327 (Optional)
17
TRANSFER TRUCK
^.^or outdoor non-walk-in Sand ISkV switchgear. 5kV 2251D4689
6" High Base 15kV 2251 D4690
1314" High Base SkV
ISkV
2251 D4691
2251D4692
o
HANDLING DOLLY
owe. NO. 2251 C 4842 (Standard)
HANOUNQ DOLLY
1. Position wheel below circuit breaker racking block with
dolly handle up.
2. Lower handle to approximate position as shown.
ENQAGEMENT^IN
3. Circuit breaker' could now be pushed in any direction
by turning handle. CIRCUIT BREAKER
FRONT WHEEL
(Standard)
A
LIFTING POINT
0 o o © -^ —
€-50R1SkV
arc
CHUTE
LIFTING YOKE
(Standard)
MAIN SHAFT
1. Attach handle to main shaft as shown.
2. Rotate downwards until contacts touch and inspect
ROTATE TO
contact sequence. CLOSE CONTACTS
REAR OF FRAME
18
ISkV MAINTENANCE CLOSE, TEST jumper; DWG. NO. 2251 C 4509 (Optional)
DWG. NO. 1551 C 5820 (Standaitl)
ACCELERATING
SPRING
jmijm COMPRESS LJ
CIRCUIT BREAKER
TERMINAL
CELL TERMINAL
1. With circuit breaker near the ceil, insert one end of the
1. Attach handle to extension of accelerating spring as jumper to the circuit breaker secondary disconnect
shown.
terminal.
2. Compress accelerating springby turning handle COW. 2. Insert the other end to the cell secondary disconnect
3. Rotate contact blades by hand and inspect contact terminal. The circuit breaker could now be tested
sequence. electrically from switch on instrument door.
APPENDIX 13
1551D5464 5kV
250 MVA
Fixed Arcing 3
Contact Pairs
1551 D5641 5kV250MVA
15kV500
19
TABLE OF SPARE PARTS FOR BREAKER SERIES OST-2
(
15S2DS641 5kV
250MVA&350MVA
3 Moving Arcing 3
Contact
24 1571D5641 15kV500MVA1200A
48 1571D 5641 15kV750MVA 1200A
/ Contact 48
48
1554 D 5641
1570 D 5641
lSkV500&750MVA
2000Aand3000A
5kV250MVA.2000A
5kV350M^A
2000A&3000A
5kV250MVA2DOOA
1568 D 5641 5kV35DMVA
1200 & 2000A
15kV 750 MVA 2000A
1557D5641 15kV
500 MVA
Fixed Aidng
7 Contact 6
5kV
Spring
1558 D 5641 250 MVA, 350 MVA.
andl5kV750MVA
20
TABIE OF SPARE PARTS FOR BREAKER SERIES DST-2
Quantity for Applied
Description Part No.
No. Sketch 1 Breaker Voltage
5kV
Rotating Moving
1559 D 5641 250MVA,350MVA,
Arcing Contact
andl5kV750MVA
Spring
Main Fixed
Contact 24 1560 D 5641 All 5 and 15kV
Spring
48VDC&
1551 A 5575
115VAC
Assembly
1554 B 5758 115VAC
U
1556 B 5758 24VDC
21
1ABLE OF SPARE PARTS FOR BREAKER SERIES OST-2
Quantity for Applied
No. Sketch Description
1 Breaker
Part No.
Voltage O
1551C5584 24VDC
1552C5584 48VDC
1554C5584 250VDC
1551B5585 48VDC
125VDC
AuxiUaty Switch
Basicbreaker is equipped
with 5 unit aux. switch
which provides "2a"and"2b*' 1551D5557 All
c*r- spare contacts. It is not
V
' ^t necessary to spediy this
switch on breaker orders.
ai • 9 H\ IS64DS641 All
17 Latch Switch
* bS^
"-S-JL
Secondary
Disconnect ISSI BS369 24 Pins
18 Contact Assembly
with 24 contacts
5kV350
Primary 3000A
20 Discormect 1572 D 5641 &15kV500
Contact Assembly or 750
3000A
23
7
t ^
INSTALLATION
>ERAI- PACIFIC
Federal Pacific Type DST-5 and DST-15 Magnetic Air Circuit Breakers
INSTALLATION INSTRUCTION MANUAL 0
TABLE OF CONTENTS
Description 3
Shipment - 3
Basic Accessories 4
Uncrating 5
Safety Precautions — 7
General Information
5KV ond 15KV Magnetic Air Circuit Breokers 8
Sources of Control 18
Coil Data - 21
Test Dato 21
2
EQUIPMENT DESCRIPTIVE SHEET
DST 15-1000
Type DST Magnetic Air Circuit Breakers can be quickly bar to insert racking-in crank trips the breaker. If the
withdrawn from their cells with ease due to their horizontal breaker is not racked-in all the way, the ceil interlock bar
drawout construction. Completely foolproof interlocking to prevents vertical interlock bar from dropping and the
meet all operator requirements is provided for by a rugged, breaker remains trip-free, if breaker is not racked-out all
positive acting racking in mechanism. the way to "Test" position, breaker remains trip-free, and
if any operation is attempted with trip coil armature down,
Primary disconnects provide positive alignment and are the breaker is trip free.
simple to maintain and inspect. Contact fingers are of high-
conductivity extruded copper, heavily silver plated. Each Racking-in mechanism's extreme simplicity provides posi
finger is independently spring loaded to assure positive tive locking in any position once racking has started.
contact.
Polestiglas insulation provides flame retardant and non-
Breaker closing mechanism is completely sc]f<ontained— tracking arc chutes and interpha.sc barriers. Polestiglas
attached to the frame by only four holts. No bearings or insulation also has the additional ideal insulating features
shafts are in contact with the breaker frame and the of low power factor, high impact strength, high tensile
mechanism can be removed for inspection and maintenance strength, high flexiiral strength and excellent dielectric
as a unit simply and quickly. The closing solenoid has an characteristics.
exclusive double acting plunger disc which provides maxi
STORED ENERSY CLOSING MECHANISM
mum closing torque and insures closing and latching of
contacts at maximum current ratings of the breaker. Federal Pacific DST Magnetic Air Circuit Breakers are
normally supplied with a d.c. closing solenoid. These
Built-in puBer assures cfTcciive arc interruption in less than breakers may be equipped, when required, with either hand
5 cycles at all current ranges, including magnetizing and charged or electric motor charged stored energy closing
line dropping currents. One large-volume air-puffer serves mechanism. Doth of these stored energy mechanisms are
all three breaker poles, The puffer piston is driven by a unique in that they occupy only the space formally used
solid connection to breakers main drive rod. This gives by the closing solenoid. The mechanism delivers more than
positive operation at the precise moment the air stream is sufficient closing energy required for cither the 5 or 15 KV
required, for fast interruption of low currents. breaker. Excess energy is absorbed by buffers at the end
of the spring stroke and considerably reduces the breaker
fety design provides four-way protection through me impact as compared with the solenoid operated breaker.
chanical breaker interlock. Breaker can not be inserted or Both types of stored energy breakers are provided with
removed in the closed position—raising vertical interlock means for maintenance closing for inspection of breaker.
BULLETIN 2
FEDERAI- FACII ELECTRIC COMPANY
DESCRIPTION Each circuit breaker, in its crate, is enclosed in a
pol-yvinyl dust and moisture-proof envelope, which
The DST magnetic air circuit breaker is electrically is zippered on three (3) sides. Within this envelope
operated, horizontal drawout, three pole, for Indoor Is a proper amount of silica-gel to absorb moisture.
and outdoor metal-clad switchgear.
It is recommended that this envelope not be opened
The component parts are mounted on a welded steel prior to putting circuit breaker into sen-ice.
frame equipped with wheels so that it can be easily
moved into its cell. It has insulated interphase bar If breakers are to be stored for three (3) months or
riers, and a steel grounded front barrier to assure longer, silica-gel should be removed and placed in a
safety to operating personnel. dry oven to remove moisture, and then replaced in
breaker envelope.
Primary disconnecting contacts carry the load current,
and secondary disconnect contacts carry the control
circuits for operating the circuit breaker.
SHIPMENT
1. Racking-in crank
2. Manual or maintenance closing lever
3. Arc-chute lifting yoke
4. Test Jumper (optional)
5. Breaker handling dolly (not illustrated)
6. Breaker transport truck (not illustrated)
(outdoor installations only)
DST 5-150 1554-1653 Uncrate the breaker. Use nail-puller for this purpose.
1551-1653 Note that the breaker was shipped with contacts open,
DST 5-250
and blocked open with a shipping strut.
DST 5-250 1552-1653
DST 15-150 1552-1655 2. Clean off any accumulated dust with a dry cloth.
DST 15-250 1551-1655
3. The contacts were not oiled or greased at the
DST 15-250 1551-0606
factory, nevertheless see that they are free from
DSr 15-500 1551-1655
any oil or grease.
DST 15-500 1551-0606
4. Check for any obvious loose hardware.
Dummy 1551-1680
5. Do not install arc-chutes and barriers until ready
Dummy 1552-1680
to push the breaker into its cell.
FIGURE 4 FIGURE 5
6. Tighten two lower bolts.
7. Check closing and tripping manuaily.
SAFETY PRECAUTIONS
FIGURE 6
1. Before placing the circuit breaker in its cell, make
sure that the circuit breaker frame will be ade
2 - Arc chute installation (Figure 6). quately grounded to the ground-bus in the cell.
10. Remove bolt (G) from front upright. 2. Be certain arc chutes and interphase barriers are
11. Making sure that coil leads at (H) are free, gently installed before entering breaker in cell.
lower arc chute until holes line up for bolt (G).
12. Install bolt (G) and tighten. This makes up 3. Check all main connections and contacts from bus
mechanical and electrical connection at this point. to breaker and from breaker to line. Examine cell
13. Tighten screws (J) on each side of bracket. secondary contact connections. Make sure that
14. Fasten both coil leads at (H) with screws (B) phasing is correct, particularly if line feeds power
removed in step 4. Note: These leads are in into the breaker. This is extremely important if
parallel. Other end of coil is connected internally the breaker controls the output of a generator or
to arc runner. synchronous motor.
15. Check operation of breaker manually for any
rubbing etc. 4. It would be advisable to clean the circuit breaker
with dry compressed air hose.
INSTALLATION OF INTERPHASE BARRIER
5. The upper part of the breaker, above the mechanism
1. Remove from crate. section, is normally enclosed by the interphase and
2. Wipe off dust with dry cloth. front barriers, and the operator is protected from
3. Inspect for damage. contact with live parts. Do not move the circuit
4. Remove two 1/2 inch bolts in front brace of breaker into the cell unless the barriers and arc
breaker frame. chutes are in place. If, however, it is necessary
5. Slide the barrier assembly into place on the to examine the action of the contacts, etc., with
breaker. Make sure the outside sheets slip inside the breaker in the cell, the front barrier may be
the frame gusset. See Figure 9. removed, but only in the "disconnect" or in the
"test position". Never push the breaker in the
Note: On 15KV breakers, slide right half of "operating position" until all barriers are in
barrier assembly into place first, then place. In that position the breaker is live, whether
ieft half. Install 1/4 inch bolt at top. closed or open.
6. Do not attempt to close the circuit breaker by hand matically pushed toward tiie operator and locked
against an energized circuit. The maintenance In Its operate position. The breaker Is now In the
operating handle should only be used In testing operating position.
the mechanical operation of the circuit breaker
when not In the cell. 4. Remove the racklng-ln handle.
b. See that the secondary sliding panel, with Its To operate In Test position, release secondary
. plug-In block, is held at the front of the contact lock-In pin and push sliding panel forward
mechanism housing by Its lock-pin. until Its contacts engage contacts In the cell.
The breaker can now be operated electrically In
c. Insert racklng-ln handle. Rotate handle counter the Test position.
clockwise until lever-and-roUer assembly Is
against Its stop. This assembly Is In the rear 7. Insert the racklng-ln handle.
of the breaker on top of the mechanism housing.
Racklng-ln lever should protrude outside the The circuit breaker can be racked to the disconnect
frame before placing breaker In frame. position by rotating the racklng-ln handle counter
clock-wise six (6) times. The secondary contact
Place breaker In Its cell, and push until lever-and- sliding panel should be pulled forward to Its
roUer assembly hits against horizontal racklng-ln hook operating position and locked there by Its lockpln,
which Is mounting on rear of cell. otherwise there will be voltage on the control
wiring of the circuit breaker.
1. Rotate racklng-ln handle clockwise six (6) turns.
Circuit breaker will at first back out a little and
Note:
then go forward to Test position as. shown by the
Indicators on the right-hand side-sheet. As stated previously, under "Description", the
circuit breaker has to be open before the operator
2. Remove racklng-ln handle. can Insert the racklng-ln handle Into Its socket.
Therefore, it Is Impossible to racks closed circuit
To operate breaker In Test position, release breaker ft'om Test to operating position, or firom
secondary contact lock-pin and push sliding panel operating to test position.
forward until Its contacts engage similar contacts
In the cell plug In block. The breaker can now be GENERAL INFORMATION
closed and tripped electrically several times to
test the control circuits. SKY AND ISKV MAGNETIC AIR CIRCUIT
BREAKERS
3. Insert the racklng-ln handle.
BREAKER • Dead Front - Figure 7
The breaker Is now open. Rotate racklng-ln handle
eleven (11) moretimes clockwise. The shutter will Note breaker has fkont steel plate that closes against
be driven open as shown by Its Indicator. The angle Irons in swltchgear cell making a completely
secondary contact sliding panel will be auto "dead front" arrangementi
FIGURE 8
FIGURE 7
FIGURE 15
FIGURE 13
FIGURE 14 FIGURE 16
ARC CHUTE • Figure 9 BAFFLE MATERIAL OF 15KV MAGNETIC
CIRCUIT BREAKER • Figures 16 & 17
By removing one bolt, the arc chute may be easily
pushed back on a hinge, so contacts can be Inspected. During fault interruptions, the arc which has a
This is a very desirable maintenance feature. temperature of several thousand degrees F comes into
intimate contact with the splitter plates or baffles.
CONTACTS - Figure 18 The material of the baffles must be able to withstand
this drastic heat-shock without cracking or otherwise
Main contacts of heavy copper and inlaid silver carry disintegrating.
the normal operating current when breaker is in opera
tion. Arcing takes place between contacts of special The arc core is surrounded by hot gases which need
alloys which are extremely resistant to arc damage. to be cooled at a high rate. Fast propagation of the
arc helps to expose large areas of the cool baffle
plates to these hot gases. Porosity of the baffle
material is of particular benefit for this action because
it multiplies the surface area in contact with the gases.
1. Blade travel and contact engagement 1. Remove the pin connecting the operating rod
to the moving blade casting.
2. Arc-chute installation and adjustment
2. Loosen lock-nut at opposite end of rod (mech
3. Mechanism description anism cover may be removed to do this).
13
is left fixed to the upper bushing. With this con surfaces involved; one on the nose of the closing
dition achieved, it is relatively easy to engage lever - the other on the end of the prop.
the flathead screws to hold the other upper plate
to the bushing. The first step in this procedure is to adjust the
position of the roller with respect to the closing
Note for SKV breaker: CautionI install copper lever. This is done by altering the position of
spacer when mounting arc-chute. the main latch assembly by the insertion or re
moval of spacing washers that bolt this assembly
The arc-chute may now be tilted forward and the to the mechanism frame. With the roller thus
front support bolt or bolts tightened. It is then adjusted to the closing lever, the breaker may be
possible to make the terminal connections between closed, and the position of the prop may then be
the coil and the upper bushing. If the arc-chute is adjusted to the roller by means of the adjusting
not vertical when mounted, it is usually possible castle-nut on the prop return spring rod.
to tip it the necessary amount after front support
bolts are loosened (15KV only). With this accomplished, the face of the prop and
the face of the closing lever will coincide when
3 - Mechanism Description the breaker is in the closed position or when the
closing lever is brought up lightly against the
The closing mechanism is a solenoid operated roller (by means of the maintenance manual
mechanical trip-free mechanism which closes and closing lever).
latches the breaker against the operating forces
exerted by the contacts, operating spring, and Mechanism Adjustments
electro-magnetic forces due to short circuits. At
any position during the closing operation the 1. Adjust roller to closing- lever face.
breaker may be tripped open, free of the closing
energy. The solenoid pushes on the closing lever (a) Tangent point of roller 1/8" frx>m bottom
which is shaped somewhat like a crescent. This comer.
force is then transmitted to the main operating (b) Adjust by varying spacers in latch.
shaft of the breaker through a roller which is held
in a fixed relation to these two parts. If the 2. Adjust prop to roller.
position of the roller is altered, it breaks the
connection between these parts, and the main (a) Tangent point 1/8". Same as closing-lever.
shaft is then free to move to the open position. (b) Adjust by castle-nut on prop spring guide." ' '
The roller is held in its fixed relationship to the 3. Adjust solenoid travel.
moving pans by the latch assembly.
(a) Close breaker manually.
Depressing ihe magnet armature releases the (b) Push solenoid plunger until it hits lightly
latch, allowing the two internal toggles to collapse against closing lever and frip-frae roller.
and thus release the roller from its relatively (c) Gap between brass washers and solenoid
fixed position. back plate 3/32"-1/8". (over-travel)
(d) Adjust by changing shims inside plunger.
During a normal closing operation this latch
linkage remains firm, allowing the solenoid and 4. Over-travel stop adjustment. Adjust so that:
closing lever to rotate the main shaft all the way
to its closed position. At this point a prop snaps (a) Mechanism cannot go over dead center.
into place engaging the latch roller and holding (b) Puffer piston does not hit rear spacer tubes.
the main shaft in the closed position. Simultane (c) Auxiliary switch linkage does not go over
ously, the solenoid cut-off switch operates to de- dead center.
energize the solenoid, and, after the necessary (d) Gap between stop and main shaft should be at
decay of current, the solenoid and closing lever least 1/8" minimum when breaker is closed.
return to their initial position leaving the operating CautionI A check should be then made (manu
shaft in the closed position as held by the roller ally) to insure that this adjustment does not
and the prop. allow the mechanism to lock on dead center.
The most important adjustment of the mechanism (a) Space between closing lever and roller,
is that of the roller. The tangent point between when circuit breaker is open, should be
the roller and the flat surface it rests against 1/16" to 1/8".
should be approximately 1/8" from the lower cor (b) SKV only - Projection of solenoid plunger
ner of the flat surface. There are two such flat beyond breaker frame 1-1/4" maximum,
14
Latch Adjustment 4. Piston should not hit tubular spaces in back.
1. Latch armature engagement with segment, Shock Absorber
(a) 1/16"to 5/64".
1. Should be lubricated inside with Lubriplate or
2. Gap between armature and segment when latch is
equivalent.
unloaded 1/16" to 3/32 ".
2. Orifice size selected will permit 10% bounce or
3. Adjust magnet frame to allow 1/32" to 1/16 " over- normal opening. Trip-free opening will have more
travel of armature after latch trips. bounce (approximately 25%).
(a) Gap between armature rivets and magnet pole
face approximately 3/8" when latch is set.
3. Plston-rlng gaps should be 180" opposite from
each other.
4. Force to trip breaker approximately 4 lbs.
Auxiliary Switch
5. Latch should break freely when armature Is
depressed when latch reset spring is overcome 1. Linkage should not go over dead center on closing.
by hand.
2. "A'' switches make just before arc contacts touch.
6. Latch engaging surfaces on armature and segment
should be free of paint or foreign matter. 3. Trip coil "A" switch makes 1" or sooner before
arc trips make.
7. Magnet pole face should be lined up with armature
face.
4. "B" contacts make after of the breaker
opening stroke.
Mechanism Check Points
Contacts
1. Latch must reset under all conditions (mechanical
and electrical). 1. Main Contacts
2. With latch armature depressed, breaker should (a) 1/8" il/32" deflection at top of bars on all
trip free before contacts have traveled half
3 poles.
way closed.
(b) Make certain the two bolts at each end of
3. Latch must have at least 1/32" clearance.
the Insulating support are tight.
4. At least 1/8" clearance between closing lever Note: The vertical insulating piece that supports
and trip free roller. the lower bushing from the breaker frame
must be tight before these adjustments are
5. Cut-off switch operates simultaneously when made. Any loosening of the bolts holding
prop engages roller. this support will allow an upward move
ment of the lower bushing when the breaker
6. Over-travel stop is not hit before the closing is being closed, thus reducing contact
armature has touched the solenoid backplate and deflection.
will not let breaker lock on dead center.
(c) Clean and bright.
Solenoid Cut-Off Switch Adjustment
(d) 50% of line to line when checked with carbon
1. The solenoid cut-off switch is adjusted so that it paper and thin tissue on manual closing.
closes its contact as prop snaps into position.
(e) 3/8"gap ± 1/16"when arcing contacts touch.
2. When the mechanism settles back onto the prop,
the cut-off switch contacts must remain closed. 2. Adjustment of Arcing Contact
3. Should not be lubricated. (b) With the individual phase thus adjusted, fine
adjustment may then be made .to effect simul-
15
taneously making of the three arcing contacts 6. Periodically test tightness of bolts. Fig. 20-F;
1/16" of each other. Fig. 21-B.
b o o o O O
c: i,„J lA.
L FIGURE 20
m.
t
Pi? ^
tit
FIGURE 19 FIGURE 21
16
0 0
ML
Vtr®
FIGURE 22 FIGURE 24
FIGURE 23 FIGURE 25
17
Fig. 22 15KV DST Mechanism Adjustments in and will remain energized until contact cs/c opens.
1. Over-travel stop, Fig. 22-A, keeps main shaft The normally closed 52/y contact in the control relay
from going dead centm*, but should not contact (52/x) circuit opens, thereby de-energizing 52/x which
main shaft during electrical operation. in turn breaks its seal-in contact and de-energizes the
breaker closing coil.
2. Adjustment, Fig. 22-B. should be 3/32" approxi
mately. This gives enough travel to insure prop Should the operator close the control switch when the
snapping into place.
breaker is already closed, the closing circuit will not
again be energized - the 52/y coil will be energized
3. Fig. 22-C is de-energized position of solenoid-
through the cs/c and 52/aa contacts thus keeping the
plunger when breaker is in either open or closed
position.
control relay (52/x) circuit open.
5. Neoprene pad to reduce shock. Fig. 23-B. If the operator closes the control switch, and holds
the switch in that position when there is a short
6. Exhaust orifice of shock absorber. Fig. 23-C. circuit on the load 'side of the circuit breaker, the
overcurrent relays will function and energize the shunt
7. Fig. 24-A - Latch rotates and permits toggle to trip coil, which will trip the breaker open.
collapse when armature is depressed.
Reclosure (pumping) of the circuit breaker is prevented
8. Main opening springs. Fig. 23-D. because at that instant the 52/y coil is energized and
its 52/y contact in the circuit of the 52/x coil is
9. Varying number of spacers will adjust position open. Therefore, the control relay 52/x cannot be
of latch-roller to closing lever. Pig. 24-B.
energized and thus attempt to close the breaker again.
10. Solenoid cut-off switch should operate only after
prop snaps into position shown (breaker is closed). Suppressor Rectifier:
Pig. 25-A.
This rectifier is shown across the solenoid closing
11. Tangent point of rolle- on surface to be 1/B" coil 52/cc. Its function is to limit the inductive kick
approximately from lower comer of surface. when the circuit is opened and thus reduces the arc
Pig. 25-B. across the 52/x contacts in series with the 52/cc coil._
12. Adjust roller to closing-lever by moving latch-
assembly. Fig. 25-C. It is used only when the control circuit is direct
current.
13. Nut to adjust prop to roller. Fig. 25-D.
Opening:
14. 3/8" or enough gap to insure b-ipping. Fig. 24-C.
Assuming breaker is in the closed position, energizing
METHOD OF OPERATION
the trip coil from control switch or relays opens the
circuit breaker by mechanical action of its operating
SEE SCHEMATIC DIAGRAM • Figure 26
mechanism.
Closing:
Special Note:
Assuming breaker is in the open position with voltage
on the control bus, close control switch contact cs/c. This instruction covers the circuit breaker as
Control relay 52/x is energized through a normally manufactured in standard form. It is necessary to
closed 52/y contact. Two (2) circuits are made simul refer to the actual diagrams supplied with the cimuit
taneously when control relay 52/x contacts close. breaker, because the diagram shown is typical, and
there are many variations for meeting job reauirements.
a. Seal-in circuit: Control relay 52/x is sealed
in through its own contact which parallels SOURCES OF CONTROL
cs/c contact.
Federal Pacific Type DST Air Circuit Breakers are
b. Closing coil circuit: Control relay 52/x operated by d-c solenoids and shunt trip coils. The
energizes the breaker closing coil 52/cc following methods of operating are available.
which closes the breaker.
Station Battery Closing and Tripping. The recommended
Cut-off switch 52/aa closes just prior to the breaker method of operation of the DST air circuit breaker is
main contacts, energizing the anti-pump relay, 52/y, by means of 125 volt d-c station batteiy-the most
through the 52/x seal-in contact. 52/y seals itself reliable source of power because it is essentially
18
.JUMPEtl.
(+) • «
P.O. FUSE BLOCK
30 A. I2SV. C.UF. J_CS
U
CO
O
-I
U
u
u
(£
3
O
CO
o
o
30 A. I2SV.C.L.
P.O. FUSE BLOCK
(-)• »>
2^ P.O. JUMPER
SCHEMATIC DIAGRAM
LEGEND
7 CONTROL SWITCH CLOSE CONTACT OPEN WHEN DEVICE
® CONTACT. IS DE-ENERGIZED.
CONTROL SWITCH TRIP CONTACT CLOSED WHEN DEVICE
T CONTACT. IS DE-ENERGIZED.
®REO INDICATINB LIGHT Y
DRAWOUT DISCONNECT
(CLOSED)
X AUXILIARY RELAY
GREEN INDICATING LIGHT
Y AUXILIARY RELAY
(OPEN)
CC CLOSING COIL
FIGURE 26
19
RATED CONTROL VOLTAGES AND THEIR RANGE
and power supply of operating mechanisms of breakers,
Rated control voltages and their ranges for control when measured the terminals of the mechanisms are;
CLOSING COILS
TRIP COILS
WIRING DIAGRAMS
Symbol
Nomeplate Marking
Rated freq. 60 60
Closing and trip volts are coil voltages not source voltages.
NOTE #1 - For use with DST 5-250, 15-500, 1200A and an.2000A breakers.
NOTE jSR - For use with DST 5-75, 5-150, 15-150 and 15-250, 1200A breakers only.
FIGURE 27
20
Coil Data chutes, arc-contacts, many contacts etc. allow a
complete inspection in a minimum of time.
Closing coil
Closing time approximately 5 cycles after coll is Particular attention should be paid toNEMA SG4-5.07,
energized. paragraphs A & K, and a maintenance schedule put in
effect based on the frequency of operation or six
Shunt trip coil month intervals, whichever comes first.
This coil is also used when capacitor trip device
is specified. Breakers installed under ideal operating conditions
naturally should require less maintenance than tiiose
Tripping time approximately 3.5 cycles from the operating under more adverse conditions.
time the coil is energized until the arc is broken.
A convenient air circuit breaker log sheet is provided
Test Data for each breaker.
50 Micro-ohm resistance top to bottom of main contact. NEMA - Standard for Power Circuit Breakers
21
chip off. If large pieces are broken a more ably clean and free of grease. (A small amount of
thorough examination should be made to determine petrolatum may be used on the two large guide
the extent of the damage.) pins and the small Interlock pin.) Crocus cloth
may be used to dress the male connectors. ^
The Interrupter chamber will become discolored
with faultcurrent Interruption, (yellow, blue-green, Primary Disconnects: The primary disconnects should
or brown color but Is operable unless mechanical be clean and ftee of pitting. All the springs should
damage Is done to the arc-chamber or arc plates. be tight and the entire assembly should rotate
freely on the stud. Loose springs will cause pit
Arc-Contacts: The arc-contacts should be reasonably ting of the contact areas and heating of the cell
clean and free of pits, voids, and Irregularities. A bushings as well as the breaker. Primary discon
fine file may be used to dress the arc contacts. nects should be replaced as an assembly.
Minor pitting, etc., Is to be expected under service
conditions and will not necessitate replacement. Lubrication
Severe fault conditions will understandably cause
more damage and may require replacement. Hip Mechanism: A good grade of silicon grease or
other lubricant that does not become stiff In cold
Arc-Contact Alignment: Hie arc-contacts should make weather should be used to lubricate the trip mech
before the main contacts and break after the main anism. The trip trigger should be kept fl-ee of
contacts. The' stationary arcing contact is not corrosion at all times. All of the pins, bearing,
adjustable, but the moving arc-contacts are indi etc., are a combination of non-ferrous metals and
vidually adjustable, and should make within no corrosion or settling should result if lightly
1/16" of each other. (Close the breaker slowly lubricated.
with maintenance closing bar and observe three
pole operation fhim the side of the breaker.) Closing Mechanism: A good grade of silicon grease
or other lulHlcant that does not become stiff In
Main Contacts: The main contacts should be reason cold weather should be used to lubricate the
ably clean and fl-ee of irregularities. Each contact closing mechanism. All of the pins, bearings,
Is spring loaded, and In the open position the etc., are a combination of non-ferrous metals
contact surfaces may not seat parallel. No current and no corrosion seizing should result If lightly
is interrupted by the main contacts and little or lubricated.
no pitting should be expected.
Racklng-in Mechanism: Any good grade of heavy
Main Contact Alignment: The lower set of main grease may be used to lubricate the bearings,
contacts should make before the upper set. Nei wormgear, etc.
ther the upper or lower main contacts are ad
justable, but are rather spring loaded. The lower Primary Disconnects: The leading edges should be
and upper contacts should deflect 1/8". The lightly greased with petrolatum to provide less
upper main contacts should be 5/16" apart when friction when racklng-ln. Caution: excessive pet
the arcing contacts touch. (Close the breaker rolatum will melt off at high temperatures and es
slowly with the maintenance closing bar and tablish a potential track path In the cell bushing.
observe three pole operation fix)m the side of the
breaker.) A positive check on contact alignment Operational Inspection
Is as follows: Insert a. piece of white paper
against the fixed main contacts with a piece of Manual Close: Close the breaker slowly with the
carbon paper between the white paper and moving maintenance closing bar (arc chutes should be
contacts. Close the breaker slowly with the main down and breaker completely operable except
tenance closing bar until it is latched closed. interphase barrier should be off). The breaker
Hip the breaker manually and observe the contact should close smoothly and easily.
line Imprints on the white paper. A line contact of
50 " per cent per contact Is acceptable. A small amount of tremor should be experienced
after the breaker latches In. CAUTION: Do not
Auxiliary Switch: The "b" contacts should make in close breaker in operate position with maintenance
the open position and the "a" contacts in the closing bar or without interphase barrier.
closed position. The fingers of the auxiliary
switches contacts can be dressed with crocus Manual Trip: Hip the breaker by lifting the interlock
cloth If pitted. Severe pitting should be investi trip bar. The breaker should trip easily with a
gated circuit-wise and the auxiliary switch re minimum of lifting effort.
placed.
Electrical Close: Close the breaker by means of the
Secondary Disconnects: The male prongs of the test cabinet or in the test position in the cell.
secondary disconnect should be clean and free
of pitting. The molded housing should be reason Low Voltage Hip: Hip the breaker electrically with
22
the trip voltage adjusted to the minimum voltage
indicated.
Rated Minimum
24V DC 14V DC
48V DC 28V DC
125V DC 70V DC
250V DC 180V DC
230V AC (CAP.) 190V AC
Ifvl
Puffer and Arc Chutes: Place a piece of thin paper
over each arc chute and trip the breaker. The air
blast from the puffer will raise the papers if the
puffer is functioning properly and the arc-chute is
free of obstructions.
VOLTAGE CLASS
FIGURE 28
, CONTINUOUS CURRENT
Remove these bolts and lift out the entire shunt
INTERRUPTING RATING trip device.
The shunt-trip coil can be replaced in a few
minutes.
CLOSING VOLTAGE
TRIP VOLTAGE
Remove circuit breaker from cell and tip forward as
shown in Figure 28. Disconnect the two coil-leads
TRIP VOLTAGE R.INGE for the terminal block. Polarity is unimportant.
DATE INSTALLED
Remove circular plunger plate, etc., by removing the
two 1-1/4" socket-head cap-screws that fasten it to
the plunger shaft. Be careful to save the brass shims
OPERATION COUNTER WHEN RECEIVED under the plunger-plate, also the two screws.
SERIAL NUMBER Lift out coil (approximately 80 lbs.) noting that leads
emerge from coil on right hand side of solenoid frame
(as seen from rear of breaker).
REPLACEMENT OF COILS Insert new coil, have leads emerge in proper direction.
Remove end-plate, thus exposing coil. 1 Shunt trip coil, 24 volts DC Dwg. 1551-0409
Insert new coil, have leads emerge in proper direction. 4 One stage only of auxiliary switch Dwg. 1551-1216
1 X Relay Contactor
1 Set of arcing contacts
Bull. 501-U-151-06-M,
1 Set main disconnecting contacts assembly Dwg. 039-016
1 Shuht trip coil 230 V, 60 Cycle
1 Set lift or pull rods 1 X Relay Contactor
1 Lot of fingers and segments for auxiliary Bull. 501-U-151-CA-187-M,
switches 250 V DC Dwg. 039-018
1 Secondary disconnecting block complete
1 Y Relay, 2 N.O. & 2 N.C.
Note: When ordering any of the items listed below Contacts, 115 V DC
the Serial Number of the breaker must be Continuous Duty, Coil Resistance
3650 Ohms Dwg. 095-002
given.
1 Y Relay, 2 N.O. 8i 2 N.C.
Contacts, 230 V, 60 Cycle
PED- Coil Resistance 180 Ohms Dwg. 095-004
Serial No..
1 Y Relay, 2 N.O. & 2 N.C.
Contacts, 250 V DC
Continuous Duty, Coil Resistance
13,000 Ohms Dwg. 095-005
RECOMMENDED SPARE PARTS
1 Fixed Resistor, 25 Watt,
1250 Ohms Dwg. 099-013
•DST-5, 250-1200 Amp Air Circuit Breaker
1 18 Point Contact Secondary Block Dwg. 2752-0107
General Assembly Drawing 1551-1653
1 18 Point Contact Secondary Block
^antity - Total for one Circuit Breaker (Cell) Dwg. 2751-0107
1st 2nd 3rd 4th Sth 6th 7th Sth 9th 10th
Inspection
Date
Inspector
OPERATION COUNTER
VISUAL INSPECTION
ARC CHUTES
ARCING CONTACTS
MAIN CONTACTS
AUXILIARY SWITCH
SECONDARY DISCONNECTS
PRIMARY DISCONNECTS
LUBRICATION
TRIP MECHANISM
CLOSING MECHANISM
RACKING IN MECHANISM
PRIMARY DISCONNECTS
OPERATIONAL INSPECTION
MANUAL CLOSE
MANUAL TRIP
ELECTRICAL CLOSE
ELECTRICAL TRIP
Code:
NOTES:
25
' ' *COMPLETE INSPECTION Ga 12-4
AND Asm. to adjust shock absm-ber.
