Worldwide

www.tyco-fire.com
Contacts

DDS Duct Deluge System


For The Protection of Ventilation Ductwork
Handling Corrosive Gases
General
Description
The TYCO DDS Duct Deluge System is
designed specifically for the protection
of ventilation ductwork handling corro-
sive gases, including extremely corro-
sive gases as defined in FM Property
Loss Prevention Data Sheet 7-78.
The DDS System features the TYCO
DN-5 Corrosion Resistant Duct Nozzle,
which is an open (non automatic) direc-
tional spray nozzle, and also includes
the TYCO Red-E Cabinet, PROTEC-
TOWIRE linear heat detection, and
FlexHead duct mounting hardware.
The DDS System is capable of achiev-
ing fire suppression and potential
extinguishment in ventilation ductwork
constructed of plastic material. The
DDS System benefits include limit-
ing down-time due to fire damage and
routine inspection and maintenance.
Ventilation duct work handling NOTICE (FRP), Polyvinyl Chloride (PVC), or
extremely corrosive environments may Polypropylene (PP), which may be cir-
The DDS System described herein
be encountered in the following indus- cular, rectangular, or irregular in shape.
must be installed and maintained in
trial settings: Duct diameter or width may range from
compliance with this document, FM
1 ft to 16 ft.
• Steel Manufacturing Global Property Loss Prevention Data

Protection
Sheets, the applicable standards of the
• Copper Mineral Processing NATIONAL FIRE PROTECTION ASSO-
CIATION, in addition to the standards of
• Lead Mineral Processing
• Zinc Mineral Processing
any other authorities having jurisdiction. Objectives
Failure to do so may impair the perfor-
• Coal Power Generation mance of this system. The TYCO DDS Duct Deluge System is
intended to reduce fire hazards inher-
• Semiconductor Fabrication The owner is responsible for main- ent in industrial exhaust systems and
taining their fire protection system prevent fire spread via these systems,
• Pulp & Paper Facilities and devices in proper operating con- whether within buildings or between
dition. Contact the installing contrac- adjacent buildings.
CAUTION tor or product manufacturer with any
This system is unique in its intent and questions. The DDS System components are
design. Anyone involved at any level capable of withstanding environments
must thoroughly understand the limita-
tions and capabilities of such systems.
Approvals & in which extremely corrosive gases may
be present, including but not limited to:
Application • Hydrochloric acid (HCL)

Criteria
• Hydrofluoric acid (HF)
• Sulfuric Acid (H2SO4)
The components of the TYCO DDS • Nitric Acid (HNO3)
Duct Deluge System are Factory Mutual
(FM) Approved for use in extremely • Sulfur Dioxide (SO2)
corrosive environments.
IMPORTANT
Refer to Technical Data Sheet The DDS System is intended for use
TFP2300 for warnings pertaining to in plastic ventilation ductwork con-
regulatory and health information. structed of Fiber-Reinforced Plastic

Page 1 of 6 AUGUST 2018 TFP870


TFP870
Page 2 of 6

PROTECTOWIRE
ZONE CONNECTION
BOX

MAXIMUM
PROTECTOWIRE NOZZLE MAXIMUM
LINEAR HEAT TO HEAT NOZZLE
DETECTOR CABLE DETECTOR SPACING IN
RUN BETWEEN SPACING: VERTICAL
ZONE BOXES 3 FEET DUCTS:
(0,9 m) 24 FEET
(TYPICAL) (7,3 m)
FIELD WIRING
FROM CONTROL
PANEL TO FIRST
ZONE BOXES VIA
FLEXIBLE CONDUIT FLEXHEAD FLEXHEAD
FLEXIBLE HOSE DETACHABLE MOUNTING
SUPPLY ASSEMBLY BLOCK ASSEMBLY
PIPE

RED-E CABINET
(DV-5 DELUGE
VALVE WITH DUCT MAXIMUM TYPE PROTECTOWIRE
ELECTRIC NOZZLE DN-5 LINEAR HEAT
ACTUATION SPACING IN NOZZLE DETECTOR LOOP
TRIM) HORIZONTAL
DUCTS:
WATER 12 FEET
SUPPLY (3,7 m)

