Catalogue

Commercial
Distribution
From Panelboards to our enhanced range of stylish
Invicta TP&N boards with metering & surge protection
capabilities, our commercial offering creates the
perfect electrical ecosystem for a building.
Innovative
Electrical
Solutions

As an independent family-owned and run company Hager Group is one of the industry’s
leading innovators for commercial and residential applications. With 11,400 employees
globally, our components and solutions are produced in 25 different locations to support
our customers projects in more than 136 countries around the world.

In the UK we have a well-established research and development team combined with


global resource to meet the needs of the market. This is backed up by the UK factory
having ISO 9001:2015 and an on-site ASTA recognised laboratory to BS EN ISO/IEC
17025:2005, which ensures that products and solutions meet all of the relevant British
standards. The UK site also has OHSAS 18001:2007, ISO 14001:2015 and the Investors in
People Bronze Award.

Working out solutions in close consultation with customers we have the vision ‘to add
value to peoples’ lives and their buildings through smart, eco-efficient and energy saving
solutions and services’.

2
3
Type A & B
Distribution Boards Panelboards

Our Invicta 3 Type B Boards have been developed as the Invicta 3 Panelboards are incredibly easy to install, the
solution for commercial installations. The whole nature pan assembly, door and front cover can all be removed to
of electrical sub and final distribution for commercial make the product lighter when fixing to the wall. Keyhole
installations has changed in recent years, with demands for slots and a central fifth keyhole fixing point make fitting and
more outgoing ways, more RCD protection, more metering levelling the board even simpler.
and more control devices.

In The Range In The Range

SP&N / TP&N Invicta 3 250A / 400A / 630A / 800A


Invicta 3 125A / 250A Incomer Kits
IP65 Meter Packs
Incomer Kits Meter Enclosures
Meter Packs Extension / Cable Spreader Boxes
Dual / Tri Metered Boards Panel & DIN Rail Meters
Hybrid CTs & Meter Cables
Extension / Cable Spreader Boxes

4
Metering & Protection
Monitoring Devices

UK wiring regulations and local building regulations create For integration in to Electrical distribution systems in
additional requirements for electrical distribution boards commercial building applications, our electrical distribution
in commercial building applications. A range of incoming boards are available with a range of protective device
device options and scalable energy metering options incomer options. SD, MCCB and RCCB incomers are
ensure specific application requirements are met. Easy to available. In addition, 4P changeover units are available for
specify and install, our metered distribution board options 125A Type B boards. Outgoing devices for MCB boards
create scalable solutions for typical commercial building also include a wide range of RCBO devices covering 10mA,
applications. 30mA and 100mA applications in B and C curve.

In The Range In The Range

Side / Top / bottom / Corner Meter Enclosures MCBs


Panel Meters RCBOs

DIN Rail Mounted Meters RCCBs

CT to Plug-in Converter Motor Starters

Plug-in CTs Fuse Carriers

Meter Cables Surge Protection

Earth Fault Relays

MCCBs

5
A thoughtful
approach to
Surge Protection
We have developed a brand new range of dedicated SPD kits,
specifically for our Commercial Distribution boards.

Our kits have been created to provide optimum end equipment


protection against surge transient voltages after an increased
focus on this requirement in the 18th Edition wiring regulations.

6
Space saving
integration.
Where required, board designs have been changed
to enable all kits to fit within the actual distribution
board, rather than in a separate enclosure next
to the distribution board. This also allows for the
shortest possible connection to the SPD from the
incoming supply, providing optimum performance.

Our SPD kits have the additional benefit of not


requiring any additional upstream protection
devices, saving more space in the board for
protection devices.

Integrated testing
The wiring regulations advise that SPD’s should be selected
from one manufacturer to ensure that they work well together.
Our Type 1 Panelboard SPDs have been tested to ensure
coordination with Type 2 SPDs in TP&N boards.

We’ve developed our boards and SPD kits together and


tested the effective performance of how well high voltage
transients are managed down to levels that don’t harm electical
equipment

Through development testing, we have


removed the need to consider many of
the application & installation variables
that previously made SPD selection
and installation complicated.

A solid connection
Through extensive testing we know that removing
secondary protective devices, using short conductor
paths to SPD’s and replacing cables with solid
copper Earth links dramitically improves the
effectiveness of the SPD.

Without these features our testing has shown


that common installation variables can easily
lead to a very significant reduction in the effective
performance of the SPD, potentially leaving surge
voltages at a level that can damage end equipment

7
Type B TP&N
Distribution Boards
Invicta 3 Type B boards have been designed for safe and
simple installation, with features to benefit both installer and
end user.

Take a look below to see all of the features we have


designed in and how this is going to make installing a
distribution board so much easier.

01
Aesthetics
Strong board aesthetics ideal for commercial offices, health care and
education projects where boards may be sited in public areas.

8
02 03
Metering Trunking Entry
A number of metering options provide a scalable solution Unique trunking entry obround system top and bottom
to energy monitoring. Type B Distribution boards are also enables quick fitting to trunking and without the extra cost
available with dual channel meters for separate monitoring in time and materials. The edge is curved, ready to bring
of Power and lighting loads. A metered three section Type cables in without the worry of sharp edges.
B board is also available to monitor power and lighting and
mechanical services.

04 05
Hybrid TP&N Board Available Shrouded Neutral Bar
Our Invicta TP&N Hybrid Distribution Board is available Clear shrouded neutral bar to IP2X allows the contractor to
to provide two 3 phase loads of up to 125A or six single install cables without removing the shroud. Ensures safe
phase loads. The larger 80-125A MCB devices, whilst and easy installation.
providing short circuit and overload protection, also give a
disconnection point for downstream circuits (isolation). This
ensures that there are no unprotected outgoing connections
from the busbar system.

9
Invicta
Panelboards
Our Invicta 3 Panelboards have been designed to make
installation a breeze, take a look below for a brief overview
of all of the features.

01
The Perfect Match
Our Invicta 3 panelboards have been designed to match perfectly
with the Invicta 3 Type B distribution boards. The Invicta 3 Panelboard
range is the most aesthetically pleasing available on the market, with
its glazed door and curved edges.

10
02 03
Twin Earth & Neutral Bars Removable Pan Assembly
Allows easy identification of earth & neutral conductors with To lighten the product when fixing to the wall, pan
corresponding line conductors. assemblies can also be purchased as a separate part or
removed for fitting into cubicle switchboards.

04 05
Energy Metering Removable Gland Plates
The installer only has to fit the packs into the board. All The top and bottom removable gland plates allows cable
internal wiring is included. RJ45 connectors simplify the entries to be prepared away from the board, preventing
connection of CTs to meters. ingress of swarf etc.

11
Metered Power
& Lighting Board
Monitoring Power and Lighting loads separately, creates
a better understanding of the where electricity is being
consumed. Our power and lighting boards employ dual
channel meters and are supplied with the main incoming
device pre-installed. Available as standard in a variety of
configurations and sizes to suit most applications up to
24TP ways. A Tri-metered TPN board is also available as
standard, where separate monitoring of Power, Lighting and
Mechanical services loads in required.

01 02 03
Energy Saving Building Regulations Choice

Installing and monitoring meters leads The Building Regulations 2010 & There are many options to monitor
to savings of 5-10% of the energy being approved document L2 recognise the energy consumption. Direct metering,
metered. For example, a meter that valuable role of metering and include measurement and estimation should all
identifies pumps being left on for 24hrs, requirements of sub-metering in be considered.
seven days a week, may save 60% of buildings other than dwellings.
energy passing through if the pump is
only used when required.

12
04 05
Communication Control & Performance

Metering helps building occupiers to Metering provides feedback to


understand how energy is being used designers, manufacturers, government
and lets them see the patterns of where and the supply side industry on
and when energy is consumed. Useful performance achieved, helping them to
trends can be shown from the data improve global energy performance by
produced. setting better targets.

13
Arc Fault
Detection
What the regs say BS 7671 18th Edition

Regulation 421.1.7 recommending installation of AFDD in AC final circuits.

- Premises with sleeping accommodation


- Buildings with risk of fire due to processed or stored materials e.g. Wood working shops
- Buildings constructed of combustible materials e.g. Barns
- Locations with irreplaceable objects e.g. Museums

Parallel Arc Fault Series Arc Fault

Potential Causes
Arc faults can be caused by all types of line faults and worn contacts. An AFDD will trip the
circuit when a potentially hazardous arc occurs, eliminating the resulting fire hazard.

Kink/break in the cable Cable wear due to Line damage resulting Incorrect wire stripping
frequent use from drilling or
construction work

Incorrect bending radii Loose screwed Defective plugs Rodent bites


connections

14
For commercial applications, our AFDD can be wired in series with MCB’s / RCBO’s to create a
flexible approach to AFDD integration.

Using any of our TPN Distribution board, standard din extension enclosures provide simple and
scalable accommodation for AFDD requirements.

Note: our AFDD is an MCB + AFDD, so when used in series with another OCP device, it is likely
that both devices will trip under an overcurrent event.

Greater breaking capacity 10 kA


Higher prospective fault currents require devices with higher breaking capacities.
So in addition to the 6kA range of AFDD for residential applications, we now
offer devices with a 10kA breaking capacity, making them more suitable for
typical commercial building installations.

This microprocessor based technology has been evolved to ensure algorithms


profiling typical UK final circuit loads, provide safe reliable operation.

Monitoring via Microprocessor


An AFDD is activated by both series and parallel arc faults. Unlike circuit breakers or
RCDs, an AFDD does not have an electromechanical trigger, but utilises electronic
technology to analyse the signature (waveform) of an arc. It reliably differentiates
between an arc fault and the signature (waveform) in normal switching and control
events, preventing false tripping.

Effective areas of protective devices depending on


fault position & type

Fault Between Short Circuit Overload Residual current Serial Arc Parallel Arc
L-L
L-N MCB/ MCB/ AFDD
L-PE RCBO RCBO RCD/RCBO RCD/RCBO/AFDD

Auxiliary contact, alarm contact and shunt


trip devices are available as supplements:
- MZ201, auxiliary contact 1C + 1O
- MZ202, alarm contact 1C + 1O
- MZ203, shunt trip 230 – 415 V AC AFDD with extension accessories from the MCB and RCCB/MCB range

15
Commercial
Distribution
Powering a building to its potential, it’s what we do. We have the perfect
solutions to help an office, factory or industrial site save energy and keep
their occupants safe. From Panelboards to our range of enhanced TP&N
boards with metering capabilities, our commercial offering will create the
perfect electrical ecosystem for a building.

16
01 Page

Distribution Boards

Type A SP&N Distribution Boards 18

Type B TP&N Distribution Boards 20

Panelboards 28

Commercial
Distribution
Metering 39

Fuse Combination Switches 40

Switch Fuses 41

Switch Disconnectors 42

Enclosed MCCBs 43

Devices

MCBs 44

RCBOs 46

RCCBs 52

Relays & Contactors 54

Motor Starters 58

Fuse Carriers 59

Surge Protection 60

Earth Fault Relays 62

MCCBs 64

Technical Pages 68

17
Type A Distribution Boards
SP&N Distribution Boards

SP&N Distribution Boards

Characteristics:
- SP&N distribution boards are available from 4-28 outgoing ways. The range comes with a choice of either 100A 2 pole
switch disconnector, 63A 30mA 2 pole RCCB Type A or 100A 30mA 2 pole RCCB Type A, or a range of split load versions.
- Conforms to BS EN 61439-3. InA = 63A/100A, Inc = 63A, Icc = 10kA
- Cable Sizes: 100A: 50mm², 63A: 16mm²
- Ample wiring space, with provision to accept RCBO’s.
- Full complement of earth and neutral terminal bars to accept up to 16mm² cable.
- Suitable for cable entry on all sides and back.
- For dimensions see page 68.
Commercial
Distribution

JK104

Description Size Cat ref.


100A Switch Disconnector Incomer
4 Way 100A Switch Disconnector Incomer 3 JK104
Sw/D/I
6 Way 100A Switch Disconnector Incomer 3 JK106
10 Way 100A Switch Disconnector Incomer 4 JK110
- 100A Switch Disconnector Incomer 14 Way 100A Switch Disconnector Incomer 5 JK114
- 63A 30mA Switch Disconnector
20 Way 100A Switch Disconnector Incomer 7 JK120
Incomer
28 Way 100A Switch Disconnector Incomer Dual Row 5 (2) JK128

63A 30mA RCCB Incomer Type A


4 Way 63A 30mA RCCB Incomer 3 JK404H
6 Way 63A 30mA RCCB Incomer 3 JK406H
10 Way 63A 30mA RCCB Incomer 4 JK410H
14 Way 63A 30mA RCCB Incomer 5 JK414H
Sw/D/I
20 Way 63A 30mA RCCB Incomer 7 JK420H

100A Switch Disconnector Incomer


Dual Row 100A 30mA RCCB Incomer Type A
4 Way 100A 30mA RCCB Incomer 3 JK304H
6 Way 100A 30mA RCCB Incomer 3 JK306H
10 Way 100A 30mA RCCB Incomer 4 JK310H
RCCB 14 Way 100A 30mA RCCB Incomer 5 JK314H
20 Way 100A 30mA RCCB Incomer 7 JK320H
100A 30mA RCCB Incomer 28 Way 100A 30mA RCCB Incomer Dual Row 5 (2) JK328H

100A Switch Disconnector and 63A 30mA RCCB Type A


6 Way Split Load Configurable 100A Switch 63A 30mA RCCB 4 JK706C
10 Way Split Load Configurable 100A Switch 63A 30mA RCCB 5 JK710C
14 Way Split Load Configurable 100A Switch 63A 30mA RCCB 7 JK714C

RCCB 100A Switch Disconnector and 100A 30mA RCCB Type A


28 Way Split Load 14+14 100A Switch 100A 30mA RCCB Dual Row 5 (2) JK527H

100A 30mA RCCB Incomer Dual Row


100A Dual Metered with MID Meter
14 Way Dual Metered 100A Configurable MID Pulsed, Modbus 7 JKD114
22 Way Dual Metered, Dual Row 100A MID Pulsed, Modbus 5 (2) JKD11111
RCCB Sw/D/I

100A Metered with MID Meter


100A Switch Disconnector Incomer & 17 Way Metered 100A MID Pulsed, Modbus 7 JKD117
63A 30mA RCCB

Sw/D/I

100A Dual Metered with MID Meter -


JKD114
Sw/D/I

Sw/D/I Sw/D/I

100A Metered with MID Meter - 100A Dual Metered with MID Meter -
JKD117 JKD11111

18 Data is subject to errors and technical modifications.  New.


Type A Distribution Boards
SP&N Distribution Boards

The relevant part of the BS EN 61439 series applies to the integration of mechanical and electrical components (switching devices, control
devices, busbars, functional units, etc.), into an enclosure. Hager systems such as consumer unit, distribution board and panel board ranges
are certified to the appropriate part of the BS EN 61439 series. When selecting other device / enclosure arrangements our Tailored Solutions
team can provide a verified solution - please contact technical support for assistance on 01952 675689.

DIN Rail Enclosures

Characteristics:
- One, two or three row 8-66 module enclosures, fitted with DIN rails to accept any combination of Hager devices. Ample
wiring space, with provision to accept RCBO’s.
- Conforms to BS EN 62208. InA = 63A/100A, Inc = 63A, Icc = 10kA
- Full complement of earth and neutral terminal bars to accept up to 16mm² cable.

Commercial
Distribution
- Suitable for cable entry on all sides and back.
- For dimensions see page 68.

Description Size Cat ref. JK008


1 Row 8 Modules 3 JK008
1 Row 12 Modules 4 JK012
1 Row 16 Modules 5 JK016
1 Row 22 Modules 7 JK022
2 Row 24 Modules (2 x 12) 4 (2) JK024
2 Row 32 Modules (2 x 16) 5 (2) JK032
2 Row 44 Modules (2 x 22) 7 (2) JK044
3 Row 66 Modules (3 x 22) 7 (3) JK066

Invicta 3 SP&N Distribution Boards

Characteristics:
- Boards are available with 14 & 29 outgoing ways. The range comes with a 100A 2 pole switch disconnector to accept
50mm² cable. Ample wiring space, with provision to accept RCBO’s.
- Conforms to BS EN 61439-3. InA = 63A/100A, Inc = 63A, Icc = 10kA
- Full complement of earth and neutral terminal bars to accept up to 16mm² cable.
- Suitable for cable entry on all sides and back.
- Enclosures are available with plain or glazed doors.
- For dimensions see page 68.
JK114AG
Cat ref. Cat ref.
Description Plain Door Glazed Door
1 Row, 14 Way 100A Switch Disconnector Incomer JK114A JK114AG
2 Row, 29 Way 100A Switch Disconnector Incomer JK129A JK129AG

Type A SP&N Distribution Board SPD Kit Type 2

- Consists of: 6mm², live & earth cables, 1x Double Pole SPD’s.

In kA In kA
Poles L-N N-PE Up kV Width (mm) Cat ref.
2 5 15 ≤ 1.2 35 VM02SPD

VM02SPD

Data is subject to errors and technical modifications.  New. 19


Type B TP&N Distribution Boards
Invicta 3 125A, Metered Boards, IP65 Distribution Boards

Invicta 3 125A TP&N Distribution Boards (125A Incoming, 63A Outgoing)

Characteristics:
- Surface mounted steel enclosures, IP3XD rated available with plain, glazed & Amendment 3 door options.
- Conforms to BS EN 61439-3, InA = 125A, Inc = 63A, Icc = 25kA
- Supplied without incoming & outgoing devices. A Hager incomer kit must be used.
- Incoming cable sizes: 125A & 100A 50mm², 63A 16mm²
- Option with factory fitted SPD Type 2 & 4 Pole SD incomer.
- For dimensions see page 69.
Cat ref.
Glazed door with Cat ref. Cat ref. Cat ref.
Description SPD type 2 & 125A 4P Sw Plain door Glazed door Residential Applications
Commercial
Distribution

JK106BG 4 Triple Pole Ways 125A TP&N Board JK104BGSPD  JK104B ¹ JK104BG ¹ JK104BA3 ¹ ²
6 Triple Pole Ways 125A TP&N Board JK106BGSPD  JK106B ¹ JK106BG ¹ JK106BA3 ¹ ²
¹ A JK101SE may be required to
8 Triple Pole Ways 125A TP&N Board JK108BGSPD  JK108B ¹ JK108BG ¹ JK108BA3 ¹ ²
provide additional incoming cable
space, see page 69. 12 Triple Pole Ways 125A TP&N Board JK112BGSPD  JK112B JK112BG JK112BA3 ²
16 Triple Pole Ways 125A TP&N Board JK116BGSPD  JK116B JK116BG JK116BA3 ²
² Full metal cover & door where
18 Triple Pole Ways 125A TP&N Board JK118BGSPD  JK118B JK118BG JK118BA3 ²
required for domestic dwelling
applications. 24 Triple Pole Ways 125A TP&N Board JK124BGSPD  JK124B JK124BG JK124BA3 ²

125A Dual Metered Boards - MID Meter

Characteristics:
- Boards are supplied with a dual channel meter that offers a pulsed & modbus output.
- Conforms to BS EN 61439-3, InA = 125A, Inc = 63A, Icc = 25kA.
- Provided with MID dual channel meter and 125A TP switch disconnector pre-fitted. Each individual pan is fully rated at 125A.
- For dimensions see page 72.
Max cable capacity Lower Upper
Description solid pan ways pan ways Cat ref.
4+6 Way Power & Lighting Board 50mm² 4 6 JKD146MID 
6+6 Way Power & Lighting Board 50mm² 6 6 JKD166MID 
JKD1416PM 6+4 Way Power & Lighting Board 50mm² 6 4 JKD164MID 
6+8 Way Power & Lighting Board 50mm² 6 8 JKD168MID 
8+8 Way Power & Lighting Board 50mm² 8 8 JKD188MID 
8+6 Way Power & Lighting Board 50mm² 8 6 JKD186MID 
4+16 Way Power & Lighting Board 50mm² 4 16 JKD1416MID 
16+4 Way Power & Lighting Board 50mm² 16 4 JKD1164MID 
8+12 Way Power & Lighting Board 50mm² 8 12 JKD1812MID 
12+8 Way Power & Lighting Board 50mm² 12 8 JKD1128MID 
12+12 Way Power & Lighting Board 50mm² 12 12 JKD11212MID 

IP65 Distribution Boards (Not suitable for outdoor use)

Characteristics:
- Suitable for three phase applications where a high IP rating is required.
- Conforms to BS EN 61439-3, InA = 125A, Inc = 63A, Icc = 25kA.
- Available with either a steel (mild steel, powder coated) or Glass Reinforced Plastic (GRP) enclosure.
- Supplied without incoming and outgoing devices. A Hager incomer kit must be used.
- Available up to 125A direct connection with outgoing distribution, rated for MCBs from 0.5A to 63A.

Description Cat ref. Steel Cat ref. GRP


4 Way IP65 Metal 125A TPN Board 800 x 600 x 300 JK104BD JK104BF

JK106BD 6 Way IP65 Metal 125A TPN Board 800 x 600 x 300 JK106BD JK106BF
8 Way IP65 Metal 125A TPN Board 800 x 600 x 300 JK108BD JK108BF
12 Way IP65 Metal 125A TPN Board 1250 x 850 x 300 JK112BD JK112BF
16 Way IP65 Metal 125A TPN Board 1250 x 850 x 300 JK116BD JK116BF

MCBs & RCBOs for Invicta 3 Type B TP&N Distribution Boards - See pages 44-46 for more info
0.5A 1A 2A 3A 4A 6A 10A

B Curve Single Pole - - - - - NBN106A NBN110A


Triple Pole - - - - - NBN306A NBN310A
C Curve Single Pole NCN100A NCN101A NCN102A NCN103A NCN104A NCN106A NCN110A
Triple Pole NCN300A NCN301A NCN302A NCN303A NCN304A NCN306A NCN310A
D Curve Single Pole NDN100A NDN101A NDN102A NDN103A NDN104A NDN106A NDN110A
Triple Pole NDN300A NDN301A NDN302A NDN303A NDN304A NDN306A NDN310A
RCBO (B Curve ) Single Pole - - - - - ADA106U  ADA110U 
RCBO (C Curve) Single Pole - - - - - ADA156U  ADA160U 

20 Data is subject to errors and technical modifications.  New.


Type B TP&N Distribution Boards
Invicta 3 125A Incomer Kits, Meter Incomer Kits, Meter Packs

Incomer Kits for 125A Boards


Max Cable
Description Capacity Solid Cat ref.
3 Pole 100A Switch Disconnector Incomer Kit (Fits within distribution board) 50mm² JK11003S 4
4 Pole 100A Switch Disconnector Incomer Kit (Fits within distribution board) 50mm² JK11004S 4
3 Pole 125A Switch Disconnector Incomer Kit (Fits within distribution board) 50mm² JK11253S 4
4 Pole 125A Switch Disconnector Incomer Kit (Fits within distribution board) 50mm² JK11254S 4
4 Pole 63A Contactor Incomer Kit includes 50mm² JK10634C 3
Switch Disconnector (fits below distribution board, 300mm high)
4 Pole 100A Contactor Incomer Kit includes M8 Lug JK11004C 3

Commercial
Distribution
Switch Disconnector (fits below distribution board, 450mm high) JK11003S
125A Direct Connection Kit (Fits within distribution board) 50mm² JK11254D
A 300 / 450mm space is
3

4 Pole 63A 30mA RCCB Type A Incomer Kit (Fits within distribution board) 25mm² JK10634RH required below the board for
4 Pole 100A 30mA RCCB Type A Incomer Kit (Fits within distribution board) 50mm² JK11004RH fitting.
4 Pole 100A 300mA RCCB Type A Incomer Kit (Fits within distribution board) 50mm² JK11004RL 4
For single phase supply
4 Pole 100A 300mA Time Delayed RCCB Type A Incomer Kit (Fits within distribution board) 50mm² JK11004RLD applications, JK1SPKIT can be
used with these incomer options.
4 Pole 100A 100mA RCCB Type A Incomer Kit (Fits within distribution board) 50mm² JK11004RM
4 Pole 100A 100mA Time Delayed RCCB Type A Incomer Kit (Fits within distribution board) 50mm² JK11004RMD
125A 4 pole Changeover Incomer Kit (Fits within distribution board) 50mm² JK11254CO 3

Side by Side Incomer Kits for 125A Boards


Characteristics:
- Complete with 125A 3P SD incomer
- Cable sets to connect to distribution boards
- Suitable for all 125A TP&N board sizes

Description Cat ref.


Dual kWh Meter Pack 125A Incomer Pulsed & Modbus M8 Lug JKD125MID 
Triple kWh Meter Pack 125A Incomer Pulsed & Modbus M8 Lug JKD125TMID  JKD125MID

Surge Protection Kits for 125A Boards


Characteristics:
- SPD kit for direct integration within 125A TPN boards
- Low Up value assured through use of solid busbar connectors and solid copper Earth
- SPD suitable for TN / TT Earth arrangements including TNC-S (PME)
- CT2 type SPD to accommodate multiple Earthing systems.
- Coordination verified with upstream Hager Panelboard SPDs.
Description Cat ref.
Type 1 & 2 Surge Protection Kit for 125A TP&N Boards JK101SPD 
Type 2 Surge Protection Kit for 125A TP&N Boards JK102SPD 

JK101SPD
Type 1 & 2 Surge Protection Kit for 125A Dual Metered Boards JKD101SPD 
Type 2 Surge Protection Kit for 125A Dual Metered Boards JKD102SPD 

Meter Packs & Kits for 125A Boards - MID


Characteristics:
- JKD1125MID – This enclosed meter pack fits below any Hager standard 125A TPN boards. Can be used in conjunction
with SPD kits – MID meter has Modbus and pulse comms.
- JK140MID – This MID meter kits can be fitted within the TPN board, but is not suitable for 4 & 6 way boards. This kit can
not be used, when an SPD is fitted – MID Meter has Modbus and pulse comms.

Description Cat ref.


Meter Enclosure & MID Meter JKD1125MID *
Multifunction Meter Pack 125A Pulsed & Modbus JK140MID *

JK140MID

16A 20A 25A 32A 40A 45A 50A 63A


NBN116A NBN120A NBN125A NBN132A NBN140A - NBN150A NBN163A
NBN316A NBN320A NBN325A NBN332A NBN340A - NBN350A NBN363A
NCN116A NCN120A NCN125A NCN132A NCN140A - NCN150A NCN163A
NCN316A NCN320A NCN325A NCN332A NCN340A - NCN350A NCN363A
NDN116A NDN120A NDN125A NDN132A NDN140A - NDN150A NDN163A
NDN316A NDN320A NDN325A NDN332A NDN340A - NDN350A NDN363A
ADA116U  ADA120U  ADA125U  ADA132U  ADA140U  ADA145U  - -
ADA166U  ADA170U  ADA175U  ADA182U  ADA190U  - - -

Data is subject to errors and technical modifications.  New. 21


Type B TP&N Distribution Boards
Invicta 3 250A TP&N Boards, Tri-Metered Board, Hybrid Boards

Invicta 3 250A TP&N Distribution Boards (250A Incoming, 63A Outgoing)

Characteristics:
- Surface mounted steel enclosures, IP3XD rated, available with plain, glazed & Amendment 3 door options.
- Conforms to BS EN 61439-3. InA = 250A, Inc = 63A, Icc = 25kA.
- Supplied without incoming and outgoing devices. A Hager incoming kit must be used.
- For dimensions see page 69.

Cat ref. Cat ref. Cat ref.


Description Plain door Glazed door Residential Applications
8 Triple Pole Ways 250A TP&N Board JK208B JK208BG JK208BA3 1
Commercial
Distribution

JK208BG 12 Triple Pole Ways 250A TP&N Board JK212B JK212BG JK212BA3 1
16 Triple Pole Ways 250A TP&N Board JK216B JK216BG JK216BA3 1
¹ Full metal cover & door where 18 Triple Pole Ways 250A TP&N Board JK218B JK218BG JK218BA3 1
required for domestic dwelling
applications. 24 Triple Pole Ways 250A TP&N Board JK224B JK224BG JK224BA3 1

200A Tri Metered Boards (Power, Lighting & Mechanical Services)

Characteristics:
- Provides separate energy information for each group of outgoing devices.
- Boards are supplied with meters that offer a pulsed & modbus output.
- Provided with a 200A switch disconnector incomer pre-fitted with ample cable space.
- Conforms to BS EN 61439-3. InA = 200A, Inc = 63A, Icc = 25kA.
- For dimensions see page 72.

Max cable Lower Middle Upper


Description cap. solid pan ways pan ways pan ways Cat ref.
8+8+4 Way Power, Lighting & Service Board M8 Lug 8 8 4 JKD2884MID 
JKD2884PM

Hybrid 250A TP&N Distribution Boards (250A Incoming, up to 125A outgoing)

Characteristics:
- A hybrid distribution board combining 2x TP ways of 27mm MCB devices to supply end loads up to 125A, with standard
18mm MCB/RCBOs for other smaller loads.
- Surface mounted steel enclosure, IP3XD rated, available with plain steel or glazed door options.
- Conforms to BS EN 61439-3, InA = 250A, Inc = 63A /125A, Icc = 25kA
- For dimensions see page 70.

Cat ref. Cat ref.


Description Plain Door Glazed Door
Hybrid 250A Distribution Boards - Supplied with 250A 3P Switch Disconnector Incomer Pre-Fitted
JK20210BG
250A 2+10 Way Hybrid TPN Board JK20210BSD JK20210BGSD
250A 2+16 Way Hybrid TPN Board JK20216BSD JK20216BGSD
250A 2+20 Way Hybrid TPN Board JK20220BSD JK20220BGSD

Hybrid 250A TPN Distribution Boards Without Incomer Supplied


250A 2+10 Way Hybrid TPN Board JK20210B JK20210BG
250A 2+16 Way Hybrid TPN Board JK20216B JK20216BG
250A 2+20 Way Hybrid TPN Board JK20220B JK20220BG

MCBs & RCBOs for Invicta 3 Type B TP&N Distribution Boards - See pages 44-46 for more info
0.5A 1A 2A 3A 4A 6A 10A

MCB B Curve Single Pole - - - - - NBN106A NBN110A


Triple Pole - - - - - NBN306A NBN310A
MCB C Curve Single Pole NCN100A NCN101A NCN102A NCN103A NCN104A NCN106A NCN110A
Triple Pole NCN300A NCN301A NCN302A NCN303A NCN304A NCN306A NCN310A
MCB D Curve Single Pole NDN100A NDN101A NDN102A NDN103A NDN104A NDN106A NDN110A
Triple Pole NDN300A NDN301A NDN302A NDN303A NDN304A NDN306A NDN310A
RCBO B Curve Single Pole - - - - - ADA106U ADA110U
RCBO C Curve Single Pole - - - - - ADA156U ADA160U

MCBs Suitable for Hybrid Distribution Boards Only - See page 50 for more info
80A 100A 125A
MCB C Curve Single Pole HMC180T HMC190T HMC199T
Triple Pole HMC380T HMC390T HMC399T
MCB D Curve Single Pole HMD180T HMD190T HMD199T
Triple Pole HMD380T HMD390T HMD399T

22 Data is subject to errors and technical modifications.  New.


Type B TP&N Distribution Boards
Incomer Kits, Invicta 3 250A Meter Incomer Kits, Meter Packs

Incomer Kits for 250A Boards


Description Connection Cat ref.
3 Pole 250A MCCB Incomer Kit (Fits within distribution board) M8 Lug JK22503M
4 Pole 250A MCCB Incomer Kit (Fits within distribution board) M8 Lug JK22504M
3 Pole 250A Switch Disconnector Incomer Kit (Fits within distribution board) M8 Lug JK22503S
4 Pole 250A Switch Disconnector Incomer Kit (Fits within distribution board) M8 Lug JK22504MCS
4 Pole 250A Direct Connection Kit (Fits within distribution board) M8 Lug JK22504D
(Where required, use the JKD2250MID meter)
4 Pole 160A Contactor Incomer Kit includes Switch Disconnector M8 Lug JK21604C
(fits below distribution board, 450mm high)

Commercial
Distribution
3 Pole 125A MCCB Incomer Kit (Fits within distribution board) M8 Lug JK21253M
4 Pole 125A MCCB Incomer Kit (Fits within distribution board) M8 Lug JK21254M

Surge Protection Kits for 250A Boards


Characteristics:
- SPD kit for direct integration within 250A TPN boards
- Type 1 + 2 SPD - Low Up value assured through use of solid copper Earth link
- Fail safe design SPD facilitates direct connection to main busbars
- SPD suitable for TN / TT Earth arrangements including TNC-S (PME)
- CT2 type SPD to accommodate multiple Earthing systems

Description Cat ref.


Type 1 & 2 Surge Protection Kit for 250A TP&N Boards JK201SPD 
Type 2 Surge Protection Kit for 250A TP&N Boards JK202SPD  JK201SPD

Side by Side Incomer Kits for 250A TP&N Boards


Characteristics:
- Complete with 3P SD incomer
- Cable set to connect to distribution boards
- Suitable for all 250A board sizes
Description Connection Cat ref.
Dual kWh Meter Module 250A Incomer Pulsed M8 Lug JKD250MID 
Triple kWh Meter Module 250A Incomer Pulsed & Modbus M8 Lug JKD250TMID 

JKD250MID (distribution boards


are not included)

Single Meter Packs for 250A Boards


Characteristics:
- Meter kit for standard 250A distribution boards & hybrid 250A distribution boards.
- Each meter pack contains: meter, 3 pole CT Block, 3 x fuses & carriers on DIN rail, wiring loom, incoming shroud &
instructions.

Description Cat ref.


MID Multifunction Meter Kit 250A Pulsed & Modbus JK240MID 
MID Multifunction Meter Pack 250A Pulsed & Modbus JKD2250MID 

JK240MID

16A 20A 25A 32A 40A 45A 50A 63A


NBN116A NBN120A NBN125A NBN132A NBN140A - NBN150A NBN163A
NBN316A NBN320A NBN325A NBN332A NBN340A - NBN350A NBN363A
NCN116A NCN120A NCN125A NCN132A NCN140A - NCN150A NCN163A
NCN316A NCN320A NCN325A NCN332A NCN340A - NCN350A NCN363A
NDN116A NDN120A NDN125A NDN132A NDN140A - NDN150A NDN163A
NDN316A NDN320A NDN325A NDN332A NDN340A - NDN350A NDN363A
ADA116U ADA120U ADA125U ADA132U ADA140U ADA145U - -
ADA166U ADA170U ADA175U ADA182U ADA190U - - -

Data is subject to errors and technical modifications.  New. 23


Type B TP&N Distribution Boards
125A & 250A DIN Extension Boxes, Cable Spreader Boxes

DIN Extension Boxes & Door Kits for 125A Primary Boards

Characteristics:
- Extension boxes have plain or glazed doors and a DIN rail for mounting modular devices.
- Conforms to BS EN 62208.
- Full width enclosure provided with sixteen modular ways per row.
- For dimensions see page 70.

Cat ref. Cat ref. Cat ref.


Description Plain door Glazed door Residential Applications
JK116EG
125A 16 Way 1 Row DIN Extension Box JK116E JK116EG JK116EA3
Commercial
Distribution

125A 32 Way 2 Row DIN Extension Box JK132E JK132EG JK132EA3


125A 16 Mod DIN Plain Spare Door Kit (Amendment 3) - - JK116EA3-DK
125A 32 Mod DIN Plain Spare Door Kit (Amendment 3) - - JK132EA3-DK

DIN Extension Boxes & Door Kits for 250A Primary Boards

Cat ref. Cat ref.


Description Plain door Glazed door
250A 16 Way 1 Row DIN Extension Box JK216E JK216EG
250A 32 Way 2 Row DIN Extension Box JK232E JK232EG
250A 16 Way 1 Row DIN Extension Box (Amendment 3) JK216EA3 -
250A 32 Way 2 Row DIN Extension Box (Amendment 3) JK232EA3 -
JK216E 250A 16 Mod DIN Plain Spare Door Kit (Amendment 3) JK216EA3-DK -
250A 32 Mod DIN Plain Spare Door Kit (Amendment 3) JK232EA3-DK -

Cable Spreader Boxes & Door Kits for 125A & 250A Primary Boards

Characteristics:
- Cable spreader boxes are used for additional cabling space therefore do not require doors. Optional door kits are available.
- Conforms to BS EN 62208.
- For dimensions see page 70.

Cat ref. Cat ref.


Description 125A 250A
JK101SE
Small Cable Spreader Box (supplied without a door) JK101SE JK201SE
Large Cable Spreader Box (supplied without a door) JK102LE JK202LE
Small Cable Spreader Box Door Kit JK101DK JK101DK
Large Cable Spreader Box Door Kit JK102DK JK102DK

JK101DK

Invicta 3 125A Flush Kits

Characteristics:
- Suitable for flush mounting our 8 - 24 way Invicta 3 TP&N Boards - 125A.
- Distribution board not included.
- Flush mounted distribution board solution has been revalidated to meet BS EN 61439-3 - additional requirements for flush
mounted solutions
- Provides low profile high aesthetic solution for open areas.

Description Cat ref.


JK08FK Flush Mounting Kit for Invicta 3 TP&N - 8 Way JK108FK 
Flush Mounting Kit for Invicta 3 TP&N - 12 Way JK112FK 
(TP&N Board not included)
Flush Mounting Kit for Invicta 3 TP&N - 16 Way JK116FK 
Flush Mounting Kit for Invicta 3 TP&N - 18 Way JK118FK 
Flush Mounting Kit for Invicta 3 TP&N - 24 Way JK124FK 

24 Data is subject to errors and technical modifications.  New.


Type B TP&N Distribution Boards
125A & 250A Side DIN Enclosures, Side Extension Boxes

Side DIN Enclosures for Primary Boards

Characteristics:
- Side extension boxes allow for the installation of DIN rail mounted devices.
- Conforms to BS EN 62208.
- Can be horizontally or vertically attached to distribution boards.
- All DIN Enclosures supplied with two removable gland plates.
- For dimensions see page 69.