OPERATING TEST PROCEDURE
FOR (d) Trip armature clearance to latch (.031 - .094)
^Ga jjl3-5
4.16 KV-75/150/250 MVA, 1200 amp.
13.8 KV-150/250/500 MVA. 1200 amp. (e) Trip armature engagement with latch (75%min.)
4.16 KV-150/250/ 2000 amp.
13.8 KV-2S0/500/ 2000 amp. If less, check armature spring tension.
Breaker Type DST. -KV (f) Trip latch free of armature throughout latch
MVA _ -AMP. DATE. stroke after tripping
If not free for complete stroke, call
Serial No. Inspection Leader.
Shop Ord. No. Fed.
Mfg. Ord. No. (g) Itip armature clearance to pole face (3/8-
7/16) Ga #2-3
Operating voltage range; Close Adjust by the number of shims under
V TRIP V- coil frame.
Operating time at normal voltage: Close sec. (h) Closing lever wipe on roiler (3/32-1/8)
Trip sec. Reclose sec.
Breaker nameplate agrees with bill of material Adjust by adding or removing shims
(V) under latch frame asm.
1. Check all hardware to be tight and in place (i) Prop wipe on roller (3/32-1/8)
(v)___
Adjust by turning adjusting nut on spring
2. Control wiring continuity check retaining screw.
Wiring Diagram No. Rev. No.
(j) Stop clearance to main shaft (1/8-3/16)
3. Resistance of coils: Closing Coil. .ohms. Ga #1-2
Trip nhmg
(k) Closing armature overtravel ciearance to
Resistance to be ±10% of the following values: plate (3/32-1/8)
Ga #2-3
Closing Colls Trip Coils Asm. to adjust by the number of shims
between plunger and armature
1551-1672 - 0.90 ohms 1551-0409 - 2.5 ohms
5. Contact adjustments before electrical operations:
1552-1672 - 4.00 ohms 1551-1002 - 5.5 ohms
1553-1672 - 1.50 ohms 1551-1003 - 25 ohms Main Contacts
(c) Closing lever clearance to roller (1/16-1/8) (c) Contact gap between stationary and moving
26
contacts. Jn. before breaker trips *( ).
5KV (2-7/8 + 1/4-0) Ga j|l3-4 Lockout switch has overtravel with hand trip
15KV (5-1/8 + 3/8-0) Ga #1-2 lifted ( ).
0A
0B 8. Lubrication
0C
Check all latch, cams, rollers, bearings, etc.
Adjust shock absorber for lubrication.
(d) Primary gap at arcing contacts make 5KV, Check alt contacts for grease.
(b) Contacts make within 1/16 of each other on During operations observe veeder counter, sema
different phases. phore, puffer operation and general performance
of breakers.
Adjust using washers under spring
guide nut.
Close and
(c) Normally closed "B" contacts make after 11. Electrical Timing
arcing contacts are 60% open ( ).
Maximum trip time at normal voltage (0.05 sec.)
Aux. contacts are adjusted by the spline sec.. I cycles
shaft relation to cam or operating arm. Maximum closing time at normal voltage (0.25 sec.)
sec. cycles
(d) Closing coil cut-off switch should make just Maximum trip free time at normal voltage (0.06sec.)
after prop engages roller ( ). /'vr.laa
7. Hard Trip and Lockout Switch (a) Close and trip at minimum voltage
Trip cam clearance to trip armature with breaker (b) Close and trip at normal voltage
closed (1/32-Mln.) Ga #5
Trip armature overtravel with hand trip lifted (c) Reclose at minimum voltage
(1/32-Min.) Ga #5
Lockout switch opens simultaneously or just (d) Reclose at normal voltage
27
(ti) Tri^ free at normal voltage taneously.
(Rebound on opening to be 10% maximum,
check Orifice size.) (b) Contacts make within 1/16 of each other on
13. Mechanical Check After Electricol Operations dinerent phases.
(c) Trip armature engagement with latch (75%min.) Resistance of new clean contacts
%
With baskets ( )
(d) Trip armature clearance to poleface (1200A - 60 microhms or less)
(3/8 • 7/16) (2000A - 40 microhms or less)
Ga #2-3
Without baskets ( )
(e) Closing lever wipe on roller (3/32 - 1/8) (1200A - 30 microhms or less)
Tn.
(2000A • 20 microhms or less)
19. Signatures:
(b) Contact gap (5KV 2 7/8 + 1/4-0) Ga #3-4,
{15KV 5-1/8 + 3/8-0), Ga #1-2,
Test Inspector.
0A
Date
0B
0C
Factory Foreman.
Revisionrwtto
Arcing Contacts
CVipinoor
(a) Contacts on same phase make simul
28
L-
lN-810.9
INSTRUCTION MANUAL
for
TYPE FP LOW VOLTAGE
POWER CIRCUIT BREAKERS
and
FM FUSEMATIC® BREAKERS
FP25-600 FM25-600
FP50-1600 FM501600
JUNE, 1971
FP-25-eoO FM-25-600
CIRCUIT BREAKER FUSEMATIC*
FM FUSEMATIC®BREAKERS
Manually and Electrically Operated
BREAKER FUSEMATIC®
INDEX PAGE
Part 1 General Description 3
Part 2 Shipment, Receiving, Handling & Storage 3
Part 3 Inspection & Installation 3
Part 4 Maintenance 6
t
Part 5 Accessories 7
\ Parts
Part 7
Overcurrent Trip Devices
Wiring Diagram
9
11
Part 8 Recommended Spare Parts 12
This Instruction Manual covers the FP25-600, FP50-I600, SECTION I Inspection - Manually Operated
FM25-600 and FM50-I600 Fusematic breakers only. For Breakers
instructions on the FP 75 series breakers refer in Instruc
tion Booklet #IN810.10. The FP and FM breakers consist of a coordinated set of
The FP line of Low Voltage Power Circuit Breakers and assemblies mounted on a steel frame, all carefully adjusted
and locked in place for long and trouble-free operation.
Fusematic Breakers, which ranges from ISA through
1600A continuous current at 600 Volt ratings, are designed To assist in properly checking and inspecting breakers
for simplicity of operation, reliability and easy mainten prior to placing into service, the following steps should be
ance. TTie FP Breaker and FM Fusematic are equipped followed in the order listed:
with a stored energy mechanism mechanically trip free in 1. Remove arc chutes and interphase barriers.
any position of the closing cycle, three unit pole assemblies,
fuUy field adjustable timing devices, multi-range series trip 2. Chaise stored energy mechanism by rotating operating
handle to a positive stop. Return handle to normal
coils, and telescoping roll-out rails. The three position vertical position by counter-clockwise rotation.
drawout mechanism is operable with the door closed.
NOTE: Charging Operation:
STANDARD ACCESSORIES
Maintenance closing handle 1151-9252 FP & FM25-600 — Rotate handle 90° counterclock
Cell racking in handle 1101-9251 wise to engage mechanism and then 180° clockwise to
positive stop. (Figure I).
PART 2
SHIPMENT, RECEIVING, HANDLING
AND STORAGE
Raise 90° to
engage ctiarging >
Each FP Breaker and FM Fusematic is thoroughly inspect ratchet
ed and tested before leaving the factory. Breakers are
shipped in individual crates or in the cell compartment. Rotate 180°
If breakers are crated, no hooks should be used in handling. clockwise to
Examine all equipment carefully for indication of damage charge springs
sustained in transit. If damage in transit is indicated, call
for an immediate inspection by the deliveringcarrier. Upon NORMAL HANDLE POSITION
assessment of the damage a claim should be filed with the
carrier or, depending on the nature of the damage, an in
tent to file for concealed damage should be registered. For Figure 1
assistance in filing the claim, advise the area sales office of
Federal Pacific Electric Company, giving a full description FP & FM50-I600 — Unfold collapsible handle from
of the damage, serial number of the breaker, delivering vertical down position to vertical up position. Rotate
carrier's name, and, if shipped by rail, the car number, 180° clockwise to positive stop. Release handle slowly.
waybill reference, and any offier iniformation that might be (Figure 2).
of help to the Company in aiding in the filing of the
damage claim.
When unpacking, make sure that all items are removed ^Roioe to extend^
from the box including packing list, instruction book, main handle
I tjjj,
• • f •
Rgure 5
CONTACT ASSEMBLY
To repair or replace moveable arcing contacts, proceed as
follows (Figure 11):
1. Charge stored energy mechanism.
2. Remove arc chutes and interphase barrier.
3. Remove insulating block and push fork assembly.
4. Tighten moveable arcing contact's adjusting screw
until springs are solid and remove retaining pins.
Figure 9 & Figure 9A
5. Remove arcing contact pivot pin and replace moveable
PART 4 MAINTENANCE arcing contacts. Both contacts should be replaced at
The breakers with all component parts have been exten one time.
sively tested for performance as per NEMA Standards SG
6. Make sure nylon bushings on arcing contact pivot pin
3 and ANSI 037-13 and proved to be satisfactory with a
are in place and in a good condition, when replacing
wide margin of safety. moveable arcing contact.
A periodic maintenance schedule should be established. An
Reassemble following the reverse sequence of operations
annual inspection should be made for clean, low-use
and adjust per Figs. 10 and 11. In most cases it is not
applications. More frequent inspections should be made
necessary to replace contacts, but occasional redressing
for dirty, corrosive or high-use applications.
and readjustments are recommended.
The following instructions and adjustments should be fol
To replace stationary arcing contacts (Figure 10), remove
lowed carefully:
unit pole assembly, replace main stud and arcing contact
CONTACT ADJUSTMENT — Figure 10 and 11 assembly, part 1151-9939, for 600A breaker and 1151-
9937 for 1600A breaker.
MAIN AND ARCING CONTACTS ADJUSTMENT
FOR FP600A AND FP1600A BREAKERS Adjust contacts as per Figures 10, 11 & 12.
"A" • Main Contact Pressure
600A 42-50 lbs., measured at
point of contact
1600A 25-35 lbs., measured at
point of contact
"B" - Over Travel Mains ^ ±%2 (Fig. 10)
"C" - Arcing Contact Press 22-25 lbs., measured at a SHOWN FULLY CLOSED
Figure 10
PART 5
ACCESSORIES
SHUNT TRIP
••I >
GAPni'^i^
v.! '.UN Kl
i;
SHOWN AS ARC
CONTACTS MAKE
Figure 21
Rgure 13
The shunt trip attachment is mounted directly above the
SHOWN FULLY OPEN trip shaft. It is a non-adjustable electro-magnet intended
for intermittent duty only, and its circuit should be inter
rupted only by an auxiliaiy contact.
SHUNT CLOSE
Bgure 12
OPERATING MECHANISM
Make sure that all retaining rings and springs are in place '• -A
and that the mechanism is free. Replace nylon bumper
rollers if excessive wear is evident. Make sure that the
operating mechanism resets when stored energy mech
anism is charged slowly and that the trip shaft is free. It
should take no more than 22 ounce inches of torque to
trip the breaker.
INTERRUPTING CAPACITY
TYPE R-4 AUXILIARY SWITCH INTERRUPTING RATING IN AMPS
DELAV
ADJUSTING I -45 I
SCREW
DOUBLE CONTACT
40
20
The undervoltage attachment is a continuous duty device,
which can be provided with or without a time delay, and
which mechanically trips the breaker if the voltage drops
to 30% to 60% of normal voltage. It is mechanically re
set and hiis no auxiliary contact in its circuit. The under
voltage time delay mechanism is of the pneumatic delay BELL ALARM SWITCH (Figure 17)
type. The time delay is controlled by the 10-32 adjusting
screw.
Figure 17
_ nm n i i i i n i i i
i t*'A r '
.c:
HhiIH 'M
Mi|Ml (M
l«r iUmiM*
ewgiae CM tibm
Figure 19
METHOD OF OPERATION
A. Series Coil and Magnet
Figure 18
The current through the series coil provides the magneto
Dual Magnetic Overcurrent Trip Device (TD-1) motive force to energize the magnet assembly. The clap
(Figure 18) per type armature exerts the force on the push rod which
The dual magnetic overcurrent trip device, in combination operates the trip unit and trips the circuit breaker. The
with the series coil and magnet, provides inverse long de current rating of the coil and magnet may be changed by
layed tripping for all ovcrcurrents hclow the instantaneous moving the pole face assembly up or down. The calibrated
pickup setting, and adjustable instantaneous tripping. All indicator plate lines up with the pointer on the armature
devices arc factory calibrated and can be field adjusted. to indicate the proper position of the poleface for each
rating.
Selective Overcurrent Trip Device (TD-2) (Fig. 18)
The selective overcurrent trip device, in combination with B. Dual Magnetic Overcurrent Trip Device (TD-1)
the series coil and dual armature magnet, provides inverse (Long Time Delay and Instantaneous Trip)
long delayed tripping for all ovcrcurrents below the short
delay pickup setting', and short delayed tripping for all The long delay overcurrent trip device consists of a dash
ovcrcurrents and faults above the short delay pickup set pot which operates by the positive displacement of a liquid
ting. All devices arc factory calibrated and can be field through a fixed orifice and an adjustable tension coupling
adjusted. spring which permits the push rod to move rapidly when
the force from the magnet exceeds a predetermined value.
Single Phasing Protection (Fig. 19) I'he lever ratio between the push rod and the dash pot is
adjustable permitting the time delay to be varied. There
When fuses arc used to protect circuits feeding three phase arc three calibrated positions or adjustment bands. The
motors or similar reactive apparatus there is always the three bands are identified as minimum, intermediate and
possibility, upon the blowing of one fuse only, that the maximum. In addition to the long delay band .adjustment
apparatus, single phased, will burn out. To eliminate this there is an adjustable tension spring which prevents motion
danger, Fusematic Air Circuit Breakers incorporate three of the push rod for currents below the maximum desired
single phase trip coils, one in parallel with each of the three continuous current. This is (he long delay pickup. It is
main fuses. Each trip coil is approximately a one thousand- adjustable from 80 percent to 160 percent with calibrated
turn coil wound to operate down to ' in of line voltage. points at SC/r. 100%, 120%, 140%. and 160%.
The tension In the coupling spring determines the current the coil retaining screws securely. This is important to pre
at which the dash pot will be mechanically by-passed. This vent overheating and possible failure. Care should be t^en
is the instantaneous pickup adjustment. The high range not to damage the coil insulation.
instantaneous.element has calibrated settings at 7.5, 10 and
15 times the coil and magnet setting. The low range has
calibrated settings at .8, 1.5 and 2.5 times. High range B. Dual Magnetic Overcuri^nt Trip Device (TD-1)
units cannot be held modified to low range units or vice (Long Delay and Instantaneous Trip)
versa.
The circuit breakers are shipped with the trip devices in
stalled and properly adjusted. It is only necessary to keep
C. Selective Service Trip Device (TD-2) the devices reasonably clean. They are lubricated for the
life of the circuit breaker and must not be lubricated again.
(Long Delay and Short Delay)
The selective service trip device is similar to the dual mag It is possible to remove and replace a trip device in the
held.
netic trip device except that it has a rigid coupling link in
place of an instantaneous pickup coupling spring and it has
a mechanical escapement timing device which provides a To Remove a Trip Device
short delay for high values of overcurrents and for faults.
The long delay dash pot is identical to that used on the The trip units which are contained in transparent plastic
dual magnetic trip device. The short delay device is oper cases should be removed as units. Remove the two screws
ated by a separate armature in the series coil and magnet which hold the plastic case to the breaker frame. These
assembly. It has an adjustable pickup spring with cali screws are located in the back side of the trip unit (looking
brated settings at 5, 7.5 and 10 times the coil and magnet into the front of breaker) and can be removed by reaching
setting. In addition, the short delay has a band adjustment in from behind. The connecting rod which connects to the
with calibrated points for the minimum, intermediate and magnet assembly must be slipped off the pin connection at
the maximum bands. the magnet Then unscrew the plastic part of connecting
rod and remove the two nuts holding the tripping pieces
in place.
10
PART 7
DEFINITION OF SYMBOLS
Trip coil 01 local
TC 01 — Control switch
01 close
TCI A phase fuse trip coil
BA Bell alarm switch
TC2 B phase fuse trip coil
PF Power fuse
TC3 C phase fuse trip coil UV Undervoltage device
X Closing release coil A Main power circuit - A phase
Y Anti pump relay B Main power circuit - B phase
M Spring charging motor C Main power circuit - C phase
MC/aa NO } Motor cut off switch (Shown with
MC/bb NC I closing mechanism spring discharged)
Auxiliary switch contact (open when breaker is open)
Auxiliary switch contact (closed when breaker Is open)
A A A A A
1111
M M M M
AUXILIARY SWITCH
* • >B£ CONTACTS FUNCTIONS
g S 8 S 1 - t CAfttV CLOSE
.21 5A 2Z *A 9^ >
6
-
-
4
6
CAOtY CLOSE
mo OFCM - • FP50 a FM90
2 S ® A
1 f"20 T®22 '*24 S «> A t
•
•
•
4
to
MiO OPCtt
CAOLV CLOSE
- - ADD FOR FPlOO a FMIOO
Ti II - It mo OPEN
Wtre 2S to • 06 FPMootf
1 1)
19
17
•
-
-
14
10
10
MIO
MIO
CLOSE
EARLY OPEN
CLOSE
Fli»0 ooty.
ii • io MID OPEN
21 • 22 EARLY CLOSE
2% - 14 M(0 OPEN
1^ [9C|Z0E^2ZF4 24F(
, , V
11
PART 8
Sealed Inrush
Sealed Inrush
Delayed Instantaneous
115 Volts A.C. 1151-9458 1151-9456
230 Volts A.C. 1152-9458 1152-9456
460 Volts A.C. 1153-9458 1153-9456
575 Volts A.C. 1154-9458 1154-9456
125 Volts D.C. 1155-9458 1155-9456
250 Volts D.C. 1156-9458 1156-9456
'MOTORS TO CHARGE FP BREAKERS STORED ENERGY MECHANISM (Common for All FP Breakers)
12
SPARE PARTS INDEX
PAGE
Insulator Assembly 15
Housing Mechanism Assembly 17
FP 50 Frame Assembly 19
Draw-Out & Indicator Mechanism Assembly 21
Arc-Chute 23
13
'H 9 BWUnUf 6 —
13 —
n
o
21 20' 19" 18® 1i rl l6o 15
SERIES TRIP
COIL a MAGNET
ASSEMBLY
ll |l
INSULATOR ASSEMBLY
NUMBER REOUIRED
NUMBER REOUIRED
PER INSUUTOR
PER INSULATOR
ASSEMBLY ASSEMBLY
400 000 2000
400 BOO 2000 ITEM PART NUMBER DESCRIPTION
ITEM PART NUMBER DESCRIPTION
Amp Amp Arap Anp Amp Amp
15
\ 2
u 13
<0 II 12 1(4
=»I5
!, 1 6 7 16
= 3 O
I
O "
18 19 20 21
22 23 24 25
o IT T 31 32
26 27 28 29 30 133 ,
.U 47
"34 O => ' e
^35
36
[37 38 39 40
l4l
42 43
1 44
^
45
"A ^
46 48 49
O50 51 52 53 54
59
0: =3 O #
60 61 62 63 64
65 66 67 68 69
16
HOUSING MECHANISM ASSEMBLY
17
•
' J&-'
FP-50 FRAME ASSEMBLY
FRAME FASTENERS
12 1S-250-10 Frame Screw 16 16 16 16
13 1W-250 Frame Lock Washer 16 16 16 16
14 N-250 Frame Nut 16 16 16 16
NAME PLATE
1101-9295 Name Plate
1101-9277 Name Plate Screw
19
1
DRAW OUT AND INDICATOR MECHANISM ASSEMBLY
MANUALLY OPERATED ELECTRICALLY OPERATED
FIXED DRAW-OUT FIXED DRAW-OUT
400 4«0
2DI0 & StOO S ZOSD & ZCCO
ITEM PART NUMBER DESCRIPTION SflD SCO
FRAME ASSEMBLY
11 1151-9710 Frame Assembly 1 1
11* 1152-9710 Frame Assembly 1 1
11* 1153-9710 Frame Assembly 1 1
11* 1154-9710 Frame Assembly 1 1
INDICATOR LINKS
9 1101-9944 O.C. Indicator Conn. Link 1 1 1 1 1 1 1 1
10 1116-9606 0.0. Indicator Conn. Spring 1 1 1 1 1 1 1 1
4 SF6-40x5/32Lg. O.C. Indicator Conn. Screw 1 1 1 1 1 1 1 1
5 lW-6 O.C. Indicator Conn. Washer 1 1 1 1 1 1 1 1
3 1101-9732 O.C. Indicator Conn. Return Spring 1 1 1 1 1 1 1 1
12 1151-9735 O.C. Indicator 1 1 1 1 1 1 1 1
13 1101-9738 O.C. Indicator Pin 1 1 1 1 1 1 1 1
16 5133-15 Indicator Pin Retaining Ring 2 2
18 102-023 C.D. Link Spring 1 1 1 1 1 1 1 1
15 1101-9718 C.D. Link Return Spring 1 1 1 1 1 1 1 1
19 1151-9739 C.D. Indicator 1 1 1 1 1 1 1 1
20 1101-9738 C.D. Indicator Pin 1 1 1 1 1 1 1 1
16 5133-15 Indicator Pin Retaining Ring 2 2 2 2 2 2 2 2
TRIP LINKAGE
35 1151-B-9528 Trip Link Assembly 1 1 1 1 1 1 1 1
28 llOl-A-5512 Trip Link Spacer 1 1 1 1 1 1 1 1
36 llOl-A-9529 Trip Link Pivot Shaft 1 1 1 1 1 1 1 1
37 llOl-A-5514 Trip Link Washer 1 1 1 1 1 1 1 1
38 52-012-062-0500 Trip Link Pin 1 1 1 1 1 1 1 1
39 1120-B-9606 Trip Link ReturnSpring 1 1 1 1 1 1 1 1
40 llOl-A-5581 Trip Link Return Spring Pin 1 1 1 1 1 1 1 1
2 lW-250 Mounting Lock Washer 6 6 8 10 6 6 8 10
1 N-250 Mounting Nut 6 6 8 10 6 6 8 10
21
I>>t
ARC CHUTE
MUHBER REODIRED
PER POU
IHM PART NUMBER DESCRIPTION AU n>-sa
23
' -<• bP
c
ni
SERIES COIL & MAGNET ASSEMBLY
SERIES COIL
7 1101-9771 15-20Amp Coil 1 1
6 1101-9772 30-50 Amp CdII 1 1
5 1151-9994 70-125 Amp Coil 1 1
4 1151-9755 150-225 Amp Coll 1 1
3 1151-9756 250400 Amp Coil 1 1
2 1151-9776 500-800 Amp Coll 1 1
1 1101-9440 1000-2000 Amp Coil 1 1
8 1101-9967 Rear Insulation 1 1 1 1 1 1 1 1 1 1 1 1 1 1
9 1101-9966 Insulation Tube 1 1 1 1 1 1 1 1 1 1 1 1 1 1
10 1101-9986 Insulation Disc 1 1 16 8 5 3 1 1 1 16 8 5 3 1
ARMATURE ASSEMBLY
33 1151-9753 Left Hand Armature 1 1 1 1 1 1 1 1 1 1 1 1 1 1
34 1151-9754 Right Hand Armature 1 1 1 1 1 1 1
31 1101-9109 Armature Shaft 1 1 1 1 1 1 1 1 1 1 1 1 1 1
29 5133-18 Armature Shaft Retaining Ring 2 2 2 2 2 2 2 2 2 2 2 2 2 2
32 1101-9784 Spacer Washer 1 1 1 1 1 1 1 1 1 1 1 1 1 1
30 1101-9379 Spacer Tube 1
MOUNTING HARDWARE
N 19S-37S-40 3/8-16 Bolt 2-1/2" Lg. 2 2 1 1 2 2 1 1
0 19S-375-48 3/8-16 Bolt 3" Lg- 1 1 1 2 4 1 1 1 2 4
t 19S-375-44 3/8-16 Bolt 2-3/4" Lg. 1 1
S 19S-500-20 1/2-13 Bolt 1-1/8" Lg. 1 1 1 1 1 1 1 1 1 1 1 1 1 1
h lW-375 3/8" Lock Washer 4 4 3 2 2 2 2 4 4 3 2 2 2 2
0 W.375 3/8" Washer 4 4 3 2 2 2 2 4 4 3 2 2 2 2
VT lW-500 1/2" Lock Washer 1 1 1 1 1 1 1 1 1 1 1 1 1 1
n W-5Q0 1/2" Washer 1 1 1 1 1 1 1 1 1 1 1 1 1 1
25
FP-50 SERIES TRIP UNIT
MOUNTING HARDWARE
TO 1 & 4 TO 2 & 3
27
iz
2£ 9£g SE
r
s
- -t
o _E1
iijuujuuuuiMjuui iuuuyyuiwju^^
z\ z\
lAAAAAjuuiMjimf mummmm
1 ti
t
STORED ENERGY MECHANISM
MANUALLY lECTNICAlir
OPERATED OPERATED
ITEM PART NUMBER DESCRIPTION 400 100 SOOO 2000
FRAME ASSEMBLY
INTERNAL MECHANISM
29
rs
(>
4 5 6 7 8
1^
o 3
.1_ I
13
10 12
'1 1
14 15
L
I 19
20
21 22 23
i 24 25
*29
30
31
« 32 33 34 35 36
30
. I
Y-RELAY; CHARGING MOTOR - SHUNT CLOSE; SHUNT TRIP; SAFETY LOCK
31
AUXILIARY SWITCH & SECTOR ASSEMBLY
MANUALLY
ELECTRICAUY OPERATED OPERATED
FP-SO BREAKERS FP-50
BREAKERS
11S7-9323 11SS-S923 I1S9-9923 11E0-$923 t161-9923
3 UNITS 4 UNITS 9 UNITS G UNITS 3 UNITS
NO EXTRA 2 EXTRA 4 EXTRA G EXTRA 6 EXTRA
CONTACTS CONTACTS CONTACTS CONTACTS CONTACTS
ITEM FART NUMBER description
AUXILIARY SWITCH
7 C46422 Unit Assembly 3 4 5 6 3
1101-9914 Right End Mounting Bracket 1 1 1 1 1
24
23 A-356791 End insuiation 1 1 1 1 1
21 1102-9914 Left End Mounting Bracket 1 1 1 1 1
20 1101-9815 Switch Cam 8 8 10 12 6
6 C45287 Terminai Jumper 2 2 2 2
8* 1101-9961 Contact insuiation Panel
8* 1102-9981 Contact insuiation Panel 2
8* 1103-9961 Contact insuiation Panel
8 1104-9961 Contact insuiation Panel
8* 1105-9961 Contact insuiation Panel
17* S8-38 Switch Assembiy Screw 2
17* S848 Switch Assembiy Screw
17* S8-58 Switch Assembly Screw
17 SB-68 SwitchAssembiy Screw 2
5 1151-9911 Operating Shaft Assembiy 1 1
4 1101-9890 Drive Link Long 1 1
1 5133-25 Drive Link Retaining Ring 2 2
3 1101-9501 Drive Link Short 1 1
2 WS64 Drive Link Lock Screw 2 2
25 S8-5 Mounting Screw 3 3
26 lW-8 Mounting Lock Washer 3 3
18 lW-8 SwitchAssembiy Lock Washer 2 2
19 N-8 Switch Assembiy Nut 2 2
33
•
•M
ARC-CHUTE RETAINING BAR - INTERPHASE BARRIER
AUXILIARY CONTACT ASSEMBLY
»IIOA
ITEM PART NUMBER DESCRIPTION FRAME FRAME FRAME
INTERPHASE BARRIER
(2 Req. Per Breaker)
9 1101-9289 Spacer Block 1 1
9* 1102-9289 Spacer Block 1
8 1101-9288 Left Barrier 1 1 1
10 1101-9288 Right Barrier 1 1 1
7 SA8-8 Assembly Screw 4 4 4
FIXED MOUNTED
35
L24
\ °28 29-'-^O
'35»37
NUMBER REQUIRED PER CIRCUIT BREAKER
FM-50 FUSEMATIC ATTACHMENTS SSOA 80IA a zcaoA ZDOOA
FRAME FRAME FRAME
ITEM PART NUMBER DESCRIPTION J J L L L L L
FUSE
6* P1690 Econolim Fuse "J" 201 to 400 Amp 3
6 P1690 Econolim Fuse "J" 401 to 600 Amp 3
5* P1700 Econolim Fuse "L" Type II 601 to 800 Amp 3
5* P1700 Econolim Fuse "L" Type II 801 to 1200 Amp 3
5* P1700 Econolim Fuse "L" Type II 1201 to 1600 Amp 3
5 P1700 Econolim Fuse "L" Type II 1601 to 2000 Amp 3
5* P1700 Econolim Fuse "L" Type II 2100 to 3000 Amp 3
INTERPHASE BARRIER
800A FM-SO FRAME 1601 -2000 AMP FUSE
LINE (UPPER STUD) FUSE MOUNTING am FRAME
39
i. 'i ' ^•3
., 1' ,*[. . '
• .• j-'.iiVv.V'
37-
3 14 55 6 7
1 « w
14 15 16 17
m
I
I o
m ^ O M «
iO II 12 18 19 20 21
M/i
27 29
23 24
30 31" 32 33 34 35^®^^ 38 39
n
? w '' f C) 2
42 43 4 4 45 46 47 ^ K
48 49 52 m
— mLII-
55 56 57 58 59 60 61 62
I
64 65 66 67 68
BELL-ALARM, UNDERVOLTAGE
TRIP SHAFT EXTENSIONS
ITEM PAST NUMBER OESCRIPTION 400 000 2000 ITEM PART NUMBER DESCRIPTION INST. DEUYED
TRIP TRIP
41
IfS'D APR 211983
IN-810.4
FP-50-800 FM-50^0
CIRCUIT BREAKER FUSEMATIC
INSTRUCTION & RENEWAL PARTS MANUAL
for
and
FM FUSEMATIC BREAKERS
BREAKER FUSEMATIC
Type FP-50-400
Type FP-50-800 FM-50-800
Type FP-50-2000 FM-50-2000
INDEX PAGE
This Instruction Manual covers the FP50-400, FP50-800, SECTION I Inspection • Manually Operated
FP50-2000, FM50-800 and FM50-2000 Fusematic break Breakers
ers only. For instructions on the FPlOO series breakers
refer in Instruction Booklet #IN810.6. The FP and FM breakers consist of a coordinated set of
assemblies mounted on a steel frame, all carefully adjusted
The FP line of Low Voltage Power Circuit Breakers and and locked in place for long and trouble-free operation.
Fusematic Breakers, which ranges from ISA through
2000A continuous current at 600 Volt ratings, are designed To assist in properly checking and inspecting breakers prior
for simplicity of operation, reliability and easy mainten to placing into service, the following 15 points should be
ance. The FP Breaker and FM Fusematic are equipped followed in the order listed:
with a stored energy mechanism mechanically trip free in 1. Remove arc chutes and interphase barriers.
any position of the closing cycle, three unit pole assemblies,
2. Charge stored energy mechanism by rotating operating
fully field adjustable timing devices, multi-range series trip
handle to a positive stop. Handle should return to
coOs, and telescoping roll-out rails. The three position
normal vertical position.
drawout mechanism is operable with the door closed.
NOTE: Charging Operation:
STANDARD ACCESSORIES
FP & FM50-400 and 50-800 — Rotate handle 90®
Maintenance closing handle 1151-9252
counterclockwise to engage mechanism and then 180®
Cell racking in handle 1101-9251
clockwise to positive stop. (Figure 1).
PART 2
SHIPMENT. RECEIVING. HANDLING
AND STORAGE
Roise 90" fo
engage chorging
Each FP Breaker and FM Fusematic is thoroughly inspect ratchet
i '•
Figure 4
Hgure 5
5. Insert maintenance closing handle #1151-9252 as in
Figure 5 and slowly operate until arcing contacts touch. Figure 6
All arcing contacts should make simultaneously with a
permissible variation of Wj max. Movcable arcing con 13. Charge stored energy mechanism and close breaker.
tact fingers should align with stationary arcing contacts. Pull padlock lever out. Breaker should trip before pad
If misalignment or misadjustments arc observed, refer lock slot is fully exposed.
to Part 4 — MAINTENANCE FOR ADJUSTING
INSTRUCTIONS. Moveable arcing contacts are de 14. Check retaining rings and hardware for tightness.
signed with side clearances for better guidance inside 15. Basket and finger assembly should be secured and re
the arc chutes. A side to side movement of '.i is allow taining bolts tight. Contact finger must bo free of
able. Close breaker and check overlravcl on main dirt and foreign particles. Secondary female contacts
contacts. mounted on breaker must operate freely.
SECTION II inspection • Electrically Operated "fill
Breakers
Motor will charge when power is applied and shutoff auto 9. Draw-out mechanism on breaker should be in OUT
matically when charging cycle is completed. position.
10. Push breaker inside the cell until racking-in cranks
Breaker cannot be closed with the maintenance closing
engage a positive stop. This is the OUT position.
handle unless stored energy mechanism is charged. On all
electrically operated FP breakers the stored energy mech 11. Close door slowly ai^d latch and make sure that the
anism will recharge immediately following a closing opera metal mask provided on outside of front box moves
tion ready for instant rcclosure if needed. freely back as it comes in contact with the door. The
door should close all the way with the breaker in the
Follow inspection procedure Steps I through 15 exactly OUT position.
as outlined in "Inspection - Manually Operated Breakers."
12. Push drawout interlock to left, insert drawout icver
In addition the following steps are recommended: 1101-9251, (Figi^e 8) into the bottom hole of the
drawout mechanism and, with an up-stroke, rack
16. From wiring diagram locale terminals on secondary
breaker into the TEST position. Remove drawout lever,
contacts and connect proper control power supply and
controls for shunt close and shunt trip attachments. drawout interlock plate should snap into position com
Close and open breaker five times electrically and pletely covering the holes.
check for proper operation. 13. Install control power fuses, circuit is now energized,
17. Disconnect control power supply. Close and trip trip- the motor will charge the stored energy mechanism
breaker manually. Do not leave breaker in the charged and closing and tripping control circuits become ener
and/or closed position while in storage. gized in the TEST position.
14. Open door and make sure that grounding contact in
cell is now in contact with the breaker. Close door
SECTION III - Installation and check breaker electrically for proper closing and
opening operation.
Before installing breaker in cell, check following points
inside cell: If breaker operates properly, rack breaker back to OUT
position and leave there until ready to be put into service.
1. Secondary contact support — make sure all connec
tions are tight and adjusted to proper dimensions.
2. Ground connections should be tight.
3. Extension rails should be free to move in and out;
check rail stops for tightness.
4. Rail rollers should be free and well lubricated.
5. Main contact slabs should be tight and free of dust
and dirt.
6. Check condition of insulating transite plate In roof of
case. Screws should be tight.
7. Remove control power fuses.
8. Place breaker on fully extended moveable rails. Make
sure all four rollers engage on inside grooves (Outside
grooves fit into stationary rails inside cell). (Figure 7).
