Professional Documents
Culture Documents
Analysis of Earth Resistance of Electrodes and Soil Resistivity at Different Environments
Analysis of Earth Resistance of Electrodes and Soil Resistivity at Different Environments
net/publication/234116820
CITATIONS READS
7 2,110
4 authors:
Some of the authors of this publication are also working on these related projects:
Experts for Africa - Graduate Training EE, HV, lightning and electromagnetic compatibility View project
All content following this page was uploaded by Chandima Gomes on 01 June 2014.
Abstract— Theoretical calculations have been done for parameters may quite be problematic in cases such as on the
determining the low frequency earth resistance of a set of rock tower sites in remote areas, as the repeated delivery of
individual electrodes, once the electrode dimensions, installation materials and site accessing is restricted due to various
geometry and soil resistivity profile are given. Accuracy of constraints [6]. Under such circumstances it is highly
theoretical estimations was tested by taking measurements of 25
necessary to have accurate set of models to determine the
electrodes installed at various soil conditions and environments.
It has been found that in most of the site locations, especially electrode configuration, once the soil resistivity profile and
vegetation and built-up environments, model predictions deviate required limiting earth resistance is given. It is also required to
considerably from measured values. Three dimensional soil find the optimum solution for a given system (power, signal,
resistivity map of a given land mass is essentially needed in lightning protection etc) that will have minimum material cost
predicting the final earth resistance of a given electrode system. without compromising the safety. Such requirement arises as
Existing models are not able to produce the large variation in the same limiting earth resistance can be achieved for a given
earth resistance, specifically due to the non-uniformity of soil installation by different electrode arrangements. The models
resistivity and probably due to the contact resistance between developed need verification of their predictability in a real
electrode and surrounding soil. The outcome of this study will
situation and investigation on various other factors (presence
immensely be helpful in designing earthing systems for a given
installation even at pre-construction stage. of vegetation, built-in environment, contact resistance,
seasonal variation etc.).
Keywords-ground resistance; grounding; environmental In this study we investigate many of the above issues with
factors; electrode; soil resistivity; contact resistance, vegetation a view of developing a set of models to pre-determine the
required earth electrode design for a given installation.
I. INTRODUCTION
Designing of an earthing electrode system to meet required II. METHODOLOGY
low frequency earth resistance is one of the biggest challenges Equations developed previously and published in literature
that an electrical engineer encounters. Based on various have been used to calculate the variation of earth resistivity for
electrical engineering standards the limiting earth resistance many different combinations of electrode length and cross
that should be achieved for a given installation differs. This section, number of electrodes and their orientation, soil
limiting value may vary from 10 Ω for most of the lightning resistivity profile, buried depth etc.
protection to as low as 1 Ω for substations and large scale Following the calculations, the validity of outcome has
switch yards, while for telecommunication systems a middle been checked by taking earth resistance of earth electrodes at
value; 5Ω or 3Ω; is recommended [1-5]. different locations. The locations selected are
Most often engineers use their long term experience or a. large open spaces with nearly uniform soil surface soil
trial-and-error techniques to determine the suitable electrode resistivity profile
system. However, such methodology sometimes leads to high b. land plots near built-in areas (close to buildings with
cost and practical complexities as either the system is under- varying depth of foundation)
designed, needing more electrodes or over-designed wasting c. land plots in the proximity of vegetation (large trees
material and labour. Grounding system designs that deviate and thick shrubs).
very much from practically achievable ground resistance
The soil resistivity profile of the selected site has been
measured by a 4-pole ground resistivity meter (MEGER
DET5/4R). Measurements were repeated for better accuracy.
Earth resistance measurements of the electrodes were taken by
a digital earth resistance meter KYORITSU MODEL4105A,
which works on fall of potential techniques. Each
measurement was repeated in perpendicular directions and the
average value has been taken for analysis. To determine the
effect of electrode-soil contact resistance, for selected number
of electrodes the measurements were repeated on daily basis
for a period of three weeks.
In this paper we present only the results obtained with
single deep driven rods installed at various locations. The
theoretical equation developed in the literature [7] for the
estimation of grounding resistance of such electrodes is
7 cm
Figure 2. The buried rod before covering the exposed part with
metal can for protecting from rain.
Where:
R = resistance of the single electrode, Ω
L = length of electrode, m The five sites where the measurements have been taken are
a = radius of electrode, m detailed below.