Cat ref. Cat ref.


Description Number of rows Glazed door Residential Applications
Side DIN Enclosures for 125A Primary Boards

Commercial
Distribution
JK104BDFG
4 Way 32 Mod Side DIN Enclosure for JK104B(G) 2 JK104BDFG JK104BDFA3
6 Way 32 Mod Side DIN Enclosure for JK106B(G) 2 JK106BDFG JK106BDFA3
8 Way 48 Mod Side DIN Enclosure for JK108B(G) 3 JK108BDFG JK108BDFA3
12 Way 64 Mod Side DIN Enclosure for JK112B(G) 4 JK112BDFG JK112BDFA3
16 Way 80 Mod Side DIN Enclosure for JK116B(G) 5 JK116BDFG JK116BDFA3

Side DIN Enclosures for 250A Primary Boards


8 Way 80 Mod Side DIN Enclosure for JK208B(G) 5 JK208BDFG JK208BDFA3
12 Way 80 Mod Side DIN Enclosure for JK212B(G) 5 JK212BDFG JK212BDFA3
16 Way 96 Mod Side DIN Enclosure for JK216B(G) 6 JK216BDFG JK216BDFA3
18 Way 112 Mod Side DIN Enclosure for JK218B(G) 7 JK218BDFG JK218BDFA3 JK208BDFG
24 Way 128 Mod Side DIN Enclosure for JK224B(G) 8 JK224BDFG JK224BDFA3

Side Extension Boxes for 125A Primary Boards

Characteristics:
- Side extension boxes allow cable ways to be fitted on site.
- Conforms to BS EN 62208.
- Available in either half or full distribution board width.
- All side extension boxes supplied with two removable gland plates.
- For dimensions see page 70.

Cat ref.
Description Plain door
Side Extension Boxes for 125A Primary Boards
JK104BSF
4 Way Side Extension Box for JK104B(G) Full Width JK104BSF
6 Way Side Extension Box for JK106B(G) Full Width JK106BSF
8 Way Side Extension Box for JK108B(G) Full Width JK108BSF
12 Way Side Extension Box for JK112B(G) Full Width JK112BSF
16 Way Side Extension Box for JK1116B(G) Full Width JK116BSF

Side Extension Boxes for 250A Primary Boards


8 Way Side Extension Box for JK208B(G) Full Width JK208BSF
12 Way Side Extension Box for JK212B(G) Full Width JK212BSF
16 Way Side Extension Box for JK216B(G) Full Width JK216BSF
18 Way Side Extension Box for JK218B(G) Full Width JK218BSF
JK104BSH
24 Way Side Extension Box for JK224B(G) Full Width JK224BSF

Half Width Side Extension Boxes for 125A Primary Boards


4 Way Half Width Extension Box JK104BSH
6 Way Half Width Extension Box JK106BSH
8 Way Half Width Extension Box JK108BSH
12 Way Half Width Extension Box JK112BSH
16 Way Half Width Extension Box JK116BSH
Small Half Width Filler Box JK101BSH

Half Width Side Extension Boxes for 250A Primary Boards


8 Way Half Width Extension Box JK208BSH
12 Way Half Width Extension Box JK212BSH
16 Way Half Width Extension Box JK216BSH
18 Way Half Width Extension Box JK218BSH
24 Way Half Width Extension Box JK224BSH
Small Half Width Filler Box JK201BSH

Data is subject to errors and technical modifications.  New. 25


Type B TP&N Distribution Boards
Accessories, Door Kits, Trunking Kits

Invicta 3 125A & 250A & IP65 Distribution Board Accessories

125A Accessories 250A Accessories


Description Cat ref. Cat ref.
Door Locking Kit JK222PK JK222PK
Spare Label Pack - All Sizes (one pack) JKLABELPACK JKLABELPACK
Single Phasing Kit JK1SPKIT JK250BSP
Single Pole Busbar Blank JK01B JK01B
JK01B
Single Pole 27mm Blank JK02B JK02B
JK1/2 Horizontal or Vertical Mechanical Connection Kit JK100HK JK100HK
Commercial
Distribution

Brass Gland Plate - 2.0mm JK1PLATEB JK2PLATEB


100A Top Tap Off Kit JK100TAP JK100TAP
Additional Earth Bar Kit JK030BEB JK030BEB
High Integrity - 2 x 15 Connections
Document Clip JK01DC JK01DC
Neutral Connecting Block 100A KRN190 KRN190
JK1/2 Neutral Clear Shroud JK1/NEUTRALSHROUD JK1/NEUTRALSHROUD
JK1/2 Busbar Stack Top Shroud JK1/2TOPSHROUD JK1/2TOPSHROUD
JK1/2 Main Incomer Shroud JK1/INCOMSHROUD JK2/INCOMSHROUD
JK222PK
Spare Gland Plate Including Drill Markings - 1.2mm JK1PLATEM JK2PLATEM

Invicta 3 125A & 250A Amendment 3 Compliant Door Kit

Description 125A Cat ref. 250A Cat ref.


4 Way TPN Plain Spare Door Kit Amendment 3 JK104BA3-DK -
6 Way TPN Plain Spare Door Kit Amendment 3 JK106BA3-DK -
8 Way TPN Plain Spare Door Kit Amendment 3 JK108BA3-DK JK208BA3-DK
12 Way TPN Plain Spare Door Kit Amendment 3 JK112BA3-DK JK212BA3-DK
16 Way TPN Plain Spare Door Kit Amendment 3 JK116BA3-DK JK216BA3-DK
18 Way TPN Plain Spare Door Kit Amendment 3 JK118BA3-DK JK218BA3-DK

JK106BA3-DK 24 Way TPN Plain Spare Door Kit Amendment 3 JK124BA3-DK JK224BA3-DK

Invicta 3 125A & 250A Trunking Kits & Spares

Characteristics:
- Each trunking kit contains a trunking channel, lid, lid joining brackets, connecting brackets and end caps.

100mm 4” 150mm 6”
Description Cat ref. Cat ref.
Trunking Kit for Invicta 3 TP&N JK04TK ¹ JK06TK
Spare Trunking Channel JK04TC ¹ JK06TC
Spare Lid JK04TL ¹ JK06TL
JK06TK
Spare End Cap JK04TE ¹ JK06TE
1
4” trunking not suitable for JKD Spare Connecting Bracket JK04TJ ¹ JK06TJ
Power & Lighting Boards.
Spare Trunking Lid Joining Bracket JK04TP ¹ JK06TP

26 Data is subject to errors and technical modifications.  New.


Tailored
solutions.
From pre-assembled standard distribution units to bespoke
composite TP&N boards and plug in distribution boards, we can
provide the solution.

We will deliver to site to an agreed deadline and specification.

To find out more, call our Estimation Team on 01952 675600.


Panelboards 250A Rated
Invicta 3 250A, Incomer Kits, Meter Enclosures

Invicta 3 Panelboards (250A Incoming 125A Outgoing)

Characteristics
- Comprises of IP3XD rated enclosure, pan assembly, twin neutral and earth bars.
- Conforms to BS EN 61439-2. InA = 250A, Inc = 125A, Icc = 25kA.
- Supplied without incoming kit, JN 250A incomer kit must be used.
- Form 3B type 2 using outgoing terminal shield (form 3A without terminal shield).
- Removable side gland plates are standard. Removable gland plates are provided top and bottom for ease of installation.
- For dimensions see page 77.
Cable Capacity Incomers & Outgoers
- Incomers: 3 and 4 pole incomers, cable capacity 150mm², max lug width 25mm, M8 bolt, direct connection kit.
- Outgoers: 1 & 3 pole MCCB 70mm² flexible, 95mm² solid.
Commercial
Distribution

JN204BG Options
- Key lock, meter pack, DIN rail, extension box, spreader box.
Outgoing MCCBs
- Adjustable thermal options on triple pole devices.

Cat ref. Cat ref.


Description Plain door Glazed door
4 Triple Pole Ways 250A Panelboard JN204B JN204BG
6 Triple Pole Ways 250A Panelboard JN206B JN206BG
8 Triple Pole Ways 250A Panelboard JN208B JN208BG
12 Triple Pole Ways 250A Panelboard JN212B JN212BG
16 Triple Pole Ways 250A Panelboard JN216B JN216BG

JN204B

Incomer Kits

Description Max cable capacity Cat ref.


3 Pole 250A MCCB Incomer Kit M8 Lug JN223BM
(Adj. Thermal 0.63, 0.8, 1) 40kA (Magnetic 5, 7, 9, 11 x In)
4 Pole 250A MCCB Incomer Kit M8 Lug JN224BM
(Adj. Thermal 0.63, 0.8, 1) 40kA (Magnetic 5, 7, 9, 11 x In)
3 Pole 250A Non-Auto MCCB Incomer Kit M8 Lug JN223BS
4 Pole 250A Non-Auto MCCB Incomer Kit M8 Lug JN224BS
3 Pole 125A MCCB Incomer Kit M8 Lug JN213BM 
4 Pole 125A MCCB Incomer Kit M8 Lug JN214BM 
250A Direct Connection Kit M8 Lug JN224BD
Palm Kit for Larger Cable >50mm2 to 2 x 120mm² with 10mm Bolt Fixing JN250SL 

250A JN Panelboard Surge Protection Device Kit

Characteristics
- SPD kit for direct integration within 250A Panelboards
- Fail safe design SPD facilitates direct connection to main busbars
- SPD suitable for TN / TT Earth arrangements including TNC-S (PME)
- CT2 type SPD to accommodate multiple Earthing systems
- Solid copper Earth link for enhanced Up performance
- Supplied with mounting & connection set
JN202SPD
Cat ref.
Description Plain door
SPD kit Type 1+2 for JN Panelboards JN201SPD 
SPD kit Type 2 for JN Panelboards JN202SPD 

JN201SPD
(Image shows Device only, kit
includes connection links)

28 Data is subject to errors and technical modifications.  New.


Panelboards 250A Rated
DIN Extension Boxes, Spreader Boxes, Meter Packs, Accessories

DIN Rail Extension Boxes

Characteristics
- Supplied with DIN Rail & without gland plate (utilise removed gland plate from panelboard)
- DIN rail extensions boxes have plain or glazed doors and DIN rail chassis.
- JK2 side extension boxes can be used with this range see page 25.
- For dimensions see page 71.
JN201BE
Cat ref. Cat ref.
Description Plain Door Glazed Door
1 Row 26 Mod (300mm Height) JN201BE JN201BEG

Commercial
Distribution
2 Row 52 Mod (450mm Height) JN203BE JN203BEG

Cable Spreader Boxes & Door Kits

Characteristics
- Supplied without gland plates (utilise removed gland plate from panelboard)
- Cable spreader boxes are used for additional cabling space therefore do not require doors. Optional door kits are available.
- For dimensions see page 77.

Description Cat ref.


Small (300mm Height) (Door not included) JN205BE
Large (450mm Height) (Door not included) JN206BE JN205BE

Door Kit for Small Cable Spreader Box JN205DK


Door Kit for Large Cable Spreader Box JN206DK

Meter Pack 250A

Characteristics
- Comprises of a digital multi function meter, three control circuit fuse carriers, wiring harness and CTs.
- The meter pack fits directly into the main panelboard.
- For metering incoming supply to the panelboard.

Description Cat ref.


MID Multifunction Meter Pack 250A Pulsed & Modbus JN201MID

JN201MID

Accessories

Description Cat ref.


Touch Up Paint 30ml JF95A
Allen Key Set JF296A
Gland Plate for Invicta 3 (250A) JN2PLATE
Key Lock with One Key JK222PK
x125 Frame Blank (3x blanks required per triple pole way) JN001BP
Multi Padlock Plate (for integral toggle lock, fits to toggle for up to 3 padlocks max ø8mm) HXA039H
Neutral Barrier Kit JN201NS
JN001BP

Outgoing Devices - See page 64 for more info

MCCBs - Single Pole MCCBs - Triple Pole Adjustable Thermal


Rating. 18kA Fixed Thermal 25kA Fixed Thermal 18kA Adjustable 25kA Adjustable
Thermal Thermal
16A HDA014E  HHA014E  Rating. 0.63, 0.8, 1 x In 0.63, 0.8, 1 x In
20A HDA018E  HHA018E  25A HDA025U HHA025U
25A HDA023E  HHA023E  40A HDA040U HHA040U
32A HDA030E  HHA030E  63A HDA063U HHA063U
40A HDA038Z HHA038Z 80A HDA080U HHA080U
50A HDA048Z HHA048Z 100A HDA100U HHA100U
63A HDA061Z HHA061Z 125A HDA125U HHA125U
80A HDA078Z HHA078Z
100A HDA098Z HHA098Z
125A HDA123Z HHA123Z

Data is subject to errors and technical modifications.  New. 29


Panelboards 400A Rated
400A Incoming 125A Outgoing, DIN Extension Boxes

Invicta 3 Panelboards (400A Incoming 125A Outgoing)

Characteristics
- Comprises of IP3XD enclosure, pan assembly, neutral bar and earth bar.
- Conforms to BS EN 61439-2. InA = 400A, Inc = 125A, Icc = 50kA.
- Supplied without incoming kit, one of the incomer kits listed below must be used.
- Form 3B type 2 using outgoing terminal shield (form 3A without terminal shield).
- Removable gland plates are provided top and bottom for ease of installation.
- For dimensions see page 78.
Cable Capacity Incomers & Outgoers
- Incomers: 3 and 4 pole incomers, cable capacity: M12 bolt, direct connection kit: M10 hexagonal bolt.
- Outgoers: 1 & 3 pole MCCB: 70mm²­flexible/ 95mm² solid.
Commercial
Distribution

Options
JF406B
- Key lock, meter pack, DIN rail, extension box, spreader box.
Outgoing MCCBs
- Adjustable thermal options on triple pole.

Cat ref. Cat ref.


Description Plain Door Glazed door
6 Triple Pole Ways 400A Panelboard JF406B JF406BG
8 Triple Pole Ways 400A Panelboard JF408B JF408BG
12 Triple Pole Ways 400A Panelboard JF412B JF412BG
16 Triple Pole Ways 400A Panelboard JF416B JF416BG
18 Triple Pole Ways 400A Panelboard JF418B JF418BG

Incomer Kits for 400A Panelboards

Max cable
Description capacity solid Cat ref.
3 Pole 400A MCCB Incomer Kit 50kA M12 Lug JF443BM
Electronic LSI MCCB,
Ir adjustable 0.4 – 1.0 x In
4 Pole 400A MCCB Incomer Kit 50kA M12 Lug JF444BM
Electronic LSI MCCB,
Ir adjustable 0.4 – 1.0 x In
3 Pole 400A Switch Disconnector Incomer Kit M12 Lug JF443BS
4 Pole 400A Switch Disconnector Incomer Kit M12 Lug JF444BS
400A Direct Connection Kit M10 Lug JF444BD

400A JF Panelboard Surge Protection Device Kit

Characteristics
- SPD kit for direct integration within 400A Panelboards
- Type 1 + 2 SPD with Integrated fuses facilitates direct connect to main busbars
- SPD suitable for TN / TT Earth arrangements including TNC-S (PME)
- CT2 type SPD to accommodate multiple Earthing systems
- Solid copper Earth link for assured lower Up performance

Description Cat ref.


JF801SPD
SPD kit Type 1 + 2 for JF Panelboards JF801SPD 

DIN Rail Extension Boxes for 400A Panelboards

Characteristics
- DIN rail extension boxes have plain or glazed doors and DIN rail chassis.
- Cable spreader boxes are used for additional cabling space therefore do not require doors. If doors are desired optional door
kits are available.
- Supplied with DIN Rail and without gland plate (utilise removed gland plate from panelboard).
JF801E
- For dimensions see page 78.

Cat ref. Cat ref.


Description Plain Door Glazed Door
1 Row 34 Mod (300mm Height) JF801E JF801EG
2 Row 68 Mod (450mm Height) JF803E JF803EG

30 Data is subject to errors and technical modifications.  New.


Panelboards 400A Rated
Cable Spreader Boxes, Meter Pack, Accessories

Cable Spreader Boxes & Door Kits for 400A Panelboards

Characteristics
- Supplied without gland plates (utilise removed gland plate from panelboard).
- Cable spreader boxes are used for additional cabling space therefore do not require doors. Optional door kits are available.
- For dimensions see page 78.
JF805E
Description Cat ref.
Small (300mm Height) (Door not included) JF805E
Large (450mm Height) (Door not included) JF806E

Commercial
Distribution
Small Cable Spreader Box Door Kit JF805DK
Large Cable Spreader Box Door Kit JF806DK

Meter Pack 400A

Characteristics
- These meter packs fit directly into the main panelboard. Suitable for single incoming cable.
- Spreader box required to mount CT’s.

Description Cat ref.


MID Multifunction Meter Pack 400A Pulsed & Modbus JF403MID

Accessories

Description Cat ref.


Locking Kit for Incoming Device (All Ratings) HXD039H
Allen Key Set JF296A
Gland Plate for Invicta 3 400A Range JFPLATE
Key Lock with One Key JK222PK
x125 Frame 1 Pole Blank (3x blanks required per triple pole) JN001BP
Outgoer Locking Kit (fits to toggle for up to 3 padlocks max ø 8mm²) HXA039H
Terminal Cover x160 1 Pole Long HYA029H JN001BP
Terminal Cover x160 3 Pole Long HYA021H

HXD039H

Outgoing Devices - See page 64 for more info

MCCBs - Single Pole MCCBs - Triple Pole Adjustable Thermal


Rating. 18kA Fixed Thermal 25kA Fixed Thermal 18kA Adjustable 25kA Adjustable
16A Thermal Thermal
HDA014E  HHA014E 
Rating. 0.63, 0.8, 1 x In 0.63, 0.8, 1 x In
20A HDA018E  HHA018E  25A HDA025U HHA025U
25A HDA023E  HHA023E  40A HDA040U HHA040U
32A HDA030E  HHA030E  63A HDA063U HHA063U
40A HDA038Z HHA038Z 80A HDA080U HHA080U
50A HDA048Z HHA048Z 100A HDA100U HHA100U
63A HDA061Z HHA061Z 125A HDA125U HHA125U
80A HDA078Z HHA078Z
100A HDA098Z HHA098Z
125A HDA123Z HHA123Z

Data is subject to errors and technical modifications.  New. 31


Panelboards 630A/800A Rated
630A/800A Incoming 125A/250A Outgoing

Invicta 3 Panelboards (630A/800A Incoming 125A Outgoing)

Characteristics
- Comprises of IP3XD enclosure, pan assembly, neutral bar and earth bar.
- Conforms to BS EN 61439-2. InA = 630/800A, Inc = 125A/250A, Icc = 50kA.
- Supplied without incoming kit, one of the incomer kits listed below must be used.
- Form 3B type 2 using outgoing terminal shield (form 3A without terminal shield).
- Removable gland plates are provided top and bottom for ease of installation.
- Switch Disconnector: 630A/800A, MCCB: 400A/630A, Direct connection: 800A.
- Incoming cable lugged via M12 hexagonal bolt.
- For dimensions see page 78.
Cable Capacity Incomers & Outgoers
Commercial
Distribution

- Incomers: 400A: 2 x 240mm², 630A/800A: 2 x 240mm² / 2 x 300mm².


JF608B
- Outgoers: X160 devices: up to 125A - 70mm² flexible, 95mm² solid,
X250 devices: 150mm2 rigid cables, palm lug max. width: 25mm
Outgoing MCCBs
- X160 adjustable thermal option.
- X250 adjustable thermal / magnetic option.
Cat ref. Cat ref.
Description Plain Door Glazed door
8 Triple Pole Ways 630A Panelboard JF608B JF608BG
12 Triple Pole Ways 630A/800A Panelboard JF812B JF812BG
18 Triple Pole Ways 630A/800A Panelboard JF818B JF818BG

1
Max allowed incomer of 630A on this Invicta 3 Panelboards (630A/800A Incoming 125A/250A Outgoing)
panelboard.
Characteristics
- These boards will accept a range of MCCB frame sizes: 125A frame: 16-125A single pole/triple pole, 250A frame: 80-250A
triple pole only
- InA = 630/800A, Inc = 250A, Icc = 50kA.

Cat ref. Cat ref.


Description Plain Door Glazed door
6 Triple Pole Ways Panelboard (2 x 250A  + 4 x 125A ) JF60204B 1 JF60204BG 1
8 Triple Pole Ways Panelboard (2 x 250A  + 6 x 125A ) JF80206B JF80206BG
8 Triple Pole Ways Panelboard (4 x 250A  + 4 x 125A ) JF80404B JF80404BG
12 Triple Pole Ways Panelboard (2 x 250A  + 10 x 125A ) JF80210B JF80210BG
12 Triple Pole Ways Panelboard (4 x 250A  + 8 x 125A ) JF80408B JF80408BG
18 Triple Pole Ways Panelboard (4 x 250A  + 14 x 125A ) JF80414B JF80414BG
18 Triple Pole Ways Panelboard (6 x 250A  + 12 x 125A ) JF80612B JF80612BG

* Select the required 630A/800A rated Incomer Kits for 630A/800A Panelboards
panelboard (e.g. JF80206BG) and add
the suffix 800LBS e.g. Characteristics
JF80206BG800LBS - A 300mm cable spreader box (JF805E) is required for all incomer kits.

Description Max cable capacity Cat ref.


4 Pole 400A Load Break Switch 25kA M10 Lug JF844BSW
4 Pole 630A Load Break Switch 25kA M12 Lug JF864BSW
4 Pole 800A Load Break Switch M12 Lug *800LBS
800A Direct Connection Kit 4 Pole M12 Lug JF884BD
3 Pole 400A MCCB Incomer Kit 50kA M12 Lug JF843BM
Electronic LSI MCCB,
Ir adjustable 0.4 – 1.0 x In
4 Pole 400A MCCB Incomer Kit M12 Lug JF844BM
Electronic LSI MCCB,
Ir adjustable 0.4 – 1.0 x In
3 Pole 630A MCCB Incomer Kit 50kA M12 Lug JF863BM
Electronic LSI MCCB,
Ir adjustable 0.4 – 1.0 x In
4 Pole 630A MCCB Incomer Kit 50kA M12 Lug JF864BM
Electronic LSI MCCB,
Ir adjustable 0.4 – 1.0 x In

630/800A JF Panelboard Surge Protection Device Kit

Characteristics
- SPD kit for direct integration within JF Panelboards
- Type 1 + 2 SPD with Integrated fuses facilitate direct connect to main busbars
- SPD suitable for TN / TT Earth arrangements including TNC-S (PME)
- CT2 type SPD to accommodate multiple Earthing systems

Description Cat ref.


JF801SPD SPD kit Type 1 + 2 for JF Panelboards JF801SPD *

32 Data is subject to errors and technical modifications.  New.


Panelboards 630A/800A
DIN Extension Boxes, Cable Spreader Boxes, Meter Pack

DIN Rail Extension Boxes for 630A/800A Panelboards

Characteristics
- DIN rail extension boxes have plain or glazed doors and DIN rail chassis.
- Cable spreader boxes are used for additional cabling space therefore do not require doors. Optional door kits are available.
- Supplied with DIN rail and without gland plate (utilise removed gland plate from panelboard).
- For dimensions see page 78.
JF801E
Cat ref. Cat ref.
Description Plain Door Glazed door
1 Row 34 Mod (300mm Height) JF801E JF801EG

Commercial
2 Row 68 Mod (450mm Height) JF803E JF803EG

Distribution
Cable Spreader Boxes & Door Kits for 630A/800A Panelboards

Characteristics
- Supplied without gland plates (utilise removed gland plate from panelboard).
- Cable spreader boxes are used for additional cabling space therefore do not require doors. Optional door kits are available.
- For dimensions see page 78.

Description Cat ref.


Small (300mm Height) (Door not included) JF805E
Large (450mm Height) (Door not included) JF806E
Small Cable Spreader Box Door Kit JF805DK
Large Cable Spreader Box Door Kit JF806DK

Meter Pack for 630A/800A Panelboards

Characteristics
- These meter packs fit directly into the main panelboard. Spreader box required to mount CT’s.
- For Meter Enclosures see page 39.

Description Cat ref.


MID Multifunction Meter Pack 800A Pulsed & Modbus JF803MID 

Outgoing Devices Thermal Magnetic - See page 64 - 66 for more info

 MCCBs x250 40kA - Triple Pole  MCCBs - 125A 18kA Single Pole
Adjustable Thermal & Rating. 18kA Fixed Thermal 25kA Fixed Thermal
Rating. Magnetic
16A HDA014E  HHA014E 
100A HNB100H
20A HDA018E  HHA018E 
125A HNB125H
25A HDA023E  HHA023E 
160A HNB160H
32A HDA030E  HHA030E 
200A HNB200H
40A HDA038Z HHA038Z
250A HNB250H
50A HDA048Z HHA048Z

 &  - Please see left hand page for corresponding numbers. 63A HDA061Z HHA061Z
80A HDA078Z HHA078Z
100A HDA098Z HHA098Z
125A HDA123Z HHA123Z

 MCCBs - 125A 25kA Triple Pole Adjustable Thermal


18kA Adjustable 25kA Adjustable
Thermal Thermal
Rating. 0.63, 0.8, 1 x In 0.63, 0.8, 1 x In
25A HDA025U HHA025U
40A HDA040U HHA040U
63A HDA063U HHA063U
80A HDA080U HHA080U
100A HDA100U HHA100U
125A HDA125U HHA125U

Data is subject to errors and technical modifications.  New. 33


Panelboards 800A Rated
800A Incoming 125A/250A Outgoing, Accessories

Invicta 3 Panelboards (800A Incoming, 125A Outgoing)

Characteristics
- Comprises of IP3XD enclosure, pan assembly, neutral bar and earth bar
- Conforms to BS EN 61439-2. InA = 800A, Inc = 125A/250A, Icc = 50kA.
- Supplied without incoming kit, one of the incomer kits listed below must be used.
- Form 3B type 2 using outgoing terminal shield (form 3A without terminal shield).
- Removable gland plates are provided top and bottom for ease of installation.
- MCCB: 800A 3 or 4 pole.
- Incoming cable lugs 44mm pad with 2 x M12 hexagonal bolt.
- For dimensions see page 79.
Cable Capacity Incomers & Outgoers
Commercial
Distribution

Incomers: 800A MCCB: 2 x 300mm²,


JHF812B
Outgoers: Single pole up to 125A - 70mm² flexible, 95mm² solid, Triple pole up to 250A - 150mm² flexible.
Outgoing MCCBs
- Adjustable thermal options on triple pole.

Cat ref. Cat ref.


Description Plain Door Glazed door
12 Triple Pole Ways 800A Panelboard JHF812B JHF812BG
18 Triple Pole Ways 800A Panelboard JHF818B JHF818BG

Invicta 3 Panelboards (800A Incoming 125A / 250A Outgoing)

- These boards will accept two MCCB frame sizes: 125A frame: 16 - 125A, 250A frame: 100 - 250A.
- InA = 800A, Inc = 250A, Icc = 50kA.

Cat ref. Cat ref.


Description Plain Door Glazed door
8 Triple Pole Ways 800A Panelboard (2 x 250A  + 6 x 125A ) JHF80206B JHF80206BG
8 Triple Pole Ways 800A Panelboard (4 x 250A  +4 x 125A ) JHF80404B JHF80404BG
12 Triple Pole Ways 800A Panelboard (2 x 250A  + 10 x 125A ) JHF80210B JHF80210BG
12 Triple Pole Ways 800A Panelboard (4 x 250A  + 8 x 125A ) JHF80408B JHF80408BG
JHF80408B
18 Triple Pole Ways 800A Panelboard (4 x 250A  + 14 x 125A ) JHF80414B JHF80414BG
18 Triple Pole Ways 800A Panelboard (6 x 250A  + 12 x 125A ) JHF80612B JHF80612BG

MCCB Incomer Kits for 800A Panelboards

Description Palm lug max (width) Cat ref.


800A 3 Pole MCCB Incomer Auto 50kA 60mm JHF883BM
800A 4 Pole MCCB Incomer Auto 50kA 60mm JHF884BM

Accessories

Description Cat ref.


Locking Kit for MCCB Incoming Device (All Ratings) HXD039H
Allen Key Set JF296A
End Plate for Invicta 3 800A Range JFPLATE
Key Lock with One Key JK222PK
x125 Frame 1 Pole Blank (3x blanks required per triple pole) JN001BP
x250 Frame 3 Pole Blank (1x blank required per triple pole) JF003BP
Outgoer Locking Kit (fits to toggle for up to 3 padlocks max ø 8mm²) HXA039H
JN001BP

Surge Protection SPD Options

Note:
- JF801SPD can not be fitted in JH* Panelboards
- Please contact our tailored solutions team for factory fitted SPD options - 01952 675 689

34 Data is subject to errors and technical modifications.  New.


Panelboards 800A Rated
DIN Extension Boxes, Cable Spreader Boxes, Meter Pack

DIN Rail Extension Boxes for 800A Panelboards

- DIN rail extension boxes have plain or glazed doors and DIN rail chassis.
- Cable spreader boxes are used for additional cabling space therefore do not require doors. Optional door kits are available.
- Supplied with DIN rail and without gland plate (utilise removed gland plate from panelboard).
- For dimensions see page 78.

Cat ref. Cat ref.


Description Plain Door Glazed door
1 Row 34 Mod (300mm Height) JF801E JF801EG
2 Row 68 Mod (450mm Height) JF803E JF803EG

Commercial
Distribution
Cable Spreader Boxes for 800A Panelboards

- Supplied without gland plates (utilise removed gland plate from panelboard).
- Cable spreader boxes are used for additional cabling space therefore do not require doors. Optional door kits are available.
- For dimensions see page 78.

Description Cat ref.


Small (300mm Height) (Door not included) JF805E
Large (450mm Height) (Door not included) JF806E
Small Cable Spreader Box Door Kit JF805DK
Large Cable Spreader Box Door Kit JF806DK

Meter Pack for 800A Panelboards

- These meter packs fit directly into the main panelboard. Spreader box required to mount CT’s.
- For Meter Enclosures see page 39.

Description Cat ref.


MID Multifunction Meter Pack 800A MID Pulsed & Modbus JF803MID 

Outgoing Devices Thermal Magnetic - See page 64 - 66 for more info.

 MCCBs x250 40kA - Triple Pole  MCCBs - 125A 18kA Single Pole
Adjustable Thermal & Rating. 18kA Fixed Thermal 25kA Fixed Thermal
Rating. Magnetic
16A HDA014E  HHA014E 
100A HNB100H
20A HDA018E  HHA018E 
125A HNB125H
25A HDA023E  HHA023E 
160A HNB160H
32A HDA030E  HHA030E 
200A HNB200H
40A HDA038Z HHA038Z
250A HNB250H
50A HDA048Z HHA048Z
63A HDA061Z HHA061Z
80A HDA078Z HHA078Z
100A HDA098Z HHA098Z
125A HDA123Z HHA123Z

 MCCBs - 125A 25kA Triple Pole Adjustable Thermal


18kA Adjustable 25kA Adjustable
Thermal Thermal
Rating. 0.63, 0.8, 1 x In 0.63, 0.8, 1 x In
25A HDA025U HHA025U
40A HDA040U HHA040U
63A HDA063U HHA063U
80A HDA080U HHA080U
100A HDA100U HHA100U
125A HDA125U HHA125U

Data is subject to errors and technical modifications.  New. 35


Metering
Panelboard Meter Enclosures

Meter Enclosures for JF Panelboards

- Blanking plates not included (utilise removed blanking plate from panelboard).
- When selecting outgoing metering, the panelboard metering system is easily configured by selecting a side, top or
combination that matches the panelboard (e.g. for the JF406B/G board, you can select a JF12504SM side mounted meter
enclosure that can house 4 ECM01 panel mounted meters). When using both side and top/bottom meter enclosures, corner
filler enclosures are available.
- For help choosing your metering solution see the Method Chart on page 79.
- Please contact us for any non-standard requirements or assembly.
- For dimensions see page 81.
Commercial
Distribution

Suitable for board type / Description Spaces for Meters Cat ref.
JF12504SM JF450CF
Side Meter Enclosures
6/8 Way JF Board 4 x Din 96 Cut-Outs JF12504SM
12 Way JF Board 6 x Din 96 Cut-Outs JF14006SM
16 Way JF Board 8 x Din 96 Cut-Outs JF15508SM
18 Way JF Board 9 x Din 96 Cut-Outs JF17009SM
Blanking Plate DIN 96  - JF96BP

JF4508TM Top/Bottom Meter Enclosures


300mm Enclosure 4 x DIN 96 Cut-Outs JF3004TM
450mm Enclosure 8 x DIN 96 Cut-Outs JF4508TM
Blanking Plate DIN 96 - JF96BP

Corner Filler Enclosures


300mm Corner Filler Side Enclosure - JF300CF
450mm Corner Filler Side Enclosure - JF450CF

Side/Top/Bottom Meter Enclosures for JN Panelboards

Characteristics
- Blanking plates not included.
- For meters see page 39.
- For dimensions see page 81.

Suitable for board type / Description Apertures for Meters Cat ref.
Side Meter Enclosures
4 Way JN Board 2 x DIN 96 Cut-Outs JN9502SM
JN11004SM 6/8 Way JN Board 4 x DIN 96 Cut-Outs JN11004SM
12 Way JN Board 6 x DIN 96 Cut-Outs JN12506SM
16 Way JN Board 8 x DIN 96 Cut-Outs JN15508SM

Top/Bottom Meter Enclosures


300mm Enclosure 3 x DIN 96 Cut-Outs JN3003TM
450mm Enclosure 6 x DIN 96 Cut-Outs JN4506TM
JN3003TM
Blanking Plate - JF96BP

Corner Filler Enclosures


300mm Corner Filler Side Enclosure JN - JN300CF
450mm Corner Filler Side Enclosure JN - JN450CF

36 Data is subject to errors and technical modifications.  New.


Metering
DIN Rail Mounted Meters

Single Phase Direct Connect kWh Meters - MID Approved

Description:
- MID approved meter range (except EC…180T)
- A range of both direct connect and CT supplied din rail mounted meters
Characteristics:
- CT supplied meters compatible with 1 A / 5A CT’s (not suitable for use with cables / ct’s from page 38)
- Choice of communication options – pulse output kWh, Modbus or Mbus

Width

Commercial
Description (1 Mod =17.5mm) Cat ref.

Distribution
40A kWh Meters ECN140D

1Ph kWh Meter Direct 40A Pulsed Output 1M 1 Mod ECN140D 


1Ph kWh Meter Direct 40A 1M Pulsed Output MID 1 Mod ECP140D 
1Ph kWh Meter Direct 40A 1M MBUS MID 1 Mod ECM140D 
1Ph kWh Meter Direct 40A 1M MODBUS MID 1 Mod ECR140D 

3 x 80A kWh Meters - Not MID Approved


1Ph kWh Meter Direct 3x80A 4M Pulsed Output 4 Mod ECP180T 
1Ph kWh Meter Direct 3x80A 4M MBUS 4 Mod ECM180T 
1Ph kWh Meter Direct 3x80A 4M MODBUS 4 Mod ECR180T 

ECA180T
80A kWh Meters
1Ph kWh Meter Direct 80A 2M Pulsed Output MID 2 Mod ECP180D 
1Ph kWh Meter Direct 80A 2M MBUS MID 2 Mod ECM180D 
1Ph kWh Meter Direct 80A 2M MODBUS MID 2 Mod ECR180D 

Three Phase Direct Connect kWh Meters - MID Approved

Width
Description (1 Mod =17.5mm) Cat ref.
80A kWh Meters
3Ph kWh Meter Direct 80A 4M MID 4 Mod ECP380D 
3Ph kWh Meter Direct 80A 4M MBUS MID 4 Mod ECM380D 
3Ph kWh Meter Direct 80A 4M MODBUS MID 4 Mod ECR380D 
ECM310D
125A kWh Meters
3Ph kWh Meter Direct 125A 6M S0 MID 6 Mod ECP310D 
3Ph kWh Meter Direct 125A 6M MBUS MID 6 Mod ECM310D 
3Ph kWh Meter Direct 125A 6M MODBUS MID 6 Mod ECR310D 

Three Phase CT Fed kWh Meters

Width
Description (1 Mod =17.5mm) Cat ref.
1-5A kWh Meters
3Ph kWh Meter via CT 1-5A 4M Pulsed Output MID 4 Mod ECP300C 
3Ph kWh Meter via CT 1-5A 4M MBUS MID 4 Mod ECM300C 
3Ph kWh Meter via CT 1-5A 4M MODBUS MID 4 Mod ECR300C 

ECM300C

Data is subject to errors and technical modifications.  New. 37


Metering
Meter Cables & Connection

Panel Mounted DIN 96 x 96 Meters

- Panel mounted meters suitable for use with Hager MCCB Panelboard enclosures
- DIN 96 x 96 mounting
- Cables not supplied with meters
- CT, CT cable & voltage reference cables to be selected from 38 - 39

Description Cat ref.


Panel Mounted Multifunction Meter Pulse/Modbus ECM01
Hager by Rayleigh MID Panel Mounted Meter Pulse/Modbus HGR96EWC 
Hager by Rayleigh MID Panel Mounted Meter Mbus HGR96EWMB 
Commercial
Distribution

HGR96EWC

DIN Rail Mounted Meters

- Cables & CT supplied separately


- CT, CT Cable & voltage reference cables to be selected from this page.

Description Cat ref.


