Professional Documents
Culture Documents
Fire Control Panel FCP dc3400 SC: Installation Manual
Fire Control Panel FCP dc3400 SC: Installation Manual
FCP dc3400 SC
Installation manual
Version 2.2 1
Installation Manual FCP dc3400 SC
Version 2.2 2
Installation Manual FCP dc3400 SC
Index
1 Installation manual purpose and structure ......................................... 6
1.1 Purpose of this manual .....................................................................................................6
1.2 Structure of the manual ....................................................................................................6
4 Installation .......................................................................................... 12
4.1 Requirements .................................................................................................................12
4.2 Inspection for completeness and damage during transport .............................................13
4.3 Internal components of the FCP dc3400 SC ....................................................................14
4.3.1 Location of the components...............................................................................14
4.3.2 Housing .............................................................................................................14
4.3.3 Mains adapter ...................................................................................................15
4.3.4 CP-PSB1 Power supply board ............................................................................16
4.3.5 CP-CPB Main board ...........................................................................................19
4.3.6 CP-MB basic module .........................................................................................21
4.3.7 CP-LI3120 Loop card .........................................................................................24
4.3.8 CP-DIS Display and control panel (DCP) .............................................................26
4.4 External components ......................................................................................................28
4.5 Housing assembly ..........................................................................................................29
4.5.1 Assembly steps .................................................................................................29
4.6 Line connections ............................................................................................................30
4.6.1 Earthing.............................................................................................................30
5 Commissioning ................................................................................... 31
5.1 First commissioning .......................................................................................................31
5.1.1 Procedure of the commissioning report .............................................................31
5.1.2 Installing the batteries .......................................................................................34
5.1.3 FCP dc3400 SC standard programming .............................................................34
5.1.4 Configuration of the FCP dc3400 SC ..................................................................35
5.1.5 Functional test for commissioning .....................................................................35
5.2 Extend / reduce loop (components) .................................................................................35
5.3 Limits, current calculation ..............................................................................................36
Version 2.2 3
Installation Manual FCP dc3400 SC
Version 2.2 4
Installation Manual FCP dc3400 SC
11 Maintenance ....................................................................................... 59
11.1 Inspections .....................................................................................................................59
11.1.1 Inspection Periods .............................................................................................59
11.1.2 Batteries............................................................................................................60
11.2 Cleaning .........................................................................................................................60
11.3 Software Updates ...........................................................................................................60
11.4 Environmentally-friendly disposal ...................................................................................60
Version 2.2 5
Installation Manual FCP dc3400 SC
Important safety precautions and special information are indicated in the text of the manual
by pictograms. These pictograms have to be followed accord ably.
Attention!
The user is alerted to practices and circumstances that could result in equipment
damage or economic loss.
Warning!
The user is made aware of precautions when dealing with electro statically sensitive
components.
Note!
The user obtains additional information that is critical for successful application and
understanding of the product.
Version 2.2 6
Installation Manual FCP dc3400 SC
The detectomat GmbH is not liable for defects which occur due to incorrect usage of the
fire control panel dc3400 SC.
Operator control actions at an already installed FCP dc3400 SC may only be done by
authorised and trained staff taking into account your countries safety regulations.
This operation manual does not include general or regional regulations. Information about
general and regional regulations and rules are prerequisite for the operations of the FCP
dc3400 SC.
Version 2.2 7
Installation Manual FCP dc3400 SC
Warning!
Removing or decommissioning safety installations may result in material damage or
bodily injuries. Thus, only authorised service technicians are allowed to remedy any
deficiencies with regard to safety installations.
The functionality of the safety installations has to be checked on a regular basis.
Version 2.2 8
Installation Manual FCP dc3400 SC
3 Product information
3.1 Brief description
The fire alarm system is the central element with regard to the fire protection of a building.
Being an alarm system for dangerous situations, it is used to save lives and to protect
people’s health, the environment as well as material assets. It consists of the central fire
alarm system, the fire detectors as well as the control and alarm organisation.
The dc3400 SC system includes several compatible assemblies as well as small, individual
centre applications. Currently, the FCP dc3400 SC monitors a loop wiring system (loop) which
may include up to 126 loop components which, in turn, can be divided into 100 detector
zones with a line length of up to 3000 m. The loop wiring system is a monitored 2-wire bus
with a ring line. The system guarantees a safe detection of fire areas or impurities due to the
individual identification of the detectors and/or the addressing and control components and
provokes a predefined action.
The different lights on the LED display indicate current alarms, faults and other messages.
The display which can be easily operated and understood provides comprehensible clear text
information with regard to operation, fault and alarm.
Version 2.2 9
Installation Manual FCP dc3400 SC
Electrical data
Fuses
Fuse holder Mains connection 230 V supply mains adapter 3,15 A delayed-action
CP-PSB1 Power Board Card F200 / Battery fuse 4 A fast-acting
F401 / 32 V system voltage 4 A fast-acting
F400 / 24 V Ub ext. devices 1 A fast-acting
CP-MB Basic Module F600 / external signallers 500 mA fast-acting
CP-LI3120 loop card F700 / loop 500 mA delayed-action
Interfaces
Number of loops 1
Length of the loop line max. 3000 m (depending on loop components)
Number of loop components 126 (per loop)
Number of programmable zones 100
Interfaces 1 x USB for connecting to PC
Display Touch screen display 320 x 240 pixels (1/4 VGA)
Version 2.2 10
Installation Manual FCP dc3400 SC
To change a polluted or defective detector you can copy the detector data to a new detector.
You need to enter the menu "System parameters" and start "Extend / reduce loop". The new
serial number of the detector will now be saved and the fault message will disappear.
The new detector will still be recognized as a new detector, which will automatically be set to
the default zone 9501 and the fault message "Wrong detector type" will be displayed.
You need to reprogram the detector to the desired zone via the dpt software.