15. When putting into service push drawout interlock to 4. Make sure nylon spacer is in place.
left, inseit drawout lever in the bottom hole of the
5. Roller 1101-9231 must roll free on its pivot pin.
drawout mechanism (Figure 8) and with an upward
stroke rack breaker into operating position. Remove 6. Surfaces marked "F" should be lubricated by a thin film
drawout lever, interlock plate should snap in position of "Conducto-Lube #240-200" before assembly.
and red IN appears. Contacts must be inspected after every known short circuit
intcrrtiption and should also be inspected at regular in
spection periods. If contacts are found to be worn or ex
cessively pitted they should be dressed or replaced.
CONTACT ASSEMBLY
To repair or replace moveable arcing contacts, proceed as
follows (Figure 11):
1. Charge stored energy mechanism and lock discharge
safely interlock (Figure 3).
2. Remove arc chutes and interphase barrier.
3. Remove arc chute retaining bar,
4. Remove insulating block and push fork assembly.
Rgure 9 & Figure 9A
5. Tighten moveable arcing contact's adjusting screw until
springs arc solid and remove retaining pins.
PART 4 MAINTENANCE 6. Remove arcing contact pivot pin and replace moveable
The breakers with all component part.s have been exten arcing contacts. Both contacts should be replaced at
sively tested for performance as per NEMA Standards one lime.
SO. 3-3-17 and SG. 3-3-18 and proved to be satisfactory
with a wide margin of safety. 7. Make sure nylon bushings arc in place and in a good
condition, while replacing moveable arcing contact.
In accordance with NEMA Standards SG3 • Part 6, a peri
odic maintenance schedule should be established. For the Reassemble following the same sequence of operations and
convenience of the user a simple log .sheet is provided with adjust per Figs. 10 & 11. In most cases it is not necessary
every breaker to ensure proper maintenance and years of to replace contacts, but occasional redrc.ssing and readjust
ments are recommended.
trouble-free operation. It should be kept and followed
conscientiously, especially in cases where breakers are re To replace stationary arcing contacts (Figure 11). remove
quired to operate under more adverse conditions. unit pole .assembly, replace main stud and arcing contact
The following instructions and adjustments should be fol assembly, part 1151-9339, for 400/800A breaker and
1151-9432 for 2000A breaker.
lowed carefully;
CONTACT ADJUSTMENT — Figure 10 and II Adjust contacts as per Figures 10, 11 & 12.
MAIN AND ARCING CONTACTS ADJUSTMENT
FOR FP400/800 AND FP 2000 BREAKERS
"A" - Main Contact 42-50 lbs., measured at
Press 400/800A point of contact
— 2000A 25-35 lbs., measured at
point of contact
"B"-
"B" - Over Travel Mains % ±V.i-j
"C"- Arcing Contact Press
Pre.ss 22-25 lbs., measured at a
point \Vi below tip of
contact
"D" - Gap (distance) between ±'Ac
mains when arcing
contacts touch
ACCESSORIES
SHUNT TRIP
-J
I • <
Rgure 11
Figure 13
The shunt trip attachment is mounted directly above the
trip shaft. It is a non-adjustable electro-magnet intended
for intermittent duty only, and its circuit should be inter
rupted only by an auxiliary contact.
SHUNT CLOSE
Figure 12
OPERATING MECHANISM
Make sure that all retaining rings and springs are in place
and that the mechanism is free. Replace nylon bumper
rollers if excessive wear is evident. Make sure that the
operating mechanism resets when stored energy mechanism
is charged slowly and that the trip shaft is free, it should
take no more than 20-22 ounce inches of torque to trip the
breaker.
GENERAL
Figure 14
Make sure that all current 'carrying parts arc secured and The shunt close attachment is mounted on top of the stored
associated hardware is tight. Basket and finger assembly energy mechanism and is used to electrically discharge the
should be secured but free enough to compensate for mis stored energy mechanism and thus to close the breaker. It
alignment in cell. The free up and down movement should is a non-adjustable intermittent duty device and its circuit
be approximately •>!(). should be interrupted by an auxiliary contact.
UNDERVOLTAGE ATTACHMENT (Figure 15 & 15A) AUXILIARY SWITCH (Figure 16)
A 4 pole or a 10pole auxiliary switch is normally provided.
Figure 17
>• .
Figure 19 •
METHOD OF OPERATION
A. Series Coil and Magnet
Figure 18
The current through the series coil provides the magneto
Dual Magnetic Overcurrent Trip Device (TD-1) motive force to energize the magnet assembly. The clapper
(Figure 18) type armature exerts a force on the push rod which
The dual magnetic overcurrent trip device, in combination operates the trip unit and trips the circuit breaker. The
with the series coil and magnet, provides inverse long de current rating of the coil and magnet may be changed by
layed tripping for all overcurrents below the instantaneous moving the pole face assembly up or down. The trip
pickup setting, and adjustable instantaneou.s tripping. All ^stem must be recalibrated after adjusting the magnet
devices are factory calibrated and can be field adjusted. pole face.
10
PART 7
WIRING DIAGRAMS
DEFINITION OF SYMBOLS
Trip coil 01 local
01 — Control switch
C1 close
A phase fuse trip coil
BA Bell alarm switch
B phase fuse trip coil
PF Power fuse
C phase fuse trip coil Undervoitage device
UV
Closing reiease coil A Main power circuit • A phase
Anti pump relay B Main power circuit - B phase
Spring charging motor 0 Main power circuit • C phase
NO ) Motor cut off switch (Shown with
NC I closing mechanism spring discharged)
Auxiliary switch contact (open when breaker is open)
Auxiiiary switch contact (closed when breaker is open)
TYPE FP a FM ELECTRICALtV
OPERATED A.C.B. SCHEMATIC DIAGRAM
FP25 FP50
I2C0 140 FM25 FM50
I flPt I At AflM I
8ASIC ELECTRICAL CONTROL I EXTRA AUXILIARY CONTACTS
1. Control switch 01-C closed (local close) or remote close via Terminal 1A.
2. "X" coil is energized thru "b" contact of the "Y" relay, "b" contact of the breaker auxiliary switch,
and "aa" contact of the motor cut-off switch.
3. Stored energy closing spring released via "X" coil, closing breaker.
4. Closing breaker operates auxiliary switch opening "b" contacts and closing "a" contact thus energizing
anti pump "Y" relay and de-energizing "X" coil.
5. "Y" relay remains energized via seal-in contact thus providing anti-pumping lockout of "X" coil if
01
is held closed.
C1
01
6. "Y" relay is de-energized when contact is opened.
C1
7. Closing breaker, closes auxiliary switch "a" contacts permitting the breaker to be tripped electrically
when control power is switched to auxiliary stabs 5B and 6B.
8. Motor cut-off switch contact "bb" closes when spring discharges and re-opens when spring is fuily
charged.
9. Auxiliary switch "b" contact closes when the breaker is tripped.
10. Motor cut-off switch contact "aa" closes when the closing mechanism spring is fully charged.
01
11. The breaker will close when control switch is closed.
C1
11
PART 8
SHUNT CLOSE
Mounting Ret.
Voltage Assembly No. Drawing
48V AC 48V DC 1151-6038
nSV AC 125V DC 1152-6038 1100-6034
230V AC 230V OC 1153-6038
SHUNT TRIP
Mounting
ng IRef.
Voltage Assembly No. wTfli
DrawTflg
48V AC 48V DC 1151-6039
115V AC 125V DC 1152-6039 1100-6035
230V AC. 250V DC 1153-6039
Mounting Ref.
Voltage Assembly No. Drawing
48V AC 48V DC 1102-6013
115V AC 125V OC 1103-6013 1100-6014
230V AC 250V OC 1104-6013
Mounting Ref.
Voltage Assembly No. Drawing
115V AC 1I51C6138
230V AC 115206138 1100C6032
480V AC 1153C6138
12
Printed in U.S.A.
• •
• '•v::;f I
PART
.r
The FP75 line of low voltage power circuit breakers and fusematic
breakers ranging from 2000a through 3000A continuous current at
600 volt ratings, is designed for simplicity of operation, -MiS
reliability, and easy maintenance.
- AvH'Ar.-.v
• .'A
STANDARD ACCESSORIES
-•k:%
•k.
. •
•k'k
:k;-Vv;
-T?l
-2-
\
PART II- ^
•' •-: 5• '• Vv :•
When unpacking, make sure that all items are removed from the box:, - .
including packing, list, instruction book, maintenance parts, and
hardware. Report any shortage immediately. See that identification ^
tags are left on the breaker. Lifting eyelets are furnished for
handling. Do not lift or handle breaker by the front box, by the
operating handle, or by the .secondary contacts. 4
i .-I"'. /Iv- •
:-V
P A R T III
Section 1. Inspection
2. Remove covers marked, "REMOVE THIS PLATE FOR EMERGENCY CH^ING;• 5"
Using emergency charging handle, 1151-5349, charge each ^
mechanism by rotating the handle clockwise 180 to positive stop*^ ^:^^
3, Lock safety discharge interlocks to prevent accidental discharge'
of stored energy mechanism (Figure 2). Miere is a safety
inter].ook on each mechanism.
• f ••
•h • •" * •
11. Basket and finger assembly should be secured and retaining bolts
tightened. Contact finger must be free of dirt and foreign,
particles. Secondary female contacts mounted on breaker must,.
.operate freely. ^
. •:t'\ \
life-
- -5-
15. When the FMlOO-SOOO is furnished, check the separate fuse truck,^^
using applicable procedures as listed above.
5. Main contact stabs should be tight and free of dust and dirt. •. '''-wT'.'',
'"'nm
• • • . ' . -• / ' \
. , -• •' • !
•f
-6-
;-j;)
6. Check condition of insulating transite plate in roof of *_ase.
Screws should, be tight. .
10. While depressing trip lever, push breaker inside the cell until
racking-in cfaijcs engage a positive stop. This is the OUT
position. Remove rail extensions and store in cell.
11. Close door slowly and latch; make sure that the metal mask which;
is provided on the-outside of front box moves freeily back as it
comes in contact with the door. The door should close all the -
way with the breaker in the OUT position. v.''/,
14. Open door and imake sure that grounding contact in cell is nov^
contact with the; breaker. Close door and check breaker 'V.'.f
electrically for proper closing and opening operation. •iSiV
.-,.a
, ••
kimmi
-7-
PA R T IV
MAINTENANCE
The breakers and all component parts have been tested extensively for
performance, per NiSMA Standards SG.3-3-17 and SG. 3-3-18, and have '. ;
proved to be satisfactory with a wide margin of safety.
, ...
CAUTION; When reinstalling the arc chutes, adjust the retaining serw,,;^^|^
holder on the ard chute retaining bar so that the arcing cpntadts do
not come in contact with the arc chute baffles.
A;
: TO
CONTACT ASSEMBLY
' /
W p.
-9-
-;,:''-V-
7. Make sure nylon bushings are in place and' in good condicion while r'.'
n
Adjust contacts per Figures 6, 7, and 8.
• '
are in place and in good condition. Remove motors to make sure rolle
is free and well lubricated. Reinstall motors. Make sure that all" : ''•y.
OPERATING MECHANISM
Make sure that ail retaining rings and springs are in place and that 'yyW''-
r, I
the mechanism is free. Replace nylon bumper rollers, if excessive :
wear is evident. Make sure that the operating mechanism resets, when . ^
the stored ener^ mechanism is charged slowly, and that the trip shaft
is free. It should take xio more than 20-22 ounce inches of torque '
trip the breaker. '• • '-a."
V.V -
-10-
i'
GE13ERAL
Make sure that all purrent-carrying parts are secured and that •]^y^ - .
associated hardware is tight. Basket and finger assembly should be^
secured/ but free enough to compensate for misalignment in ceil„ vr" ^
' • . • • : . . . .•
P A R T V
ACCESSORIES
SHUNT TRIP
'M
The shunt trip attachment is mounted directly below the trip shaft.
It is a nonadjustable solenoid intended for intermittent duty only/
'V v'
and its circuit shpvild be interrupted only by an auxiliary contaqt. • r.'
SHUNT CLOSE
UNDERVOLTAGE ATTACHMENT
I.'
-v.;.-
•-•.I'-• •" r / i ' 1
.T- T'" ' '"i"
-11-
r
The position and condition of all contacts can be seen and inspected
through a transp^ent dust cover.
r',-- ' -•
•• ' :''rv V 'Vi
•: V
-12-
SINGLE BREAK
24 20.0 15.0
48 10.0 7.5
115 50 30
125 2.5 ; 2.0
230 25 15
250 0,5 0.45
D 0 U B L E B R E A K
24 50.0 40.0
:ilir
48 25.0 20.0
' .
115 80 60
v-V-
125 12.0 7.0 MM-
:• 1xV'- \ -
230 50 30
250 2.25 2.0
To check the alarm switch attachment, trip breaker With trip button,
then with shunt trip. In both cases, the switchl should not be
actuated. Trip brewer by moving the series trip, coil magnet; the
switch should operate. .
. .V '• •
.-V>,
f: • • t ;
-13-
P A R T V I
GENERAL DESCRIPTION
The direct acting series coils and magnet assemblies provide the
energy to operate the overcurrent time delay device and to trip the
circuit breaker, thus, interrupting sustained overcurrents and faults.,
Each magnet is adjusted at the factory and calibrated for either >
2000 to 2500 ampexres, or 3000 amperes. •
n!,
When fuses are used-to protect circuits feeding three phase motors or
similar reactive apparatus, there is always the possibility, upon the
blowing of one fuse only, that the apparatus, single phased, will burn
out. To eliminate this danger, fusematic air circuit breakers
incorporate three single phase trip coils, one in parallel with each
of the three main fuses. Each trip coil is approximately a one
thousand-turn coil, wound to operate down to 1/10 Of line voltage. -
Each of the single phase trip coils can be looked upon as a shunit' tri^, / '
continuously energized by the voltage drop across its fuse. Under
normal conditions, the "fuse drop" voltage is zero, but it immediately , ;^
rises to a value of full phase voltage—when the load fuse blows..
This energizes the single phase trip coil, causing the common trip bar
to unlatch and trip the fusematic air circuit breeker. The coil is //
specifically rated at 1/10 line voltage to assure instantaneous :
operation, even vAien the fusematic air circuit breaker is used as a :r/^;
motor starter. In this case, although the back E.M.F. induced in the V;
motor winding is equal to phase voltage, because of phase angle -
displacement, the resultant voltage drop across the fuse i^Sufficient^^.
to trip the fusematic air circuix. breaker. ' , =
' I
METHOD OF OPERATION
A. Series Magnet , .; v
V '-5
' i''
f >.
-15-
C. Selective Service Trip Device '(TD-2) (Long Delay and Short Delay)
-16-
The circuit hreakers are shipped with the trip devices installed
and properly adjusted. It is only necessary to keep rhe devices '•f-'
reasonably clean. They are lubricated for thd life of the circuit. 5 >•'
breaker and must not be lubricated again.
C, Selective Service Trip Device (TD-2) (Long Delay and Short Delay) '•r
v' i: VY'"'
r
.» ' • '.wAfc''. '
mfST 7
DEFiMm©?^ ©F' SVaViBOLS'
TC ,. Trip coll V }.•';/]• 01 Control switch
01 local
, A phase fuse trip coll T : ^ ^ i I 01 close
TCI
— Bell alarm switch 1V
iVf.! .?•{
-ifirx '• Closing release coil — ivK'. Main power circuit • A phase /.i?;,:Hk
•.1
f' AntI pump relay
SI•j. U •^;. Spring charging motor
»u •;i.; MC/aa — NO ). Motor cut off switch tSnown with
i 1.'
i MC/bb :— NO ) closing mechanism spring discharged)
Auxiliary ^Kch contact (open when breaker is open)
r-a
^;.b Auxlliaty ^Itdi contact (closed when breaker is open) "V •• •! \ -.''Srvw •
A A
A A S S a S A 'S S % I'
lA^ «e$ M9 C9$ 785 M5 '-|NS*I»< teMIRtinlllfl wi
v;v\
IS
ii'lrnrr
* I «k M M Bk
AUXILIARY
CONTACTS
SWITCH
ruwcTiONt
I . i ctosi
CAAI.T CI.OM • ^• ••
,is ,» ,iT n M «»,. •
t"r& f. » ab » :» ::«
' M Vie ' 19 ' M' ' kl"< M
;i
BIB ortn'
mo OBIN
tAIItT 5>-B« • AAoorva moea.ntce. :•
, • •;!
MIS OXB
nis t u i r aowt Wlro 19eaWWov ' ";\V>sJi,
»«lll,T BBCO • ra89.wlr.: .;
-H- "'B «">»«
IV' I caatT c t o g
3 • r.; '«*; r. •
FP BREAKER OPERATINGT SEQUENCE
"t'^ri IT•(I't
f fr.. : . ! '• i--«A. Control swItch. Ol'C closed.
"X" coil Is energized thru "b" contact of the "V" relay, "b" contact of the breaker awt-
Il\
-i;
P A R T VIII V.1P
I.'.'•«*»•••;
MINIMUM RECOMMENDED SPARE PARTS
Description Required P a r t No 2.
• • t:;.
Moving arcing, contacts 12 ' 1151A9986
Upper stud assembly 3 1151B5023
- .!4
48 volts A.C., 60 cycles 1151A5326
115 volts A.C., 60 cycles 1152A5326
230 volts A.C., 60 cycles 1153A5326
48 volts D.C.
1151A532S;
125 volts D.C. 1152A5326
250 volts D.C. 1153A5325 : • .I'V4
'V
• • -r^W'V
fe-l
W-i
' !•
-19-,
delayed instantaneous
P a r t No.
5liN>
h SIDE VIEW
(FIGURE #1)
(FIGURE #2)
vti—^
FRONT VIEW
ACTUATOR'
r>i
TRIP PADDLE
SIDE VIEW
(FIGURE #2)
FP-50 RETROFIT
Reset Arm
(FIGURE #3)
INDIGATING ASSEMBLY
ACTUATOR
(FIGURE #3)
FP-50 RETROFIT
Amptector Mounting
(FIGURE #4)
<- v%-
4 o C' G o
7
o »
G Ci
1-^
e iiy 0
0 0
vj y
CSQ
-<- 0 o
V 0
O 0 ©
/1 ^
0 0
L ;
V. /
0
o
0
/^'Ah
(FIGURE H)
\
MAINTENANCE INSTRUCTIONS I
r
FOR ^
^ LIST OF CONTENTS
t:
Ifjr.,-
item no. DESCRIPTION PAGE NO.
1 Introduction 3
2 Shipment 3
3 Storage 3
4 Unpacking 3
5 Location 3
6 Mounting 3
7 Connections 3 i;
8 Inspection a .
* " A-
9 Closing the breaker 4
10 Maintenance 4
I
n Removing the faceplate 6
12 Stored energy mechanism 6
13 Spring mechanism 6
14 Spring release mechanism 6
15 Motor mechanism 7
16 Breaker mechanism 3
17 Adjustments 9
18 Overload relays JO f'
19 Main contacts ]] |
20 Hood ]] (•
21 Arc chutes ]] j
22 Arcing contocts ]] f
23 Drawout circuit breakers 13 f
24 Spare parts I5 ;
FF^E
TYPE H AIR CIRCUIT BREAKERS
INTRODUCTION LOCATION
FPE Type H low voltage power circuit breakers Unless the circuit breaker enclosure is specifi
are designed to provide many years of reliable cally designed for outdoor or unusual service con-,
service even under severe conditions. The mecha ditions, circuit breakers should be installed in a
nism design employs high throw-off toggles to clean dry place which is free from atmospheric
ensure tripping even after long periods of inacti contaminants and where good ventilation con be
vity. Current carrying parts are designed for low secured. Sufficient space shduld be provided to
current densities and the extremely efficient trip moke connections and so that the breaker is read
ping relays do not require high current density ily accessible for operation and maintenance. Re
coils thus realizing a low temperature rise even ference should be mode to local code regulations.
when the circuit breaker is loaded to its full rating. MOUNTING
Normal maintenance and replacement of ore con Circuit breakers should be enclosed in sheet steel
trol parts can be mode without special tools or coses in accordance with recommended dimensions
resetting factory adjustments and thus maintenance and in general these cases provide the mounting
shut down periods can be very short. for the breaker.
Fixed mounted breakers ore mounted with-4-3/8"
SHIPMENT bolts through the base, (Frame size 2 & 3 use 'V
bolts), while drowout type breakers will roll in or
Eoch circuit breaker is carefully inspected and out on roils which ore fixed to the enclosure. A
tested before leaving the factory and then packed worm and nut assembly is used to pull the breaker
by workmen experienced in the proper handling either on or off the disconnecting contacts.
ond packing of electrical equipment. Every circuit
breaker should be examined immediately on receipt The mounting support should be a rigid structure
for any damage sustained enroute. If damage is able to withstand the impact of breaker closing and
evident or if indication of rough handling is visi tripping.
ble, 0 claim should be filed immediately with the CONNECTIONS
transportation company. FPE should be notified
immediately if replacement parts are required. Before making any electrical connections to the
circuit breaker, every precaution must be taken to
ensure that all cables which are to be connected
STORAGE to the circuit breaker are safely de-energized.
Air circuit breakers should be stored in their ship Breaker terminals are silver plated for maximum
ping crates in the upright position in a clean dry joint efficiency and cable connectors should be
area. Should the breaker get wet it must be thor clean and free from dents or burns and bolted se
oughly dried out using forced worm air over an curely to the breaker terminals. Poor joints lead
extended period until "infinite" readings ore to breaker overheating and subsequent contact
deterioration and eventual breaker failure so that
obtained using a 600 volt megger.
considerable care should be exercised in making
these primary connections.
UNPACKING Cables or bus connections should be properly sup
ported so that the circuit breaker terminals are not
Crates used for domestic shipment of air circuit subjected to unnecessary weight or strain. Any
breakers ore of open lattice work construction so strain which at first has no apparent affect, may
that the breaker may be readily uncroted without cause poar contact alignment after prolonged peri
damage. The breaker is bolted into the crate using ods of vibration or shock from normal breaker opera
its normal mounting holes so it is preferable to tions.
first remove top, front and sides of the crate. The Meter shunts, resistors and similar devices which
breaker may then be unbolted and removed from the
remaining crate. Do not lift the breaker by the reor operate at relatively high temperatures should be
connecting terminals or the operating handle. Lift mounted far enough away from the circuit breaker
on the steel channel at the front and hold the base so that they do not contribute to breaker heating.
to keep the breaker steady. The steel side plates Control circuit wiring where applicable should be
will support the breaker but core should be taken made in strict accordance with detailed wiring
to set the breaker on a level surface to avoid da diagrams. Wiring connections are made to terminal
mage to the relays or the interlock linkage on draw blocks or to secondary drawout contacts and should
out type breakers. Check the breaker thoroughly to be run in a supported and protected manner such
see that no ports ofthe breaker hove been damaged that control wires cannot come into contact with
or forced out of alignment during shipment. primary connections.
type h air circuit breakers
CLOSING THE BREAKER
ceeding with inspection.
completely before pro
sforedthe
energy as
0
opposed to spring assisted closing, en«qy
fhoJld U'^?^®"9hly checkedwhen
the breaker
and itoperated to en- tore the breaker con be closed.
sore trouble free operation is placed in
manual CLOSING
The handle is rotated counter-clockwise to the up-
1. Make visible inspection after installotion to fS:;'"9will
charging cam.
ensure no parts have been damaged or forced ptating the handle through 180" then comp
out of alignment. letely chorge the springs. A rochet mechanism
l'^ allows severol short strokes instead of one 180°
2. peck door interlock lever (see page 5) for single stroke if preferred and also prevents any
freedom of movement ond block in depressed spring fly back during the charging stroke. The
position. This Will allow normal breaker opera- springs con be charged when the breaker is closed
tion With the door open.
which will alowone immediate reclosure. Pressing
3. On drowout breakers check the drowout mecha a mechanical push button on the face plate releases
nism to see that the breaker rolls freely on the
breaker®^ compression springs to close the
pulls .L L 1 completely
the breaker ®"9oges thethe
home on nutcon
and
tact. There should be approximotely 1/8" clear ELECTRICAL CLOSING
ance between the mole stab and the contact A universal ac/dc 120 volt '4 H.P. motor is used
tinger spacer. to wind the spring closing mechanism and a shunt
4. On drowout breakers check the drowout inter- close releases the stored energy to close the break
l^ock. The interlock should be free with the er. Upon supplying control power with the breaker
breaker fully engaged or in the test positionopen, the motor will automatically charge the
but should ride up on the wedge to trip the Spring (time 2-4 seconds). Pressing a close button
breaker as it moves from either position. ®' *ii then close theP'breaker.
®^® ®'' When
®remote location
will the breaker is
5. peck contacts to see that they ore clean and tripped the motor will immediately rewind the mech-
tree of foreign material. onism to charge the spring ready for the next close
6. peck ony control wiring to ensure it has not operation.
been damaged during installation. An emergency closing handle is supplied which
7. Check overload relays. Push on armature to en can be used in the event of control power failure.
sure that the relay will trip the breaker. If mo Ihe handle is inserted into the faceplate connect
derate force is used the relay armature will ion and is used in the same manner as for manual
move slowly because of the delay characteris closing to store the energy in the spring. To close
tics. the breaker insert the opposite end of the handle
A heavier force will extend the instantaneous in the small hole to the lower right as illustrated
figure 1, page5 . '
springs and should trip the breaker immediately.
Note that a small amount of oil seepage may MAINTENANCE
occur during shipment if the breaker has not
been in the upright position but the relay de The breakers have been manufactured and tested
sign emplays sufficient cavities to trap ample in accordance with NEMA standards SG-3 and to
amounts of oil for relay operation. ensure the safety and the successful functioning
of connected apparatus which depends upon the
5. Close and trip the breaker several times to proper operation of the circuit breaker, the circuit
ensure correct operations. Note that interlocks breaker must have regular, systematic care and
should be voided or in normal released position inspection.
so that the spring closing mechanism will The following points require special attention:
pick up the contacts and thus avoid discharging
the mechanism without its normal load. Dis- 1. Be sure that the circuit breaker and its mech
charging the spring closing mechanism without anism are disconnected from allelectric power,
load 'niposes severe stresses on the linkage both high voltage and control circuit: also be
and should be avoided. sure that the main closing spring is discharged
before being inspected or repaired.
- v..
2. Inspect the operoting mechanism periodically the effective life of the circuit breaker. It is
and keep it cleon. recommended that this practice be followed
3. Exomine the contocts frequently, see that they except that a circuit breaker which is operated
ore oMgned and that contact surfoces bear with every few days will not require much attention.
firm uniform pressure. Replace badly pitted 5. See that bolts, nuts, washer, clips and oil ter
or burned contacts before they are burned away
sufficiently to cause damage to other parts of minal connections are in place and tight.
the apporotus. 6. Clean the circuit breoker at regular intervals
4. The contact members of all types of discon where obnormal conditions sucn os salt de
necting or interrupting devices must be kept posits, cement dust or acid fumes prevoil to
clean ond bright to insure maximum operating avoid flashovers as a result of the accumulation
efficiency, it has been found by experience of foreign substances on the surface of the
that operoting the circuit breoker several times circuit breaker.
at intervals of not over two weeks will remove 7. Always check for loose nuts and bolts after any
the effects of oxidation ond materially prolong mointenonce work has bee'n completed.
'M.
Figure la Figure lb
MANUAL
ELECTRICAL
1. Front Plate 6. Spring chorge indicator
2. Frome 10. Emergency close handle
7. Door Interlock lever 11. Emergency spring chorge
3. Floating Trim 8. Rating plate
4. Manual Trip 12. Emergency manual close
9. Close button 13. Local close button
5. On-Off indicotor
14. Motor cut off switch
type h air circuit breakers
REMOVING THE FACEPLATE
With the front plate and frame removed the complete
consists of three ports: mechanism is exposed and inspectian and lub-
UMhe front plote, (2)the frome and (3) the fiooting ncatian of moving ports is readily accomplished.
trim end it is mounted to the cross channel of the Use o very light good quality machine grease such
mechanism bracket. OS lubroplateon the rochet assembly. Alight moch-
To disassemble, first remove the 4 oval heod
screws in eoch corner of the front plote. In remov be^opplied" where grease cannot
ing the front plate turn it to the left so it will slip SPRING MECHANISM
over the trip lever (4). The floating trim will The spring mechanism is located in the steel cross
then be free to be removed. Note that one side of channel and consists of seven parts (See fig. 2).
the trim is bevelled to correspond with the hinging
ot the front cover and it must be reploced correct The spring is charged by turning the crank approx
imately 180° in a clockwise direction. The rochet
ly to ensure smooth action os the door closes and holding panel prevents ony flyback during the
over the faceplate.
charging stroke. The spring in the charged position
The monuol handle is coptive in the front plate IS 10° over toggle and is held by a needle bearina
and moy be removed by drawing out the %" rolpin com. "
r\
'bracket-croBs channel
PLAN VIEW
»•
FP^E
TYPE H AIR CIRCUIT BREAKERS
1
m
MOTOR MECHANISM
The motor mechanism consists of a '4 h.p. univers embly from the breoker.The eccentric driving lever
al motor with a worm gear reduction. An eccentric is threoded onto the end of the worm gear reduction
lever is mounted on the end of the worm gear re- of the motor. Tap lightly in a counter clockwise
dution and drives the osci Hating lever. The driving direction to remove the eccentric and then remove
pawl is mounted on the oscillating lever and with the motor mounting bolts.
eoch stroke of the lever drives the ratchet around A spRciol greose is used in the worm gear reduct
one tooth at a time until the spring is charged and ion assembly and should not require replacement.
the limit switch is actuated to cut off the motor. If necessary use only Led-Plate compound 250.
To remo-e the motor mechanism, remove the two The following table lists the stondard ratings of
'4 - 20 Allen Head screws inside the steel cross motors. Note thot for a.c. applicotions 115 volt
channel (see Fig.4). Tilt the motor in to disengage motor is used throughout ond a control tronsformer
it from the oscilloting lever and remove the ass- is supplied for voltages other than 115V.
RATED
MAXIMUM TRIPPING
CLOSING SHUNT SHUNT
MOTOR VOLTAGE
CONTROL VOLTAGE CLOSE TRIP
VOLTAGE CURRENT RANGE
RANGE AMPS AMPS
AMPS VOLTS
48V dc
28-60
125V dc 90 - 130 70 - 140
250V dc 180 - 260 140 - 280
cross I
channel ^
I I • J
®—
lever
plunger
micro switch
1. Driving pawl
2. Oscillating lever
3. Motor assembly
4. Shunt close
5. Motor limit switch
Electrically operated breakers use a motor to rotate the cronk and fully charge the spring.
Figure 4— Motor Mechanism
ADJUSTMENTS
7/ 1. Latch Adjustment
When the breaker fails to latch the spring mech
anism discharges without carrying the contact
assembly to the closed position. Without the in
ertia of the contact assembly to absorb the energy
from the closing spring, severe stress is imposed
(See Fig. 6) on the closing mechanism and damage will result
if this process is repeated.
Figure 5(o) To adjust the latch first loosen the lock screw (9).
Turn the adjusting screw (10) counter-clockwise
two or three turns to ensure proper latching. Close
the breaker and then turn the adjusting screw clock
wise slowly until the breaker trips. Then turn the
adjusting screw back counter-clockwise one and
one quarter turn and lock with lockscrew (9). If
the breaker is subjected to severe vibration which
results in nuisance tripping more latch travel is
needed and one and a half turns can be used.
2. Holding Cam
If the holding cam does not reset properly it may
be jarred when the closing spring is charged, the
breaker will attempt to close as the closing spring
is charged without pressing the close button or
operating the shunt close device.
Figure 5b Referring to the spring mechonism shown in Figure
3, adjustments can be made as follows and should
be tried one at a time.
I
TYPE H AIR CIRCUIT BREAKERS
All type H breokers are supplied with the new type The relays ore colibrafed of the foctory at 80%,
PA direct acting overcurrent relay. These relays 100% ond 160% of trip coil rating and may be ad
are dual mognetic type consisting of long delay justed in the field to these calibrated marks.
element ond an instantaneous element.
INSTANTANEOUS CALIBRATION
A series coil is used on breakers below 600 amp
eres while a single conductor provides sufficient The relays are colibroted at the facto.y at 10 times
mognetic flux for all ratings over 600 amperes.The the trip coi Irating or for the range to suit the cont
very efficient magnetic design permits operation of inuous rating of the breaker and may be adjusted
the reloy ot very low ampere turn values ond thus in the field to these colibroted marks.
the coil normally associated with air circuit breo-
ker reloys is completely eliminated for oil ratings STANDARD TRIP RATINGS
of 600 amperes and over. In addition, coils used on
the lower rotings employ much lower current dens
ities than usual for this type of device and thus Breaker Overcurrent Trip instantaneous Trip
will operote ot much lower temperatures. Type Ratings (100% Calibration) Range (Adjustable)
Adjustable Screv
OIL FILLER HOLE
Figure 8o Figure 8b
(1) Fixed Arcing Contacts 25H-1 (5) Fixed Arcing Contact 50H—1
(2) Moving Arcing Contacts (6) Lower fixed orcing contoct 50H—1
(3) Pin (7) Blowout coil
(4) Moin contact (8) Contact sideplate.
ff^e
type h air circuit breakers
50-1600 AMP.
n.
2000-4000 AMP
thip shaft
(1) Roller
(2) Folding Roil
(3) Crank Nut
(4) Crankshaft
(5) Interlock com
' (6) Shock Absorber wJ
(7) Control tab
(8) Thrust bearing
(9) Interlock lever tab
(10) Interlock trip rod
(11) Truck Stops
(12) Rolpin
TAtP Sff4Pr
5000-6000 AMP
f'
13
FRyE
TYPE H AIR CIRCUIT BREAKERS
1. Tie Bar
2. Hood
3. Arc-chute
4. Base
5. Operating Handle
6. Overload Relay
7. Insuloted Couplinq .
8. Yoke
9. Tripshaft
10. Operating Lever
11. Operating Link
12. Cronkshaft
13. Faceplate
14. Spring Mechanism Frome
15. Braid
16. Main Contacts
17. Arcing Contacts
18. Faceplate Bracket
19. Terminols
20. Blowout Coil
21. Armoture
22. Trip Button
23. Interlock Lever
24. Wing Nuts
25. Ground Steel Com
26. Ratchet Wheel
27. Spring Crank
28. Main Spring
29. Holding Com Assembly
30. Spring Charge Indicator
31. Manual Close Button (55)
32. Provision for Padlocking
Trip Button
33. Provision for Padlocking
Operating Handle
34. Handle Clutch
35. Interlock Lever Spring
36. Floating Trim
37. Floating Trim Springs
38. Moving Main Contacts
14
TYPE H AIR CIRCUIT BREAKERS
SPARE PARTS
Quantity ITEM
PART NUMBER FOR BREAKER TYPE
•(1) DESCRIPTION NO. 25H.] SOH-t 75H.1.3000A I00H.I.4OOOA TOOH-1
I600AMP 50H.1.3000A 75H.t.4000A 6000A
49B-9888 49B-9888
Arc Chute 1 41A-4 41A-9880B 41A-9B80B 41A-8 41A-2-3
Main Braids 5 27A-81 27A-45A-1 27A-89 27A-45A-1 27A-58
Relay Oil (60cc) 195A-1 i95A-l 195A-1 I95A-1
-
195A-1
-P
\i> "^1
•4©
1. Arc chutes
2. Moving arcing contacts
» ©4
3. Stationary arcing contacts
3a. Upper stationary arcing contact
3b. Lower stationary arcing contact
4. Main moving contact
5. Braids
6. Upper main contact
7. Lower main contact 50H-1, 75H-1, lOOH.]
FOR ELECTRICALLY OPERATED BREAKERS ADD
©
m ©
©
©
\
% © 1. Antl-pumping relay
2. Coil assembly for No Volt Trip
3. Shunt Close assembly
4. Control transformer
5. Spring Limit Switch (S.LS.)
6. Closing Coil Limit Switch (C.C.
7. Motor
feOe^AL fAo'Fic
S^4> TW/j
AJ)^ JU7o^
71^^ T S- X5~o /
7^ .-
AjAajS/A'
-
r^
C-3-222
JUNE,1983
TYPEH-3,HL-3
LOW VOLTAGE POWER AIR
CIRCUIT BREAKERS •V.>
• •
; . -
:.;.v . • -.s' t
•;:'i
.i .
