The document discusses electrical system design and protection of generators and feeder cables. It outlines requirements for overload protection, short-circuit protection, thermal damage protection, reverse power protection, prime mover shutdown protection, and undervoltage protection of generators. It also requires overload and short-circuit protection of each feeder conductor at the supply end by a circuit breaker or fuse with disconnecting switchgear. Protection settings are not to exceed cable ratings except where starting currents need consideration.
The document discusses electrical system design and protection of generators and feeder cables. It outlines requirements for overload protection, short-circuit protection, thermal damage protection, reverse power protection, prime mover shutdown protection, and undervoltage protection of generators. It also requires overload and short-circuit protection of each feeder conductor at the supply end by a circuit breaker or fuse with disconnecting switchgear. Protection settings are not to exceed cable ratings except where starting currents need consideration.
The document discusses electrical system design and protection of generators and feeder cables. It outlines requirements for overload protection, short-circuit protection, thermal damage protection, reverse power protection, prime mover shutdown protection, and undervoltage protection of generators. It also requires overload and short-circuit protection of each feeder conductor at the supply end by a circuit breaker or fuse with disconnecting switchgear. Protection settings are not to exceed cable ratings except where starting currents need consideration.
The document discusses electrical system design and protection of generators and feeder cables. It outlines requirements for overload protection, short-circuit protection, thermal damage protection, reverse power protection, prime mover shutdown protection, and undervoltage protection of generators. It also requires overload and short-circuit protection of each feeder conductor at the supply end by a circuit breaker or fuse with disconnecting switchgear. Protection settings are not to exceed cable ratings except where starting currents need consideration.
Generators are to be protected by circuit breakers providing long-time delay overcurrent protection not exceeding 15% above either the full-load rating of continuous-rated machines or the overload rating of special-rated machines. Alternatively, generators of less than 25 kW not arranged for parallel operation may be protected by fuses.
9.11.2 Short-circuit Protection
Generators are to be protected for short circuit by circuit breakers provided with short-time delay trips. For coordination with feeder circuit breakers, the short-time delay trips are to be set at a suitable current and time which will coordinate with the trip settings of feeder circuit breakers. Where two or more AC generators are arranged for parallel operation, each generator’s circuit breaker is, in addition, to be provided with instantaneous trip set in excess of the maximum short-circuit contribution of the individual generator. For generators of less than 200 kW driven by diesel engines or gas turbines which operate independently of the electrical system, consideration may be given to omission of the short- time delay trip if instantaneous and long-time trips are provided.
9.11.3 Thermal Damage Protection
Generator circuit breakers at the main and emergency switchboard are to have tripping characteristics and to be set such that they will open before the generator sustains thermal damages due to the fault current. See 4-8-2/9.7.
9.11.4 Reverse Power Protection (2006)
A reverse power protection device is to be provided for each generator arranged for parallel operation. The setting of the protective devices is to be in the range 2% to 6% of the rated power for turbines and in the range 8% to 15% of the rated power for diesel engines. A setting of less than 8% of the rated power of diesel engines may be allowed with a suitable time delay recommended by the diesel engine manufacturer.
9.11.5 Prime Mover Shutdown
The shutting down of the prime mover is to cause the tripping of the generator circuit breaker.
9.11.6 Undervoltage Protection
Generators arranged for parallel operation are to be provided with means to prevent the generator circuit breaker from closing if the generator is not generating, and to open the same when the generator voltage collapses. In the case of an undervoltage release provided for this purpose, the operation is to be instantaneous when preventing closure of the breaker, but is to be delayed for discrimination purposes when tripping a breaker.
9.13 Protection of Feeder Cables (2005)
Each feeder conductor is to be protected by a circuit breaker, or fuse with disconnecting switchgear, from short circuit and overload at the supply end. Fuse ratings and rating of time-delay trip elements of circuit breakers are not to exceed the rated current capacity of the feeder cables, except as otherwise permitted for motor and transformer circuits where starting in-rush current need be taken into account.
ABS RULES FOR BUILDING AND CLASSING STEEL VESSELS . 2007 603