The fault message will disappear doing so.
The following conditions lead to the detector change fault (type check):
• Concerning detectors have an isolator (3300 series)
• There are no further faults in the loop
A Pollution of >80% will automatically lead to a fault message and the fault relay will be
triggered.
Version 2.2 11
Installation Manual FCP dc3400 SC
3.4.5 Mappings
The possible mappings have been extended. Further source and targets have been added.
Additional information can be found in the dpt manual.
3.4.6 Firmware-Updates
Firmware updates of the single FCP boards are now only possible via the dpt. A FCP dc3400
SC version 2.1.5 can now be updated to version 2.5. All FCP boards will be updated
automatically. Exception is the Display and Indication Board. The board can be updated
separately to install new languages.
4 Installation
4.1 Requirements
The following procedures are to be assured in order to ensure a fault free operation of the
FCP dc3400 SC, the following
• Only install the FCP dc3400 SC in dry, clean and conditionally accessible rooms.
In this connection, observe chapter "3.2 Environmental conditions" on page 9.
• Assemble the FCP dc3400 SC without mechanical stress on a level mounting surface.
The FCP dc3400 SC may only be commissioned after it has been professionally attached
to a wall or mounting surface with sufficient load-bearing capacity.
• Avoid strong electrical / electro-magnetic and mechanical influences. This applies in
particular to the assembly of the FCP dc3400 SC, components and installation lines in the
immediate vicinity of fluorescent lamps or energy cables and the fastening on vibrating,
instable surfaces like, e.g. thin partition walls.
• Do not mount the FCP dc3400 SC in rooms with detrimental influences.
• Connect the PE and FE connection (functional earth) of the FCP dc3400 SC housing with
the PE rail of the distribution/sub-distribution from which the FCP dc3400 SC-is supplied
with mains voltage.
• Do not connect the FCP dc3400 SC to IT voltage supply systems.
• Only install the FCP dc3400 SC in places with normal room temperature in order to
guarantee a perfect life time of the batteries.
Version 2.2 12
Installation Manual FCP dc3400 SC
Note!
Before starting with the assembly:
Check all supplied parts of the FCP dc3400 SC for completeness and damage. In
case of damage, contact the manufacturer.
The housing is supplied completely, with the modules that have already been pre-assembled
by the manufacturer:
• "CP-MB" Basic Module
• "CP-PSB1" Power Supply Board
• "CP-CPB" Central Processing Board
• "CP-DIS" Display and control panel
• "CP-LI3120" Loop Card
The batteries are not contained in the delivery and can be acquired from the manufacturer.
Version 2.2 13
Installation Manual FCP dc3400 SC
Note!
In the FCP dc3400 SC software, the devices connected to the CAN bus are called
“CAN devices” and/or CAN components. In this connection, both terms have the
same meaning.
4.3.2 Housing
The housing consists of sheet steel and is provided with a lockable door. It is assembled on
the surface. The lines are either led into the housing at the back or through the upper and
lower bush openings. The housing accommodates the whole electronics and the energy
supply. The modules for the display and the operation are attached to the housing door. In the
lower part of the housing, the batteries for the emergency power supply can be installed.
Version 2.2 14
Installation Manual FCP dc3400 SC
Input
Output
Version 2.2 15
Installation Manual FCP dc3400 SC
Technical Data
Input voltage (input) 32V Medium power consumption 32 V max. 1600mA (idling, max. charging current)
Output voltage (UbExt.) 24V up to max. 28V DC, 500mA KTY81-210 Temperature sensor ±1%
5V supply voltage 5.39V DC (internal) F200 / Battery fuse 4A fast-acting
Batteries 24V (2 x 12V / 26 Ah) in series F400 / 24 V Ub ext. devices 1A fast-acting
Final charging voltage ca. 27.3V / ± 5 % at 20 °C F401 / 32 V system voltage 4A fast-acting
Final discharging voltage 22.7V / ± 5 % at 20 °C Board dimensions 127 x 100 mm
Medium power consumption 32 V 200mA (idling, no charging)
Version 2.2 16
Installation Manual FCP dc3400 SC
Function
The voltage supply of the FCP dc3400 SC and the 24V DC supply voltage for external devices
are located on the power board card. The maximum current load due to external devices is
400mA.
CPU
The mains adapter’s CPU measures and monitors all voltages and if necessary, forwards
these values via the CAN bus. Additionally, the CPU controls the charging controller for the
connected battery.
Charging controller
The battery voltage varies by means of temperature. The current is consistently maintained at
1.6 A. When the final charging voltage is reached, the system will change over into trickle
charge mode. In case of negative temperatures, the battery will not be charged.
Disablement criteria
The battery charge is disabled as soon as:
• The actual temperature falls below or exceeds the temperature specified by the battery
manufacturer
• The charging current exceeds 1.8 A
• After 24 hours, if the battery has still not taken up 80% of its charge
• The final charging voltage is not achieved within a predefined period
Temperature compensation
If the ext. temperature sensor is not connected, the temperature sensor is analysed in the
processor of the power board card. As soon as the ext. temperature sensor (type KTY 81-218)
is connected, it accepts the battery control function.
Batteries
The power board card is designed for a battery capacity of maximally two batteries (12 Ah)
with the dimensions 100 mm x 151 mm x 99 mm (H x W x D). If the mains voltage fails, the
batteries continue the voltage supply without interruption. Maximum charging current: 1.6 A.
Version 2.2 17
Installation Manual FCP dc3400 SC
1 1 0 0 0
Jumper-No. Description
Legend
Version 2.2 18
Installation Manual FCP dc3400 SC
Technical Data
Power consumption 21mA
Function
The CPB is the central control unit of the FCP dc3400 SC.
Interfaces
Every main board is equipped with 3 plug sockets.
- 1 RS232 jack for a record printer (not available in the SC version)
- 1 USB jack to connect to a computer (for uploading and downloading the
configuration data using the programming programming tool (dpt from V9.0).