•1:V- i
: - -
i ./'5.
• V -r..-
/ E D E R
PIONEER '-mM-
F E D H R A PIONEER L 1 M IT E D
•• • ..T d"
; ^ -c;
;,m . V
^••V—1^-—
t-
APPLICATION switchgear conform to the following standards:
Type H-3and HL-3 low voltage power air circuit breakers ANSI C37.13 — "Low-Voltage AC Power Circuit
are used in metal-enciosed switchgear and unit Breakers"
substations lor the protection and control of low voltage ANSI C37.16 —"Preferred Ratings, Reiated
power circuits up to 250 volts dc and 600 volts ac. They are Requirements, and Application ' ^
a means of safelyswitching loads and automatically Recommendations for Low-Voltage
clearing circuits when such abnormal conditions as Power Circuit Breakers and AC
sustained overloads, short circuits, ground faults, or Power Circuit Protectors"
under-voltage occur. ANSI C37.17 —'Trip Devices for AC and General-
RATINGS Purpose DC Low-Voltage Power
600, 800,1600,2000, 3000, 3200, 4000 and 6000 ampere Circuit Breakers"
continuous current rating are available. Interrupting ANSI C37.19 —"Low-Voltage AC Power Circuit
capacities from 30,000 to 130,000 amperes for Type H-3, Breakers and Switchgear
and up to 200,000 amperes for Type HL-3 fused air circuit Assemblies"
breaker are available. ANSI C37.20 —"Switchgear Assemblies including
metal-enclosed bus"
DRAWOUT OR FIXED MOUNTING
ANSI C37.28 —"Low-Voltage AC Integrally Fused
Type K-3 and HL-3 breakers are available mounted on a
Power Circuit Breakers"
drawout cradle with disconnecting primary power and ANSI C37.50 —'Test Procedures for Low-Voltage
secondary control contacts. Type H-3 breakers can also be
AC Power Circuit Breakers Used in
provided lor fixed mounting.
Enclosures".
ELECTRICAL OR MANUAL OPERATION
British Standard 4752, "Part 1"
The breakers are provided with either a manually operated
handle or an electric motor for charging the stored-enei^ CSA C22.1 • "Canadian Electrical Code, Part 1".
closing mechanism. CSA (22.2 • No. 31, "Switchgear Assemblies"
EEMAC C8-2 • "Switchgear Assemblies"
USD SOLID STATE OVERCURRENT RELAY
Full overcurrent protection features include USD solid- lEC 1S7-1, • 1A "Specification for Switchgear
state relays with Federal Pioneer's ZSIF^ (ZONE SELECTIVE and Control Gear for voltages up to
INSTANTANEOUS PROTECTION). and including 10(X)V ac and 1200V
dc. Part 1, Circuit Breakers."
STANDARDS
Federal Pioneer Ty^ H-3 and HL-3 circuit breakers and NEMASC-3 - - "Low-Voltage Power Circuit
Breakers"
NEMASC-S - - "Switchgear Assemblies"
OPERATING MECHANISM 2
MAIN CONTACTS 3
ARC CONTROL 4
DRAWOUT CONSTRUCTION 5
ZSIP® 17
TYPICAL SPECIFICATION 24
SUPPORTING FRAME
The type H-3 and HL-3 breakers are
assembled on a moulded base of high
strength polyester-glass compound
using individual pole pieces carefully
interlocked together and supported by
a stainless steel frame. The use of
stainless steel prevents magnetic
heating. The mouldings are deeply
ribbed to provide large creepage
distances between adjacent current
carrying parts. These ribs also serve as
stiffeners to resist bending and
distortion under conditions of Manually operated H-3breaker
DETAILED maximum stress. Manual Operation
CONSTRUCTION The circuit breaker frame is For manual operation the charging
manufactured to close tolerances and handle, located centrally on the
jig-assembled to ensure accurate breaker faceplate, is first rotated
alignment of all parts. Close control is counter-clockwise and then pressed in
maintained over dimensional stability to engage a clutch mechanism.
to ensure complete uniformity and Rotating the handle clockwise
interchangeability of finished breakers approximately 180° will fully charge
of each frame size. the closing spring. A positive ratchet
OPERATING MECHANISM wheel mechanism allows a pause
Two types of operating mechanisms anywhere during the charging stroke
are available on the complete range of without handle fly-back. The breaker
type H-3 and HL-3 circuit breakers; can then be closed by pressing a direct
manual for local control and electrical acting manual close button on the
for both local and remote operation. A breaker faceplate. The closing spring
high strength compression type can also be charged manually when
closing spring is employed in all the breaker is open and left in the
operating mechanisms to give positive charged position, to be released from a
control of closing speed and force, remote position.
independent of the operator. The manually operated mechanism
includes provision for padlocking the
handle. On frame sizes 1600 amperes
and above, the handle has a pull-out
KJ extension for ease of operation.
m
Arcing contacts parted .Arc extinguished
CONNECTEDposition
Sp^:i:
DISCONNECTEDposition
DRAWOUT CONSTRUCTION
SeK'V.'
Thedrawout mechanism provides three
^4-- - positions for the breaker with the door
^;:' closed.
CONNECTED —Primary and
secondary contacts energized
TEST —Primary contacts isolated;
secondary contacts energized
DISCONNECTED — Primary and
secondary contacts isolated
A positive gear drive can be
operated from the breaker faceplate
even when the enclosure door is closed
and operates a cam lever on each side of
the draw-out cradle to move the breaker
through its positions. Normally, the
door can be opened with the breaker in
TESTposition
any position. An optional door interlock
can be provided to trip the breaker if the
door is opened.
The breaker is guided accurately on
grooved steel wheels fitted to the
outside of the breaker frame. As the
breaker is moved in from the
"disconnected" position, the grounding
contact is engaged first. This is a sturdy
phosphor bronze to copper contact
which ensures a positive ground
connection to the breaker frame. The
secondary or control contacts make
next, as the breaker reaches the "test"
position. Finallythe main contacts are
made as the breaker reaches the
"connected" position. A positive stop
DETAILED on the mechansim ensures that the 7jm\ \'
CONSTRUCTION breaker isfully connected before it can
be closed. Breaker position is also
clearly shown by indicators on the side .'-/.•v.,;::" ^
of the faceplate box.
Whenever the breaker is moved out
Rejection Feature
the reverse sequence takes place. After
the breaker reaches the "disconnected" Rejection Safety Feature
position and the enclosure door is A rejection feature is standard on all
opened, rugged folding tracks can be frame sizes and prevents entry of a
pulled down to roll the breaker by hand breaker into an enclosure intended for a
fully clear of the enclosure, exposing all different frame size. Pins on both sides
the plug-in contacts for examination. of the breaker frame must match slots
Safety shutters are available as an option cut in brackets mounted on both sides
to cover the main plug-in contacts of the of the cradle. If the cradle is a different
enclosure. frame size than the breaker, the breaker
Safety interlock pins will not match the slots cut in the
The drawout mechanism is provided cradle brackets.
with a safety interlock as standard to
ensure that the breaker is open and the
closing spring is discharged before the
breaker is either withdrawn from the
cell or connected into the cell.
Thedrawout mechanism operating
shaft is located behind a padlockable
sliding gate interlock on the breaker
faceplace. Lowering the gate to insert
the drawout handle trips the air circuit
breaker if it is closed, and then
discharges the closing spring if it is
charged. As long as the handle is
inserted, the breaker cannot be closed.
M
/ain Drawout Contacts - 1600A H-3
mm,
m »
TYPEHL-3
FUSED AIR
CIRCUIT
BREAKERS
800 NEMA L
1200 NEMA L
2000 NEMA L
3000 NEMA L
4000 NEMA L
6000 NEMA L
Secondary Conirol Contacts
ni
The device is energized directly, or
from a control transformer, and is
connected across two phases.
If voltage is available on the line
^mi
side terminals, the coil is energized
and will compress the springs. The
breaker may then be closed in the
normal manner. In operation, the coil
drops-out at 35% of rated voltage for
120V a.c. and 46% of rated voltage for
240V a.c. Both pull in at 80% rated
voltage.
Overload Lockout Device
The overload lockout device prevents
reclosing of the breaker either
manually or electrically after the
Shunt Uose
breaker has been tripped by the
overload relay, until this device is
Shunt Close
manually reset.
The shunt close device is used to release
The direct acting shunt trip
the energy stored in the closing spring
to close the breaker from a remote
solenoid plunger mechanically holds
position. It is standard on electrically the closing mechanism in the trip-free
position, preventing closing of the
operated breakers and is available as an
main contacts. The latch check switch
option on manually operated breakers.
wired in series with the closing coil is
open in this position, to block
electrical operation of the closing coil.
The device is reset by pushing the
manual overload lockout reset button
on the breaker faceplate. This reset
button is spring returned to its normal
position.
Alarm Contacts
A Single Pole Double Throw contact is
supplied and operated In conjunction
with the overload lockout device.
Contact is reset with the overload
lockout device. Where overload
lockout is not required a momentary
overload alarm contact can be supplied
Undenoltage Trip with Time Delay Attachmenl
to operate a remote flag relay.
Undervoltage Trip
The undervoltage trip provides
protection on loss of system voltage or
low system voltage. It is an a.c.
solenoid holding two compressed
springs which will trip the breaker
mechanically when the supply voltage
-•\'^al!s too far below normal. (See rating
'' data). Tripping action may be
instantaneous or delayed up to 5
seconds when the adjustable time-
delay attachment is specified.
N/r Y *4 ^
Auxiliary Sw.tch
V..-
r.ot
Door Interlock
All H-3 and HL-3 circuit breakers may
be fitted with a device which acts to
trip the unit when the cell door is
opened. In operation, the door lever
acts internally on the mechanical trip Cell Switches
button causing it to move in towards
^he faceplate. Cell Switches
Cell switches mounted in the cradle
can be provided to serve as position
indicators or as an electrical interlock
bypass. The switches are operated
when the breaker is removed from the
"connected" position in the enclosure.
Each switch contains one normally
closed and one normally open contact.
A total of six switches can be supplied.
These contacts are rated 10 amperes
up to 300V a.c.
mssBm
Ke)' Interlock
^ev Interlocks
/pe VF key interlocks, single or
double lock, with 3/8 inch (9.5mm)
projection can be provided. Provision
is made for key interlocks on all frame
Shutters
Shutters are available for all frame
sizes up to and including 3200 amperes
for both line and load side main
plug-in contact stabs.
For the 600, 800,1600, 3000 and
3200 ampere H-3 frame sizes, shutters
are of the lifting type. They have a
padlock bracket in the bottom of the
enclosure for locking in the down
position.
When the breaker moves from the
"test" to the "connected" position,
shutter bolts on the frame of the
ACCESSORIES breaker lift the shutter to expose the
FOR H-3 AND
main plug-in contacts.
For the 2000 ampere H-3 and for Lifting Device facilitates safe handling of breaker
HL-3 CIRCUIT
the 600, 800, 1600, 2000 and 3000
BREAKERS Lifting Device
amperes HL-3, shutters are of the
splitting type. When the breaker A lifting device is available from
moves from the test to operating Federal Pioneer for all frame size
position, shutter bolts on the frame of breakers. The lifting device is a one-
the breaker open the shutter to expose piece yoke which fits into lugs on the
the main plug-in contacts. breaker sideplates. This permits safe
A separate blanking truck may be removal of the breaker from the
used in 4000 ampere drawout breaker enclosure drawout tracks. Lifting yokes
cells. are ordered as follows.
Part Number 26G-542 for 600, 800,
1600 and 2000 ampere H-3's.
Part Number 26G-151 for 3000,
3200 and 4000 ampere H-3's.
Part Number 26G-601 for 600, 800,
1600 and 2000 ampere HL-3's.
Part Number 26G-603 for 3000 and
4000 ampere HL-3's.
Part Number 26G-150 for 6000
ampere 100H-2.
v.—Ti. tTS"
I^
®||j^|£
| ^H|> ^'W
la " l^« J^-4jjl ^^^SSSlpi
[f to ^^Pl'^^j^pj'^^en-™-—jj^^l^^jf
USD SOLID
STATE
ERCURRENT
RELAY
^
Carefully matched components of the USD trip system
USD-3IR
D
' - With ZSIP® the trip device that
senses a fault in its zone of protection LONG TIME • • • •
Ul
SHORT TIME
WITHOUT ZSIP®
SHORT TIME
• •
USD-6*
restraint signal to all upstream devices %
UJ
WITH ZSIP® • •
17
TYPE H-3 BREAKER DATA
BREAKER TYPE 30H-3 42H-3 50H-3 65H-3 50H-3 75H-3 100H-3 100H-2
MINIMUM ENCLOSURE
WIDTH (INCH) 25 25 25 25 32 32 32 32
VOLTAGE Voltage Ratings 600 600 600 600 600 600 600 600
(VOLTS)
Rated Maximum
Voltage 635 635 635 635 635 635 635 635
1 minute withstand 2200 2200 2200 2200 2200 2200 2200 2200
CURRENT CONTINUOUS 600/800 600/600 1600/2000 1600/2000 3000/3200 3000/3200 4000 6000
(AMPERES) CURRENT
INTERRUPTING
TECHNICAL CURRENT
DATA (RMS SYMMETRIC:AL) (1)
SUMMARY WITH INSTANTANEOUS
TRIP
TEMPERATURE RISE ON
TERMINALS (40°C AMBIENT) less than 55°C
(1) INTERRUPTING DUTY CYCLE consists,of an opening operation, a15 second interval,
followed by a close-open operation, perANSI Std. C37.50. . . <
(2) SHORT-TIME DUTY CYCLE consists of 2 —30 cycle intervals with a 15 second period of zero
current between the two periods, perANSI Std. C37.50. i
(3) Maximum Arcing Time in critical current range (Range 175-400A) is .035 seconds.
(4) Operating factor for reclosing duty is 100%.
18
TYPE HL-3 BREAKER DATA*
Ml data for HL-3 is same as corresponding size H-3 air circuit breaker, except for increased
-interrupting capacity.
NOMINAL 48 VOLTS 125 VOLTS 250 VOLTS 120 VOLTS 240 VOLTS
VOLTAGE DC DC DC AC AC
CURRENT REQUIRED
(INTERMITTENT) 7 amperes 4 amperes 2.5 amperes 4 amperes 2.5 amperes
MOTOR CHARGING
TIME 4.0 sec. 4.0 sec. 4.0 sec. 4.0 sec. 4.0 sec.
NOTES:
Type Ashunt trip is continuously rated and is used only when acontinuous rated coil for aseparate
trip source is required.
Type Bshunt trip is momentary rated. It is used as the dedicated solenoid for theUSD relay or
earlier SD relay and/or when onlya separate trip coil is required.
20
USD RELAY SETTINGS
INSTANTANEOUS 4X, 5X, 6X, ex, 10X, 12X, OFF (1) NO INTENTIONAL TIME
DELAY
GROUND FAULT
Catalogue Numbers:
USD-6(IR)-6 .25, .50, .75,1.0,1.5, 2.0 .08, .14, .20, .26, .32,
USD-6 (IR) -8 .25, .50, .75, 1.0,1.25,1.5 .02 in ZSIP® mode
USD-6 (IR) -16 .20, .30, .40, .50, .60, .70 regardless of ground
USD-6 (IR) -20 .20, .25, .30, .40, .50, .60 fault time delay setting.
USD-6 (IR) -32 .20, .22, .24, .28, .32, .36
USD-6 (IR) -40 .20, .22, .24, .26, .28, .30
TEMPERATURE RANGE: The USD relay is is supplying a load of less than 0.04Xthe sensor
ambient temperature compensated over the tap setting. If the breaker closes and the cu rrent
range-20°C to +55°C. Tolerances apply over is greater than 0.04X,but less than 13Xthe
this range. Operation outside this range is sensor tap setting, the discriminator monitors
possible. Consult Federal Pioneer. the current for 40ms. and if the fau It level of 13X
(1) DISCRIMINATOR: When the instantaneous is not exceeded during this time, the
pick-up switch is in the "OFF" position, the discriminator switches itself off.
instantaneous element will not pick up unless (2) SHORTTIME Time Delay .55 sec. @6X
the breaker closes on a fault that exceeds 13X (3) LONG TIME Time Delays shown @ 6X
the sensor tap setting, in wh ich case a
TOLERANCES: ± 8% on pick up values
discriminator will initiate tripping. In addition a
trip will be initiated if a fault of 13Xthe sensor ± 10% on time delay values
setting, or greater occurs while the breaker RELAY RESETTIME: 30ms
CURRENT SENSOR SIZES
AND AMPERE TAPS
TECHNICAL
DATA SENSOR TAPS BREAKER SENSOR TAPS BREAKER
SUMMARY TYPE AVAILABLE IN FRAME TYPE AVAILABLE IN FRAME
PRIMARY TAPS PRIMARY TAPS
22
TYPE USD SOLID STATE OVERCURRENT RELAY
TIME-CURRENT CHARACTERISTICS
oo<sec_
ooooee
.4 S .6.7.8.91 20 10 40 SO 5 Kggg
10000 « I HI I HIT 10000
0000 9000
8000 MODEL 8000
USD-3 USD-6 - 7000
CURVES
6000 6000
5000 LONG TIME 5000
4000 SHORT TIME -]4000
3000 INSTANTANEOUS 3800
GROUND (AULT
mS:
CURVES BASED ON NOMINAL VALUES
1000 WITH SINLiSOlDAl CURRENT. 1000
900 PROOuaiCN TOLERANCES AND 900
080 AMBIENT TEMPERATURE EFFECTS FROM 800
700 700
600
•30*C TO * 55*C Will CAUSE MAXIMUM 600
110% VARIATION ON TIME DEUY AND - 500
SOO
18% ON PICKUP.
408
• 300
BACKUP PROTECTION
2. PICKUP AT 2, 3,4,6,8
& 10 TIMES SENSOR TAP
SHOWN AT 2 TIMES
SENSOR TAP.
.3 .4 .5 .6.7.8.91 2 3 4 5 6 7 8910 20 30 40 SO
e SSoeeS
tAU>r>too>o
^L
Low voltage power air circuit breakers with enclosure door closed, and shall
shall be 3 pole 600 volt class with be equipped with an interlock to
continuous current ratings and trip ensure breaker contacts are open and
ratings as detailed on the plans. closing spring is discharged when
Interrupting ratings will be in racking tool is inserted. Faceplate
accordance with NEMA Standards for mounted control buttons, indicators
the frame and/or their application in a interlocks etc. shall be accessible
fully rated system. Breakers shall have without opening enclosure door.
double break main contacts, a 3 phase Electrically operated breakers must
solid state overload relay and shall be have provision for emergency manual
trip free in operation. A compression closing by inserting a special tool
spring stored energy closing through the faceplate. A control
mechanism (either manually or isolating switch shall be provided on
electrically charged) shall be used for the faceplate to isolate the supply to
all ratings, with breakers being closed the spring charging motor.
by means of a push button and shall Relay pickup and time delay
have the ability to close and latch at settings shall be selected in discrete
interrupting rating at 600 volts. An factory calibrated values by means of
emergency manual spring charging detent action thumbwheel actuated
handle shall be supplied for electrically switches with gold-plated contacts.
operated breakers. When a solidly-grounded system is
Breaker faceplate shall have used, the relay shall be equipped with
"closed-open" indicator, spring Zone Selective Intantaneous
"charged-discharged" indicator, Protection feature on short time and
provision to padlock manual charging ground fault elements. A direct acting
handle, provision to lock breaker in dedicated solenoid shall be used for
"open" position, and provision to lock initiating breaker triping.
drawout mechanism. Drawout circuit Breakers shall be Federal Pioneer
breakers shall be suitable for 3 position Limited Type H-3 or HL-3.
(connected, test, disconnected) racking
r^i
C-3-222-1
PIONEER FEBRUARY 1984
INSTRUCTIONS
FOR THE CARE AND MAINTENANCE OF
r '
mbi
•ft'
. F
This manual applies to H-3and HL-3 breakers.
For H-2and HL-2 breakers, consult the following instruction
manuals:
Lubrication . 5
. 7
Close Latch Adjustment
Mechanism Latchingand TripShaft Adjustment . 9
Page 1
PART NUMBERS AIR CIRCUIT BREAKERS (DRAWOUT)
Type30H-3 Typ«50H-3 Type SOH-3 Type50atKl75H-3 Type 100H-3
FIGURE 1 4000 Amp
600 and 600 Amp 1600 Amp 2000 Amp 3000 and 3200 Amp
SECTION OF K-3 BREAKER
41A-504D 41A-504D 41A-504D 41A-504D 41A-5040
1. Arc Chute Assembly
13A-574C 13A-574C 13A-574C 13A-578C 13A-578C
2. Intemliase Barrier
13A-575C 13A-575C 13A-575C 13A-172A-1 13A-172A-1
3. R. H. End Barrier
13A-576C 13A-S76C 13A-576C 13A-172A-1 13A-172A-1
4. L H. End Barrier
182A-542B 182A-542B 182A-542B 182A-40A-1 182A-40A-1
5. Front Flash Shield (^1A-1)
(-41A-1)
170A-585 170A-585 170A-585 170A-585 170A-585
6. Closed-Open Link
54C-507 54C-507 54C-507 54C-507 540507
7. Crank Assembly
24A-15A-2 24A-15A-2 24A-15A-2 24A-15A-2 24A-15A-2
8. Crank Box
29B-514 29B-514 29B-S14 29B-514 29B-514
9. Crank Box Bearings
210A-505 210A-505 210A-505 210A-505 210A-505
10. Holding Pawl
35A-508 35A-508 35A-508 35A-50d 35A-508
11. Ratchet Wheel
12. Osciilating Lever 168B-S92 1686-592 1686-592 1686-592 168B-592
(FIXED)
45. Uppsr Stdtionary Main Contact 49E-555 49E-549 49E-549 49E-549 49E-549
/j®®
&
Page 3
Except for the mounting the following instructions for 6. Close and open the unit several times to ensure
fixed mounted breakers equally apply to drawout correct operation. Interlocks should be defeated or be in
mounted breakers. normal release position, if an undervoltage trip unit is
attached hold it down manually so the spring closing
mechanism will pick up the contacts, and thus avoid
FIXED MOUNTED BREAKERS discharging the mechanism without its normal contact
spring load.
H-3 and HL-3 circuit breakers should be mounted in 7. Manually activate the tripping devices to estaJjIish that
sheet steel enclosures in accordance with recommended they are operable. These devices include manual trip
dimensions. The mounting support should be a rigid Rg. 2, spring discharge lever Rg. 9, shunt trip Rg. 11
structure able to withstand the impact caused by the and 12, and undervoltage trip Rg. 13.
switching operations, without any distortion and undue
vibration of the mechanism. 8. Check all cable connections to ensure that they are
tight.
9. The electrical operation of drawout breakers shouldbe
POWER TERMINAL CONNECTIONS
checked in the "test" position.
The H-3 and HL-3 terminals are silver plated for
maximum joint efficiency and cable connectors must be Manual Closing
clean and free from dents or burrs, and bolted securely
The closing mechanism compresses a mainspringwhich
to the terminals. Poor joints lead to over-heating and
subsequent contact deteriorafion, and an eventual is held compressed until released. The handle is rotated
counter-clockwise to the vertical position and pushed In
failure. Cables or bus connections should be properly
supported so as not to transfer any unnecessary to engage the clutch. Rotating the handle ISO" clockwise
mechanical or short circuit stress to the terminals. Any fully chargesthe spring and as the internal crankpasses
strain which may have no apparent effect initially may through top-dead-centre, rotation is stopped, and held by
after prolonged periods of vibration and shock from the close release latch. Operation of tftis latch by means
normal operation, cause poor contact alignment. of the close push button Rg. 2 in the faceplate releases
the spring energy to close the breaker. A multi-tooth
Meter shunts, resistors, and similar devices which ratchet wheel prevents recoil and permits the spring
operateat relatively high temperature should be mounted charging to be performed in sevet^ short strokes if
awayfrom the circuit breakerso they do not contribute to desired. On frame sizes 1600 amperes and above, the
the heating of the unit. handle is a pull-out extension typeforease of operation.
Electrical Closing
SECONDARY CONTROL CIRCUITS
On all electrically operated units the motor charges the
Control circuit wiring, where applicable, should be made spring unit the close release latch engages. The close
in strict accordance with detailed wiring diagrams. Wiring latch Is operated by a solenoid energized from the push
connections, which are made to terminal blocks should button in the faceplate. Fig. 2 or by a remote button. The
be run in a supported and protected manner, so control closing stroke then follows in a similar manner to that of
wiring cannot come into contact with the primary the manual type described above. A removable handle is
connections. provided to permit manual charging of the spring. A
mechanical close button similar to that on the manually
operated unitis not Included. Emergency operationof the
PRE-SERVICE INSPECTION close release latch is accomplished by insertion of a pin
through a small aperture in the faceplate. Fig. 2. A
Read this instruction manual completely and inspect and suitable pin is provided in the upper end of the manual
check the unit in accordance with this manual. charging handle.
The following itemsshouldbe specifically checked.
BREAKER MAINTENANCE
1. Make a visual Inspection after installation to ensure
that no parts have been damaged or forced out of The safe and successful operation of connected ap
alignment. paratus depends uponthe proper operation of the circuit
breaker. Therefore, it must have regular, systematic care
2. Check the door interlock lever for freedom of and inspection. ITie following points require special
movement, when supplied. (Fig. 27). attention.
3. Check the main and drawout contacts to see that they 1. Beforeinspectingor repairing the H-3 or HL-3 be sure
are clean and free from foreign material. it is disconnected from any electric power, either high
4. Check all the control wiring to ensure that it has not voltage or control voltage. Also check that the main
been damaged or moved during the installation. spring is discharged. If the breaker is electrically
operated,turnthe motor isolating switch on the faceplate i
5. Check the single phase protection (when supplied) by to the "off" position before tripping the unit to prevent the ' Y
manually raising each tripping plunger in turn on the motor from recharging the spring. (Fig. 2).
threetripping coils, Rg. 24. If the unit is closed, itshould
trip and the correct indicator should show on the 2. Inspect the operating mechanism periodically and
faceplate. (Rg. 2). keep It clean.
Page 4
FIGURE 2(A) FIGURE 2(B)
FACEPLATE FOR ELECTRICALLY OPERATED FACEPLATE FOR MANUALLY OPERATED
LEGEND
Grease-Lubrlplate Lo-Temp.
LUBRICATION
1. Spring guide pin (located at the lower end of the
H-3 breakers have been tested for mechanical endur closing spring).
ance to the prescribed numl>er of operations by ANSI 2. Ratchet wheel teeth.
standards without lubrication during the tests. No seizing
of the mechanism occurred and the breakers were still ELECTRICALLY OPERATED MECHANISM
operational. In service It Is possible to encounter dust, (Ref. Fig. 3).
corrosive atmospheres and other adverse conditions Oil-SAE30
which may Impair proper operation. Therefore, we
consider It prudent to lubricate and dean breakers 1. All linkage pivots within the mechanism compartment
periodically. ANSI standards recommend lubrication and 2. All closing shaft bearings.
sen/icing to be carried out at the following periods. 3. Holding pawl pivot (located within the faceplate
enclosure-upper left hand corner).
In frame sizes 600 and 800 amps this inten/al Is 1750 4. Motor limit switch lever pivot (located with the front
operations, In sizes 1600 and 2000 amps the Interval Is channel - left hand corner).
500 operations, and in sizes 3000 amps and atxive, 250 5. Close latch pivot (located below the main ratchet
operations. The following points should receive attention: v^eel).
Page 5
FIGURES
ELECTRICALLY OPERATED LUBRICATION
Grease-Lubriplate Lo-Temp.
FIGURES
1. Spring guide pin (located at (he lower end of the
MANUALLY OPERATED closing spring).
LUBRICATION 2. Ratchet wheel teeth.
3. Front face of the ratchet wheel.
4. Oscillating lever - right hand end (at the motor
drive cam).
5. Driving pawl pivot and springs (located on left hand
end of the closing spring.)
LINKAGE
X — Oil - SAE 30
Y — Grease - Lubripiate
FIGURE 4
MANUALLY OPERATED
1. Ratchet Wheel
2. Holding Pawl
3. Close Latch
4. Auxiliary Switch
5. Spring Guide Pin
6. Solid State Overcurrent Relay
m.
Page 7
FIGURES
ELECTRICALLY OPERATED
1. Ratchet Wheel
2. Holding Pawl
3. Oscillating Lever
4. Close Latdi
5. Shunt Close
6. Motor
7. Auxiliary Switch
8. Spring Limit Sviritch
9. Spring Guide Pin
ml 10. Solid State Overcurrent Relay
11. Anti-Single Phase Device and
Blown Fuse Indicator
Page 9
This adjustment, located on the left hand side of the FIGURE 10
mechanism compartment, controls the engagement of ECCENTRIC ADJUSTMENT
the trip shaft to the latch roller. If this engagement Is
insufficient, the roiier may release during the dosing
stroke, resulting in faiiure to close. The main contacts wiii
appear to move but not compiete the travel.
To adjust, the following procedure should be used. With
reference to Rg. 8 loosen iocknut (item 1) and turn
adjusting screw (item 2) counter-clockvrtse two turns.
Close the breaker and slowly turn the screw clockwise
until the unit trips. Now turn Ihe screw counter-clocdcwise
one and one quarter turns and tighten the iocknut.
•-1/52 IN.
NOTE: Whenever this adjustment is made the following (•6mm)
should be checked if present on the breaker. SEE DETAtL W
SHUNT TOIP
Two types of shunt trip units are available for use on ail
H-3 and HL-3 breakers each having specific performance
features.
Page 10
attempt to reclose the breaker before resetting the relay FIGURE 12
will preclude a restriking of the ground fault. No SHUNT TRIP TYPEB
adjustment is required on this device and the only
attention needed is that of ensuring that the plunger is
\ free of any binding or friction. This unit is capable of
:.f y-«4ripping at 50% of the rated voltage.
TypeB(Fig.12)
This is a cylindrical solenoid mounted within the
mechanism compartment at the lower rear and acting
directly on the trip shaft. Unlike the Type A unit, it is not
continuously rated and for any application a normally
open auxiliary switch contact must be used. In the 120
volt ac application the Type B uriit is equivalent in
performance to the Type A device (i.e. will operate at
50% of rated voltage) but in the 125 volt do rating,
tripping can be perfomied at levels as low as 25% of
nominal rating. One adjustment is provided in the Type B
trip unit to control the extent of free travel between the
plungerand the trip shaft lever. By lifting the plungeruntil
the striker rod is lightly touching the trip shaft lever a 1. Plunger
space of 1/16 inch (1.6 mm) should exist between the 2. Stop Plate
end of the plunger and the stop plate as shown in Figure 3. Mechanism Sideplate
12. 4. Shunt Trip (Separate Trip Source)
5. Shunt Trip (USD Relay Trip Source)
If adjustment is required, loosen the 8-32 socket head
screw located at the bottom end of the plunger and turn
the striker rod within the plunger as required. Retighten 2. With USD relay, a Type B is used between the
the set screw. If trip shaft adjustment (Fig. 8) is altered at mechanism sideplaies to operate wiUi the relay, and
any time, this striker rod adjustment should be checked. possibly a Type B mounted outside the left hand
mechanism sideplate to be used as a separate trip
The shunt trip is identified on the wiring diagram by the
coil.
symtrol "TC".
3. A Type A. mounted only outside the left hand
^'''^^oth units can be installed on one breaker. With regard mechanism sideplate, is used only when a continuous
_ to use, the following rules are usually adhered to: rated coil for a separate tripsource is required.
4. Type Aand Type Bused in conjunction with the USD
1. A Type B is used where only a separate trip coil is relaycan both be used on the same unit.
required.
UNDERVOLTAGE TRIP (Fig. 13)
FIGURE 11 The Undervoltage Trip is a spring operated unitmounted
SHUNT TRIP TYPE A on the left hand side of the main mechanism compart
ment and acting directly on the trip shaft. In operation
two springs are held in compression by a rectangular
solenoid.
• $
Normally supplied in the 120 volt ac rating, the solenoid
has a holding currentof 340 milliamperes, with an inrush
of 2.45 amperes. A mechanical escapement time delay
attachment is available which provides a delay adjusta
ble from 0 to 5 seconds.
Page 11
FIGURE 13 No adjustment is required on this unit and the only
UNDERVOLTAGETRIP attention needed is that of ensuring that the plunger is
free of any binding or friction. The device is capable of
operating at 75% of rated voltage.
' ' •• 0
Preferred control circuitry permits spring charging to take
place after the breaker has tripped only. While a unit can
be supplied to charge after close, this should be used
only in applications requiring high speed reclosing.
Unless otherwise specified all units are supplied to
1. Striker operate in the "charge after trip" sequence.
2. Trip Shaft Lever
3. Timer
The charging motor is identified on the wiring diagram by
4. Vernier Time Adjustment the symbol "M".
FIGURE 14
SHUNT CLOSE
In operation, the undervoltage trip has a dropout of
35% of rated voltage for 120 V. a.c. and 46% of rated
voltage for 240 V. a.c. Both have a pull-in of 85% rated
voltage and are identified on the wiring diagram by the
syml5ol "27".
Page 12
To remove the motor, first remove the bracket assembly FIGURE 16
from the frame channel, noting the number of shims at
LATCH CHECK SWITCH
the top and iDOttom faces of the motor bracket. The drive
cam and outboard bearing should then be removed. The
I I
drive cam Is threaded to the motor output shaft and can
be readily released by a light tap in the counter-clockwise
direction. Remove the hex head bolt holding the front fb' 0
bracket to the motor. Next, remove the mounting screws
at the end opposite to the drive and motor housing can
be withdrawn from the rear bracket. When replacing the
\C-'5
motor bracket assembly in the channel, replace the
shims as originally installed. Do not tighten the hex head ® )<]
bolt holding the front bracket to the motor until the
screws holding the motor brackets in the front channel
have been tightened securely.
