Download as pdf or txt
Download as pdf or txt
You are on page 1of 60

Fire Control Panel

FCP dc3400 SC

Installation manual

Software Version 2.5

Version 2.2 1
Installation Manual FCP dc3400 SC

detectomat GmbH Headquarter: Phone: +49 (0) 4102 2114 60


An der Strusbek 5 Fax: +49 (0) 4102 2114 670
D – 22926 Ahrensburg
Hotline: Phone: See www.detectomat.com
Fax: +49 (0) 4102 2114 9670

Manual-No.: 56245 Version 2.2 – 18.02.2013


* Please specify your customer number when contacting the hotline!

Version 2.2 2
Installation Manual FCP dc3400 SC

Index
1 Installation manual purpose and structure ......................................... 6
1.1 Purpose of this manual .....................................................................................................6
1.2 Structure of the manual ....................................................................................................6

2 General safety notes ............................................................................. 7


2.1 Intended application .........................................................................................................7
2.2 Requirements for the operating company .........................................................................7
2.3 Safety Installations ...........................................................................................................8

3 Product information .............................................................................. 9


3.1 Brief description ...............................................................................................................9
3.2 Environmental conditions ..................................................................................................9
3.3 Technical data ..................................................................................................................9
3.4 New features in Version 2.5 ............................................................................................11
3.4.1 Serial number check..........................................................................................11
3.4.2 Detection of detector change (Type check) ........................................................11
3.4.3 Indication of detector pollution ...........................................................................11
3.4.4 Key lock function ...............................................................................................11
3.4.5 Mappings ..........................................................................................................12
3.4.6 Firmware-Updates .............................................................................................12

4 Installation .......................................................................................... 12
4.1 Requirements .................................................................................................................12
4.2 Inspection for completeness and damage during transport .............................................13
4.3 Internal components of the FCP dc3400 SC ....................................................................14
4.3.1 Location of the components...............................................................................14
4.3.2 Housing .............................................................................................................14
4.3.3 Mains adapter ...................................................................................................15
4.3.4 CP-PSB1 Power supply board ............................................................................16
4.3.5 CP-CPB Main board ...........................................................................................19
4.3.6 CP-MB basic module .........................................................................................21
4.3.7 CP-LI3120 Loop card .........................................................................................24
4.3.8 CP-DIS Display and control panel (DCP) .............................................................26
4.4 External components ......................................................................................................28
4.5 Housing assembly ..........................................................................................................29
4.5.1 Assembly steps .................................................................................................29
4.6 Line connections ............................................................................................................30
4.6.1 Earthing.............................................................................................................30

5 Commissioning ................................................................................... 31
5.1 First commissioning .......................................................................................................31
5.1.1 Procedure of the commissioning report .............................................................31
5.1.2 Installing the batteries .......................................................................................34
5.1.3 FCP dc3400 SC standard programming .............................................................34
5.1.4 Configuration of the FCP dc3400 SC ..................................................................35
5.1.5 Functional test for commissioning .....................................................................35
5.2 Extend / reduce loop (components) .................................................................................35
5.3 Limits, current calculation ..............................................................................................36

6 Operation of the FCP dc3400 SC ........................................................ 37


6.1 Display ...........................................................................................................................37

Version 2.2 3
Installation Manual FCP dc3400 SC

6.1.1 Normal Operation Mode .....................................................................................37


6.1.2 Function Keys and Main Menu ...........................................................................38
6.1.3 Message Structure ............................................................................................38
6.2 LED-Display ....................................................................................................................39
6.2.1 Meaning of the LEDs .........................................................................................39

7 Operating States ................................................................................. 40


7.1 Operation........................................................................................................................40
7.2 Alarms ............................................................................................................................41
7.2.1 Alarm "Main Alarm" ..........................................................................................41
7.2.2 Alarm "delay" & "detector/zone dependency" ...................................................41
7.2.3 Alarm "Maintenance Mode" ..............................................................................42
7.3 Faults .............................................................................................................................42
7.4 Maintenance/Service ......................................................................................................43
7.4.1 Disablements ....................................................................................................43
7.4.2 Maintenance mode ............................................................................................43

8 Operation Procedures at events ......................................................... 44


8.1 Alarm (Main alarm) .........................................................................................................44
8.2 Alarms ............................................................................................................................44
8.3 Faults .............................................................................................................................45

9 Operation and Setting ......................................................................... 46


9.1 Operating, authorisation / access levels ..........................................................................46
9.2 Functions in the "In operation" window ..........................................................................47
9.2.1 Reset.................................................................................................................47
9.2.2 Silence alarms...................................................................................................47
9.2.3 Disabling the "Transmission Unit" .....................................................................47
9.2.4 Mute buzzer .....................................................................................................47
9.2.5 "Delay on/off" ...................................................................................................47
9.3 Enable ............................................................................................................................48
9.4 Disable ...........................................................................................................................48
9.4.1 Disabling detectors ............................................................................................49
9.4.2 Disabling zones .................................................................................................49
9.4.3 Disabling input ..................................................................................................49
9.4.4 Disabling outputs...............................................................................................50
9.4.5 Disabling external alarm signals ........................................................................50
9.5 Service ...........................................................................................................................51
9.5.1 Viewing the service event log ............................................................................51
9.5.2 Maintenance Mode ............................................................................................51
9.6 System Parameters ........................................................................................................52
9.6.1 Delete event log ................................................................................................52
9.6.2 Bring FCP into Service .......................................................................................52
9.6.3 Extend / reduce loop ..........................................................................................53
9.6.4 Show detectors .................................................................................................53
9.6.5 Factory settings .................................................................................................53
9.6.6 Software Versions..............................................................................................54
9.7 Alarm Counter ................................................................................................................54
9.8 User Interface .................................................................................................................54
9.8.1 Configure display ...............................................................................................55
9.8.2 Language Settings .............................................................................................55
9.8.3 Lamp Test .........................................................................................................55
9.8.4 Set date and time ..............................................................................................56
9.8.5 Set default display configuration ........................................................................56

Version 2.2 4
Installation Manual FCP dc3400 SC

10 Faults and diagnostics displays......................................................... 57


10.1 Fault messages ..............................................................................................................57

11 Maintenance ....................................................................................... 59
11.1 Inspections .....................................................................................................................59
11.1.1 Inspection Periods .............................................................................................59
11.1.2 Batteries............................................................................................................60
11.2 Cleaning .........................................................................................................................60
11.3 Software Updates ...........................................................................................................60
11.4 Environmentally-friendly disposal ...................................................................................60

Version 2.2 5
Installation Manual FCP dc3400 SC

1 Installation manual purpose and


structure
1.1 Purpose of this manual
This instruction manual applies to technically qualified users who have been or will be trained
in the operation of the fire control panel dc3400 SC.
As an operator and/or user you are obligated to read and understand this installation manual
in its entirety before proceeding. It contains relevant information on the installation, operation
and maintenance of the FCP dc3400 SC. It will help you to operate the panel safely and
efficiently.

1.2 Structure of the manual


The following conventions will be applied in this installation manual:
• Lists provided with bullet points only contain information and no working steps.
• Numbered lists contain a sequence of working steps or hierarchically arranged
information.
• Texts displayed in quotation marks indicate menu options.
• Shortcuts are displayed in squared brackets, e. g. [ Reset ].

Important safety precautions and special information are indicated in the text of the manual
by pictograms. These pictograms have to be followed accord ably.

Attention! Danger of an electric shock


Turn the power off before working on electrical connections.
Severe injuries could be incurred by the user.

Attention!
The user is alerted to practices and circumstances that could result in equipment
damage or economic loss.

Warning!
The user is made aware of precautions when dealing with electro statically sensitive
components.

Note!
The user obtains additional information that is critical for successful application and
understanding of the product.

Version 2.2 6
Installation Manual FCP dc3400 SC

2 General safety notes


The FCP dc3400 SC meets the present day safety regulations at the time of publication.
Nevertheless danger could occur by incorrect operation or from misuse of the equipment:

• for life and limb of the user or a third party


• for the FCP dc3400 SC and other material assets of the operator
• for the efficient usage of the FCP dc3400 SC

2.1 Intended application


The FCP dc3400 SC is part of a fire detection system, which consists of multiple,
exchangeable and compatible components from small single panel systems up to large
multiple networked detection systems. It is exclusively designed to receive, analyse and
forward measured date received by detection units (for example smoke detectors or manual
call points).

For specified normal operation it is also important to:


• attend and follow the safety instructions in this manual
• attend and follow the maintenance instructions in this manual

The detectomat GmbH is not liable for defects which occur due to incorrect usage of the
fire control panel dc3400 SC.

2.2 Requirements for the operating company


Installation, maintenance and service of the fire control panel may only be carried out by
companies which are trained and qualified in the fire alarm industry.

Operator control actions at an already installed FCP dc3400 SC may only be done by
authorised and trained staff taking into account your countries safety regulations.

For safety reasons and to avoid malicious operations:


The necessary passwords for operation should only be forwarded to authorised personnel.

This operation manual does not include general or regional regulations. Information about
general and regional regulations and rules are prerequisite for the operations of the FCP
dc3400 SC.

Version 2.2 7
Installation Manual FCP dc3400 SC

2.3 Safety Installations

Warning!
Removing or decommissioning safety installations may result in material damage or
bodily injuries. Thus, only authorised service technicians are allowed to remedy any
deficiencies with regard to safety installations.
The functionality of the safety installations has to be checked on a regular basis.

The FCP dc3400 SC is equipped with different safety installations:


• Monitored emergency power supply
• Mounting of the batteries
• Short and open circuit tolerant loop card outputs
• Powered by a switch-mode power supply
• Fuse-protected outputs of the power board card
• Monitoring of the external signaller output
• Earthing of all metal parts of the housing

Version 2.2 8
Installation Manual FCP dc3400 SC

3 Product information
3.1 Brief description
The fire alarm system is the central element with regard to the fire protection of a building.
Being an alarm system for dangerous situations, it is used to save lives and to protect
people’s health, the environment as well as material assets. It consists of the central fire
alarm system, the fire detectors as well as the control and alarm organisation.

The dc3400 SC system includes several compatible assemblies as well as small, individual
centre applications. Currently, the FCP dc3400 SC monitors a loop wiring system (loop) which
may include up to 126 loop components which, in turn, can be divided into 100 detector
zones with a line length of up to 3000 m. The loop wiring system is a monitored 2-wire bus
with a ring line. The system guarantees a safe detection of fire areas or impurities due to the
individual identification of the detectors and/or the addressing and control components and
provokes a predefined action.