FIGURE 1
DDS DUCT DELUGE SYSTEM
SCHEMATIC DIAGRAM

System • FlexHead Duct Sprinkler


• FRP Ductwork Model Installation System Design
Components and Maintenance Manual
• PVC Ductwork Model Installation
Criteria
Nozzle and Maintenance Manual Hydraulic Requirements
TYCO Type DN-5 Corrosion Resis- • Polypropylene Ductwork Model Base the water supply on a design of
tant Duct Nozzle with HALAR (ECTFE) Installation and Maintenance 20 gpm (75,7 lpm) per nozzle for ducts
coating. This component is described Manual less than 4 ft (1,2 m) in diameter or
in Technical Data Sheet TFP808. width. Design for 30 gpm (113,6 lpm)
PROTECTOWIRE Linear per nozzle for ducts 4 ft to 8 ft (1,2 m
Deluge Valve and Releasing Heat Detection to 2,4 m) in diameter or width.
Control Panel This component is described in PRO-
TYCO DV-5 Red-E Cabinet with Elec- TECTOWIRE data sheet “DS-6592 Ducts that are greater than 8 ft to 16
tric Actuation. This component is PWC”. Installation and maintenance ft (2,4 m to 4,9 m) in diameter or width
described in Technical Data Sheet procedures for this component are require two nozzles at each plane of
TFP1300. described in: installation. Base the water supply on a
design of 20 gpm (75,7 lpm) per nozzle,
Installation Hardware • PROTECTOWIRE Linear Heat 40 gpm (151,4 lpm) total at each plane
FlexHead HALAR Mounting System. Detector Installation, Operation & of installation.
Installation and maintenance proce- Maintenance Manual
dures for this component are described Refer to Figure 4 for additional detail.
• Duct Deluge Linear Heat Detector
in: Installation Instructions for Part For ducts exceeding 16 ft (4,9 m) in
Number PDK-1 diameter, contact your local authority
• DS-6592 PWC having jurisdiction or the engineer of
record.
TFP870
Page 3 of 6

System Data Sheet and Temperature


Functional Model Description Installation Size Rating
Description Instruction
HALAR
Type DN-5
Nozzles Coated Stainless Steel TFP808 — —
Nozzle Nozzle
1-1/2 in.
2 in.

Deluge Valve and Releasing Electric Actuation Deluge 3 in.


TYCO Red-E Cabinet TFP1300 —
Control Panel with Galvanized Trim 4 in.
6 in.
8 in.

FlexHead Duct 2 ft Hose


Sprinkler
Installation and
Maintenance for
FRP Ductwork
HALAR Upper Mounting Model 3 ft Hose —
FlexHead Special
Nozzle and LHD Installation Block with FRP, PP, or PVC Installation and
FRP/HALAR Duct
Methodology Lower Mounting Block and Maintenance for
System a Viton Gasket PP Ductwork
Model
4 ft Hose
Installation and
Maintenance for
PVC Ductwork No Hose
Model For Use with —
LHD
190 °F for max.
Protectowire 150 °F
Linear Heat
Detector 220 °F for max.
PROTECTOWIRE Installation, 175 °F
Fluoropolymer Jacket
Type XCR Operation & 100 ft min.
Linear Heat Detector 280 °F for max.
Construction Maintenance
Manual 200 °F

Duct Deluge 356 °F for max.


Linear Heat Detection 250 °F
Linear Heat
Detector
Installation
Instructions for
PROTECTOWIRE One kit required for each Part Number
PDK-1 — —
PDK-1 Installation Kit LHD insertion point
DS-6592 PWC

TABLE A
DDS DUCT DELUGE SYSTEM
COMPONENTS

Nozzle Placement Detection Placement Water Delivery


Install the TYCO Type DN-5 Corrosion Install a loop of PROTECTOWIRE linear Water delivery time (from initial detec-
Resistant Duct Nozzle no more than 12 heat detection cable inside the duct at tor activation to full discharge from all
ft (3,7 m) on center in horizontal ducts, the same maximum spacing as the nozzles) is not to exceed one minute.
and 24 ft (7,3 m) on center (preferably nozzles. Locate the loops within 3 ft Refer to FM Data Sheet 7-78 for further
at the top) in vertical ducts. Refer to (0,9 m) of the nozzles. Refer to Figure detail.
Figure 3 and 4 for positioning details. 1 for placement details and Figure 5 for
installation details.
NOTICE
Install a Type DN-5 Corrosion Resistant NOTICE
Duct Nozzle at the top of every vertical Install a loop of PROTECTOWIRE linear
run of duct, as close as possible to the heat detection cable at the top of every
transition from vertical to horizontal. vertical run of duct, as close as pos-
sible to the transition from vertical to
The maximum continuous operating
horizontal.
temperature should not exceed 302 °F
(150 °C).
TFP870
Page 4 of 6