1. Cam
2. SLS Lever Actuator
3. Spring Limit Swritch
FIGURE 15
MOTOR CLOSING SPRING LIMIT SWITCH
Page 13
CONTACT MAINTENANCE
MAIN MOVING CONTACT DEFLECTION
Examine the main breaker contacts (and disconnecting At intervals as recommended by ANSI standards (see
contacts on drawout mounting breakers) frequently to paragraph on Lubrication), the deflection of the main
see that they are properly aligned and that the contact moving contacts should be checked. The deflection
surfaces bear with firm uniform pressure. should be maintained between the limits of 3/64 to 4/64
inches (1.2 to 1.6 mm) for 600, 800, 1600, and 2000
The contact surfaces of all types of disconnecting or ampere frame sizes, and 2/64 to 3/64 inches (0.8 to 1.2
interrupting devices must be kept clean and bright to mm) for 3000, 3200, and 4000 ampere frame sizes. A
ensure maximum operating efficiency. Contact surfaces gauge is available for measuring purposes which carries
which are corroded by contaminated atmospheres will a scale graduated in 1/64 inch (0.4 mm) divisions. For
cause overheating and subsequent failure of the device. the 1600 amp and larger frames use Gauge Number
The alloy contacts of the type H-3 and HL-3 will resist 96A-500, and for the 600 and 800 amp frame use Gauge
contamination to a great degree but in areas where Number 96A-501.
sulphur is present or other chemicals which readily
combine with silver, regular maintenance is required to With the circuit breaker open establish the starting or
ensure contact efficiency. "zero" point for each main moving contact assembly.
Applythe gauge to the left hand side as shown in Figure
See that bolts, nuts, washers, clips and ail terminal 20 (A) and note the position of the pointer. To assist in
connections are in place and tight, espedaiiy after positioning the gauge the pointer should be moved
completion of any maintenance work. fonivard or "up scale" then released to allow the indicator
When abnormal conditions exist, such as salt deposits, pins to locate as shown.
cement dust or add fumes the breaker should be With the circuit breaker closed again apply the gauge as
cleaned at regular intervals. This will prevent fiashovers shown in Figure 20(B), and note the position of the
caused by the accumulation of foreign substances. pointer. The number of divisions the pointer has moved
from "zero" position indicates the amount of main
contact deflection, each division representing 1/64 inch
MAIN POWER CONTACTS (0.4 mm) deflection.
Main contacts are silver alloy and should be dean, bright When adjustment is required, proceed as shown in
and free from pitting. They may be gently sanded if Figure 21. Using any suitable blocking device, position
necessary using a fine emery to remove pit marks. Avoid the moving contact members toward the closed position
having particles fail into the mechanism, and wipe as shown and loosen capscrews (Item 1). Shims (Item 2)
contacts clean with doth after sanding. are added as required to restore deflection to within the
If the main contacts are severely damaged make a limits stated above. After shims are added, it is important
careful inspection of ail current carrying parts. Supporting that the capscrews be finnly tightened before closing the
pins, linkage, and especially springs should be examined unit in the normal manner.
for damage due to excess heat. Annealed or distorted A supply of shims is included with tire gauges.
parts should be replaced. Before attempting this, consult
the manufacturer.
FIGURE 17
CONTACT DIFFERENTIAL ADJUSTMENT
CONTACT DIFFERENTIAL (Fig. 17 and 18)
At intervals as recommended by ANSI standards (see
paragraph on Lubrication), the differential between the
main and arcing contacts should be checked. The y-® (SK
differential should be maintained between the limits of
0.050 to 0.065 inches (1.3 to 1.6 mm). Using the slow
close device (Fig. 16 (A)) close the contacts until the
moving arcing contact touches the stationary arcing
contact (Fig. 16 (B)). A gap of 0.050 to 0.065 inches (1.3
to 1.6 mm) between the main moving wafer contacts and
the main upper fixed contact should exist The gap is
checked using a feeler gauge. If adjustment is neces
sary, shims (Fig. 17, Item 4) are placed between the
stationary arcing contacts and the main upper fixed
contact. This is done by removing the stationary arcing
contacts. Shims are available from the manufacturer
(Part Number 241A-500).
Note that it is not important nor necessary that the arcing
contacts touch simultaneously. The differential should be
measured on each pole by closing the contacts until the V4-20XVa Inch Long Hex Bolt and Lockwasher
arcing contacts touch on the pole being measured. V4-20 Hex Nut and Lockwasher
V4-20 X1 inch Long Hex Boltand Lockwasher
Contact differential should always be checked before Shim
main moving contact deflection. V4-20 X=»/4 Inch Long Hex Boltand Lockwasher
Page 14
FIGURE 18(A)
SLOW CLOSE DEVICE
/ V
FIGURE 18(B)
SLOW CLOSE DEVICE
B I
SPACER
[/ T I
©iFBicD
Page 16
FIGURE 20(A)
MOVING CONTACT DEFLECTION
FIGURE 20(B)
MOVING CONTACT DEFLECTION
r*
Page 17
FIGURE 21 OVERLOAD LOCKOUT DEVICE {Fig. 23)
MOVING CONTACT ADJUSTMENT The overload lockout device prevents reclosing of the
breaker either manually or electrically after the breaker
has been tripped by the overload relay, unti this device Is
manually reset. Two micro switches with normally open
contacts are also available to act as overload alarm
contacts.
FIGURE 23
plates. One adjustment is provided to give a space of OVERLOAD LOCKOUT DEVICE
1/16 inch (1.6 mm) between the end of the plunger and
the stop plate on the trip shaft. If adjustment is required,
refer to the section entitled Shunt Trip, Type B (Fig. 12).
Many H-3 and HL-3 type breakers have been supplied
with the SO type solid state relay. This relay has been
replaced in manufacturing by the USD type solid state
relay. The USD relay Is an improved design incorporating
many features not available on the SD relay.
For complete details of the SD relay refer to instruction
manual C-3-216-2.
li? 01
FUSE MOUNTING — HL-3 ONLY
Page 18
HL-3 Frame Relay Rating
supply voltage in excess of 250 Is to be used, the higher
Maximum Fuse
Rating (Amperes) (Amperes) Rating (Anperes) voltage contacts are double spaced (I.e. the adjoining
contact Is unused).
1600NEMAL
1600 NEMAL AUXILIARY SWITCH (Fig. 5)
3000NEMAL
3000 NEMAL On all H-3 and HL-3 units a multi-section rotary switch Is
4000 NEMAL
used. It is coupled directly to (he closing shaft and
6000 NEMAL
operates on a snap-action principle which provides quick
break switching. No adjustment is required and the
ANTI-SINGLE PHASE DEVICE AND BLOWN FUSE switch is available in the following contact arrangements.
INDICATOR — HL-3 BREAKER ONLY (Fig. 24)
4-pole, providing 2 normally open and 2 normally dosed.
The anti-single phase device is supplied on all frame 6-pole, providing 4 normally open and 4 normally closed.
sizes. The unit consists of three trip solenoids each t2-pole, providing 6 normally open and 6 normally closed.
acSng upon an independent slide, which in turn acts 16-pole, provldng 8 normally open and 8 normally closed.
directly onto the trip mechanism. When activated by the 20-pole, providing 10 normally open and 10 normally closed.
solenoid, Uie slide moves forward and latches in this The following contact ratings apply.
position, thus locking the breaker in a trip-free state.
Each solenoid coil is connected In parallel across the 10 amperes up to 254 V.a.c.
corresponding power fuse and in normal operation the 1 ampere at 250 V.d.c.
trip coil Is, in effect, shorted out. 2 amperes at 125 V.d.c.
The slides are colour coded, red, yellow and blue and
when tripped they protrude through an aperture in the
faceplate (Ret. Fig. 2), thus providing a blown fuse
indicator. Red indicates the left hand phase, yellow
FIGURE 24
centre and blue right hand. To reset, the slide is lifted
and pushed in at the faceplate opening. The breaker ANTI-SINGLE PHASE DEVICE
cannot be redosed until the anti-single phase device and
blown fuse indicator is reset. |P> ^
SECONDARY CONTROL CONTACTS (Fig. 34) MECHANICAL OPERATIONS COUNTER (Rg. 25)
Secondary control contacts are provided on drawout A five digit mechanical counter can be supplied. It is
units to automatically connect or disconnect control mounted in the faceplate of the breaker (Fig. 2).
circuits, as the circuit breaker moves through its positions
In the cradle. The contacts are designed such that the This device is mechanically driven by the "charged-
control circuit can be energized or isolated in the test discharged" indicator. The counter operates once for
position. These connections can be altered In the field, each charging of the breaker main spring. No adjustment
, when required, by means of jumpers between contacts of or maintenance is required for successful counter
•T the stationary block. operation.
Supplied In multiples of 8 contacts, a total of 48 can be Operations counters are recommended where breakers
provided, and each contact has a continuous current will be subjected to frequent operations as an indicator of
rating of 30 amperes, in applications where a control the recommended maintenance intervals.
Page 19
FIGURE 25 FIGURE 26(A)
MECHANICAL OPERATIONS COUNTER MECHANICAL INTERLOCK
I* ^
DrSCHARGEDl
3l»
CLOSE
I Qm\H
I
DU V9IU'
LC OISJOSCUU^
1. Breaker Frame
2. Upper Plunger (Connected to ClosingShaft)
3. Lower Plunger (Connected to Trip Shaft)
MECHANICAL INTERLOCK (Fig. 26)
FIGURE 26(B)
Mechanical interlocks are available on all H-3 and HL-3 MECHANICAL INTERLOCK
breaker frame sizes. They are used to mechanically
interlock breakers in a two or three breaker transfer
scheme. In the case of a two breaker transfer scheme,
mechanical interlocks ensure only one breaker is closed
while the other is held in a trip free position. In a three
breaker transfer scheme, mechanical interlocks ensure
only two breakers are closed while the third is held In a J
trip free position.
Mechanical Interlocks connect with flexible cable the Jl) pi
closing shaft of one breaker to the trip shaft of a second
breaker, and vice versa. If one breaker is closed, the
other breaker Is held in a trip free position. Drawout
breakers are interiocked by cable connections between
the two cradles. There are no permanent connections
between the breaker and matching cradle when interlock
ing is supplied, so the breaker can be freely withdrawn
^ t
from the cell. Mechanical interlocks are operable only « .J
when the breaker is in the connected position. When
withdrawn to the test position, breakers are not
interlocked and can be test operated in the normal
manner.
1. Breaker Frame
Mechanical interlocks are preset at the factory and 2. Cradle Frame
require no adjustment. The plungers at the rear of the 3. Upper Flipper
breaker should be checked for freedom of movement at 4. Lower Flipper
intervals as recommended by ANSI standards (see 5. Cable Connections to Lower Cradle
paragraph on Lubrication).
DOOR INTERLOCK (Fig. 27)
With the breaker removed from the cell, manually close
the main contacts using the slow close device (Fig. 18). All H-3 and HL-3 circuit breakers may be fitted with a
With reference to figure 26 (a), the top plunger at the rear device which acts to trip the unit when the cell door is
of the breaker connected by cable to the closing shaft opened. In operation, the door lever acts internally on the
should move freely with movement of the closing shaft. mechanical trip button causing it to move in towards the
Next, charge the main spring and close the breaker. faceplate. This interlock may be defeated by arresting
Pushinginon the lowerplunger at the rear of the breaker the movement of the trip button. A screwdriver blade or
should open the main contacts. If the plungers do not similar tool inserted through the slot in the trip button will
move freely, the cable must be removed from the sheath allow the door to be opened without tripping the circuit
and cleaned to restore free movement. breaker.
Page 20
FIGURE 27 CELL SWITCHES (Fig. 29)
DOOR INTERLOCK Cell switches mounted in the cradle can be provided
when required to serve as position indicators or external
electrical interlocks. The switches are operated when the
breaker is moved from the test to operating position in
the enclosure.
FIGURE 29(A)
CELL SWITCHES (600, 800, 1600 & 2000 AMP)
m
KEY INTERLOCKS (Fig. 28)
Type VP key interlocks single or double lock with 3/8
Inch (9.5 mm) projection can be provided. They mount
with 3/8-16 screws behind the breaker faceplate. Key
interlocks can be installed in the factory. Provision is
made for key interlocks on all frame sizes.
The lock plunger engages the tapered section of the
manual trip button when the key Is removed. With the
key removed the dosing mechanism Is completely trip 1. Breaker Frame
free thus preventing ciosing of the main contacts. For 2. Cradle Frame
electrically operated units an auxiliary switch contact is 3. Operating Bracket
provided to operate in conjunction with the Interlock to 4. Cell Switches
Isolate the closing circuit.
FIGURE 28
KEY INTERLOCK FIGURE 29(B)
CELL SWITCHES (3000, 3200 & 4000 AMP)
FEDERAL P ONEE
POLES
VOltS
'R. SIZE
RELAY
NT.CAP. 1. Cell Switches
CONtAai.C
2. Cradle Bus Pan
CONTROL
3. Ground Stab
FREO.
4. Shutter (In Open Position)
Page 21
SHUTTERS (Fig. 30) For the 2000 ampere H-3 and for the 600, 800,1600 and
2000 ampere HL-3 shutters are of the splitting type
Shutters are available for all frame sizes up to and shown In figure 30 (B). When the breaker moves from
including 3200 amperes for both line and load side main the test to operating position, shutter bolts on the frame
plug-in contact stabs. of the breaker open the shutter to expose the main
For the 600, 800, 1600, 3000, and 3200 ampere H-3 plug-In contacts.
frame sizes, shutters are of the lifting type shown In The shutters do not require field maintenance.
figure 30 (A). They have a padlock bracket In the bottom
of the enclosure for locking In the down position. When REJECTION FEATURES (Fig. 31)
the breaker moves from the test to operating position,
shutter bolts on the frame of the breaker lift the shutter to
Rejection features are provided on all frame sizes. The
expose the main plug-In contacts.
rejection feature prevents entry of a breaker into an
enclosure of a different frame size. Pins on both sides of
FIGURE 30(A) SHUTTERS the breaker frame match slots cut in brackets mounted
on both sides of the cradle.
asi atf (T) If the cradle is a different frame size than the breaker, the
breaker pins will not match the slots cut In the cradle
brackets. Entry of the breaker Into the wrong frame size
enclosure Is then prevented.
1. Cell Switches
2. Secondary Control Contacts
3. Ground Stab
4. Shutter Mechanism
5. Padlock Bracket
FIGURE 30(B) SHUTTERS
1. Breaker Frame
2. Rejection Pin
3. Rejection Bracket
4. Cradle Sideplate
Page 22
FIGURE 32
LIFTING DEVICE
lU''
l«.
FIGURE 33
COIL DATA
Rated Minimum
Control Operating
Voltage Voltage
120 AC
Shunt 240 AC
Trip 48 DC
Type A 125 DC
250 DC
120 AC
Shunt 240 AC
Trip 48 DC
TypeB 125 DC
250 DC
120 AC
240 AC
48 DC
125 DC
250 DC
Unden/oltage 120 AC
Trip 240 AC
Anti-Single 240 AC
Phase 480 AC
Device 600 AC
120 AC
240 AC
Charging 48 DC
Motor 125 DC
250 DC
Page 23
SPARE PARTS (Fig. 34)
By the nature of its application and its switching recommended spare parts list shouid be carried in stock.
capability spare parts for the circuit breaker should When ordering spare parts, the compiete natiepiate
nomn^iy not be required. If Uie unit is going to be used data, especially the breaker serial number, shouid be
for frequent load switching, then the parts shown on the provided to ensure that the correct parts are supplied.
FIGURE 34
SPARE PARTS
MAIN DRAWOUT
MAIN DRAWOUT
CONTACT ASSEMBLY CONTACT ASSEMBLY
(4000 Amp)
(600 & SOD Amp)
MAIN DRAWOUT
CONTACT ASSEMBLY
(1600. 3000 & 3200 Amp)
MAIN DRAWOUT
CONTACT ASSEMBLY
(2000 Amp)
I \
-U.-
Page 24
ARC CHUTE
ASSEMBLY
ARC CHUTE
LOWER FLASH SHIELD
CHARGING MOTOR
MAIN MOVING
CONTACT SPRING GUIDE
nci -:::i
SOLENOID COIL
SHUNT TRIP TYPE B
SOLENOID COIL
ANTI-SINGLE PHASE DEVICE LIMIT SWITCH
SHUNT TRIP TYPE A
UNDERVOLTAGETRIP
SHUNT CLOSE
SECONDARY CONTROL CONTACTS
i.'•o "i
IP I O N E E R
K'^SISIvF .t^-iii-ilr-'^-'ai:--;--
•r.
»
USD Solid State Relay
Description
The USD overcurrent protection
package is comprised of a 3 phase
USD relay, current sensors and a
high input energy direct acting
solenoid type shunt trip. In the
case of a 3 phase 3 wire system
3 sensors are mounted in the
breaker. On a 3 phase 4 wire ZSIP® co-ordinated protection mode,
solidly grounded system a fourth Selectivity between main and increasing service continuity.
sensor is required for ground feeder breakers is conventionally
obtained by using time ZSIP® is available on the short time
fault protection. and ground fault elements of the
co-ordinated trip devices, with the
device furthest downstream set for USD relay.
Available Relay Models
There are two basic types of USD minimum time delay. The
disadvantages of this method are Local and Remote Indication
relays, the USD-3 and the USD-6. Local indication is by long-life
The features of these relays are that fault levels increase in zones
closer to the main breaker and the LED's on the relay faceplate while
listed below.
time to clear these faults increases. remote indication is facilitated
The power system must withstand through a set of dry contacts which
these high fault current levels until can be connected to remote
Reiay Features
the time delay on the first device annunciating or alarm devices.
USD-3 Long Time, Short Time 120 volt a.c. 2.5VA control power
and Instantaneous. upstream of the fault expires.
is required.
USD-3IR As USD-3 -r local With ZSIP® the trip device that
indication and contacts
senses a fault in its zone of
for remote indication.
protection trips instantaneously,
USD-6 Long Time, Short Time with
ZSIP, Instantaneous and
minimizing system damage.
Ground Fault with ZSIP. The USD relay also sends a
USD-6IR As USO-6-f local restraint signal to all upstream
Indication and contacts
for remote indication. devices and causes them to
operate according to their time
USD Solid State Relay
USD Relay Models Figure 2 — Remote Indication and ZSIP Connections for USD-6IR
s
n n <0 S •
USD RELAY
Q 6 O Q
CO (A CO CO
Characteristics 3 3 3 3
OPENING ON LEFT
HAND SfOE OF RELAY
LongTime , • • •
Elements
CONNECTOR HARNESS
Short Time CATALOGUE NO. USO«((U4
Elements • • COLOUR CODED IS OA. WIRES
without ZSIP*
TYPE TEW. 600V INSUt IDS CU
AU WIRES ARE LOOSE ANO
7S CNCMESLONG. 1
Short Time
Elements • •
with ZSIP*
0
Instantaneous , • • •
Elements
PROMT VUW
Ground Fault
Elements • •
with ZSIP*
piNNa coioua
OfWKtt
Local and Remote • •
CONTROL POWER
Indication IJOVSOHtZSVA
N
0
0
local indication, remote indication plated contacts are used on the
and the Zone Selective thumbwheel switches for selecting
C
0 Instantaneous Protection (ZSIP) is settings, assuring long lasting
Mutrwicsor
0 0 accomplished by means of a colour positive electrical performance.
4 A 0
coded wiring harness. The harness
is attached to a 10 pin connector
that plugs and locks into the left
hand side of the relay enclosure.
MC This connection is shown in
unvNTsiucnoH
Figure 2.
3 I USD Solid State Relay
"drifting" in service.
MONTTOR t
C.F.
PtCMJP
Long Time BYPASS OLY
C9S0 10 J911
tripping, investigation is required CSD4 0499
0900
90
lie
.110
.199
01009 199 M
CSO>t9 01309 339 MS
01M9 919 430
840
JB30
200
Shunt Trip . - , ,
The high input energy direct acting
shunt trip is a cylindrica! solenoid
which is mounted in the circuit
breaker in such a way that the
plunger is held in the reset position
by gravity. The USD relay, while
operating in the trip level, provides
a pulse with an initial voltage of
140V. When this trip pulse is
supplied to the solenoid, the
plunger travels free striking the trip
lever of the air circuit breaker.
ipi
Relay Testing
The USD Relay has a test plug
mounted on the faceplate which is
used to connect a (type DDT-USD)
Test Set or a metering device in
order to run a complete
operational test on the relay. This
unit also checks the output tripping
energy provided by the relay to the
shunt trip. The Test Set is plugged
Figure 6 — Current Sensor Size and Ampere Taps into a convenient test plug
provided on the faceplate of the
Sensor Taps Federal Pioneer Breaker Frame
relay. The pinout of this test plug is
Type Available
as follows:
CUD-1.5 100.150 600A 30H-3. 62H-3
800A 30H-3, 42H-3
1600A 50H-3, 65H-3 Pin Signal
2000A 50H-3, 6SH-3
Overcurrent Signal
CSD-6 250,400. 600 600A 30H-3. 42H-3
800A 30H-3. 42H-3 Ground Fault Signal
1600A SOH-3. 65H-3
2000A 50H-3, 65H-3 Ground Fault Positive Input
Special Applications
The USD relay can be modified to
suit custom applications. For
further details consult Federal tia25m:.=ii.
the USD-3. Time delays in all cases compartment for test leads and a the required amount of energy
are the same as the regular USD carrying handle, and is capable of when given the signal to do so by
relay. checking all facets of the relays' any of the four elements. The test
operations. The Test Set contains a set has a built-in feature to monitor
Long Time Version current source and the logic the trip capacitor voltage and give
The USD relay is available with circuitry which performs the test indication of a LOW TRIP during
only long time pick-up under the functions. The digital readout the Overall Time Delay Test.
catalogue number USD-LT. The display selection switches and all
long time pick-up levels and time controls are mounted on a fully
delays are the same as those on labelled front panel.
the regular USD relay. This relay The Test set operates by delivering
will not provide any instantaneous a momentary 70 amp (14 per unit)
or short time protection. It is also secondary injection current to the
available with local and remote relay, thereby allowing the
indication under the catalogue complete testing of the
number USD-LT-IR. instantaneous element To allow
accurate calibration testing of the
pickup settings on all elements, the
current source of the Test Set is
controlled to provide three output
ranges with metering from 0.2 per
unit to 14 per unit.
USD Solid State Relay
g g s ssgsii
cutvcs
lOMC 1IMI
SHORT TtMT
INfTANIAKfOlJS
CROUNO UUIZ
lONCTIMI CURVfS
MMC
i.iNoiCAnovAiuu
The USD relay is the brains of the H'3 UKC
RlnUUNTTlMTDtUV
ATOTlMlSSfNSORTAP
breaker. U SIC
3. PtC«UPATeiA,0.9.«4.
».t.l.e.*UT{MtS
SfNSOtTAP
I. MSSICtfPUSINTS
TIME DEUT AT « TIMES
SENSOR TAP.
2. PtCKUPAT2.3.4,«,0.
t A POOIfl 20 M 40 SOgRSr o
F EDS R A1. 1
Federal Pioneer Limited P 1 O N E e r|
initQxajiuKsit
Parts Information
Type H-3/HL^3 Circuit Breakers
lecommended Spare Parts
le H-3 Circuit Breakers
6SH-3(1600/2000A)
NOTE ADDITIONAL SPARE PARTS FOR BREAKERS ELECTRICALLY OPERATED ARE LISTED ON PAGE 2
FPE circuit breakers are subject to continuous product improvement which may result in minor part changes. To ensure that the correct parts
are supplied, it is essential that complete nameplate data be provided, especially the serial number, when spare parts ate ordered.
2/86
NEW ISSUE FEDERAL PACIFIC
RELIANCE ELECTRIC
ULASS 0O125P
Parts Information
lype H-3/HI^3 Circuit Breakers
Recommended Spare Pai
lype H-3 Circuit Break^
41A-504D 6 41A-504D 6
Arc Chute Assembly
13A-S66B 6 13A-S12 6
Arc Chute Lower Flash Shield
182A-40A-1 1 182A-40A-1 1
R.H. Front Flash Shield
182A-41A-1 1 182A-41A-1 1
LH. Front Flash Shield
49E-552 6 49E-SS2 6
Moving Arcing Contact
49E-551 6 49E-651 6
Stationary Arcing Contact
6 4gE-623 6
Upper Stationary Main Contact (Hxed) 49E^9
49E-548 6 49E^23 6
Upper Stationary Main Contact (Orawout)
49E-5S0 6 49E-624 6
Center Stationary Main Contact
49E-519 12 49E-S03C 12
Main Orawout Contact Assembly
49E-575 36 49E-S75 36
Main Moving Contact (Wafer Assembly)
241B-532 6 241B^32 6
Spacer for Wafer Assembly (Outer)
241B-533 38 241B-633 36
Spacer for Wafer Assembly (Inner)
242A-520 72 242A-S20 72
Main Moving Contact Spring
Main Moving Contact Spring Hoider 55B^2 6 SSB^ (Inner) 6
55B^ (Outer) 12
13A-578C 2 13A-S78C 2
Interphase Barrier
13A-172A-1 2 13A-172A-1 2
End Barrier
27A-500 6 27A-600 6
Main Braid
FPE circuit breakers are subject tocontinuous product improvement which may result in minor part changes. To ensure that^ecorrect parts
are supplied, itisessent'el that complete nameplate data be provided, especially the serial number, when spare parts are ordered.
2/6<
FFiE FEDERAL RAOFIG NEW ISSU
RELIANCE ELECTRIC e 1985 Federal l^cilic Electri
PRINTED UN US
CLASS 602SP
Parts Information '(elUXSl
SOHL-3 (1600/2000A)
30HL-3 (800A)
PART QUANTITY
QUANTITY
NUMBER PER BRKR
description NUMBER PER BRKR
41A-504D 3
41A-S04D 3
13A-566B 3
Arc Chute Assembly 13A-566B 3
1
182A-542B
Arc Chute LowerFlash Shield 182A-542B 1
3
Front Flash Shield 3 49E^52
49E-S52 3
Moving Arcing Contact 3 49E-551
49E-551 3
Stationary ArcingContact 3 49E-668
4gE-567 3
Upper Stationary Main Contact 3 49E-650
49E-577 12
Center Stationary Main Contact 6 49E-573
49E-130 18
Main DrawoutContact Assembly 12 49E-575
49E-575 3
Main Moving Contact (Wafer Assembly) 3 241B-532
Z41B-532 18
Spacer for Wafer Assembly (Outer) 12 241B-533
241B-533 36
Spacer for Wafer Assembly (Inner) 24 242A-520
242A-521 6
Main Moving Contact Spring 6 558-502
55B-502 2
Main Moving ContactSpringHolder 2 13A-574C
13A-574C 1
Interphase Barrier 1 13A-675C
13A-575C 1
R.H. End Barrier 1 13A-576C
13A-576C 3
I M PnrI Barrier a 27A-500
100HL-3 (40C0A)
75HL-3 (3000A)
PART
QUANTITY
PART
QUANTITY
NUMBER PER BRKR
DESCRIPTION NUMBER PER BRKR
41A-504D 6
41A-504D 6
13A-612 6
Arc Chute Assembly 13A-566B 6
1
Arc Chute Lower Flash Shield 1 182A-40A-1
182A-40A-1 182A-41A-1 1
R.H. Front Flash Shield 182A-41A-1 1
6
LH. Front Flash Shield 6 49E-5S2
49E-552 6
Moving Arcing Contact 6 49E-551
49E-551 6
Stationary Arcing Contact 6 70.12J013B.1
49E-569-1 6
L.H. Upper Stationary Main Contact 6 70.12X)13B5
49E-569-2 6
R.H. Upper Stationary Main Contact 6 49E-624
49E-550 12
Center Stationary MainContact 12 49E-509C
49E-519 36
Main Drawout Contact Assembly 36 49E-575
49E-575 6
Main Moving Contact (Wafer Assembly) 6 241B-532
241B-532 36
Spacer for Wafer Assembly (Outer) 241B-533 36 241B-S33
72
Spacer for Wafer Assembly (Inner) 72 242A-520
242A-520 6
MainMoving Contact Spring 6 55B-504 (Inner)
55B-502 12
Main Moving ContactSpring Holder S5B-S05 (Outer)
13A-578C 2
13A-578C 2
13A-172A-1 2
Interphase Barrier 13A-172A-1 2
6
End Barrier 6 27A-500
27A-500
Main Braid
notes:
2/86
FEDERAL FACFIC1
RELIANCE ELECTRIC m
NEW ISSUE
f-iryAUjiyfe.!!,
Parts Information
type H-3/H1^3 Circuit Breakers'
Part IdentificatiM
Type H-3 Circuit Breai"'
2000 AMP
Arc Chute Asscably 22. Handle Atseably 43. Centre Stationary Main Contact
Interphese Barrier 23. Close Lever 44. Hain Hoving Contact (Wafer Assyi
ft.H. End Barrier 24. Close Latch 45. Upper Stationary Ham Contact
L.H. End Barrier 25. Trip Rod Atseably 46. Closing Link Asseably
2i. Spring Guide Pin 47. Braid
Front Flash Shield
Closed-Open Link 27. Closing Casting 48. Wafer Contact Spring
Crank Asseibly 28. Closing Pin 49. Spring Holder
Crank Bos 29. Tie Rod Atseably 50. Hoving Arcing Contact
Crank Bos Bearings 30. Closing Shalt 51. Stationary Arcing Contact
Holding Panl 31. Hain Spring 52. Load Terainal
Ratchet Wheel 32. Guide Bushings 53. Anti-Bounce Plate
Oscillating Lever • 33. Claap Asseably 54. Base Houlding
Clutch 34. Breaker Fraae 55. Trip Flipper
Charged-Oischarged Link 35. Trip Shaft 56. Trip Coil Asseably
Closed-Open Button 36. Trip Latch 57. Loaer Channel
Charged-Oischarged Button 37. Latch Bearing 58. Finger Spacer
Front Plate 38. Leaer Houlding 59. Drauout Contact Asseably
Indicator Plate 39. Sensor Hounting Bracket 60 SLS Caa
Faceplate Bo> Atseably 40. Barrier 61. Ground Stab
20 Floating Trie 41. Sensor 62. Loner Flash Shield
21 Faceplate Atseably 42. Juaper
• not shonn
2/
RELIANCE ELECTRIC
os.Maiof ov^eof
lrTO(aMSS£
Parts Information
Type H-3/HLp3 Circuit Breakers
tart Identification
lf^HL-3 Circuit Breakers
14X16
1 0.] -a
Tcrria
1. Arc Chute Actiably 24. Close Latch 46. Closing Link Assenbly
2. Interphise Berritr 25. Trip Rod Assenbly 47. Braid
3. R.H. End Barrier 26. Spring Guide Pin 48. Haler Contact Spring
4. L.N. End Barrier 27. Closing Casting 49. Spring Holder
5. Front Flash Shield 28. Closing Pin 50. Moving Arcing Contact
6. Closed-Open Link 29. Tie Rod Assenbly 51. Stationary Arcing Contact
7. Crank Assenbly 30. Closing Shalt 52. Load Terninal
S. Crank Boi 31. Main Spring 53. Anti-Bounce Plate
4. Crank Bos Bearings 32. Guide Bushings 54. Base Houlding
10. Holding Paul 33. Clanp Assenbly 55. Trip Flipper
11. Ratchet Wheel 34. Breaker Frane 56. Trip Coil Assenbly
12. Oscillating Lever • 35. Trip Shalt 57. Louer Channel
13. Clutch 36. Trip Latch 58. Finger Spacer
14. Charged-Oischarged Link 37. Latch Bearing 59. Orauout Contact Assenbly
15. Closed-Open Button 38. Louer Houlding 60 SLS Can
16. Charged-Discharged Button 39. Sensor Mounting Bracket 61. Ground Stab
17. Front Plate 40. Barn.ier 62. Louer Flash Shield
IB. Indicator Plate 41. Sensor 63. Line Side Bar
If. Faceplate Bos Assenbly 42. Junper 64. Line Side Terninal
20. Floating Trin 43. Centre Stationary Hain Contact 65. Fuse
21. Faceplate Assenbly 44. Main Moving Contact (Haler Assy) 66. Interphase Barrier
22. Handle Assenbly 45. Upper Stationary Hain Contact 67. R.H.6 L.K. Orauout Wheel Assy
23. Close Lever
* not shoun
FEDERAL mClFIC
RELIANCE ELECTRIC
Parts Information
Type H-3/HL-3 Circuit Breakers
Recommended Spare Part^
•Y
V-'
MAIN DRAWOUT
CONTACT ASSEMBLY
(800 Amp)
MAIN DRAWOUT
CONTACT ASSEMBLY
MAIN DRAWOUT (4000 Amp)
CONTACT ASSEMBLY
-f.
(1600, 3000 & 3200 Amp)
•V
,V'
MAIN DRAWOUT
CONTACT ASSEMBLY
(2000 Amp)
ftM
•. -r.
MOVING ARCING
STATIONARY ARCING
CONTACT ASSEMBLY
CONTACT ASSEMSJv
FEDERAL PACIFIC f f
RELIANCE ELECTRIC mB
Parts Information
Type H-3/H1^3 Circuit Breakers
Recommended Spare Parts
ARC CHUTE
ASSEMBLY
ARC CHUTE
LOWER FLASH SHIELD
MAIN
BRAIDS CHARGING MOTOR
MAIN MOVING
CONTACT SPRING GUIDE
'W 62cr
SOLENOID COIL
jp-^T TRIP TYPE A SOLENOID COIL
K (VOLTAGE TRIP SHUNT TRIP TYPES
SHUNT CLOSE ANTI-SINGLE PHASE DEVICE LIMIT SWITCH
2/86
NEVV ISSUE FEDERAL PACIFIC
HeUANCE ELECTniC
CLASS 602SP
pro(sj
©aitii Parts Information
Type H-3/HL-3 Circuit Breaker
Recommended Spare Pa
Federal Pacific / 2500 Blue Ridge Road / Raleigh. North Carolina / 919-783-100(
FEDERAL PACIFIC f*
RELIANCE ELECTRIC MM
!N-820.4A
INSTALLATION, OPERATION AND
MAINTENANCE INSTRUCTIONS
FEDERAL PACIRC
METAL-CUD SWITCHGUR
JANUARY 1972
^.1
-"5!
fex..
•^:-
,...
•0:
•A
r\
INDEX Page
Part I. General
Features
Shipment
Inspection
Moving and Lifting
Storage 4
Foundation 4
Part 11. installation
Housing 5
Inspection 5
Assembly A—Protected Work Aisle 5
Assembly B—Center Aisle 6
Assembly C—Non-Walk-in 6
Tightening Connections 6
Bus Duct 6
Additions to Existing Equipment 6
Equipment
Batteries I
Wiring 1
Grounding I
Fuses I
Dummy Breaker I
Insulation
Taped Connections 12
Ground Fault CT Terminations .12
List of Illustrations
Figure 1—Lifting Gear—21 feet and Under (Dwg. 2200C0I66) 2
Figure 2—Lifting Gear—Over 21 feet (Dwg. 220OC0I67) 3
Figure 3—Installation of Floor Channels—Indoor 4
Figure 4—Installation of Floor Channels—Outdoor 4
Figure S—Table A—Recommended Torque Values 6
Figure 6—Base Assembly (Dwg. 220OC0I68) 7
Figure 7—Outdoor Protected Work Aisle Construction
(Dwg. 2200DOI69) 8
Figure 8—Outdoor Center-Aisle Construction
(Dwg. 22C0DOI70) 9
Figure 9—Base Connections and Cell Bolting
(Dwg. 2200C0I7I) 10
Figure 10—Additions to Existing Units (Dwg. 2200C0172) 10
Figure 11—Boot Installation 12
Figure 12—Taping Instructions ; 13
Figure 13—Table B—Dielectric Test Values 14
1. Switchgear Housings and DST-2 Air Circuit Breakers REMOVAL FROM CARRIER AND
are jig constructed in alignment flxtures to assure INSPECTION FOR DAMAGE
interchangeability of breakers. Compartmentalized Immediately upon receipt of the shipment, identify all
construction segregates the circuit breaker, main component parts and check them against the shipping
bus, current transformers, potential transformers, list. Make a thorough examination to detect any dam
and control power transformers. age which may have been incurred during transit
2. Complete interlocking between tha cell and circuit If any dama^ is discovered, file a claim immediately
breaker provides safety to personnel and equipment with the carrier, and send notice of the extent of the
by prevention of incorrect operating procedure; damage to the Federal Pacific Electric Company plant
from which shipment waa mader giving complete-iden
3. Equipment is-designed to reduce installation time, tification, carrier's name, and railroad car number if
and to comply with ANSI Standards C37.20. the shipment was made by rail.
