PDx8x

Single and Dual Channel DIN rail


Parking Detector

User Manual

Nortech International (Pty) Ltd


All rights reserved
Copyright © 2020
Document Number: 308UM0000_00
Date: July 2020

CONFIDENTIAL
Introduction

This manual provides the reader with a detailed product overview, feature description, configuration
instructions and installation guidelines for the Nortech PDx8x Inductive Loop Parking detector.

1.1 Description
The 8 series Parking Detector is Nortech’s new flagship Parking Vehicle Detector which addresses the
market’s need for a slimline, advanced vehicle detection solution. Our Automatic Frequency Selection
(AFS) algorithms introduced in the 7 series detectors have been refined and optimised resulting in
simplified setup and installation of complex multi-lane access control sites. The new wireless diagnostic
unit, the DU800, supported by the 8 series detectors allows for detector configuration and installation
feedback on any iOS or Android device. This eliminates the need to adjust any mechanical interfaces once
the unit has been installed.
The 8 series comes with the default settings to match the performance of the legacy 3-series detector.
The new slimline, DIN Rail mount housing allows for more physical connections than the traditional relay
base and Nortech’s innovative modular design allows for the expansion of detection solutions, including
but not limited to: Relay expansion units, channel expansion units, and communications interfaces.

1.2 Safety precautions


All installation, commissioning, repair and service work to this product must be undertaken by suitably
qualified and trained personnel.

• This unit must be earthed.


• Disconnect the power before working on the unit.
• On the 90-240VAC model, a readily accessible disconnect device must be incorporated into the
mains wiring.
• On both AC and DC models, the power supply MUST have short circuit protection and over current
protection installed at the power source. Typically, this will be a 5Amp Magnetic Circuit Breaker
for AC models and a fuse for DC models.

• This product must be installed in an enclosure.


• Always suspend traffic through the barrier area during installation and test as this may result
in unexpected operation of the barrier.
There are no serviceable parts or internal settings inside the product. The product warranty will be
void if the cover has been removed or if there is any tampering with the product.

1.3 Related documentation


Please contact Nortech International if any further documentation is required.

308UM0000_00 PDx8x User Manual July 2020


Page 5 of 50
Product Overview

2.1 Applications
• Parking barrier control
• Safety loop
• Arming control
• Motorised gates and doors
• Industrial control systems
• To arm card readers and ticket dispensers
• As a barrier/gate/door closing detector
• As a barrier/gate/door opening detector
• To generate pulses for vehicle counting
• As a logic unit to determine the direction of traffic flow

2.2 Features
The PDx8x is the most slimline of the Nortech parking detectors facilitating
Slimline form installation in even the most physically constrained environments. Maximum outer
factor dimensions are 94mm x 94mm x 22.5mm
The innovative expansion port on the PDx8x allows for the addition of modules to
Expandable the system. These modules include but are not limited to extra relay/opto outputs,
extra detection channels and communication modules.
The 8 series feature an all-new Synchronization and Expansion bus. This allows all
the detectors on the bus to be channel-mux synchronized to reduce crosstalk and
Sync Bus
noise from adjacent loops. The Synchronization bus auto-establishes as soon as more
than one detector is connected.
Automatic Frequency Selection (AFS) automatically examines the detector
environment and sets the optimal operating frequency to ensure minimal
AFS interference and maximum reliability, significantly decreasing installation time.
Frequency can also be manually set via wireless configuration channel.

In the event of a power failure, the PDx8x will retain the presence of the vehicle
when power is restored. The detector is also able to determine if a vehicle has driven
PowerFail onto the loop while the power is off and detect it immediately when the power
Memory returns. This is most useful in applications where damage to vehicles could occur
(E.g. Rising Bollards). The PowerFail memory is infinite.
Comprehensive, wireless diagnostics allow for accurate diagnosis of loop and
Diagnostics installation problems as well as configuration adjustments to eliminate issues. This
is made possible via Nortech’s DU800 and Integr8 App.

308UM0000_00 PDx8x User Manual July 2020


Page 6 of 50
2.3 Ordering information
Please refer to the tables below for ordering information on the single and dual channel variants of the
PDx8x.

Single Channel Detectors


Model Number Power Supply Output Type Order Number
2x Relays 308FT0101
PD182 90 – 240VAC
3x Optos 308FT0103

2x Relays 308FT0102
PD184 12 – 24VAC/DC
3x Optos 308FT0104

Dual Channel Detectors


Model Number Power Supply Output Type Order Number
2x Relays 308FT0201
PD282 90 – 240VAC
3x Optos 308FT0203