= soil resistivity, Ω m
Site-1: A land adjacent to a large water mass (artificial lake)
Steel rods bonded with 250 micron layer of copper have and a small building complex. It is flat lowland which
been used as earth electrodes (Fig. 1). each rod has length temporarily floods during heavy rain (Fig.3).
1.65m and diameter 13mm. Twenty five rods were installed at
five sites (five rods at each site). The rods were forced driven Site-2: A land next to a large building complex from one side
into the earth using hammers. Rods have been installed at and the rod. A small lake is situated within about 100 m. This
buildup environment (manmade structures), natural is also lowland subjected to temporarily flooding during the
environment (vegetation and water masses such as lakes and rainy season (Fig.4).
ponds) and open area. Installation was done in such that 7 cm
segment of the upper part of the rod protrudes above ground Site-3: A barren land on a hill. From the site, there are about
level for measurement purposes (Fig. 2). An exposed part of 100 m to the nearest building. It composed of very dry rocky
the rod was covered after taking the measurements to prevent soil. Except for few low-height bushes there are no vegetation
rainwater from contaminating with the electrode. in the area (Fig.5).
Site 1
B4 2.2m
Lake in 33.2m
faculty of 0.5m
A3 16.6m 3.4m
5.5m
engineering
(UPM)
18.1m 9.1m Academic 0.4m B5
Complex B1 B3 4.2m
10.4m 16m
17m
A1 A4
3m
1.3m
45.1m
8m
6.4m
B2
A2 2m
2.6m
5.6m A5
1.6m
Walkway
Banquet Hall
Hill
1.3m C3 4m
C2 11.8
m
14.4m
Slope
17.7
C1
m
2.8m
14m
C5 16.4m 6m
C4
1.5m
6.7m 2m 5m
D1 4.5m
D2
9m 7m
24m
D3
Solar Panel
10.7m
2.6m
14.8m D5
D4
Figure 4. Site-3. C1-C5 are positions of electrodes Figure 5. Site-4. D1-D5 are positions of electrodes
III. RESULTS AND DISCUSSION
E3 13.6
E2 1.2m
n
B
a. Close to built up area
13.9 m o
a
b. Close to vegetation
E5 m r
d c. Close to water mass
4.6m E4
4.6m d. Away from any of the above.
Comparison of ρs (red) and ρa (blue) Table I shows a detectable pattern of variation. In both cases
2000 of near the water and near the built up area soil resistivity
1685 1685 1685 1685 1685 Δρ shows higher values than the average soil resistivity for the
Soil resistivity, ρ (Ωm)
ΔR%
32%
-10% 0 2 4 6
20%
18% -20%
10% 15%
-30% -21%
0% 9% -32%
-40%
0 2 4 6
Earth electrode A1- A5 Earth electrode A1-A5
Figure 11. ΔR for each electrode at Site-1where Rc is calculated by considering ρs and ρa as soil resistivity
-10% 0 2 4 6
ΔR%
-20% 0 -32% 2 4 6
-20% -40% -19%
-36%
-30% -60%
-66%
-40% -80%
Earth electrode B1-B2 Earth electrode B1-B5
Figure 12. ΔR for each electrode at Site-2 where Rc is calculated by considering ρs and ρa as soil resistivity
41%
34% 40% 50%
20% 44%
27%
20% 30%
0%
0 2 4 6 0%
Earth electrode C1-C5 0 2 4 6
Earth electrode C1-C5
Figure 13. ΔR for each electrode at Site-3where Rc is calculated by considering ρs and ρa as soil resistivity
ΔR at each electrode where ΔR at each electrode where
Rc is calculated by ρs Rc is calculated by ρa
40% 50%
27% 27% 14%
20% 34%
0%
0% 21% 0 2 4 6
-20% 0 2 4 6 -50%
ΔR%
ΔR%
-27%
-15%
-40% -100%
-60% -39%
-150%
-80%
-87% -155%
-100% -200%
Earth electrode D1-D2 Earth electrode D1-D2
Figure 14. ΔR for each electrode at Site-4where Rc is calculated by considering ρs and ρa as soil resistivity
ΔR%
0 2 4 6 0%
-20% 0 2 4 6
-15% -14%
-40% -50%
-47%
-47%
-60% -100%
Earth electrode E1-E2 Earth electrode E1-E2
Figure 15. ΔR for each electrode at Site-2where Rc is calculated by considering ρs and ρa as soil resistivity
Deviation of Rc from Rm as shown in Fig. 11 – 15 indicates There are no apparent relationships to the values of ΔR and
that irrespective of considering average soil resistivity of the the location, in either cases of using ρa or ρs in calculating Rc.