DIN Rail Mounted Plug-in Meter CT Fed JKM01
DIN Rail Mounted Plug-in Meter CT Fed - Dual Channel Input JKM02
Hager by Rayleigh MID DIN Rail Mounted Plug-in Meter CT Fed Pulse/Modbus HGR41EWC 

HGR41EWC

Meter Cables

Cat ref. Meter to Cat ref. Voltage


Description Meter Supply Cable Supply Cable
Meter Supply Cable - PVC
1m - Voltage Supply Cable with Fuse Carrier (For JF Meter Enclosures) - JF130VMF
1m - Voltage Supply Cable with Fuse Carrier (For JN Meter Enclosures) - JN130VMF

PGMF300 0.15m - Hi Flex Supply Cable PGMFT150 -


0.30m - Hi Flex Supply Cable PGMFT300 PGMF300
0.50m - Hi Flex Supply Cable PGMFT500 PGMF500
1.00m - Hi Flex Supply Cable PGMFT1000 PGMF1000
1.30m - Hi Flex Supply Cable PGMFT1300 PGMF1300
2.00m - Hi Flex Supply Cable PGMFT2000 PGMF2000
3.00m - Hi Flex Supply Cable PGMFT3000 PGMF3000

PGMFT300

RJ45 Connection Cable

Description Cat ref.


0.30m - RJ45 Connector Cable 67 7003 PGRJ300
0.50m - RJ45 Connector Cable 67 L7005 LSZH PGRJ500
1.00m - RJ45 Connector Cable 67 L7005 LSZH PGRJ1000

PGRJ1000 1.50m - RJ45 Connector Cable 67 L7005 LSZH PGRJ1500


2.00m - RJ45 Connector Cable 67 L7005 LSZH PGRJ2000
3.00m - RJ45 Connector Cable 67 L7005 LSZH PGRJ23000

38 Data is subject to errors and technical modifications.  New.


Metering
Metering Accessories

3 Phase CT Splitter Box

- This 3 Phase current transformer splitter box allows the separate monitoring of each phase of a three phase current
transformer on individual energy meters.

Description Cat ref. JFS03


3 Phase CT Splitter Box JFS03

Plug-in CTs

Commercial
Distribution
- No leads supplied with these CTs (RJ45 connection cable)
- For technical data see page 86.
- Suitable for use with ECM01, JKM01, JKM02 & Hager by Rayleigh meters.

Cat ref. Cat ref. Cat ref.


Description 125A 250A 400A
60A 3 Phase CT EC1260CT EC2560CT -
100A 3 Phase CT EC12100CT EC25100CT -
125A 3 Phase CT EC12125CT EC25125CT - EC1260CT

160A 3 Phase CT EC12160CT EC25160CT -


200A 3 Phase CT - EC25200CT -
250A 3 Phase CT - EC25250CT EC40250CT
400A 3 Phase CT - - EC40400CT
630A 3 Phase CT - - EC40630CT
800A 3 Phase CT - - EC80800CT

Converter

Description Cat ref.


Standard CT to plug in adapter JFA03

JFA03

Accessories

- Supply voltage connector plugs are for making up your own power cable looms.

Description Cat ref.


Supply Voltage Connector Plugs Voltage IN (Male) Connector PG9523MALE
JFT03 PG9522FEMALE
Supply Voltage Connector Plugs Voltage OUT (Female) connector PG9522FEMALE
CT Output and RJ45 Lead Tester JFT03

Data is subject to errors and technical modifications.  New. 39


Fuse Combination Switches
Fuse Combination Switches 20-800A

Fuse Combination Switches 20 - 800A

Characteristics
- Provides individual protection and control of circuits.
- Enclosures up to 100A have been designed to provide adequate cabling space without the need for additional cable
spreader boxes.
- Operation of the device is through a door mounted rotary handle which is mechanically interlocked to prevent access to live
conductors when the switch is in the on position. The handle is padlockable in the off position.
- All versions will accept standard BS 88 fuse links and can be converted to switch disconnector by fitting copper links.
Utilisation category
- AC22B - 630 - 800A
- AC23A - 20 - 630A
Commercial

Product features
Distribution

JF12504SM - Conforms to: BS EN 60947-3


- Rated IP31.
Note: Maximum rated fuse links are fitted in all fuse combination switches.
Note: Copper links for conversion to isolating switches
- For dimensions see page 88.
- For technical information see page 89.

Cat ref.
Cable extension
Description Cat ref. boxes if required
Fuse Combination Switches Single Pole & Switched Neutral
20A Fuse Combination Switch SP&SN JFB202U -
32A Fuse Combination Switch SP&SN JFB203U -
63A Fuse Combination Switch SP&SN JFD206U -
JFG416U
100A Fuse Combination Switch SP&SN JFE210U JZA701

Cable Capacity
20A = 16mm² Fuse Combination Switches Triple Pole & Neutral
32A = 16mm²
63A = 25mm² 20A Fuse Combination Switch TP&N JFB302U -
100A = 95mm² = M8 Lug 32A Fuse Combination Switch TP&N JFB303U -
125A = 95mm² = M8 Lug
63A Fuse Combination Switch TP&N JFD306U -
160A = 95mm² = M8 Lug
200A = 240mm² = M10 Lug 100A Fuse Combination Switch TP&N JFE310U JZA701
250A = 240mm² = M10 Lug 125A Fuse Combination Switch TP&N JFG312U JZA701
315A = 240mm² = M10 Lug
400A = 240mm² = M10 Lug 160A Fuse Combination Switch TP&N JFG316U JZA701
630A = 2 x 300mm² = M12 Lug 200A Fuse Combination Switch TP&N JFG320U JZA701
800A = 2 x 300mm² = M12 Lug
250A Fuse Combination Switch TP&N JFG325U JZA701
Spare Fuse types 315A Fuse Combination Switch TP&N JFH331U JZA702
20A = NIT20 400A Fuse Combination Switch TP&N JFH340U JZA702
32A = NIT32
63A = TIS63 630A Fuse Combination Switch TP&N JFI363U JZA703
100A = TCP100 800A Fuse Combination Switch TP&N JFI380U JZA703
125A = TF125
160A = TF160
200A = TF200 Fuse Combination Switches Triple Pole & Switched Neutral
250A = TKF250
315A = TKF315 20A Fuse Combination Switch TP&SN JFB402U -
400A = TMF400 32A Fuse Combination Switch TP&SN JFB403U -
630A = TTM630
800A = TLM800 63A Fuse Combination Switch TP&SN JFD406U -
100A Fuse Combination Switch TP&SN JFE410U JZA701
125A Fuse Combination Switch TP&SN JFG412U JZA701
160A Fuse Combination Switch TP&SN JFG416U JZA701
200A Fuse Combination Switch TP&SN JFG420U JZA701
250A Fuse Combination Switch TP&SN JFG425U JZA701
315A Fuse Combination Switch TP&SN JFH431U JZA702
400A Fuse Combination Switch TP&SN JFH440U JZA702
630A Fuse Combination Switch TP&SN JFI463U JZA703
800A Fuse Combination Switch TP&SN JFI480U JZA703

Copper Links
63A JC60L -
100A JC10L -
125 / 200A JC20L -
315 / 400A JC40L -
630A JC63L -

40 Data is subject to errors and technical modifications.  New.


Switch Fuses
Switch Fuses, Switch Disconnectors 20-800A

Switch Fuses

Characteristics
- Amendment 3 compliant switch fuses have a full metal construction to comply with BS 7671, when used in residential
applications
- For dimensions see page 91.

Cat ref.
Description Cat ref. Amd 3 door
4 Module Metal Unit 1 x 100A Isolator, AC22A. Connection Capacity: 50mm² Rigid IU44-16 IU44-16D
Conductor, 35mm² Flexible Conductor, 1 x 63A Fuse
4 Module Metal Unit 1 x 100A Isolator, AC22A. Connection Capacity: 50mm² Rigid IU44-18 IU44-18D

Commercial
Distribution
Conductor, 35mm² Flexible Conductor, 1 x 80A Fuse IU44-11
4 Module Metal Unit 1 x 100A Isolator, AC22A. Connection Capacity: 50mm² Rigid IU44-11 IU44-11D
Conductor, 35mm² Flexible Conductor, 1 x 100A Fuse

Switch Disconnectors 20-800A

Characteristics
- Designed to provide individual isolation of circuits up to 800A.
- Provides adequate cabling space without the need for additional cable spreader boxes.
- Operation of the device is through a door mounted rotary handle which is mechanically interlocked to prevent access to live
conductors when the switch is in the on position. The handle is padlockable in the off position.
Utilisation category
- AC-21, AC-22 (page 92)
Product features
- Conforms to: BS EN 60947-3
- IP rating: IP31.
- For technical information see page 88 - 92.
JAB402B
Cat ref.
Cable extension Cable Capacity
Rating Cat ref. boxes if required 20A = 16mm²
Switch Disconnectors Triple Pole & Neutral 32A = 16mm²
63A = 25mm²
160A JAC316 JZA700 100A = 95mm² = M8 Lug
200A JAE320 JZA701 125A = 95mm² = M8 Lug
160A = 95mm² = M8 Lug
250A JAE325 JZA701
200A = 240mm² = M10 Lug
315A JAG331 JZA701 250A = 240mm² = M10 Lug
400A JAG340 JZA701 315A = 240mm² = M10 Lug
400A = 240mm² = M10 Lug
630A JAH363 JZA702 630A = 2 x 300mm² = M12 Lug
800A JAH380 JZA702 800A = 2 x 300mm² = M12 Lug

Switch Disconnectors Triple Pole & Switched Neutral


20A JAB402B -
32A JAB403B -
63A JAB406B -
100A JAB410B -
125A JAC412B -
160A JAC416 JZA700
200A JAE420 JZA701
250A JAE425 JZA701
315A JAG431 JZA701
400A JAG440 JZA701
630A JAH463 JZA702
800A JAH480 JZA702

Data is subject to errors and technical modifications.  New. 41


Switch Disconnectors
IP65 Switch Disconnectors, Auxiliary Changeover Contacts

IP65 Switch Disconnectors

- A range of enclosed switch disconnectors to IP65 for individual isolation.


- The devices are padlockable in three positions and offer plenty of cabling space. Clip on auxiliary contacts can be fitted
retrospectively.
Product features
- Conforms to: BS EN 60947-3.
- IP65 to BS EN 60529.
Range: TPN 10, 16, 25, 40, 63 & 80A.
Utilisation category
- AC- 21.
- AC- 22.
Commercial

- For technical information see page 91.


Distribution

JG01S

In AC 21 In AC 22 Cat ref.
Cable Capacity
20 - 40A = 16mm² 20A 10A JG00S
63 - 100A = 35mm² 25A 16A JG01S
40A 25A JG02S
63A 40A JG03S
80A 63A JG04S
100A 80A JG05S

Auxiliary Changeover Contacts

Description Cat ref.


1 Normally Open / 1 Normally Closed Auxiliary Contacts 16-80A JG10A
2 Normally Open / 2 Normally Closed Auxiliary Contacts 16-80A JG20A

IP65 Switch Disconnectors - DC

- Used in applications such as photovoltaic installations where they isolate the incoming side of the inverter.
- They are supplied in grey with a black handle so that it is easy to distinguish them from the yellow/red A.C. switches used on
the outgoing side of the inverter.
Product Features
- Conforms to: BS EN 60947-3 IP65 to BS EN 60529.
- An interlock ensures that the cover cannot be removed in both the ON and PADLOCKED OFF positions.

Rating Utilisation Category Cat ref.


12A at 500V DC-21B, 10A at 600V DC-21B DC-21B JG416DC
JG440DC 8A at 800V DC-21B, 6A at 440V DC-22B
16A at 500V DC-21B, 12A at 600V DC-21B DC-21B JG425DC
Cable Capacity 10A at 800V DC-21B, 6A at 440V DC-22B DC-22B
20 - 40A = 16mm² 20A at 500V DC-21B, 16A at 600V DC-21B DC-21B JG440DC
63 - 100A = 35mm² 12A at 800V DC-21B, 16A at 440V DC-22B DC-22B

D
Enclosed ATS

Characteristics
- A range of enclosed Automatic Transfer Switches in IP30 rated enclosure. Available in ratings 40A – 125A.
- Conforming to BS EN 60947-3 & IEC 60947-6-1
- Overvoltage Category II
- Pollution degree 3
- Electromagnetic compatibility – Environment category – A
- Rated voltage of assembly: Un = 415V A.C. 50Hz
- Rated operational voltage of assembly: Ue = 415V A.C. 50Hz
- Rated insulation voltage of assembly: Ui = 690V A.C. 50Hz (Power Circuits) / 300V (Control Circuits)
- Rated impulse voltage of assembly: Uimp = 6kV (Power Circuits) / 2.5kV (Control Circuits)
- Rated current of assembly: Ina / Inc = 125A max
Interior diagram JK***ATS - Rated peak withstand current: Ipk = 105kA conditional (table 7, n = 2.1)
- Rated short-time withstand current: Icw = 7kA / 0.3 secs
: Icw = 4kA / 1.0 sec
- For dimensions see page 80.

Description Cat ref.


40A Enclosed ATS unit JK140ATS 
63A Enclosed ATS unit JK163ATS 
80A Enclosed ATS unit JK180ATS 
100A Enclosed ATS unit JK1100ATS 
125A Enclosed ATS unit JK1125ATS 

42 Data is subject to errors and technical modifications.  New.


Enclosed MCCBs
Enclosed MCCBs

Enclosed MCCBs

- The devices are mounted in IP31 enclosures, with removable cable entry plates located on the top and bottom.
- Single & triple pole devices are equipped with fully rated neutral links.
Non-Auto MCCB
- Triple pole: 125A - 250A - 400A - 630A.
- Four pole: 125A - 250A - 400A - 630A.
Specification
- Conforms to BS EN 61439-2.
Cable Capacity
- 63 - 125A: Flexible cable: min 6mm², max 70mm², Rigid cable: min 6mm², max 95mm².
- RCD add-on adjustable from 0.03A, 0.1A, 0.3A, 1A, 3A, 6A.

Commercial
- Time delay - Instantaneous, 60ms, 150ms, 300ms, 500ms, 1s.

Distribution
- For technical details and dimensions see page 94. JG38BR

Description Icu Cat ref.


Enclosed MCCBs Single Pole & Neutral
63A Single Pole Enclosed MCCB 18kA JG25BM
100A Single Pole Enclosed MCCB 18kA JG28BM
125A Single Pole Enclosed MCCB 18kA JG31BM

Enclosed MCCBs Triple Pole and Neutral (63-125A)


63A 3-Pole Enclosed MCCB (40A-50A 63A) 18kA JG26BM
100A 3-Pole Enclosed MCCB (63A-80A-100A) 18kA JG29BM
125A 3-Pole Enclosed MCCB (80A-100-125A) 18kA JG32BM
JG41BM
125A 3-Pole Enclosed Non-Auto MCCB Non-Auto JG34BS

Enclosed MCCBs Triple Pole and Neutral (160-250A)


160A 3-Pole Enclosed MCCB (Adjustable) 25kA JG36BM
250A 3-Pole Enclosed MCCB (Adjustable) 25kA JG40BM
250A 3-Pole Enclosed Non-Auto MCCB Non-Auto JG42BS

Enclosed MCCBs Triple Pole and Neutral (400-630A)


400A 3-Pole Enclosed MCCB (Adjustable) 50kA JG44BM
400A 3-Pole Enclosed Non-Auto MCCB Non-Auto JG46BS
630A 3-Pole Enclosed MCCB (Adjustable) 50kA JG48BM
630A 3-Pole Enclosed Non-Auto MCCB Non-Auto JG50BS
JG45BM

Enclosed MCCBs Four Pole (63-125A)


63A 4-Pole Enclosed MCCB (Adjustable) 18kA JG27BM
63A 4-Pole Enclosed MCCB (Adjustable) + RCD Add-on 18kA JG27BR
100A 4-Pole Enclosed MCCB (Adjustable) 18kA JG30BM
100A 4-Pole Enclosed MCCB (Adjustable) + RCD Add-on 18kA JG30BR
125A 4-Pole Enclosed MCCB (Adjustable) 18kA JG33BM
125A 4-Pole Enclosed Non-Auto MCCB Non-Auto JG35BS

Enclosed MCCBs Four Pole (160-250A)


160A 4-Pole Enclosed MCCB (Adjustable) 25kA JG37BM
160A 4-Pole Enclosed MCCB RCD Add-on 25kA JG37BR
200A 4-Pole Enclosed MCCB RCD Add-on 25kA JG38BR
250A 4-Pole Enclosed MCCB (Adjustable) 25kA JG41BM
250A 4-Pole Enclosed Non-Auto MCCB Non-Auto JG43BS

Enclosed MCCBs Four Pole (400-630A)


400A 4-Pole Enclosed MCCB (Adjustable) 50kA JG45BM
375A 4-Pole Enclosed MCCB RCD Add-on 50kA JG45BR
400A 4-Pole Enclosed Non-Auto MCCB Non-Auto JG47BS
630A 4-Pole Enclosed MCCB (Adjustable) 50kA JG49BM
630A 4-Pole Enclosed Non-Auto MCCB Non-Auto JG51BS

Data is subject to errors and technical modifications.  New. 43


MCBs
Single & Triple Pole MCBs

MCBs 10kA

Characteristics
- Provides protection against short circuits, protection against overload current, control, isolation, trip free mechanism.
Isolation
- The state of isolation is clearly indicated by the “OFF” mechanical position on the toggle with the green colour.
- Connection capacity: 25mm² flexible conductor, 35mm² rigid conductor.
- Conforms to: BS EN 60898-2 (10kA), BS EN 60947-2 (15kA).

Width Cat ref. Cat ref. Cat ref.


Rating (1 Mod = 17.5mm) “B” Curve “C” Curve “D” Curve
Single Pole MCBs
Commercial
Distribution

NCN116A 0.5A 1 Mod - NCN100A NDN100A


1A 1 Mod - NCN101A NDN101A
2A 1 Mod - NCN102A NDN102A
3A 1 Mod - NCN103A NDN103A
4A 1 Mod - NCN104A NDN104A
6A 1 Mod NBN106A NCN106A NDN106A
10A 1 Mod NBN110A NCN110A NDN110A
16A 1 Mod NBN116A NCN116A NDN116A
20A 1 Mod NBN120A NCN120A NDN120A
25A 1 Mod NBN125A NCN125A NDN125A
32A 1 Mod NBN132A NCN132A NDN132A
40A 1 Mod NBN140A NCN140A NDN140A
50A 1 Mod NBN150A NCN150A NDN150A
63A 1 Mod NBN163A NCN163A NDN163A

Triple Pole MCBs


0.5A 3 Mod - NCN300A NDN300A
1A 3 Mod - NCN301A NDN301A
2A 3 Mod - NCN302A NDN302A
3A 3 Mod - NCN303A NDN303A
4A 3 Mod - NCN304A NDN304A
6A 3 Mod NBN306A NCN306A NDN306A
10A 3 Mod NBN310A NCN310A NDN310A
16A 3 Mod NBN316A NCN316A NDN316A
20A 3 Mod NBN320A NCN320A NDN320A
25A 3 Mod NBN325A NCN325A NDN325A
32A 3 Mod NBN332A NCN332A NDN332A
40A 3 Mod NBN340A NCN340A NDN340A
50A 3 Mod NBN350A NCN350A NDN350A
63A 3 Mod NBN363A NCN363A NDN363A

44 Data is subject to errors and technical modifications.  New.


MCBs
Double & Four Pole MCBs

MCBs 10kA (Continued)

Width Cat ref. Cat ref. Cat ref.


Rating (1 = 17.5mm) “B” Curve “C” Curve “D” Curve
Double Pole MCBs
0.5A 2 Mod - NCN200A NDN200A
1A 2 Mod - NCN201A NDN201A
2A 2 Mod - NCN202A NDN202A
3A 2 Mod - NCN203A -
4A 2 Mod - NCN204A NDN204A

Commercial
Distribution
6A 2 Mod NBN206A NCN206A NDN206A NCN316A
10A 2 Mod NBN210A NCN210A NDN210A
16A 2 Mod NBN216A NCN216A NDN216A
20A 2 Mod NBN220A NCN220A NDN220A
25A 2 Mod NBN225A NCN225A NDN225A
32A 2 Mod NBN232A NCN232A NDN232A
40A 2 Mod NBN240A NCN240A NDN240A
50A 2 Mod NBN250A NCN250A NDN250A
63A 2 Mod NBN263A NCN263A NDN263A

Four Pole MCBs


0.5A 4 Mod - NCN400A NDN400A NCN416A
1A 4 Mod - NCN401A NDN401A
2A 4 Mod - NCN402A NDN402A
3A 4 Mod - NCN403A NDN403A
4A 4 Mod - NCN404A NDN404A
6A 4 Mod NBN406A NCN406A NDN406A
10A 4 Mod NBN410A NCN410A NDN410A
16A 4 Mod NBN416A NCN416A NDN416A
20A 4 Mod NBN420A NCN420A NDN420A
25A 4 Mod NBN425A NCN425A NDN425A
32A 4 Mod NBN432A NCN432A NDN432A
40A 4 Mod NBN440A NCN440A NDN440A
50A 4 Mod NBN450A NCN450A NDN450A
63A 4 Mod NBN463A NCN463A NDN463A

Accessories

Description Cat ref.


Padlockable Locking Kit for MCB, RCCB & RCBO MZN175
Padlock with 2 keys 3/4” JK25A

MZN175
(device & padlock
not included)

Data is subject to errors and technical modifications.  New. 45


RCBOs
Single Pole, Single Module

RCBOs - Single Pole - 10kA B & C Curve Type A

Characteristics
- Compact protection devices which combine the overcurrent functions of an MCB with the earth fault functions of an RCCB
in a single unit.
- These devices are single pole & solid neutral.
- Locking kit = Cat ref.: MZN175.
Technical Data
- Conforms to IEC 61009-1, IEC 61009-2-2, EN 61009-1.
Sensitivities (fixed)
- 10mA, 30mA & 100mA.
- Flying neutral lead: 700mm.
Commercial

- Terminal Capacities, 25mm² rigid, 16mm² flexible.


Distribution

ACB125 Operating Voltage


- 230V A.C.

Width B Curve C Curve


Current rating (1 Mod = 17.5mm) Cat ref. Cat ref.
Sensitivity 30mA (10kA) B / C Curve, Type A
6A RCBO Single Pole 30mA 10kA 1 Mod ADA106U ADA156U
10A RCBO Single Pole 30mA 10kA 1 Mod ADA110U ADA160U
16A RCBO Single Pole 30mA 10kA 1 Mod ADA116U ADA166U
20A RCBO Single Pole 30mA 10kA 1 Mod ADA120U ADA170U
25A RCBO Single Pole 30mA 10kA 1 Mod ADA125U ADA175U
32A RCBO Single Pole 30mA 10kA 1 Mod ADA132U ADA182U
ADB106
40A RCBO Single Pole 30mA 10kA 1 Mod ADA140U ADA190U
45A RCBO Single Pole 30mA 10kA 1 Mod ADA145U ADA195U

Sensitivity 10mA (10kA) B / C Curve, Type A


6A RCBO Single Pole 10mA 10kA 1 Mod ACA106U ACA156U
16A RCBO Single Pole 10mA 10kA 1 Mod ACA116U ACA166U
25A RCBO Single Pole 10mA 10kA 1 Mod ACA125U ACA175U
32A RCBO Single Pole 10mA 10kA 1 Mod ACA132U ACC182U

Sensitivity 100mA (10kA) C Curve, Type A


10A RCBO Single Pole 100mA 10kA 1 Mod - AEC110
AEC132
16A RCBO Single Pole 100mA 10kA 1 Mod - AEC116
20A RCBO Single Pole 100mA 10kA 1 Mod - AEC120
25A RCBO Single Pole 100mA 10kA 1 Mod - AEC125
32A RCBO Single Pole 100mA 10kA 1 Mod - AEC132

46 Data is subject to errors and technical modifications.  New.


Arc Fault Detection Devices
2 Pole, 10kA

Arc Fault Detection Devices

Characteristics:
- Protection device which combines an MCB with Arc Fault Detection.
- Conforms to BS EN 62606
- Current rating 6A - 40A 10kA
- Available in B & C curve
- Terminal Capacities, 25mm² rigid, 16mm² flexible.

Description Cat ref.


B Curve Arc Fault Detection Devices (10kA)

Commercial
Distribution
6A 2P Arc Fault Detection Device + MCB B Curve 10kA ARC506U  ARC506U
10A 2P Arc Fault Detection Device + MCB B Curve 10kA ARC510U 
13A 2P Arc Fault Detection Device + MCB B Curve 10kA ARC513U 
16A 2P Arc Fault Detection Device + MCB B Curve 10kA ARC516U 
20A 2P Arc Fault Detection Device + MCB B Curve 10kA ARC520U 
25A 2P Arc Fault Detection Device + MCB B Curve 10kA ARC525U 
32A 2P Arc Fault Detection Device + MCB B Curve 10kA ARC532U 

C Curve Arc Fault Detection Devices (10kA)


6A 2P Arc Fault Detection Device + MCB C Curve 10kA ARC556U 
10A 2P Arc Fault Detection Device + MCB C Curve 10kA ARC560U 
13A 2P Arc Fault Detection Device + MCB C Curve 10kA ARC563U  ARC540U

16A 2P Arc Fault Detection Device + MCB C Curve 10kA ARC566U 


20A 2P Arc Fault Detection Device + MCB C Curve 10kA ARC570U 
25A 2P Arc Fault Detection Device + MCB C Curve 10kA ARC575U 
32A 2P Arc Fault Detection Device + MCB C Curve 10kA ARC582U 

Data is subject to errors and technical modifications.  New. 47


RCBOs
Single Pole & Switched Neutral

RCBOs - Single Pole & Switched Neutral - 4.5kA C Curve

Characteristics
- Compact protection devices which provide MCB overcurrent protection and RCCB earth fault protection in a single unit.
- The device switches both the line and neutral conductors. All ratings have 30mA earth fault protection. The units feature
indicators which show whether a trip is due to an overcurrent or earth fault.
Technical Data
- Breaking capacity: 4.5kA.
- Conforms to EN 61009-1.
- Operating Voltage: 230V A.C. -15% +10% 50Hz.
- Mechanical life: 20,000 operations.
- Connection Capacity: Rigid conductor 25mm², Flexible conductor 16mm²
Commercial

- Note: Not for use in fixed busbar consumer units or distribution boards.
Distribution

ADC816F

Width C Curve
Current rating (1 Mod = 17.5mm) Cat ref.
6A RCBO SPSN 4.5kA 2 Mod ADC806F
10A RCBO SPSN 4.5kA 2 Mod ADC810F
16A RCBO SPSN 4.5kA 2 Mod ADC816F
20A RCBO SPSN 4.5kA 2 Mod ADC820F
25A RCBO SPSN 4.5kA 2 Mod ADC825F
32A RCBO SPSN 4.5kA 2 Mod ADC832F

RCBOs - Single Pole & Switched Neutral - 6kA B & C Curve Type A

Characteristics
- Compact protection devices which provide MCB overcurrent protection and RCCB earth fault protection in a single unit.
- The device switches both the line and neutral conductors. All ratings have 30mA earth fault protection. The units feature
indicators which show whether tripping is due to an overcurrent or earth fault.
Technical Data
- Breaking capacity: 6kA.
- Conforms to EN 61009-1.
- Operating Voltage: 230V A.C. +10%/-15% 50Hz.
- Mechanical life: 20,000 operations.
- Connection Capacity: Rigid conductor 25mm², Flexible conductor 16mm²
- Neutral connection flying lead - 700mm.
ADA990U
Width B Curve C Curve
Current rating (1 Mod = 17.5mm) Cat ref. Cat ref.
6A RCBO SPSN 6kA 2 Mod ADA906U ADA956U
10A RCBO SPSN 6kA 2 Mod ADA910U ADA960U
16A RCBO SPSN 6kA 2 Mod ADA916U ADA966U
20A RCBO SPSN 6kA 2 Mod ADA920U ADA970U
25A RCBO SPSN 6kA 2 Mod ADA925U ADA975U
32A RCBO SPSN 6kA 2 Mod ADA932U ADA982U
40A RCBO SPSN 6kA 2 Mod ADA940U ADA990U

Triple Pole RCD Add-On Blocks for MCB Devices

Characteristics
- Compatible with NBN, NCN & NDN range of MCB devices.
- Can be used in combination with any Hager 3 pole 10kA MCB up to 63A. Requires the use of the adjacent outgoing way.
- Type A RCD provides added protection against ‘pulsating D.C. current’
- 3 Phase earth leakage protection up to 63A.
- One module add-on block + MCB combinations suit all Hager distribution boards.
- BS EN 61009-1 Appendix G.
- For technical details see page 105.

Sensitivity
l∆n In A Width (35mm) Cat ref.
BD163T
30mA 63A 4 Mod BD163T
100mA 63A 4 Mod BE163T
300mA 63A 4 Mod BF163T

48 Data is subject to errors and technical modifications.  New.


RCCB Add-on Block for MCBs
RCCB Add-On Blocks, One Module Add-On Block

RCCB Add-On Blocks for MCB Devices

Characteristics
- Provide earth fault protection when associated with the 10kA (types NBN, NCN, NDN) range of MCBs.
- Designed to be fitted to the right hand side of 2 and 4 pole MCBs and the completed unit provides protection against
overload, short circuit & earth faults.
- Protection against nuisance tripping.
- All devices have a test facility.
- Note: Not for use in fixed busbar distribution boards.
Technical Data
- Nominal voltage 230 - 400V.
- Selective (time delay) versions are available in 100mA & 300mA.

Commercial
- Connection Capacity: 16mm² Flexible, 25mm² Rigid.

Distribution
- Conforms to BS EN 61009 Appendix G BD264

Sensitivity Width
l∆n In A (1 Mod = 17.5mm) Cat ref.
Double Pole RCCB Add-On Blocks
30mA 63A 2 Mod BD264
100mA 63A 2 Mod BE264
300mA 63A 2 Mod BF264
Time Delayed 100mA 63A 2 Mod BN264
Time Delayed 300mA 63A 2 Mod BP264 BD464

Four Pole RCCB Add-On Blocks


30mA 63A 3 Mod BD464
100mA 63A 3 Mod BE464
300mA 63A 3 Mod BF464
Time Delayed 100mA 63A 3 Mod BN464
Time Delayed 300mA 63A 3 Mod BP464

One Module Add-On Blocks for MCB Devices

Characteristics
- Compatible with NBN, NCN & NDN range of MCB devices.
- Can be used in combination with any Hager 3 pole 10kA MCB up to 63A. Requires the use of the adjacent outgoing way.
- Type A RCD provides added protection against ‘pulsating D.C. current’
- 3 Phase earth leakage protection up to 63A.
- One module add-on block + MCB combinations suit all Hager distribution boards.
- BS EN 61009-1 Appendix G.
- For technical details see page 105.

Sensitivity Width
l∆n In A (1 Mod = 17.5mm) Cat ref.
BD163T
30mA 63A 4 Mod BD163T
100mA 63A 4 Mod BE163T
300mA 63A 4 Mod BF163T

Data is subject to errors and technical modifications.  New. 49


11/2 Mod MCBs
80 - 125A 10kA C Curve, 15kA C & D Curve

MCBs 80 - 125A

- Suitable for isolation (according to BS EN 60947-2). The isolation of the circuit breakers is indicated by a green indicator on
the toggle.
Standards
- 10 kA: BS EN 60898-1, 10 kA BS EN 60947-2
- 15 kA: BS EN 60898-1, 15 kA BS EN 60947-2
- In 80 to 125A
Connection Capacity
- 35mm² flexible (50mm² possible with some cable pin lugs).
- 70mm² rigid.
Nominal Voltage
Commercial
Distribution

- 230/415 V A.C.
HMF199T
- Calibration setting: 30 °C
- (BS EN 60898-1)
- Insulation voltage: 500 V
Lockable Toggle
- MCB can be locked in “Off” position by the integrated locking facility on the toggle.
- This lock allows the insertion of a 2.5-3.5mm plastic cable tie where you can fit a warning card if necessary, allowing a safer
working environment.
- Compatible with RCD Add-On Blocks.

Width Cat ref. Cat ref. Cat ref.


Rating (1 = 17.5mm) 10kA C Curve 15kA C Curve 15kA D Curve
Single Pole MCBs
80A 1 ½ Mod HMF180T HMC180T HMD180T
100A 1 ½ Mod HMF190T HMC190T HMD190T
HMF299T
125A 1 ½ Mod HMF199T HMC199T HMD199T

Double Pole MCBs


80A 3 Mod HMF280T HMC280T HMD280T
100A 3 Mod HMF290T HMC290T HMD290T
125A 3 Mod HMF299T HMC299T HMD299T

Triple Pole MCBs


80A 4 ½ HMF380T HMC380T HMD380T
Mod
100A 4 ½ HMF390T HMC390T HMD390T
HMF399T Mod
125A 4 ½ HMF399T HMC399T HMD399T
Mod

Four Pole MCBs


80A 6 Mod HMF480T HMC480T HMD480T
100A 6 Mod HMF490T HMC490T HMD490T
125A 6 Mod HMF499T HMC499T HMD499T

HMF499T

Terminal Covers Screw Cap

Description Cat ref.


To cover connection terminals and screws of circuit breaker. MZN130
The screw covers can be sealed.

MZN130

Phase Barrier

Description Cat ref.


1 Set of 3 Phase Separators MZN131

MZN131

50 Data is subject to errors and technical modifications.  New.


RCCBs, SPSN MCBs
RCCB Add-On Blocks Type AC for MCBs 11/2 Mod

RCCB Add-On Blocks Type A.C. for HMF, HMC, HMD MCBs (Not suitable for Hybrid DBs)

Fixed
- High sensitivity 30 mA instantaneous, low sensitivity 300 mA instantaneous
Adjustable
- Sensitivity I∆n 0.3-0.5 - 1A
- Delay ∆t 0 - 60 -150 ms
Adjustable Blocks
- The setting is done by actuating dial on the front face. The setting dials are protected by a transparent sealable cover.
Disassembly
- The bistable latch (two positions) facilitate the assembly or disassembly by the bottom of the add-on block.
- These RCD add-on blocks exist in version AC. BDC280E

Commercial
- The earth fault is indicated when the handle is in the lower position (yellow colour). Test button for earth fault check.

Distribution
Connection Capacity
- 35mm² flexible connection
- 70mm² rigid connection.
Nominal voltage
- 2 pole 230V, three & four pole: 230 / 400V
- Test button: 230 / 400V.
- Conforms with BS EN 61009-1 appendix G.
- Conforms with BS EN 60947-2.

Sensitivity Width
Fixed / Adjustable l∆n In/A (1 = 17.5mm) Cat ref.
Double Pole RCD Add-On Blocks BDC380E
Fixed 30mA 125A 6 Mod BDC280E
Adjustable 0.3-0.5-1A 125A 6 Mod BTC280E
Time Delayed 0-60-150ms

Triple Pole RCD Add-On Blocks


Fixed 30mA 125A 6 Mod BDC380E
Adjustable 0.3-0.5-1A 125A 6 Mod BTC380E BDC480E
Time Delayed 0-60-150ms

Four Pole RCD Add-On Blocks


Fixed 30mA 125A 6 Mod BDC480E
Fixed 300mA 125A 6 Mod BFC480E
Adjustable 0.3-0.5-1A 125A 6 Mod BTC480E
Time Delayed 0-60-150ms

Single Pole & Switched Neutral MCB - 6kA C Curve

Description
- For protection and control of circuits against overloads and short circuits.
Technical Data
- Conforms to BS EN 60898
- Voltage rating - 230V A.C.
Connection Capacity
- Rigid 16mm²
- Flexible 10mm²
- Locking kit = Cat ref.: MZN175

Width
Rating (1 = 17.5mm) Cat ref.
MLN710A
6A SPSN MCB 6kA 1 Mod MLN706A
10A SPSN MCB 6kA 1 Mod MLN710A
16A SPSN MCB 6kA 1 Mod MLN716A
20A SPSN MCB 6kA 1 Mod MLN720A
32A SPSN MCB 6kA 1 Mod MLN732A
40A SPSN MCB 6kA 1 Mod MLN740A

Single Module Blank

Description Cat ref.


Shrouds busbar and blanks spare ways JK01B

JK01B

Data is subject to errors and technical modifications.  New. 51


RCCBs
2 & 4 Pole RCCBs

2 & 4 Pole RCCBs

Characteristics
- To open a circuit automatically in the event an earth fault between line and earth, and/or neutral and earth.
Technical Data
- Conforms to BS EN 61008, IEC1008
- Terminal capacities: 16-63A Rigid 25mm², Flexible 16mm² / 80 & 100A Rigid 50mm², Flexible 35mm²
Features
- Positive contact indication is provided by the rectangular flag indicator
- Red = Closed
- Green = Open
- Indication of trip is provided by the flag indicator
Commercial

- Yellow = Tripped
Distribution

CDC225U - All RCCBs have trip free mechanisms and can be padlocked either on or off with the use of a MZN175.
Operating Voltage
- 2P 127- 230V A.C.
- 4P 230 - 400V A.C.

2 Pole 4 Pole 2 Pole 4 Pole 2 Pole 4 Pole


Type F Type F Type B Type B Type A Type A
Sensitivity type A Cat ref. Cat ref. Cat ref. Cat ref. Cat ref. Cat ref.
RCCBs Sensitivity 30mA
RCCB 25A 30mA CDF525U  CDF625U  CDB525E  - CDA225U CDA425U
RCCB 40A 30mA CDF540U  CDF640U  CDB540E  CDB640E  CDA240U CDA440U
RCCB 63A 30mA CDF563U  CDF663U  - CDB663E  CDA263U CDA463U
RCCB 80A 30mA - - - - CDA580U  CDA680U 
CFC425U
RCCB 100A 30mA - - - - CDA584U  CDA684U 
RCCB 125A 30mA - - - - - CDA690 

RCCBs Sensitivity 100mA


RCCB 25A 100mA - - - - CEA225U -
RCCB 40A 100mA - - - - CEA240U CE440J
RCCB 63A 100mA - - - - CEA263U CE463J
RCCB 80A 100mA - - - - CEA580U  CEA680U 
RCCB 100A 100mA - - - - CEA584U  CEA684U 

RCCBs Sensitivity 300mA


RCCB 25A 300mA - - - - CFA225U CF425J
RCCB 40A 300mA - - - - CFA240U CF440J
RCCB 63A 300mA - - - - CFA263U CF463J
RCCB 80A 300mA - - - - - CFA680U 
RCCB 100A 300mA - - - - CFA584U  CFA684U 
RCCB 125A 300mA - - - - - CFA690 

RCCBs Time Delayed


RCCB 100A 100mA - - - - CNA584U  CNA684U 
RCCB 100A 300mA - - - - CPA584U  CPA684U 

Terminal Covers

2 Pole 4 Pole
Current Rating Cat ref. Cat ref.
16 - 63A CZN005 CZN006
80 - 100A CZ007 CZ008

CZN006

52 Data is subject to errors and technical modifications.  New.


RCCBs
RCCB Auxiliaries

RCCB Auxiliaries

Auxiliary Interface
- Indicates the position of the associated RCCB on, off or tripped. Also acts as RCCB interface with standard MCB auxiliaries
MZ203-MZ206.
Shunt Trip
- Allows remote tripping of the associated device, operation of the coil is indicated by a flag on the front of the device.
Under Voltage Release
- Allows RCCB to be closed, only when voltage is above 85% of Un. RCCB will automatically trip when voltage falls to
between 70-35% of Un (230V). Operation of the release is indicated by a flag on the front of the device.