The different lights on the LED display indicate current alarms, faults and other messages.
The display which can be easily operated and understood provides comprehensible clear text
information with regard to operation, fault and alarm.

3.2 Environmental conditions


In order to ensure a safe use of the FCP dc3400 SC it is necessary to observe and comply
with certain environmental conditions when installing the system.

Environmental condition Recommendation


Ambient temperature -5 °C to 40 °C
Relative humidity 5 – 95 % (non-condensing)
Premises no humid rooms
no strong vibrations

3.3 Technical data


Constructive data
Housing Sheet steel, RAL 7035
Dimensions (H x W x D) 300 x 400 x 135 mm
Weight 6,5 kg (without batteries)
(without batteries)
Bushes At the top 8 x Ø 20 mm
Back top opening 2x (W x H) 95 x 26 mm
P class IP30

Version 2.2 9
Installation Manual FCP dc3400 SC

Electrical data

Supply voltage 180-264 V AC


Mains frequency 47-63 Hz
Nominal panel voltage 32 V DC
Standby current with the 300 mA
following development:1x CP-
DIS, 1x CP-LI3120, 1x CP-MB,
1x CP-PSB1, 1x CP-CPB
Nominal loop voltage 30 V DC
Output 24 V DC max. 400 mA
Alarm current with the 350 mA
following development:1x CP-
DIS, 1x CP-LI3120, 1x CP-MB,
1x CP-FBI, 1x CP-PSB1, 1x CP-
CPB
Charging current max. 1.6 A
Imax. a 1,4 A
Outputs of the CP-BM module 3 outputs potential-free (relay) 30 V DC / 2 A
configurable using the dct 3400
programming tool Output 1 default = collective alarm
Output 2 default = collective fault (inverted)
Output 3 default = extinction out (not changeable)

Output monitored (not potential-free) 500 mA


default = external signallers)
Batteries max. 2 x 12V/12Ah
Mains Adapter 32 V DC / 250 W

Fuses
Fuse holder Mains connection 230 V supply mains adapter 3,15 A delayed-action
CP-PSB1 Power Board Card F200 / Battery fuse 4 A fast-acting
F401 / 32 V system voltage 4 A fast-acting
F400 / 24 V Ub ext. devices 1 A fast-acting
CP-MB Basic Module F600 / external signallers 500 mA fast-acting
CP-LI3120 loop card F700 / loop 500 mA delayed-action

Interfaces
Number of loops 1
Length of the loop line max. 3000 m (depending on loop components)
Number of loop components 126 (per loop)
Number of programmable zones 100
Interfaces 1 x USB for connecting to PC
Display Touch screen display 320 x 240 pixels (1/4 VGA)

Version 2.2 10
Installation Manual FCP dc3400 SC

3.4 New features in Version 2.5


3.4.1 Serial number check
The loop card of the FCP checks the serial number of all read in loop components. If
differences are notified, then a fault message "Serial number changed" appears. This fault
can NOT be reset by pressing "Reset".

To change a polluted or defective detector you can copy the detector data to a new detector.
You need to enter the menu "System parameters" and start "Extend / reduce loop". The new
serial number of the detector will now be saved and the fault message will disappear.

3.4.2 Detection of detector change (Type check)


New is also the perusal of the detector type.
Changing a detector type, for example from an "O" to an "OT" detector, then you need to
start the "Extend / reduce loop" procedure from the menu "System parameters".

The new detector will still be recognized as a new detector, which will automatically be set to
the default zone 9501 and the fault message "Wrong detector type" will be displayed.

You need to reprogram the detector to the desired zone via the dpt software.
The fault message will disappear doing so.

The following conditions lead to the detector change fault (type check):
• Concerning detectors have an isolator (3300 series)
• There are no further faults in the loop

The type check cannot be done in line operation.

3.4.3 Indication of detector pollution


All automatic detectors with a optical measure chamber (O, OT, OTi, Oti Fusion...) are
poluttion monitored. The FCP can determine the grade of pollution in three levels.
Level 1 & 2 do not lead to a fault message, only a notify message will be generated.

Level 1: Pollution >30% = Notify message


Level 2: Pollution >70% = Notify message
Level 3: Pollution >80% = Fault message

A Pollution of >80% will automatically lead to a fault message and the fault relay will be
triggered.

3.4.4 Key lock function


A key lock function can be installed from version 2.5 or newer. This key lock function can be
used to unlock the user password levels.
This must be programmed in the dpt software in the system parameters.
Hardware implementation is done via a contact on the "Display and Indication Board".

Version 2.2 11
Installation Manual FCP dc3400 SC

3.4.5 Mappings

The possible mappings have been extended. Further source and targets have been added.
Additional information can be found in the dpt manual.

3.4.6 Firmware-Updates
Firmware updates of the single FCP boards are now only possible via the dpt. A FCP dc3400
SC version 2.1.5 can now be updated to version 2.5. All FCP boards will be updated
automatically. Exception is the Display and Indication Board. The board can be updated
separately to install new languages.

4 Installation
4.1 Requirements
The following procedures are to be assured in order to ensure a fault free operation of the
FCP dc3400 SC, the following

• Only install the FCP dc3400 SC in dry, clean and conditionally accessible rooms.
In this connection, observe chapter "3.2 Environmental conditions" on page 9.
• Assemble the FCP dc3400 SC without mechanical stress on a level mounting surface.
The FCP dc3400 SC may only be commissioned after it has been professionally attached
to a wall or mounting surface with sufficient load-bearing capacity.
• Avoid strong electrical / electro-magnetic and mechanical influences. This applies in
particular to the assembly of the FCP dc3400 SC, components and installation lines in the
immediate vicinity of fluorescent lamps or energy cables and the fastening on vibrating,
instable surfaces like, e.g. thin partition walls.
• Do not mount the FCP dc3400 SC in rooms with detrimental influences.
• Connect the PE and FE connection (functional earth) of the FCP dc3400 SC housing with
the PE rail of the distribution/sub-distribution from which the FCP dc3400 SC-is supplied
with mains voltage.
• Do not connect the FCP dc3400 SC to IT voltage supply systems.
• Only install the FCP dc3400 SC in places with normal room temperature in order to
guarantee a perfect life time of the batteries.

Version 2.2 12
Installation Manual FCP dc3400 SC

4.2 Inspection for completeness and damage


during transport

Note!
Before starting with the assembly:
Check all supplied parts of the FCP dc3400 SC for completeness and damage. In
case of damage, contact the manufacturer.

The housing is supplied completely, with the modules that have already been pre-assembled
by the manufacturer:
• "CP-MB" Basic Module
• "CP-PSB1" Power Supply Board
• "CP-CPB" Central Processing Board
• "CP-DIS" Display and control panel
• "CP-LI3120" Loop Card

The batteries are not contained in the delivery and can be acquired from the manufacturer.

Version 2.2 13
Installation Manual FCP dc3400 SC

4.3 Internal components of the FCP dc3400 SC

Warning! EMC protective measures.


When handling electronically assemblies, always take suitable measures for
discharging static electricity.

Note!
In the FCP dc3400 SC software, the devices connected to the CAN bus are called
“CAN devices” and/or CAN components. In this connection, both terms have the
same meaning.

4.3.1 Location of the components

4.3.2 Housing
The housing consists of sheet steel and is provided with a lockable door. It is assembled on
the surface. The lines are either led into the housing at the back or through the upper and
lower bush openings. The housing accommodates the whole electronics and the energy
supply. The modules for the display and the operation are attached to the housing door. In the
lower part of the housing, the batteries for the emergency power supply can be installed.

Version 2.2 14
Installation Manual FCP dc3400 SC

4.3.3 Mains adapter


Technical Data

Input

Input voltage range 180-264V AC


Mains frequency 47-63Hz

Output

Total output power 250W (32V)


Output voltage 32V DC
Overload protection electronic

Version 2.2 15
Installation Manual FCP dc3400 SC

4.3.4 CP-PSB1 Power supply board


The power supply board card is equipped with a low voltage disconnect. That means that if
the batteries’ final discharging voltage (22.7 Volt) is reached, the FCP dc3400 SC is disabled
in case of a mains fault.

Technical Data

Input voltage (input) 32V Medium power consumption 32 V max. 1600mA (idling, max. charging current)
Output voltage (UbExt.) 24V up to max. 28V DC, 500mA KTY81-210 Temperature sensor ±1%
5V supply voltage 5.39V DC (internal) F200 / Battery fuse 4A fast-acting
Batteries 24V (2 x 12V / 26 Ah) in series F400 / 24 V Ub ext. devices 1A fast-acting
Final charging voltage ca. 27.3V / ± 5 % at 20 °C F401 / 32 V system voltage 4A fast-acting
Final discharging voltage 22.7V / ± 5 % at 20 °C Board dimensions 127 x 100 mm
Medium power consumption 32 V 200mA (idling, no charging)

Version 2.2 16
Installation Manual FCP dc3400 SC

Function
The voltage supply of the FCP dc3400 SC and the 24V DC supply voltage for external devices
are located on the power board card. The maximum current load due to external devices is
400mA.

CPU
The mains adapter’s CPU measures and monitors all voltages and if necessary, forwards
these values via the CAN bus. Additionally, the CPU controls the charging controller for the
connected battery.

Sub voltage disablement of the battery


If the battery voltage falls below 22.7 V, the battery is disabled. This function can be bridged
using jumper 201 in order to achieve an emergency start function. Please keep in mind that
an exhaustively discharged battery can normally not be used anymore.

Charging controller
The battery voltage varies by means of temperature. The current is consistently maintained at
1.6 A. When the final charging voltage is reached, the system will change over into trickle
charge mode. In case of negative temperatures, the battery will not be charged.

Disablement criteria
The battery charge is disabled as soon as:
• The actual temperature falls below or exceeds the temperature specified by the battery
manufacturer
• The charging current exceeds 1.8 A
• After 24 hours, if the battery has still not taken up 80% of its charge
• The final charging voltage is not achieved within a predefined period

Temperature compensation
If the ext. temperature sensor is not connected, the temperature sensor is analysed in the
processor of the power board card. As soon as the ext. temperature sensor (type KTY 81-218)
is connected, it accepts the battery control function.

Explanation of the two fault messages


• Battery fault / missing: Means the battery is actually missing or the voltage is below
14 Volt.
• Battery totally discharged: Means that the battery voltage is below 22,7V and can only
appear in mains operation.

Batteries
The power board card is designed for a battery capacity of maximally two batteries (12 Ah)
with the dimensions 100 mm x 151 mm x 99 mm (H x W x D). If the mains voltage fails, the
batteries continue the voltage supply without interruption. Maximum charging current: 1.6 A.