The information will enable the company to supply
OUTDOOR:
necessary information in support of claim.
4. Equipment is constructed so that additional
sections may be readily added in the fleld. MOVING AND LIFTING SWITCHGEAR^
1. It is extremely important that care be taken in
5. Protected work-aisle provides ample space for a
handling, rigging, hoisting, rolling, or moving
scheduled maintenance program regardless of
assembled switchgear into place. Metal-clad switch-
weather. Breakers draw out into aisle with suflicient
space for interchangeability. The service area is ven- gear isdesigned to be bandit only inan upright posi
tUated, waterproof, and adequately lighted; service tion and should never be handled in any other way
receptacles are provided. without first consulting with the Switchgear Engineer
ing Department.
6. The undercoated structural foundation supports are
2. Each shipping section of indoor switchgear is bolted
designed to be self-contained making it necessary
to support foundation steel only. This design permits to a heavy shipping skid which- should remain with
the gear until it is moved into final location. Each
elevating switchgear on supporting structures and
thereby reduces flood hazards.
section of outdoor gear is supplied with heavy lift
ing lugs bolted to the switchgear base.
7. Outdoor finish: Three-coat system consisting of a
3. When lifting shipping units with a crane, it is prefer
zinc chromate primer, an intermediate coat, and a
final ASA-24 dark*gray exterior coat. able to use two hooks simultaneously, one on each
end. Each pair of lifting hooks should be equipped
SHIPMENT with a spanner bar to prevent excessive distortion.
If only a single hook crane is available, arrange
The switchgear is assembled, wired, adjusted and given
complete tests at the factory, after which it is inspected spannerfs) to lifting rig as shown on typical outdoor
and packed for shipment, llie air circuit breakers are gear lifting drawings 2200C0166 and 2200CX)167.
not shipped in the switchgear compartments, but are (Figures 1 and 2).
packed in separate crates. Each crate is identified, and 4. When cranes are not available, equipment can be
a complete list of its contents is included in the shipping rolled into place on shipping skids (indoor) or steel
papers. All instruments and relays are suitably blocked base (outdoor) provided with each shipping section.
as required to prevent damage to bearings and move Pushingor pullingforces should beapplied to the skid
Pv ments.
To
FIGURE 1
o o o
x>
CELLS(2|-0. LG.
recommended method
AND OVER) AND of LIFTING
ALL WORK A|SLE SECTIONS FPE DWG. NO.
2200C0I67
FIGURE?
^ STORAGE BEFORE INSTALUTiON Breakers should be prepared for storage separately.
Protection against loss of equipment is an important Refer to appropriate breaker instruction book.
precaution. Trouble and delay will be avoided by hav FOUNDATION
ing good storage facilities arranged so that the appa Federal Pacific Metal-Clad Switchgear is accurately
ratus will be accessible only to authorized persons and built on true and level betlplates. This care and accuracy
so that it can be quickly located when required in the insures ease of operation and interchangeability. Equal
erection program. care during installation should be used.
Switchgear equipment, regardless of whether it is to be True and level supports for this equipment are ofutmost
installed immediately or stored for a while before being importance. Little more than ordinary care in laying out
erected, should be kept in a dry, clean place. Conditions arid preparing the foundation will be repaid in reaction
of cost and labor of installation.
such as dampness caused by rain or change in tempera
ture, cement dust, etc., should be carefully gturded
The steel supporting members Used in the floor should •
against. Covering the equipment with a temporary be held level until the concrete is set. The surface of the
shelter or tarpaulin is frequently necessary both during floor under the housing should not project above the
storage and erection. The longer the period of storage, supporting members. For indoor switchgear only, the
the greater must be the care taken for protection of the ^rface ofthe floor should not lie below the supporting
equipment. If dampness or condensation may be en ^embers by more than 'A'.
countered in the storage location, heaters should be *Thefloor infrom ofthe housing should not very more then W in ony
placed inside the units to prevent moisture damage. squareyardandtmsantAptosfisX.ehovt the level ofthestqiportingmem-
Approximately 600 watts of heaters per unit will be re bers. A smoothfloor'willmake rolling ofthe removable element easier.
quired. Remove all cartons and other miscellaneous *Wheninstallingswitchgearwherefloors alretidyexist, it will usually be
desirable to pour a newfinishedfloor above with embedded channels
material packed inside the units before energizing any or cut slots for embedding and leveling the supporting channels.
heaters. If the equipment has been subjected to mois Encircling loops of reinforcing or building steel aroimd
ture it should be tested with a lOOOV or 2500V megger single phase conduaors should be avoided in the main
after heaters have been turned on for approximately one cableentrancearea ifthese are rated 600amperes orabove.
week. A reading of at least 100 megohms should be FIG. 3 or an equivalent must be used to obtain an ade
obtained. - quate foundation. Bolting the switchgear to the foimda-
Batteries should be uncrated and put on trickle charge tion is an acceptable method. Welding to the founda
.immediately on receipt. tion is preferred because it does not require an accurate
Relay covers should never be left off since the relays are lining up of holes.
%delicate devices and future malfunctions because of mois FIG. 4 or an equivalent must be used to obtain an ade
ture arid dust oould prevent proper tripping of circuit quate foundation for outdoor equipment. Welding to
breakers. the foundation is the preferred method of securing.
*For indoor switchgear only.
SWITCHGEAR BASE
WELD HERE
FIGURE 3 FIGURB4
PART 11 - INSTALLATION
HOUSING ASSEMBLY "A**: OUTDOOR PROTECTED
WORK AISLE CONSTRUCTION
INSPECTION (See dwg. 2200D0169.)
1. Before setting equipment in place, refer to switchgear 1. Locate the cell sectionsaccurately on the foundation.
When cell equipment is in two sections, locate the
drawings and, after completely uncrating equipment,
sections from the center of the foundation.
check permanent location to see that equipment will
properly fit on channels and foundation location. Align 2. Check the leveling of the units; use shims where foun
and bolt all shipping sections together so that a con dation is uneven. Remove lifting lugs.
tinuous switchgear installation is obtained. (Refer 3. When cells are in two sections and the above are pro
to Assemblies "A", "B", and "C below.) perly leveled and aligned, firmly bolt the bases,
2. Carefully inspect all portions of the circuit, breakers cells, and roofs together with the hardware furnished
for posable damage. SkV 250 MVA-circuit breakers for this purpose.
are shipped completely assembled with arc chutes. 4. Aisle Section:
15kV and SkV 350 MVA circuit breakers are shipped A. When aisle section is in one piece, remove ail
separate from arc chutes and may be assembled protective lumber and bracing except wooden
properly in the protected work aisle and center aisle horizontal and center vertical braces. Remove
outdoor houses by use of the arc chute lifting bracket lifting lugs. ,
attached to the aisle ceiling. After inspection, the B. When aisle section is in two pieces, remove all
circuit breakers should be carefully inserted and protective lumber and bracing from each section
racked into the switchgear cells. except wooden horizontal brace, wooden vertical
comer and vertical center brace, and open end
3. Remove shipping braces, inspect for damaged parts, wooden frame bracing. Remove lifting lugs.
cracked epoxy bus, primary disconnect btishings,
bent secondary disconnects, cracked porcelain, in
sulators, wiring insulation — check and report evi
WARNpiG: UNDER NO CONDITION MAY
dence of abuse to equipment. THE WOODEN HORIZONTAL ROOF SUP
4. Inspect cells to be certain that power contacts and PORT BE REMOVED BEFORE ITEM 5 BELOW
secondary disconnect contacts located in rear of cell IS COMPLETED.
are free ofdirt and dust. Cell floor must be clear of all
dust and debris to facilitate easy handling of circuit
breaker.
5. The breaker is provided with a maintenance closing
5. Slide aisle section(s) into place, making sure that
aisle roofs overlap cells and reston top of cell roofs.
device for manually closing the breaker. It cannot be Aisle side sheets must be'on outside of cell sections.
used as a manual device to close in the breaker when
in the cell. This handle should be used only when the 6. When aisle section is aligned with the cell portion,
breaker is withdrawn from the compartment. apply caulk (furnished) between overlapping roof
and sidesheet surfaces. Firmly bolt bases, roof, and
6. Refer to the circuit breaker Instruction Manual
lN-820.11 before inserting breakers into cells.
Si^e sheets together and apply cement (furnished) to
roof gasket joints. ' '
7. If porcelain entrance or load bushings are mounted 7. Remove existing wooden braces.
in the roof, use flexible connections from incoming
and outgoing lines to reduce the strain on the por 8. Remove floor plates at ends and at base anchor
celains. ing points.
9. Fasten aisle base to cell base. (See dwg. 22(X)C0171,
8. Inspect all instrument doors for damage to protective
Figure 9).
relays.
10. Tackweld or anchor the bases to the foundation as
Control-wiring underground conduit from the control indicated on the floor plan drawing.
building should terminate inside the switchgear at a level 11. Re-install floor plates.
above any existing high-water marks (4" maximum
above floor line). 12. Check and adjust instniment doors for proper align
ment to correa possible mishandling during shipment.
Heaters are furnished in front and rear of each outdoor
unit. 13. Complete the assembly of the main and ground
buses (when required) by inserting the sections
The followingdescriptions and drawings give the general shipped loose for the shipping breaks. (Tighten the
ft arrangement, sequence of installation, method of fas
tening the gear to the foundation, location of conduit
bus bar connections per Table **A" on page 6.)
Assemble the PVC boots around the main bus joints
areas, and other information for the proper location and fasten together with the nylon hardware fur
and a&sembly of the equipment: nished. ($ee instruction page 12.)
G
14.Re-connect ^wiring at shipping breaks and where All joints in the bus should be assembled and insulated
required per wiring diagrams furnished. as described above for main buses. Adjustable joints
are provided to allow for variations in building construc
NOTE: tion, etc. These joints should be loosened before installa
A. Customer control wiring connections must be tion ofthe duct, then tightened after being set in the posi
terminated at terminal blocks only — no splicing tion required by the flxed points at the ends ofthe duct;
is permitted. Outdoor bus duct must be gasketed at the joints between
B. Allwiringin conduits must be in accordance with shipping sections.
National Electrical Code. All removable covers on outdoor bus duct except bottom
ASSEMBLY^B": OUTDOOR CENTER coversmustbe gasketed.Do not bolt covers in place until
AISLE CONSTRUCTION all interior assembly work on the duct is completed and
.1.Complete items 1, 2, 3, 10, 12, 13, and 14 per access will no longer be required.
assembly "A" above. Outdoor bus duct of the 13.8 kv class are provided with
2. Bolt aisle-end channels in place. heaters. Connect these heaters in accordance with the
. 3. Install floor plates.
wiring diagrams furnished with the equipment before
energizing the bus duct.
4. Assemble end panels of the aisle section.
5. Assemble aisle roofs and seam gaskets.
6. Apply caulk (furnished) between overlapping roofand ADDITIDN OF UNITS TO
side sheet sumces. Firmly bolt roofs and side sheets EXISTING EQUIPMENT
together and apply cement to roof gasket joints. Beforeadding units to existing equipment, consult and
•7. Check and adjust instrument doors for proper align- study all drawings furnished with the equipment. In
mentrtocorrect possible mishandling dunng shipment addition to the usual drawingsfurnishedwith nw equip
ment, specialdrawings may be furnished covering com
ASSEiyiBLY'"(r:t)UTDOOR plicated or special assembly work. Ako, checkto make
NON^WALK-IN CONSTRUCTION sureall necessary parts are«n hand.
1.Complete items1,2,3.10,12,13 and 14per assembly BEFORE ANY COVERS ARE REMOVED OR ANY
^A" above. DOORS OPENED WHICH PERMIT ACCESS TO
THE PRIMARY CIRCUITS, IT IS ESSENTIAL
TIGHTENING CONNECTIONS THAT THE CIRCUIT OR CIRCUITS BE DE-ENER
1. Bus splices at shipping break should be carefully in GIZED AND BREAKERS BE WITHDRAWN TO A
spect to becertain that good clean, uncontammated DISCONNECTED POSITION AND TAGGED.
contact is obtained before bolting up tight. A torque
wrench should be used. IF WORK IS TO BE DONE ON REMOTE EQUIP
2. It is also important to be sure that all outgoing-cable MENT CONNECTED TO A UNIT THE BREAKER
connections ^re tightened in the same manner as FOR THAT UNIT SHOULD BE PLACED IN THE
bus splices. DISCONNECTED POSITION ANDTAGGED. ALSO
TABLE A THE REMOTE EQUIPMENT SHOULD BE ISO
RECOMMENDED TORQUE LATED FROM ANY OTHER POWER SOURCES
CONNECTED TO FT.
(Values in Foot Pounds)
Type Bolt Steel* Everdur
Dwg. No. 2200C0172 (Figure 10) indicates the special
i/lb'-lS 18 15 procedures required to add new inetal-clad units to out
3/8M6 31 21 doorequipment with protected aisle. For indoor equip
ment it is usually necessary only to remove the end
l/2''-13 55 45
cover sheets and to re-assemble them on the new units
S/S'-Il 80 65 after these are located and bolted to the existing units.
'••Steel hardware must be SAE 5 or stronger. Otherwise, the installation procedure is the same as
FIGURES described in Part 11.
BUS DUCT
Busduct connectingbetweengroupsof metal-clad switch- When the units are in place and mechanical assembly is
gear, or between metalclad switchgear and other ap completed, assemble the main bus and other primary O
paratus, should be installed as shown on the arrange connections. Secondary wiring and control bus con
mentdrawings furnished with the duct. Supports should nections should be made in accordance with the wiring
be provided as indicated on the drawings. diagrams furnished with the equipment.
V J
-CONTROL CONDUIT
I5KW—H»KVh
FRONT POOR^ ^
.REAR DOOR >1 "TT 'ri ''TTI^REAR DCiOH
•D _ li! 1J .11I I I l_l-l».E,
If COHOOII
I LEVEUN^HANNEL-
OR *rBEAM
CONCRETE CURBS
tSila u53
OR PADS
SPECIAL CANTILEVER MOUNTING NON-WALK-IN
INSTRUMENT
pOOR
FRONT MNa REAR DOOR
NOTES AISLE FLOOR CELL FU»R
FOR SHIPPING SECTIONS AND SPECIAL
H0UNTIN6 DIMENSIONS SEE.JOB OWGS
AND FLOOR PLAN AISLE BASE CULBASE
N •INSTRUMENT DOOR-
1
! ltl
rA AISLE BASE
f
CHANNEL SUPPORT
F|6URP§
)
IMPORTANT NOTE; *
NOTE I: ONE PIECE AISLE SHIPPING SECTION
- 00 NOT REMOVE WOODEN HORIZONTAL AND CENTER VERTICAL
ROOF BRACES UNTIL AISLE ROOF OVERLAPS AND RESTS ON SWITCHGEAR ROOF
CAULK
MOTE 2: SPLIT AISLE SHIPPING SECTION
DO NOT REMOVE WOODEN HORIZONTAL.VERTICAL CORNER
AND VERTICAL CENTER BRACES i AND OPEN END
•WOODEN FRAME BRACING UNTIL AISLE ROOF OVERLAPS NOTE:APPLY CAULKING COMPOUND TO ALL
AND RESTS ON SWITCHGEAR ROOF BUTTING AND OVERLAPPING JOINTS
Vi-itx i'u.*atr t
MAUM MSMII
WOODEN
HOnZONTAL
ROOF BRACE MTU CEMtNT
V«-nxru.aotrt
WALHCWMn
MSU
ROOT
MXMAU iOtf
SWITCHGEAR
SECTION
X i.ztu.ieLT
hoURET
o
3
iSXI'l&Mf A
SEALMO WASKtR
ARPLY- "^swItchcearroof
CAULKIHO
COMPOUMO
AISLE ROOF
ROOF A^EMBLY iixusiAooa
N07E:AmV UULKiN& COMPOUKD TO ALL
OUTOOOA ROOT lUTTiNO AND OVCALAfRlNG JOtMTR
MSKET
(USLC)
AISLE OOOR
FRAME ASSEMeUr
fIDEAHCET
AISLE EXTENSION
UOE SHEET
AISLE OOOR
fLOOR PLATES
SWITCHGEAR SECTION
FffiURES
-|h6Xs'lg. hex hd. bolt
LOCK 4 nM WASHER ^-Z0X.79LG.HEX HD.60LT
LOCKWASHER A HEX NUT
CELL SIDE SHEET
14 HEX NUT (WCLOCO)
CELL— REAR FRAME
UPRIGHT UPRIGHT
FIGURES
-fWSTING ROOF-
TTTTym?
FIGURE 10
10
EQUIPMENT
BATTERIES nection is necessary for every switchgear. installation.
A poor ground may be worse than no ground since it
Follow batteiy manufacturer's instructions carefully gives a false feeling ofsafety to thoseworking aroundthe
when installing the battery. Be sure that ventilation is - equipment. It ^buld also be of sufficient capacity to
provided to carry off the fumes. If steel work seems to handle any abnormal condition that might occur on the
be affected by the fumes, apply black asphaltum paint system and should be independent of the grounds,used
Make sure that the battery charger is functioning, and for any other apparatus.
that the charging rate is not excessive. Test for specific
graviQr regularly. CONTROL CIRCUIT FUSES
If battery is installed remote from the switchgear, have FPEECON* CLASS 1330 ^
cables of sufncient size to keep the voltage drop at a DUAL ELEMENT CONTROL CIRCUIT FUSES
minimum. 100,000 AMP RMS A.C.
INTERRUPTING CAPACITY
Be sure battery is charged and no abnormal loads are
evident before putting switchgear in service. Catalog #-2S0V Ampere'
WIRING ECN-1 1
All incoming and. outgoing control connections ECN-3.2 , 3.2
should be made i» accordance with the switchgear sche ECN-d.25 6.25
matic and wiring diagrams. Afier wiring is completed,, ECN-10 la
all connections should, be carefully checked against the ECN-15 15
diagrams to insure that all coimections are correct and' ECN-20 2B
proper. ECN-25 , 25-
rs The wiring diagram number of each switchgear unit is
ECN-30 30'
ECN-35 35
stamped on the nameplate of the control panel. The wir 60
ECN-60
ing diagram number applying to each circuit breaker
isstam^ oneach breaker onthe nameplate. These fuses provide instantaneous- protection against
Interconnecting wiring diagrams between the asso short circuits plus a hi^ degree of current limiting
ciated equipment are not normally supplied with metal- ability within the sizes listed.
clad switchgear.
DUMMY BREAKER
GROUNDING Dununy removable elements are used as a means of
Each switchgear assembly is provided with a ground isolating drcuits or bus sections where operation is.in
bus extending the full length of the complete assembly. frequent and a circuit breaker caimot be economically
Sections of ground bus previously discoimected at justified for an interim of time. The deviceconsbts of a
shipping breaks must be reconnected when the units framework to simulate the circuit breaker removable
are installed. element with a set of six studs similar to those on the
«
The ground bus should be connected to the station breakers. The studs are connected by shorting^ bars
ground at both ends with as direct a connection as pos which are fully insulated and metal-enclosed. The sta
sible and should not be run in metal conduit. The tionary structure is the same as for a circuit breaker.
grounding conductor should be capable of carrying the When the device is racked into position, it connects the
maximum line-to-ground current for the duration of line and load side of bus.
the fault Under no conditions must the dummy element be
When switchgear has center aisle construction, insure racked into or out of the cell when the bus or the unit is
that the connecting ground bus is connected between ener^zed. Key interlocks are applied to insure that all
sources of power are dbconnected before the dununy
opposite aisle sections. element can be operated. Floor interlocks are provided
A reliable permanent and low resistance ground con to prevent insertion into specific ceUs.
11
o
INSULATION BOOTS
ON 5 AND 15KV CLASS EQUIPMENT,BUS BAR JOINTS
ARE INSULATED-WITH MOLDEDtBUS BAR BOOTS.
THE BOOT IS:PULLED IN PLACE AROUND THE .BUS
BAR/JOINT. AFTER FITTING, HOLES ARE PUNCHED
FOR CLEARANCE OF THE NYLON HARDWARE.
TAP
1:1 xz
NOTE V
NOTE V
r
1 oi MAIN. .JLl MAIN o|
THRU
I
1
12
D o
) (VARNISH CAMBRIC)
•AT EACH STEP USE S TUIWS OF TA«.
9 DESCAIPTION
l/jNVLPtASTIC ^lOTHK
rwiDex36Y0&. tc.
ftCD ELECTRIC At TAPE
1
ELEaRICAL GLASS
TAPE-MEDIUM WEAVE
M/2*WIDE X.004THK
3
3G YDS* to.
BURLINGTON
'hesgon a'or equal
SECURE BRAIO WITH 2 LAPS
TAPER (PQUrETHYLENE) TAPE U 310 or CAN
AS SHOWN VARNISH
(NOTE 1} 4
STERLING VARNISH
SEWICKLEY.PA.
TYPE 7
TYPE S
BUS-FLEXIBLE CONNECTOR- CABLE TO
*T' BUS & CABl-E TP BUS PORCELAIN TERMINAL
PORCELAIN TERMINAL
TAPING INSTRUCTIONS
FIGURIW
PAItr III - PRE ENERGIZATION TESTS
PREPARATION TABLED
BEFORiE STARTING ANY INSPECTION OR TEST DIELECTRIC TEST VALUES
ING BE SURE PRIMARY CIRCUITS ARE DE- Standard
ENERGIZED. 60 Cycle 60 Cyde Full-Wave
Careful reference should be made to each component Rated KV KV Impulse
instruction leaflet before attempting to place the switch- Voltage Field Test Factory Test (Withstand)
gear in servii%. If dry-type or oil askarel-fllled -power Tests KV
transformers are furnished as part of the switchgear 1.6 2.2 NA-
600 V
equipment, consult their instruaion books or leaflets, 4.16 kV 14.25 19 60
particularly regarding absorption of moisture, and 36 95
7.2 kV .27.0
effects of dust and sand, etc. 36 95
13.8 kV 27.0
The equipmentshould be checked to be certain no tools 23 kV 45.0 60 150
or any other equipment have been left in the switchgear. 34.5 kV 60.0 80 150
When coimections are to be made to or from an electric
HGURE13
utility, public or privately-owned, consult their -repre
sentatives very early in the construction period, as When the switchgear has electrically operated circuit
many of them have very strict requirements which must breakers, they are operated in some installations from
be met before service connections will be made. local battery or auxiliary control supply, and in other
Any indication of moisture will require that equipment installations are operated from the switchgear bus, or
be dried out before placing in service. Care should be a connection ahead of the incoming master circuit
exercised in diying-out operations to be certain that the breaker. In the event the primary source of power is
maYimiim temperature during the drying period does locked open, it will be necessary to use an auxiliary
not exceed70 to 75° C. on switchgear. In the event it is source of power to operate the circuit breakers, lamps,
desired to give the equipment a high potential test be- bell-alarm switch, undervoltage devices, rectifiers,
_ fore placing in service, thb test should only be made capacitor shunt trips, etc. Check circuit breakers in
after the equipment is thoroughly dry. The value of "test" and "operate" positions, paying particular atten
test voltage should correspond to the voltages listed tion to good contact between movable stationary secon
• "inTable B. Note that field tests are 75% of the factory dary contacts in both positions. Check puffer by placing
• test values. hand over arc chute and feeling puff of air during open
ing operation. Check that primary disconnect penetra
tion is at least 14" on cell stabs. Check that breaker
DIELECTRIC TESTS mechanism closing springs discharge between "test" and
Dielectric tests are made at the factory to determine "removed" positions. ' i
the adequacy of insulation. Devices used as part of interlocks should be operated manually to make
switchgearassemblies shall be capable of meeting these sure that protection is complete. Remove spare Iceys to
tests. supervisory office.
Exception — There is certain apparatus such as poten Each relay and trip device or other component should
tial transformers, auto transformers, motor starting, be operated manually to be certain its contacts perform
reactors, and motor-operated devices whose standards their required function. Removeany material that was
call for a lower test voltage than those given in Table B. installed at the factory to block parts or devices during
When such devices are used, they must be disconnected shipment. Preliminary settings for test purposes should
during these tests. be applied to relays. The various operational functions
Altemating<current test voltage shall have a crest value are indicated on the schematics and wiring diagrams of.
equal to 1.41 times the values specified. A sine wave the switchgear equipment.
stepe is TMominended. The frequency shall not be less After completion of all operation tests, all relays
than the rated frequency of the apparatus tested. The should be set according to specified requirements. If a
- test voltage shall be applied for one minute. coordination study has been made this study should be
Direct-current test voltage, if used inlieu ofaltema^g- referred to for thesettings. Check that theprimary d^
current test voltage, shall be 1.41 times the specified vice settings are accepted by the Power Company if
alternating-current voltage. required. All trip indicators on the relays should be
checked to see that they function properly.
Upon completion of device settings and test, the main
OPERATIONAL TESTS incoming and feeder cables should be properly phased
out and connected to the switchgear. Incoming and
Upon completion of installation, and inspection of the
circuit breakers and other components, together with outgoing cables should be braced so as to take mechan O
installation of any incoming and outgoing control con ical strain off studs of circuit breakers and -porcelain
nections, it is time to start operational testing. Outgoing supports of various types. Clean out construction
feeder cables should not be connected at start of test. -materials, dirt, nests,-etc.
14
Inspect for damaged parts, cracked epoxy bus, primary Check proper operation ofdoors, transfer trucks, laches,
disconnect bushings, bent secondary disconnects, filter units, lifting, hinges, key interlocks (keys and
cracked porcelain insulators, wiring insulation — check function), gaskets and seals.
and report evidence of abuse to equipment. On prdtected work aisle and center aisle O.D. house
check that contractor properly assembled and caulked
The entire switchgear structure and all bus duct should the shipping breaks, and aisle split. Check undercoating,,
be carefully vacuum cleaned (preferred) or blown out, foundation, and for rodent holes.
and all rear and side plates that have been removed Check phasing connections of buses (especially at
should be rebolted in place. All secondary ,and power transition points) and connections to transformers and
connections should be tested for grounds with high bus ducts. Capacitor trip device — check operation and
potential tester or megger. Megger readings of one check that it will hold charge at least 5 minutes, by
megohm per thousand volts are acceptable. If readings de-energizing primary power as checking operation 5
are lower, equipment should be dried out until insula minutes later. Spot check-secondary voltages to make
tion resistance values improve to one megohm per sure proper connections and proper transformer iatios
thousand volts. have been selected. Overvoltage can cause premature
burnouts ofindicating lights. Check lamp burnouts.
Preferable readings are:
Check that C. T. secondaries are not open circuits,
Operating voltage KV . 1.2 2.5 5.0 8.66 15- 23 38 especially if going off the board to a remote location.
Insulation Resistance .. 12 25 50 100 150 250 400 Check that zero seq. C. T.'s have been properly con
Megohm at 2S''C. nected and that cable has been properly grounded.
PART LV - MAINTENANCE
The following preventive maintenance program is out 2. Nameplate data of the equipment and its major com
lined for medium and high voltage metal-clad switch- ponents, instruction books, renewal parts' bulletins
gear with air-magnetic or low oil content type power and drawings.
circuit breakers.
3. A list ofall items which have to be inspected and what
Should the need occur, the Field Service Department adjustments are to be checked.
of the Power Equipment Systems Division of Federal
Pacific Electric Company is equipped to assist you with 4. A record of past inspections and test results.
any maintenance or repair which may be required
throughout the anticipated long life of this equipment. C. MAINTENANCE TESTS
FPE "On-Site Test Facilities" are available to you. This Maintenance tests are applicable as indicated:
service includes engineering inspection and testing of
electrical equipment planned to supplement your regular 1. Insulation resistance tests of the breakers and of the
maintenance program, to improve equipment reliability switchgear bus can be useful in determining the con
and to protect your investment. dition of the insulation if they are made regularly.
Since definite limits caimot be given for satisfactory
MAINTENANCE BENEHTS AND FACILITIES insulation resistance, a record must be kept of the
readings and comparisons made. Deterioration of
Basic elements are outlined for a maintenance program insulation and the need for corrective action can be
of switchgear installations. recogniked if the instrumentreadingsare progressively
A. MAINTENANCE PROGRAM lower after each test.
A well executed program has these benefits:
2. High potential tests are not required and are not
1. Longer life of switchgear. and fewer replacements. recommended except in special circumtances, such
2. Reduced time on repairs and overhauls, and the op as after repairs or modifications to the equipment that
tion of scheduling them at an opportune time. included the primary circuit. When such tests are
3. Fewer failures with unexpected outages.
necessary,theymay be made using 75%of the standard
4. Timely detection of any undesirable operating con 60-^cle insulation test voltage for new equipment
ditions which require correction. at the factory.
5. Improved plant performance and increased oper 3. After the switchgear has been serviced and adjusted,
ating economies. its operation should be checked before it is returned
to service. This can be best done by putting the
Q B. MAINTENANCE RECORDS
A file should be established and include:
breaker in the test position and operating it with its
associated control and protective devices. If it is
l.A record of all installed switchgear and its main desired to test the breaker outside its compartment,
tenance schedule. use the test-jumper supplied with the switchgear.
IS
D. MAINTENANCE EQUIPMENT wear or other damage. Note: Discoloration of the
Adequate maintenance equipment should include: silvered surface is not usually harmful unless
' 1. Spare parts for at least those parts of the switchgear caused by sulphide deposits which can be removed
that are vital to continued operation. Manufacturer's by a solvent, such as alcohol, or by silver polish. (j
recommended list of spare parts can be used as a 6. Check adjustments and operation of safety shut
guide in combination with operating experience to ters, interlocks, auxiliary and limit switches.
determine variety and quantity of parts to be stocked. 7. Inspect all relays, contactors, switches, fuses and
2. A well-lighted shop equipped with the following: other devices for correct operation.
a. A test cabinet for air magnetic breakers or an 8. Check tightness of main bus bolts, anchor bolts, and
inspection rack. structui'e bolts, also control connections and conti
b. Maintenance closing device ,for power breakers. nuity of wiring.
c. Test jumper for connecting breaker to control 9. Check strip heaters and clean air filters at ventila
circuit when it is outside its compartment. tion openings when these are present.
d. Relay test plugs for making tripping, timing and 10. Repair damaged paint finishes.
calibration tests of relays. 11. Check seals, gaskets, watertightness, etc., of out
e.A selection of ammeters, voltmeters and instru door equipment.
ment transformers.
f. An insulation resistance tester. B. POWER BREAKERS
g.An overhead crane or hydraulic lifting device. Air magnetic type and low oil content breakers should
be maintained on the same schedule as the metal-clad
TREQUENCY OF INSPECTIONS units, or at least every year, or per the following
It is generally good practice to inspect equipment tkree schedule, whichever comes first:
to six months after it is first put in service and then in
spect and maintain it every one to three years depend — Air magnetic type — every 2000 non-fault operations,
ing on its service and operations conditions. This refer to instruction manual lN-820.11.
suggested schedule is only a guide. Conditions that dan — Low oil content — every 100 non-fault operations,
make more frequent maintenance necessary are: refer to instruction manual 1N-82S.0.
High humidi^ and ambient temperature. It is also recommended that when the normal operating
*2. Corrosive atmosphere. duty isa combination offault interruptions and repetitive O
3.£xcessiveidust and dirt. operations, the breaker should be inspected :and ser
viced after a fault operation at or near its interrupting
4.^!gh repetitive duty. rating. Remove the breaker from its housing for in
'^.'Frequent interruption of faults, spection. '
b. Older equipment. 't
16
with dosing device to check freedom from binding compartment.
or friction and check that contacts move to the fully 10. Check oil level and dielectric condition (Low oil
opened and fully dosed positions. Check electrical content only).
operation either in test position or removed from
11. Check for leaks (Low oil content only).
17
PART VI • SWITCHGEAR ACCESSORIES O
OHMS Voltage
l!, AC or DC control voltage— 2708-0116 110 24
"close" and "motor", 50
2701-0116 800
DC voltage "trip" 2251D4340 1400 70
2702-0116
2. AC or DC control voltage— 2703-0116 2900 115
"close" and "motor". % 2704-0116 3200 125
AC voltage "capacitor trip" 2252D4340 2705-0116 5800 208
2706-0116 6500 230
MISCELLANEOUS 2707-0116 7100/ 250
SWITCHGEAR ACCESSORIES Indicating Lamp Parts
CELL HEATERS — Complete Assembly 064-007 24-E Ump 24 V. .032-.038
120 Volts with terminal block -amps.
125 watts 2751C0706 2701-0124 Spacer 1/32'
208-240-277 Volts with terminal block 2751-0119 Receptacle assembly.
220-300-375 watts 2752C0706 less Resistor, Bezel and
Color Cap.
120 Vohs without terminal block 2701-0118 Spring Retainer Washer
125 watts 2751C0704
208-240-277 Volts without terminal block ,
220-300-375 watts 2752C0704
THERMOSTAT
120-240 Volt Thermostat
(TypellTll)
(Close 100°F., Open llO'F.) 237-001
O
18
. N
IN-800.0
a
FEDERRL PACIFIC ELECTRIC COMPANY
*V ; .T
- 1 -
tu-'m
3. GBtoftL INSTRUCTIONS TO QUALIFIED PERSCBTSr
March 1966
'•'t''
1^1
A
f.
&-t
-rTTTTT"
PART I
PART II
MAINTENANCE
SHIPMENT
The switchgear is assembled, wired, adjusted and given Switchgear equipment, r^ardiess of whether it is to be .
complete tests at the factory, after which it is inspected installed immediately or stored for a while before being -
and packed for shipment. The air circuit breakers are not erected, should be kept in a dry, clean place. Conditions .
shipped in the switchgear compartments, but are packed such as dampness caused by rain or change in tempera
in separate crates. Each crate is identified, and u com ture, cement dust, etc.,should becarefully guarded against. '
pletelist of its contents is included in the shipping papers. Covering the equipment with a temporary shelter ot tar
All instruments and relays are suitably blocked to pie- paulin is frequently necessary both during storage and .
vent damage to bearings and movements. erection. The longer the period of storage, the greater
REMOVAL FROM CARRIER & INSPECTION
must be the care taken for protection of the equipment.