- 1 RS232 jack not in use.
Due to the small housing form factor there is no record printer for dc3400 SC available.
Version 2.2 19
Installation Manual FCP dc3400 SC
SP number DIP 1 2 3 4 5 6 7 8
(1) (2) (4) (8) (16) (32) (64) (128)
1 1 0 0 0 0 0 0 0
2 0 1 0 0 0 0 0 0
3 1 1 0 0 0 0 0 0
4 0 0 1 0 0 0 0 0
5 1 0 1 0 0 0 0 0
6 0 1 1 0 0 0 0 0
7 1 1 1 0 0 0 0 0
8 0 0 0 1 0 0 0 0
…
255 1 1 1 1 1 1 1 1
There is an alarm display at the CP-DIS display and control panel. The internal buzzer of the
FCP dc3400 SC will sound and the collective fault relay on the CP-MB basic module will
change into fault mode. There is an alarm display at the fire brigade control panel.
Jumper-No. Description
Legend:
Version 2.2 20
Installation Manual FCP dc3400 SC
Note!
The fault relays are energised in standby by and will de-energised in case of fault
conditions
Technical Data
Power consumption 40 – 56mA Inputs / outputs 2 inputs potential-free 24V DC / 5.8mA
3 outputs potential-free 30V DC / 2A
1 output monitored (not potential-free) 500mA
Version 2.2 21
Installation Manual FCP dc3400 SC
Function
The main board provides standard inputs and standard outputs.
Inputs / outputs
The outputs are programmed as follows:
Jumper description
Jumper No.: Description
Legende:
Version 2.2 22
Installation Manual FCP dc3400 SC
1 1 0 0 0
Emergency operation: The “Alarm” message is forwarded between the CAN devices via
emergency paths. For the “Alarm” relay activation in emergency operation, jumper Jp 401
must be plugged in. For the activation of external signallers, jumper Jp 600 must be plugged
in.
Fault
Normal operation: The basic module activates the fault relay. JP 402 must be plugged in.
Emergency operation: The “Fault” message is forwarded between the CAN devices via
emergency paths. For the “Fault” relay activation in emergency operation, jumpers Jp 401
and 402 must be plugged in.
Version 2.2 23
Installation Manual FCP dc3400 SC
Technical Data
Function
Communication with the loop components is effected via the loop card. Thus, it is the
connection between central computer and loop components.
Version 2.2 24
Installation Manual FCP dc3400 SC
1 1 0 0 0
Attention!
The CP-LI3120 Loop card does not provide the same diagnostic possibilities as the
detectomat loop-tester LT3000. Use the loop tester LT3000 to check possibly
manual assigned detector addresses and the loop structure on correctness at first
installation or after extending the structure. This can assure a correct and confident
running of the fire control system.
Jumper-No. Description
Legende:
Version 2.2 25
Installation Manual FCP dc3400 SC
Technical Data
Power consumption 35 – 70 mA
Function
The DCP constitutes the connection between the operator and the FCP dc3400 SC. Here, any
important information is shown and/or here, the operator is able to send different commands
to the central computer.
Version 2.2 26
Installation Manual FCP dc3400 SC
Watchdog LED
Signals various conditions every few seconds
- 3 sec. flash = normal mode
- 1 sec. flash = programming mode (updates)
- 0,1 sec. flash = Emergency mode
1 1 0 0 0
Jumper-No. Description
Legende:
Version 2.2 27
Installation Manual FCP dc3400 SC
Display calibration
Information!
The fault message "Fault CP-DIS 1 Display calibr. took place" will appear after
every display calibration. This is normal and can be reset by pressing [ Reset ].
1 Touch the display anywhere using your finger or a pin with a blunt tip.
2 While still touching the display, press the [ RESET ] button on the back of the CP-DIS DCP.
The information “Loading program …” and afterwards “!Calibration!” appears. Adhere to
the following instructions in the display.
3 Touch the indicated spots in the corners as exactly as possible.
4 Subsequently touch several freely selected points at the display.
5 Press the [ Ok ] button if the presentation of the points is exactly below the touch point.
6 If it has not been possible to complete the display calibration orderly, click on the []
button and repeat the procedure.
Version 2.2 28
Installation Manual FCP dc3400 SC
Warning!
Connect the housing to an earth potential in order to avoid electrostatic charging.
Observe the precautions when dealing with electrostatically sensitive components.
The FCP dc3400 SC is to be fitted to the wall so that the displays can easily be read and the
keyboard can easily be used. The mounting height should lie between 1.50 m and 1.80 m.
Display and LED display should be at eye level so that the operator can operate the display
without problems.
The housing is provided without batteries and only with the internal lines. The use of batteries
as replacement power supply is absolutely necessary. For more information please refer to
chapter “5.1.2 Installing the batteries“ on page 34.
1 For the wall assembly, use S8 dowels and Ø 6 mm cylinder head bolts. Select a screw
length ensuring a stable suspension.
2 Make the upper two borings (Ø 8 mm) in the wall according to the assembly drawing.
3 Insert the dowels and screw two cylinder head bolts into them. When doing so, comply
with a distance between the screw head and the wall of approx. 19 mm. The cylinder
head screws must not bear the housing on the spacers!
4 For the time being, hook up the housing.
5 Mark the dimensions for the bottom borings.
6 Remove the housing again in order to make the bottom borings (Ø 8 mm) into the wall.
7 Hang the housing finally onto the top screws and apply the bottom screws.
8 Make sure that the housing is firmly hanging at the wall and that no mechanical stress is
generated.
Version 2.2 29
Installation Manual FCP dc3400 SC
Note!
For concealed wires, use the opening in the housing’s back wall.
For surface-mount wires, use the openings on the top of the housing for cable
connections. In the delivery condition, these openings are closed by means of a
cover plate.