Sign of life LED


The sign of life LED must flash every second. If this is not the case, the input voltage has
failed or the power board card is defective. In this case, check the mains adapter connection
and/or the main fuse at the mains connection.

Version 2.2 17
Installation Manual FCP dc3400 SC

CAN device address of the power supply board


A CAN device address must be assigned to address 1.
Identical addresses can be assigned to different CAN devices.

CAN address DIP 1(1) 2(2) 3(4) 4(8)

1 1 0 0 0

Description of the jumper

Jumper-No. Description

ST100 not set; WD


ST101 not set; JTAG
ST201 not set; Deep discharge protection
ST402 set; PE Measurement

Legend

JTAG: Joint Test Action Group


WD: Watchdog

Version 2.2 18
Installation Manual FCP dc3400 SC

4.3.5 CP-CPB Main board

Technical Data
Power consumption 21mA

Function
The CPB is the central control unit of the FCP dc3400 SC.

Interfaces
Every main board is equipped with 3 plug sockets.
- 1 RS232 jack for a record printer (not available in the SC version)
- 1 USB jack to connect to a computer (for uploading and downloading the
configuration data using the programming programming tool (dpt from V9.0).
- 1 RS232 jack not in use.

Due to the small housing form factor there is no record printer for dc3400 SC available.

Version 2.2 19
Installation Manual FCP dc3400 SC

Setting the Sub-Panel Number (SP Number)


Here, the number of the sub-panel in the network is set. If there is only one sub-centre, the
SP number “1” must be set. The setting is completed in the binary code. A dc3400 SC
always is a stand-alone system.

SP number DIP 1 2 3 4 5 6 7 8
(1) (2) (4) (8) (16) (32) (64) (128)
1 1 0 0 0 0 0 0 0
2 0 1 0 0 0 0 0 0
3 1 1 0 0 0 0 0 0
4 0 0 1 0 0 0 0 0
5 1 0 1 0 0 0 0 0
6 0 1 1 0 0 0 0 0
7 1 1 1 0 0 0 0 0
8 0 0 0 1 0 0 0 0

255 1 1 1 1 1 1 1 1

Sign of life LED and emergency path


The sign of life LED must flash every second. If this is not the case, the main processor of the
central computer has stopped or failed. The FCP dc3400 SC is in emergency operation and a
system fault is displayed. Safe functioning of the FCP dc3400 SC is not guaranteed any more.

There is an alarm display at the CP-DIS display and control panel. The internal buzzer of the
FCP dc3400 SC will sound and the collective fault relay on the CP-MB basic module will
change into fault mode. There is an alarm display at the fire brigade control panel.

Description of the jumper

Jumper-No. Description

JP202 not set; JTAG


JP300 not set; Ext. CAN determ.
JP500 not set; WD

Legend:

JTAG: Joint Test Action Group


WD: Watchdog

Version 2.2 20
Installation Manual FCP dc3400 SC

4.3.6 CP-MB basic module

Note!
The fault relays are energised in standby by and will de-energised in case of fault
conditions

Technical Data
Power consumption 40 – 56mA Inputs / outputs 2 inputs potential-free 24V DC / 5.8mA
3 outputs potential-free 30V DC / 2A
1 output monitored (not potential-free) 500mA

Version 2.2 21
Installation Manual FCP dc3400 SC

Function
The main board provides standard inputs and standard outputs.

Inputs / outputs
The outputs are programmed as follows:

Outputs Standard programming

Relay 1 Collective alarm


Relay 2 Collective fault
Relay 3 Default interface (not active)
External signaller 1 External signallers

Jumper description
Jumper No.: Description

J100 not set; JTAG


K115 not set; JTAG
J200 not set; without function
J201 not set; without function
J202 not set; without function
J203 not set; without function
JP400 not set; WD
J400 set by default; Alarm via WD
J401 set by default, Fault relay via WD
J402 set by default, Fault relay via NP
J403 set by default; Alarm via Controller
J404 set by default; Fault relay via Controller

Legende:

JTAG: Joint Test Action Group


NP: Emergency path
WD: Watchdog

Description of the LEDs


LED number Description

D 201 Sign of Life LED


D 405 Alarm relay LED; indicates triggered relay
D 406 Fault relay LED; indicates triggered relay
D 407 Relay 3 LED; indicates triggered relay
D 601 acoustic signal generator relay LED; indicates triggered relay
D 408 Watchdog LED; signals various conditions every few seconds
- 3 sec. flash = normal mode
- 1 sec. flash = programming mode (updates)
- 0,1 sec. flash = Emergency mode

Version 2.2 22
Installation Manual FCP dc3400 SC

Sign of life LED


The sign of life LED must flash every second. If this is not the case, the main processor of the
CP-MB basic module has failed. The FCP dc3400 SC is in emergency operation and a system
fault is displayed. Safe functioning of the FCP dc3400 SC is not guaranteed any more. In
emergency operation, corresponding information (alarm / fault) is transmitted through the
emergency paths. Only minimum functions (depending on the settings on the CAN device
cards) (e.g. basic module) can be performed. For more information please refer to chapter
“Sign of life LED and emergency path“ on page 20.

CAN device address of the basic module


A CAN device address must be assigned to address 1.
Identical addresses can be assigned to different CAN devices.

CAN address DIP 1(1) 2(2) 3(4) 4(8)

1 1 0 0 0

Emergency operation functions


Alarm
Normal operation: The basic module activates the alarm relay (jumper JP 403 must be
plugged in) and the external signallers.

Emergency operation: The “Alarm” message is forwarded between the CAN devices via
emergency paths. For the “Alarm” relay activation in emergency operation, jumper Jp 401
must be plugged in. For the activation of external signallers, jumper Jp 600 must be plugged
in.

Fault
Normal operation: The basic module activates the fault relay. JP 402 must be plugged in.
Emergency operation: The “Fault” message is forwarded between the CAN devices via
emergency paths. For the “Fault” relay activation in emergency operation, jumpers Jp 401
and 402 must be plugged in.

Version 2.2 23
Installation Manual FCP dc3400 SC

4.3.7 CP-LI3120 Loop card

Technical Data

Power consumption 30 – 380 mA ML connections 2 Terminals / 1 loop or 2 lines

Function
Communication with the loop components is effected via the loop card. Thus, it is the
connection between central computer and loop components.

Sign of life LED


The sign of life LED must flash every second. If this is not the case, the main processor of the
loop card has failed. At the FCP dc3400 SC, a system fault is displayed. The status of all
detectors of this loop card is not updated any more.

Version 2.2 24
Installation Manual FCP dc3400 SC

CAN Device address of the loop card


A CAN device address must be assigned to address 1.
Identical addresses can be assigned to different CAN devices.

CAN address DIP 1(1) 2(2) 3(4) 4(8)

1 1 0 0 0

Emergency operation functions (Central computer CPU has failed)


The “Alarm” and “Fault” emergency paths are activated by the loop card if there is an
emergency operation and a corresponding message. If at least one loop components supplies
an alarm or fault and/or if there is an internal fault on the loop card, the corresponding
emergency path is activated. The corresponding control, independent of the FCP dc3400 SC
programming, however dependent on the settings made on the CAN device cards (e.g. basic
module) is activated, as well. For more information please refer to chapter “Sign of life LED
and emergency path“ on page 20.

Attention!
The CP-LI3120 Loop card does not provide the same diagnostic possibilities as the
detectomat loop-tester LT3000. Use the loop tester LT3000 to check possibly
manual assigned detector addresses and the loop structure on correctness at first
installation or after extending the structure. This can assure a correct and confident
running of the fire control system.

Description of the jumper

Jumper-No. Description

JP100 not set; JTAG

Legende:

JTAG: Joint Test Action Group

Version 2.2 25
Installation Manual FCP dc3400 SC

4.3.8 CP-DIS Display and control panel (DCP)

Technical Data
Power consumption 35 – 70 mA

Function
The DCP constitutes the connection between the operator and the FCP dc3400 SC. Here, any
important information is shown and/or here, the operator is able to send different commands
to the central computer.

Version 2.2 26
Installation Manual FCP dc3400 SC

Sign of life LED


The sign of life LED must flash every two seconds. A continuously glowing signals a
programming status. The FCP dc3400 SC is in emergency operation and a system fault is
displayed if the LED does not light at all. Safe functioning of the FCP dc3400 SC is not
guaranteed any more. In emergency operation, corresponding information (alarm / fault) is
transmitted through the emergency paths.
Only minimum functions (depending on the settings on the CAN device cards) (e.g. basic
module) can be performed. For more information please refer to chapter “Sign of life LED and
emergency path“ on page 20.
Apart from that, an LED shows the status of the watchdog. This LED must also flash every
second. If this LED is not flashing, emergency operation is not possible any more. At the
display, the presentation of information is not possible any more.

Watchdog LED
Signals various conditions every few seconds
- 3 sec. flash = normal mode
- 1 sec. flash = programming mode (updates)
- 0,1 sec. flash = Emergency mode

CAN device address of the display and control panel


A CAN device address must be assigned to address 1.
Identical addresses can be assigned to different CAN devices.

CAN address DIP 1 2 3 4

1 1 0 0 0

Emergency operation functions


Only minimum information (alarm/fault) can be presented in the display if the FCP dc3400 SC
is in emergency operation (system fault). If the Display is without function, then the fault
status can still be recognized by the LEDs and the buzzer.

Description of the jumper

Jumper-No. Description

J100 not set; JTAG


JP 101 set by default; Buzzer activation
J102 not set; CAN-Bus termination
J103 External door contact
ST105 not set; JTAG
K201 not set; WD

Legende:

JTAG: Joint Test Action Group


WD: Watchdog

Version 2.2 27
Installation Manual FCP dc3400 SC

Display calibration

Warning! Danger due to electric shock.


For the display calibration, the FCP dc3400 SC must be energised.
Thus, only authorised and trained service technicians are allowed to calibrate the
display.

Information!
The fault message "Fault CP-DIS 1 Display calibr. took place" will appear after
every display calibration. This is normal and can be reset by pressing [ Reset ].

1 Touch the display anywhere using your finger or a pin with a blunt tip.
2 While still touching the display, press the [ RESET ] button on the back of the CP-DIS DCP.
The information “Loading program …” and afterwards “!Calibration!” appears. Adhere to
the following instructions in the display.
3 Touch the indicated spots in the corners as exactly as possible.
4 Subsequently touch several freely selected points at the display.
5 Press the [ Ok ] button if the presentation of the points is exactly below the touch point.
6 If it has not been possible to complete the display calibration orderly, click on the []
button and repeat the procedure.