1/2" NPT
THREAD
WATERWAY Nozzle
BLOW-OFF Installation
2-9/16"
(65,1 mm)
PLUG WITH
INTEGRATED Instructions
O-RING
The TYCO Type DN-5 Corrosion Resis-
1-15/16"
tant Duct Nozzles must be installed in
(49,2 mm)
FRAME accordance with this section.
NOMINAL Step 1. With pipe-thread sealant
SPLITTER applied to nozzle pipe threads, hand
tighten nozzle into Mounting Block
until the O-Ring makes contact with the
DEFLECTOR
Mounting Block Sealing Surface, then
continue hand tightening the nozzle
1-7/8" NOTE: HALAR coating on all nozzle another 1/4 to 1/2 turn.
(47,6 mm) surfaces except 1/2" NPT thread.
FIGURE 2 CAUTION
TYPE DN-5 CORROSION RESISTANT DUCT NOZZLE Do not hand tighten more than 1/4 to
ASSEMBLY 1/2 turn once the Type DN-5 Nozzle is
seated to the Mounting Block Sealing
Surface. Over-tightening may result in
equipment failure.
Use of a metal wrench when installing
the Type DN-5 Nozzle may damage the
nozzle coating and decrease the nozzle
FLEXHEAD corrosion resistance.
FLEXIBLE HOSE
ASSEMBLY Step 2. Ensure Type DN-5 Nozzle
THREADED OUTLET O-Ring is firmly seated between Nozzle
PIPE CONNECTION and Mounting Block Sealing Surface.
(FIGURE 730 Correctly installed O-Ring forms a seal
MECHANICAL around the Type DN-5 Nozzle pipe
TEE SHOWN) SUPPLY threads.
PIPE
Step 3. Ensure Blow-Off Plug is fully
seated into nozzle waterway.

Care and
Maintenance
FLEXHEAD
FLEXHEAD FIXED The TYCO DDS Duct Deluge System
DETACHABLE
LOWER MOUNTING UPPER MOUNTING
must be maintained and serviced in
BLOCK WITH ADHESIVE BLOCK WITH accordance with this section.
GASKET Before closing a fire protection system
control valve for inspection or main-
DUCT tenance work, obtain permission to
shut down the affected fire protection
system from the proper authorities
and notify all personnel who may be
BLOW-OFF affected by this action.
PLUG O-RING
FLUSH WITH Exercise care to avoid damage to the
TYPE DN-5 MOUNTING TYCO DDS Duct Deluge System com-
NOZZLE BLOCK ponents before, during, and after instal-
lation. Replace components damaged
by improper handling, dropping, strik-
ing, or the like.
FIGURE 3
Water spray systems for fire protec-
DN-5 CORROSION RESISTANT DUCT NOZZLE
tion service require regularly sched-
INSTALLATION
uled care and maintenance by trained
personnel.

NOTICE
It is recommended that TYCO DDS
Duct Deluge System components be
inspected six months after installa-
tion. Inspect components located in
TFP870
Page 5 of 6

HYDRAULIC REQUIREMENTS
D FLOW
DUCT SIZE NOZZLE NOZZLE EACH NOZZLE
FEET QTY POSITION GPM NOTES:
(METERS) (LPM) 1. MEASURED ALONG SURFACE
CONTOUR OF DUCT
20 2. CONTACT FM APPROVALS FOR
Less than 4 (1,2) 1 X (75,7) APPLICATIONS REQUIRING
GREATER VARIATION
30
4 (1,2) TO 8 (2,4) 1 X (113,6)
Greater than 8 (2,4) 20
2 Y and Z
to 16 (4,9) (75,7)

POSITION VARIATION POSITION VARIATION


X A Y AND Z A
D NOMINAL MAXIMUM D NOMINAL MAXIMUM
DUCT SIZE POSITION VARIATION2 DUCT SIZE POSITION VARIATION2
FEET FEET
(METERS) INCHES1 (METERS) INCHES1 INCHES1
DEGREES DEGREES DEGREES DEGREES
(CM) (CM) (CM)
2 6.25 10 62.81 10.43
0 30 60 10
(0,6) (15,9) (3,0) (159,6) (26,5)
4 12.63 12 75.38 12.50
0 30 60 10
(1,2) (32,1) (3,7) (191,5) 931,8)
6 18.81 14 88.00 14.63
0 30 60 10
(1,8) (47,8) (4,3) (223,4) (37,1)
8 25.06 16 100.50 16.75
0 30 60 10
(2,4) (63,7) (4,9) (255,4) (42,5)

A A

NOMINAL 60° 60°


NOZZLE A A
POSITION

X A A
NOZZLE
POSITION Y Z
VARIATION
NOMINAL
NOZZLE
POSITION
DUCT DUCT

NOZZLE
POSITION
VARIATION
D D
FIGURE 4
NOZZLE HYDRAULIC REQUIREMENTS
AND POSITION VARIATION

the area of highest chemical concen-


trations, near the beginning of the
The owner is responsible for the inspec-
tion, testing, and maintenance of their Limited
process duct. Inspect components
annually thereafter unless damage
fire protection system and devices in
compliance with this document, as well Warranty
to the coating is noted. Inspect for as with the applicable requirements of For warranty terms and conditions, visit
damage due to corrosion, deterioration FM Global Property Loss Prevention www.tyco-fire.com.
of the coated surfaces of components, Data Sheets, the applicable standards
improper orientation, or other evidence of the NATIONAL FIRE PROTECTION
of impaired protection per the method- ASSOCIATION, in addition to the stan-
ology described in the Protection for dards of any other authorities having
Ducts in Extremely Corrosive Environ- jurisdiction. Failure to do so may impair
ments section of FM Data Sheet 7-78. the performance of this system.
After placing a fire protection system Contact the installing contractor
in service, notify the proper authorities or product manufacturer with any
and advise those responsible for moni- questions.
toring proprietary and/or central station
alarms.
TFP870
Page 6 of 6