2x Relays 308FT0202
PD284 12 – 24VAC/DC
3x Optos 308FT0204

DU800 Diagnostic Unit


Model Number Order Number
DU800 895FT8000

308UM0000_00 PDx8x User Manual July 2020


Page 7 of 50
2.4 Technical specifications
Self-tuning range 20µH to 1000µH
0.01% ΔL/L to 5% ΔL/L
Sensitivity
Automatic Sensitivity Boost (ABS) is selectable
Automatic Frequency Selection (AFS) or select from 6 frequency bands.
Frequency
30 – 150kHz (Frequency is determined by loop geometry)
Automatic Frequency Automatically evaluates all frequency bands on start-up and selects the
Selection most suitable in the given environment based on signal strength and noise.
Detect: < 58ms ±1.5ms
Response time
Undetect: < 58ms ±1.5ms
Fault detection Open circuit and short circuit
Presence time Permanent or limited selectable, with optional timeout on both
Incorporated method of tracking changes caused by environmental
Drift compensation
conditions at a rate approximating 1% ΔL/L per minute.
Incorporated algorithm accommodates the influence of positive inductance
Anti-locking
changes to avoid detector lock-up.
Outputs are fully programmable with options for presence or pulse. Each
Outputs
output also has a configurable Filter, Delay and Extend option.
Two options available:
• 2x Relays with NO, NC and COM connections exposed
Number of outputs
• 3x Optically isolated outputs
(refer to the ordering information in section 2.3)
Output mode Fail Safe or Fail Secure
Fully configurable. Outputs can also be linked to any input (2-channel
Output assignment
detectors only).
90 – 240VAC ±10% (50/60Hz) – PD182 and PD282 models
Rated operating voltage
12 – 24VAC/DC ±10% – PD184 and PD284 models
Rated AC supply
45 – 65Hz (PD182 and PD282 models)
frequency
PD182 and PD282 Power Relay Output:
consumption @110VAC : < 3.5VA - with a DU800 connected
@240VAC : < 5.5VA - with a DU800 connected
Opto Output:
@110VAC : < 5.5VA - with a DU800 connected
@240VAC : < 7.5VA - with a DU800 connected
PD184 and PD284 Power Relay Output:
consumption @12VDC : < 2.2W - with a DU800 connected
@24VDC : < 2.0W - with a DU800 connected
Opto Output:
@12VDC : < 3.6W - with a DU800 connected
@24VDC : < 2.8W - with a DU800 connected

308UM0000_00 PDx8x User Manual July 2020


Page 8 of 50
Protection Polarity protection, loop isolation transformer, Zener diode clamping, gas
discharge tubes.
Operating temperature -40°C to +80°C
Dimensions 94mm x 94mm x 22.5mm

2.5 Electrical data


Power requirements
IEC 60950-1 Class II device

90 – 240VAC ± 10% (48 to 62Hz) (PD182 and PD282)


12 – 24VAC/DC ± 10% (48 to 62Hz) (PD184 and PD284)
Relay Contact Rating

Load Resistive Load

Rated Load 0.3A at 125VAC, 1A at 30VDC


Rated carry current 1A
Max. switching voltage 125VAC, 110VDC

Max. switching current 1A

For ambient temperatures above 60°C De-rate the relay


Maximum current as per graph below: (check and either remove or update)

Opto Isolated Output Rating


Maximum Collector Current: 50 mA
Maximum Collector-Emitter Voltage: 80 V
Maximum reverse Voltage (Emitter-Collector): 7V

308UM0000_00 PDx8x User Manual July 2020


Page 9 of 50
2.6 Environmental Data
Storage Temperature -40°C to +80°C

Operating Temperature -40°C to +80°C

Humidity Up to 95% relative humidity without condensation

Circuit protection Conformal coating over the PCB and all components

IP Rating IP30 – This product MUST be installed in an enclosure

2.7 Mechanical Data


Housing Material Black Base: High heat ABS
Red cover: Polyamide 6
DIN Rail Clip: Acetal

Mounting Position DIN rail mounting

Connections 1x 3-way plug for power


1x 4-way plug for loops
2x 3-way plugs for outputs

2.8 Approvals
CE Regulations: TBC

Safety: TBC

308UM0000_00 PDx8x User Manual July 2020


Page 10 of 50
Connection Diagrams

3.1 PD18x Single Channel Detectors

Supply Supply

308UM0000_00 PDx8x User Manual July 2020


Page 11 of 50
Detector Configuration and Diagnostics

Contrary to Nortech’s traditional detectors, the 8 series configuration is undertaken via a wireless
connection between a mobile device and the detector, rather than via DIP switches.

To facilitate this connection, a DU800 diagnostic unit, Integr8 App and Android or iOS mobile device are
required. The Integr8 App is available on both Google Play Store and the Apple App Store.

308UM0000_00 PDx8x User Manual July 2020


Page 20 of 50
6.1 Connecting to the 8 Series Detector
Once power has been applied to the detector, insert the DU800 Diagnostic Unit into the connector
provided on the front face of the detector. The red LED on the DU800 will be illuminated indicated no
network connection.
The DU800 is, by default, in Hotspot mode which means a mobile device can connect to it directly via
WiFi.
On the mobile device, go to the WiFi settings. The DU800 will be listed as a network with an SSID of
DU800_XX_YY_ZZ where XX_YY_ZZ are the last 3 bytes of the device’s MAC address. Tap on the DU800
to make the connection. When prompted for a password use: 895SW8000.
Once the connection is established, the red LED on the DU800 device will go green.

Open the Integr8 App on the mobile device.

Tap on the ‘Scan Current Network’ button. The App will search for the DU800 on the network and once
found, an entry will be created in the ‘Device Scan Result’ List. Tap on the entry to connect to the detector.

308UM0000_00 PDx8x User Manual July 2020