Download as xls, pdf, or txt
Download as xls, pdf, or txt
You are on page 1of 4

BUSBAR SIZES

RATED CURRENT CBB SIZE AMPACITY

16 1/8 X 3/8 46
32 1/8 X 3/8 46
40 1/8 X 3/8 46
50 1/8 X 1/2 62.5
63 1/8 X 1/2 62.5
70 1/8 X 3/4 93.75
80 1/8 X 3/4 93.75
90 1/8 X 3/4 93.75
100 1/8 X 1 = 1/4 X 1/2 125 = 125
125 1/8 X 1 = 1/4 X 1/2 125 = 125
150 1/4 X 5/8 156
160 1/4 X 3/4 187
175 1/4 X 3/4 187
200 1/4 X 1 250
225 1/4 X 1 250
250 1/4 X 1 250
300 3/8 X 1 = 1/4 X 1 1/2 375 = 375
320 3/8 X 1 = 1/4 X 1 1/2 375 = 375
350 3/8 X 1 = 1/4 X 1 1/2 375 = 375
400 3/8 X 1 1/4 468
500 1/4 X 2 500
600 1/4 X 2 1/2 625
800 3/8 X 2 1/2 937
1000 1/2 X 2 1000
1200 1/2 X 2 1/2 1250
1250 1/2 X 2 1/2 1250
1500 2 PLY 3/8 X 2 1500
2000 2 PLY 1/4 X 4 2000
3000 3 PLY 1/4 X 4 = 2 PLY 3/8 X 4 3000 = 3000
4000 4 PLY 1/4 X 4 4000
5000 5 PLY 1/4 X 4 5000
6000 4 PLY 3/8 X 4 6000
MOTOR CURRENT
POWER 1 PHASE 3 PHASE
KW HP 220V 220V 440V

0.37 0.5 3.88 1.98 0.99


0.55 0.75 5.2 2.72 1.36
0.75 1 6.59 3.5 1.75
1.1 1.5 9.6 5.16 2.58
1.5 2 12.7 6.8 3.4
1.8 2.5 15.7 8.41 4.2
2.2 3 18.6 9.98 4.99
3 4 24.3 12.9 6.4
4 5 29.6 15.7 7.9
4.4 6 34.7 18.6 9.3
5.2 7 39.8 21.2 10.6
5.5 7.5 42.2 22.6 11.3
6 8 44.5 23.8 11.9
7 9 49.5 26.4 13.2
7.5 10 54.4 29 14.5
9.3 12.5 66.8 35.7 17.8
11 15 78.6 42 21
15 20 103 54.7 27.4
18.5 25 127 67.5 33.8
22 30 150 80 40
26 35 92.5 46.2
30 40 105 52.5
33.5 45 117 58.6
37 50 130 65
45 60 155 77.5
52 70 180 90
55 75 192 96.1
60 80 204 102
67 90 229 114
75 100 253 126
90 125 311 156
110 150 369 184
132 175 423 212
150 200 482 241
160 220 520 260
200 270 640 324
220 300 710 357
250 350 823 406
315 425 1000 511
355 475 1112 568
400 535 1271 650
450 610 1410 688
475 645 1490 730
500 680 1570 770
560 760 1750 860
600 810 920
670 910 1030
IEC PROTECTION

First Digit-Protection from Solid Bodies Second Digit-Protection from Liquids

0 Unprotected 0 Unprotected
1 Protection from solid bodies of not 1 Protection from vertical water drop fall
exceeding 50mm
2 Protected from solid bodies of 2 Protected from water drop fall
dimension exceeding 12mm inclined by 15 deg. max
3 Protected from solid bodies of 3 Protected from rain
dimension exceeding 2.5mm
4 Protected from solid bodies of 4 Protected from water splashes
dimension exceeding 1mm
5 Protected from dust 5 Protected from water jets
6 Totally protected from dust 6 Protected from waves
7 Protected from immerson
8 Protected from submersion
COIL CONSUMPTION IN VA

Control Transformer = VA of Contactor x 1.5

MC PULL-IN HOLDING
B9 75 9
B12 75 9
B16 75 9
B18 75 9
B25 97 10
B30 97 10
B40 195 19
B50 195 19
B63 195 19
B75 195 19
EH80 325 25
EH90 325 25
EH100 490 35
EH145 490 35
EH150 900 55
EH160 900 55
EH250 1200 70
EH370 2900 105
EH550 2900 105
EH700 4000 10
EH800 4000 10

You might also like