Commercial
Distribution
CZ001

MZ203 CZ001 RCCB


to MZ206
Width
Description (1 Mod = 17.5mm) Cat ref.
Auxiliary Interface
2 Normally Open / 2 Normally Closed 6A A.C.1 230V 1 Mod CZ001

MZ203

Auxiliaries for MCBs & RCCBs

Characteristics
- All auxiliaries are common to both single and multi-pole 10kA circuit breakers and RCCBs.
Connection capacity
- 4mm² flexible, 6mm² rigid
Shunt Trip: Allows remote tripping of devices. Operation of the coil is indicated by a flag on the front of the device.
Under Voltage Release: Allows MCB to be closed only when voltage is above 85% of Un. MCB will automatically trip when
voltage falls to between 70-35% of Un. Operation of the coil is indicated by a flag on the front of the device.

MZ201

MZ203 to + MZ201 + MZ201 + MZ202 + MCB


MZ206 MZ201 MZ201 MZ201

Width
Description (1 Mod = 17.5mm) Cat ref.
Auxiliary Contacts 5A - 230V A.C.
1NO +1NC Allows remote indication of main contact status ½ Mod MZ201

MZ202

Auxiliary Contacts & Alarm Induction


Allows indication of MCB status when turned off or tripped ½ Mod MZ202

Shunt Trip
230V - 415V A.C. 1 Mod MZ203
110V - 130V D.C.
24 - 48V A.C. 1 Mod MZ204
12 - 48V D.C.
MZ204
Under Voltage Release
230V A.C. 1 Mod MZ206
48V D.C. 1 Mod MZ205

Data is subject to errors and technical modifications.  New. 53


Relays & Contactors
Latching Relays, Auxiliary Contacts, Relays

Latching Relays

Description
- Operate when impulsed by a signal voltage.
- The impulse can be provided via a pushbutton or pushswitch. The first pulse operates the relay and latches it to its set
(opposite) state, the next operation of the pushbutton returns the relay to its reset (original) state.
- Auxiliary contacts (EPN050, EPN051).
- Are available for remote signalling and centralised control applications and can be easily combined with the latching relays.
- Connection: 10mm² flexible, 6mm² rigid.
- For technical details see page 106.
Commercial
Distribution

Width
EPN510 Coil Power Circuit AC1 (1 Mod =17.5mm) Cat ref.
Latching Relay 1 NO
230V 50Hz 16A - 250V A.C. 1 Mod EPN510
24V 50Hz 16A - 250V A.C. 1 Mod EPN513

Latching Relay 2 NO
230V 50Hz 16A - 250V A.C. 1 Mod EPN520
24V 50Hz 16A - 250V A.C. 1 Mod EPN524
12V 50Hz 16A - 250V A.C. 1 Mod EPN521

Latching Relay 1 NC + 1 NO
EPN520 230V 50Hz 16A - 250V A.C. 1 Mod EPN515
24V 50Hz 16A - 250V A.C. 1 Mod EPN518
12V 50Hz 16A - 250V A.C. 1 Mod EPN519

Latching Relay 2 NC + 2 NO
230V 50Hz 16A - 250V A.C. 2 Mod EPN525
24V 50Hz 16A - 250V A.C. 2 Mod EPN528
12V 50Hz 16A - 250V A.C. 2 Mod EPN529

Latching Relay 4 NO
230V 50Hz 16A - 400V A.C. 2 Mod EPN540
EPN518 24V 50Hz 16A - 400V A.C. 2 Mod EPN541

Auxiliary Contacts

Width
Description Power Circuit (1 Mod =17.5mm) Cat ref.
Auxiliary Contact 2A - 250V A.C. ½ Mod EPN051
Auxlliary Contacts for Centralised Control 110-230V A.C. ½ Mod EPN050

EPN050

Relays

Characteristics
- To provide control of low power circuits max 16A; associated with switches, time switches etc for remote control
applications.
- The relays will accept an auxiliary contact for remote signalling applications (ESC080).
- For the command of ELV circuits use interface relays EN145 and EN146.
- For the command of high power circuits (20, 40 & 63 Amps) use contactors as shown on page 55.

Width
Coil AC Voltage Power Circuit AC1 (1 Mod =17.5mm) Cat ref.
Relays 1 NC + 1 NO
ERD218 230V 50Hz 16A - 250V~ 1 Mod ERC218
24V 50Hz 16A - 250V~ 1 Mod ERD218
8/12V 50Hz 16A - 250V~ 1 Mod ERL218

Relays 2 NC + 2 NO
230V 50Hz 16A - 250V~ 2 Mod ERC418
24V 50Hz 16A - 250V~ 2 Mod ERD418
8/12V 50Hz 16A - 250V~ 1 Mod ERL418

54 Data is subject to errors and technical modifications.  New.


Relays & Contactors
Low Noise Contactors

Low Noise Contactors

Description
- For the remote switching and control of power circuits where noise may be a concern i.e. hotel bedrooms etc.
Technical Data
- The choice of contactor depends upon a number of parameters, e.g. The nature of the supply, the power it is switching, the
characteristics of the load, the control voltage required & number of operations.
- All contactor ratings are for AC1 loads only – if the load differs from AC1 the contactor may need de-rating
- The use of LZ060 (heat dissipation inserts) between all contactors installed or between contactors and adjacent devices is
required.
- For technical data, see page 107.
Options

Commercial
Distribution
- Contact choice: Normally open (NO), Normally closed (NC). ESC225S

Width
Description Coil AC Voltage Power Circuit (1 Mod =17.5mm) Cat ref.
25A 2NO 230V 50Hz 25A - 400V A.C. 1 Mod ESC225S
40A 2NO 230V 50Hz 40A - 400V A.C. 3 Mod ESC240S
63A 2NO 230V 50Hz 63A - 400V A.C. 3 Mod ESC263S

25A 3NO 230V 50Hz 25A - 400V A.C. 2 Mod ESC325S


40A 3NO 230V 50Hz 40A - 400V A.C. 3 Mod ESC340S

25A 3NO + 1NC 230V 50Hz 25A - 400V A.C. 2 Mod ESC428S
ESC463S

25A 4NO 230V 50Hz 25A - 400V A.C. 2 Mod ESC425S


40A 4NO 230V 50Hz 40A - 400V A.C. 3 Mod ESC440S
63A 4NO 230V 50Hz 63A - 400V A.C. 3 Mod ESC463S

25A 4NC 230V 50Hz 25A - 400V A.C. 2 Mod ESC426S

Auxiliaries & Accessories

Width
Description Power Circuit (1 Mod =17.5mm) Cat ref.
Heat Dissipation Insert - ½ Mod LZ060
Sealable Terminal Cover for 1 Module Contactors - - ESC001
Sealable Terminal Cover for 2 Module Contactors - - ESC002
Sealable Terminal Cover for 3 Module Contactors - - ESC003
1NO + 1NC Auxiliary Contact 6A - 250V A.C. ½ Mod ESC080

ESC001

ESC002

ESC080

Data is subject to errors and technical modifications.  New. 55


Relays & Contactors
Standard contactors

Standard Contactors

Description
- For the remote switching and control of power circuits (25A-63A AC1)
Technical Data
- The choice of contactor depends upon a number of parameters, e.g. the nature of the supply, the power it is switching, the
characteristics of the load, the control voltage required, number of operations.
- All contactor ratings are for AC1 loads only – if the load differs from AC1 the contactor may need de-rating (see technical
characteristics on page 108).
- The use of LZ060 (heat dissipation inserts) between all contactors installed or between contactors and adjacent devices is
required.
Options
Commercial
Distribution

ESC225 - Contact choice


- Normally open (NO)
- Normally closed (NC)
Auxiliary
- All contactors will accept auxiliary, ESC080 contact.

Width
Description Coil AC voltage Power circuit AC1 (1 Mod =17.5mm) Cat ref.
25A 1NO 230V 50Hz 25A - 250V~ 1 Mod ESC125

25A 2NO 230V 50Hz 25A - 250V~ 1 Mod ESC225


25A 2NO Manual Override 230V 50Hz 25A - 250V~ 1 Mod ERC225
40A 2NO 230V 50Hz 40A - 400V~ 3 Mod ESC240
ESC425 63A 2NO 230V 50Hz 63A - 400V~ 3 Mod ESC263
25A 2NO 24V 50Hz 25A - 250V~ 1 Mod ESD225
25A 2NO Manual Override 24V 50Hz 25A - 250V~ 1 Mod ERD225
40A 2NO 24V 50Hz 40A - 250V~ 3 Mod ESD240
25A 2NO 24V 50Hz 25A - 250V~ 1 Mod ESD225 
63A 2NO 24V AC 50Hz 63A - 250V~ 3 Mod ESD263 

25A 2NC 230V 50Hz 25A - 250V~ 1 Mod ESC226

25A 2NO + 2NC 230V 50Hz 25A - 400V~ 2 Mod ESC427 


40A 2NO + 2NC 230v 50Hz 40A - 400V~ 3 Mod ESC442 

25A 1NO + 1NC 24V 50Hz 25A - 250V~ 1 Mod ESD227


25A 1NO + 1NC 230V 50Hz 25A - 250V~ 1 Mod ESC227 

25A 3NO 230V 50Hz 25A - 400V~ 2 Mod ESC325


25A 3NO Manual Override 230V 50Hz 25A - 400V~ 3 Mod ERC326
40A 3NO 230V 50Hz 40A - 400V~ 3 Mod ESC340
40A 3NO + 1NC 230V 50Hz 40A - 400V~ 3 Mod ESC443
63A 3NO + 1NC 230V 50Hz 63A - 400V~ 3 Mod ESC466

25A 4NO 230V 50Hz 25A - 400V~ 2 Mod ESC425


40A 4NO 230V 50Hz 40A - 400V~ 3 Mod ESC440
63A 4NO 230V 50Hz 63A - 400V~ 3 Mod ESC463
25A 4NO 24V 50Hz 25A - 400V~ 2 Mod ESD425

25A 4NC 230V 50Hz 25A - 400V~ 2 Mod ESC426


40A 4NC 230V 50Hz 40A - 400V~ 3 Mod ESC441
63A 4NC 230V 50Hz 63A - 400V~ 3 Mod ESC464

63A 2NC + 2NO 230V 50Hz 63A - 250V~ 3 Mod ESC465

56 Data is subject to errors and technical modifications.  New.


Relays & Contactors
Override Contactors

Override Contactors

Description
- Manual override facility allows temporary override, with automatic return at next coil energisation. Permanent off can also be
selected. ETC225S is a low noise version.
Technical Data
- The choice of contactor depends upon a number of parameters, e.g. the nature of the supply, the power it is switching, the
characteristics of the load, the control voltage required, number of operations.
- All contactors ratings are for AC1 loads only – if the load differs from AC1 the contactor may need de-rating (see technical
characteristics on page 108).
- The use of LZ060 (heat dissipation inserts) between all contactors installed or between contactors and adjacent devices is
- recommended. ETC225S

Commercial
Distribution
Options
- Contact choice
- Normally open (NO)
- Normally closed (NC)
Auxiliary
- All contactors will accept auxiliary, ESC080 contact.

Width
Coil AC voltage Power circuit AC1 (1 Mod =17.5mm) Cat ref.
2 NO
230V 50 Hz 25A - 250V~ 1 Mod ETC225S
230V 50 Hz 25A - 250V~ 1 Mod ETC225
ETC340

3 NO
230V 50 Hz 20A - 400V~ 2 Mod ETC325
230V 50 Hz 40A - 400V~ 3 Mod ETC340

4 NO
230V 50 Hz 20A - 400V~ 2 Mod ETC425
230V 50 Hz 40A - 400V~ 3 Mod ETC440

ETC425

Auxiliary for 25A Contactors

Width
Power circuit AC1 (1 Mod =17.5mm) Cat ref.
2A - 250V~ ½ Mod ESC080

Accessories

Width
Description (1 Mod =17.5mm) Cat ref.
Heat Dissipation Insert ½ Mod LZ060

Data is subject to errors and technical modifications.  New. 57


Motor Starters
Motor Starters, Motor Starter Accessories

Motor Starters

- To ensure localised control and protection of single and three phase motors.
Technical Data
- Adjustable thermal relay
- AC 3 utilisation category
Connection capacity
- 2 conductors: Max size flexible 1 to 4mm², rigid 1.5 to 6mm²
Options
- Conforms to IEC 947-1, IEC 947-2 (appropriate parts of)

Standard power ratings of 3 phase


Commercial
Distribution

motors 50/60Hz (A.C. 3 category)


MM501N Width
Current setting 230V (kW) 400V (kW) (1 Mod = 17.5mm) Cat ref.
0.1 - 0.16A - - - MM501N
0.16 - 0.25A - 0.06 2 ½ Mod MM502N
0.25 - 0.4A 0.06 0.09 2 ½ Mod MM503N
0.4 - 0.6A 0.09 0.12 2 ½ Mod MM504N
0.6 - 1.0A 0.09 0.12 2 ½ Mod MM505N
1.0 - 1.6A 0.25 0.55 2 ½ Mod MM506N
1.6 - 2.5A 0.55 0.8 2 ½ Mod MM507N
2.5 - 4A 0.8 1.5 2 ½ Mod MM508N
4 - 6A 1.5 2.5 2 ½ Mod MM509N
6 - 10A 2.5 4 2 ½ Mod MM510N
10 - 16A 4 7.5 2 ½ Mod MM511N
16 - 20A 5.5 9 2 ½ Mod MM512N
20 - 25A 7.5 12.5 2 ½ Mod MM513N

Auxiliary & Alarm Contacts for Motor Starters

- Auxiliary Contacts - Act as an indicating device to monitor the ON or OFF position.


- Alarm Contact - Mounted inside the motor starter

Width
Characteristics (1 Mod = 17.5mm) Cat ref.
Auxiliary Contacts 1 Normally Closed + 1 Normally Open 2A AC 1 - 400V A.C. ½ Mod MZ520N
Alarm Contact 1 Normally Closed 1A AC 1 - 400V A.C. / 2A AC 1 - 230V A.C. ½ Mod MZ527N

MZ520N

Under Voltage Release for Motor Starters

- To prevent automatic restarting of the controlled device

Characteristics Cat ref.


230V A.C. 50Hz MZ528N
400V A.C. 50Hz MZ529N

MZ528N

Surface Mounting Enclosure for Motor Starters

Dimensions
Description (H x W x D mm) Cat ref.
IP55 Surface Mounting Enclosure for Motor Starter 78 x 150 x 95 MZ521N

MZ521N

Emergency Stop Button

Description Cat ref.


IP65 External Emergency Stop Button MZ530N

MZ530N

58 Data is subject to errors and technical modifications.  New.


Fuse Carriers
SPSN Fuse Carriers

SPSN Fuse Carriers (supplied without cartridge fuse)

Characteristics
- Protection and control of circuits against overloads and short-circuits.
Technical Data
- Characteristics type (fuse) gF
- Short-circuit rating: 4kA (10-20A), 6kA (25 & 32A).
- Voltage rating - 250V A.C.
- Connection Capacity: Rigid 16mm², Flexible 10mm²

Width Cat ref. Cat ref.


Rating (1 = 17.5mm) SPSN Fuse Carrier Fuse Type gF

Commercial
10A 1 Mod L12401 LF138

Distribution
L12401
16A 1 Mod L12501 LF139
20A 1 Mod L12601 LF140
25A 1 Mod L12701 LF141
32A 1 Mod L12801 LF142

LF140 LF138

Data is subject to errors and technical modifications.  New. 59


Surge Protection
Surge Protection Kits

Surge Protection Kits

Characteristics
- Developed to ensure effective protection of end equipment from fast transient overvoltages, where supplied from Hager
Commercial distribution boards.
- Solid copper Earth links on all SPD kits and other design principles ensure optimum protection of end equipment through
validated low Up effective SPD performance.
- For more information on these Surge Protection Kits see distribution board pages.

Surge Protection Kits for 125A TP&N Boards Cat ref.


Commercial

JK101SPD
Distribution

Type 1 & 2 Surge Protection Kit for 125A Boards JK101SPD 


Type 2 Surge Protection Kit for 125A Boards JK102SPD 

Type 1 & 2 Surge Protection Kit for 125A Power & Lighting Boards JKD101SPD 
Type 2 Surge Protection Kit for 125A Power & Lighting Boards JKD102SPD 

Surge Protection Kits for 250A TP&N Boards


Type 1 & 2 Surge Protection Kit for 250A Boards JK201SPD 
Type 2 Surge Protection Kit for 250A Boards JK202SPD 

JKD101SPD Surge Protection Kits for JN Panelboards


SPD kit Type 1+2 for JN Panelboards JN201SPD 
SPD kit Type 2 for JN Panelboards JN202SPD 

Surge Protection Kit for JF Panelboards


SPD kit Type 1 + 2 for JF Panelboards JF801SPD 

JK201SPD

60 Data is subject to errors and technical modifications.  New.


Surge Protection
Replacement Cartridges, Devices

Type 1 + 2 (Type 1 + 2 + 3 if less than 5m) (with lifetime indicator)

Single or Cat ref.


Iimp Iimp Three with remote
TN / TT Poles L-N N-PE Up kV Phase Width (mm) Cat ref. contact
TN / TT 2 12.5 25 ≤1.5 Single 35 SPA201 -
TN / TT 4 12.5 50 ≤1.5 Three 70 SPA401 -
TN / TT 4 25 100 ≤1.5 Three 140 SPN802 SPN802R
SPN801R

Commercial
Distribution
Type 2 (with lifetime indicator)

Single or Cat ref.


In kA In kA Three with remote
Poles L-N N-PE Up kV Phase Width (mm) Cat ref. contact
2 5 15 ≤ 1.2 Single 35 SPN215D SPN215R
2 15 40 ≤ 1.2 Single 35 SPN240D SPN240R
4 5 15 ≤ 1.5 Three 70 SPN415D SPN415R
4 15 40 ≤ 1.5 Three 70 SPN440D SPN440R

SPN415D

Type 3 (Fine Protection) (with lifetime indicator)

In kA In kA
Poles L-N N-PE Up kV Width (mm) Cat ref.
2 3 3 ≤ 1.5 17.5 SPN203N

PV Applications (DC side) (with lifetime indicator)

Single or
In kA In kA Three
Poles L-N N-PE Up kV Phase Width (mm) Cat ref.
3 12.5 25 ≤4 - 52.5 SPV325

Replacement Cartridges

Description Cat ref.


Phase replacement for SPN215D, SPN415D, SPN115D SPN015D
Phase replacement for SPN215R, SPN415R, SPN115R SPN015R
Phase replacement for SPN240D, SPN440D SPN040D
Phase replacement for SPN240R, SPN44R SPN040R
Neutral replacement for SPN215D, SPN415D, SPN215R, SPN415R SPN040N

SPN040D

Replacement Cartridges (SPN8* Range)

Description Cat ref.


Phase replacement for SPN801, SPN801R, SPN802, SPN802R SPN080
Neutral replacement for SPN801, SPN801R, SPN802, SPN802R SPN080N

SPN080

Data is subject to errors and technical modifications.  New. 61


Earth Fault Relays
Earth Fault Relays

Earth Fault Relays

Characteristics
- Provides monitoring of earth fault currents. When the fault current rises above the selected level, the output contacts of the
product operate.
- Depending on the relay selected, it can have either fixed or adjustable sensitivity. A time delay is also available for selectivity
purposes. The relays are linked with detection torroids, available in circular and rectangular variants.
- Positive safety: the relay trips in the event of a break in the relay/torroid link.
- Positive reset required after a fault is detected.
- Test button for simulation of a fault.
- Protected against nuisance tripping from transients.
- Conforms to BS EN 61008.
Commercial

Technical Data
Distribution

HR500 - Type A RCD protection.


- Output: 1 C/O contact, 250V A.C. 5/6A AC1.
- Visual display of fault by red LED.
Specific device features of HR525 & HR534.
- Display of fault current before it triggers the relay (5% to 75%).
- Extra output contact (250V 0.1A max.) to enable remote indication if fault currents over 50% of IΔn.
- Remote test and reset
Connection capacity
- Relay - 1.5 to 6mm²
- Relay - torroid link: 2 wires, 25m max.
- Test and remote reset link: 3 wires, 20m max.

Description Characteristics Width Cat ref.


Earth Fault Relay with Separate Detection Torroids
Earth fault relay C/O contact Instant trip, fixed sensitivity 1 Mod HR500
HR510
5A A.C.1 I∆n = 30mA
Earth fault relay C/O contact Instant trip, fixed sensitivity 1 Mod HR502
5A A.C.1 I∆n = 300mA
Earth fault relay C/O contact Adjustable sensitivity 3 Mod HR510
6A A.C.1 I∆n = 30mA, 100mA, 300mA
500mA, 1A, 3A, 10A
Instant trip or time delay
0.1 - 0.3 - 0.4 - 0.5 - 1 - 3 secs
Earth fault relay C/O contact Adjustable sensitivity 3 Mod HR520
6A A.C.1 I∆n = 30mA, 100mA, 300mA
500mA, 1A, 3A, 10A
HR520 LED optical scale
Instant trip or time delay
0.1 - 0.3 - 0.4 - 0.5 - 1 - 3 secs
Earth fault relay C/O contact Adjustable sensitivity 3 Mod HR522
6A A.C.1 I∆n = 30mA, 100mA, 300mA
500mA, 1A, 3A, 10A
LED optical scale
Instant trip or time delay
0.1 - 0.2 - 0.25 - 0.3 - 0.4 - 0.5 secs
Earth fault relay C/O contact Adjustable sensitivity 3 Mod HR523
6A A.C.1 I∆n = 500mA, 1A, 3A, 5A,
10A, 20A & 30A
LED optical scale
Instant trip or time delay
0.1 - 0.2 - 0.25 - 0.3 - 0.4 - 0.5 secs
HR440
Earth fault relay C/O contact Adjustable sensitivity 3 Mod HR525
6A A.C.1 I∆n = 30mA, 100mA, 300mA,
Trip / reclose input feature 500mA, 1A, 3A, 5A, 10A & 30A
LCD Display
Instant trip or time delay
0.02 - 0.1 - 0.3 - 0.4 - 0.5 - 1 - 3 - 5 - 10
secs
Earth fault relay C/O contact Adjustable sensitivity 3 Mod HR534
6A A.C.1 I∆n = 30mA, 100mA, 300mA,
Solid State relay output 500mA, 1A, 3A, 5A, 10A & 30A
Trip / reclose input feature LCD Display
HR441 Instant trip or time delay
0.02 - 0.1 - 0.3 - 0.4 - 0.5 - 1 - 3 - 5 - 10
secs

Earth Fault Relay with Integral Torroids


Earth fault relay with integral Adjustable sensitivity 4 Mod HR440
torroid adjustable sensitivity I∆n - 30mA, 100mA, 300mA,
25mm² max. cable size 500mA, 1A & 3A
Instant trip or time delay
0.1 - 0.3 - 0.5 - 0.75 - 1 secs
Earth fault relay with integral Adjustable sensitivity 6 Mod HR441
torroid adjustable sensitivity I∆n - 30mA, 100mA, 300mA,
35mm² max. cable size 500mA, 1A & 3A
Instant trip or time delay
0.1 - 0.3 - 0.5 - 0.75 - 1 secs

62 Data is subject to errors and technical modifications.  New.


Earth Fault Relays
Torroids

Circular Section Torroids

Characteristics Cat ref.


ø 30mm HR700
ø 35mm HR701
ø 70mm HR702
ø 105mm HR703
ø 140mm HR704
ø 210 mm HR705

Commercial
Distribution
HR702

Rectangular Section Torroids

Dimensions Cat ref.


70 x 175mm HR830
115 x 305mm HR831
150 x 350mm HR832

HR830

Rectangular Split Torroids

Dimensions Cat ref.


20 x 30mm HR820
50 x 80mm HR821
80 x 80mm HR822
80 x 121mm HR823
80 x 161mm HR824

HR820

Data is subject to errors and technical modifications.  New. 63


MCCBs x160
MCCBs x160 18kA

Moulded Case Circuit Breakers x160 18kA

Characteristics
- Thermal magnetic trip unit, two versions: Z/E version: fixed thermal and fixed magnetic. U version: adjustable thermal and
fixed magnetic.
- Access to mechanical test button on cover.
- Lockable cover protects MCCB settings.
- Integrated padlocking handle: Ø 4mm.
- Connection capacity: 95mm² rigid cables, 70mm² flexible cables.
- Cage terminals
- Conforms to BS EN 60947-2.
- Fixed thermal: 1x In
Commercial

- Adjustable thermal: 0.63 - 0.8 - 1 x In


Distribution

HDA125Z - For technical details see table on page 121.

Description Breaking Capacity Cat ref. 1 pole Cat ref. 3 pole

Moulded Case Circuit Breakers, 18kA, Fixed Thermal


MCCBs x160 - 16A Icu / Ics: 18 kA HDA014E  HDA016Z
MCCBs x160 - 20A Icu / Ics: 18 kA HDA018E  HDA020Z
MCCBs x160 - 25A Icu / Ics: 18 kA HDA023E  HDA025Z
MCCBs x160 - 32A Icu / Ics: 18 kA HDA030E  HDA032Z
MCCBs x160 - 40A Icu / Ics: 18 kA HDA038Z  HDA040Z
MCCBs x160 - 50A Icu / Ics: 18 kA HDA048Z  HDA050Z
MCCBs x160 - 63A Icu / Ics: 18 kA HDA061Z  HDA063Z
MCCBs x160 - 80A Icu / Ics: 18 kA HDA078Z  HDA080Z
MCCBs x160 - 100A Icu / Ics: 18 kA HDA098Z  HDA100Z
MCCBs x160 - 125A Icu / Ics: 18 kA HDA123Z  HDA125Z
MCCBs x160 - 160A Icu / Ics: 18 kA - HDA160Z

Moulded Case Circuit Breakers, 18kA, Adjustable Thermal


MCCBs x160 - 25A Icu / Ics: 18 kA - HDA025U
MCCBs x160 - 40A Icu / Ics: 18 kA - HDA040U
MCCBs x160 - 63A Icu / Ics: 18 kA - HDA063U
MCCBs x160 - 80A Icu / Ics: 18 kA - HDA080U
MCCBs x160 - 100A Icu / Ics: 18 kA - HDA100U
MCCBs x160 - 125A Icu / Ics: 18 kA - HDA125U
MCCBs x160 - 160A Icu / Ics: 18 kA - HDA160U

Moulded Case Circuit Breakers 25kA Fixed Thermal

MCCBs x160 - 16A Ics: 20 kA, Icu: 25 kA HHA014E  HHA016Z


MCCBs x160 - 20A Ics: 20 kA, Icu: 25 kA HHA018E  HHA020Z
MCCBs x160 - 25A Ics: 20 kA, Icu: 25 kA HHA023E  HHA025Z
MCCBs x160 - 32A Ics: 20 kA, Icu: 25 kA HHA030E  HHA032Z
MCCBs x160 - 40A Ics: 20 kA, Icu: 25 kA HHA038Z  HHA040Z
MCCBs x160 - 50A Ics: 20 kA, Icu: 25 kA HHA048Z  HHA050Z
MCCBs x160 - 63A Ics: 20 kA, Icu: 25 kA HHA061Z  HHA063Z
MCCBs x160 - 80A Ics: 20 kA, Icu: 25 kA HHA078Z  HHA080Z
MCCBs x160 - 100A Ics: 20 kA, Icu: 25 kA HHA098Z  HHA100Z
MCCBs x160 - 125A Ics: 20 kA, Icu: 25 kA HHA123Z  HHA125Z
MCCBs x160 - 160A Ics: 20 kA, Icu: 25 kA - HHA160Z

Moulded Case Circuit Breakers 25kA Adjustable Thermal


MCCBs x160 - 25A Ics: 20 kA, Icu: 25 kA - HHA025U
MCCBs x160 - 40A Ics: 20 kA, Icu: 25 kA - HHA040U
MCCBs x160 - 63A Ics: 20 kA, Icu: 25 kA - HHA063U
MCCBs x160 - 80A Ics: 20 kA, Icu: 25 kA - HHA080U
MCCBs x160 - 100A Ics: 20 kA, Icu: 25 kA - HHA100U
MCCBs x160 - 125A Ics: 20 kA, Icu: 25 kA - HHA125U
MCCBs x160 - 160A Ics: 20 kA, Icu: 25 kA - HHA160U

64 Data is subject to errors and technical modifications.  New.


x160 Devices
Accessories for x160 Devices

Accessories for x160 Devices

Indication contacts
- 1 changeover switch (ON/OFF): indicates the position of the MCCB “open” or “close”.
- 1 changeover alarm contact: indicates MCCB tripped.
Coil connection
- Connection capacity: 0.75 mm² flexible or rigid cables
- The cable capacity of the terminals is 0.5 to 1.25mm².
Shunt trip
- Remote tripping of MCCBs
- Operating voltage: 0.7 to 1.1 x Un
Under voltage release

Commercial
- Enables tripping of MCCBs or moulded case switches when voltage level drop between 35 and 70% of Un. Pick up voltage

Distribution
0.85 x Un. HXA021H HXA024H
- Padlockable direct rotary handle is equipped with front cover and handle, fixing without additional screws.

Description Cat ref.

Auxiliary Contacts
1 Changeover contact (On/Off), 250V A.C. / 3A, 125V D.C. / 0.4A, 1 NO+ 1NC HXA021H
1 Changeover alarm contact, 250 V A.C. / 3A, 125 V D.C. / 0.4A, NO + 1 NC HXA024H
Low level contact (On/Off), 125V A.C. , NO + 1 NC HXA025H
Low Level alarm contact, 125 V A.C. , NO + 1 NC HXA026H

Shunt Trips
24V DC HXA001H HXA014H
48V DC HXA002H
100-120V A.C. HXA003H
200-240V A.C. HXA004H
380-450V A.C. HXA005H

Undervoltage Releases HXA039H


24V DC HXA011H
100-120V A.C. HXA013H
200-240V A.C. HXA014H
380-450V A.C. HXA015H

Delayed Undervoltage Releases


24V DC HXA051H
100-120V A.C. HXA053H
200-240V A.C. HXA054H
380-450V A.C. HXA055H HYA021H

Accessories
Locking Device to Mount on MCCB for Handle Locking for 3 Padlock Max ø 8mm HXA039H
Set of Three Extended Spreader Connections HYA014H
Pair of Terminal Covers for Extended Straight Connections 1 Pole HYA029H
Pair of Terminal Covers for Extended Straight Connections 3 Pole HYA021H
Pair of Terminal Covers for Extended Spreader Connections HYA023H

HYA023H

Add-On Blocks for x160 Devices

Characteristics
- These devices are intended to be fixed on the right side of the devices.
- Type A RCD protection for protection against pulsating D.C.
- High Immunity reduces unexpected tripping (generated by micro-processing, electronic ballast etc.).
- Fixed version: 300 mA sensitivity and instantaneous tripping, adjustable version: adjustable sensitivity and time delay.
- Test button for electrical functioning check.
- LED fault indication and auxiliary output for remote indication - (25-50% IΔn).
- Assembly and disassembly facilitated by the drawer assembly system.
- Connection capacity: 95 mm² rigid cables, 70 mm² flexible cables.
- Sensitivity lΔn, adjustable: 0.03 - 0.1 - 0.3 - 1 - 3 - 6A
- Adjustable tripping: instantaneous or time delay: 0.06 - 0.15 - 0.3, 0.5 - 1s
- Conforms to BS EN 60947-2. HBA125H

Description Cat ref. 3P

Fixed Add-on Block - 125A HBA127H


Adjustable Add-on Block - 125A HBA125H
Adjustable Add-on Block - 160A HBA160H

Data is subject to errors and technical modifications.  New. 65


MCCBs x250
MCCBs x250 25kA

Moulded Case Circuit Breakers x250 25kA

Characteristics
- Thermal magnetic trip unit, two versions: Z version: fixed thermal and fixed magnetic. H version: adjustable thermal
magnetic.
- Access to mechanical test button on cover.
- Lockable cover protects MCCB settings.
- Integrated padlocking handle: Ø 4mm.
- Connection capacity: 150mm² rigid cables, palm lug max. width: 25mm
- Conforms to BS EN 60947-2
- AC 22/23A.
- For technical data see page 131.
Commercial

x250 25kA
Distribution

HNB100Z - Fixed thermal: 1x In


- Fixed magnetic: > 10 x In
x250 40kA
- Adjustable thermal: 0.63, 0.8, 1 x In
- Adjustable magnetic: 6 - 8 - 10 - 13 x In (100 - 200A). 5 - 7 - 9 - 11 x In (250A).

Description Breaking capacity Cat ref. 3P


Moulded Case Circuit Breakers 25kA - Fixed
MCCBs x250 - 100A Ics: 20 kA, Icu: 25 kA HHB100Z
MCCBs x250 - 125A Ics: 20 kA, Icu: 25 kA HHB125Z
MCCBs x250 - 160A Ics: 20 kA, Icu: 25 kA HHB160Z
MCCBs x250 - 200A Ics: 20 kA, Icu: 25 kA HHB200Z
MCCBs x250 - 250A Ics: 20 kA, Icu: 25 kA HHB250Z

Moulded Case Circuit Breakers 40kA - Fixed


MCCBs x250 - 100A Ics: 20 kA, Icu: 40 kA HNB100Z
MCCBs x250 - 125A Ics: 20 kA, Icu: 40 kA HNB125Z
MCCBs x250 - 160A Ics: 20 kA, Icu: 40 kA HNB160Z
MCCBs x250 - 200A Ics: 20 kA, Icu: 40 kA HNB200Z
MCCBs x250 - 250A Ics: 20 kA, Icu: 40 kA HNB250Z

Moulded Case Circuit Breakers 40kA - Adjustable


MCCBs x250 - 100A Ics: 20 kA, Icu: 40 kA HNB100H
MCCBs x250 - 125A Ics: 20 kA, Icu: 40 kA HNB125H
MCCBs x250 - 160A Ics: 20 kA, Icu: 40 kA HNB160H
MCCBs x250 - 200A Ics: 20 kA, Icu: 40 kA HNB200H
MCCBs x250 - 250A Ics: 20 kA, Icu: 40 kA HNB250H

66 Data is subject to errors and technical modifications.  New.


x250 Devices
Accessories for x250 Devices

Accessories for x250 Devices

Indication contacts
- 1 changeover switch (ON/OFF): indicates the position of the MCCB “open” or “close”.
- 1 changeover alarm contact: indicates MCCB tripped.
Coil connection
- Connection capacity: 0.75 mm² flexible or rigid cables
- The cable capacity of the terminals is 0.5 to 1.25mm².
Shunt trip
- Remote tripping of MCCBs
- Operating voltage: 0.7 to 1.1 x Un
Under voltage release

Commercial
- Enables tripping of MCCBs or moulded case switches when voltage level drop between 35 and 70% of Un. Pick up voltage

Distribution
0.85 x Un HXA021H HXA024H
- Padlockable direct rotary handle is equipped with front cover and handle, fixing without additional screws.

Description Cat ref.