4.4 External components


The detectors, modules, manual call points and loop components are combined in a loop
using a two-wire line and connected directly to the FCP dc3400 SC.
The maximum length of a loop is 3000m. A loop comprises a maximum of 126 addresses
and/or loop components. The elements like detectors, manual call points, signallers, etc.
must be easily accessible and permanently fastened.

Example of Connection Possibilities

Version 2.2 28
Installation Manual FCP dc3400 SC

4.5 Housing assembly


Warning! Danger due to electric shock.
Assembly and installation of the FCP dc3400 SC must be carried out in a dead-
voltage state!
The FCP dc3400 SC may only be operated with closed housing. Operation is
inadmissible if the housing is open, the housing openings have been manipulated
or if housing plates are missing.

Warning!
Connect the housing to an earth potential in order to avoid electrostatic charging.
Observe the precautions when dealing with electrostatically sensitive components.

The FCP dc3400 SC is to be fitted to the wall so that the displays can easily be read and the
keyboard can easily be used. The mounting height should lie between 1.50 m and 1.80 m.
Display and LED display should be at eye level so that the operator can operate the display
without problems.

The housing is provided without batteries and only with the internal lines. The use of batteries
as replacement power supply is absolutely necessary. For more information please refer to
chapter “5.1.2 Installing the batteries“ on page 34.

4.5.1 Assembly steps

1 For the wall assembly, use S8 dowels and Ø 6 mm cylinder head bolts. Select a screw
length ensuring a stable suspension.
2 Make the upper two borings (Ø 8 mm) in the wall according to the assembly drawing.
3 Insert the dowels and screw two cylinder head bolts into them. When doing so, comply
with a distance between the screw head and the wall of approx. 19 mm. The cylinder
head screws must not bear the housing on the spacers!
4 For the time being, hook up the housing.
5 Mark the dimensions for the bottom borings.
6 Remove the housing again in order to make the bottom borings (Ø 8 mm) into the wall.
7 Hang the housing finally onto the top screws and apply the bottom screws.
8 Make sure that the housing is firmly hanging at the wall and that no mechanical stress is
generated.

Version 2.2 29
Installation Manual FCP dc3400 SC

4.6 Line connections


After the housing assembly, the lines of the external components (detectors and/or modules)
of the FCP dc3400 SC are inserted.

Note!
For concealed wires, use the opening in the housing’s back wall.
For surface-mount wires, use the openings on the top of the housing for cable
connections. In the delivery condition, these openings are closed by means of a
cover plate.
The wires used must be shielded in order to provide protection against
interferences. We recommend using correspondingly prescribed fire alarm lines.

In order to avoid short-circuits with other terminals and other earth faults due to not
insulated, blank lines of the drain wire, they should be insulated. This measure must
particularly be complied with in the area of fire-extinguisher cabinets, when connecting
pressure switches in metal housings on IOMs or in assemblies with metal consoles at profiled
sheeting and other metal constructions.

Warning!
Do only complete the line connections if the FCP dc3400 SC is in a dead-voltage
state.

1 Pull off the mains fuse holder at the 230V terminal so that there is no mains voltage after
connection of the voltage supply.
2 Pass the detector lines and the supply line for the voltage supply through the provided
openings into the housing.
3 Attach all signal lines (detectors, sirens, etc.) to the strain relieves. Do, however, not yet
wire them! In limit value detectors you have to make sure that the terminating resistor
5.6kOhm / 0.25W that is installed in the FCP dc3400 SC housing is removed and
installed into the last detector in the line.
4 Connect the supply lines for the voltage supply to the 230 V terminals.
5 Proceed as described in chapter “5 Commissioning“ from page 31.

4.6.1 Earthing
Like all electrical devices, the FCP dc3400 SC can be damaged by a strike of lightening. By
means of an orderly earthing, the risk of damage can be minimised.
For this purpose, connect the PE of the mains connection of the FCP dc3400 SC with the PE
rail of the distribution/sub-distribution from which the FCP dc3400 SC is supplied with mains
voltage.

Version 2.2 30
Installation Manual FCP dc3400 SC

5 Commissioning
5.1 First commissioning
Warning! Danger due to electric shock.
The FCP dc3400 SC must still be in a dead-voltage state.

One prerequisite for the commissioning is an orderly assembly of the FCP dc3400 SC.
This includes the wall assembly incl. all inserted signal lines (detectors, sirens, etc.) that have
not been wired, yet.

The CAN devices that are assembled on the top of the connection board on the left and on the
right constitute the CAN bus beginning and the CAN bus end. If more modules are attached to
the CAN devices specified above, the former constitute the bus beginning and the bus end.
All other CAN devices are correspondingly located in the bus centre.

1 Check the correct seat of all CAN devices on the connection board.
2 Wire all open, monitored outputs that are not to be wired with corresponding terminating
resistors:
• Output External signallers
• Monitored outputs loop components

You complete the first commissioning by means of our commissioning record. The
commissioning record supports you in the commissioning and also simplifies the support by
the manufacturer. For wiring the lines use the supplied connection plans of the loop devices.

Note!
Record the completed commissioning action in the supplied commissioning record.

5.1.1 Procedure of the commissioning report


The commissioning report contains the chronological order of all necessary steps to
successively commission the FCP dc3400 SC. Document all measurements in the
commissioning report.

The FCP dc3400 SC does not provide the same diagnostic possibilities as the Fire Control
Panel detect 3004 (Order-No.: 31973). Use the loop tester LT3000 (Order-No.:31625) to
check possibly manual assigned detector addresses and the loop structure on correctness at
first installation or after extending the structure of the loop. This can assure a correct and
confident running of the fire control system.

Wiring and checking Lines


If available, wire the following lines or check lines that have already been wired (the drain
wire must not be wired to the PE potential, yet!):
• Power supply (do not turn on)
• Signallers
Note!
Only use shielded lines.

Version 2.2 31
Installation Manual FCP dc3400 SC

Measuring terminating resistors on conventional lines


If there are conventional lines, measure the terminating resistors on all conventional lines at
the lines in the FCP dc3400 SC that have not been wired, yet. If the terminating resistor is ok,
you can wire the detector lines.

Measuring cable resistance loop technology on +ML


Measure the cable resistance at the lines that have not been wired, yet. Check the wires if
there are any deviations.

Line resistance Corresponding line length Wire diameter Fire alarm cable

max. 76 Ohm 1 km 0.8 mm

Line resistance of the drain wire (shield)


Measure the line resistance of the drain wire (shield) per loop. The drain wire must not be
wired in the FCP dc3400 SC, yet.

Line resistance Corresponding line length Drain wire diameter

max. 150 Ohm 1 km 0.5 mm

In case of deviations, check the lines!

Earth-Fault test on power supply board


Note!
Do not connect any devices (Notebook, PC, ...) to a FCP interface (USB, RS232)
during the earth-fault test or if the panel reports an earth fault. This could cause
damages to the dc 3400 SC or to the device.

1 Check that the Jumper 402 (Earth) is set


2 Connect PE-Connection to – and/or + terminal
3 An earth fault should rise after a few seconds

Wiring the loop and the conventional lines


Wire the loop and conventional lines according to the connection diagrams to the
corresponding terminals.

Version 2.2 32
Installation Manual FCP dc3400 SC

Powering the FCP dc3400 SC and Read-in the CAN-Devices


If the FCP dc3400 SC is started for the first time, the CAN devices are firstly read in
automatically.
1 Check date and time after the first start and correct them, if necessary!
2 Calibrate the display. For more information please refer to chapter “Display calibration“
on page 28.

Note!
For the operation of the display, please refer to more information in chapter 6
„ Operation of the FCP dc3400 SC “ on page 37.

Warning!
Only unplug and/or plug the CAN devices if the FCP dc3400 SC is in a dead-voltage
state.

1 Push the fuse holder back into place to supply the voltage supply via the 230 V terminals.
The FCP dc3400 SC starts up. At the display, the message “Building up Loop” appears.

2 In the first commissioning, all CAN devices are shown in the beginning. If all CAN devices
are shown in the display correctly, you have t confirm it. If not all CAN devices are
shown, check the correct seat, the addressing and the function standby (sign of life LED)
of the CAN devices. In this case, repeat the CAN device read-in by pressing the [ Scan
FCP mod. again ] button.
3 Press the [ Ok ] button at the display, if all CAN devices have been recognised properly.

Detector Read-in
After you have read in the CAN devices, you need to press [ Ok ] to open the read in
functions.

1 Select the desired read in funktion.

Learn loopstructure (SCAN): The existing addresses or those that have first been
assigned manually (easy check) are scanned in. In this way, an existing system can be
extended, i.e. the new detectors are assigned free addresses via the easy check and are
then read-in by means of this scan command.

Readdress loopstructure (AUTO): Comprises the automatic addressing. In the automatic


addressing, loop components are automatically assigned addresses according to the line
run. It is thus suitable for the first commissioning.

Note!
Read-in of the loop components (detectors) can be repeated as often as you want
(e. g. for the troubleshooting in the loop structure).

2 Press the [ Ok ] button if all loop components are displayed correctly. Thus, the “Detector
Read-in” process is completed.
3 Press the [ Ok ] button in order to confirm the display. After the confirmation, the
“Standby” menu appears.

Version 2.2 33
Installation Manual FCP dc3400 SC

As no batteries have been connected, yet, the “Fault – Open circuit Batteries” error message
still appears in the display and at the LED display. In order to remedy the fault, connect the
specified batteries. More information in chapter „3.3 Technical Data“ from page 9.

Wiring the shield on one side to PE


Wire the shield on one side to PE. If it is wired on both sides, the shield must be separated
approximately in the centre of the loop.

Testing the loop communication


One after the other, separate the –ML individually. Corresponding loop faults (open circuit L-)
must be displayed.

5.1.2 Installing the batteries


The batteries guarantee an emergency power supply for the FCP dc3400 SC in case of a
voltage fault. The batteries are not contained in the delivery. The FCP dc3400 SC is designed
for a maximum of two batteries. Only use the battery types recommended by the manufacturer.
For more information please refer to chapter “3.3 Technical Data“ from page 9.

Warning! Danger due to electric shock.


Installation of the FCP dc3400 SC may only be carried out in a dead-voltage state.
For this purpose, the fuse holder at the mains connection terminal must be opened
in order to disconnect the emergency power supply.

Put the FCP dc3400 SC into a dead-voltage state. (Pull out the detachable mains fuse)
1 Put the batteries into the housing.

Warning!
Pay attention to the polarity of the connections. In case of wrong polarity, the
battery fuse on the power board card will blow.

2 Connect the batteries using the supplied connection lines. For more information see
annex 2. After the batteries have been connected, the battery fault message at the
display disappears.