The wires used must be shielded in order to provide protection against
interferences. We recommend using correspondingly prescribed fire alarm lines.
In order to avoid short-circuits with other terminals and other earth faults due to not
insulated, blank lines of the drain wire, they should be insulated. This measure must
particularly be complied with in the area of fire-extinguisher cabinets, when connecting
pressure switches in metal housings on IOMs or in assemblies with metal consoles at profiled
sheeting and other metal constructions.
Warning!
Do only complete the line connections if the FCP dc3400 SC is in a dead-voltage
state.
1 Pull off the mains fuse holder at the 230V terminal so that there is no mains voltage after
connection of the voltage supply.
2 Pass the detector lines and the supply line for the voltage supply through the provided
openings into the housing.
3 Attach all signal lines (detectors, sirens, etc.) to the strain relieves. Do, however, not yet
wire them! In limit value detectors you have to make sure that the terminating resistor
5.6kOhm / 0.25W that is installed in the FCP dc3400 SC housing is removed and
installed into the last detector in the line.
4 Connect the supply lines for the voltage supply to the 230 V terminals.
5 Proceed as described in chapter “5 Commissioning“ from page 31.
4.6.1 Earthing
Like all electrical devices, the FCP dc3400 SC can be damaged by a strike of lightening. By
means of an orderly earthing, the risk of damage can be minimised.
For this purpose, connect the PE of the mains connection of the FCP dc3400 SC with the PE
rail of the distribution/sub-distribution from which the FCP dc3400 SC is supplied with mains
voltage.
Version 2.2 30
Installation Manual FCP dc3400 SC
5 Commissioning
5.1 First commissioning
Warning! Danger due to electric shock.
The FCP dc3400 SC must still be in a dead-voltage state.
One prerequisite for the commissioning is an orderly assembly of the FCP dc3400 SC.
This includes the wall assembly incl. all inserted signal lines (detectors, sirens, etc.) that have
not been wired, yet.
The CAN devices that are assembled on the top of the connection board on the left and on the
right constitute the CAN bus beginning and the CAN bus end. If more modules are attached to
the CAN devices specified above, the former constitute the bus beginning and the bus end.
All other CAN devices are correspondingly located in the bus centre.
1 Check the correct seat of all CAN devices on the connection board.
2 Wire all open, monitored outputs that are not to be wired with corresponding terminating
resistors:
• Output External signallers
• Monitored outputs loop components
You complete the first commissioning by means of our commissioning record. The
commissioning record supports you in the commissioning and also simplifies the support by
the manufacturer. For wiring the lines use the supplied connection plans of the loop devices.
Note!
Record the completed commissioning action in the supplied commissioning record.
The FCP dc3400 SC does not provide the same diagnostic possibilities as the Fire Control
Panel detect 3004 (Order-No.: 31973). Use the loop tester LT3000 (Order-No.:31625) to
check possibly manual assigned detector addresses and the loop structure on correctness at
first installation or after extending the structure of the loop. This can assure a correct and
confident running of the fire control system.
Version 2.2 31
Installation Manual FCP dc3400 SC
Line resistance Corresponding line length Wire diameter Fire alarm cable
Version 2.2 32
Installation Manual FCP dc3400 SC
Note!
For the operation of the display, please refer to more information in chapter 6
„ Operation of the FCP dc3400 SC “ on page 37.
Warning!
Only unplug and/or plug the CAN devices if the FCP dc3400 SC is in a dead-voltage
state.
1 Push the fuse holder back into place to supply the voltage supply via the 230 V terminals.
The FCP dc3400 SC starts up. At the display, the message “Building up Loop” appears.
2 In the first commissioning, all CAN devices are shown in the beginning. If all CAN devices
are shown in the display correctly, you have t confirm it. If not all CAN devices are
shown, check the correct seat, the addressing and the function standby (sign of life LED)
of the CAN devices. In this case, repeat the CAN device read-in by pressing the [ Scan
FCP mod. again ] button.
3 Press the [ Ok ] button at the display, if all CAN devices have been recognised properly.
Detector Read-in
After you have read in the CAN devices, you need to press [ Ok ] to open the read in
functions.
Learn loopstructure (SCAN): The existing addresses or those that have first been
assigned manually (easy check) are scanned in. In this way, an existing system can be
extended, i.e. the new detectors are assigned free addresses via the easy check and are
then read-in by means of this scan command.
Note!
Read-in of the loop components (detectors) can be repeated as often as you want
(e. g. for the troubleshooting in the loop structure).
2 Press the [ Ok ] button if all loop components are displayed correctly. Thus, the “Detector
Read-in” process is completed.
3 Press the [ Ok ] button in order to confirm the display. After the confirmation, the
“Standby” menu appears.
Version 2.2 33
Installation Manual FCP dc3400 SC
As no batteries have been connected, yet, the “Fault – Open circuit Batteries” error message
still appears in the display and at the LED display. In order to remedy the fault, connect the
specified batteries. More information in chapter „3.3 Technical Data“ from page 9.
Put the FCP dc3400 SC into a dead-voltage state. (Pull out the detachable mains fuse)
1 Put the batteries into the housing.
Warning!
Pay attention to the polarity of the connections. In case of wrong polarity, the
battery fuse on the power board card will blow.
2 Connect the batteries using the supplied connection lines. For more information see
annex 2. After the batteries have been connected, the battery fault message at the
display disappears.
The loop sounders and IO-modules (outputs) will also be activated by default depending on
the loop structure. The default standard programming of the relays and components will also
be downloaded and indicated in the corresponding dpt-explorer of the detectomat
programming tool.
Version 2.2 34
Installation Manual FCP dc3400 SC
Note!
After you have successfully commissioned the FCP dc3400 SC, store the completed
commissioning record in the FCP dc3400 SC for maintenance purposes. Make a
copy and take it to your documents.