Auxiliary Contacts
1 Changeover contact (On/Off), 250V A.C. / 3A, 125V D.C. / 0.4A, 1 NO+ 1NC HXA021H
1 Changeover alarm contact, 250 V A.C. / 3A, 125 V D.C. / 0.4A, NO + 1 NC HXA024H
Low level contact (On/Off), 125V A.C. , NO + 1 NC HXA025H
Low Level alarm contact, 125 V A.C. , NO + 1 NC HXA026H

Shunt Trips
24V DC HXA001H HXA014H
48V DC HXA002H
100-120V A.C. HXA003H
200-240V A.C. HXA004H
380-450V A.C. HXA005H

Undervoltage Releases HXA039H


24V DC HXA011H
100-120V A.C. HXA013H
200-240V A.C. HXA014H
380-450V A.C. HXA015H

Delayed Undervoltage Releases


24V DC HXA051H
HYB010H
100-120V A.C. HXA053H
200-240V A.C. HXA054H
380-450V A.C. HXA055H

Accessories
Locking Device to Mount on MCCB for Handle Locking for 3 Padlock Max ø 8mm HXA039H
Set of Four Extended Straight Connections HXB010H HYB019H
Set of Four Extended Spreader Connections HYB011H
Set of Three Interphase Barriers HYB019H
Pair of Terminal Covers for Extended Straight Connections HYB021H
Pair of Terminal Covers for Extended Spreader Connections HYB023H

HYB021H

Data is subject to errors and technical modifications.  New. 67


A Boards
Dimensions

A
Height

B
Commercial
Distribution

Depth Width
SP&N A Boards

Dimensions Fixing Centres Knockout Size No of Knockouts


Enclosure Width Height Depth A B Top Bottom Left Right Back
Size
ø 20 3 3 - - -
ø 32 1 1 1 1 -
3 254 236 125 186 150
ø 25 1 1 - - -
25 x 50 - - - - 3
ø 20 6 6 - - -
ø 32 1 1 1 1 -
4 326 236 125 258 150
ø 25 1 1 - - -
25 x 50 - - - - 5
ø 20 8 8 - - -
ø 32 1 1 1 1 -
5 398 236 125 330 150
ø 25 1 1 - - -
25 x 50 - - - - 7
ø 20 11 11 - - -
ø 32 1 1 1 1 -
7 505 236 125 437 150
ø 25 1 1 - - -
25 x 50 - - - - 9
ø 20 6 6 - - -
ø 32 1 1 2 2 -
4 (2) 326 472 125 258 388
ø 25 1 1 - - -
25 x 50 - - - - 6
ø 20 8 8 - - -
ø 32 1 1 2 2 -
5 (2) 398 472 125 330 388
ø 25 1 1 - - -
25 x 50 - - - - 8
ø 20 11 11 - - -
ø 32 1 1 2 2 -
7 (2) 505 472 125 437 388
ø 25 1 1 - - -
25 x 50 - - - - 10

A
Invicta 3 SP&N A Boards B

Dimensions (mm) Fixing Centres (mm)


Height Width Depth A B C
Height

JK114A/AG 300 465 107.7 350 35 228 C


JK129A/AG 450 465 107.7 330 35 378

Depth Width

68 Data is subject to errors and technical modifications.


Invicta 3 Type B TP&N Primary Boards, Side DIN Enclosures
Dimensions

125A Primary Boards


A

Dimensions (mm) Fixing Centres (mm)


B
UN
LOCK
UN
LOCK
Height Width Depth A B C
ISOLATE SUPPLY
BEFORE REMOVING COVER
JK104B/BG/A3 500 465 132.5 365 100 300
L1 JK106B/BG/A3 550 465 132.5 365 100 350
L2
JK108B/BG/A3 625 465 132.5 365 100 425
L3
L1 JK112B/BG/A3 850 465 132.5 365 100 650
L2

L3
JK116B/BG/A3 950 465 132.5 365 100 750
Height

Commercial
JK118B/BG/A3 1100 465 132.5 365 100 900

Distribution
L1 L2 L3

JK124B/BG/A3 1250 465 132.5 365 100 1050

250A Primary Boards

L1 L2 L3
Dimensions (mm) Fixing Centres (mm)
Height Width Depth A B C
JK208B/BG/A3 950 465 165.5 365 100 750
Depth JK212B/BG/A3 1100 465 165.5 365 100 900
JK216B/BG/A3 1250 465 165.5 365 100 1050
JK218B/BG/A3 1400 465 165.5 365 100 1200
JK224B/BG/A3 1550 465 165.5 365 100 1350

Width

Contactor Incomers

Dimensions (mm)
Height Width Depth
JK10634C 300 465 165.5
JK11004C 450 465 234.5
JK21604C 450 465 234.5

125A Side DIN Enclosures


A

Dimensions (mm) Fixing Centres (mm)


B
Height Width Depth A B C
JK104BDFG 500 465 132.5 365 100 300
JK106BDFG 550 465 132.5 365 100 350
JK108BDFG 625 465 132.5 365 100 425
JK112BDFG 850 465 132.5 365 100 650
JK116BDFG 950 465 132.5 365 100 750
Height

C
250A Side DIN Enclosures

Dimensions (mm) Fixing Centres (mm)


Height Width Depth A B C
JK208BDFG 950 465 165.5 365 100 750
JK212BDFG 1100 465 165.5 365 100 900
JK216BDFG 1250 465 165.5 365 100 1050
JK218BDFG 1400 465 165.5 365 100 1200
JK224BDFG 1550 465 165.5 365 100 1350

Depth

Width

Data is subject to errors and technical modifications. 69


Invicta 3 DIN Extension Boxes, Cable Spreader Boxes, Hybrid
Dimensions

A 125A DIN Extension Boxes

B Dimensions (mm) Fixing Centres (mm)


Height Width Depth A B C
JK116E/EG 300 465 132.5 365 150 -
Height

C JK132E/EG 450 465 132.5 365 80 290

250A DIN Extension Boxes


Commercial
Distribution

Depth Dimensions (mm) Fixing Centres (mm)


Height Width Depth A B C
JK216E/EG 300 465 165.5 365 150 -
JK232E/EG 450 465 165.5 365 80 290

Width

A 125A Cable Spreader Boxes

B Dimensions (mm) Fixing Centres (mm)


Depth
with
optional
Height

C Height Width Depth door A B C


JK101SE 300 465 91.5 132.5 365 150 -
JK102LE 450 465 91.5 132.5 365 80 290

Depth 250A Cable Spreader Boxes

Dimensions (mm) Fixing Centres (mm)


Depth
with
Width optional
Height Width Depth door A B C
JK201SE 300 465 124.5 165.5 365 150 -
JK202LE 450 465 124.5 165.5 365 80 290

Hybrid 250A TPN Distribution Boards

UN UN

Dimensions (mm)
Width
LOCK LOCK

ISOLATE SUPPLY
BEFORE REMOVING COVER

L1

L2
Height Width Depth
L3
L1

L2 JK20210B/BG 1250 465 165.5


L3

JK20216B/BG 1400 465 165.5


L1

L2

L3

JK20220B/BG 1400 465 165.5


L1

L2

L3

L1

L2

L3
JK20210B/BGSD 1250 465 165.5
L1 JK20216B/BGSD 1400 465 165.5
L2

JK20220B/BGSD 1400 465 165.5


L3
Height

1 19
2 20
3 21
4 22
5 23
6 24
7 25
8 26
9 27
10 28
11 29
12 30

E E
B1 B1
B2 13 31 B2
B3 14 32 B3
1 15 33 1
2 2
3 3
4 4
5 5
6 6
7 7
8 8
9 9
10 10
11 11
12 12

3 3
4 4
5 5

6 6

7 7

8 8

L1 L2 L3

Depth

70 Data is subject to errors and technical modifications.


Invicta 3 Side Extension Boxes
Dimensions

125A Side Extension Boxes


A

Dimensions (mm) Fixing Centres (mm)


B
Height Width Depth A B C
JK104BSF 500 465 91.5 365 100 300
JK106BSF 550 465 91.5 365 100 350
JK108BSF 625 465 91.5 365 100 425
JK112BSF 850 465 91.5 365 100 650
JK116BSF 950 465 91.5 365 100 750

Commercial
Distribution
Height

C
250A Side Extension Boxes

Dimensions (mm) Fixing Centres (mm)


Height Width Depth A B C
JK208BSF 950 465 124.5 365 100 750
JK212BSF 1100 465 124.5 365 100 900
JK216BSF 1250 465 124.5 365 100 1050
JK218BSF 1400 465 124.5 365 100 1200
JK224BSF 1550 465 124.5 365 100 1350

Depth

125A Half Width Side Extension Boxes

Dimensions (mm) Fixing Centres (mm)


Width Height Width Depth A B C
JK104BSH 500 232.5 91.5 170 100 300
JK106BSH 550 232.5 91.5 170 100 350
JK108BSH 625 232.5 91.5 170 100 425
JK112BSH 850 232.5 91.5 170 100 650
JK116BSH 950 232.5 91.5 170 100 750
JK101BSH 300 232.5 91.5 170 100 100

250A Half Width Side Extension Boxes

Dimensions (mm) Fixing Centres (mm)


Height Width Depth A B C
JK208BSH 950 232.5 124.5 170 100 750
JK212BSH 1100 232.5 124.5 170 100 900
JK216BSH 1250 232.5 124.5 170 100 1050
JK218BSH 1400 232.5 124.5 170 100 1200
JK224BSH 1550 232.5 124.5 170 100 1350
JK201BSH 300 232.5 124.5 170 100 100

Data is subject to errors and technical modifications. 71


Invicta 3 Metered Board, Dual Power & Lighting Board
Technical Data & Dimensions

Dual Power & Lighting Boards UN


LOCK
UN
LOCK

ISOLATE SUPPLY
BEFORE REMOVING COVER

L1

Dimensions (mm) L2

L3
Height Width Depth L1

L2
JKD146MID 1100 465 165.5 L3

JKD166MID 1100 465 165.5 L1

L2

JKD164MID 1100 465 165.5 L3

JKD168MID 1250 465 165.5


L1 L2 L3
Commercial
Distribution

JKD188MID 1250 465 165.5


JKD186MID 1250 465 165.5
JKD1416MID 1400 465 165.5
JKD1164MID 1400 465 165.5
JKD1812MID 1400 465 165.5 UN
LOCK
UN
LOCK

JKD1128MID 1400 465 165.5


ISOLATE SUPPLY
BEFORE REMOVING COVER

JKD11212MID 1400 465 165.5 L1

Height
L2

L3
L1

L2

L3

Triple Power, Lighting & Services Board


L1

L2

L3

L1 L2 L3

Dimensions (mm)
Height Width Depth
JKD2884MID 1850 465 165.5

L1 L2 L3

Width Depth

Meter Characteristics
Supply 60 to 300V AC, 50/60Hz (±5%)
Serial Communication
Interface Standard and Protocol RS485 and MODBUS RTU
Input (CT)
Pluggable RJ45 Input 1/ Input 2
Output
Pulse Output: Voltage Range : 24V DC max
Current Capacity : 100mA max
Pulse Duration : Selectable Between 0.1 to 2.0sec
Pulse Weight : Selectable between 0.01 to 9.99kWh
Accuracy of meter
Measurement Accuracy
Voltage VL-N 0.5% of full range
Voltage VL-L 0.5% of full range
Current A 0.5% of full range
Frequency
For L-N Voltage > 20V 0.1% of full range
For L-L Voltage > 35V"
Active power 1.0% of full range
Apparent Power 1.0% of full range
Reactive Power 1.0% of full range
Power Factor ±0.01% of full Range
Active Energy 1.0% of full range
Reactive Energy 1.0% of full range
Max/Min Active Power 1.0% of full range
Max/Min Reactive Power 1.0% of full range
Max Apparent Power 1.0% of full range
Power Consumption Less than 8VA

72 Data is subject to errors and technical modifications.


Invicta 3 Type B TP&N
Technical Data, Torque Settings

Characteristics JK1** JK2**


Designed, manufactured and tested to Designed, manufactured and tested to
Standards
BS EN 61439-3 BS EN 61439-3
Busbar Current Rating 125A 250A
Busbar Type Fully shrouded copper Fully shrouded copper
Busbar Rating 25kA Conditional 25kA Conditional
100A Switch 250A MCS
125A Switch 250A MCCB
63A contactor AC3 160A contactor AC3
Incoming

Commercial
100A contactor AC3

Distribution
Direct connection Direct connection
RCCB incomers
Outgoing Ways 4, 6, 8, 12, 16, 18, 24 Triple pole outgoing ways 8, 12, 16, 18, 24 Triple pole way outgoing ways
Type B MCB (6A to 63A, 1P & 3P) Type B MCB (6A to 63A, 1P & 3P)
Outgoing Protection Type C, D MCB, (0.5A to 63A, 1P & 3P) Type C, D MCB, (0.5A to 63A, 1P & 3P)
1Mod and 2Mod RCBO 1Mod and 2Mod RCBO
Voltage Rating in AC 230 / 415V 230 / 415V
IP Protection IP3X to BS EN 60529 IP3X to BS EN 60529
Enclosure Body Type Steel Steel
Enclosure Paint Type Powder Coat Grey White BS4800 00A01 Powder Coat Grey White BS4800 00A01
Cable Entry Obround protected cable entry points Obround protected cable entry points
Terminal Connection Capacity
Incoming Line Terminal 50mm2 120mm2
Incoming Earth Terminal M8 stud M8 stud
Incoming Neutral Terminal 50mm² cage or M6 stud M8 Stud
Outgoing Earth Terminals 16mm² 16mm²
Outgoing Neutral Terminals 16mm² 16mm²
Enclosure Earth Stud M8 M8
Installation
4 x key hole fixing holes plus central top key hole for 4 x key hole fixing holes plus central top key hole
Mounting one fixing hanging / levelling for one fixing hanging / levelling
Surface Wall Mount Surface Wall Mount
Gland Plate Top and bottom removable Top and bottom removable
Coin lock as standard, key lock as Coin lock as standard, key lock as
Integrated Locking System
accessory accessory

Torque Settings
Cables >1.5mm2 Cables ≤1.5mm2
Cable Stripping (mm)
Tightening torque (N.m) Tightening torque (N.m)

Pz No. (mm) Single Cable Multi Cables Single Cable Multi Cable
Consumer unit terminals
Earth and neutral terminal bars 2 6.5 2 2 1.5 1.5 10
Isolation
Switch Disconnectors / Surge 2 6.5 3.6 3.6 3.6 3.6 15
Circuit protection
MCB 2 6.5 2.8 2.8 2.8 2.8 13
RCBO 2 5.5 2.1 2.1 2.1 2.1 13
RCCB 2 5.5 2.8 2.8 2.8 2.8 13
AFDD 2 2 2.1 2.1 2.1 2.1 13

Data is subject to errors and technical modifications. 73


Invicta 3 Metered Board
Technical Data

Interface Characteristics Dual Power & Lighting Boards Triple Power, Lighting & Services Board
Rated & operational voltage (Un / Ue ) 415V A.C. 50Hz 415V A.C. 50Hz
Rated insulation voltage (Ui ) 690V A.C. 50Hz 690V A.C. 50Hz
Rated impulse withstand voltage (Uimp ) 4kV 4kV
Rated current of the Assembly (InA ) 125A 200A
Lower Pan (In) = 125A (RDF=1)
Lower Pan (In) = 125A (RDF=1)
Rated current of pan assembly Middle Pan (In) = 125A (RDF=1)
Upper Pan (In) = 125A (RDF=1)
Upper Pan (In) = 125A (RDF=1)
MCB 0.5A - 63A (marked rated current on device) MCB 0.5A - 63A (marked rated current on device)
Rated current of an Outgoing Circuit (Inc )
RCBO 6A - 45A (marked rated current on device) RCBO 6A - 45A (marked rated current on device)
Commercial
Distribution

Rated conditional short-circuit current of the 10kA with equipment and arrangements specified in 10kA1 with equipment and arrangements specified
assembly (Icc ) Hager’s technical documentation/catalogue in Hager’s technical documentation/catalogue
Equipment shall be installed in an electrical system Equipment shall be installed in an electrical
Protection against electric shock
conforming to IEC 60364 / BS 7671 system conforming to IEC 60364 / BS 7671
Rated Diversity Factor (RDF) / Values of assumed 10 way to 24 way = 0.5 Note: RDF only applies to 10 way to 24 way = 0.5 Note: RDF only applies to
loading continuously and simultaneously loaded circuits. continuously and simultaneously loaded circuits.
Rated frequency (fn) 50 Hz 50 Hz
Pollution degree 2 2
Types of system earthing for which the assembly is TNC-S, TN-S and TT when installed in an electrical TNC-S, TN-S and TT when installed in an electrical
designed system conforming to BS 7671 system conforming to BS 7671
Intended locations Indoor use only Indoor use only
Stationary Assembly
IP3XD with Door Closed IP3XD with Door Closed
Degree of protection
IP2XC with Door Open IP2XC with Door Open
Distribution boards intended to be operated by Distribution boards intended to be operated by
Intended use
ordinary persons (DBO) ordinary persons (DBO)
Electromagnetic compatibility (EMC) classification EMC Environment B EMC Environment B
External design Wall-mounted, surface type, enclosed assembly. Wall-mounted, surface type, enclosed assembly.
Mechanical impact protection IK05 IK05
The type of construction Fixed parts Fixed parts
DBO Type Type B DBO Type B DBO
Incoming Line Terminal 70mm2 (switch disconnector) 70mm2 (switch disconnector
Incoming Neutral Terminal 50mm2 Cage 50mm2 Cage
Enclosure Earth Stud M8 M8
Standards BS EN 61439-3 BS EN 61439-3

74 Data is subject to errors and technical modifications.


Invicta 3 Metered Incomer
Technical Data

Interface Characteristics JKD125MID JKD125TMID JKD250MID JKD250TMID


Rated & operational voltage 415V A.C. 50Hz 415V A.C. 50Hz 415V A.C. 50Hz 415V A.C. 50Hz
(Un / Ue )
Rated insulation voltage (Ui ) 690V A.C. 50Hz 690V A.C. 50Hz 690V A.C. 50Hz 690V A.C. 50Hz
Rated impulse withstand voltage 4kV 4kV 4kV 4kV
(Uimp )
Rated current of the Assembly 125A 125A 250A 250A
(InA ) Right Side Pan Assembly Right Side Pan Assembly Right Side Pan Assembly Right Side Pan Assembly
(In ) 125A (In ) 125A (In) 250A (In) 200A
Left Side Pan Assembly Middle Pan Assembly Left Side Pan Assembly Middle Pan Assembly
(In ) 125A (In) 125A (In) 250A (In) 200A

Commercial
Distribution
Left Side Pan Assembly Left Side Pan Assembly
(In ) 125A (In) 200A
Rated conditional short-circuit 10kA with equipment and 10kA with equipment and 10kA with equipment and 10kA with equipment and
current of the assembly (Icc ) arrangements specified arrangements specified arrangements specified arrangements specified
in Hager’s technical in Hager’s technical in Hager’s technical in Hager’s technical
documentation/catalogue documentation/catalogue documentation/catalogue documentation / catalogue
Protection against electric shock Equipment shall be installed Equipment shall be installed Equipment shall be installed Equipment shall be installed
in an electrical system in an electrical system in an electrical system in an electrical system
conforming to IEC 60364 / conforming to IEC 60364 / conforming to IEC 60364 / conforming to IEC 60364 /
BS 7671 BS 7671 BS 7671 BS 7671
Rated frequency (fn) 50 Hz 50 Hz 50 Hz 50 Hz
Pollution degree 2 2 2 2
Types of system earthing TNC-S, TN-S and TT when TNC-S, TN-S and TT when TNC-S, TN-S and TT when TNC-S, TN-S and TT when
for which the ASSEMBLY is installed in an electrical installed in an electrical installed in an electrical installed in an electrical
designed system conforming to BS system conforming to BS system conforming to BS system conforming to BS
7671 7671 7671 7671
Intended locations Indoor use only Indoor use only Indoor use only Indoor use only
Degree of protection IP3XD with Door Closed IP3XD with Door Closed IP3XD with Door Closed IP3XD with Door Closed /
IP2XC with Door Open IP2XC with Door Open IP2XC with Door Open IP2XC with Door Open
Intended use Distribution boards intended Distribution boards intended Distribution boards intended Distribution boards intended
to be operated by ordinary to be operated by ordinary to be operated by ordinary to be operated by ordinary
persons (DBO) persons (DBO) persons (DBO) persons (DBO)
Electromagnetic compatibility EMC Environment B EMC Environment B EMC Environment B EMC Environment B
(EMC) classification
External design Wall-mounted, surface type, Wall-mounted, surface type, Wall-mounted, surface type, Wall-mounted, surface type,
enclosed assembly. enclosed assembly. enclosed assembly. enclosed assembly.
Mechanical impact protection IK05 IK05 IK05 IK05
The type of construction Fixed parts Fixed parts Fixed parts Fixed parts
Incoming Line Terminal M8 M8 M8 M8
Incoming Neutral Terminal M8 Lug M8 Lug M8 Lug M8 Lug
Enclosure Earth Stud M8 M8 M8 M8

Data is subject to errors and technical modifications. 75


Invicta 3 Metered Incomer
Technical Data & Dimensions

Meter Characteristics
Supply 60 to 300V AC, 50/60Hz (±5%)
Serial Communication
Interface Standard and Protocol RS485 and MODBUS RTU
Input (CT)
Pluggable RJ45 Input 1/ Input 2
Output
Pulse Output: Voltage Range : 24V DC max
Current Capacity : 100mA max
Commercial
Distribution

Pulse Duration : Selectable Between 0.1 to 2.0sec


Pulse Weight : Selectable between 0.01 to 9.99kWh
Accuracy of meter
Measurement Accuracy
Voltage VL-N 0.5% of full range
Voltage VL-L 0.5% of full range
Current A 0.5% of full range
Frequency
For L-N Voltage >20V 0.1% of full range
For L-L Voltage >35V"
Active power 1.0% of full range
Apparent Power 1.0% of full range
Reactive Power 1.0% of full range
Power Factor ±0.01% of full Range
Active Energy 1.0% of full range
Reactive Energy 1.0% of full range
Max/Min Active Power 1.0% of full range
Max/Min Reactive Power 1.0% of full range
Max Apparent Power 1.0% of full range
Power Consumption Less than 8VA

Dual & Triple Meter Incomers

Dimensions (mm)
Height Width Depth
Height

JKD125MID 450 930 132.5


JKD125TMID 450 1395 132.5
N L1 L2 L3
JKD250MID 625 930 165.5
JKD250TMID 625 1395 165.5

Width Depth
Height

N L1 L2 L3

Width Depth

TP&N Board Meter Enclosures


Width
Height

JKD1125MID 300 465 132.5


JKD2250MID 300 465 165.5

76 Data is subject to errors and technical modifications.


Invicta 3 Panelboard - 250A Rated, Extension Boxes
Dimensions

Primary Boards

Dimensions (mm)
ISOLATE BEFORE
REMOVING COVER
Height Width Depth Spare Door Cat Refs
L1
JN204B/G 950 710 160 JN204BG/D
L2

L3
JN206B/G 1100 710 160 JN206BG/D
L1

L2
JN208B/G 1100 710 160 JN208BG/D
L3
JN212B/G 1250 710 160 JN212BG/D
JN216B/G 1550 710 160 JN216BG/D
ISOLATE BEFORE

Commercial
Height

Distribution
REMOVING COVER

1 7

2 8
1 7
3 9
2 8
4 10

Terminals
3 9
5 11
4 10
6 12
5 11

6 12

B1

B2

L1 L2 L3
B3

Neutral Earth Bond


2 x 6 x 50mm 2 x 6 x 50mm 1 x 3 x 50mm
2 x 9 x 50mm 2 x 9 x 50mm 1 x 3 x 50mm
2 x 12 x 50mm 2 x 12 x 50mm 1 x 3 x 50mm
2 x 18 x 50mm 2 x 18 x 50mm 1 x 3 x 50mm
2 x 24 x 50mm 2 x 24 x 50mm 1 x 3 x 50mm
Depth

Cables outgoing ways:


25 - 50mm2 CSA Flex
25 - 70mm2 CSA Solid

Width MCCB Connections M8


Earth M8
Neutral M8
Height

Depth

Width

Extension Boxes

Dimensions (mm)
Height Width Depth
JN201BE/G 300 710 160
JN203BE/G 450 710 160
JN205BE 300 710 130
JN206BE 450 710 130

Data is subject to errors and technical modifications. 77


Invicta 3 Panelboard - 400A, 630A, 800A Rated
Dimensions

Primary Boards

Dimensions (mm)
Height Width Depth Spare Door Cat Refs
ISOLATE BEFORE
REMOVING COVER
JF406B/G 1250 900 220 JF812BG/D
L1
JF408B/G 1250 900 220 JF812BG/D
L2

L3
JF412B/G 1400 900 220 JF814BG/D
JF416B/G 1550 900 220 JF815BG/D
L1

L2

L3

L1 JF418B/G 1700 900 220 JF817BG/D


L2
Commercial

JF808B/G 1250 900 220 JF812BG/D


Distribution

L3

JF812B/G 1400 900 220 JF814BG/D


Height

JF818B/G JF817BG/D
ISOLATE BEFORE

1700 900 220


REMOVING COVER

JF60204B/G 1250 900 220 JF812BG/D


1

3
1 10
10

11

12
JF80206B/G 1250 900 220 JF812BG/D
2 11

JF80404B/G 1250 900 220 JF812BG/D


4 13
3 12
5 14
4 13
6 15
5 14
7 16
6 15
8 17

JF80210B/G 1400 900 220 JF814BG/D


7 16
9 18
8 17

9 18

B1

B2

B3
JF80408B/G 1400 900 220 JF814BG/D
JF80414B/G 1700 900 220 JF817BG/D
L1 L2 L3
JF80612B/G 1700 900 220 JF817BG/D

Terminals

Depth Neutral Earth Bond


2 x 9 x 50mm 2 x 9 x 50mm 1 x 3 x 50
2 x 12 x 50mm 2 x 12 x 50mm 1 x 3 x 50
2 x 18 x 50mm 2 x 18 x 50mm 1 x 3 x 50
2 x 24 x 50mm 2 x 24 x 50mm 1 x 3 x 50
2 x 12 x 50mm 2 x 12 x 50mm 1 x 3 x 50
Width 2 x 18 x 50mm 2 x 18 x 50mm 1 x 3 x 50
2 x 27 x 50mm 2 x 27 x 50mm 1 x 3 x 50
2 x 6 x 50mm 2 x M8 Bolt 2 x 9 x 50mm 1 x 3 x 50
2 x 9 x 50mm 2 x M8 Bolt 2 x 12 x 50mm 1 x 3 x 50
2 x 6 x 50mm 4 x M8 Bolt 2 x 12 x 50mm 1 x 3 x 50
2 x 15 x 50mm 2 x M8 Bolt 2 x 18 x 50mm 1 x 3 x 50
2 x 12 x 50mm 4 x M8 Bolt 2 x 18 x 50mm 1 x 3 x 50
2 x 21 x 50mm 4 x M8 Bolt 2 x 27 x 50mm 1 x 3 x 50
2 x 18 x 50mm 6 x M8 Bolt 2 x 27 x 50mm 1 x 3 x 50

Cables outgoing ways:


25 - 50mm2 CSA Flex
25 - 70mm2 CSA Solid

MCCB Connections:
400A M10
630A M12

Earth:
400A M10
630A M10
Height

Extension Boxes

Dimensions (mm)
Height Width Depth
JF801E/G 300 900 220
Depth
JF803E/G 450 900 220
JF805E 300 900 158
JF806E 450 900 158

Width

78 Data is subject to errors and technical modifications.


Invicta 3 Panelboard - 800A Rated
Dimensions, Metering Method Chart

Primary Boards

Dimensions (mm)
Height Width Depth
JHF812B/G 2050 900 220
JHF818B/G 2200 900 220
JHF80206B/G 1900 900 220
JHF80404B/G 1900 900 220
JHF80210B/G 2050 900 220

Commercial
JHF80408B/G 2050 900 220

Distribution
Height

JHF80414B/G 2200 900 220


JHF80612B/G 2200 900 220

Depth

Width

Invicta 3 Panelboard Metering Example

Example below: 250A, 6 way panelboard, requiring 4 outgoing meters (not including incomers & outgoers).

Step Selection method Order code Quantity


1 Select panelboard JN206BG 1
eg. 6 way with glazed door
2 Identify quantity of meters required ECM01 4
eg. 4 metered ways modbus
(If MID required, use HGR96EWC)
3 Select position for meter enclosure (Top or side) JN11004SM 1
eg. Side - 6/8 Way JN Board 4xDIN 96 Cut-Outs
(If top mount required, use JN4506TM)
4 Number of blanking plates required JF96BP 2
eg. Side - 6/8 Way JN Board 4xDIN 96 Cut-Outs
5 Meter voltage supply cable. JN130VMF 1

6 Supply cable for remaining meters PGMFT150 3


(Link meter to meter)
7 Identify which CT's are required EC12100CT 4
eg. 100 Amp

Data is subject to errors and technical modifications. 79


Invicta 3 Panelboard, Enclosed ATS
Technical Data

Characteristics 250A 400A 630 / 800A 800A


Series JN2** JF4** JF6**/JF8** JHF8**
Busbar current rating 250A 400A 800A 800A (for 800A MCCB only)
Busbar type Type B Fully Shrouded Copper
Busbar rated short-time with-
25kA for 1 sec 35kA for 1 sec 35kA for 1 sec 35kA for 1 sec
stand current
Internal separation Form 3A
Incoming Up to 250A MCCB, MCS Up to 400A MCCB, MCS Up to 630A MCCB, 800A LBS 800A MCCB
16 - 125A 16 - 125A
Outgoing 16 - 125A max. 16 - 125A max.
Commercial
Distribution

100A - 250A 100A - 250A


Voltage rating in A.C. 415V 415V 415V 415V
IP Protection IP30
Enclosure body type Steel
Enclosure paint type Powder coat Grey White BS 4800 00A01
Cable entry Via Gland Plates
Terminal Connection capacity
Incoming earth terminal M8 M10 M10 M10
Incoming neutral terminal M8 M12 M12 M12
Outgoing earth terminals Up to 50mm² Up to 50mm² Up to 50mm² Up to 50mm²
16A - 125A: Up to 50mm2 16A - 125A: Up to 50mm2
Outgoing neutral terminals Up to 50mm² Up to 50mm²
100A - 250A: M8 Stud 100A - 250A: M8 Stud
Enclosure earth stud M8 M10 M10 M10
Installation
Mounting Surface (Wall)

D Enclosed ATS
W

Dimensions (mm)
Width Height Depth Weight
JK140ATS 465 450 132.5 10.5
H JK163ATS 465 450 132.5 10.5
JK180ATS 465 450 132.5 10.5
JK100ATS 465 450 132.5 10.5
JK125ATS 465 450 132.5 10.5

80 Data is subject to errors and technical modifications.


JF/JN Meter Enclosures
Dimensions

Corner Filler Enclosures Width Depth

Dimensions (mm)
Width Height Depth Number of
JF cutouts
JF300CF 350 300 160 -

Height
JF450CF 350 450 160 -

JN

Commercial
JN300CF 300 710 160 -

Distribution
JN450CF 450 710 160 -

Top/Bottom Enclosures

Width
Dimensions (mm)
Width Height Depth Number of
JF cutouts
JF3004TM 900 300 160 4

Height
JF4508TM 900 450 160 8

JN
JN3003TM 710 300 130 3
JN4506TM 710 450 130 6

Side Enclosures
Depth

Dimensions (mm)
Width Height Depth Number of
JF cutouts
JF12504SM 350 1250 160 4
JF14006SM 350 1400 160 6
JF15508SM 350 1550 160 8
JF17009SM 350 1700 160 9

JN
JN9502SM 350 950 143 2
JN11004SM 350 1100 143 4
JN12506SM 350 1250 143 6
JN15508SM 350 1550 143 8

Width Depth
Height

Data is subject to errors and technical modifications. 81


Multi-Function Meter - ECM01
Single CT Connection, DIN 96

- 96 x 96mm Flush mounting - 3-phase: 140…460Vac measured voltage


- Single phase or 3 phase (4 wire) network balanced or unbalanced load - Single phase: 80…265Vac measured voltage
- Built in energy pulsed output or with pulsed output and RS485 (modbus) - THD up to 31st harmonic for voltage and current
- Backlit LCD display with bargraph current indication on every page - Self supplied auxiliary
- Automatic or manual scrolling display - Programmable CT ratio 5 to 10,000A
- 330mV current transformer input - Frequency 45/65Hz
- Active energy class 1 (EN62053-21) - Wide range of measured parameters (see table below)
- Reactive energy class 2 (EN62053-23) - Selectable CT phase correction allows reversal of L1 and L3
- Programmable VT ratio - Weight 230g

Function Diagram
Commercial
Distribution

Voltage Current Voltage Power Factor Active Power Active Energy


current and power factor
line to neutral and average phase and average of phase 1 & frequency 3-phase and average 3-phase and total 3-phases

Voltage Current Voltage Reactive Power Apparent Energy


line to line and average Maximum Demand current and power factor 3-phase and total 3-phases
of phase 2 & frequency

THD Voltage THD Current Voltage Apparent Power Reactive Energy


line to neutral and average phase and average current and power factor 3-phase and total 3-phases
of phase 3 & frequency

THD Voltage Average Voltage Active, Reactive, Apparent


line to line and average current and power factor Power and Power Factor
of 3-phases & frequency first phase
Active, Reactive, Apparent
Power and Power Factor
ECM01
second phase
Active, Reactive, Apparent
Power and Power Factor
third phase
Total Active, Reactive, Apparent
Power & Average Power Factor
three phases
Max. Active Power Demand,
Reactive Power Demand and
Apparent Power Demand

Min. Active Power Demand


Button Selection and Reactive Power Demand
Dimensions Diagram (mm)

91.5 96

91.5 96 50 5
Please allow space at the rear of the meter for cable connections.

82 Data is subject to errors and technical modifications.


Multifunction Meter - JKM01
Single CT Connection, DIN Rail Mounted

- 4 Module DIN rail mounting - 3-phase: 140…460Vac measured voltage


- Single phase or 3 phase (4 wire) network balanced or unbalanced load - Single phase: 80…265Vac measured voltage
- Built-in energy pulse output and RS485 MODBUS communication - Self supplied auxiliary
- Wide range of measured parameters (see table below) - Programmable CT ratio 5…10,000A
- High quality backlit LCD display - Programmable VT ratio
- 330mV current transformer input - Frequency 45/65Hz
- Active energy class 1 (EN62053-21) - Selectable CT phase correction allows reversal of L1 and L3
- Reactive energy class 2 (EN62053-23) - Weight 190g
- THD up to 31st harmonic for voltage and current

Commercial
Distribution
Function Diagram

x1 x2 x3 x4

3 Phase Average Power Factor 3 Phase Average


Line to Neutral Voltage Voltage Current Frequency Average Power Factor Three Phases
3 Phase Active Energy - kWh Line to Neutral Per Phase Per Phase L - N Voltage and Current Frequency

Home Page Power Factor 3 Phase Average


(Unit will default to this Voltage Frequency Average Active Power
page after 60 seconds) Line to Line Per Phase L - L Voltage and Current Three Phases

Reactive Power
Three Phases

Apparent Power
Three Phases
1
Current
Input 1 2 3 4 5 6 7

Active Power
Total
JKM01

Avg PAGE
Reactive Power
kW h L-N V
Total
PRG

Apparent Power
100%
INT
Total

Active Power
8 9 10 11 12 13 14 15 16 17 18 19
Max. Demand

Button Selection Apparent Power


Max. Demand

Dimension Diagrams (mm)

90 95 45

70 67
Please allow space above and below the meter for cable connections.

Data is subject to errors and technical modifications. 83


Multifunction Meter - JKM02
Dual CT Connection, Panel Mounting

- Split Load, Dual CT input meter - High quality backlit LCD display - Self supplied auxiliary
- 4 Module DIN rail mounting - 330mV current transformer input - Programmable CT ratio 5…10,000A per load
- Single phase or 3 phase (4 wire) network - Active energy class 1 (EN62053-21) - Programmable VT ratio
balanced or unbalanced load - Reactive energy class 2 (EN62053-23) - Frequency 45/65Hz
- Built-in dual energy pulse output, one for each - THD up to 31st harmonic for voltage and - Selectable CT phase correction allows reversal
load and RS485 MODBUS communication current of L1 and L3
- Wide range of measured parameters (see table - 3-phase: 140…460Vac measured voltage - Weight 200g
below) - Single phase: 80…265Vac measured
voltage

Function Diagram
Commercial
Distribution

x1 x2 x3 x4

3 Phase Average L-N Voltage Power Factor 3 Phase Average 3 Phase Average L-N
Active Energy kWh - Load 1 Voltage Current Frequency Active Energy
Active Energy kWh - Load 2 Line to Neutral Per Phase Per Phase - Load 1 Load 1 Load 1 and 2
Home Page As above - Load 2 3 Phase Average L-N
(Unit will default to this Voltage Current Reactive Energy
page after 60 seconds) Line to Line Per Phase Per Phase - Load 2 Active Power Load 1 and 2
Three Phases
Load 1
As above - Load 2
Reactive Power
Three Phases
1 1
Load 1
Current Current

As above - Load 2
Input 1 Input 2 1 2 3 4 5 6 7

Apparent Power
JKM02
Three Phases
Load 1
Avg PAGE

1
kW h L-N V
As above - Load 2
PRG
2
Total Active Power
Three Phases
100%
INT
Load 1 and 2
Total Reactive Power
Three Phases
8 9 10 11 12 13 14 15 16 17 18 19
Load 1 and 2
Total Apparent Power
Button Selection Three Phases
Load 1 and 2
Active Power
Max. Demand
Load 1 and 2
Active Power
Max. Demand
Load 1 and 2
Dimension Diagrams (mm)

90 95 45

70 67

Please allow space above and below the meter for cable connections.

84 Data is subject to errors and technical modifications.


Standard CT to Plug-in Adaptor - JFA03
Technical Data

- Connect up to three standard or split core CT’s (1A or 5A secondaries)


- Integrated protection circuitry

Standard CT to plug-in Adaptor Technical Specification


The JFA03 converter allows for the connection of up to three standard current Burden: <2VA per channel (5A Version)
transformers, or standard split-core current transformers (with 1A or 5A <0.5VA per channel (1A Version)
secondary’s), to the plug-in system.
Accuracy: 0.4%
The unit has integrated protection circuitry allowing for disconnection from
meter under load conditions for maintenance. Suggested Cable Size: 1.5mm2 or 2.5mm2 (2.5mm2 Max.)
(CT to Adaptor)

Commercial
Distribution
Mounting: DIN rail 35mm

Important Note Termination: CT to adaptor - Rising clamp


This converter does not provide electrical isolation. screw terminals
Current transformer secondaries may not be earthed and should be wired as Adaptor to Meter - RJ45 Patch Cable
shown. Operating Temperature: –10°C…+45°C
Storage Temperature: –25°C…+70°C

330mV

Converter
5A or 1A secondary
S1 S2 S1 S2 S1 S2

S1 S2
Meter

S1 S2
Plug-in Energy Meter
CT 1
S1 S2

CT 2

3 x Standard
Current Transformers CT 3

Dimension Diagrams (mm)

90 45

53 58

Data is subject to errors and technical modifications. 85


Three Phase Measuring CTs
Technical Data

Description Installation
Designed for use with Hager x160 MCCBs and the plug-in multifunction The CT uses plug-in technology allowing much faster installation, saving you
power meters. time and money. Additionally, all our three phase current transformers have
been designed with hole centres and apertures to fit most standard industrial
Internal safety circuitry is provided which limits the output voltage to a safe circuit breakers.
level, allowing the transformer secondary to be left disconnected under load.