5.1.3 FCP dc3400 SC standard programming


The FCP dc3400 SC automatically sets up a few standard programming's at commissioning.
The relay 1 will be set as an alarm relay, the relay 2 will be set as a fault relay. So the relays
will be triggered in case of an alarm or fault. The external signallers will also be activated in
case of an alarm by default programming from the basic module.

The loop sounders and IO-modules (outputs) will also be activated by default depending on
the loop structure. The default standard programming of the relays and components will also
be downloaded and indicated in the corresponding dpt-explorer of the detectomat
programming tool.

Version 2.2 34
Installation Manual FCP dc3400 SC

5.1.4 Configuration of the FCP dc3400 SC


Note!
For more information regard to the dpt 3000 detectomat programming tool Art. No.:
30138 (From V9.0 upwards)

5.1.5 Functional test for commissioning


Complete the following functional tests:
• Releas automatic and non-automatic detectors
• Test the external signallers
• Test the external activation (if available)
• Test mains fault
• Test the batteries for open circuits
• Test the standby current of the FCP dc3400 SC in case of mains fault

Note!
After you have successfully commissioned the FCP dc3400 SC, store the completed
commissioning record in the FCP dc3400 SC for maintenance purposes. Make a
copy and take it to your documents.

5.2 Extend / reduce loop (components)


Compared to the first commissioning, there is already a configuration of the FCP dc3400 SC
that is stored in the EEPROM.

There are the following possibilities for reading in the loop structure. Check and test if the
changes to the loop are still conform to the programming before continuing.

Learn loopstructure (SCAN)


Using this option, an existing loop can be extended by one or more loop components. One
prerequisite is that the newly installed loop components must be assigned a free loop
address manually in advance. This manual addressing is exclusively completed using the
“Easy Check” diagnosis and programming device.

1 Read in the detectors via [ Menu | System Parameters | Extend / reduce loop ].
2 Press [ OK ] to confirm.
3 Confirm the selected FCP modul again pressing [ OK ]
4 Press [ Start ]. The existing addresses and/or those that have first been assigned
manually are scanned in and/or read in.

Version 2.2 35
Installation Manual FCP dc3400 SC

5.3 Limits, current calculation


Standby current in mA Alarm current in mA, in addition

Device: Individually Units Total Individually Units Total

Power board card 47 0


CPU 21 0
Basic module 40 16
DCP 35 33
Loop card >30 0

Loop component
Line length max. 3000m (with Ø 0.8mm)
Operating current max. 36mA (900 current units with ≤ 2000m)
Components max. 126

Detector/Module Standby current Current units

PL 3200 / 3300 O 250 μA 7


PL 3200 / 3300 T 250 μA 7
PL 3200 / 3300 OT 280 μA 7
PL 3300 PBDH 250 μA 7
PL 3300 MCP 250 μA 7
PL 3300 COBT 250 μA 15
PL 3300 Oti/Oti Fusion 250 μA 7
PL 3302 Oti/Oti Fusion 250 μA 7
PL 3300 PA 280 μA 7
LS 3300 VLC 280 μA 150
LS 3300 VXB 400 μA 125
LS 3300 270 μA 125
SDM 3300 250 μA 125
IOM 3311 500 μA 11
IOM 3322 760 μA 19
OMS 3301 500 μA 11
OMS 3301 mini 370 μA 10
TCM 3300 560 μA 14
AMD 3311 /MCP kit 370 μA 10
AOM 3301 400 μA 11
Verso 32 via AOM 3301 400 μA 11
CS 200 via AOM 3301 400 μA 11

Version 2.2 36
Installation Manual FCP dc3400 SC

6 Operation of the FCP dc3400 SC


The FCP dc3400 SC is housed in a sheet-steel casing. The panel is protected with a key
against unauthorized access. The following operating and display elements can be accessed
from the outside:
• Display
• LED display

6.1 Display
The FCP dc3400 SC is equipped with a touch screen display in a landscape format which can
be used to control the program sequence with only a single touch. You can operate the
display with your fingers or by using a PDA pen.

Warning!
Never use a ball point pen or other objects with a sharp tip. Using such objects will lead
to damage of the display.
Clean the display with a soft, dry cloth. Do not use benzene, paint thinners or cleaning
alcohol (spirit).

If the display has been turned on but has not been used for a period of 12 seconds, the
background lighting of the display will disable automatically (normal operation mode).
The background lighting of the display will be automatically activated if a message
(alarm/fault) is detected or if you touch the display.

6.1.1 Normal Operation Mode


If the dc3400 SC is in its normal operation mode, i.e. no messages have been received and
no functions have been setup from the main menu, the menu button will be in the top right of
the display. The display and keys have the following meaning.

Display Meaning

Zones in Alarm 0000 Displays the number of any present alarms


Faults 0000 Displays the number of any current faults
Disablements 0000 Displays the number of current disablements
Info 0000 Displays the number of current information messages
Reset Resets any faults or fire that may be displayed. If the cause has not been
solved then the fault or fire message will be indicated again.
Silence alarms Silence or enable any sounder outputs
Transm.Unit Alarm on/off* Turns the transmission unit on or off*
Mutes or un-Mutes the internal buzzer during alarms of faults
Delay on/off Enables or disables any delays programmed
Menu Main menu key
* In the present version not available

Version 2.2 37
Installation Manual FCP dc3400 SC

6.1.2 Function Keys and Main Menu


The keys and the menu headings on the display have the following meaning.

Display Meaning
 Scroll up
 Scroll down
Ok Confirm and select
 Back to previous menu
Transm.Unit Alarm on/off* Switches the transmission unit on or off*
Mutes or un mutes the internal buzzer during alarms of faults
Delay on/off Enables or disables any delays programmed
Return to the “Home” screen
Enable Enables detectors, zones, outputs, ext. sounders, which have been disabled
Disable Disables detectors, zones, outputs, ext. sounders.
Service For viewing the event log and to enable/disable the maintenance mode
System parameters To delete the event log, read CAN devices and detectors, reset to default
settings and to view the software version of the panel.
Alarm counter Displays the number of main alarms (any alarms generated while in
maintenance mode or detector / zone dependencies are not recorded here)
User interface Configure display
Select language
Lamp test
1 2 Set date and time
Set default display configuration
Keys 0 - 9 numeric keys
 deletes a wrong entry
C deletes the whole entry in area 2
1 Panel required information
2 Entry fields Touch the respective box in order to make an entry.
* In the present version not available

6.1.3 Message Structure


The messages in the display are shown as clear text. The graphic to the left provides an
overview of the general message structure. If you scroll using the [] and [] buttons, the
display automatically resets to the first message after 5 seconds.

1 Current date and time


2 3 4 2 Message date and time
3 Message number and text
4 Location (zone/detector number and detector type)
5 Custom text for detectors and/or detector zones
6 Message text (fine text)
7 Display of the last pending message
8 in case of alarm: Indicates further detectors in the zone are in alarm.
5 in the case of a fault and or a disablement: The display remains empty

7 1
Version 2.2 38
Installation Manual FCP dc3400 SC

6.2 LED-Display
The LED display automatically indicates an alarm, fault or any other information generated
from the panel.

6.2.1 Meaning of the LEDs


The LEDs have the following meaning.

Designation / display Meaning


ALARM (double LED) Red Is illuminated in case of a fire alarm. The corresponding alarm is
stored and the internal buzzer is activated.
FAULT (double LED) yellow Flashes when a fault is present. The fault message is stored and
the buzzer is activated.
Operation green Is on when the panel is in normal operation mode.
Flashes while in service mode.
Dis. Extinguishing Syst.* yellow Not available for the dc3400 SC.
Mains yellow Is lighted when the mains voltage is no longer present and the
system is running on batteries.
Battery yellow Is lighted when no batteries are present.
System yellow Is lighted during a system fault.
Ext. Outputs yellow Is lighted if the external sounders are disabled.
Flashes in the case of an external sounder fault.
Maintenance Mode yellow Is lighted when the system or zones have been switched to
maintenance mode.
Earth Fault yellow Is lighted to indicate an earth fault on the system or loop.
Disabled yellow Is lighted if detectors, zones and modules have been disabled.
Main Alarm Red Is lighted when a main alarm has been triggered.
Fire Brigade Called* Red Not available for the dc3400 SC.
Call Fire Brigade Red The user should alert the fire brigade.
Key Box Sabotage* yellow Not available for the dc3400 SC
Key Box Open* Green Not available for the dc3400 SC
Delay ON yellow Is lighted when a delay has been activated.
Transm. Unit-Alarm* yellow Not available for the dc3400 SC
* In the present version not available

Version 2.2 39
Installation Manual FCP dc3400 SC

7 Operating States
The current operating states are shown via an LED and in the display. If an alarm, fault or a
disablement message is generated at the same time, the messages are displayed according
to priority:
1. Alarm messages
2. Fault messages
3. Disablement messages
4. Information

In this case, the message with the higher priority is always displayed.

7.1 Operation
The “In operation” state is the normal operating mode of the FCP dc3400 SC. For this
operation, the door of the FCP dc3400 SC must be closed.

LED display
• “Operation” LED is on

Display
• “In operation” / “! Please touch display for operation!”

Version 2.2 40
Installation Manual FCP dc3400 SC

7.2 Alarms
7.2.1 Alarm "Main Alarm"
The dc3400 SC is in alarm and all programmed relays, sounders and outputs will be activated if
not

LED display
• “Alarm” double LED is on.
- The “Alarm” relay from the basic module is activated (standard programming)
• “Main alarm” LED is on.
- External sounders are activated if they have not been disabled or in fault.
• "Call Fire Brigade" LED is on
- Please inform the Fire Service immediately!

Display
• On the display, information regarding the device activated and the programmed message
texts are displayed.
• In the centre of the display, in which you can scroll using the [] and [] keys, the first
message is displayed. In the bottom field, you are always shown the last, current or
pending message.
• The alarm display is zone-related. The alarm counter only counts the zones that are in
alarm. If more detectors from one zone are in alarm, the number of detectors is displayed
on the right, between the [] and [] keys (e.g. two more detectors).
In order to view these additional detectors from that zone, touch this key.

7.2.2 Alarm "delay" & "detector/zone dependency"


The FCP dc3400 SC is in alarm state of a detector dependency, zone dependency or in delay
action mode.