There are the following possibilities for reading in the loop structure. Check and test if the
changes to the loop are still conform to the programming before continuing.
1 Read in the detectors via [ Menu | System Parameters | Extend / reduce loop ].
2 Press [ OK ] to confirm.
3 Confirm the selected FCP modul again pressing [ OK ]
4 Press [ Start ]. The existing addresses and/or those that have first been assigned
manually are scanned in and/or read in.
Version 2.2 35
Installation Manual FCP dc3400 SC
Loop component
Line length max. 3000m (with Ø 0.8mm)
Operating current max. 36mA (900 current units with ≤ 2000m)
Components max. 126
Version 2.2 36
Installation Manual FCP dc3400 SC
6.1 Display
The FCP dc3400 SC is equipped with a touch screen display in a landscape format which can
be used to control the program sequence with only a single touch. You can operate the
display with your fingers or by using a PDA pen.
Warning!
Never use a ball point pen or other objects with a sharp tip. Using such objects will lead
to damage of the display.
Clean the display with a soft, dry cloth. Do not use benzene, paint thinners or cleaning
alcohol (spirit).
If the display has been turned on but has not been used for a period of 12 seconds, the
background lighting of the display will disable automatically (normal operation mode).
The background lighting of the display will be automatically activated if a message
(alarm/fault) is detected or if you touch the display.
Display Meaning
Version 2.2 37
Installation Manual FCP dc3400 SC
Display Meaning
Scroll up
Scroll down
Ok Confirm and select
Back to previous menu
Transm.Unit Alarm on/off* Switches the transmission unit on or off*
Mutes or un mutes the internal buzzer during alarms of faults
Delay on/off Enables or disables any delays programmed
Return to the “Home” screen
Enable Enables detectors, zones, outputs, ext. sounders, which have been disabled
Disable Disables detectors, zones, outputs, ext. sounders.
Service For viewing the event log and to enable/disable the maintenance mode
System parameters To delete the event log, read CAN devices and detectors, reset to default
settings and to view the software version of the panel.
Alarm counter Displays the number of main alarms (any alarms generated while in
maintenance mode or detector / zone dependencies are not recorded here)
User interface Configure display
Select language
Lamp test
1 2 Set date and time
Set default display configuration
Keys 0 - 9 numeric keys
deletes a wrong entry
C deletes the whole entry in area 2
1 Panel required information
2 Entry fields Touch the respective box in order to make an entry.
* In the present version not available
7 1
Version 2.2 38
Installation Manual FCP dc3400 SC
6.2 LED-Display
The LED display automatically indicates an alarm, fault or any other information generated
from the panel.
Version 2.2 39
Installation Manual FCP dc3400 SC
7 Operating States
The current operating states are shown via an LED and in the display. If an alarm, fault or a
disablement message is generated at the same time, the messages are displayed according
to priority:
1. Alarm messages
2. Fault messages
3. Disablement messages
4. Information
In this case, the message with the higher priority is always displayed.
7.1 Operation
The “In operation” state is the normal operating mode of the FCP dc3400 SC. For this
operation, the door of the FCP dc3400 SC must be closed.
LED display
• “Operation” LED is on
Display
• “In operation” / “! Please touch display for operation!”
Version 2.2 40
Installation Manual FCP dc3400 SC
7.2 Alarms
7.2.1 Alarm "Main Alarm"
The dc3400 SC is in alarm and all programmed relays, sounders and outputs will be activated if
not
LED display
• “Alarm” double LED is on.
- The “Alarm” relay from the basic module is activated (standard programming)
• “Main alarm” LED is on.
- External sounders are activated if they have not been disabled or in fault.
• "Call Fire Brigade" LED is on
- Please inform the Fire Service immediately!
Display
• On the display, information regarding the device activated and the programmed message
texts are displayed.
• In the centre of the display, in which you can scroll using the [] and [] keys, the first
message is displayed. In the bottom field, you are always shown the last, current or
pending message.
• The alarm display is zone-related. The alarm counter only counts the zones that are in
alarm. If more detectors from one zone are in alarm, the number of detectors is displayed
on the right, between the [] and [] keys (e.g. two more detectors).
In order to view these additional detectors from that zone, touch this key.
LED display
• "Alarm" double LED is flashing at enabled delay action mode
• Yellow LED "Delay ON" is on at enabled delay action mode
• No LED indication (except Operation) at detector/zone dependency
Version 2.2 41
Installation Manual FCP dc3400 SC
Display
• On the display, information regarding the source the alarm and any programmed
message texts are displayed.
• In the centre of the display, where you can scroll using the [] and [] keys, the first
message is displayed. In the bottom field, you are always shown the last message.
• The alarm display is zone-related. The alarm counter only counts the zones that are in
alarm. If more detectors from one zone are in alarm, the number of further detectors are
shown in the display on the right, between the [] and [] keys (e.g. two more
detectors).
In order to view these additional detectors of that zone, touch this key.
LED display
• Maintenance mode LED glows yellow when enabled.
Display
• If a maintenance alarm is triggered, this will be displayed in the "Mainten. notes". The
zones or detectors in maintenance mode will also be indicated in the "Mainten. notes"
window.
7.3 Faults
LED display
• “Fault” double LED is flashing in yellow.
Display
• A message appears specifying the fault.
• In the centre of the display, where you can scroll using the [] and [] keys, the first
message is displayed. In the bottom field, you are always shown the last message.
After the fault has been rectified, there are two possibilities for resetting the dc3400 SC:
• Fault is reset automatically (e.g. in the case of an open circuit or a missing detector).
• Fault is reset by pressing the [ Reset ] key.
Warning!
Defective detectors, zones, inputs and outputs will not trigger an alarm. Inform the
Service or maintenance company.
Version 2.2 42
Installation Manual FCP dc3400 SC
7.4 Maintenance/Service
Warning!
Any detectors which are in maintenance mode will not activate any fire alarm outputs!