EC1260CT, EC12100CT, EC2560CT, EC25100CT, EC2512CT, EC40250CT, EC40400CT, EC80800CT


EC12125CT, EC12160CT EC25160CT, EC25200CT, EC25250CT EC40630CT
Commercial
Distribution

Accuracy Class 1 1 1 1
Aperture 3 @ 15.5 x 30mm 3 @ 21 x 25mm 3 @ 31 x 31mm 3 @ 54 x 50mm
Width 75mm 105mm 140mm 215mm
Primary Current 60 to 160A 60 to 250A 250 to 630A 800A
Hole Centres 25mm 35mm 45mm 70mm
Housing Material Self extinguishing Nylon IEC185 classification VO according to UL-94
Reference Standard EN6004-8

Weight 500g 550g 680g 1200g

EC1260CT, EC12100CT, EC2560CT, EC25100CT, EC40250CT, EC40400CT, EC80800CT


EC12125CT, EC12160CT EC2512CT, EC25160CT, EC40630CT
EC25200CT, EC25250CT

Current Transformer Ratios Current Transformer Ratios Current Transformer Ratios Current Transformer Ratios
Primary Primary Primary Primary
Current Output Current Output Current Output Current Output
60 330 060 60 330 060 250 330 250 A mV Code
100 330 100 100 330 100 400 330 400 800 330 800
125 330 125 125 330 125 630 330 630 330mV Secondary
160 330 160 160 330 160 330mV Secondary
330mV Secondary 200 330 200
250 330 250
330mV Secondary

EC2560CT, EC25100CT,
EC1260CT, EC12100CT, EC2512CT, EC25160CT, EC40250CT, EC40400CT,
EC12125CT, EC12160CT EC25200CT, EC25250CT EC40630CT

76.00 Hole appertures 30 x 15mm 54 54

60.00 38 105 38 140


76.00
90
80.00

80

31
25

16
27.50

16

31 45
21 35

25.00

EC80800CT

54
38 215
124
50
24

54 70

86 Data is subject to errors and technical modifications.


Essential Extras & Accessories
Technical Data

CT Output and RJ45 Lead Tester 3 Phase CT Splitter Box


This device makes it possible to test the RJ45 patch lead used to connect the This 3 Phase CT Splitter Box allows the separate monitoring of each phase of
current transformer to the meter. It also enables a standard electricians multi- a three phase current transformer on individual energy meters.
meter to measure the individual secondary outputs of the current transformer. Model Reference: JFS03
To test the RJ45 patch lead, simply disconnect the lead
from the meter and current transformer. Plug one end into socket 1 and the oth-
er end into socket 2 on the test box. Press the test button - the Green LED will
light to indicate the lead is OK or the Red LED will light to indicate a faulty lead.
When the lead is proven to be OK you can then check the individual second-
ary outputs of the current transformer. To measure the secondary output plug
one end of the RJ45 patch lead into the current transformer and the other end 3 Phase CT Splitter Box
into socket 2 on the test box. You can now use a standard multimeter to test To Single Phase Meters

Commercial
Distribution
the secondaries using the test points on the front of the test box. The output
measured for each phase should be between 0 and 330mV A.C.
Model Reference: JFT03 L3 L2 L1 CT

CT
Meter Meter Meter
1 2 3

Meter Voltage Supply Cable Meter to Meter Supply Cable RJ45 Connection Cable
Our high quality Meter Voltage Supply Cables are Our high quality Meter to Meter Voltage Supply The high quality low loss Category 5e RJ45 Connec-
fitted with a plug at one end and insulated bootlace Cables are fitted with a plug at one end and socket tion Cable provides secondary connection between
ferrules at the other and provide power to the plug-in at the other. This allows multiple plug-in meters to be the plug-in current transformer and meter.
meter from your mains supply. energised from a common supply. Up to 32 meters
can be powered in a ‘daisy chain’ arrangement using
this method.

Two type of cable material are available:- LSZH (Low


Smoke Zero Halogen).

Data is subject to errors and technical modifications. 87


Fuse Combination Switches, Switch Disconnectors
Dimensions

Fuse Combination Switches Switch Disconnectors

All dimensions are in mm and exclude the handle. All dimensions are in mm and exclude the handle.
Add 45mm to the depth to allow for the handle (110mm for 630 / 800A)
3 Pole Dimensions (mm)
SPSN Dimensions (mm) Description Width Height Depth Handle
Description Width Height Depth Depth
JFB202U 20A SPSN 200 250 150 JAC316 160A TPN 250 300 150 195
JFB203U 32A SPSN 200 250 150 JAE320 200A TPN 375 400 200 245
JFD206U 63A SPSN 300 325 150 JAE325 250A TPN 375 400 200 245
JFE210U 100A SPSN 375 400 200 JAG331 315A TPN 375 500 200 245
Commercial
Distribution

JAG340 400A TPN 375 500 200 245


JAH363 630A TPN 500 650 300 345
JAH380 800A TPN 500 650 300 345
TPN Dimensions (mm)
Description Width Height Depth
JFB302U 20A TPN 200 250 150
4 Pole Dimensions (mm)
JFB303U 32A TPN 200 250 150
Description Width Height Depth Handle
JFD306U 63A TPN 300 325 150 Depth
JFE310U 100A TPN 375 400 200 JAB402B 20A TPSN 175 232 65 78
JFG312U 125A TPN 375 500 200 JAB403B 32A TPSN 175 232 65 78
JFG316U 160A TPN 375 500 200 JAB406B 63A TPSN 175 232 65 81
JFG320U 200A TPN 375 500 200 JAB410B 100A TPSN 200 300 80 97
JFG325U 250A TPN 375 500 200 JAC412B 125A TPSN 200 300 80 97
JFH331U 315A TPN 500 650 300 JAC416 160A TPSN 250 300 150 195
JFH340U 400A TPN 500 650 300 JAE420 200A TPSN 375 400 200 245
JFI363U 630A TPN 600 800 350 JAE425 250A TPSN 375 400 200 245
JFI380U 800A TPN 600 800 350 JAG431 315A TPSN 375 500 200 245
JAG440 400A TPSN 375 500 200 245
JAH463 630A TPSN 500 650 300 345
JAH480 800A TPSN 500 650 300 345
TPSN Dimensions (mm)
Description Width Height Depth
JFB402U 20A TPSN 200 250 150
JFB403U 32A TPSN 200 250 150
JFD406U 63A TPSN 300 325 150
JFE410U 100A TPSN 375 400 200
JFG412U 125A TPSN 375 500 200
JFG416U 160A TPSN 375 500 200
JFG420U 200A TPSN 375 500 200
JFG425U 250A TPSN 375 500 200
JFH431U 315A TPSN 500 650 300
JFH440U 400A TPSN 500 650 300
JFI463U 630A TPSN 600 800 350
JFI480U 800A TPSN 600 800 350

Cable Extension Boxes for Fuse Combination Switches

Dimensions (mm)
Rating Width Height Depth
JZA701 125 / 250A 375 200 200
JZA702 315 / 400A 500 250 300
JZA703 630 / 800A 600 300 350

88 Data is subject to errors and technical modifications.


Fuse Combination Switches
Technical Data

Thermal current lth (40ºC) 20A 32A 63A 100A 125A 160A 200A
Fuse size: BS A1 A1 A2-A3 A4 B1-B2 B1-B2 B1-B3
Rated insulated voltage
Ui (V) 800 800 800 800 800 800 800
Impulse voltages Uimp 8000 8000 8000 8000 8000 8000 8000 8000 8000 8000 12000 12000 -
Operational current Ie (A) A B A B A B A B A B A B A B
415V ac AC-22A/AC-23B 20 20 32 32 63 63 100 100 125 125 160 160 200 200
Motor power (kW) 400V ac 9 15 30 51 63 80 100
Reactive power 400V ac (kVAr) 15 45 25 45 55 60 75

Commercial
Distribution
Overload capacity
Short-circuit with fuses (kA RMS) 50 50 50 50 50 50 50
Fuse rating (A) BS 88 20 32 63 100 125 160 200
Making & Breaking Capacity
Breaking capacity 400V AC-23B
160 256 500 800 1000 1280 1600
(A RMS)
Making capacity 400V AC-22
200 320 630 1000 1250 1600 2000
(A RMS)
Withstand mechanical
20,000 20,000 10,000 10,000 10,000 10,000 10,000
(number of operations)
Tightening torque 2 2 6 9 9 9 20
Connection (mm2)
Minimum Cu cable section 2.5 2.5 10 25 35 50 70
Maximum Cu cable section 16 16 25 95 95 95 240
Maximum terminal lug selection - - - M8 M8 M8 M10
Fuse types NIT20 NIT32 TIS63 TCP100 TF125 TF160 TF200

Thermal current lth (40ºC) 250A 315A 400A 630A 800A


Fuse size: BS B1-B3 B1-B4 B1-B4 C1-C2 C1-C2-C3
Rated insulated voltage Ui (V) 800 800 800 1000 1000
Operational current Ie (A)
A = Frequent operation
B = Infrequent operation A B A B A B A B A B
415V A.C. AC-22A/AC-23B 250 250 315 315 400 400 630 630 800 800
Motor power (kW) 400V A.C. - 160 160 220 220 355 355 -
Reactive power 400V A.C. (kVAR) - 125 150 2 x 125 -
Overload capacity
Short-circuit with fuses (kA Rms) 50 50 50 50 50
Fuse rating (A) BS 88 250 315 400 630 800
Making & Breaking Capacity
Breaking capacity 400V AC-23B
2000 2520 3200 - -
(A R.M.S)
Making capacity 400V
2500 3150 4000 - -
AC-23B (A R.M.S)
Withstand mechanical
10,000 10,000 10,000 8000 8000
(number of operations)
Tightening torque (Nm) - 20 20 40 40
Connection (mm2)
Minimum Cu cable section 70 185 185 2 x 150 2 x 150
Maximum Cu cable section 240 240 240 2 x 300 2 x 300
Maximum terminal lug selection M10 M10 M10 M12 M12
Fuse types TKF250 TKF315 TMF400 TTM630 TLM800

Data is subject to errors and technical modifications. 89


Fuse Combination Units
Technical Data

Fuse - Combination Units - BS EN 60947-3 Utilisation categories


Many people are attracted to fuse-combination units by their Utilisation categories are not new but they are important because they help
simplicity in application and their reliability in operation. They are particularly the designer or specifier identify the correct unit for a particular application.
useful for use on very high prospective fault level systems where the high
energy limiting characteristic of the HRC fuse can be effectively utilised. The designation of the utilisation category is made up of three parts:
In the past fuse-combination units came in two forms:
1. The prefix AC or DC, which indicates the nature of the current.
Switch Fuse A switch in which one or more poles 2. The two digit number, which indicates the type of application
have a fuse in series. the unit is suitable for:
20 Connecting and disconnecting under no-load.
21 Switching of resistive loads.
22 Switching of mixed resistive and inductive loads.
Commercial
Distribution

Fuse Switch A switch in which one or more poles 23 Switching of highly inductive loads.
have a fuse carrier/link which forms the 3. The suffix A or B, which indicates whether the unit is suitable
moving contact. for frequent or infrequent operation.
A Frequent operation
B Infrequent operation.
The definitions of these two basic types of fuse combination units have now
been extended to include units suitable for making, For example a fuse-combination unit feeding a 400V AC circuit of mixed
breaking and isolation and units which are only suitable for providing isolation resistive and inductive loads which would need to be operated frequently
for maintenance work. would require a minimum utilisation category of AC-22A.

If the load was highly inductive, i.e. motor loads, then the minimum utilisation
Definition Symbol Function
category would be AC-23A.
Switch Fuse Making and
breaking current Generally, category AC-23 does not cover the switching of capacitors.
Usually this is the subject of agreement between manufacturer and user.

Disconnector Fuse Isolating Motor Power Circuit Protection


Fuse-combination units can be used very effectively for motor power circuit
protection, the energy limiting HRC fuse offering very good protection to its
associated starter. Category AC-23A should be specified for this duty.
Switch Disconnector Making, breaking and
Special motor circuit protection fuse links are available which eliminate the
Fuse isolating
need to fit a larger bodied fuse just to take care of the starting current of the
motor.
Fuse Switch Making and
breaking current The protection of motor power circuits should not be confused with the direct
switching of a single motor. If a fuse-combination unit is required to perform
this function then it must comply with the requirements of Appendix A of BS
Fuse Disconnector Isolating EN 60947-3 which makes provision for different utilisation categories for this
application.

Fuse Switch Making, breaking and


Disconnector isolating

However, in order to keep the selection of fuse-combination units as simple as


possible, Hager offer a range of high performance double break switch-fuses,
which also satisfy the isolating requirement of the British standard. These are
correctly shown as and defined as a Fuse Combination Switch.

Switch disconnectors - BS EN 60947-3. A range of switch disconnectors


(isolators) are available for use on lower current ratings from 20A to 125A.
These switches are rated at AC-22 and provide a cost effective alternative to
the fuse combination switch, especially where the utilisation category AC-23
is not required. ie; mixed resistive and inductive loads.

90 Data is subject to errors and technical modifications.


Switch Fuses & IP65 Enclosed Isolating Switch
Dimensions

Width Depth Switch Fuses

Dimensions (mm)
Width Height Depth Depth with Door Knockouts
Height

IU44-16 115 187 61.5 - 2 x 25mm


IU44-18 125 312 73.5 - None
IU44-11 125 312 73.5 - None
IU44-16-D 125 312 74 96 None
IU44-18-D 125 312 74 96 None

Commercial
IU44-11-D 125 312 74 96 None

Distribution
IP65 Enclosed Isolating Switch

All dimensions are in mm and exclude the handle.


Add 27mm to the depth to allow for the handle on 10-25A products.
Add 32mm to the depth to allow for the handle on 40-80A products.

Dimensions (mm)
Description Width Height Depth
JG00S 10A TPN 100 136 74
JG01S 16A TPN 100 136 105
JG02S 25A TPN 100 136 105
JG03S 40A TPN 136 201 105
JG04S 63A TPN 136 201 118
JG05S 80A TPN 136 201 118

Enclosed thermal current lthe 16 25 40 63 80


Rated insulation voltage Ui (V) 690 690 690 690 690
Rated thermal current lthe (A) 25 40 63 80 100
Rated operational current
AC21 400V Ie (A) 25 40 63 80 100
AC22 400V 16 25 40 63 100
AC22 400V cos phi 0.65 16 20 32 63 100
AC23 400V 16 20 32 63 100
AC23 400V cos phi 0.35 16 15 25 40 63
Rated operational power
AC23 230V (kW) 4 5.5 7.5 11 15
AC23 400V 7.5 11 15 22 30
Rated fused short circuit current
Back-up fuse (A) 63 63 63 80 100
R.M.S value Ik (kA) 50 50 50 50 50
Peak value (kA) 5.4 6.6 7.2 8.3 8.7
Rated short circuit making capacity (Icm) (kA) 690V 2.5 2.5 2.5 3.3 3.3
Rated short time withstand current (lcw) (kA) 690V (1s) 1 1.1 1.6 1.7 2.3
Rated breaking capacity Icn (A) AC23
400V cos phi 0.35 250 270 320 480 504
Electrical endurance (number of operations) 3000 3000 3000 3000 -
Mechanical endurance (number of operations) 50,000 50,000 50,000 50,000 -
Terminals mm2 1.5 - 16 1.5 - 16 1.5 - 16 2.5 - 35 2.3 - 35
Max. thermal torque (Nm) 1.8 1.8 1.8 2.5 2.5

Data is subject to errors and technical modifications. 91


Switch Disconnectors
Technical Data

Enclosed thermal
20 32 63 100 125 160 200 250 315 400 630 800
current lthe
Rated insulation
800 800 800 800 800 800 800 800 800 800 1000 1000
voltage Ui (V)
Rated thermal
20 32 63 100 125 160 200 250 315 400 630 800
current lthe (A)
Rated operational current
AC21A 500VAC 20 32 63 100 125 160 160 250 250 250 630 800
AC22A 500VAC 20 32 63 100 125 125 125 250 250 250 500 800
AC21A 690VAC 20 32 63 100 125 160 160 200 200 200 500 800
Commercial
Distribution

AC22A 690VAC 20 32 63 100 125 125 125 125 125 125 315 800
Overload capacity
Icw rated short time
1.26 1.26 1.5 1.5 7 7 7 9 9 9 13 26
withstand value (kA)
R.M.S value (kA) 0.16 0.256 0.504 0.64 1 1.28 1.28 2 2 2 5.04 6.4
Peak withstand value
- - - - 20 20 18 30 23 23 45 55
(kA)
Rated short circuit
making 1.8 1.8 2.1 2.1 11.9 11.9 11.9 15.3 15.3 15.3 26 54.6
capacity (kA)
Rated impulse
withstand voltage 8 8 8 8 8 8 8 8 8 8 12 12
Uimp (kV)
Mechanical
endurance
100,000 100,000 100,000 100,000 10,000 10,000 10,000 10,000 10,000 5,000 5,000 5,000
(number of
operations)
Maximum cable size 16 16 50 50 50 95 95 150 185 240 2 x 300 2 x 300
Tightening torque
2 2 4 4 9 9 9 20 20 20 20 -
(Nm)

Product Reference JAB402B JAB403B JAB406B JAB410B JAC412B


Thermal Current In 20A 32A 63A 100A 125A
Switch 3PSN 3PSN 3PSN 3PSN 3PSN
Rated Insulation Voltage Ui 800V 800V 800V 800V 800V
Rated Impulse Voltage Uimp 8kV 8kV 8kV 8kV 8kV
Dimensions
Height (mm) 232 232 232 232 300
Width (mm) 175 175 175 175 200
Depth (mm) 81 81 81 81 83
Operational Current Ie (A)
415V AC - AC21A / AC21B 20/20 32/32 63/63 100/100 125/125
415V AC - AC22A / AC22B 20/20 32/32 63/63 100/100 125/125
415V AC - AC23A / AC23B 20/20 32/32 63/63 100/100 125/125
500V AC - AC21A / AC21B 20/20 32/32 63/63 100/100 125/125
500V AC - AC22A / AC22B 20/20 32/32 63/63 100/100 125/125
500V AC - AC23A / AC23B 20/20 25/25 63/63 80/80 100/100
690V AC - AC21A / AC21B 20/20 32/32 63/63 100/100 125/125
690V AC - AC22A / AC22B 20/20 32/32 40/63 80/100 100/126
690V AC - AC23A / AC23B 20/20 25/25 40/40 63/63 63/63
Operational Power in AC-23 (kW)
At 415V AC 9 15 30 45 55
At 500V AC 9 15 30 45 55
At 690V AC 11 15 30 45 55
Overload Capacity
Fuse rating 20 32 63 100 125
Fused Icc 50 50 50 25 25
Icw (kA) 2.5 / 0.3s 2.5 / 0.3s 3.0 / 0.3s 5.0 / 0.3s 5.0 / 0.3s
Ipk (kA) 6 6 9 12 12
Cable Connection
Max Cu cable CSA mm2 16 16 35 70 70

92 Data is subject to errors and technical modifications.


IP Rated Enclosures
Ingress Protection Chart

The IP rating for all low voltage enclosures up to 1000 V A.C. and 1500 V The second character numeral indicates the degree of protection provided
D.C. is defined in identical fashion by the standards EN 60529 - IEC 529. It by the enclosure with respect to harmful effects on the equipment due to the
comprises the letters IP followed by two character numerals and or additional/ ingress of water. An X signifies that the tests are not applicable to the product.
supplementary letters.

The first character numeral indicates the degree of protection


provided by the enclosure against access to hazardous parts by preventing or
limiting the ingress of a part of the human body or an object held by a person
and ingress of solid foreign objects.

The first character numeral: The second character numeral:

Commercial
Distribution
Protection against foreign objects Protection against ingress of water with harmful effects

IP Description IP Description

0 Non-protected 0 Non-protected

1 Protected against solid objects ≥ than 50mm 1 Protected against dripping water

Protected against dripping water when tilted


2 Protected against solid objects ≥ than 12.5mm 2
up to 15º

3 Protected against solid objects ≥ than 2.5mm 3 Protected against spraying water

4 Protected against solid objects ≥ than 1.0mm 4 Protected against splashing water

5 Dust-protected 5 Protected against jetting

6 Dust-tight 6 Protected against powerful jetting

Protected against the effect of temporary


7
immersion

8 Protected against continuous immersion

Additional letter (optional) Additional letter (optional)


Protection of people against access to hazardous parts Specific information on the product

Description Description
A Protected against access to hazardous parts with the H High voltage apparatus
back of the hand M Motion during water test
B Protected against access to hazardous parts with a finger S Stationary during water test
C Protected against access to hazardous parts with a tool W Weather conditions
- ø 2.5mm
D Protected against access to hazardous parts with a tool
- ø 1mm

Data is subject to errors and technical modifications. 93


Enclosed MCCBs
Technical Data

JG36BM, JG37BM,
JG44BM, JG45BM, JG48BM, JG50BS, JG40BM, JG42BS,
Interface Characteristics JG46BS, JG47BS JG49BM, JG51BS JG41BM, JG43BS JG37BR, JG38BR JG45BR
Rated & operational voltage (Un / Ue ) 415V A.C. 50Hz
Rated insulation voltage (Ui ) 690V A.C. 50Hz
Rated impulse withstand voltage (Uimp ) 6kV
630A JG36BM, JG37BBM JG37BR - 160A 375A
-160A JG38BR - 200A
Rated current of the Assembly (InA ) 400A JG40BM, JG42BS,
JG41BM, JG43BS
Commercial

- 250A
Distribution

Rated conditional short-circuit current of 25kA 50kA


50kA
the assembly (Icc )*
Standards - Enclosed MCCB assembly BS EN 61439-2
Standards - MCCB only BS EN 60947-2
Rated frequency (fn) 50 Hz
Pollution degree 3
Types of system earthing for which the
TNC-S, TN-S and TT when installed in an electrical system conforming to BS 7671
ASSEMBLY is designed
Intended locations Indoor use only
Stationary assembly external design Wall mounted
Degree of protection IP30 with cover fitted
Intended use Skilled persons only
Electromagnetic compatibility (EMC)
EMC Environment B
classification
External design Wall-mounted, surface type, enclosed assembly.
Mechanical impact protection IK05
Form of seperation Form 2a
Connection of functional unit:
F (fixed)
Incoming/outgoing circuit protection
Incoming Line Terminal(s) M10 Bolt M12 Bolt M8 Socket Cap Screw M10 Bolt
JG37BM, JG41BM, M8 Socket Cap M10 Bolt
JG43BS - M8 Screw
Socket Cap Screw
Incoming Neutral Terminal M10 Bolt
JG36BM, JG40BM,
JG42BS - M10 Bolt
Enclosure Earth Stud M10 M12 M8 M10

Enclosed MCCB (63A - 125A)

Characteristics
JG25BM, JG26BM, JG27BM, JG27BR, JG28BM, JG29BM,
Series JG30BM, JG31BM, JG32BM, JG33BM, JG30BR, JG34BS,
JG35BS
MCCB 63A to 125A MCCB
MCCB + RCCB Add on block 63A & 100A
Voltage rating in AC 240 / 415 V
IP Protection IP3X
Enclosure body type Steel
Enclosure paint type Powder coat Grey white BS 4800 00A01
Terminal Connection capacity
Maximum terminal capacity 95mm²
Enclosure earth stud M8
Installation
Mounting Wall

94 Data is subject to errors and technical modifications.


Enclosed MCCBs
Technical Data

Width Depth
Height

Commercial
Distribution
Dimensions (mm) (kg)
Height Depth Width Weight
JG25BM 420 106 200 3.9
JG26BM 420 106 200 4.5
JG27BM 420 106 200 4.5
JG27BR 420 106 300 20
JG28BM 420 106 200 3.9
JG29BM 420 106 200 4.5
JG30BM 420 106 200 4.5
JG31BM 420 106 200 3.9
JG32BM 420 106 200 4.5
JG33BM 420 106 200 4.5
JG30BR 420 106 300 8
JG34BS 420 106 200 4.5
JG35BS 420 106 200 4.5
JG44BM 900 151 400 21.9
JG46BS 900 151 400 21.9
JG45BM 900 151 400 23.2
JG47BS 900 151 400 23.2
JG48BM 1130 153 500 29.6
JG50BS 1130 153 500 29.6
JG49BM 1130 153 500 32.1
JG51BS 1130 153 500 32.1
JG36BM 660 135 260 10.5
JG37BM 660 135 260 10.5
JG40BM 660 135 260 10.5
JG42BS 660 135 260 10.5
JG41BM 660 135 260 10.5
JG43BS 660 135 260 10.5
JG37BR 865 120 260 11.5
JG38BR 865 120 260 11.5
JG45BR 1019 151 400 21.9

Torque settings
M8 13Nm
M10 22Nm
M12 45-65Nm

Data is subject to errors and technical modifications. 95


Miniature Circuit Breakers
Technical Data

Electrical Characteristics

MLN MTN NBN NCN NDN HMF* HMC* HMD*


Poles SP+SN SP SP DP TP 4P SP DP TP 4P SP DP TP 4P SP DP TP 4P
Rated Operational Voltage 230 230 230 / 400 230 / 400 230 / 400 230/400
Ue (V)
Nominal Current 6 - 40A 6 - 63A 6 - 63A 0.5 - 63A 0.5 - 63A 80 - 125A
Breaking Capacity (Icn) 6kA 6kA 10kA 10kA 10kA 10kA 15kA
to BS EN 60898
Commercial
Distribution

Breaking Capacity (Ics) 6kA 6kA 7.5kA 7.5kA 7.5kA 7.5kA 7.5kA
to BS EN 60898
Breaking Capacity (Icu) N/A N/A 15kA 15kA 15kA N/A 15kA
to BS EN 60947 Part 2
Breaking Capacity (Ics) N/A N/A 7.5kA 7.5kA 7.5kA N/A 7.5kA
to BS EN 60947 Part 2
Rated Insulation Voltage 500V 500V 500V 500V 500V 500V
Ui (V)
Rated Impulse Voltage 4kV 4kV 6kV 6kV 6kV 6kV
Uimp (kV)
Electrical Endurance 10,000 10,000 cycles
cycles
Connection of Auxiliaries No Yes

Table 1

*Din rail mount only, not for use in fixed busbar distribution boards.

Power Loss
The power loss of MCB’s is closely controlled by the standards and is calculated on the basis of the voltage drop across the main terminals measured at rated
current. The power loss of our circuit breakers is very much lower than that required by the British Standard, so in consequences run cooler and are less affected
when mounted together.

The table below gives the watts loss per pole at rated current.

MCB Rated
current (A) 0.5 1 2 3 4 6 10 13 16 20 25 32 40 50 63

Watts loss per


pole 1.2 1.3 1.5 2.0 1.8 1.4 1.9 2.1 2.5 2.8 3.2 3.8 4.0 4.5 5.1

For use with DC


No. of poles 1 pole 2 poles in series
Because of their quick make and break design and excellent arc quenching
capabilities, our circuit breakers are suitable for DC applications. Range max voltage breaking Max voltage breaking
capacity capacity
The following parameters must be considered: L/R=15ms L/R=15ms
1. System voltage:
MTN 60V 6kA 125V 6kA
Determined by the number of poles connected in series (see Table 14).
NCB NCN NDN 60V 10kA 125V 10kA
2. Short circuit current:
(See Table 14). Table 13

3. Tripping Characteristics:
If the thermal trip remains unchanged the magnetic trip will become less
sensitive requiring derating by √2 the ac value (See Table 14). Characteristic curve B C D

Magnetic strip 50Hz dc 50Hz dc 50Hz dc


Irm1 3In 4.5 In 5In 7.5 In 10 In 15 In
Irm2 5In 7.5 In 10In 15 In 20 In 30 In

Table 14

96 Data is subject to errors and technical modifications.


Miniature Circuit Breakers
Technical Data

Connection
The circuit breaker can have the line\load connected to either the top or bottom terminals

Temperature Derating
MCBs are designed and calibrated to carry their rated current and to operate within their designated thermal time/current zone at 30ºC. Testing is carried out with
the breaker mounted singly in a vertical plane in a controlled environment. Therefore if the circuit breaker is required to operate in conditions which differ from the
reference conditions, certain factors have to be applied to the standard data.

In (A) -25ºC -20ºC -15ºC -10ºC -5ºC 0ºC 5ºC 10ºC 15ºC 20ºC 25ºC 30ºC 35ºC 40ºC 45ºC 50ºC 55ºC 60ºC
0.5 0.72 0.7 0.68 0.66 0.64 0.62 0.6 0.58 0.56 0.54 0.52 0.5 0.48 0.46 0.44 0.42 - -

Commercial
Distribution
1 1.44 1.4 1.36 1.32 1.28 1.24 1.2 1.16 1.12 1.08 1.04 1 0.96 0.92 0.88 0.84 0.8 0.76
2 2.88 2.8 2.72 2.64 2.56 2.48 2.4 2.32 2.24 2.16 2.08 2 1.92 1.84 1.76 1.68 1.6 1.52
3 4.32 4.2 4.08 3.96 3.84 3.72 3.6 3.48 3.36 3.24 3.12 3 2.88 2.76 2.64 2.52 2.4 2.28
4 5.76 5.6 5.44 5.28 5.12 4.96 4.8 4.64 4.48 4.32 4.16 4 3.84 3.68 3.52 3.36 3.2 3.04
6 8.64 8.4 8.16 7.92 7.68 7.44 7.2 6.96 6.72 6.48 6.24 6 5.76 5.52 5.28 5.04 4.8 4.56
10 14.4 14 13.6 13.2 12.8 12.4 12 11.6 11.2 10.8 10.4 10 9.6 9.2 8.8 8.4 8 7.6
13 18.7 18.2 17.7 17.2 16.6 16.1 15.6 15.1 14.6 14.0 13.5 13 12.5 12 11.4 10.9 10.4 9.9
15 21.6 21 20.4 19.8 19.2 18.6 18 17.4 16.8 16.2 15.6 15 14.4 13.8 13.2 12.6 12 11.4
16 23 22.4 21.8 21.1 20.5 19.8 19.2 18.6 17.9 17.3 16.6 16 15.4 14.7 14.1 13.4 12.8 12.2
20 28.8 28 27.2 26.4 25.6 24.8 24 23.2 22.4 21.6 20.8 20 19.2 18.4 17.6 16.8 16 15.2
25 36 35 34 33 32 31 30 29 28 27 26 25 24 23 22 21 20 19
32 46.1 44.8 43.5 42.2 41 39.7 38.4 37.1 35.8 34.6 33.3 32 30.7 29.4 28.2 26.9 25.6 24.3
40 57.6 56 54.4 52.8 51.2 49.6 48 46.4 44.8 43.2 41.6 40 38.4 36.8 35.2 33.6 32 30.4
50 - - - - - 62 60 58 56 54 52 50 48 46 44 42 40 38
63 - - - - - - - - - - - 63 60.5 58 55.4 52.9 50.4 47.9

Diversity Factor - Commercial Distribution boards to BS EN 61439-3


Consideration should be given to the proximity heating effect of the breakers when fully loaded and mounted together in groups.

Adjacent circuit breakers having a load 'on' time exceeding 30 minutes or where the load not exceeding 30 minutes has an 'off' time less than the 'on' time, will
need to have the rated diversity factor applied.

No. of Outgoing Circuits Assumed Loading Factor


2 and 3 0.8
4 and 5 0.7
6 to 9 inclusive 0.6
10 and above 0.5

Frequency
Circuit breakers are designed to operate at a frequency of 50-60Hz. Should the supply differ from this then the following factors should be applied
Thermal – unchanged
Magnetic – value multiplied by coefficient K

F (Hz) 17Hz - 60Hz 100Hz 200Hz 400Hz


K 1 1.1 1.2 1.5

Consideration should be given to the proximity heating effect of the breakers when fully loaded and mounted together in groups. (continuously & simultaneously
loaded).

Data is subject to errors and technical modifications. 97


Miniature Circuit Breakers
Time Current Characteristics

B Curve (BS EN 60898) C Curve (BS EN 60898)


MCBs: MTN rated 6 - 63A MCBs: NCN rated 0.5 - 63A
NBN rated 6 - 63A MLN rated 2 - 32A
HMF/HMC rated 80 - 125A
MCB Curve B Time Current Characteristic
Calibration temperature: 30˚C MCB Curve C Time-Current Characteristic
10000 Calibration temperature: 30°C
10000

1000
Commercial
Distribution

1000

10
100

10
10

1
1
Time in seconds

Time in seconds

0.1
0.1

0.01
1 10 100 0.01
Current in multiple of rated current 1 10 100
Current in multiple of rated current

D Curve (BS EN 60898)


MCBs: NDN rated 6 - 63A
HMD rated 80 - 125A

MCB Curve D Time-Current Characteristic


Calibration temperature: 30°C
10000

1000

100

10

1
Time in seconds

0.1

0.01
1 10 100
Current in multiple of rated current

98 Data is subject to errors and technical modifications.


Miniature Circuit Breakers
Peak Current Cut-off

10 10
80 A, 100 A, 125 A 50 A, 63 A
32 A, 40 A
20 A, 25 A

13 A, 16 A
10 A

5 6A

3 A, 4 A

1 A, 2 A

Commercial
Distribution
0,5 A

1 NBN
NCN
1
MBN
MCN

0.5
Peak cut-off Current in kA

Peak cut-off Current (A)

0.1
0.1 0.5 1 5 10 40
Short Circuit Current (kA)
.1
.1 1 10 100
Short Circuit Current (kA)

Data is subject to errors and technical modifications. 99


Miniature Circuit Breakers
Let-Through Energy

B Curve C Curve

10000 10000
63 A

50 A
63 A
40 A
50 A
32 A
1000 40 A
1000 25 A 32 A

20 A 25 A

16 A 20 A
13 A 16 A
50 A, 63 A

10 A
100 13 A 32 A, 40 A
20 A, 25 A
50 A, 63 A 13 A, 16 A
Commercial

10 A
100
Distribution

32 A, 40 A 10 A
20 A, 25 A 6A
6A 13 A, 16 A 3 A, 4 A
6A
10 A
1 A, 2 A
6A
10 4A
0,5 A
3A

10
2A

NCN
1
NBN
1A

Miniature
1 circuit breaker
0,5 A
DISJONCTEUR 1 MODULE 0.1
Norme IEC 60898 Cou rbe C / Contrainte

Let Through Energy kA²s


Let Through Energy k A² s

0.1
0.01

0.01 0.001

0.001 0.0001
0.1 1 10 100 1000 10000 100000
1 10 100 1000 10000 100000
Icc in A Icc in A

D Curve

10000

63 A
50 A
1000 40 A
32 A

25 A
20 A
16 A 50 A, 63 A
32 A, 40 A
100 13 A 20 A, 25 A
13 A, 16 A
10 A 10 A
6A
3 A, 4 A
6A 1 A, 2 A

10 4A
0,5 A
3A

2A

1 NDN
1A

0,5 A

0.1
Let Through Energy kA² s

0.01

0.001

0.0001
0.1 1 10 100 1000 10000 100000
Icc in A

100 Data is subject to errors and technical modifications.


Miniature Circuit Breakers
Circuit Breaker Auxiliaries

Functions MZ203 Shunt Trip*


Tripping and indication auxiliary contacts are common to the range of multi- Allows tripping of the device by feeding the coil. The contacts also allow for
pole 10kA MCBs, and RCCBs. They should be mounted on the left hand side remote indication of operation.
of the device.
MZ206 Under Voltage Release* (Fig 10)
Auxiliary Contact MZ201 (Fig 9) Allows the MCB to trip when the voltage drops or by pressing a remote off
Allows remote indication of the status of the device contacts to which it is switch (i.e. emergency stop).
associated.
* Indication that the product has tripped due to the voltage release is provided
Auxiliary Contact and Alarm Contact MZ202 by a flag on the product.
This accessory has two separate functions. Like the MZ201 auxiliary contact,
however the alarm contact will provide indication if the breaker trips under MZ206 Under Voltage Release

Commercial
Distribution
fault conditions.
Ph
Wiring Diagram
N
MZ201 Auxiliary Contact and Alarm Contract

Ph
N

MZ206
MZ202
D1
14 22 91 93
U
D2 92 94

MZ 201
13 21 Fig. 10

Electrical connection
Fig. 9 By terminal fitted with fixed clamp screws wiring capacity.
Flexible : 2 x 1.5mm2
Rigid : 2 x 1.5mm2
Electrical Characteristics
MZ203
MZ201/MZ206 MZ203 MZ206 Power - 8VA
tolerance : -15% of Un
1xO1xC
Contact MZ206
230V ~ 6A Latching voltage is between 35 and 70% of Un 230V~
AC-1 Coil consumption 3VA
230 - 415~ 230V~
110 - 130... 50Hz

Grouping / Combination of Several Auxiliaries


On 2, 3 and 4 pole MCBs it is possible to associate 3 auxiliaries – 2 indication auxiliaries and 1 release auxiliary. In this case, it is important to first fix the
indication auxiliary (MZ201 and MZ202) and then the release auxiliary (MZ203 and MZ206).