site or soil resistivity specifically close to the electrode, the However, it is of interest to investigate how these observation
calculated earth resistance of an electrode by the empirical will change (or remain the same) as the depth of the electrode
equations given in the literature has large variation from the increases.
measured values. Interestingly in some cases the calculated It should be noted that the above observations may also be
value may be higher or lower than the measured value affected by soil compactness which in turn determines the
depending on what soil resistivity parameter has been used in contact resistance between the earth electrode and the
the calculation. However, in the comparison of extreme cases; surrounding soil. Loosely bound soil may give poor contact,
cases where ρs is considered for calculations there were 11 increasing the overall earth resistance of the electrode.
cases where ΔR is less than 20% and only two cases ΔR where
is greater than or equal to 50%. The same two parameters for IV. CONCLUSIONS
cases ρa is considered for calculation are seven and six One of the basic drawbacks of empirical formulae
respectively. This shows that using the soil resistivity at the developed in the literature in calculating the earth resistance of
location close to the electrode gives marginally better grounding systems is the non-specification of what soil
estimation when the earth resistance of the electrodes are resistivity to be used as the input parameter. In a given site the
calculated using the empirical formula. However, a larger soil resistivity varies with depth as well as location. Hence the
sample is required to make solid conclusion in this regard as even at a given depth the average soil resistivity at a site and
well.
soil resistivity in the proximity of any specific location may
have a difference over 50%.
Our investigations show that the soil resistivity at a given
location has some dependence to the environmental factors.
Soil resistivity within about 5 m from water masses and built-
up area may have higher soil resistivity than the respective
average values of the site. In contrast, close to vegetation the
local soil resistivity tends to be less than the average resistivity
of the site. Somewhat similar observations have been made
earlier as well [8].
No matter whether ρa or ρs, has been used, the calculated
earth resistance of an electrode by the empirical equations may
have large deviation from the corresponding measured value.
However, marginally more accurate results can be obtained by
using ρs instead of ρa.
Apparently there is no correlation between the percentage
difference between the measured and calculated earth
resistance, Δ, and the location of the electrode, irrespective of
of using ρa or ρs in calculating Rc.
The above observations should be further investigated with
larger sample size. The readings should also be repeated after
about one year to investigate the effects of soil compactness
which may affect the contact resistance of the electrode and
the surrounding soil. However, with information available so
far, it can firmly be confirmed that there are many flaws in the
empirical formulae, in their present state, in calculating
accurate estimation of earth resistance of a given electrode.
ACKNOWLEDGMENT
This research has been supported by Grant No: 05-01-11-
1195RU/F-RUGS. Facilities provided by the Department of
Electrical and Electronics Engineering, Universiti Putra
Malaysia is greatly acknowledged.
REFERENCES
[1] IEC 62305: Protection against lightning, 2006
[2] IEEE SDT-142 (Green Book), IEEE Recommended Practice for
Grounding of Industrial and Commercial Power Systems, 2007
[3] IEEE Guide for safety in AC substation grounding, IEEE Std.80-2000
[4] ITU-T REC K.27:1996, Bonding configuration and earthing inside a
telecommunication building, 1996
[5] ITU-T REC K.31:1993, Bonding configuration and earthing inside a
subscriber’s building, 1993
[6] C. Gomes and A G Diego, “Lightning protection scenarios of
communication tower sites; human hazards and equipment damage”,
Safety Science, Vol. 49, 1355–1364, 2011
[7] Elya B. Joffe, Kai-Sang Lock. “Ground for Grounding”, A Circuit-to-
System Handbook. Wiley, IEEE, 2010
[8] Yamaura, I.; Tanaka, K.; Yajima, M.; Takahashi, N.; Yamada, K.; , "An
estimation method of ground resistance of trees growing in different
lands," Instrumentation and Measurement Technology Conference,
2002. IMTC/2002. Proceedings of the 19th IEEE , vol.2, no., pp. 949-
952 vol.2, 2002.