7.4.1 Disablements
LED display
• “Disabled” yellow LED is on.
Display
• A message will be displayed specifying the disablement. In this example the Sounder are
disabled.
• In the centre of the display, in which you can scroll using the [] and [] keys, the first
message is displayed. In the bottom field, you are always shown the last message.
LED display
• The yellow LED “Maintenance Mode” is on.
Display
• A message will be displayed specifying which zones, detectors or outputs have been
switched into maintenance mode.
• If a maintenance alarm is triggered, this will be displayed according to the “Alarm
Display”. The triggered detector will be reset after approx. 40 seconds.
* The function "Enable/Disable detectors for maintenance" is in this version not possible.
Version 2.2 43
Installation Manual FCP dc3400 SC
If the ext. sounders have been disabled they will have to be enabled again via the “Enable”
menu. If the sounders have been silenced using the "Silence alarms" button then after the
reset the sounders are enabled automatically.
8.2 Alarms
If the dc3400 SC goes into alarm and is set to a detector or zone dependency, the following
processes are started automatically:
• The internal buzzer sounds continually.
• The alarm messages are shown in the display
• The following alarms are possible:
- Alarm caused via a detector dependency (Fire D1. knock trig.)
- Alarm caused via a zone dependency (Fire Z1. knock trig.)
- Alarm with an enabled delay
- Maintenance mode alarm
Version 2.2 44
Installation Manual FCP dc3400 SC
If the ext. sounders have been disabled they will have to be enabled again via the “Enable”
menu. If the sounders have been silenced using the [ Silence alarms ] button then after the
reset the sounders have become enabled.
8.3 Faults
The following processes are started automatically if a fault is detected by the FCP dc3400 SC
• The internal buzzer sounds intermittently.
• The “Fault” LED is flashing.
• On the display, the fault message is displayed.
• Depending on the panel configuration, alarm outputs, control modules and relays can be
activated.
Warning!
If a system fault is displayed, the function of the dc3400 SC may be impaired!
You must contact your local service or maintenance company.
Version 2.2 45
Installation Manual FCP dc3400 SC
Operation of the FCP dc3400 SC is governed via different password levels which are user
authorisation specific. Password level 2 should only be accessible for authorised operators.
The password level 3 should only be used for the installation and the construction.
Password levels
Reset X
Silence alarms X
Transm. Unit Alarm on/off* X
X
Version 2.2 46
Installation Manual FCP dc3400 SC
• " "
• "Delay on/off"
• "Menu"
9.2.1 Reset
Resets any fault or fire message if indicated in the display.
Note!
If the cause has not been solved then the fault or fire message will be
indicated again.
Note!
The external sounders can only be activated if they are enabled.
Note!
When the panel is reset the sounders are no longer silenced.
Version 2.2 47
Installation Manual FCP dc3400 SC
9.3 Enable
Via the level 2 password, you can access the “Enable” menu. Disabled elements can be
enabled again. Disabled messages shown in the display and the LEDs are reset.
The enabling procedure is done in the same way as disabling. Instead of selecting the menu
"Disable" you have to select the menu [ Enable ]. Starting from the “In operation” menu,
select the menu sequence [ Menu | Enable ]. All additional steps are similar as described in
the next chapter.
9.4 Disable
Via the password level 2, you can access the “Disablement” menu.
The FCP dc3400 SC offers the following disablement options:
• Detectors or detector zones
• Input 1 and 2 of the basic module
• Output 1 and 2 of the basic module
• External alarm signals
1 Starting from the “In operation” screen, press the following key combination:
[ Menu | Disable ].
2 Press the [ Ok ] button. The password prompt appears.
3 Enter the password.
4 Press the [ Ok ] button in order to confirm the entry. The “Disablements” menu opens.
5 Select one of the following options:*
- Detector
- Zone
- Output
- External alarm signals
Version 2.2 48
Installation Manual FCP dc3400 SC
1 Starting from the “In operation” screen, press: [ Menu | Disable | Detector ], you will see
the following:
2 Touch the [ Zone ] entry field and enter the zone number.
3 Touch the [ from detector ] entry field and enter the detector number as of which
detector in the zone needs to be disabled.
4 Touch the [ to detector ] entry field and enter the detector number up to which detectors
in the zone are to be disabled.
5 Press the [ Ok ] button. On the display a disable message appears specifying which
detectors have been disabled. The disablement counter, located in the top centre of the
display will show the amount of disablements. Also the “Disable” LED will be on.
1 Starting from the “In operation” screen, press [ Menu | Disable | Zone ]. You will then see
the following in the display.
2 Touch the [ from Zone ] entry field and enter the zone number you wish to disable.
3 Touch the [ to Zone ] entry field and enter the zone number up to which zones is to be
disabled.
4 Press the [ Ok ] button. On the display a disablement message appears specifying the
disabled zones. The disablement counter on the display shows the amount of
disablements. The “Disabled” LED is also on.
1 Starting from the “In operation” screen press: [ Menu | Disable | Input ].
2 Touch [] or [] in order to select the “Base module” option.
3 Touch the [ Address ] entry field and enter the CAN address of the module on which the
output is located.
4 Touch the [ from Output ] entry field and enter the output number which requires disabling.
5 Touch the [ to Output ] entry field and enter the output number up to which outputs are to
be disabled.
6 Press the [ Ok ] button. In the display a disabled message appears specifying which input
has been disabled.
Version 2.2 49
Installation Manual FCP dc3400 SC
1 Starting from the “In operation” screen press: [ Menu | Disable | Output ].
2 Touch [] or [] in order to select the “Basic module” option.
3 Touch the [ Address ] entry field and enter the CAN address of the module on which the
output is located.
4 Touch the [ from Output ] entry field and enter the output number which requires disabling.
5 Touch the [ to Output ] entry field and enter the output number up to which outputs are to
be disabled.