Flag indicating that the product


has tripped due to the voltage
release

MZ203 to + MZ201 to + MZ201 to + MZ202 to + MCB MZ203 to MZ206


MZ206 MZ201 MZ201 MZ201
Fig. 12
Fig. 11

Data is subject to errors and technical modifications. 101


Miniature Circuit Breakers
Zs Values

Earth Fault Loop impedance (Zs) values for MCBs and MCCBs
Below are the maximum permissible values of Zs to obtain disconnection for
compliance with BS 7671:2008 Amendment 3

Max Let-Through Energy (kA2s) at Max Zs (ohms)


PSCC
In 3kA 6kA 10kA 0.2 - 1s 5 sec
sec
MTN/NBN (B Curve)
Commercial
Distribution

6 5.9 10.5 15 7.28 7.28


10 6.5 12.2 21.5 4.37 4.37
16 8.0 17.5 30 2.73 2.73
20 8.8 19.5 34 2.19 2.19
25 10 21 38 1.75 1.75
32 11 24 42 1.37 1.37
40 12.5 29 50 1.09 1.09
50 15 34 61 0.87 0.87
63 16 38 72 0.69 0.69
NCN/HM (C Curve)
0.5 0.01 0.01 0.01 43.7 62.43
1 4.0 7.0 10 21.85 31.21
2 4.0 7.0 10 10.93 15.61
3 5.0 10.0 15 7.28 10.40
4 5.9 10.5 15 5.46 7.80
6 5.9 10.5 15 3.64 5.20
10 6.5 12.2 21.5 2.19 3.12
16 8.0 17.5 30 1.37 1.95
20 8.8 19.5 34 1.09 1.56
25 10 21 38 0.87 1.25
32 11 24 42 0.68 0.98
40 12.5 29 50 0.55 0.78
50 15 34 61 0.44 0.62
63 16 38 72 0.35 0.50
80 - - - 0.27 0.39
100 - - - 0.22 0.31
125 - - - 0.1 0.25
NDN (D Curve)
0.5 0.01 0.01 0.01 21.85 62.43
1 4.0 7.0 10 10.93 31.21
2 4.0 7.0 10 5.46 15.61
3 5.0 10.0 15 3.64 10.40
4 5.9 10.5 15 2.73 7.80
6 5.9 10.5 15 1.82 5.20
10 6.5 12.2 21.5 1.09 3.12
16 8.0 17.5 30 0.68 1.95
20 8.8 19.5 34 0.55 1.56
25 10 21 38 0.44 1.25
32 11 24 42 0.34 0.98
40 12.5 29 50 0.27 0.78
50 15 34 61 0.22 0.62
63 16 38 72 0.17 0.50
80 0.14 0.39
100 0.11 0.31
125 0.09 0.25

102 Data is subject to errors and technical modifications.


Notes
Technical Data

Commercial
Distribution

Data is subject to errors and technical modifications. 103


Residual Current Devices
Technical Data

Residual Current Devices


A residual current device (RCD) is the generic term for a device which simultaneously performs the functions of detection of the residual current, comparison of
this value with the rated residual operating value and opening the protected circuit when the residual current exceeds this value. These devices can take several
different forms I.e. Residual Current Circuit Breaker (RCCB), Residual Current Circuit Breaker with integral Overload protection (RCBO), or a residual current
device incorporated within a socket outlet or other accessory (SRCD)

Residual current circuit breakers (RCCB) protect against earth faults only and not short circuits. They are usually therefore used in conjunction with overcurrent
protective devices.

MCB/RCCB Co-ordination
Commercial
Distribution

Short circuit capacity of the RCCB With MCB’s


only


RCCB MTN 6-63A B NBN 6-63A B NCN 6-63A C NDN 6-63A D
2 poles
16A 1500A 6kA 10kA 10kA 6kA
25A 1500A 6kA 10kA 10kA 6kA
40A 1500A 6kA 10kA 10kA 6kA
63A 1500A 6kA 10kA 10kA 6kA
80A 1500A 6kA 10kA 10kA 6kA
100A 1500A 6kA 10kA 10kA 6kA
4 poles
16A 1500A 6kA 6kA 6kA 4.5kA
25A 1500A 6kA 6kA 6kA 4.5kA
40A 1500A 6kA 6kA 6kA 4.5kA
63A 1500A 6kA 6kA 6kA 4.5kA
80A 1500A 6kA 6kA 6kA 4.5kA
100A 1500A 6kA 6kA 6kA 4.5kA

104 Data is subject to errors and technical modifications.


Residual Current Devices
Add-on Blocks

Double Pole RCCB Add-on Block Four Pole RCCB Add-on Block 3 Phase Earth Leakage Protection
In ≤63A
Sensitivity 30mA 100mA 300mA 30mA 100mA 300mA 30mA 100mA 300mA
Cat ref. (Standard) BD264 BE264 BF264 BD464 BE464 BF464 BD163T BE163T BF163T
Cat ref. (Time Delayed) BN264 BP264 BN464 BP464
MCB Suitability
NBN 6-63A 6-63A 6-63A 6-63A 6-63A 6-63A 6-63A 6-63A 6-63A

Commercial
NCN 0.5-63A 0.5-63A 0.5-63A 0.5-63A 0.5-63A 0.5-63A 0.5-63A 0.5-63A 0.5-63A

Distribution
NDN 0.5-63A 0.5-63A 0.5-63A 0.5-63A 0.5-63A 0.5-63A 0.5-63A 0.5-63A 0.5-63A

Width when combined with MCB 4 Module 70mm 7 Module 122.5mm 4 Module 70mm

Mounting
Double Pole RCCB Add-on Block

In E

1
2

Mounting
Three Pole RCCB Add-on Block

1 2 3 Tighten the 3 MCB


OFF
screws before cover
closing

PZ2
4
A
12 mm
C Open slider

Data is subject to errors and technical modifications. 105


Latching Relays
Technical Data

Technical Characteristics

EPN510 EPN513 EPN519 EPN525 EPN528 EPN529


EPN515 EPN518 EPN521 EPN540 EPN541
EPN520 EPN524
Voltage 230V 24V 12V 230V 24V 12V
Start Consumption 24VA 24VA 24VA 48VA 47VA TBC
Contact Rating AC1 - - 16A 250V~¹ - - -
Electrical Endurace AC1 - 16A 150,000 Operations
Mechanical Endurance 500,000 Operations
Commercial
Distribution

Current in Open Position 8 mA


Max Duration of Voltage Supply to Coil 1h
Min Duration of Current Supply to Coil 0.1s
Working Temperature -5 to +40ºC
Storage Temperature -40 to +80ºC
Connections
Coil:
Flexible 0.5 to 4mm2
Rigid 1 to 6mm2
Power:
Flexible 1 to 6mm2
Rigid 1.5 to 10mm2
¹ 400~ for EPN540 and EPN541.

Auxiliary Contacts (EPN051) L


The range of latching relays have been designed for use with an
auxiliary contact. The devices simply clip on the side of the relay.

23

21
2 A1 1 3

A2 2 4

22

3
1 24

x 0,5
mêmes épaisseurs

Technical Characteristics

EPN051 2
Voltage -
Contact Rating 2A / 250V
Imin / 230V 15mA

¹ Voltage dependant on associated relay

3
1

4
3

AI3_EP050_T1_01

106 Data is subject to errors and technical modifications.


Contactors
Contactor Selection

Heating Type of Load


The choice of the contactor depends on the mechanical endurance (number Loads are categorised into various AC ratings, (AC1, AC2, AC3 etc.) and the
of operations) and on the electrical heating load higher the AC rating the more inductive the load becomes.
i.e. resistive elements, infra-red element, convectors. All Hager contactor ratings are given at AC1, therefore they must be de-rated
if used on other types of AC load.
Choice of Contactors
The choice of contactor is dependant upon many parameters Heat Dissipation Inserts
i.e. operating voltage, size of contacts, number of operations, The ambient temperature around a contactor can affect its life
ambient temperature, type of load supplied etc. expectancy, therefore, we strongly recommend that heat
dissipation inserts (LZ060) are fitted between all contactors and
adjacent devices.

Commercial
Distribution
Single Phase Three Phase

U R

U R R U R

U R

Number of operations
100,000 150,000 200,000 500,000 1,000,000
16A 3 2.5 1.9 0.85 0.7
25A 4.6 4 3 1.35 1
230V
Max. load in kW

40A 7.3 6.3 4.7 2.2 1.6


63A 11.6 10 7.5 3.5 2.5
16A 8.9 8 5.8 2.8 2
25A 13.8 12 8.6 4.3 3
400V

40A 22 18.5 14.385 6.3 5


63A 35 30 22.6 10.2 7.6

Contactor selection when using with motors

Single Phase 230V (AC3 or AC7b) Three Phase 400V (AC3 or AC7b)

L1 U L1 U

L2 V M
M

L2 V L3 W

Choice of Contactor According to control diagram


Single Phase with Capacitor 230V Three Phase (AC3 or AC7) 400V 2 Wires 3 Wires
0.88 2 pole 25A
Maximum load

2.6 2 pole 40A


in kW

2.6 3 pole 25A


7.8 3 pole 40A
10 3 pole 63A

Requirements of Use Close Fitting


Influence of Working Temperature It is necessary to put a heat dissipation insert (reference LZ060) between each
Derating factor between 40°C and 50°C : 0.9 contactor.
Example: Heating with convector
The maximum load of ESC225 is 4.6kW for 50,000 operations and for
a temperature <40°C.
between 40°C and 50°C, the load is 4.6 x 0.9 i.e. 4.14kW

Data is subject to errors and technical modifications. 107


Contactors & Override Contactors
Technical Data

Auxiliary
Description Modular contact
contact
Standard conformity EN 61095
Approvals NF - VDE- IMQ - KEMA - RMC / CCC
Relay Contactor Relay Contactor Contactor Contactor Contactor
Number of modules 1 2 3 ½
Thermal current lth (40ºC) 16A 25A 16A 25A 40A 63A 6A
Rated frequency 50 - 60 Hz 50 - 60 Hz 50 - 60 Hz 50 - 60 Hz 50 - 60 Hz 50 - 60 Hz 50 - 60 Hz
Rated insulation voltage (Ui) 250V 250V 440V 440V 440V 440V 250V
Rated impulse withstand voltage (Uimp) 4kV 4kV 4kV 4kV 4kV 4kV 4kV
Commercial
Distribution

Polution Degree 2 2 2 2 2 2 2
Rated Operating currents and power ratings in AC
AC-1 / AC-7a Rated operational currents Ie 16A 16A 16A 25A 40A 63A -
Rated operational power 230V 3kW 4.6kW 3kW 4.6kW 7.3kW 11.6kW -
400V - - 8.9kW 13.8kW 22kW 35kW -
AC-3 / AC-7b Rated operational currents Ie 5.5A 8.5A 5.5A 8.5A 25A 32A -
Rated operational power 230V 570W 880W 570W 880W 2.6kW 3.3kW -
400V - - 1.7kW 2.6kW 7.8kW 10kW -
AC-12 Rated operational currents i.e. @ 230V - - - - - - 6A
AC-15 Rated operational currents i.e. @ 230V - - - - - - 2A
Mechanical and Electrical Endurances
Number of
Mechanical endurance 1,000,000 1,000,000 1,000,000 1,000,000 1,000,000 1,000,000 1,000,000
operations
Electrical endurance @ Ie AC7a (AC12 for aux Number of
60,000 60,000 60,000 60,000 60,000 60,000 60,000
contact) operations
MCB Protected short-circuit withstand
Prospected short-circuit current rms 1kA 3kA 1kA 3kA 3kA 3kA 1kA
MCB C16- MCB C25- MCB C16- MCB C25- MCB C40- MCB C63- 6A 10x38
Associated protection
6kA 6kA 6kA 6kA 10kA 10kA gG Fuse
Power dissipation
Power dissipation per current path 1W 1.5W 1W 1.5W 3.2W 5W 0.4W
Magnetic system for Eco and standard contactor
Pick-up 2.2W 2.2W 2.8W 2.8W 5W 5W -
Coil consumption 2.2W 2.2W 2.8W 2.8W 5W 5W -
Closing delay 25ms 25ms 25ms 25ms 25ms 25ms -
Opering delay 15ms 15ms 15ms 15ms 20ms 20ms -
Connection
Main contact cable section Rigid 1...10mm 2 1...10mm2 1...10mm2 1...10mm2 4...25mm2 4...25mm2 1...6mm2
Flexible 1...6mm 2
1...6mm 2
1...6mm 2
1...6mm 2
4...16mm 2
4...16mm 2
1...6mm2
Main contact connection screw Type M3.4 M3.4 M3.4 M3.4 M5 M5 M3.4
Posidrive PZ2 PZ2 PZ2 PZ2 PZ2 PZ2 PZ2
Max. tight.
1.2Nm 1.2Nm 1.2Nm 1.2Nm 2Nm 2Nm 1.2Nm
torque
Coil connection cable section Rigid 1...10mm 2
1...10mm 2
1...10mm 2
1...10mm 2
1...10mm 2
1...10mm 2
-
Flexible 1...6mm2 1...6mm2 1...6mm2 1...6mm2 1...6mm2 1...6mm2 -
Coil connection screw Type M3.5 M3.5 M3.5 M3.5 M4 M4 -
Posidrive PZ2 PZ2 PZ2 PZ2 PZ2 PZ2 -
Max. tight.
1.2Nm 1.2Nm 1.2Nm 1.2Nm 1.5Nm 1.5Nm -
torque
Working temperature
-10ºC to +50ºC
Storage temperature
-40ºC to +80ºC

108 Data is subject to errors and technical modifications.


Contactors & Relays
Technical Data

Lighting systems with electronic ballasts cause inrush current peaks. Therefore we recommend you use the chart below to determinate the maximum amount of
lamps that can be connected to a Hager contactor: The chart gives the maximum amount of lamps per contact. In 2014 the performances of the contactors in
combination with lights increased. The products identified on the front face with the ‘+’ can accept a higher number of lamps. For these products, see the figures
in the column with the ‘+’ in the header.

Lamp Power 16A 25A 16A + 25A + 40A 63A


Compact fluo lamps
Compact fluo lamp with external electronic ballast 5W 11 15 17 27 49 76
7W 11 15 17 27 49 76
9W 9 13 16 26 40 63
11W 9 13 16 26 40 63

Commercial
Distribution
15W 7 11 14 22 36 57
18W 7 11 14 22 36 57
20W 7 11 14 22 36 57
23W 7 11 14 22 36 57
26W 7 11 14 22 36 57
Compact fluo lamp with integrated electronic ballast 5W 17 27 34 54 86 135
7W 17 27 34 54 86 135
9W 17 27 34 54 86 135
11W 17 27 34 54 86 135
15W 17 27 34 54 86 135
18W 13 20 25 40 63 100
20W 13 20 25 40 63 100
23W 13 20 25 40 63 100
26W 13 20 25 40 63 100
Incandescent lamps
Tungsten & halogen lamps 230V 40W 32 50 36 57 76 120
60W 21 33 28 45 67 105
75W 17 27 24 38 63 100
100W 13 20 17 28 41 65
150W 8 13 11 18 29 45
200W 6 9 8 14 22 35
300W 4 7 6 10 15 23
500W 2 3 3 6 9 14
1000W 0 0 1 2 4 7
Tungsten & halogen lamps 12 ou 24V 20W 13 20 25 40 139 218
35W 8 13 16 26 82 129
50W 6 9 11 18 60 94
75W 4 6 7 12 52 82
100W 2 3 3 6 35 55
150W 1 2 2 4 20 31
LED
LED 230V with integrated electronic ballast - non dimmable 4W 17 27 34 54 86 135
4.5W 17 27 34 54 86 135
6W 17 27 34 54 86 135
7W 17 27 34 54 86 135
8W 17 27 34 54 86 135
12W 17 27 34 54 86 135
17W 13 20 25 40 63 101
18W 13 20 25 40 63 101
22W 13 20 25 40 63 101
30W 9 14 17 28 44 70
34W 9 14 17 28 44 70
40W 9 14 17 28 44 70
50W 7 11 14 22 35 55
LED 230V with integrated electronic ballast - dimmable 4W 38 60 76 120 159 250
5.5W 38 60 76 120 159 250
6W 38 60 76 120 159 250
7W 38 60 76 120 159 250
8W 38 60 76 120 159 250
12W 38 60 76 120 159 250
17W 28 44 56 88 118 185
18W 28 44 56 88 118 185
22W 28 44 56 88 118 185
30W 20 31 39 62 82 130
34W 20 31 39 62 82 130
40W 20 31 39 62 82 130
50W 16 24 30 48 65 102
LED 230V headlight with integrated electronic ballast 100W - - 3 5 6 9
150W - - 1 3 4 6
200W - - 1 2 4 6
LED 12V with separated transformer - dimmable 1W 38 60 76 120 180 220
2.5W 38 60 76 120 180 220
4W 38 60 76 120 180 220
5W 38 60 76 120 180 220
7W 38 60 76 120 160 200
10W 38 60 76 120 160 200
15W 28 44 56 88 160 200

Data is subject to errors and technical modifications. 109


Contactors & Relays
Technical Data

Lamp Power 16A 25A 16A + 25A + 40A 63A


Fluorescent tubes
T5 double - uncompensated 2 x 18W 13 20 25 40 50 78
2 x 20W 12 19 24 38 50 78
2 x 36W 12 15 19 30 44 69
2 x 40W 10 13 16 26 40 63
2 x 42W 9 12 15 24 40 63
2 x 58W 7 9 11 18 27 42
2 x 65W 6 8 10 16 27 42
2 x 80W 5 7 8 14 22 35
2 x 115W 4 5 6 10 16 25
Commercial
Distribution

T5 double - serie compensation 2 x 18W 7 11 14 22 34 53


2 x 20W 7 11 14 22 29 45
2 x 36W 6 10 12 20 27 42
2 x 40W 6 10 12 20 27 42
2 x 42W 6 10 12 20 27 42
2 x 58W 6 10 12 20 25 39
2 x 65W 5 7 8 14 23 36
2 x 80W 5 7 8 14 20 31
2 x 115W 4 5 6 10 17 25
T5 single - electronic ballast 15W 7 11 14 22 36 57
18W 7 11 14 22 36 57
20W 7 11 14 22 36 57
36W 7 11 14 22 34 53
40W 7 11 14 22 29 45
42W 7 11 14 22 29 45
58W 6 10 12 20 27 42
65W 6 10 12 20 27 42
80W 6 10 12 20 27 42
115W 6 10 12 20 25 39
T5 double - electronic ballast 2 x 18W 7 11 14 22 34 53
2 x 20W 7 11 14 22 29 45
2 x 36W 6 10 12 20 27 42
2 x 40W 6 10 12 20 27 42
2 x 42W 6 10 12 20 27 42
2 x 58W 6 10 12 20 25 39
2 x 65W 5 7 8 14 23 36
2 x 80W 5 7 8 14 20 31
2 x 115W 4 5 6 10 17 25
Fluorescent tubes
T5 single - uncompensated 15W 13 20 19 30 70 100
18W 13 20 19 30 70 100
20W 12 19 19 30 70 100
36W 12 15 17 28 60 90
40W 10 13 16 26 60 90
42W 9 12 15 24 55 83
58W 7 9 10 17 35 56
65W 6 8 10 17 35 56
80W 5 7 9 15 30 48
115W 4 5 6 10 20 32
140W 3 5 6 10 16 26
T5 single - paralell compensation 15W 7 11 12 20 36 57
18W 7 11 12 20 36 57
20W 7 11 12 20 36 57
36W 7 11 12 20 34 53
40W 7 11 12 20 29 45
42W 7 11 12 20 29 45
58W 6 10 9 15 27 42
65W 6 10 9 15 27 42
80W 6 10 9 15 27 42
115W 6 10 9 15 25 39

110 Data is subject to errors and technical modifications.


Contactors & Relays
Technical Data

Lamp Power 16A 25A 16A + 25A + 40A 63A


Discharge lamps
High-pressure mercury-vapor lamps - without 50W 9 14 17 28 32 50
compensation 80W 6 9 11 18 24 37
125W 3 5 6 10 18 28
250W 2 3 3 6 10 15
400W 1 1 1 2 6 9
700W 0 0 0 0 4 5
High-pressure mercury-vapor lamps - paralell 50W 7 11 14 22 26 40
compensation 80W 5 8 10 16 22 34
125W 3 5 6 10 15 23

Commercial
Distribution
250W 2 3 3 6 9 14
400W 1 1 1 2 5 8
700W 0 0 0 0 3 5
1000W 0 0 0 0 2 3
Low pressure sodium lamps - without compensation 18W 8 10 8 12 17 23
35W 4 6 7 9 14 20
55W 3 6 7 9 14 20
90W 2 4 5 6 9 14
135W 1 3 3 4 6 8
180W 1 2 2 4 6 8
Low pressure sodium lamps - paralell compensation 18W 5 7 5 8 12 24
35W 4 6 4 7 10 23
55W 3 5 3 5 10 19
90W 2 3 3 4 8 16
135W 1 2 1 2 5 7
180W 1 2 1 2 5 6
High pressure sodium lamps - without compensation 35W 11 14 15 24 30 50
50W 9 12 10 15 22 34
70W 8 9 8 12 18 28
110W 6 8 6 10 14 22
150W 4 7 5 8 10 16
250W 2 4 3 5 6 10
400W 0 1 1 2 4 6
1000W 0 1 1 1 2 3
High pressure sodium-vapour lamps - electronic 35W 6 9 11 18 31 50
ballast or parallel compensation 50W 6 9 11 18 22 35
70W 4 6 7 12 16 25
110W 3 5 6 8 13 21
150W 3 5 4 6 8 13
250W 2 3 3 4 7 11
400W 1 1 1 2 5 8
1000W 0 0 0 1 2 3
Metal halide lamps - without compensation 35W 12 24 19 30 42 55
70W 10 15 12 17 26 36
150W 6 7 8 12 14 20
250W 3 5 5 8 9 14
400W 1 2 2 4 6 9
1000W 0 0 0 0 3 5
Metal halide lamps - electronic ballast or parallel 35W 6 10 12 18 22 39
compensation 70W 5 8 10 13 22 39
150W 3 5 6 8 12 22
250W 3 5 6 7 9 16
400W 1 1 1 2 5 7
1000W 0 0 0 1 2 3

Data is subject to errors and technical modifications. 111


Transformers & Motors
Protection

Transformer Protection
Tables 19 & 20 show the recommended MCB’s for the protection of single
phase (230V) and three phase (400V) transformers.

Single Phase 230V Three Phase 400V


Recommended MCB Recommended MCB
Transformer Primary NBN NCN NDN Transformer Primary NBN NCN NDN
Rating (VA) Current Rating (VA) Current
50 0.22 - 1 6 500 0.72 - 3 6
100 0.43 - 2 6 750 1.08 6 4 6
Commercial
Distribution

200 0.87 - 3 6 1000 1.44 10 6 6


250 1.09 6 4 6 2000 2.88 16 10 6
300 1.30 10 4 6 3000 4.33 25 16 10
400 1.74 10 6 6 4000 5.77 32 20 10
500 2.17 16 10 6 5000 7.21 40 25 16
750 3.26 16 10 6 7500 10.82 63 32 20
1000 4.35 25 16 10 10000 14.43 - 50 25
2500 10.87 63 40 20 15000 21.64 - 63 32
5000 21.74 - 63 32 20000 28.86 - - 50
7500 32.60 - - 50 25000 36.07 - - 63
10000 43.48 - - 63

Motor Circuit Protection


Tables 28,29,30 and 31 give general recommendations for the selection of
circuit breakers and HRC fuses for the protection of motor power circuits and
are based on the assumptions shown in Table 28 for a cage motor running at
approximately 1400 Rev/Min. 3 Phase 400V Assisted Starting Star-Delta

Motor Rating DOL Starting Assisted Start Conditions Recommended Circuit Breaker
Conditions kW hp FLC A (A) NCN (A) NDN HRC Fuse (A)
Up to 0.75kW 5 x FLC for 6 secs 2.5 x FLC for 15 secs 3 4 6.3 16 10 16
1.1 to 7.5kW 6 x FLC for 10 secs 2.5 x FLC for 15 secs 4 5.5 8.2 20 10 16

11 to 75kW 7 x FLC for 10 secs 2.5 x FLC for 15 secs 5.5 7.5 11.2 32 16 20
7.5 10 14.4 40 25 25
90 to 160kW 6 x FLC for 15 secs 2.5 x FLC for 20 secs
11 15 21 50 32 32
15 20 27 - 40 35
1 Phase 230V DOL Starting 18.5 25 32 - 50 40
Recommended Circuit Breaker 22 30 38 - 63 50
kW hp FLC A (A) NBN (A) NCN (A) NDN Fuse (A) 30 40 51 - - 63
0.18 0.25 2.8 16 10 10 10 37 50 63 - - 80

0.25 0.33 3.2 16 10 10 16 45 60 76 - - 80


55 75 91 - - 100
0.37 0.5 3.5 16 10 10 16
75 100 124 - - 160
0.55 0.75 4.8 20 16 16 16
90 125 154 - - 200
0.75 1.0 6.2 25 20 20 20
110 150 183 - - 200
1.1 1.5 8.7 40 25 25 25
132 175 219 - - 250
1.5 2.0 11.8 50 32 32 32 150 200 240 - - 315
2.2 3.0 17.5 - 50 50 40 160 220 257 - - 315
3.0 4.0 20 - 63 63 50
3.75 5.0 24 - - - 63
5.5 7.5 36 - - - 80
7.5 10 47 - - - 100

112 Data is subject to errors and technical modifications.


Transformers & Motors
Protection

3 Phase 400V DOL Starting


Recommended Circuit Breaker
kW hp FLC A (A) NBN (A) NCN (A) NDN HRC
Fuse (A)
0.18 0.25 0.87 - 2 - 4
0.25 0.33 1.17 - 3 - 4
0.37 0.5 1.2 - 3 - 4
0.55 0.75 1.8 - 4 - 6
0.75 1.0 2.0 10 6 6 6

Commercial
Distribution
1.1 1.5 2.6 16 10 6 10
1.5 2.0 3.5 16 10 10 16
2.2 3.0 4.4 20 16 16 16
3.0 4.0 6.3 25 20 20 20
4.0 5.5 8.2 32 25 25 25
5.5 7.5 11.2 50 40 40 32
7.5 10 14.4 63 50 50 40
11 15 21 - - - 63
15 20 27 - - - 80
18.5 25 32 - - - 80
22 30 38 - - - 80
30 40 51 - - - 100
37 50 63 - - - 125
45 60 76 - - - 125
55 75 91 - - - 160
75 100 124 - - - 200
90 125 154 - - - 250
110 150 183 - - - 315
132 175 219 - - - 355
150 200 240 - - - 355
160 220 257 - - - 355

Data is subject to errors and technical modifications. 113


Surge Protection Devices
Type 1 + Type 2 SPN8***

SPN802 / SPN802R
Tested to EN 61643-11
(VDE0675-6-11) 2002-12
L1/L2/L3 => N N => PE
SPD type / class Type 1 + Type 2 / I / B
Type of connection Parallel connection
Type of power supply system TN/TT - System
Type of protection Common and differential modes
Nominal voltage UN 230V / 400V ac
Rated voltage Uc 255V ac
Commercial
Distribution

Voltage protection level Up ≤ 1.5kV 255V ac


TOV-voltage UT 440V / 5s 1200V / 200ms
Rated load current I(L) 315A
I(L-L) 125A
Follow current interrupting rating Ifi 50 kA 100kA
Nominal discharge current (8/20) In 25kA 100kA
Impulse current (10/350) Iimp 25kA 100kA
Residual current IPE ≤ 100mA
Max. rating of overcurrent protection fuse 125A gL / gG serial or 315A parallel
MCCB 125A serial or 160A parallel
Short-circuit withstand capability with fuse 25kA ac
max. overcurrent protection MCCB 25kA ac
Response time tA < 100ns
Operating temperature range - 40°C ….+ 60°C
Indication of SPD disconnector Green - red on L1, L2, L3, N
Cross sectional area min 10mm2 solid / flexible
L1, L2, L3, PE max 50mm2 multi-stranded / 35mm2 flexible
Tightening torque for terminals 7.0 Nm
Mounting on 35mm DIN rail in accordance with EN 60715
Enclosure material grey thermoplastic, UL 94V-0
Degree of protection IP20
Modular width 8
Weight 1272 g
Approval marking VDE

114 Data is subject to errors and technical modifications.


Surge Protection Devices
Type 1 + Type 2

SPA201 SPA401
Tested to EN 61643-11 2002-12
SPD type / class Type 1 + Type 2 / Class I
Energy-coordinated protection Type 1 + Type 2
effect on terminal equipment
Energy-coordinated protection Type 1 + Type 2 + Type 3
effect on terminalequipment
≤5m
Type of connection Parallel connection
Type of power supply system TT / TN system

Commercial
Distribution
Type of protection common and differential modes
Nominal voltage UN 230V/400V ac
Rated voltage Uc 255V ac
Voltage protection level Up ≤ 1.5kV
TOV Voltage UT 440V / 5s
1200V / 200ms
Rated load current I(L) n/a
I(L-L) n/a
Follow current interrupting rating Ifi 25kA rms
100A rms
Nominal discharge current (8/20) In 12.5kA 12.5kA
25kA 50kA
Impulse current (10/350) Iimp 12.5kA 12.5kA
25kA 50kA
Max. rating of overcurrent fuse 160A gL / gG
protection MCCB n/a 160A
Short-circuit withstand fuse 25kA rms
capability with max. overcurrent MCB n/a
protection
Response time tA ≤ 100ns
Operating temperature range - 40°C ….+ 80°C
Indication of SPD disconnector Green/Red flag on L and N Green/Red flag on L1, L2, L3 and N
Cross sectional area min 1,5mm2 solid / flexible
max 35mm2 stranded / 25mm2 flexible
Tightening torque for terminals 4 Nm
Mounting on 35mm DIN rail in accordance with EN 60715
Enclosure material grey thermoplastic, UL 94V-0
Degree of protection IP20
Modular width 2 4
Weight 275 g 480 g
Approval marking KEMA

Data is subject to errors and technical modifications. 115


Surge Protection Devices
Type 2, SPN215*, SPN415*, SPN440*, SPV325

SPN215D/R SPN415D/R SPN440D/R


Tested to EN 61643-11 (VDE0675-6-11) 2002-12
SPD type Type 2 according to EN 61643-11
Type of connection Parallel connection
Maximum continuous operationg voltage Uc Line / Neutal ≤ 255V
Neutral/ PE ≤ 275V
Voltage protection level Up ≤ 1kV ≤ 1kV ≤ 1.2kV
Nominal discharge current (8/20 µs) In 5kA 5kA 15kA
[(DC+/DC-) --> PE]
Max. discharge current (8/20 µs) Imax 15kA 15kA 40kA
Commercial
Distribution

Short-circuit withstand capability with max. overcur- 10kA - 32A 10kA - 32A 20kA - 32A
rent protection
Operating temperature range - 40°C ….+ 80°C
Indication of SPD disconnector Green - Red
Cross sectional area min 1,5mm2 solid / flexible
max 35mm2 multi-stranded / 25mm2 flexible
Tightening torque for terminals 4.0 Nm
Mounting on 35mm DIN rail in accordance with EN 60715
Enclosure material grey thermoplastic, UL 94V-0
Degree of protection IP20
Modular width (DIN 43880) 2 2 4
Auiliary contact. Voltage/ nominal current 230V/ 0.5A
(only applicable on the R suffix products) 12Vdc
10mA

SPV325
Tested to EN 61643-11 (VDE0675-6-11) 2002-12
SPD type Type 2 according to EN 61643-11
Type of connection Parallel connection
Maximum continuous operationg voltage UcPV ≤ 1000V
Voltage protection level Up ≤ 4kV
Voltage protection level for 5kA Up ≤ 3,5kV
Total discharge current (8/20 µs) Itotal 40kA
Nominal discharge current (8/20 µs) In 12.5kA
Max. discharge current (8/20 µs) Imax 25kA
Short-circuit withstand capability with max. overcur- IscwPV 50 A / 1000 V DC
rent protection
Response time tA ≤ 25ns
Operating temperature range - 40°C ….+ 80°C
Indication of SPD disconnector green - red
Cross sectional area min 1.5mm2 solid / flexible
max 35mm2 multi-stranded / 25mm2 flexible
Tightening torque for terminals 4.0 Nm
Mounting on 35mm DIN rail in accordance with EN 60715
Enclosure material Grey thermoplastic, UL 94V-0
Degree of protection IP20
Installation width 3 modules, DIN 43880
Weight 316g

116 Data is subject to errors and technical modifications.


Surge Protection Devices
Type 3, SP203N

Characteristics
Tested to EN 61643-11 (VDE0675-6-11) 2007-08
SPD type Type 3
Ports one port
Type of connection Parallel connection
Type of power supply system TT / TN system
Nominal voltage UN 230V ac
Rated voltage Uc 255V ac
Voltage protection level ( L- N) Up ≤ 1.25kV

Commercial
Distribution
Voltage protection level (L/N - PE) Up ≤ 1.5kV
TOV - Characteristic (L - N) UT 335V / 5s
TOV - Characteristic (L/N - PE) (I) UT 400V / 5s
TOV - Characteristic (L/N - PE) (II) UT 1200V / 200 ms
Rated load current IL 16 Aeff
Nominal discharge current (8/20) In 3kA
Maximal discharge current (8/20) Imax 5kA
Combination wave (1,2/50 - 8/20) (L - N) Uoc 6 kV
Combination wave (1,2/50 - 8/20) (L/N - PE) Uoc 10 kV
Residual current IPE ≤ 5μA
Remplacement cartridge NO
Maximal rating of overcurrent protection fuse 16 A gL / gG
MCB 16A B curve
Short-circuit withstand capability with max. overcur- fuse 6kA eff ac
rent protection MCB 1kA eff ac
Response time tA ≤ 25ns
Operating temperature range - 25°C ….+ 40°C
Indication of SPD disconnector NO
Remote signalisation contact Green light off
Cross sectional area min 1.5mm2 solid / flexible
max 10mm2 stranded / 6mm2 flexible
Tightening torque for terminals 1.2 Nm
Mounting on 35mm DIN rail in accordance with EN 60715
Enclosure material Grey thermoplastic, UL 94V-2
Degree of protection IP20
Installation width 2 modules, DIN 43880

Reserve Indicator Light

Neutral cartridges cannot be put into


spares reserved for phase cartridges and
visa versa.