FOR DAMAGE
Il| is advisable to place electric strip heaters or lamps
within enclosures to raise temperature approximately
Immediately upon receipt of the shipment, identify all 10 degrees above outside temperature at all limes.
component parts and check them against the shipping list." Crated apparatus which is not to be erected immediately
.Make a thorough examinationto detect any damage which will store much better if left crated. It should, however,
may have heen incurred during transit. be inspected to make sure that no damage has been in-
If any damage is discovered, file a claim immediately with . curred during transit.
the carrier, and send notice of the extent of the damage When arrangements are made prior to shipment, electric
to the Federal Pacific Electric Company plant from which strip heaters circuit can be taketi out of crate so that'
shipment was made, giving complete ideuiification, car heaters can be energized while switchgear equipment re
rier's name and railroad car number if the shipment was mains in the crates.
made by rail.
The information wilt enable the compan) to supply nec ALIGNMENT OF FOMNDaTION
essary information in support of claim. Federal Pacific metal switchgear is accurately built on
MOVING AND LIFTING SWITCHGEAR
true and level bedplates. This care and accuracy insures
ease of operation and interchangeability. Equal care in '
1. The importance cannot be overstressed regarding the installation should be used.
care in handling, rigging, hoisting, roiling or moving A true and level floor for this equipmei.i is of utmost
assembled switchgearinto place. Metal-clad switchgear importance. Alittle more than ordinary care in laying out •
is designed to be handled only in ai. upright position and prepaiing the foundation will be repaid in reduction
and should never be handled in any other way with of cost and labor of installation.
out first consulting with switchgear headquarters de The steel supporting members used in the floor should be
sign section. held lev<"l until the concrete is set. The surface of the
2. Each shipping section of indoor switchgear is bolted floor under the housing should not project above the sup
to a heavy shipping skid which should remain with porting member.
the gear until it is moved into final location. Each The floor in front of the housing shuuld not, vary more
section of outdoor gear is supplied with heavy lifting than Yti" in any square yard and must not project above
lugs bolted to switchgcai' base. the level of the supporting members. The heticr this floor
3. When lifting shipping units with a crane, it is prefer is finished the easiei will be the rolling of the removable
able to use two hooks simultaneously, one on each breaker unit.
end. Each pair of lifting hooks should be equipped When installing metal-clad switchgear on existing floors '
with a spanner bar to prevent excessive distortion. it will usually be desirable to pour a new finish floor with
If only a single hook crane is available, arrange spaii- embedded channels or cut slots for embedditig and level
ner to lifting rig as shown on typical outdoor gear ing the supporting channels.
drawing 2200-0114. Lifting from front and rear of Encircling loops of reinforcing or building steel around
units permits placing shipping sections side by side single phase conductor should be avoided in .the areas
for bolting without interference from lifting rig or marked foi main cables—when these circuits are rated at
hook. 600 amperes or above.
4. When cranes are not available, equipment can be One of these methods or its equivalent must be used to
rolled into place on shipping skids provided with each obtain an adequate foundation. Fig. 2 and 3 tack welding
shipping section. Pushing or pulling forces should be equipment to floor channels is preferred since this method
applied to the skid and not the Switchgear. does not require accurate lining up of bolts.
5. Shipping skids can be removed by using a foot jack
in each corner of the shippingsection aftei tlie switch-
gear has been moved to its final location. t). HOLES PROVIDED IH SWGR.
BASE FOR WELDING (PREFERRED) Vj-16 TAP IN
STORAGE BEFORE INSTALLATION OR BOLTING. SUGGEST W HOWE. CHANNa OK PLUG
WELD SW'GR. TO
SEE FLOOR PUN FOR LOCATION.
Protection against loss of equipment is an important pre 2" HOLES ON EACH UNIT
LEVEL AND HOLD
WITH Ml" 0. BOLT,
..CHANNa IRON.
caution. Trouble and delay will be avoided by having FOR GROUTING THEN POUR IN CONCRETE.
good storage facilities arranged so that the apparatus will
be accessible only to authorized persons and so that it . '/4" PUTS WELDED
can be quickly located when required in the erection BETWEEN EUNGES
UNDER ^ROUTING HOLES.
program.
FIG. #2 fie, >3
) ) )
WIDTH 4FPR0XIUATE
R4TIN0 OF CELl
OF CELL NET WEICMT •
COWOU^T OR
BREAKER ORAWOJT AREA CABve SPACE
DETAIL V
CONDUIT OR
BREAKER OAAWOUT AREA CABLE SPACE
r
ACCeSS^OPENlNG
SECURING ANGLE
SUGGEST WetOING OR
BOLTING "
REuovaBLE urTine 'j\o
SECURING ANSLEy^ ; ;.va •'V;'^e, J
^ SEE DETAIL -A
DETAIL "B*
WECOMMENDEO METM003 OF J>HCHQHINB
CONCRETE RAO AND LEVELING CHANNELS TO BE SURAUEO ST CUSTONER
UNLESS OTMERWISE SPECIFIED.
RECOUUENOEO NETHODS Of ANCHORING ARE SHOWN IN DETAILS 'A' B'a'
The units UAY be bolted, welded or anchored to the CH«MNfL.
SUGCEST 1/1 INCH HARDWARE FOR BOLTING. (HARDWARE SUPPLIED BY
CUSTOUER I
PHDHWAL PACIWtC WLMTWIO CHiMVELS SHOUID BE l-EVEl. WITH EACH OTHER ANO LEVEL OVER THEIR
ENTIRE LENGTH I RECOUUENDED SIZE OF CHANNEL 4-X».AiP/FTI
~~ neCCMUENOEO HETHOO-W LIFTtNe FINISHED FLOOR SHOULD NOT BE HIGHER Than LEVELING CHANNELS'
an;- SHOULO ALSO HAVE SLIGHT PITCH AWAY FRON CH4KNEI.S.
2200-0114
•1.'.
v;
.'k-
J
•TTT'"?"
"Folestiglas" is a two part resin system. It is shipped in Taping a fiat or a cylindrical surface such as a bus bar
separate containers, so that the catalyst, which is about or cable is a relatively simple pinress in which much the
19' by weight of the resin, when completely stirred and same technique b used whether the tape is paper, cloth,
mixed can he poured directly from the large container film or plastic. The tape lies tnitiirally in a spiral, and
into the compound box mold. there are no problems of conformance. However, when a
small degree of irregularity is present, it b helpful to use
Casting compound is supplied in separate containers— a tape with some elongation so that wrinkles are not
each container of compound and container of catalyst, created. This property is also u-sefui in guiding the tape
when mixed, will fill one compound box. to maintain the proper overlap. \ inyl tapes possess this
elongation lo an exceptional degree. Combined with it is
The identification number of the material supplied with a "memoiy" in the tape which causes it to contract after
each joh is as follows: application and pull down to a snug fit, mininiii:ing voids
Field joints with compound boxes. or other irregularities in the insulation. This is an ad
vantage if properly understood and used coriectly, but
Current Transformer^ etc 2700-5053 can be harmful if the tape is stretched unnecessarily to
Patching Compound 2700-5054 make it "conform" to certain contours. The pressure
sensitive adhesive is not designed to withstand large side-
Catalyst 2700-5051 wise (shear) forces for a long time; and if the contour
Picture Number 1 - . . shows the standard assembly of is such that the tape tension can he relaxed by a side
a bus joint with compound box. Assemble compound box slippage, some slippage will take place.
as indicated in picture 2, mix resin and catalyst in line Many surfaces requiring insulation-stress cones, for in
with instructions furnished with material, and described stance—are of such shape that they cannot be wra|^>ed
above, and pour, as illustrated in picture 3, up to the top spirally without excssive stretching of the tape. Usually
of the mold. This material will then set to a hard non- in such cases a taping method can be devised thai will
hydroscopic mass. The black compound box is left in make use of the "men.ory" or "regain" characteristics of
position in this operation, and is not removed. The final the tape lo insure proper insulation.
joint looks exactly as picture 3, with .the exception that it
is filled with Polestiglas. If the surface is developable (capable of being covered fay
a flat sheet without stretching), it is always possible to
An alternate method of making compound boxes in the apply the tape in such a way t.hnt there are no forces
field is illustrated in picture 4, where a foam mold is tending to make it slip sidewise. This is done by wrap
supplied. This foam mold is supplied as a unit, and is ping along the geodesies of the surface (lines of shortest
clamped lo the joint that is to be insulated. The foam distance between two points.) The general principle is
mold should be waxed inside with Johnson's paste wax that of letting _the tape lay itself on tlie surface to be
before it is assembled on the joint. It is recommended covered; if necessary, the tape can be cut several times
that the outside surface of the compound box and adja for some surfaces.
- <
:^-- 'N
— -
m-'-.. •
r'.kJj.-'-i.' -1
v^
Jt^-
I:- '.A
, •'-. -<! -
M,'
I -|
.'-.-'v^-'j •
<* ' .- •' . -V.- W' ', < . >V, - J
^•a-r'-'.'-l
.' 'h' "'•-. ' • ••'-*•
ir-'i.
" ii; ,
^i ' ••;. '-:C:;:!^":'V;^ m • ' ». ,A : -;y ' ,
>-'?J
m-A
;t:>^irrV,- M'l
I .V '
Ws-Iroj,! ;, ,
/' . •
:,-v:
\-l''
1 •' . •- ' •
)
SI PART NO. DESCRIPTION kEM
TAPiNG INSTRUCTIONS VINYL PLASTIC ELECTRICAL TAPE 1 INCH
a ROLLS ISO- 100 1
(from ORAWINO Z7SI-04A2.j WIDE X 36 YARDS LG. FLAME RETARDCNT
15 FEEr 002-009 1 4 INCH WIDE KNtTTED COPPCA MESH. 2
THE FOLLOWING INSTRUCTIONS SHOULD 8E FOLLOWED IN TAPING ALL
1/2 ROLL
1CARBON
1
SLACK^^,0£
BIASjg SEMI-CONOUCTlVE
72 yards long 3
main connections as required on SWITCHGEAR.
SEMI - CONDUCTIVE
SEMI - CONDUCTIVE TAPE (ITEM 3)
TAPE I ITEM 31
AT EACH GTEP USE 3 TURNS tape (irtii II
FIG. 4 ! I
(VARNISH CAMBRIC)
OF TAPE. IN CASES WHERE END
MUST BE BENT. SUFFICIENT AREA
MUST BE TAPED TO PREVENT
VARNISH CAMBRIC FROM COMING
LOOSE.
SEE FIG. 4
TAPE I ITEM
COPPER
MESH fITEM 21
II
COPPER
rircM
MESH
ei
SECURE BRAID
WITH 2 LAPS TAPE OVER
TAPER 80* LOO
OF TAPE 150- SECOND RING
AS SHOWN 100
NOTE o/
-H f
-c
-r
I
1
FIG: 7
INSULATED WIRE TO 'BUS BAR TO DISCONNECT
{folyethylene) BUS CONNECT/ON SWtTCH STUD CONNECTION
E::;: -•.V - •
: -
J ^.
(MSULATION BOOTS
' On 5KV class equipmcn! electrical joints are insulated with
molded bus bar hoots. The boot is pulled in place around the
bus bar joint. After htting two (or three as conditions require)
holes are punched for clearance of the 10-32 nylon hardware.
(Insulation boots can be applied to I.IKV class when phase id . C
"Vi!..
to phase clearance is 7" min. and phase to ground clearance
is 6" min. If rodgap situation is present increase dimensions
by 1 inch.)
DETAIL BOOT
RIGHT ANGLE
.NOTE "m-
DETAIL BOOT
NOTE "A"
.i THRU
OCTAIl BOOT
DETAIL BOOT
f •• .".MG nSADY FOR SERVICE The equipment .should be checked to be certain no tools
rcA rcnce should be made to each component in- on any other equipment have been left in the switchgear.
•iirrir.'ion I' -iilct before attempting to place the switchgear When connections are to be made to or from an Electric
in if Irv-type or oil or askarel-filled power trans- Utility, [ uhlic.or privately owned, consult their represen
forinors are furnished as part of the switchgear equip tatives V-TV early in the construction period, as many of
ment. consult their instruction books or leaflets, particu them have very strict requirements which must be met
larly regarding absorption ofmoisture, and eflfects ofdust before service connections will be made.
and sand, etc.
Any indication of moisture will require that equipment OPERATIONAL TESfiNG
be dried out before placing in service. Care sliuuld be Upon completion of installation, and inspection of the cir
exercised in drying-out operations to be certain that the cuit breakers and other components, together with instal
maximum temperature during the drying period docs not lation of any incoming and outgoing control connections,
exceed 70 to 75 degrees centigrade on switchgear. In the it is time to start operational testing. Outgoing feeder
event it is desired to give the equipment a high potential cables should not be connected at start of test.
test before placing in service, this test should only be If it is a Power Center with Power Transformer and high-
made after the equipment is thoroughly dry, allowing voltage di.sconnect or interrupter switch ahead of the
approximately 10 days drying time. The value of test
voltage should correspond to the voltages listed below. switchgear, lock the switch in the open position in order
to protect the test operator. r
DIELECTRIC TESTS Similarly if it is a generating station, the generator
The following dielectric tests shall be made to determine breaker should be locked opeu.
the adequacy of insulation. Devices used as part of sw itch- If there are low voltage manual breakers, they may be
gear assemblies shall be capable of meeting the following , checked in "test" and "operate" positions. Extreme care
dielectric tests. should be taken that all contacts and housing switches
Exception—^There is certain apparatus such as pclenlial (if any) align properly.
transformers, auto transformers, motor starting reactors, When the switchgear has dectrically operated circuit
and motor-operated devices the standards for which call breakers, they are operated in some installaiiona from
for lower test voltage than those given below. When such local battery or auxiliary control supply, and in other
devices are used, they may be disconnected during these installations are operated from the switchgear bus, or a
tests. connection ahead of the incoming master circuit breaker.
Alternating-current test voltage shall have a crest value In the event the primary source of power is locked open,
equal to 1.41 times thevalues specified. A sine wave shape it will be neces-sary to use an auxiliary source of power
is recommended. The frequency shall not be less than the to operate the circuit breakers, lamps, belbalarm switch,
rated frequency of the apparatus tested. The test voltage undervoltage devices, rectifiers, capacitor shunt trips, etc.
shall be applied for one minute. Check circuit breakers in "test" and "operate" positions,
Direct-current test voltage, if used in lieu of alternaciiig- paying particular attention to good contact between mov
current test voltage, shall be 1.41 times the specified altei- able and stationary secondary contacts in both positions.
/^>nBting-current voltage. Key Interlocks should he operated manually to makesure
A. Equipment Rated 60 Volts and Below that protection is complete. Remove spare keys to super
That part of assembled equipment rated 60 volts or less visory office.
shall withstand an altemating-curreni voltage tesi of SCO Each relay and trip device or other component should be
volts.
operated manually to be certain its contacts perform their
B. Equipment Rated 61 to 600 Volts required function. Remove any material that wasinstalled
Alternating-current assembled equipment and alternating- at the factory to block relay contacts during the shipment.
current circuits of equipment of higher rated voltage Preliminary settings for test purposes should be applied
rated 61 to600 volts shall withstand an alternating-current to relays. The various operational functions are indicated
voltage test of 1000 volts plus twice rated voltage, witii on the schematic and wiring diagrams of the switchgear
a minimum of 1500 volts. Factory Test. When assembled equipment.
in field and connected, test voltages should be 75% of After completion ofall operational tests, all relays should
factory test value.
be set. All trip indicators on the relays should be checked
C. Equipment Rated 601 to 2399 Volts— to see that they function properly. •-
Alternating Current Upon completion of device settings and tests, the main
Alternating-current asseunbled equipment rated 601 to incoming and feeder cables should be properly phased
2399 volts shall withstand an alternating current voltage out and connected to the switchgear. Incoming and out
test of 20(W volts plus 2^ times rated voltage. When going cables should be braced so as to take mechanical
assembled in field and connected, test voltages should be strain off studs ofcircuit breakers and porcelain supports
75% of factory value. of various types.
D. Equipment Rated 2400Volts Alternating-Current The entire switchgear structure shdud be carefully vacuum
and Above Standunl cleaned (preferred) or blown out, and all rear and side
Full-Wave
Impuhe
plates that have been removed should be rebolted in
DotedVeltoge 60 Cytio KV 60 CyeloKV IWIIhtland) place. All secondary and power connections should ^
KV Field Conn. Facloty Tetli KV tested for grounds with high potential tester or merger.
2.4 11-25 15 45 Megger readings of one megohm per thousand volts is
4.16 14.25 19 60
7.2
acceptable. If readings are lower equipment" should be
27.0 36 95 dried out until insulation resistance vdues improve to
13.8 27.0 36 95
14.4
one megohm per thousand volts." Preferable readings are
37.50 50 110 Operating Voltage KV 1.2 2.5 5.0 8.66 15
23 45.0 60 150
34.5
Insulation Resistance 12 25 50 150 300
60.0 80 200 Megohm at 25
•Sir
11
A preventive maintenance program is outlined for me After the switchgear has been serviced and adjusted,
dium-voltage, metal-clad type switchgear, low voltage its operation should be checked before it is returned
metal-enclosed switchgear, and air-magnetic powei c-licuit to service. This can be best done by putting the
breakers. The outline lists benefits to be derived, recorda, breaker in the test position and operating it wWb
tests and facilities required, and inspection and servicing its associated control and protective devices. If it is
steps. desired to lest the breaker outside its compartment,
use the nine-foot test-jumper drawing #3352-0017
supplied with the switchgear.
MAINTENANCE BENEFITS AND FACatTiES
Basic elements are outlined for a maintenance program D. MAINTENANCE EQUIPMENT
of switchgear installations.
Adequate maintenance equipment ^ould include:
A. MAINTENANCE PROGRAM I. Spare parts for at least those parts of the switchgear
that are vital to continued operation. Manufacturer's
A well executed program has these benefits; recommended list of spare parts can be used as a
1. Longer life of switchgear and fewer replacements. guide in combination with operating experience to
determine variety andquantity of parts to bestocked..
2. Reduced time on repairs and overhauls, and the op
tion of scheduling them at an opportune time. 2. A well-lighted shop equipped with following;
a. A test cabinet for air magnetic breakers or an
3. Fewer failures with unexpected outages. inspection rack. '
4. Timely detection of any imdesirable o^ratingco.idi- b. Maintenance closing device for power breakers.
tions which require correction. c. Test jumperfor connecting breaker to control cir
cuit when it is outeide its compartment.
5. Improv^ plant performance and increased operating
economies.
d- Relay test plugs for making tripping, timing and
calibration tests of relays.
e. A selection of ammeters, voltmeters and instru
B. MAINTENANCE RECORDS ment transformers.
A file should be established and include: An insulation resistance tester.
1. A record of all installed switchgear and its mainte An overhead crane or hydraulic lifting device.
nance schedule.
FREQUENCY OF INSPEaiON
Nameplate data of the equipment and its major com It is generally good practice to inspect equipment three
ponents, instruction books, renewal parts bulletins to six months after it is first put in service and Aen in
and drawings. spect and maintain it every one. to three years depending
A list of all items which have to be inspected and on its service and operation conditions. This suggest^
what adjustments are to be checked. schedule is only a guide. Conditions that can make more
frequent maintenance necessary are:
4. A record of past inspections and test results. 1. High humidity and ambient temperature, 2. corrosive
atmosphere, 3. excessive dust and dirt, 4. high repetitive
C. MAINTENANCE TESTS duty, 5. frequent interruption of faults, 6, older equip*
ment, and 7. history on preceding inspections. .
Maintenance tests are applicable as indicated:
. Insulation resistance tests of the breakers and of the SAFETY PRACTICES
switchgear bus can be useful in determining the con Maintenance employees must follow all recognized safety
dition of the insulation if they are made regularly. practices, such as those contained in the National Electri- >
Since definite limits cannot be given for satisfactory cal Safely Code and in company or other local safety regu
insulation resistance, a record must be kept of the lations during maintenance. All of the units of switchgear
readings and comparisons made. Deterioration of in to be maintained must be de-energized, tested for poten-
sulation and the need for corrective action can be ^®1| pounded and tagged out before removing covers and '
r^gnized if the instrument readings are progres barriers for acct^ to primary circuits. As is well known, .
sively lower after each test. the solid insulation surrounding an energued conductor
High potential tests are not required and are not
in power apparatus should not be relied upon to provide
protection to personnel. Another example is the mainte
recommended except in special circumstances, such nance closing device, which is exactly what the name
as after repairs or modifications to the equipment imphes and should never be used to close manually a'
that included the primary circuit. When such tests circuit breaker that is connected to an energized circuit:
are necessary, they may be made using 75% of the All removable devices, ^uch as the circuit breakers and
standard 60-cycle insulation test voltage for new rollout potential transformeis, should be removed from •
equipment.
the metal-clad switchgear hpqsing.
, ance program for switchgear V. Clean silver-plated breaker primary disconnecting de
vices. Wiether cleaned or not, lubricate devices by
•—'*, nUllML
lllC ,„r, ri.nancf
Ilc-I" - prosram should include
. f the
1 rthorough
11 • • applying a thin film of slow aging, heat resistant
inspecliiin. servicing and adjustment of the totlowing petrolatum.
components for 2.4-13.8 KV operating service.
' 5. Inspect breaker operating mechanism for loose hard
ware and missing or broken cotter pins, retaining,
A. METAL-CLAD STATIONARY UNITS rings, etc. Examine cam, latch and roller surfaces
1. Remove accumulated dust and dirt. Vacuum cleaning for damage or excessive wear.
is recommended.
6. Clean and relubricate operating mechanism. Use a
2. Wipe insulated buses and bus supports with a clean non-hardening grease to lubricate cams, rollers,
cloth mobtened (when necessary) with a petroleum latches and props, and pins and bearings. We recom
solvent or similar cleaner. Wipe insulation dry after mend LUBRIFLATE, "AERO" grade, manufactured
cleaning. by Fiske Bros. Refining Company, Newark, N. J.
3. Inspect buses and connection bars for physical dam 7. Check breaker operating mechanism adjustments and
age, evidence of corona cutting or other conditions readjust as described in the instruction book. If these
that can indicate deterioration of the insulation. adjustments cannot be made within specified toler
ances, it will usually indicate excessive wear and
4. If taping has been damaged or needs replacing fol need for a complete overhaul.
low instructions on Federal Pacific drawing page 6.
8. Check control device for frradom of operation. Re
5. Inspect alignment and contacting of primary discon place contacts when badly worn or burned.
necting devices, checking for signs of abnormal wear
or other damage. Note; Discoloration of the silvered 9. Inspect breaker control wiring for tightne^ of
surface is not usually harmful unless caused by sul connections.
phide deposits which can be removed by a solvent,
such as alcohol, or by silver polish. 10. After the breaker has been serviced, operate it slowly
with -closing device to check freedom from binding
6. Check adjustments and operation of safety shutters, or friction and check that contacts move to the fully
interlocks, auxiliary and limit switches. opened and fully closed positions. Check electrical
operation either in test position or rerhoved from
7. Inspect all relays, contactors, switches, fuses and compartnient.
other devices for correct operation.
8. Check tightness of anchor bolts and structure bolts,
also control connections and continuity of wiring. C. LOW VOLTAGE POWER CIRCUIT BREAKERS
600 VOLT AC
9. Check strip heaters and clean air filters at ventilation
openings when these are present. The preceding information applies in nearly all details to
Low Voltage Metal Enclosed (600 Volt AC) switchgear,
10. Repair damaged paint finishes. both indoor and outdoor, the differences are only minor,
and are due to physical differences in the switchgear.
B. MEDIUM VOLTAGE POWER CIRCUIT BREAKERS METAL-ENCLOSED SWITCHGEAR 600 VOLT
(AIR MAGNETIC TYPE) 2.4 TO 13.8 KV MAXIMUM
Air magnetic type circuit breakers should be maintained SWITCHGEAR ACCESSORIES
on the same schedule as the metal-clad units, or ever>- Descriptipn Part No.
2500 non-fault operations, of at least every six months,
whichever comes first. It is also recommended that when
"Breaker Racking-in Handle or Crank .
the normal operating duty is a combination of fault in FP-25 and 50 1101 B 9251
terruptions and repetitive operations, the breaker should FP-75 11.51 C5036
be inspected and serviced after a fault operation at or
near its interrupting rating. Remove the breaker from "Breaker Maintenance Closing Handle
its housing for inspection. FP-25 and 50 1151B 9252
FP:75(2Reg.)
1. Wipe insulating parts, including bushings and the
inside of box barriers, clean of smoke and dust. Breaker Extension Rails
Repair moderate damage to bushing insulation by . FP-75 (2 Req.) 1151 C 5214
sanding smooth and refinishing with a clear insulat
ing varnish. "Breaker Emergency Charging Handle
FP-75 Only 1.151 B 5349
2. Inspect alignment and condition of movable and sta Breaker Lift Yoke or Chain (Use With Overhead Crane)
tionary contacts. Check their adjustment as described FP-25 and 50 . 4051 A 3274
in the instruction book.
FP-75 167-002
3. Check arc chutes for evidence of damage, and re Breaker Hydraulic Lift Truck
place damaged parts. When arc chutes are removed, FP-25, 50 and 75 only 2651 B 0200
blow out dust and loose particles. . FP-25 and 50 only • 2652 B 0200
FP.25, 50, 75 and 100 2653 B 0200
10
•' ,• I -1-•
•Breaker Test Jumper Cable—9 Ft. (30 Points) (Re- Closing Rectifiers — 240 V 60 cycle AC (264V Max)
quired only if test of hrkr. out of cell must include 125 volt DC intermittent duty. AC not to be applied
circuit function of the auxiliary contacts) longer than one (1) second nor more than ten (10)
times in any one minute period.
3354 B 0017
•Breaker Outdoor Transfer Truck Part No.
DST-5KV-20" Wide Breakers 3351-1458 100 Amp4-8-1 Stock, 240V AC. 125 Volt DC 2701-0244
DST.5KV.30" Wide Breakers . 60 Amp 4-8-1 Stock. 240V AC.125 Volt DC 2702-0244
(except 5-350) 3352-1458
DST-15KV-30" Wide Breakers 3353-1458 Arc Suppression Rectifier (DST Breaker only)
125 volt DC—Service 1-Stack 087^^)04
Steel & Aluminum Bolted Cell Non-Walkin
DST.17".21" Alum. House 2251 D 2851
DST 30" Alum. House
Hook Stick For Disconiiecting Switches
2252 D 2851
\viMJ S-foot Stick 3751-0540
DST-17".21" Steel House 2253 D 2851
DST 30" Steel House 2254 D 2851 10-foot Stick 3752.8540
DST 30" Steel House 5350 & 12-foot Stick 3753-0540
15-1000 14-foot Stick 3754-0540
DST 30" Steel House 5350 &
15-1000 Cable Lugs, Cast Eyebolt—Dwg. 2701-0010
'Breaker Handling Dolly—Indoor Cable Range
DST-5-75 1551-2825 #10W to #2W 2701-0010
DST.5-250, 5-350, 15-500, 15-1000 2251-0333 2C to 4/oC 2702-0010
250MCM to 500MCM 2703-0010
Breaker Test Cabinet^—Indoor 600MCM to lOOOMCM 2704-8610
(Except 15-10()0) 1250MCM to 1500MCM 27a'>-0010
125VDC QoseS Trip 1500MCM to 2000MCM - 27064)010
(4101 D 0116) 3354 D 0070
230V ACClose Cap.Trip. Touch Up Paint
(4101 D 0117) ; 3355 D0070 Exterior outdoor dark gray ASA-24 Finish S-18
230V AC Qo8eBll%iiyTrip Interior indodr light gray ASA-61 • Finl^ S-20.
(4101 D 0115) - 3356 D 0070
250V DCQoseS Trip Joint Compound Box Ordering information X 3,
(4101 D 3987) 3357 D 0070
1/4 X 3 Conductors Kit
230V ACGose Cap. Ttlp
(4101 D 0117) 3359 D0070 Box &Compound (1 Connection) 2751-0470 • •
230V ACGoseDCTVip
(4101 D 0115) : 3360 D 0070 Joint Compound Box Ordering Information ViX 6t
48V DC Gose, Trip &Motor V4 X 6 Conductors Kit
(4101 D 5114) 3366 D 0070 Box & Compound (1 Connection) ' 2752-()470
125V DCClose, Trip &Motor ' For Insulation Boot Ordering, .See Page7 - '•
(4102 D 5114) 3367 D 0070 Unit Heaters
48V DC Gose, Trip &125V aC Motor
(4103 D 5114) 3368 D 0070 Description Part No.
125V DC Close, Trip &12SVAC Motor 120-208 Volts, Complete Assembly,
(4104 D5U4) 3369 D 0070 125-375 Watts 2752 B 0569
115V AC Close, Motor &DC trip 3370 D0070 240-277 Volts, Complete Assembly, .
230V AC Close, Motor &DC Trip 3371 D 0070 300-375 Watts . 2751B 0569
. 230V AC Gose, Motor &Cap. Trip . 3372 D 0070 120-240Volt Thermostat (Close55'F, Open65°C 1604)01
277 Volt Thermostat (Close 55'F; Open 65.°.C)
11
Switchgeor Indicating Lamps
amps.
2702-0117 green
amber 2701-0124 Spacer 1/32"
2703 0117'
27040117 . blue 2751-0119 ' Receptacle asseinbly, leas
Resistor, Bezel and Color
27054)117 white
Cap.
2701-0118 Spring Retainer Washer
Instruction Books
March, 1966
V:.'
-Low Voitago Switcfoear
600 Volts a-c—25,GGG iO IGG.GCC Amperos \i Descriptive- Sheet
Pago •?
.; •».>•>/•">• .''G'-'Ph
h..: • •V A
"•/r", •?;,,,
&•-;
• non GfinTbrApT-i
D
• m •
D [_j- ^' S
IL-' AG-pA-i 1K a
I •• • '• "• . - ",•' - *•-.' \ • i 1
'Vyii-
nilWhM"-'**
iiuiiiiuiilH
»G'v'
! iu i y! 1A
r-i';?
5h;>
••',• fAiJi.
iiixi,
ii AAMf
I ;• •.-aaa-A'I'
, Low Voltage Metal-EnclpsctI Switch- i .Vi»-I :T'---1t--v,v-.jA
gear with Type FP Air Circuit Breakers
- -AAaaA'
Federal Pacific Metal-Gncloscd Switchgear is specifi- • •All Federal Pacific circuit brokers employ. K stored „ .
cally designed for use in industrial plants, commercial energy mechanism. This permits safe closing on all . - ^
buildings, and utility cpjppanies whore a high degree of circuits because the fast closing, speed, of the circuit f-'. V.V'h
service continuity and reliability arc required. This
equipment may be anplied at 208, 240, 480, and 600 volts "
a-c witH vitejryptij.g ratini^S up to 130,000 amperes
synmit.k'h—.! vl'iO."?'! atnperes asymmetrical incrcas.-'s the range ot the breaker siisc n.atcan be safely ' ^
operated mahuallyj apd reduces breaker inaihienanoe r-iA • d'
g^r assembly, .Federal: PaoW builds a>pe PP50 air •by extending:contMt'lue. .'>' ' •
circuit brcakei's having SPiCop a^npcrcs interrupting Every switchgear unit incompletelyi^^ksemb^ed.andr .:^
capacity which:may be stacked foiir high. . G-" wired priorto shipment. Rigid testing andfquality con- /vA. :
Federal Pacific Low Voltage Switchgear utili-zes the| trol procedures insure cbihpliancc \rith thm £uierV rn . V
most modern design'concepts providing maximum pro-'' quirements and applicablQ industry .stahdarids, fnduding •• '
tection to distrfbution equipment and complete safety to those of ASA. NEMA, and IEEE. ' ' , '; ' .^' A; V
*•?--'"••"•t I-—".^nnel. With tell dooc -/feu, circuit-.'' Signif.cant design improvements—primacny.iri the air • "A" ; '"
liieakers can be placed in either of three positions: circuit breakor.'—enable Federal.Pacific to produce.rpli- AAri..;v:
"C<mnected" "Test" and "Disconnected" enabling safe able metal-enclosed switehgear^arid pm'TOit 'consjd«jib}*e4A'r' ' f/^^^
mmntenance and operating techniques to be employed. sayings in their applicatioiL .-''AA-'AAAIA^'AAA
AA'•: A:•• •;-A-A-AAA'::A'AAA..AAAi^^
i'x'l
• .,• £'
' •••'.f-ii io u.t.4.'i -r . F£=OE;RAl- P»ACfF;Cr El£..tJC T}-
----- 1A1
Low Voltage [ItetarEncfosed Swltchge^r
600 Volts a-c—25,000 to 150,GOG AiTiporss 10
I
Y '
*' '••i; •- • • •
::••..j: ''
••' ^ ; i:!: 1 '•
• f j '
'if.-! ; • "hk ;ife*vy.v!5l^" fe;?;''"- •' ••l* • y:-,.A-
; t t •', y.-.'' •,•'•• .--
: I
iGj'j.'riV"'' • ' ' :- I ^n •;
3') t.*
• ^$1
! i
: -r
f -li •
;• ,
. , «v.- -v < • .*-
i }
't '..'^ i '* V. -../ • — TT/V. ' ; \ "i ' • I J ' ' iv'
*1' '}-.5.• • "'' :'•. r*
Ceil for FP25-8dO clrcnit breakers
('•
Iv.Mfer •<:••••.''
1;:^
, tvO : r Bu^compartment
'(71^
CONSTRUCTION ,
Federal Pacific Low Voltagre Switehgear utilizes the Cellfor FP50-i600 circuit breakers
most modern design concepts. Circuit breaker cells 'are
made of formed sheet steel and are jig-welded to insure
accurate alignment for interchangeability of circuit
breakers. Universal bolted frame conscruciion provides
the rigid steel framework for the switcbgear exterior.
Top, side, and rear bus compartments are covered by
removable steel plates. Bus bars arc heavily silver ! v ,'5 1 - /? • . .V j!'-: .v-!-
plated for maximum conductivity and are securely
braced to withstard the shucks and. magnetic stresses
caused by fnu:^ "iirrents capable of being produced by
the system in which the switcbgear is installed.
Terminal blocks for control circuits arc located a safe
distancc.from the bus, and are accessible from the rear
of the switchboard. . •
Each breaker cell door is louvered to provide adequate
ventilation ncce.ssa ry for the switcbgear to stay below 'ijl: •' X.K''-- ' - .• -lA' . I' •"• ' • ; |';y'
lb" prp«erib»f' rpmpp'o^ure rise. Prior to paiiitiiip-. all • I- G '
nietal paiU are tompietely degreased and given a phos- A. 7,. , • . .
phaiizing treatment. This preparation is followed by
.T application of a standard ASA-61 light gray paint that
ISbaked on to.provide a durable finish. Cell (orFP75-3D00 circuit breakers !
• .»>;• V?v"v.rv-'.v.':--vrr.v:' ^ .
.. ......... .-..-t.. . --.....j,.. ... l.'i^VV'V 'V.-
-t r pv
SCTR5C -iCOfWPA-NV
Low Voltage Metal-Enclosed •^QaT
600 Volts 2-0—25,009 to 15.0,000 Amperes !C Oescrir -V* Sheet
r»c,- • • 3
V-
L
-r-.v"., :;V- ?
I .