6 Press the [ Ok ] button. In the display a disabled message appears specifying which output
has been disabled.
• all
All external acoustical and optical sounders/beacons will be disabled
Note!
The external alarm signals can only be activated by an alarm if they are enabled.
1 Starting from the “In operation” screen, press: [ Menu | Disable | External alarm signals ].
2 Please select if you want to disable all signals or only the audible or only the visual. In the
following example, “all” has been selected. Press the [ Ok ] button. The information
“Disable external alarm signals all?” appears.
3 Press the [ Ok ] button in order to disable all external alarm signals.
The “Ext. sounders” and the “disablements” LED is on.
Version 2.2 50
Installation Manual FCP dc3400 SC
9.5 Service
Via the level 2 password, you can access the “Service” menu. Important information like, for
example, the event log can be viewed.
1 Starting from the “In operation” screen, select the menu sequence:
[ Menu | Service | Event Log ].
You are in the “Service Event log” menu. On the display, the current events appear.
Version 2.2 51
Installation Manual FCP dc3400 SC
1 Starting from the “In operation” menu, select the menu sequence:
[ Menu | System Parameters ]- You are in the “System Parameters” menu.
2 Press the [ Ok ] button. The password prompt appears.
3 Enter the password.
4 Press the [ Ok ] button. The “System Parameters” menu opens.
5 Select one of the following options.
• Delete event log
• Bring FCP into Service
• Extend / reduce loop
• Show detectors
• Restore to factory presets
• Software versions
1 Starting from the “In operation” menu, select the menu sequence:
[ Menu | System parameters | Bring FCP into Service ].
2 Press the [ Ok ] button. The following information text appears:
“Scan for FCP modules and detectors ?”
3 Press the [ Ok ] button. At the display a list with all FCP modules that are installed in the
FCP dc3400 SC and their set address appear.
4 Press the [ OK ] button to open up the next menu where you have the choice of:
"SCAN", or "AUTO" command.
Learn loop structure (SCAN): The existing addresses or those that have first been assigned
manually (easy check) are scanned in. In this way, an existing system can be extended, i.e.
the new detectors are assigned free addresses via the easy check and are then read-in by
means of this scan command.
Warning!
If the loop members have been addressed manually in advance, you must not use
the “AUTO” option! In this case, all addresses are overwritten irrevocably.
Readdress Loop structure (AUTO): Comprises the automatic addressing. In the automatic
addressing, loop members are automatically assigned addresses according to the line run. It
is thus suitable for the first commissioning.
Version 2.2 52
Installation Manual FCP dc3400 SC
1. Select the desired option and press [ Start ]. The reading process is started. A status bar
indicates the progress of the reading process. At the end, the detected loop members are
shown. Press the [ Ok ] button to confirm the read in detectors. The read in detectors will
now be programmed in the flash.
1 Starting from the “In operation” menu, select the menu sequence:
[ Menu | System parameters | Extend / reduce loop ].
2 Press the [ Ok ] button. At the display a list with the installed loop cards in the FCP
dc3400 SC and their set address appear.
3 Press the [ OK ] button to open up the next menu where you have to confirm the
"Learn loop structure (SCAN)" command.
4 Press the [ Start ] to beginn.
Learn loop structure (SCAN): The existing addresses or those that have first been assigned
manually (easy check) are scanned in. In this way, an existing system can be extended, i.e.
the new detectors are assigned free addresses via the easy check and are then read-in by
means of this scan command.
1 Starting from the “In operation” menu, select the menu sequence
[ Menu | System Parameters | Restore to factory presets ].
You are in the “System Parameters Factory Settings” menu.
2 Press the [ Ok ] button. The following information text appears: “System parameters
Restore to factory presets?”.
Warning!
By means of the Factory settings command, all settings of the FCP dc3400 SC are
irrevocably reset. Before this step, back-up your data.
Press the [ Ok ] button. The FCP dc3400 SC settings are reset to the factory values.
Version 2.2 53
Installation Manual FCP dc3400 SC
1 Starting from the “In operation” menu, select the menu sequence:
[ Menu | User interface ] .
2 Press the [ Ok ] button. The “User interface” menu opens.
3 Select one of the following options.
• Configure display
• Select language
• Lamp test
• Set date and time
• Set default display configuration
Version 2.2 54
Installation Manual FCP dc3400 SC
1 Starting from the “In operation” menu, select the menu sequence:
[ Menu | User interface | Configure display ].
2 The password prompt appears.
3 Enter the password.
4 Press the [ Ok ] button. The “Configure display” menu opens.
5 Select the "Brightness" or "Contrast" and press [ Ok ]
6 You can now change the values with the [ • ] and [ – ] keys.
- Brightness: min. 5 --> max. 20
- Contrast: min. 10 --> max. 40
The default setting for both is: 20.
1 Starting from the “In operation” menu press: [ Menu | User interface | Select language ].
2 Press the [ Ok ] button.
3 Select your desired language using the [] and [] buttons.
4 Press the [ Ok ] button. you need to confirm the selected language in the next window.
5 Press the [ Ok ] button. The menu display now appears in your selected language.
1 Starting from the “In operation” screen press: [ Menu | User interface | Lamp Test ].
2 Press the [ Ok ] button.
• All LEDs should come on.
• The display will go out and come on again.
• The internal buzzer sounds during this test.
Version 2.2 55
Installation Manual FCP dc3400 SC
Display Meaning
/ Changing values (up / down)
/ Moving the cursor from one digit to the next
[ Ok ] Entries are stored
Back to previous menu
Back to the Home menu
1 Starting from the “In operation” press: [ Menu | User interface | Set date and time ].
2 Press the [ Ok ] button. The “Set date and time” view opens.
3 Adjust time and date.
4 Press the [ Ok ] button. Time and date are saved in the FCP dc3400 SC.
1 Starting from the “In operation” press: [ Menu | User interface | Set default display
configuration ].