LED display
• "Alarm" double LED is flashing at enabled delay action mode
• Yellow LED "Delay ON" is on at enabled delay action mode
• No LED indication (except Operation) at detector/zone dependency

The following alarms can occur:


• Detector dependency "Fire D1. knock trig."
Will occur as soon as a detector or MCP from a configured “Detector dependency” zone
goes into alarm. The main alarm will become active as soon as another detector or MCP
from the same zone becomes active.
• Zone dependency "Fire Z1. knock trig."
Occurs as soon as a detector or MCP from a zone configured as “Zone dependency”
goes into alarm. The main alarm is activated as soon as the second defined zone goes
into alarm.
• Alarm with the delay active
Occurs if a delay has been enabled and the corresponding detectors become active. After
receiving the alarm, the "Delay time" starts. If within the “Delay time” the " ” is
pressed, the “Intervention time” will start (main alarm starts if the “Delay time” has
expired or the delay is disabled). If within the “Intervention Time”, the FCP is reset, the
alarm is cancelled. The main alarm will become active once the “Intervention Time” has
expired. The "Delay time" and "Intervention time" can be programmed with the dpt 3000
detectomat programming tool. The total delay time cannot exceed 10 min.

Version 2.2 41
Installation Manual FCP dc3400 SC

Display
• On the display, information regarding the source the alarm and any programmed
message texts are displayed.
• In the centre of the display, where you can scroll using the [] and [] keys, the first
message is displayed. In the bottom field, you are always shown the last message.
• The alarm display is zone-related. The alarm counter only counts the zones that are in
alarm. If more detectors from one zone are in alarm, the number of further detectors are
shown in the display on the right, between the [] and [] keys (e.g. two more
detectors).
In order to view these additional detectors of that zone, touch this key.

7.2.3 Alarm "Maintenance Mode"


The FCP dc3400 SC is in "Maintenance Mode" and will not activate the sounders. Triggered
detectors will be indicated in the "Mainten. notes" window. (Maintenance is activated directly
at the FCP dc3400 SC). The alarm status will remain for about 40 seconds

LED display
• Maintenance mode LED glows yellow when enabled.

Display
• If a maintenance alarm is triggered, this will be displayed in the "Mainten. notes". The
zones or detectors in maintenance mode will also be indicated in the "Mainten. notes"
window.

7.3 Faults
LED display
• “Fault” double LED is flashing in yellow.
Display
• A message appears specifying the fault.
• In the centre of the display, where you can scroll using the [] and [] keys, the first
message is displayed. In the bottom field, you are always shown the last message.

After the fault has been rectified, there are two possibilities for resetting the dc3400 SC:
• Fault is reset automatically (e.g. in the case of an open circuit or a missing detector).
• Fault is reset by pressing the [ Reset ] key.

Warning!
Defective detectors, zones, inputs and outputs will not trigger an alarm. Inform the
Service or maintenance company.

Version 2.2 42
Installation Manual FCP dc3400 SC

7.4 Maintenance/Service
Warning!
Any detectors which are in maintenance mode will not activate any fire alarm outputs!

7.4.1 Disablements
LED display
• “Disabled” yellow LED is on.

Display
• A message will be displayed specifying the disablement. In this example the Sounder are
disabled.
• In the centre of the display, in which you can scroll using the [] and [] keys, the first
message is displayed. In the bottom field, you are always shown the last message.

7.4.2 Maintenance mode


When the dc3400 SC is in maintenance mode, the system can be tested without activating
alarms.

LED display
• The yellow LED “Maintenance Mode” is on.

Display
• A message will be displayed specifying which zones, detectors or outputs have been
switched into maintenance mode.
• If a maintenance alarm is triggered, this will be displayed according to the “Alarm
Display”. The triggered detector will be reset after approx. 40 seconds.

* The function "Enable/Disable detectors for maintenance" is in this version not possible.

Version 2.2 43
Installation Manual FCP dc3400 SC

8 Operation Procedures at events


Attention!
Regard to your alarm organisation in case of fire alarm events

8.1 Alarm (Main alarm)


When the dc3400 SC is in alarm (main alarm), the following processes are automatically
started:
• The internal buzzer sounds continually.
• The following LEDs are illuminated:
- “Alarm” double LED is on
- Main alarm” LED is on
- “Call Fire Brigade alarm” LED is on
• The display shows the alarm message with any programmed text.
• According to the dc3400 SC configuration, alarm outputs, control modules and relays are
activated.

Recommendation for the operating sequence


1 Press the [ ] key. The internal buzzer is disabled.
2 In the case of an alarm follow any evacuation procedures, alerting the fire brigade and
the inspection of the activated device.
3 To silence any ext. sounders press the [ Silence alarms ] button.
4 If the cause of the alarm has been rectified, press the [ Reset ] button and all modules
and detectors will be reset to their normal working state.

If the ext. sounders have been disabled they will have to be enabled again via the “Enable”
menu. If the sounders have been silenced using the "Silence alarms" button then after the
reset the sounders are enabled automatically.

8.2 Alarms
If the dc3400 SC goes into alarm and is set to a detector or zone dependency, the following
processes are started automatically:
• The internal buzzer sounds continually.
• The alarm messages are shown in the display
• The following alarms are possible:
- Alarm caused via a detector dependency (Fire D1. knock trig.)
- Alarm caused via a zone dependency (Fire Z1. knock trig.)
- Alarm with an enabled delay
- Maintenance mode alarm

Version 2.2 44
Installation Manual FCP dc3400 SC

• Detector dependency "Fire D1. knock trig."


The main alarm will become active as soon as two detectors or MCP from the same zone
are triggered.

• Zone dependency "Fire Z1. knock trig."


The main alarm is activated as soon as two defined zones go into alarm.

• Alarm with the delay active


The main alarm will become active once the “delay time" or Intervention Time” has
expired.

• Maintenance mode alarm


A maintenance mode alarm will not raise a main alarm and is only for service purposes.
Detectors in maintenance alarm will be indicated for 40 sec. in the "Mainten. notes"
window.

Recommendations for the operating sequence


1 Press the [ ] key. The internal buzzer is disabled.
2 Proceed according to the present Instructions in the case of an alarm.
3 Once the cause of the alarm has been found and rectified, press the [ Reset ] button and
all modules and detectors are reset.

If the ext. sounders have been disabled they will have to be enabled again via the “Enable”
menu. If the sounders have been silenced using the [ Silence alarms ] button then after the
reset the sounders have become enabled.

8.3 Faults
The following processes are started automatically if a fault is detected by the FCP dc3400 SC
• The internal buzzer sounds intermittently.
• The “Fault” LED is flashing.
• On the display, the fault message is displayed.
• Depending on the panel configuration, alarm outputs, control modules and relays can be
activated.

Warning!
If a system fault is displayed, the function of the dc3400 SC may be impaired!
You must contact your local service or maintenance company.

Recommendations for the operating sequence


1 Press the [ ] key. The internal buzzer will silence.
2 Examine the displayed fault and/or the reasons for the fault. If possible, rectify the fault.
3 If it is not possible to rectify the fault, note the fault message in the display and inform
your local service company.
4 Press the [ Reset ] button if the fault has been rectified.

Version 2.2 45
Installation Manual FCP dc3400 SC

9 Operation and Setting


When the FCP dc3400 SC is in its normal “In operation” mode, the main menu key is located
in the top right hand corner of the display. By pressing this menu, you are able to access the
sub menus which you can see in the picture located to the left:
1 Select the corresponding sub-menu using the [] and [] keys.
2 Press the [ Ok ] button.
3 Proceed in the same way in order to access the remaining sub-menus.

9.1 Operating, authorisation / access levels


Authorisation for operating the FCP dc3400 SC is by means of different passwords. When
prompted to do so, enter the password directly from the display. Each entered number is
shown by the “*” symbol. After the entry of the password, the [ Ok ] button must then be
pressed. In the case of a wrong entry, the number(s) can either be deleted using the [] key
or the entry can be cancelled using the [] key.

Operation of the FCP dc3400 SC is governed via different password levels which are user
authorisation specific. Password level 2 should only be accessible for authorised operators.
The password level 3 should only be used for the installation and the construction.

System parameters (Password level 3 - "33333")


Service configuration (Password level 2 - "22222")
Basic functions (Password level 1 - "no password necessary")

Password levels

Operation according to functions 1 2 3

Reset X
Silence alarms X
Transm. Unit Alarm on/off* X
X

Delay enable / disable X


Menu X
Enable X
Disable X
Service X
System parameters X
Alarm counter X
User interface X
Configure display X
Select language X
Lamp test X
Setting date and time X
Set default display configuration X
*without function at present

Version 2.2 46
Installation Manual FCP dc3400 SC

9.2 Functions in the "In operation" window


The following functions can be executed in the "In operation" window:
• "Reset"
• "Silence alarms"
• "Transm.Unit Alarm on/off"

• " "
• "Delay on/off"
• "Menu"

9.2.1 Reset
Resets any fault or fire message if indicated in the display.

Note!
If the cause has not been solved then the fault or fire message will be
indicated again.

9.2.2 Silence alarms


This function can only be used during an Alarm. Using the “Silence alarms” button, only the
audible alarm signals are silenced. It has to be noted that they are re activated when another
fire alarm from another zone it triggered.

Note!
The external sounders can only be activated if they are enabled.

1 In the “In operation” screen press: [ Silence alarms ] button.


The information “Silenced sounder” appears.
2 Confirm using the [ Ok ] button. The “Ext. sounders” LED and the disablements LED will
be on.

Note!
When the panel is reset the sounders are no longer silenced.

9.2.3 Disabling the "Transmission Unit"


Not available at present.

9.2.4 Mute buzzer ( )


The internal buzzer will be disabled. A new alarm message from a further zone or a new fault
message will reactivate the buzzer again.

9.2.5 "Delay on/off"


The delay function will be activated by pressing this button. The delay times can be
programmed in the "dpt detectomat programming tool". Further information can be found in
the "dpt manual (Order-No.: 53656)"

Version 2.2 47
Installation Manual FCP dc3400 SC

9.3 Enable
Via the level 2 password, you can access the “Enable” menu. Disabled elements can be
enabled again. Disabled messages shown in the display and the LEDs are reset.

The dc3400 SC offers the following enabling options:


• Detectors or detector zones
• Input 1 and 2 of the basic module
• Output 1 and 2 of the basic module
• External alarm signals

The enabling procedure is done in the same way as disabling. Instead of selecting the menu
"Disable" you have to select the menu [ Enable ]. Starting from the “In operation” menu,
select the menu sequence [ Menu | Enable ]. All additional steps are similar as described in
the next chapter.