''''''
[ i
(A*' T-'M..,, .
TELESCOPiNQ ROLLUUT
Breakers can bo completely with
t" —i •'.
'!3 i-it'-'.' 1' drawn from the cell for examina
tion, maintenance, or replacement.
-, ti 1ii ^ •- Teles-oping guide rails rigidly at-
^chod to the breaker cell provide
a substantial support for the
breaker to roli in and out A posi
tive "stop" at the end of the rails
prevents further travel after the
breaker has completely cleared the
enclosure.
s.
I: ..-V'' •%
*• ".'i '-" 'l
?•
•k- ""^>^1 i ,
'S'i'
ICraaait. W-
-i-.'iR'i-.
OUTDOOR CONSTRUCTION
A fuH sekction of both steei and aluminum outdoor
housings is availu!)lc—with standard piMtcotod-nisle
construction. Tho .basic indoor switchi^car assembly
r.V''
is mounted on a steel or aluminum base. Then an
outdoor enclosure is built around ,tbe switchgear. Tbe
outdoor housing oonfain.s lights and reeejitacles, as well
as screened ventilating louvers and heaters to prevent
condensation. Accessibility to the front and rear is pro
vided by doors. Outdoor steel housings are phgsuhatized
followed by an epoxy undercoat and given a finish coat- .
ing of ASA-2-$ dark gray paint
Aluminum outdoor housings may bo natural finish or
at user's tipt'on ol'odi'ed a light green color. The allodiz-
ing process is aiso a preparation for paint; and either at
the time of manufacturing or at a future date, a com
patible paint may be applied.
All outdoor switchgear is coated with an automotive 1. ''i:
type "uudcrseal" to provide protection against deterio 11 ^< 1'
ration to all surfaces not acceasi'ole after iiistallation.
Federal Pacific outdoor enclosures have been tested in
accordance with MEMA standards and were found to
•i;-N
'i/
greatly exceed the requirements in that wat«!r whb com-
»• •
pletely excluded. r-i i
i'
♦"
, . , \rf .1 l-
. '1 r>'i"
•' .•
. •Ibi • .^Mv
''iv-'Ss:
rrtl'fi'if."
11
te'' 'IV
Lr "•.'V r''
'V-
. .•••-,r^v.'.'v- V,-
'PSDKIRAl. PAC
©LASS
Voitage Motal-Encbsec. /
SOO Volts 2-c—25,000 to 150,0'7o . .t;pares D':i;.cnr -!•••":' Shee-i
1 '
•1-'
"m'
ilf '-v-ij ,
; ,•*?J: ?"'^f
A."* »1
FP75-3000
v4-
f^;; IT;;'-?!;! g
I**- "u'.V ;
. FP25-600
'•'\ r .
•' < .
'1 7'
•«a 'Nv-
•, i- "
-:.gT
'! >•
• <•'
h -• "= i
• >• i ' 1 •.' . •. ^
^ 1^71 FP50-1600 FPlGO-4000
i i. '••V-'-.-V"''•' •" -';
, , •*•:• «V-* ? '* *^i.' •**'*' • t-r«
r-4 ^
• tz^'fcaA'
""*11'"-'"'
• %tfr
"Open Position" and stay in the "Open Position" regard if.'Vi.. •
less of any closing effiort wiiich may be applied to the
mechanism. It is impossible for the springs to discharge
and attempt to close the breaker unless the springs have
previously reached the fully-chargcd condition.
Type FP25 and FP50 breakers have an advanced-
design. stored energy assembly which nmy be specified
with any one of three different operating mechanisms:
manuclly charged, electrically charged, or a combina
tion monualiy/Glectrieaiiy charged. The FP75 and S !..
. rX'. -j
PPIOO breakei-s are supplied electrically operated.
Provisions for emergency manual-closing is standard.
Springs
Manual operation:
Discharged
Manually spring-charged, atored-energy mechanisms Breaker closed
have the energy stored by a front-operated handle and latched
rotated clockwise 180°. An indicator on the breaker
escutcheon indicates "Spring Charged."
The breaker may be manually closed by pushing a
"Close" button or electrically closed by a remote contact four closing springs. A closing operation may he initi
which energizes a latch release coil. Manual trip is ated only after the springs are fully charged, cither
accomplished by pushing a "Trip" button or by an elec from a remote source or by pushing a "Close" button on
tric shunt trip coil. the breaker front plate.
Electrical operation: The "Close" button in the face pl.atc of a standaid
electrically operated breaker closes an electrical contact
On the FP breakers a frae^onal horsepower, high which energizes a latcb-rclease coil. The use of nn elec-
speed a-c/d-c universal motor provides through a ratchet . trica! "Close" contact facilitate.s intcriocking breakers,
system spring-charging energy, in approximately one providing safer systems. As an option, the breaker may
I second. be equipped with a mechanical "Close" button. A trip
oper.ition is accoiiipltshed by pushing the "Trip" button
Motor energy Is applied to a gear and r.-vtchet reduc on the breaker or by remote operation of a shunt trip
tion vnit which provides high charging torque to the coil.'
S5L.ASS
:. .i^" "
'.•;•••• s';:
:i' v;-'-
tfe "~V-"• •* r
TD-2 Selective Timing Device
'i-i
SERIES TRIP COIL AND MAGNET ASSEMBLY TD-3 zone selective timing device: Provides long delay, •
The Federal Pacific series trip unit consists of two shoH delay pickups and instantaneous trip, as well as
basic components; the series trip coil and magnet as long delay and short delay band adjustment.
sembly plus the timing device. Removable connecting Other special combinations of trip, characteristics can
rods join the coil and .magnet assembly to the timing be offered. Requests for additional inforniatlon on these
device. This unique arrangement permits the timing
special devices should be referred to the factory.-
device to be brought out to the front of the breaker
where it is conveniently read and adjusted.
Timing device: Timing is obtained by a single clement, ,
Timing Pevices: The FP line of .-eries trip coils. In magnet on the general purpose TD-1 timing device and •.
conjunction with the flexible ^D-l and TD-E liming by a dual element magnet on the selective l"D-2 timinf
devices, permit a wide range of trip choructcristlcs device. Long delay timing is obtained by the po.sitlvo '
and greatly simplify system coordination. displacement of a silicone damping fluid in a dash pot..
TD-1 general purpose timing device: Provides long A simple and rugged mechanical escapement-type
delay pickup adjustable from,80% to 160%. Instantane mechanism provides short delay.
ous trip is adjustable from iVi to 15 times coll rating. The timing device is mounted up-fi-ont-for unob-'
Three long delay band selections are available—mini
mum, intermediate, and maximum.
structed accessibility. Aeijusting screws are accessible'
with breaker in connoc' -a. j.j"; ion. The trsn-sparcnt 'ca--o
TD-2 Kolcctivc timing device: Provides long delay pick permits quick visual metniinism check. Easily read mdi-
1'.^ up .and short delay pickup, as well as long delay and cators pinpoint Lsctory-calibr-'itcd trip settings. A wide
short delay band adjustment. range of special trip characteristics i.s available. '• '• . '
l;,
V *I —. .
. <•.* , ; V.v..; - . ^ . •' IV•»;• W w; <tj J.\j K '
f'
Ij .--p'I •*..y/I
'cpi-r-i'-i «=" ''E t.~•. ' ^p
b •
' ' '—0° ..P.' ! - I
•»' ;
I . IJ .«NT.
>Ktr n -/jir I t-
y VV
II
t
!:•'
A K ,l^\xUtX* *>
i:^AiaJXKl
' I . lii •Oi
i 1:"
« 0
•i • " '
".. ... isiBi;, :;y;yv;.'oSKORTofiAY
fcSii r,-^nr'.V
TD-1 Tifflliig DeylctFrontyieW. : . .TD-2 Tiinlng bovice Front View
. . , c i - ,ir!3
...., I •-. •• •• if ••-1 'i ^
' Vi ; •• ; ' mmM IKiliC
. i;-- j .
t -<•
J V ^
' '^TDiT^tlhiirig Defe TD-2 TimihgDeviCB Side VioW' : .
•;5y / '•
•.. . •:
' : "I TRIP COIL
WITH SHORT DElftV TRIP
INTEaRUPT NO RATING
• wiTHilHSTANTANEOOS
TRIP HIH. BifiD INTER. BAND;' .Max."3SHn- :•
G CYC. 14 CYC. 30 CYC.
ASyMMHTRlOAL . STMMETRICAt
.amperes . .. : AHPESESv'..: vj . 24pV; 480V socV; 240V • 48DV COPV 240V 430V.; BOOV :240V 4C0V SQOV
, •:, is.ocQ ; •..' .-.14,000'' -'i" : IS • IS" 70
Z9 70 70' 70 : v.-w : .70 70.• . ,' .'70
• zs.MoV v, 22,000:•.• :.: 7o; • •• .'3 • v. /w 70 150 • 150 . ' 150- •••150 • .150
. . . ?0,CC0'.. ^••; ; ; .•.••«,ooo--.-
4-
' ^
'CC.OOO ; ; '."50,000 •
150'
' 5co;
7;-.ooq •'>:•'•: • .•.•••..•:'.';;ts,oo9...:' "v .:;. 500 •.;
soo 3" •
•
250.
500
;5oo..
.
-•
500
250 2;4l
1000--
250
loop"
•
.-aso;' ! '250
- '.lOOS; . ."1000,
: 2bo
'
I'T/ t f.-V •• •.*" -w-. . ^ '"i
'^,r.':A'.. Voriisge Metal-Enclosed Swfijcffgear • ••.-••
. 300 Vfilts ?i-c—23,000 to 150,000 Ainpefa$ iC Dvr ..:h-
V'"-'
i.-' •. •. :•.'
FP25-600 • „ t'• •
V
•V •'
AIR GIRaOlT V'!'
. •• i,'•" K-
BRtAKERS' I
STORED ENERGY
MECHAM.ISWi
r •' •P • f 'i;
Manually, Electrically or
Manually/ElDctrjcally ;> '• • -'i .. . .* i -'
Operated t >•;,•: s."), ^ ...\ ' ..
" rAp:' M}:..
r V I. •.r
i ?. V ^rV-..
' - • ,
DiMENSIONS!
iilAA
::-'v
•;-\v
r -Fyv;'. ^=
; • '•
• 'V i''." - •.
' 3?iiS3^m-. ^\
••3--3 -'i >'•'•' '.:-
•• • tf-' 3— -i I ... . • •
•-.-•.p .;'
iiliWiP'-
•••••.;— — - ^•.^ .1 .. .;— 1. 1-^—: .. 1 -
::'-fns-m': 480-241 35000'j.:; ;-. • • ' •; • 130000 •' > - • 3:3-;2SOOO; yAj, •22000 • .600
-i : • •"
' .'• A
240andBijloW / "•• •' mnnn • ' ,, 42000 ^ •: ;2,2POO • V-- - *• ••
\3 .3 p.--
' . ". -.- ' '." '
•r-.yy •! •
42000 . '
240 AJRI S«!ow 4?M0
Ssri^H'psiAi- r
;?• SLAS.f-
Lin^f \/o?tage xear
600 Volts a-c—25,000 tc 150,0 Ai-n^HrCi: IC Dti3C;'ip' A'O ShftOs
. •• ii<:
L"^;; - - ; •
FP75-3000
AIR CIRCUIT
BREAKER M'-; • ••
stored Energy r •
Mechanism
Electrically • :
Operated ^ ' "V 'l — " ' a I
The normal method of operating this ; i -
•ui
-
n
I
a.3
esw
• • A A-
--V- •
y . •>•>11' iV.iAAi-i
• rrJ: At-
28>y„"
1, : vli; ^
^
IHTERRUPTINC RAimS CURRENT MEASURED 30 CYCU SHORT-TIKE BATINO WITHOUT FRAME sac CON-
AT % CYCLE AFTER FAUITS, AMPERES SERIES TRIPS, AMPERES TINUOUS CURRENT
BRtAKEa
VOLTABE RATINS OF CURHENT
TYPE
CARRYmO PASTS
. •
ASTMMETRiClU. SYMMETRICAL ASYMHETlilCiL SYMMHRICAL V/ITHCUT
SERIES TRIPS
3 V :i fx • r.
r. . r a }•*»
3 ii/Pv;^U-n;-'•!
•'•X '.'w.-ii
FP100-4000
AIR cmcuiT
BREAKER
stored Energy
n;r'-'
i3'-.- ! . Meciianism ' ;
- - '••• 1 ..•
Electrically ' .' •.''('-A"' •
•t.M
Operated
• ' i -
r:%s^p?s¥";PS^ A ip :S;' •- i
'•. I vA-'-'i. ;* •• " .• '•••<'
v:,:ny- ''-i v i
>•<
DIMENSIONS:
—i
;Vt^A . ; r • s-
esii-
aV ib •
Tinniniwff
, ^''inZ-i-'A .;V,|4Uj-j-
'f
•;"-.'i-iHj''n •»
• • •" •
};i;
J^'-i
•s.'d
IHTERRUPTIKG RATING CURRENT KEASUREO 30 CYCLE SNORT-TIME RATING WITHOUT FRAME SIZE CGH-
AT U CYC.LE AFTER FAULTS, AMPERES SERIES TRIPS, AMPERES • TIHUOUS CURRENT
SREAKER RATING OF CURRENT
VOLTAGE
TYPE CARRYING PARTS
ASYMMETRICAL SYMMETRICAL ASYMMETRICAL SYMMETRICAL WITHOUT
SERIES TRIPS
i' '
^6D0-A81 100000 kWi"-- 100000 85OO0 .' i ' v •' '•
230 V. a-c
TO-l Dual Magnetic Time Ovcr-
IS 30 currcnt Trip Devices-—
one per poto X X X X
Bell alarm switch: A bull alarm switch attachment is Manual Trip Button X X X X
Manual Close Button X '
mounted on the right side of the breaker and will fut>c- Electrical Close Button —
X X •X .•
tion only when breakei is tripped by the overcurrcnt Position Indicator "Connected",
trip units. The bell alarm can be manually and/or elec "Test", "Disconnected" X X X X' •
Condition Indicator—"Opcn"- .
trically reset. Rcclosing breaker also resets the alarm "Closed" X X X X• ' •
switch. Bell alarm switch- is available with either .nor Mechanism Indicator
mally open or normally closed contacts. "Sprlnss Charced"
"Sprlnits Discharged" X X X X •
Attached Manual Closing Handle
Shunt trip: The shunt trip attachment is mounted di- *Eleptfical Ch3rs'(^2 Mechanism
X X
i-ectly above the trip shaft. It is a non-adjustable IIS a-c, 125 d-c control X X
electro-magnet intended for intermittent duty only, and Closing relay with cut off.
its circuit is interrupted only by an auxiliary contact. seal-in and anti-pump features
for maintained contact control X X . *
Draw-out interlock X X X X
Shunt close: The shunt close attachment is mounted on Padlocking Provision X X •X X
top of the stored energy mechanism and is used to elec $hunt Close device X X X
trically discharge the stored energy mechanism and Shunt trip device- —
X X X
the removal and handing of the largest type Federal Shunt Trip Oevirc X \ — 1'
arcs. The arc is confined within tv/o low-volume, high- •• MSJitnum—'.J Circuit
• 4S volt <J-c <r volt <! c are a'/ailable.
pressure parallel arc chamber.'.. This means rapid deioni-
t Eichl circuit, tncljaer. (cur spares,
sation with extremely fast arc extinction. t Four circuit
aSCI!!' « 'AKER
i •• I
Single Break
24 20 15 _
48 10 7.5
115 50 30
• ne ** p n A
i^zy ^.o £.u —
•:. -»jj;
230 25 15 l^3fXWi'^S
250 0-5 0.45 SW'l
440 _
10
—
7
.Cl 3079 "if
I t ri
600 0.18 0.12 3 2
Double Break
24 50 40 —
—
48 25 20 _
115 80 60
125 12 7 —
230 —
—r— 50 30
250 2.25 2 —
_
440 1
20 15
600 0.3 0.25 6 4
tCSl.3?S
JCSl.JS
3W'* • 2
MIDGET FUSES—Ptmensions; Overall length, T/V; Cap diameter t3/32". Carton quantity! 10
Cstaleg I CaUiog IT . ,. .1 . • -'Wi
'C«t*lDg
AjiWm Wu.Tbef I teiptrw Number gmpgi^ ' HugNwnber li Ameeres
i Ni
32 VOIW II t» V0t7S r " -
r~ Mtltl
MEItl
.15 KEM.1S
.2 . MEN.2 •
.3 MEN.3
.4 MEN.4
125 vain II •?
MENI-O
MEN1.125
BUDE
WIOTR
L!^:
ja,. * '^':''y-\\'
, 177*^7' •/ '
•• .•^^^,. -iJ-. A
-
•A' .•
.u-
If:';,-
Type 3-175 IndiratinE J.amps are dcsiRiied for use on ^ Additional spacers,. Cat<l^i'i701-012'1 (1/^7 thl-k).
switchboards, remote indicatinK panels, control desks should be used for lit' thick.
and any other applitatiuiis requiring a panel .mounted
signal or indicating lamp.
Complete assembly consists of plug assembly, re qlONNECTIONS
sistor, lamp, beeel and color cap. The indicating lamp
can be installed in panels with 14 inch maximum Connect one lead to 'sfde terminal screw on tor,
thickness. .'Spacers are supplied for panuU with less the other to binding screw at the rear of rec-.cl.rc'e. '
than inch thickness.
The terminals of receptacle are de.signed for Nj .'.2.
wire which may be inserted and .squeezed. Smaller ci/'-s
Color caps are available in five colors: red, green, should be wrapped around terminal screw.
ambor, blue, and white.
Resistor pigtail should be coivaectcd to the remaiiii-'iT
receptacle terminal.
RATINGS
•to " • .-
'm
.-. RE6I5T0H5 • ; _
•I', Oesciption
lage; . o-t J*. Ohini Seivict Voltage
^/9ff«ne ilO "24
2701-0116 800 • 50
2702-0116 140O 70
2703-0116 2900 US
2704-0116 3200, ,- 125
• -0
2705-0116 5800 . 208 .
2706mU6 • 6500.'• 230
V-' •^' -i
-'•!.••• «« 2707-OnS 7100 , ' 250
imiBAIlHC UMP HUTS
...
0<ryERING INFORMS iv
••fai " rnmpl'ilo indicaUr.K: lamp asaemWy—specify botJi obc required and the catalojr number^-of the desired
'iilalosr number of the indicating; lamp of the-Voit- color cap. , •• •
.•••••• ..;-4
fiiff-'- :5ioNs
Irr MAX.
ORILIING PLAN
' I
• •;
KE 1 .•s.i • /.'
' • '•''••;• '.1
--4>
-•A:.. -
j* if TYPE VD
. I
TYPE VFN
mm.
APPLICATION
Key interlocks are attached to mschantcal and electrical S'cindard arrangement is for the key to be renpNT
device? to insure a safe prtxictermined sequence of oper the "plunger extended" position only. The opposite
ations. Hie intcrlc^c':? are a simple mechanical device be supplied at no addilicnal charge when specified.
that a.rc pi'.titivc ir ->ction but very difficult to defeat and
may bt .itlached 'n any equipmeni v;h:'re it is possible TYPE VD
to engage irio'.'iny operators. This lock is used on removable or hinged panels a:.d
Various acccssrries are available to extend the basic supplied with
vr«1(l an
<UA accessory
<lWvS>»dUi^ iatch
iUlViJ block which is illVAlll'.V.
VYXiiWU 19 moiintc > V''
operation of tiic interlock for control circuit switching. to &B Stationary part oi' the mechanism. The lock hdus >.
However,,it shotildbe rcmemhcrci tliat ilie reliabflityof mg is
ic mounted on the fArMj^xrnKfn
iTi^T removable rxairfr
part and
unH once
t^nia It ir
Ii.' •'
such arratigomeni? mus' dcpem' on tho rcliabiUty of the ^cmo^'ed from the latch block tlie ke\' is trapped pnd can-
control source and .should "iai' safe" in the event of a
II.X' be removed. In all other respects tltis lock asse.a'-ly
power failure. is identical .o the Haste locks previously described.
TYPE T
INTERLOCKS - Typf- VB. VF. VFN
the type T is a traasfcr'interlock desigilcd for .a key
These imerhiuk.s f^rm the basic group of mierlocks used
;ni-.:rcliangc and usually consists of.a master IcKk and
in aH application-. Tlte choice bet'voyn locks in this
or more Tclsase locks.
group depends entirely on the •mounting arrangement
preferred; Honslttgs arc of brass either machined from In operation the key to the,master lock is retjuned. ilntO - .-m
bar stock or cast, and carry the 5/P" diameter, bfass all. the release keys are.'insened in the lock'.assembty,'
plunger in exactly rhc same relatioasblp to the lock. then the master key can bc r^oved and ia.s.? doing •
Plunger travel is 3/4' and the plunger exren'sion from traps all the release keys. •'
the Uv;k body in the ret<-.,ctcd position may be any one Nry combi:=ation of master and release ,s is posrir'e
of six siaiKi. .-'1 irnyi'ts. Nisii standard pmjecdons can b'ji it should be noted there is no extc ual pluTrger.fo:-
be stippficd •I. additjonal cost. locking operation. " •.
• -•.bli.S
TYPE VF
•m
1r rf-
U rJ —« - -f
Tl 1(
IBBi
SEMI-FLUSH MOUNTING
FLAT PANEL
URFACE^ MOUNTING - fr ]•
FLAT OR DISHED PANEL
is
1 U-, y
V ' . fr
[• T]—- !'
.fe-'i li • --
li rl
vrt-j v---:-L-
SEMI-FLUSH MOUNTING
DISHED FANEL
DRIUINCi DETAIL
J6 /'-
1 I 'Us
. .Hi-ECTRJC COrV3:RANY
•- i;. _ ^•'••'eET.'.NPWAR«;-N =w'JEPSEy
Lo'v- ''>"^ K "ai^r^einT?;- ''-r"* "' " :."•-
Im
FEATURES
Tamper Proof: Stiids permanently mounted on case ' 1 1'^""
])roliibit removnl of instrument cover by unauthorized 'Vv- ,8-5 iRJjjBtnsrtt—.. .•]<,•!
personnel. Instruments nre flush mounted on panels
uptolVi''.
Accurate: 1% of full scale value, V, • •
Zero Adjustment*. Zero adjuster is provide<l on front Long fecale': 7 inch, scale fiieilitjrtifis'reading, reduces-' 'C",'''
window for quick and easy scale adjustment. errors. • • y'-l/'t-vi''',.:
• . ' •• ' • ' -'(-"rO'i- "y''-
Standardized: AU type's and ranges housed in standard Instrument Ranges: Ammeti-l—S asnp.erB'coil; or self* ,
casing. contained to 20 amperes." • "
Specification: All instruments conform to ASA stand •VoTtmetc-r—150 volt coil; or s;-iI-.-:-mtnin«d to 800 volts." ..' '^^'5
ards C 39.1. Wattmeter—5 amperes 130 volt roiif:
•'1 • .
M.l • !• •
Insulator 4 • 'iki
•".r.npliig 3c>'>
V-'ItbO"*. ZtVf
fe'M
fiW.
August, fSiSe: ^
F.EDERAI. iPACI.FlO ei-ECTF?IC COMRANV^^
•)-'"-Jl!7 'lifts :
. .T
.KT"'-:
' 'f-',
1:5'4.1
.ifv
"•VT- W ' m.
•IT''?:!
'' m'
f?' 30 •
.tT "-b--
•V j. «n<Ti *"
kZl:
• V- J3*'
jSWv,
, typiwi .il-C,JAgtfiil^Typs .iD
-;'-I''- . --i : •• y'ri-
5":
'h
0—lOOwattt
o-^OO wMU
P—1 KW.
&—IJKW.
0—2KW.
KW.
.y W
iia .I."''
.jneters (See nuir G) .
: iZO vnils 0—- KW, •
y /::•
: 240 yotts O—• KW.
' atid furnished with pair of traasformor having 150 v secondary. Insert this
i. Insert value in place of ®" value.fn place of e.g. JA-150W-1500VV
o. Select full sc.ale value to suit application and insert
' e to suit application, and insert m ylace uf * Indicate product of current trans-
•D.001M.\-:5000y\'. KxternaJ re- fonner i-a:io and potential transformer ratio e.a
a. re!|uired; availauie separately. JA-0011CW/.141/I2<!-75KW for use wth S00:5 c.t.
vaiiie to suit priuiary of current and 2:1 p.t. indicating 75 KW full scale.
3/•-p secondary. Insert this value 6. Burden on current circuit—2.1 va. per phase.
rV • • 005AA-250AA. Burden on potential circuit—.5.5 va. per phase.
'>•1 I . -I-'X,
r /• ^.^•v
'".•V Mm
^•• •^- ^r-
^a-V''v
.• , I-
V" • ^
•- '-it yy\
i • - S
^1-''. li'iS .i-'Vl'tiSl iV'V'"' •
15 KV Typi! lI Interfiip'-fiv S\/tUT. witii Manualiy operwrtJ
Staretl &eri;y Meshanism. ' .
•'•CV.XL. ei-.H'CVlF' •
I'll)
'• ]»'• ; •
3, >1*8
'^1^.
FU^E KIT PURCHASING DATA*
Fata fypt .. Rni Ul
sa'c- "j wST Cals'ag flsBiMr
. ., EJO-l-O" - SM-*- 1 • Cl'£-r
E30;!-a0 t SM-5, ' 2631'1«!I6
SlE-2
OA-ZOO. ytalcd '
'V £»-l-0
E)9-l-90
$M-4
SM-S
SA-200. w<)A
-<cnOeater if.,
' 2S52-JAM
E»-l^£ . ei!:''a/ge !
Altar • I
OROEPJNG INFORMATION*
- W*-
•f
•,
•'
V
•>
". >•
•- — -rt _ ^ rj:
•• «;• j, •
AU Federal Paeifie's Tvpu I'FH" trarisformers arc shipped Type "FH" trar..sfornK-r.s 225 KVA and below arc supplied with
niountcd on ciiiicr a sHid. or In the case of the snral.f'cr sizes, Korfund isohitors which .should he placed under the four, cor
on a pallet. Adequate size and strength of the skid- or pallet ners of tlie unit wh-en it is floor mounted for full isolation of
insures protection during shipment and ease of handling. The vibration.frora the buiiiiing stcucfure. This isolation in adiiftion-
transformer lionsing is covered with a he.'ivy laminated'paper to the internal isolating monnis will provide a ma.ximuni of
and the complete tfansformcr is cither b.andcd to the.-pallet or vibration isolation and sound reduction. Those transformers
.bolted to the skid. : .. suitable,.for wail hiounting art- equipped with brackets for this
purpose; The heavy angle.br.-ickets mounted to.the base are
Core and Coils designed, to carry the transformer's weight when bolted lo the
building structure. The top .slide-type brackets are intended to
Core and cods shipped from the Federal Pacific factory i.s hold the transformer in an upright position. ..
.skid moiinletl .an! overcd with protcoled iv.per wrapping, and
ha-.-c !i protccti-.-e box frame covering the complete'structure' Type "FH" transformers 300 KVA and'aboive are also equipi\c(i
to insure that ilu itaiisformcr will not be 'l;un.e:ed with normal with vibration Isolators, l lbwevci-.-becaiise of the weight o'" iht-se
handling durinesh.nnnoi:.- trnnsformcrs, the vibrrition isviviors ,-uc made ineffective (•iifim:
.shipment .by the piaccmeni of r.-d -nipping bars in parailci -,vi;l:
the isdlallng maieriiil. Upon insiaiiaiion f/ie hnli iloy.i: iteim;
ypoEHS
painted red and the shipping bars also painted red shnni'd he
R12CB5PT' removed io permit the core and-coils to be eifectivciy i.solaidd. ... •
• 'v.-.'I;
Ail transformers leaving the Federal Pacific Fleci'ric factory arc The bolt down items and isolation shipping bar ctin b'o stored
in first-cl.iss condition. Therefore, upon arrival at destination a within the transformer housing so 'as to be readily r>v.tilabie
visual inspection should he m.ade pi lor to unloading, to deter-' for use in the event the transformer ever need be removed
mine any evidence of rough handling. If damage is.cvidcnt or from its installation site. .. i; •
•;any'indication of rough handling visible, a claim shouici be filed
• •.immediately with the carrier and noilficailon of this claim
If fishould be.sent to the Federal Pacific Electric salcsntan. • 1.0CATi0N
For satisfactory operation transformers should be so positioned
as not to restrict free air flow through the transformex louver.s.
-No fixed rule applies; however, the larger tlte air: circulation
'. <'V.,
'' I . = :•
: .PalJel-s and skids are constructed so.that all inmsformers may louver, the farther from a wdU it should-'be piaccdt Tlte small
be,moved by a forkiift truck. All tra'hsformers in.iy be skidded, lighting transformer need only' be placed two inches froni a .
• draped or rolled into position on their shipping forms. Lifting wail whereas a large power transformer should be ptaecd at'
least six inches from a wall. Good air circulation is essential '
I •; • 1 / eyes are provided on all transformers and are of sufficient in the-area in which a dry-type transformer is installed. There
' ..strength, to permit overhead* lifts with a crane. i ...
! --.'vr. .5 shoiild be available at least one. hundred.cubic feet:of air per
••i;OkVdv Federal Pacific trarisformer shouid'bevlhid on-its minute per kilowatt loss of 'thc trahsforfher. Sticli a volume
'- V-1. /'•'iside fof'any reason. All transformers arc supported on vibra- of air will iestrict the ambient afr ris'e.in the rbom to less-than
"tion_.isolators underneath the core-and coll stru'cture find this 10° centigrade. To determine the air requirements of a planned
••.. isolating material could be damaged beyond repair if the trans-: instalintidn, :the KVA size of-transformer to be used and its
. •T'fornier is.tnrncd on its side. : ' .' i,/',;
full load total watts loss,should be used -to calculate the above
V '"fi' ;t'A .spreader bar need only Iks'us^d on the large power sized air requirements.
I'*!?'
encased dry-typc trnnsformcrsi This is because the lifting
arc-fastened to the base and long lifting cables or sling might ^ Transformers weighing in excess of "one thoiisand pounds
should be installed close to a main, building, support to insure
'l'!.
• possibly crush the casing unless a spreader is used. a minimum of vibration transmission throughout the structure.
• iH
STORAGB COL^SiMECtSO'^S
Dry-type transformers preferably should be .stored in a warm Wiring compartments are provided at the bottom .of the trans
, do' location with uniform tcmpcraiiire. 'Ventilating openings former enclosure. Knockouts arc not provided because.of the
should be kept covered to keep out dust. If It is necessary difficulty of insuring the correct size and the chrrcct location
.to leave a transformer put of doors it should be thoroughly .for eachvinstallation. However, both cnds..as';wolI as Ihb: rear
'.protected to prevent moisture and foreign material froth ciitei- and bottom, of the wiring comparlnienl arc :suitabie cable en
ing. Conden.salion and the alisorptihn of moi.sture can be greatly trance'areas. All'transformer terminals'are rigidly supported
; reduced by the insiaiiaiion of either heat lampsor space heaters. to insure that no damage occurs to the coils during the period
Transformers arc e.iipensive items^of electrical equipment and the connections arc.made-to the transformer. A complete per-,
should be treated with reasonable care in choice of storage mancnt connection diagram is included as: arf intcgral part of
location. . • . the transformer nameplate.
•|':-v r-- •• a'l ,
qiiir; - .-.•e •••
All COP,- and coil sliuc'iircs. aUiioiigli isolated from thi:. trans moisture iron: : - ••.•.andiTei;:ic .s
former casing by vibration isolators, have a flexible grounding .dirt upon ir.ialaiioii h.oconiL.-, r In., in .vhnion
connection which insures that all non-ciirrent carrying parts absorbs, a consicici'.ibic anionni , t moj-i'nre .iud the sui-aec i-,
arc at the same potential. Standard practice of adequately contaminated; It h atit isr.bie to •.spec; aiiil clean any -f ne
grounding the ti-ansformer to the station or circuit ground transformer susnccted of havi'v; ireen cont.'smiiiatcd v ti' diji,
should be followed. If this procedure is followed no danger and moisture, especially print lo rc-encrgizins
a, opcaf'tS or maintenance personnel.
©PiElRATaOS^
It is advisable to drt' ;-,i' dry-type transforniei jvliea
.To maintain safe operating conditions do not remove covers, been known to have beer eXDOSttd to long |ieri'HK
of panels over openings in the trtinsformcr housing while the humidity-or other moisinre. Whenever mpiiiur ; vj : ..;;otr.
transformer is energized. the surface.of ihc in'-.v.irnioTi. ii must be cii-i-.-.i i i- • iri. n::ir-
./ormer's ability to retain its electrical strength. However, in- former. ,\ttempts htivc it.-cn made to :-.feei/y'rcs!siu:ic DCS;
sonic instances if is necessary to install Type "FH" transform- which wiirindicate, IninMormcr uryr.csr, .nal dielecliic tiieii.eib.
,ers opt of doors with the proieclibh afforded cither by rain The nature of the'-insuhiiioh ti.scd; in drynyite irwvtV.rnttTs is
shields or a building shelter. Under sueh conditions of operation such thtit megger feaUinyt cannot be relied upt.T,.
the greatest reliability will be obtaincci if the tra'iisfpfmer ,is
continually, under load./Condensate,may form and ti'ltimaicly
be absorbed in the insulation" if an outdoor triinsformer is de-
.energized for .long periods of time. If such a situation arises,
.the transformer should be inspected for visible signs of moisture
.oil the core and coils, before rc-energizihg. If moisture is ob-:.
TVansformers/iiypc "HH" 50t kVA and above may l-r tup-' :
plied with supplemenlti! fan cooling. Fan motor mtiiiMcnance
served the transformer, shdiild bo dried as indic.aicd in the
consists only of. periodic iiibricalion if used froiiueidK. No
paragraph under DRYING.
maintenance is feqiiired on thc'diai-iype thcrmoipelct and al im
cbmaets which coiitro! the circuit.. Since the dial-type
Type "FH" transformers may be loaded in accordance with eter is of the bourdon type, the therniometcr cither uvil.s/.
the ASA loading giiidc for dry-type transformers. accurately"or not at till. It will only fail to oper.ite .i iht
bourdon tube ;is punctured and loses its liquid pressure. The.
Caution: Under no conditions should Type "FH" transformers
control and alarm, contacts are of the micro .switch v.iricty and
be.asked to carry more than 110% overload for a long period
suitable for many hundreds of thousands of oportitions.
of time for the reason that extreme temperatures may de
velop and cause transformer failure. If It is necessary under
emergency conditions to exceed this value of loading, fan .SURGE pnoTtBormm
cooling should be added as an emergency measure. Adequate
•forced air cooling will permit load increases of 33'/<% of
For normal opcrtition on protected lines dry-type transfornii r>
nameplate rating. Type "FH". transformers 501 KVA and
need no surge proicctiou. However, when these ininsfonuers
above may.be purchased with factory supplied supplemental.
are. applied to circuit.s with some exposure to lightning surges •
fan cooled rating,
it is advisable, to protcct with'suitable lightning avrcstors. The
•Form 28 and: Typo RM arrestors. will give adcqnute protection,
when properly,'chosen for thc'vqliage rating they are to protect..