2 The password request window opens.
3 Enter the password and press [ OK ].
4 Confirm to reset the display to default values by pressing [ OK ].
The default values are set.
- Language: English
- Brightness: 20
- Contrast: 20
Version 2.2 56
Installation Manual FCP dc3400 SC
Note!
Faults (like e.g. missing detector, open circuits, etc.) are automatically reset when
2 3 4 the fault has been rectified (self-resetting) and the respective LED goes out. Short-
circuits and system faults are not self-resetting and have to be reset manually.
Message level Message text LED display Cause / Meaning Inspection / troubleshooting
Alarms (general)
1 Alarm Alarm LED on Main alarm
Main alarm LED on (see message text level 2)
Call FB LED on
Buzzer on
1 Fire Z 1. knock trig. Buzzer on First Alarm in a zone dependency
(see message text level 2)
1 Fire D 1. knock trig Buzzer on First Alarm in a detector dependency
(see message text level 2)
1 Alarm MCP Alarm LED on Fire in manual call point zone
Main alarm LED on (see message text level 2)
Call FB LED on
Buzzer on
Faults (general)
Disable (general)
Version 2.2 57
Installation Manual FCP dc3400 SC
Message level Message text LED display Cause / Meaning Inspection / troubleshooting
2 Loop member Fault LED intermittent Communication with the loop device Check loop device / wiring, change
communication Buzzer intermittent is causing problems. loop device, if necessary.
2 Wrong device type Fault LED intermittent Another detector type than the one Use the correct detector type or
Buzzer intermittent configured in the FCP dc3400 has change the configuration.
been used.
– No display No display Power supply or control panel Check the “Input” status LED on the
defective. power board card.
Check the mains fuse
Check the mains supply
Check the input voltage at the power
board card
Try to reboot the system
2 Mains fault Fault LED intermittent Mains fault Check the mains fuse
Mains LED intermittent Check the mains connection
Buzzer intermittent
Check the input voltage at the power
board card
2 Open circuit battery Fault LED intermittent Open circuit between the batteries. Check the battery connection
Battery LED intermittent Check the fuse on the power board
Buzzer intermittent card
2 Short-circuit Battery Fault LED intermittent Short-circuit Batteries Check the battery connection
Battery LED intermittent Check the batteries and exchange
Buzzer intermittent them, if necessary.
2 Low voltage Battery Fault LED intermittent Low batteries voltage. May occur during a longer mains
Battery LED intermittent failure; afterwards, the batteries have
Buzzer intermittent to be recharged.
Check the batteries and exchange
them, if necessary.
2 Earth fault Fault LED intermittent Earth fault within the fire alarm Check the system for earth faults and
Buzzer intermittent system. rectify.
2 Open circuit Loop (+) Fault LED intermittent Open circuit on L+ Check the loop wiring
Buzzer intermittent
2 Open circuit Loop (-) Fault LED intermittent Open circuit on L- Check the loop wiring
Buzzer intermittent
2 Short-circuit Loop Fault LED intermittent Short-circuit on the loop Check the loop wiring
Buzzer intermittent
2 Open circuit acoustic Fault LED intermittent Open circuit in the wiring of the ext. Check wiring of the external signals
Ext. Outputs LED intermittent signals or missing or wrong EOL and/or check the EOL resistor.
Buzzer intermittent resistor fitted.
2 Short-circuit acoustic Fault LED intermittent Short-circuit in the wiring of the ext. Check wiring of the ext. signals
Ext. signals LED intermittent signals or wrong EOL resistor. and/or check the EOL resistor.
Buzzer intermittent
2 CRC error ROM Fault LED Storage error Card Perform a cold start of the fire alarm
System LED system
Buzzer exchange the card, if necessary
Version 2.2 58
Installation Manual FCP dc3400 SC
11 Maintenance
Warning! Danger due to electric shock.
Maintenance and repair works at the FCP dc 3400 may only be carried out in a
dead-voltage state. For this purpose, the mains supply at the mains adapter
connection technology (or the mains fuse is to be removed) and the emergency
power supply (batteries) are to be disconnected.
The inspections and maintenance works completed at the FCP dc3400 SC are to be recorded
in an operating log,
11.1 Inspections
11.1.1 Inspection Periods
In order to ensure the operating ability of the FCP dc3400 SC, inspections are to be carried
out in regular intervals.
Every day
Check the readiness of operation of the FCP dc3400 SC. In case of failures that have
incurred, check whether they are noted in the operating log and whether measures have
been taken for removing the failure.
Every year
In addition to the quarterly inspections, an authorised service technician must individually
inspect each module of the fire alarm system including wiring, all outputs and/or activations.
Each detector of the fire alarm system must be tested at least once per year. Record the
implementation in the operating log.
Version 2.2 59
Installation Manual FCP dc3400 SC
11.1.2 Batteries
The batteries must be exchanged according to the manufacturer’s specifications, after four
years, however, at the latest. For more information please refer to chapter “5.1.2 Installing
the batteries“ on page 34.
1 Turn off the mains voltage. The FCP dc3400 SC is now running in battery operation.
2 After approx. one hour, measure the voltage at the battery terminals. In order to
guarantee the functionality of the FCP dc3400 SC, the battery voltage should exceed 12 V
and be identical at both batteries.
3 Subsequently, turn the mains voltage on again.
11.2 Cleaning
To clean the outer housing of the FCP dc3400 SC use a moist, soft, and lint-free cloth. Do not
use cleaning solvent, paint thinners or cleaning agents that contain alcohol (spirit).
If necessary, the inside of the housing may and should only be cleaned by the service
technician.
Clean the display with a soft, dry cloth. Do not use cleaning solvent, paint thinners cleaning
agents that contain alcohol
The batteries should only be disposed in official waste management plants. Your local
environmental authority can provide you with addresses of waste management plants.
Version 2.2 60