9.4 Disable
Via the password level 2, you can access the “Disablement” menu.
The FCP dc3400 SC offers the following disablement options:
• Detectors or detector zones
• Input 1 and 2 of the basic module
• Output 1 and 2 of the basic module
• External alarm signals

1 Starting from the “In operation” screen, press the following key combination:
[ Menu | Disable ].
2 Press the [ Ok ] button. The password prompt appears.
3 Enter the password.
4 Press the [ Ok ] button in order to confirm the entry. The “Disablements” menu opens.
5 Select one of the following options:*
- Detector
- Zone
- Output
- External alarm signals

Version 2.2 48
Installation Manual FCP dc3400 SC

9.4.1 Disabling detectors


In the disable detector menu, you can select which detectors you want to disable.

1 Starting from the “In operation” screen, press: [ Menu | Disable | Detector ], you will see
the following:
2 Touch the [ Zone ] entry field and enter the zone number.
3 Touch the [ from detector ] entry field and enter the detector number as of which
detector in the zone needs to be disabled.
4 Touch the [ to detector ] entry field and enter the detector number up to which detectors
in the zone are to be disabled.
5 Press the [ Ok ] button. On the display a disable message appears specifying which
detectors have been disabled. The disablement counter, located in the top centre of the
display will show the amount of disablements. Also the “Disable” LED will be on.

9.4.2 Disabling zones


In the disable zone screen, you can choose which zone(s) you wish to disable.

1 Starting from the “In operation” screen, press [ Menu | Disable | Zone ]. You will then see
the following in the display.
2 Touch the [ from Zone ] entry field and enter the zone number you wish to disable.
3 Touch the [ to Zone ] entry field and enter the zone number up to which zones is to be
disabled.
4 Press the [ Ok ] button. On the display a disablement message appears specifying the
disabled zones. The disablement counter on the display shows the amount of
disablements. The “Disabled” LED is also on.

9.4.3 Disabling input


Here you can select which outputs on the corresponding modules are to be disabled:
• Base module

1 Starting from the “In operation” screen press: [ Menu | Disable | Input ].
2 Touch [] or [] in order to select the “Base module” option.
3 Touch the [ Address ] entry field and enter the CAN address of the module on which the
output is located.
4 Touch the [ from Output ] entry field and enter the output number which requires disabling.
5 Touch the [ to Output ] entry field and enter the output number up to which outputs are to
be disabled.
6 Press the [ Ok ] button. In the display a disabled message appears specifying which input
has been disabled.

Version 2.2 49
Installation Manual FCP dc3400 SC

9.4.4 Disabling outputs


Here you can select which outputs on the corresponding modules are to be disabled:
Base module

1 Starting from the “In operation” screen press: [ Menu | Disable | Output ].
2 Touch [] or [] in order to select the “Basic module” option.
3 Touch the [ Address ] entry field and enter the CAN address of the module on which the
output is located.
4 Touch the [ from Output ] entry field and enter the output number which requires disabling.
5 Touch the [ to Output ] entry field and enter the output number up to which outputs are to
be disabled.
6 Press the [ Ok ] button. In the display a disabled message appears specifying which output
has been disabled.

9.4.5 Disabling external alarm signals


All outputs configured as “External alarm signals” will react to the “Disable external alarm
signals” command.

• all
All external acoustical and optical sounders/beacons will be disabled

• Acoustical signals (Sounders)


All loop sounders, loop sounder modules like AOM / OMS and the “Ext. sounders output
on the CP-MB basic module. The acoustic sounders can also be temporally disabled
when the [ Silence alarms ] button is pressed. The silenced alarm will be re-activated if a
new alarm / fire is recognised.

• optical signals (Beacons)


All loop beacons will be disabled by selecting "all" or "Beacons".

Note!
The external alarm signals can only be activated by an alarm if they are enabled.

1 Starting from the “In operation” screen, press: [ Menu | Disable | External alarm signals ].
2 Please select if you want to disable all signals or only the audible or only the visual. In the
following example, “all” has been selected. Press the [ Ok ] button. The information
“Disable external alarm signals all?” appears.
3 Press the [ Ok ] button in order to disable all external alarm signals.
The “Ext. sounders” and the “disablements” LED is on.

Version 2.2 50
Installation Manual FCP dc3400 SC

9.5 Service
Via the level 2 password, you can access the “Service” menu. Important information like, for
example, the event log can be viewed.

1 Starting from the “In operation” screen, press: [ Menu | Service ].


2 Press the [ Ok ] button. The password prompt appears.
3 Enter the password.
4 Press the [ Ok ] button. The “Service” menu opens.
5 Select one of the following options.
• Event log
• Maintenance mode

9.5.1 Viewing the service event log


In the “Service Event log” menu, you can view all activities that have occurred, like alarms
and faults.

1 Starting from the “In operation” screen, select the menu sequence:
[ Menu | Service | Event Log ].
You are in the “Service Event log” menu. On the display, the current events appear.

The buttons have the following functions:


Display Meaning
 Scroll up
 Scroll down
 Back to previous menu
!!0379!! Total Event messages, Indicates the last event.

9.5.2 Maintenance Mode


In order to test and carry out maintenance work on the fire alarm system without disabling all
outputs this mode should be enabled. Single zones, several zones or even the whole system
can be enabled to maintenance mode.

Enable / disable zones for maintenance


1 Starting from the “In operation” menu, select the menu sequence:
[ Menu | Service | Maintenance mode ].
2 Select the “Enable” or “Disable” option using [] or [] and confirm [ OK ]
3 In the field “from Zone” you have to enter the first zone and in the field “to Zone” the last
zone number which are to be enabled / disabled from the maintenance mode.
4 Press the [ Ok ] button. At the display, you can see in the menu which zones are in
maintenance mode. At the LED display, the “maintenance mode” LED is illuminated in
yellow. Simultaneously, the “Mainten.notes” counter counts up according to the selected
zones.

Enable / disable all groups for maintenance


This will set the complete FCP and all programmed zones into maintenance mode.
1 Press [ Menu | Service | Maintenance mode ]
2 Select [ OK ]
3 Select [ Enable / Disable system outputs from maintenance ]
All zones programmed to the FCP will be enabled / disabled from the maintenance mode.

Version 2.2 51
Installation Manual FCP dc3400 SC

9.6 System Parameters


Via password level 3, you can access the “System Parameters” menu that is only intended
for installers. In this menu, FCP dc3400 SC configurations can be changed or deleted.

1 Starting from the “In operation” menu, select the menu sequence:
[ Menu | System Parameters ]- You are in the “System Parameters” menu.
2 Press the [ Ok ] button. The password prompt appears.
3 Enter the password.
4 Press the [ Ok ] button. The “System Parameters” menu opens.
5 Select one of the following options.
• Delete event log
• Bring FCP into Service
• Extend / reduce loop
• Show detectors
• Restore to factory presets
• Software versions

9.6.1 Delete event log


With this function you have the possibility to delete the event log. All stored messages will be
erased. This function must be confirmed by the [ Ok ] key.

9.6.2 Bring FCP into Service


Here, CAN devices and loop structures can scan for detectors or auto address the loop
components connected to the panel.

1 Starting from the “In operation” menu, select the menu sequence:
[ Menu | System parameters | Bring FCP into Service ].
2 Press the [ Ok ] button. The following information text appears:
“Scan for FCP modules and detectors ?”
3 Press the [ Ok ] button. At the display a list with all FCP modules that are installed in the
FCP dc3400 SC and their set address appear.
4 Press the [ OK ] button to open up the next menu where you have the choice of:
"SCAN", or "AUTO" command.

Learn loop structure (SCAN): The existing addresses or those that have first been assigned
manually (easy check) are scanned in. In this way, an existing system can be extended, i.e.
the new detectors are assigned free addresses via the easy check and are then read-in by
means of this scan command.

Warning!
If the loop members have been addressed manually in advance, you must not use
the “AUTO” option! In this case, all addresses are overwritten irrevocably.

Readdress Loop structure (AUTO): Comprises the automatic addressing. In the automatic
addressing, loop members are automatically assigned addresses according to the line run. It
is thus suitable for the first commissioning.

Version 2.2 52
Installation Manual FCP dc3400 SC

1. Select the desired option and press [ Start ]. The reading process is started. A status bar
indicates the progress of the reading process. At the end, the detected loop members are
shown. Press the [ Ok ] button to confirm the read in detectors. The read in detectors will
now be programmed in the flash.

9.6.3 Extend / reduce loop


Here the loop structure can scan for detectors or auto address the loop components
connected to the panel.

1 Starting from the “In operation” menu, select the menu sequence:
[ Menu | System parameters | Extend / reduce loop ].
2 Press the [ Ok ] button. At the display a list with the installed loop cards in the FCP
dc3400 SC and their set address appear.
3 Press the [ OK ] button to open up the next menu where you have to confirm the
"Learn loop structure (SCAN)" command.
4 Press the [ Start ] to beginn.

Learn loop structure (SCAN): The existing addresses or those that have first been assigned
manually (easy check) are scanned in. In this way, an existing system can be extended, i.e.
the new detectors are assigned free addresses via the easy check and are then read-in by
means of this scan command.

9.6.4 Show detectors


The last saved loop structure with the detectors will be indicated.

9.6.5 Factory settings


When loading the factory settings, any existing programming is deleted and/or parameters
that are important for the function of the FCP dc3400 SC are set to “Standard”. This includes
all zone and detector assignments, customer texts, delays, event log, etc.
Control links are deleted except for the standard control. The loop components are
maintained and are moved into the standard zones.
Zone 9501 for loop card 1.

1 Starting from the “In operation” menu, select the menu sequence
[ Menu | System Parameters | Restore to factory presets ].
You are in the “System Parameters Factory Settings” menu.
2 Press the [ Ok ] button. The following information text appears: “System parameters
Restore to factory presets?”.

Warning!
By means of the Factory settings command, all settings of the FCP dc3400 SC are
irrevocably reset. Before this step, back-up your data.

Press the [ Ok ] button. The FCP dc3400 SC settings are reset to the factory values.

Version 2.2 53
Installation Manual FCP dc3400 SC

9.6.6 Software Versions


In the “Software Versions” menu, you can view the current software versions of the installed
modules in the FCP dc3400 SC.

1 Starting from the “In operation” screen press:


[ Menu | System parameters | Software versions ].
2 Press the [ Ok ] button. The “Software Versions” menu opens.
Displayed is a list with the FCP dc3400 SC modules with their software version.

Here, the minimum SW-versions of the panel components in this manual:

Package ver.: 002.005.0000


Display and control panel (CP-DIS): 002.000.0806
Loop carte (CP-LI3120): 003.000.0158
Basic module (CP-MB): 001.003.0251
Power supply board (CP-PSB1): 001.001.0131
Main board (CP-CPB): 002.000.0958

9.7 Alarm Counter


In the “Alarm counter” menu, the total number of all the main alarms since the installation of
the FCP dc3400 SC is recorded. The alarm counter can only be deleted via “dpt software”.