PROTECTOWIRE PROTECTOWIRE NOTES:


MOISTURE-TIGHT ZONE STRAIN RELIEF
1. SEPARATE LHD SPLICE
CONNECTION BOX CONNECTOR 2,3
CONNECTOR INTO PAIRS AS
PROTECTOWIRE SHOWN TO ACCOMMODATE
LHD SPLICE LHD CABLE WITHIN ZONE BOX
MOISTURE-TIGHT PROTECTOWIRE
CONNECTOR 1
ZONE BOX LHD LINEAR HEAT 2. HAND-TIGHTEN ONLY STRAIN
(SEE DETAIL)
MOUNT 5 DETECTOR CABLE 4
RELIEF GLAND NUTS
3. DRILL 11/16" (17,5 mm) DIA.
CLEARANCE HOLES THROUGH
FLEXHEAD FIXED FLEXHEAD DETACHABLE ZONE BOX AS NEEDED TO
LOWER MOUNTING UPPER MOUNTING BLOCK ACCOMMODATE 3/8" NPT
BLOCK WITH ADHESIVE WITH GASKET STRAIN RELIEF CONNECTOR

1" NPT 4. LEAVE SUFFICIENT SLACK IN


PROTECTOWIRE INLET PROTECTOWIRE LHD CABLE FROM ZONE BOX TO
LHD CABLE MOUNT LHD LINEAR HEAT ALLOW FOR EXTRACTION AND
WITH TIE AND DETECTOR CABLE RUN INSPECTION OF LHD LOOP
ADHESIVE TO NEXT ZONE BOX
5. DRILL 1" (26 mm) DIA.
DUCT CLEARANCE HOLE THROUGH
ZONE BOX TO ACCOMMODATE
MOUNTING COMPONENTS
PROTECTOWIRE
STRAIN RELIEF
8" to 10" LHD
CONNECTOR 2
(200 mm CABLE
(SEE DETAIL)
to
250 mm)
PROTECTOWIRE LHD SPLICE CONNECTOR PROTECTOWIRE LHD LINEAR
LHD LINEAR HEAT
HEAT DETECTOR CABLE TO
DETECTOR CABLE LOOP DETAIL LHD SPLICE CONNECTOR
2-1/2" (64 mm)
PROTECTOWIRE LHD SPLICE
MIN. BEND RADIUS
CONNECTOR MODIFICATION 1 FLEXHEAD
2" (50 mm) DIA. UPPER
FIELD WIRING FROM CLEARANCE MOUNTING
CONTROL PANEL VIA HOLE FIELD WIRING TO CONTROL BLOCK
FLEXIBLE CONDUIT PANEL VIA FLEXIBLE CONDUIT OUTLET
OR TERMINATE LHD WITH
PROTECTOWIRE EOLR IN LAST ZONE BOX
48" MAX. ZONE BOX PROTECTOWIRE
(1,22 m) VITON O-RING
PROTECTOWIRE
2-HOLE VITON PROTECTOWIRE
STRAIN RELIEF SEAL RING
CONNECTOR
PROTECTOWIRE
GLAND LHD LINEAR HEAT
NUT 2 DETECTOR
PROTECTOWIRE DUCT PROTECTOWIRE
DETAIL CABLE LOOP
LHD LINEAR HEAT LHD LINEAR HEAT
DETECTOR CABLE RUN PROTECTOWIRE DETECTOR PROTECTOWIRE LHD CABLE LOOP STRAIN
TO NEXT ZONE BOX CABLE MOUNT CABLE LOOP RELIEF CONNECTOR AND COMPONENTS
FIGURE 5
LINEAR HEAT DETECTION
INSTALLATION

1400 Pennbrook Parkway, Lansdale, PA 19446 | Telephone +1-215-362-0700


© 2018 Johnson Controls. All rights reserved. All specifications and other information shown were current as of document revision date and are subject to change without notice.
NATIONAL FIRE PROTECTION ASSOCIATION is a registered trademark of National Fire Protection Association;
PROTECTOWIRE is a registered trade of The Protectowire Company, Inc.; HALAR is a trademark of The Solvay Solexis Corporation;
VITON is a registered trademark of Dupont