9.8 User Interface


You have the possibility to change the settings of the display.

1 Starting from the “In operation” menu, select the menu sequence:
[ Menu | User interface ] .
2 Press the [ Ok ] button. The “User interface” menu opens.
3 Select one of the following options.
• Configure display
• Select language
• Lamp test
• Set date and time
• Set default display configuration

Version 2.2 54
Installation Manual FCP dc3400 SC

9.8.1 Configure display


Here you have the possibility to change the display brightness and contrast.

1 Starting from the “In operation” menu, select the menu sequence:
[ Menu | User interface | Configure display ].
2 The password prompt appears.
3 Enter the password.
4 Press the [ Ok ] button. The “Configure display” menu opens.
5 Select the "Brightness" or "Contrast" and press [ Ok ]
6 You can now change the values with the [ • ] and [ – ] keys.
- Brightness: min. 5 --> max. 20
- Contrast: min. 10 --> max. 40
The default setting for both is: 20.

7 Press [ *1 ] to return to select "Brightness" or "Contrast".

The settings are saved automatically.

9.8.2 Language Settings


In the language setting, you can choose between English and the alternatively installed
language.

1 Starting from the “In operation” menu press: [ Menu | User interface | Select language ].
2 Press the [ Ok ] button.
3 Select your desired language using the [] and [] buttons.
4 Press the [ Ok ] button. you need to confirm the selected language in the next window.
5 Press the [ Ok ] button. The menu display now appears in your selected language.

9.8.3 Lamp Test


By means of the lamp test you can check whether all LEDs and all pixels from the display are
working and whether the internal buzzer of the FCP dc3400 SC functions properly. The test
takes about two seconds and is reset automatically.

1 Starting from the “In operation” screen press: [ Menu | User interface | Lamp Test ].
2 Press the [ Ok ] button.
• All LEDs should come on.
• The display will go out and come on again.
• The internal buzzer sounds during this test.

Version 2.2 55
Installation Manual FCP dc3400 SC

9.8.4 Set date and time


In the “Set date and time” menu, you have the possibility to change date and time.
During the initial commissioning of the FCP dc3400 SC, you should check the date and time
and correct them if necessary!
The buttons have the following functions:

Display Meaning
/ Changing values (up / down)
/ Moving the cursor from one digit to the next
[ Ok ] Entries are stored
 Back to previous menu
Back to the Home menu

1 Starting from the “In operation” press: [ Menu | User interface | Set date and time ].
2 Press the [ Ok ] button. The “Set date and time” view opens.
3 Adjust time and date.
4 Press the [ Ok ] button. Time and date are saved in the FCP dc3400 SC.

9.8.5 Set default display configuration


All display configurations will be reset to the default settings. The language will be set to
"English" and the brightness and contrast will be set to "20".

1 Starting from the “In operation” press: [ Menu | User interface | Set default display
configuration ].
2 The password request window opens.
3 Enter the password and press [ OK ].
4 Confirm to reset the display to default values by pressing [ OK ].
The default values are set.
- Language: English
- Brightness: 20
- Contrast: 20

Version 2.2 56
Installation Manual FCP dc3400 SC

10 Faults and diagnostics displays


In the following chapter, you are given an overview of the possible problems that could occur
during commissioning and general operation of the FCP dc3400 SC and the possible remedies.

Note!
Faults (like e.g. missing detector, open circuits, etc.) are automatically reset when
2 3 4 the fault has been rectified (self-resetting) and the respective LED goes out. Short-
circuits and system faults are not self-resetting and have to be reset manually.

10.1 Fault messages


1 Current date and current time
5 2 Message date and message time
3 Message number and message text
6 4 Location (zone number / detector number / detector type)
5 Customer text for detectors and/or zone
6 Message text
8 in the case of alarm:
7 1 the number of further detectors that are in alarm in the displayed zone appears
in case of fault and disablement: the display remains empty

Following the main fault indications:

Message level Message text LED display Cause / Meaning Inspection / troubleshooting

Alarms (general)
1 Alarm Alarm LED on Main alarm
Main alarm LED on (see message text level 2)
Call FB LED on
Buzzer on
1 Fire Z 1. knock trig. Buzzer on First Alarm in a zone dependency
(see message text level 2)
1 Fire D 1. knock trig Buzzer on First Alarm in a detector dependency
(see message text level 2)
1 Alarm MCP Alarm LED on Fire in manual call point zone
Main alarm LED on (see message text level 2)
Call FB LED on
Buzzer on

Faults (general)

1 Fault Fault LED intermittent Fault


Buzzer intermittent (see message text level 2)
1 Fa: Techn. message Fault LED intermittent Fault message zone Adhere to the alarm organisation
Buzzer intermittent (see message text level 2)
1 Fault Main-CPU Fault LED intermittent Fault
System LED intermittent (see message text level 2)
Buzzer intermittent

Disable (general)

1 Disable Disable LED on Disablement Adhere to the alarm organisation


(see message text level 2)

Version 2.2 57
Installation Manual FCP dc3400 SC

Message level Message text LED display Cause / Meaning Inspection / troubleshooting

Maintenance mode (general)

1 Maintenance mode Maintenance mode LED on Corresponding zone or whole system


in maintenance mode.
1 Alarm in maintenance Maintenance mode LED on
mode

Fault messages (specified)

2 Loop member Fault LED intermittent Communication with the loop device Check loop device / wiring, change
communication Buzzer intermittent is causing problems. loop device, if necessary.
2 Wrong device type Fault LED intermittent Another detector type than the one Use the correct detector type or
Buzzer intermittent configured in the FCP dc3400 has change the configuration.
been used.
– No display No display Power supply or control panel Check the “Input” status LED on the
defective. power board card.
Check the mains fuse
Check the mains supply
Check the input voltage at the power
board card
Try to reboot the system
2 Mains fault Fault LED intermittent Mains fault Check the mains fuse
Mains LED intermittent Check the mains connection
Buzzer intermittent
Check the input voltage at the power
board card
2 Open circuit battery Fault LED intermittent Open circuit between the batteries. Check the battery connection
Battery LED intermittent Check the fuse on the power board
Buzzer intermittent card
2 Short-circuit Battery Fault LED intermittent Short-circuit Batteries Check the battery connection
Battery LED intermittent Check the batteries and exchange
Buzzer intermittent them, if necessary.
2 Low voltage Battery Fault LED intermittent Low batteries voltage. May occur during a longer mains
Battery LED intermittent failure; afterwards, the batteries have
Buzzer intermittent to be recharged.
Check the batteries and exchange
them, if necessary.
2 Earth fault Fault LED intermittent Earth fault within the fire alarm Check the system for earth faults and
Buzzer intermittent system. rectify.
2 Open circuit Loop (+) Fault LED intermittent Open circuit on L+ Check the loop wiring
Buzzer intermittent
2 Open circuit Loop (-) Fault LED intermittent Open circuit on L- Check the loop wiring
Buzzer intermittent
2 Short-circuit Loop Fault LED intermittent Short-circuit on the loop Check the loop wiring
Buzzer intermittent
2 Open circuit acoustic Fault LED intermittent Open circuit in the wiring of the ext. Check wiring of the external signals
Ext. Outputs LED intermittent signals or missing or wrong EOL and/or check the EOL resistor.
Buzzer intermittent resistor fitted.
2 Short-circuit acoustic Fault LED intermittent Short-circuit in the wiring of the ext. Check wiring of the ext. signals
Ext. signals LED intermittent signals or wrong EOL resistor. and/or check the EOL resistor.
Buzzer intermittent
2 CRC error ROM Fault LED Storage error Card Perform a cold start of the fire alarm
System LED system
Buzzer exchange the card, if necessary

Version 2.2 58
Installation Manual FCP dc3400 SC

11 Maintenance
Warning! Danger due to electric shock.
Maintenance and repair works at the FCP dc 3400 may only be carried out in a
dead-voltage state. For this purpose, the mains supply at the mains adapter
connection technology (or the mains fuse is to be removed) and the emergency
power supply (batteries) are to be disconnected.

The inspections and maintenance works completed at the FCP dc3400 SC are to be recorded
in an operating log,

11.1 Inspections
11.1.1 Inspection Periods
In order to ensure the operating ability of the FCP dc3400 SC, inspections are to be carried
out in regular intervals.

Every day
Check the readiness of operation of the FCP dc3400 SC. In case of failures that have
incurred, check whether they are noted in the operating log and whether measures have
been taken for removing the failure.

Every quarter year


The FCP dc3400 SC must be inspected and/or tested every three months by an authorised
service technician for the following. Record the implementation in the operating log:
• Entries in the operating log
• Visual inspection of the FCP dc3400 SC and its modules
• Check the external voltage supply
• Check the batteries as well as their charging voltage
• Test at least one detector from each detector zone
• Test the readiness for operation of the alarm signallers
• Test the LEDs on the DCP (lamp test)

Every year
In addition to the quarterly inspections, an authorised service technician must individually
inspect each module of the fire alarm system including wiring, all outputs and/or activations.
Each detector of the fire alarm system must be tested at least once per year. Record the
implementation in the operating log.

Version 2.2 59
Installation Manual FCP dc3400 SC

11.1.2 Batteries
The batteries must be exchanged according to the manufacturer’s specifications, after four
years, however, at the latest. For more information please refer to chapter “5.1.2 Installing
the batteries“ on page 34.
1 Turn off the mains voltage. The FCP dc3400 SC is now running in battery operation.
2 After approx. one hour, measure the voltage at the battery terminals. In order to
guarantee the functionality of the FCP dc3400 SC, the battery voltage should exceed 12 V
and be identical at both batteries.
3 Subsequently, turn the mains voltage on again.

11.2 Cleaning
To clean the outer housing of the FCP dc3400 SC use a moist, soft, and lint-free cloth. Do not
use cleaning solvent, paint thinners or cleaning agents that contain alcohol (spirit).
If necessary, the inside of the housing may and should only be cleaned by the service
technician.

Clean the display with a soft, dry cloth. Do not use cleaning solvent, paint thinners cleaning
agents that contain alcohol

11.3 Software Updates


This option is only available possible by the manufacturer at present.

11.4 Environmentally-friendly disposal


The FCP dc3400 SC contains batteries. Exchange these batteries according to the
manufacturer’s specifications. The batteries should only be exchanged by authorised service
technicians.

The batteries should only be disposed in official waste management plants. Your local
environmental authority can provide you with addresses of waste management plants.

Version 2.2 60

You might also like