Normal End of Life


Clear Red

Data is subject to errors and technical modifications. 117


Earth Fault Relays
Technical Data

Non-Adjustable Adjustable
HR500 HR502 HR510 HR520 HR522 HR523 HR525/HR534 HR440 HR441
Supply Voltage ~50/60Hz 220-240V
Residual Voltage ~50/60Hz 500V Maximum
Power Absorbed 3VA 5VA
Output Volt Free Contacts
Contact Rating 6A / 250V AC-1
Sensitivity I∆n 30mA 300mA 30mA / 100mA / 300mA / 500mA / 500mA / 30mA / 100mA / 30mA / 100mA / 300mA
Commercial
Distribution

1A / 3A / 10A 1A / 3A / 300mA / 500mA / / 500mA / 1A / 3A


5A / 10A / 1A / 3A / 5A / 10A
20A / 30A / 30A
Instantaneous / Time Delay Instantaneous Instantaneous or Instantaneous or Time Instantaneous or Instantaneous or Time
Time Delay 0.1 - Delay 0.1 - 0.2 - 0.25 - 0.3 - Time Delay 0.02 Delay 0.1 - 0.3s - 0.5s -
0.3 - 0.4 - 0.5 - 1 0.4 - 0.5 seconds - 0.1 - 0.3 - 0.4 - 0.75s - 1s
- 3 seconds 0.5 - 1 - 3 - 5 - 10
seconds
Torroid Withstand Capacity 50kA / 0.2s
Distance between Torroid and 50 Meter Maximum
Relay
Relay Cable Connection 1.5mm2 to 10mm2
• Rigid 1mm2 to 6mm2
• Flexible

Torroid Cable Conection 1.5mm2 to 4mm2


• Rigid 1mm2 to 2.5mm2
• Flexible

Relay -10ºC to +55ºC -5ºC to +55ºC


• Working Temperature -25ºC to +40ºC -25ºC to +40ºC
• Storage Temperature
Torroid -10ºC to +70ºC -10ºC to +70ºC
• Working Temperature -40ºC to +70ºC -40ºC to +70ºC
• Storage Temperature

Main Characteristics Sealable Settings


“Reset” Button A sealable cover prevents interference once the settings have been made.
When pressed, the output remains switched and return to normal is obtained
by either: by pressing the “reset” clear pushbutton or cutting off the power Standard Output (1 C/O contact)
supply. If the “reset” button is not pressed the device remains in the fault Switching to state 1 on:
position. • Failure of the core/relay connection
• Fault current in the monitored installation
Test Button
Pressing the test button allows a fault simulation which operates the relay and Positive Safety Outlet (1 C/O contact)
the output contacts.The fault level display is shown by an LED on the front of Switching to state 1: Switching on the power
the product. Switching to state 0: Failure of the core/relay connection
fault current in the monitored installation
l∆n Selector failure of relay supply
Sensitivity setting: 0.03A instantaneous internal failure of relay
0.1A/0.3A/1A and 3A time delay
Optical scale display by 5 LEDs of the fault in % of I∆n
Time Delay Selector Optical scale display by (5 LEDs) of the fault in % of I∆n
Adjustable time setting - instantaneous / 0.13s / 0.3s / 1s and 3s Common pin 6:
State 1 : output terminal 8
N L1 L2 L3
State 0 : output terminal 4 9 10 10
N L1 L2 L3 9 10 10
1. Reset push button
2. Test push button
3. Fault signal LED 11 12 13 14 15 16 18 19 20
4. Device on indicator
11 12 13 14 15 16 18 19 20
5. Sensitivity setting 11
test reset 6. Time delay setting On 75
7. Standard output 4 60 11 3
0,5 1 3 10 0,4 0,5 1 3

test reset 8. Safety output 0,3 75 0,3


45
4 5
On 0,1 0,1
3 6
11 12 13 14 15 16 18 19 20 9. Prealarm output 0,5 1 3 10 0,4
0,03
I Dn(A)
0,5 1 3 Dt(s) 60 30
0

10. Remore reset 0,3 0,3


45 15
5 2 0,1 0,1
6 1
11 12 13 14 15 16 18 19 20 HR 425 11. Optical scale 0,03
Test
0
Reset 30
5
I Dn(A) Dt(s)
15
HR 4251 2 3 4 5 6
2 1
5
Test 1 2 3 Reset4 5 6

1 2 3 4 5 6
1 2 3 4 5 6

7 8

7 8

118 Data is subject to errors and technical modifications.


Torroids
D 14 17
5.5
Technical Data

24.5 D Cat ref. Dimensions (mm)


D 14 17
5.5 A B C D E
A C E HR700 30 70 70 30 -
C A HR701 35 92 86 43.5 74
24.5 D HR702 70 115 118 60.5 97
HR703 105 158 162.5 84.5 140
A C E
1.5 33.5 HR704 140 218 200 103.5 183
29 B C A B
HR705 210 290 295 150 265

Commercial
Distribution
E

1.5 33.5
29 B B

D F Cat ref. Type Dimensions (mm)


H A1 A1 B C D E F G H
HR830 70x175 70 175 176 260 85 225 22 40 7.5
HR831 115x305 115 305 239 400 116 360 25 50 8.5

D HR832
F 150x350 150 350 284 460 140 415 28 50 8.5
H

A2 C E

A1
A2 C E

2.5 14 A1 G
B

B D Cat ref. Dimensions (mm)


2.5 14 G
A1 A1 B C D E F
B
HR820 20 30 89 110 41 32 46
HR821 50 80 114 145 50 32 46
HR822 80 80 145 145 50 32 46
HR823 80 121 145 185 50 32 46
HR824 80 161 184 244 70 37 46
A2
C

A1
E

Data is subject to errors and technical modifications. 119


Torroids
Selection Chart

Mounting of Circular Torroids


With Cables
U 1000 R2V U 1000 R2V U 1000 R2V U 1000 R2V U 1000 R2V H07 V - U H07 V - U
Sinlge Pole Single Pole Multi Pole Multi Pole Multi Pole Single Pole Single Pole

Ø Type of
Torroids
torroid
torroid
torroid torroid
torroid
torroid
torroid
torroidtorroid
torroid
torroidtorroid
torroid
torroid
torroid
torroid
torroid
torroid
torroid
torroidtorroid
torroid torroid
torroid torroid
torroid
torroid
torroid torroid
torroidtorroid
torroid
torroid
torroidtorroid
torroid
torroid torroid
torroid
torroid
torroid
torroidtorroid
torroid
torroid
torroid
torroid
torroidtorroid
torroid
torroid
torroid
torroid
torroidtorroid
torroid
torroid torroid
torroid
torroid torroid
torroid
torroidtorroid
torroid torroid
torroid
torroid
torroidtorroid
torroidtorroid
torroid
Commercial
Distribution

30 HR700 4 x 16mm2 2 x 50mm2 35mm2 35mm2 50mm2 4 x 35mm2 2 x 70mm2


35 HR701 4 x 25mm2 2 x 70mm2 50mm2 35mm2 70mm2 4 x 50mm2 2 x 95mm2
70 HR702 4 x 185mm 2
2 x 400mm or2
240mm 2
35mm 2
300mm 2
4 x 240mm 2
2 x 400 or
4 x 150mm2 4 x 185mm2

105 HR703 4 x 500mm2 2 x 630mm2 or 300mm2 35mm2 300mm2 4 x 400mm2 2 x 400 or


4 x 185mm2 4 x 240mm2

140 HR704 4 x 630mm2 2 x 630mm2 or 300mm2 35mm2 300mm2 4 x 400mm2 2 x 400 or


4 x 240mm2 4 x 240mm2

210 HR705 4 x 630mm2 2 x 630mm2 or 300mm2 35mm2 300mm2 4 x 400mm2 2 x 400 or


4 x 240mm2 4 x 240mm2

70 x 175 HR830 4 x 630mm2 2 x 630mm2 or 300mm2 35mm2 300mm2 4 x 400mm2 2 x 400 or


4 x 240mm2 4 x 240mm2

115 x 305 HR831 4 x 630mm2 2 x 630mm2 or 300mm2 35mm2 300mm2 4 x 400mm2 2 x 400 or
4 x 240mm2 4 x 240mm2

150 x 350 HR832 4 x 630mm2 2 x 630mm2 or 300mm2 35mm2 300mm2 4 x 400mm2 2 x 400 or
4 x 240mm2 4 x 240mm2

20 x 30 HR820 4 x 16mm2 2 x 70mm2 10mm2 35mm2 16mm2 4 x 10mm2 2 x 35mm2


50 x 80 HR821 4 x 240mm 2
2 x 630mm or2
120mm 2
35mm 2
150mm 2
4 x 185mm 2
2 x 240mm2
4 x 185mm2

80 x 80 HR822 4 x 500mm2 2 x 630mm2 or 300mm2 35mm2 300mm2 4 x 400mm2 2 x 400 or


4 x 185mm2 4 x 240mm2

80 x 120 HR823 4 x 630mm2 2 x 630mm2 or 300mm2 35mm2 300mm2 4 x 400mm2 2 x 400 or


4 x 240mm2 4 x 240mm2

80 x 160 HR824 4 x 630mm2 2 x 630mm2 or 300mm2 35mm2 300mm2 4 x 400mm2 2 x 400 or


4 x 240mm2 4 x 240mm2

120 Data is subject to errors and technical modifications.


MCCBs
Technical Data

Frame x160 x250


Product MCS Switch MCCB MCS Switch MCCB
Reference HCA HDA HHA HNA HCB HHB HNB
Number of poles [No.] 3-4 1-2-3-4 1-2-3-4 3-4 3-4
Electrical characteristics
Rated current In [A] 160 250
Current rated range [A] 125-160 16-125 (1P), 16-160 (2, 3, 4P) 250 100-250
Rated service voltage, (AC) Ue [V] 220-440 220-440
Frequency F [Hz] 50/60 50/60
Rated insulation voltage Ui [V] 690 800

Commercial
Rated impulse withstand voltage Uimp [kV] 8 8

Distribution
Rated ultimate short-circuit breaking capacity, (Icu)
-
(AC) 50-60 Hz 220/230 V Icu [kA] 25 35 85 - 35 85
(AC) 50-60 Hz 380/415 V Icu [kA] - 18 25 40 - 25 40
(AC) 50-60 Hz 480/500/525 V Icu [kA] - 6 7.5 12.5 - - 10
(AC) 50-60 Hz 660/690 V Icu [kA] - - - 6 - - 4
(DC) 250 V - 2 poles in series Icu [kA] - 12.5 20 25 - 25 25
Rated service short-circuit breaking capacity, (Ics)
-
(AC) 50-60 Hz 220/230 V Ics [kA] 25 25 40 - 25 40
(AC) 50-60 Hz 380/415 V Ics [kA] - 18 20 20 - 20 20
(AC) 50-60 Hz 480/500/525 V Ics [kA] - 3 4 7.5 - 7.5
(AC) 50-60 Hz 660/690 V Ics [kA] - - - 3 - - 2
(DC) 250 V - 2 poles in series Ics [kA] - 7 10 13 - 13 13
Rated short-circuit making capacity Icm [kA] 2.8 - - - 6 - -
Rated short-time withstand current for 1s Icw [kA] 2 - - - 3 - -
Category of use (EN 60947-2) - A - A
Calibration temperature - 50°C - 50°C
Derating 40°C - 100% - 100%
50°C - 100% - 100%
55°C - 95% - 94%
60°C - 93% - 91%
65°C - 90% - 88%
Suitability for isolation ok ok
Electric endurance in number of cycles 10000 10000
Mechanical endurance in number of operations 20000 20000
Operating temperature -25 to +70°C -25 to +70°C
Storage temperature -35 to +70°C -35 to +70°C
Power loss (at In for 3P) [W] 39 60
Reference standard IEC 60947-3 IEC 60947-2 IEC 60947-3 IEC 60947-2
Releases: switch ok - ok -
Releases: TM (thermomagnetic) - ok - ok
T fixed, M fixed - ok (1P) - ok
T adjustable, M fixed - ok (3/4 P) - -
T adjustable, M adjustable - - - ok
Thermal adjustment value - 0.63 to 1 x In - 0.63 to 1 x In
6-8-10-13 x In (200A)
Magnetic adjustment value - - -
5-7-9-11 In (250A)
Releases: LSI (electronic) - - - -
Long delay - - - -
Short delay - - - -
Time delay - - - -
Terminations
Standard terminal type cage lugs
Maximum terminal capacity 95 mm2 185 mm2 (cage)
Terminal width mm - 25
Terminal shields ok ok
Cage terminal integrated ok
Extended connections ok ok
Rear connections no ok
Dimensions
Height mm 130 165
Width 1P mm - 25 - -
2P mm - 50 - -
3P mm 75 105
4P mm 100 140
Depth mm 68 68
Weight 1P kg - 0.29 - -
2P kg - 0.48 - -
3P kg 0.715 1.3
4P kg 0.95 1.6

Data is subject to errors and technical modifications. 121


MCCBs
Add-on Blocks Technical Data

Product Add-on blocks


Frame
x160 x160 x250
Number of poles 3,4 3,4 4
Tripping Access mechanical mechanical mechanical
Standards CEI/EN 60947-2 appendix B ü ü ü
Electrical Characteristics
Max rated current (40) In A In 125A 125 - 160A 160 - 250A
Rated service voltage Ue V AC Ue 240 - 415V 240 - 415V 240 - 415V
(50/60Hz)
Commercial

Mechanical Characteristics
Distribution

Top and bottom supply ü ü ü


For tripping, no additional external electrical sources ü ü ü
Possible operating with two active phases ü ü ü
Settings
Sensitivity IΔn IΔn (A) 300mA 0.03, 0.1, 0.3, 1, 0.03, 0.1, 0.3, 1,
3, 6A 3, 6A
Time delay Δt Δt (s) inst. inst., 0.06, 0.15, 0.3, 0.5, 1 inst., 0.06, 0.15, 0.3, 0.5, 1
Max. opening time ms 10 10 10
Delay add-on block is not possible if IΔn = 30mA - ü ü
Selective product - ü ü
Mechanical test button ü ü ü
Isolating test without cable removal ü ü ü
Electrical test button ü ü ü
Reset button ü ü ü
Sealable setting button - ü ü
Isolation level signaling by led 25 and 50% - ü ü
In running signalisation by led - ü ü
Residual default signaling contact ü ü ü
Signaling contact 50% Idn - ü ü
Anti-transient type AC ü ü ü
Pulsating DC current type A ü ü ü
High immunity type HI ü ü ü
-25°C ü ü ü
Accessories and connection
Steel terminal cage (x3/x4) ü ü accessories
Connection by lugs - - ü
Extended connections (x4) ü ü ü
Spreaders (x4) ü ü ü
Terminal covers (3P/4P) - - ü
Interphase barriers (x3) ü ü ü
Rigid cables connection capacity mm² 4 - 95 4 - 95 35 - 185
Flexible cables connection capacity mm² (with terminal) 4 - 70 4 - 70 35 - 150
Tightening torque Nm 6 6 12
Copper bar (width) in mm - - 25
Mounting
Clips on DIN rail ü ü -
Fixed on mounting plate - - ü
Fixation type side side bottom
Mounting by customer ü ü ü
Dimensions and weight
Dimensions (WxHxD) in mm W 100 100 140
Side mounted 4P
H 165 165 107.5
D 95 95 85
Weight 3P 1.4 1.4 -
4P 1.55 1.55 1.2

122 Data is subject to errors and technical modifications.


MCCBs
x160 Technical Data

MCCBs

220/240V AC 380/415V AC
IEC 60 947-2 IEC 60 947-2

HDA Icu 25 kA 18 kA

Ics 25 kA 18 kA

Commercial
Distribution
HHA Icu 35 kA 25 kA

Ics 25 kA 20 kA

PUSH TO TRIP
HCA Icm - 2.8 kA

Icw - 2 kA - 1s

Thermal settings

1 Ech. 30% 2
Ir
(x In)

TRIP

For DIN rail mounting, use HYA033H.

Magnetic adjustment fixed > 10 x In

3 Ech. 65%
In 16 - 50 A 63 - 80 A 100 - 125 A 160 A
Imag 600 A 1000 A 1500 A 1600 A
6

Thermal adjustment from 0.63 to 1 x In

IP
PUSH TO TR

Data is subject to errors and technical modifications. 123


MCCBs
x160 Technical Data

Dimensions

MCCB x160

AA 11 97
25

A (mm)

1P 24.8

3P 74.5
Commercial
Distribution

4P 99.5
111
130
114

45

25 25 15
68

Terminal covers for extended straight connections


Ech. 30%
AA C
61

A (mm)

1P 24.4
B

3P 74.5

4P 99.5
230

Terminal cover for extended spreader connections

A
A 61

A (mm)

3P 106.5
B

4P 141.5

124 Ech. 15% Data is subject to errors and technical modifications.


MCCBs
x160 Technical Data

Connection with terminals

Terminals for copper conductors (standard)

min. 6 mm2 max. 70 mm2

min. 6 mm2 max. 95 mm2


16
maxi
6 6 Nm
4

Commercial
Distribution
12 % noir

Terminals for aluminium / copper conductors (accessory)


HYA005H, HYA006H
PUSH TO TRIP

min. 35 mm2 max. 70 mm2

6
5 10 Nm

12 % noir

PUSH TO TRIP

Interphase barriers
PUSH TO TRIP

Ech. 40%

Ech. 60%

Ech. 40%

55 L (mm)

HYA019H 50

HYB019H 97
PUSH TO TRIP
L

AI1_x250_T1_19

Ech. 60%

AI1_x250_T1_19

PUSH TO TRIP

Data is subject to errors and technical modifications. 125


MCCBs
x160 Technical Data

Extended straight connections

3P
17 Ø8

28
67
Commercial
Distribution

203 mm
92

6 Nm
4P
25 25 25

PUSH TO TRIP

Extended spreader connections

Ech.
26.8 30%
16.8 10

Ø8
3P
Ø 8.3

54
17.6

12.7
87

203 mm
6 Nm
122

4P
PUSH TO TRIP
35 35 35

Ech. 30%

126 Data is subject to errors and technical modifications.


MCCBs
x160 Technical Data

Auxiliaries

Auxiliaries for MCCBs and moulded case switches

Commercial
Distribution
TRIP

PUSH TO TRIP

Mounting combination for auxiliaries and releases


Ech. 65%

AX
Auxiliary contact

Contact 4P Ech. 50% Bobine


auxiliaire 3P émission
AX SH
SH
Shunt trip

AX AL SH / UV

Signal Bobine à
défaut
AL UV minimum
AL UV
Undervoltage release
Alarm contact de tension

DUVR
DUVR
Delayed
undervoltage
release

Data is subject to errors and technical modifications. 127


x160 Add-on Block
Technical Data
4
A (I n) Characteristics
1
0.03 0.1 0.3 1 3 6 Reset button :
A
Signals add-on block tripping and must be reset before switching on the
inst. OK OK OK OK OK OK installation.

Test button for RCD function :


0.06 non OK OK OK OK OK
S ( t)

0,3 0,5
1
13
Checks the electrical operating of the MCCB / Add-on block
0,1
0,03
3
10

I n (A)
association.
0.15 non OK OK OK OK OK
0,15 0,3
0,5
3 0,06
1
Inst.
6 t (s)

I n (A) Mechanical test button :


0.5 0.3 non OK OK OK OK OK Checks the mechanical operating of the MCCB / Add-on block association.
Commercial

0,3 0,5
Distribution

B
0,1 1
3
0,03

0.5 non OK OK OK OK OK LED signaling residual current level in the installation:


t (s)
I n (A)

25% (orange) and 50% (red) IΔn; green light to signal correct operating. 0,06
0,15 0,3
0,5
1
Inst.

1 non OK OK OK OK OK Remote tripping and advanced warning (50% IΔn) signaling thanks to these
t (s)

contacts:
When associated with MCCB, the add-on block provides an earth fault
protection and protects against electrical shocks by direct or indirect contact. USH TO TRIP

The add-on blocks are protected against nuisance tripping caused by


V
transient voltages. It’s able to detect sinusoidal alternating currents and
residual pulsating directmax. 1.5 ( A type
currents max. 1.5 B
2 ). It also avoids miss
tripping (HI type - High Immunity).
12 V
1, 2, 3 . . . 12
12 Click
A

TEST
3 2 1
ON

A (I n)
PUSH TO TRIP

2.5
Clack ! 0.03 0.1 0.3 1 3 6
Earth leakage current (IΔn) and delay (Δt) setting Add-on block operating

inst. OK OK OK OK OK OK
incoming
2
N 0.06
L1 L2 L3 non OK OK OK OK OK
S ( t)

0.3 1
0.1
0.03
3
6 0.15 non OK OK OK OK OK
I n (A)

0,1
0,03
0,3 0,5
1
3

I n (A)
0,1
0,03
0,3 1
3
10

I n (A)
5
0.06
0.15 0.3
0.5 0.3 non OK OK OK
CA
OK OK
0,06
0,15 0,3
0,5 0,06
0,15 0,3
0,5 Inst. 1
1
1 Inst.

50%
Inst.

OK OK OK OK OK
t (s)

0.5 non
t (s)
t (s)

ON
electronic
1 non OK OK OK OK OK
125A
250A
test button
4
N L1 L2 L3
A outgoing
B
3 6

OK OK
max. 1.5 max. 1.5

OK OK A (IΔn) 0,1
0,03
0,3 0,5
1
13
3
10

I n (A)

OK OK
0,15 0,3
0,06 0,5

0.03 0.1 0.3 1 3 6


1
Inst.

12
t (s)

OK OK
Inst. OK
B
OK OK OK OK OK
12 Click
A
OK OK 0.06 no OK OK OK OK OK
S (Δt)

OK OK 0.15 no OK OK OK OK OK

0.3 no OK OK OK OK OK

0.5 no OK
V
OK OK OK OK 3
B
1 no OK OK OK OK OK
2.5
V
A

2 1

2.5
0.3 1
0.1 3
0.03 6
I n (A)
128 Data is subject to errors and technical modifications. 0.15 0.3
0.06 0.5
Inst. 1
x160 Add-on Block
Technical Data

Add-on block mounting


1 1 2 2
OFF OFF
j k
1 2
OFF OFF

OFF OFF

TRIP OFF

Commercial
Distribution
l m
3 4 4 5 5

4 5

Ech. 25%
PUSH TO TRIP PUSH TO TRIP

(inclinaison Isodraw angle 20-6 :


PUSH TO TRIP PUSH TO TRIP

O TRIP
- axe X = -90° PUSH TO TRIP PUSH TO TRIP
PUSH TO TRIP

- axe Y = +45°)
4 4 PUSH TO TRIP

4 6 Nm
Nm
6 Nm

6 Nm

Exclusive drawer assembly system allows quick mounting and makes MCCB
and add-on block association a complete monoblock unit.1 2
1 2
Reinforced insulation connection (class II)
1 2
System avoids the omission of terminal tightening

Dimensions

ON ON 3 3
ON A ON
ON 3
ON A PUSH TO TRIP
A
B
PUSH TO TRIP
PUSH TO TRIP

B
PUSH TO TRIP

3P 4P

PUSH TO TRIP
A A (mm) 100
Clack !
100 Clack !
B
PUSH TO TRIP

B (mm) 174.5 199.5


Clack !
165

1 1 2 ON = TRIP2 OFF ON = TRIP OFF


+ OFF ON + OFF ON
1 2 ON = TRIP OFF

6 Nm 6 Nm + OFF ON

B B
37

6 Nm
ON ON
ON
TRIP TRIP 4 ON B 4
PUSH TO TRIP

25 25 B
PUSH TO TRIP

B
ON PUSH TO TRIP
ON A PUSH TO TRIP
A
TRIP 4
B
PUSH TO TRIP

B PUSH TO TRIP
A
Data is subject to errors and technical modifications. A mini mini
A mini mini 129
6 6 6 6
mm
MCCBs x160
Technical Data

Tripping curve MCCB Disconnection Data

MCCB x160 Earth Fault Loop Impedance Data


Disconnection time 0.2s, 0.4s, 1s
10000

Device Instantaneous Instantaneous add 20% Zs = (230 x


rating trip (xIn) trip (A) tolerance (Ia) 0.95) / Ia
(A)
16 40.3 644.8 773.8 0.28
1000
20 32.2 644.0 773 0.28
25 25.7 643 771 0.28
Commercial
Distribution

32 20.13 644.2 773.0 0.28


40 15.0 600.0 720.0 0.30
100
50 12.0 600.0 720.0 0.30
63 16.6 1045.8 1255.0 0.17
Tripping time (sec)

80 13.1 1048.0 1258 0.17


100 15.4 1540.0 1848.0 0.12
126 12.3 1538 1845.0 0.12
125A, 50A

10
160A

100A, 40A

160 10.22 1635.2 1962.2 0.11


80A

63A

32A

25A

20A

Disconnection time 5s
16A

1 Device trip (xIn) Ia (A) Zs = (230 x 0.95)


rating / Ia
(A)
16 10 160 1.37
The magnetic 20 10 200 1.09
0.1
threshold trippting 25 10 250 0.87
curves is mean value.
The tripping area is 32 10 320 0.68
Irm ±20% 40 10 400 0.55
50 10 500 0.44
0.01 63 10 630 0.35
1 10 100
x In @ Tcal (A) 80 10 800 0.27
100 10 1000 0.22
125 10 1250 0.17
160 10 1600 0.14

Thermal constraint curve at 400V (Let-through energy) Current limiting curve at 400V (Let-through peak current)

MCCB x160 MCCB x160


7
10 100

0.25

160A
0.3 125A
100A
80A
63A
160A 40A
125A 16A
6 100A 0.5
10 80A
63A 10
0.7
40A
16A 0.8
Ip (kA)

0.9
I2t (A 2 s)

105
1

104
0.1 1 101 102 0.1
IPF (kA rms) 0.1 1 10 1 10 2
IPF (kA rms)

130 Data is subject to errors and technical modifications.


MCCBs x160 Single Pole 16A - 32A
Technical Data

Tripping Curve SP MCCB x160 16A - 32A

10,000
Earth Fault Loop Impedance To BS 7671:2018
Instantaneous trip current : Data
16A to 25A : 210A +/- 42A Disconnection time 0.2s, 0.4s, 1s
32A : 240A +/- 48A
Device rating Instantaneous Instantaneous add 20% Zs = 230 x
(A) trip (xIn) trip (A) tolerance (Ia) Cmin / Ia
1,000
16 13.0 210.0 252.0 0.87
20 10.5 210.0 252.0 0.87
25 8.5 210.0 252.0 0.87

Commercial
Distribution
100 32 7.5 240.0 288.0 0.76
Tripping time (sec)

10 Earth Fault Loop Impedance To BS 7671:2018


32A
25A

Data
20A

16A

Disconnection time 5s
Device rating Instantaneous Instantaneous If Magnetic Zs = 230
(A) trip (xIn) trip (A) trip add 20% x Cmin
1 tolerance (Ia) / Ia
16 11.0 176.0 176.0 1.24
20 10.5 210.0 210.0 0.99
25 8.5 212.5 255.0 0.86
0.1 32 7.5 240.0 288.0 0.76

0.01
1 10 100
x In @ Tcal (A)

Thermal constraint curve at 230V (Let through energy) Current limiting curve at 230V (Let through peak current)

1,000

100

0.25
32A

25A
0.3
16A - 20A

0.5
100 32A
25A
10
16A - 20A
0.7
Let-through energy I2t (kA2s)

Let-through peak current Ip (kA)

0.8

0.9

10 1

0.95
HDA up to 18kA

HDA up to 18kA

0.1
1 0.1 1 10 100
0.1 1 10
Prospective current (kA rms) Prospective current Iccp (kA rms)

The earth fault loop impedance requirements for larger devices can be
calculated by the formula given in BS7671:2008
Zs ≤ 230 x Cmin
la
Where la = In of MCCB x Mag setting x 1.2

Data is subject to errors and technical modifications. 131


MCCBs x250
Technical Data

MCCBs

220/240V AC 380/415V AC
IEC 60 947-2 IEC 60 947-2

HHB Icu 35 kA 25 kA
Ics 25 kA 20 kA

HNB Icu 85 kA 40 kA

Ics 40 kA 20 kA
Commercial
Distribution

PUSH TO TRIP PUSH TO TRIP

HCB Icm - 9 kA

Icw - 3 kA - 1s

Magnetic and thermal settings


Ech. 25%
1 2

6
5 1
8
TRIP 0.8

13 10 0.63
PUSH TO TRIP l i (xIn) l r (xIn)

Thermal adjustment from 0.63, 0.8, 1 x In

Magnetic adjustment from 6 to 13 x In (100 - 200A)



PUSH TO TRIP
from 5 to 11 x In (250A)

100 - 200A 250A PUSH TO TRIP

Ir (x In) 1 0.63 - 0.8 - 1 x In

Ii (x In) 2 6 - 8 - 10 - 13 x In 5 - 7 - 9 - 11 x In

0 - 100%
x In/Ii 3
0 - 60%
%0

6 1
8
100% 0.8

xIn / Ii 13 10 0.63
Ech. 50% l i (xIn) l r (xIn)

3 Ech. 50% 2 1
Ech. 80 %

132 Data is subject to errors and technical modifications.


MCCBs x250
Technical Data

Dimensions 105 (3 P)
140 (4 P)
MCCB x250 35 35 96

165
144
126

45

Commercial
Distribution
PUSH TO TRIP

35 24
68

Terminal covers for extended straight connections

A C
64

Ech. 30% A (mm)

3P 105

4P 140
55B

PUSH TO TRIP

1,9
1,7
55
100

Connection with end lugs Interphase barriers


3,7

55

Ø8

25 Ech. 20%
97

9 mm
Ø8 max.

25
25 mm
max.
Max.
6

5 12 Nm
PUSH TO TRIP

PUSH TO TRIP

55

Data is subject to errors and technical modifications. 133


MCCBs x250
Technical Data

Connection

Extended straight and spreader connections

23
23
Ø 11
Commercial
Distribution

6 12 Nm 6 12 Nm

PUSH TO TRIP

PUSH TO TRIP

48.5 48.5

13.5 35

11.5
Ø 11

3P 3P

23
52.5
29.5

Ø 11
29.5

Ø 8.5
11.5

36.5 23
93

226
226

120

128 168

4P 4P
35 35 35 50 50 50

Ech. 27% Ech. 27%

134 Data is subject to errors and technical modifications.


MCCBs x250
Technical Data

Accessories

Terminal cover for extended spreader connections

A
A 64 A B C
(mm) (mm) (mm)
3P 147.5 54.5 64
4P 196 54.5 64
B

Commercial
Distribution
PUSH TO TRIP

Terminal cover for rear connections

AA C
64
A
B

(mm)

3P 105

4P 140
Ech. 20 %

PUSH TO TRIP

Terminal covers for collar terminals

A C
A 64
A
(mm)
29B

3P 105

4P 140

Data is subject to errors and technical modifications. 135


MCCBs x250
Technical Data

Auxiliaries

Auxiliaries for MCCBs and moulded case switches


Commercial
Distribution

TRIP

PUSH TO TRIP

Mounting combination for auxiliaries and releases

AX
Auxiliary contact

Contact 4P SH Bobine
3P Shunt trip
auxiliaire Ech.
AX50% SH
émission

AX AX AL SH / UV

Signal Bobine à
AL
défaut UV minimum
Alarm contact AL UV
Undervoltage release
de tension

DUVR
Delayed
undervoltage
release
DUVR

AI1_x250_T1_08

136 Data is subject to errors and technical modifications.


MCCBs x250
Technical Data

Tripping curve Tripping curve

MCCB x250 MCCB h250 TM

10000 100000

Instantaneous trip current:


up to 200A = 13 x In +/-20%
250A = 11 x In +/- 20%

hour
1000 10000
déclenchement (s)

Commercial
Distribution
100 1000

Déclenchement

minute
Cold start
à froid From cold state

100
de (s)

10

Tripping time (sec)


Tempstime
Tripping

10
1

time
Déclenchement
Hot start
à chaud From hot state
(rated current)
(courant nominal)
(75% rated current)

second
1
0.1
min. max.

0.1

0.01

0.01

0.001
100 1000 10000
% In @ Tcal (A)
1 10 100
xIn (A)
Earth fault loop impedance (Zs) can be calculated from the formula
Zs ≤ 230x0.95
Ia
Where Ia = In of MCCB x mag setting x 1.2

Thermal constraint curve at 400V (Let-through energy) Current limiting curve at 400V (Let-through peak current)

MCCB x250 MCCB x250

109 100
250 A 0.25

100 A 0.3
8
10

0.5
10
0.7
107 0.8
Ip (kA)
I2t (x 106 A2 s)

0.9

106
1

105

104 0.1
2 3 4 5 0.1 1 10 100
10 10 10 10 IPF (kA)
IPF (kA)

Data is subject to errors and technical modifications. 137


Fuse MCB
Technical Data - Cascading Values

Upstream

Max Values (kA) Fuse BS 88

In (A) 10 16 20 25 32 40 45 50 63 80 100
6A 80 80 80 80 80 80 80 80 80 6 6
10A 80 80 80 80 80 80 80 80 80 6 6
16A - 80 80 80 80 80 80 80 80 42 6
20A - - 80 80 80 80 80 80 80 42 6
B Curve
Commercial
Distribution

MTN

25A - - - 80 80 80 80 80 80 42 6
32A - - - - 80 80 80 80 80 42 6
40A - - - - - 80 80 80 80 42 6
50A - - - - - - - 80 80 42 6
63A - - - - - - - - 80 42 23
6A 80 80 80 80 80 80 80 80 80 80 15
10A 80 80 80 80 80 80 80 80 80 80 15
16A - 80 80 80 80 80 80 80 80 80 80
20A - - 80 80 80 80 80 80 80 80 80
B Curve
NBN

25A - - - 80 80 80 80 80 80 80 80
32A - - - - 80 80 80 80 80 80 80
40A - - - - - 80 80 80 80 80 80
50A - - - - - - - 80 80 80 80
63A - - - - - - - - 80 80 80
0,5A 80 15 15 15 15 15 15 15 15 15 15
1A 80 80 80 80 80 80 80 15 15 15 15
2A 80 80 80 80 80 80 80 15 15 15 15
3A 80 80 80 80 80 80 80 80 80 15 15
Downstream

4A 80 80 80 80 80 80 80 80 80 15 15
6A 80 80 80 80 80 80 80 80 80 80 15
10A 80 80 80 80 80 80 80 80 80 80 80
C Curve
NCN

16A - 80 80 80 80 80 80 80 80 80 80
20A - - 80 80 80 80 80 80 80 80 80
25A - - - 80 80 80 80 80 80 80 80
32A - - - - 80 80 80 80 80 80 80
40A - - - - - 80 80 80 80 80 80
50A - - - - - - - 80 80 80 80
63A - - - - - - - - 80 80 80
0,5A 80 15 15 15 15 15 15 15 15 15 15
1A 80 80 80 80 80 80 80 15 15 15 15
2A 80 80 80 80 80 80 80 15 15 15 15
3A 80 80 80 80 80 80 80 80 80 15 15
4A 80 80 80 80 80 80 80 80 80 15 15
6A 80 80 80 80 80 80 80 80 80 80 15
10A 80 80 80 80 80 80 80 80 80 80 80
D Curve
NDN

16A - 80 80 80 80 80 80 80 80 80 80
20A - - 80 80 80 80 80 80 80 80 80
25A - - - 80 80 80 80 80 80 80 80
32A - - - - 80 80 80 80 80 80 80
40A - - - - - 80 80 80 80 80 80
50A - - - - - - - 80 80 80 80
63A - - - - - - - - 80 80 80
80A - - - - - - - - - 80 80
C Curve
HMC /
HMF

100A - - - - - - - - - - 80
125A - - - - - - - - - - -
80A - - - - - - - - - 80 80
D Curve
HMD

100A - - - - - - - - - - 80
125A - - - - - - - - - - -

138 Data is subject to errors and technical modifications.


Fuse RCBO
Technical Data - Cascading Values

Upstream

Max Values (kA) Fuse BS 88

In 10A 16A 20A 25A 32A 40A 45A 50A 63A 80A 100A
6A 80 80 80 80 80 80 80 80 80 6 6
10A 80 80 80 80 80 80 80 80 80 42 6
6kA, Type A
ADA3**G

16A - 80 80 80 80 80 80 80 80 42 6
B Curve,

20A - - 80 80 80 80 80 80 80 42 6

Commercial
Distribution
32A - - - - 80 80 80 80 80 42 6
40A - - - - - 80 80 80 80 42 6
45A - - - - - - 80 80 80 42 6
6A 80 80 80 80 80 80 80 80 80 80 10
10A 80 80 80 80 80 80 80 80 80 80 10
Downstream

10kA, Type A

16A - 80 80 80 80 80 80 80 80 80 10
ADA1**U
B Curve,

20A - - 80 80 80 80 80 80 80 80 10
25A - - - 80 80 80 80 80 80 80 10
32A - - - - 80 80 80 80 80 80 80
40A - - - - - 80 80 80 80 80 80
45A - - - - - - 80 80 80 80 80
6A 80 80 80 80 80 80 80 80 80 80 10
10A 80 80 80 80 80 80 80 80 80 80 10
6kA, Type A
ADA1**U

16A - - 80 80 80 80 80 80 80 80 10
C Curve,

20A - - - 80 80 80 80 80 80 80 10
25A - - - - 80 80 80 80 80 80 80
32A - - - - - 80 80 80 80 80 80
40A - - - - - - 80 80 80 80 80

Data is subject to errors and technical modifications. 139


MCB - RCBO
Technical Data - Cascading Values

Upstream

Max Values NBN NCN


(kA) B Curve C Curve
In (A) 6 10 13 16 20 25 32 40 50 63 0.5 1 2 3 4 6 10 13 16 20 25 32 40 50 63
6A 15 15 15 15 15 15 15 15 15 15 - - - - - 15 15 15 15 15 15 15 15 15 15
B Curve, 10kA Type A

10A - 15 15 15 15 15 15 15 15 15 - - - - - - 15 15 15 15 15 15 15 15 15
16A - - - 15 15 15 15 15 15 15 - - - - - - - - 15 15 15 15 15 15 15
ADA1**U

20A - - - - 15 15 15 15 15 15 - - - - - - - - - 15 15 15 15 15 15
Commercial
Distribution

Downstream

25A - - - - - 15 15 15 15 15 - - - - - - - - - - 15 15 15 15 15
32A - - - - - - 15 15 15 15 - - - - - - - - - - - 15 15 15 15
40A - - - - - - - 15 15 15 - - - - - - - - - - - - 15 15 15
45A - - - - - - - - 15 15 - - - - - - - - - - - - - 15 15
6A 15 15 15 15 15 15 15 15 15 15 - - - - - 15 15 15 15 15 15 15 15 15 15
C Curve, 10kA, Type A

10A - 15 15 15 15 15 15 15 15 15 - - - - - - 15 15 15 15 15 15 15 15 15
16A - - - 15 15 15 15 15 15 15 - - - - - - - - 15 15 15 15 15 15 15
ADA1**U

20A - - - - 15 15 15 15 15 15 - - - - - - - - - 15 15 15 15 15 15
25A - - - - - 15 15 15 15 15 - - - - - - - - - - 15 15 15 15 15
32A - - - - - - 15 15 15 15 - - - - - - - - - - - 15 15 15 15
40A - - - - - - - 15 15 15 - - - - - - - - - - - - 15 15 15
45A - - - - - - - - 15 15 - - - - - - - - - - - - - 15 15

Upstream

Max Values NDN HMB HMC / HMF HMD


(kA) D Curve B Curve C Curve D Curve
In (A) 0.5 1 2 3 4 6 10 13 16 20 25 32 40 50 63 80 100 125 80 100 125 80 100 125
6A - - - - - 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15
B Curve, 10kA Type A

10A - - - - - - 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15
16A - - - - - - - - 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15
ADA1**U

20A - - - - - - - - - 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15
Downstream

25A - - - - - - - - - - 15 15 15 15 15 15 15 15 15 15 15 15 15 15
32A - - - - - - - - - - - 15 15 15 15 15 15 15 15 15 15 15 15 15
40A - - - - - - - - - - - - 15 15 15 15 15 15 15 15 15 15 15 15
45A - - - - - - - - - - - - - 15 15 15 15 15 15 15 15 15 15 15
6A - - - - - 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15
C Curve, 10kA, Type A

10A - - - - - - 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15
16A - - - - - - - - 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15
ADA1**U

20A - - - - - - - - - 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15
25A - - - - - - - - - - 15 15 15 15 15 15 15 15 15 15 15 15 15 15
32A - - - - - - - - - - - 15 15 15 15 15 15 15 15 15 15 15 15 15
40A - - - - - - - - - - - - 15 15 15 15 15 15 15 15 15 15 15 15
45A - - - - - - - - - - - - - 15 15 15 15 15 15 15 15 15 15 15

Upstream

NKN / NBN / HMC / HMF HMD


Max Values (kA)
NCN / NDN C Curve D Curve

Icn 15kA 15kA 15kA


ARC9***
6kA 15 12 12
B Curve
Downstream

ARC9***
6kA 15 12 12
C Curve

ARC5***
10kA 15 15 15
B Curve

ARC5***
10kA 15 15 15
C Curve

140 Data is subject to errors and technical modifications.


MCB - AFDD, MCCB - MCB, MCCB - MCCB
Technical Data - Cascading Values

Upstream
x160 x250 H250 TM H250 TM+ H250 LSI
Downstream

Max Values (kA) 18kA 25kA 40kA 25kA 40kA 25kA 50kA 50kA 70kA 50kA 70kA
TM TM TM TM+ LSI

NBN /NCN / NDN 18 20 40 25 40 25 50 23 50 23 50

HMC
18 25 40 25 40 25 50 23 50 23 50
C Curve
HMD

Commercial
Distribution
18 25 40 25 40 25 50 23 50 23 50
D Curve

Upstream

HDA
Max Values x250
x160
(kA) 25 / 40kA
18 / 25kA

In 16 20 25 32 40 50 63 80 100 125 160 100A 125A 160A 200A 250A


6A 18 18 18 18 18 18 18 18 18 18 18 13 13 13 13 13
10A 18 18 18 18 18 18 18 18 18 18 18 13 13 13 13 13
B Curve, 10kA Type A
RCBO - ADA1**U

16A 18 18 18 18 18 18 18 18 18 18 18 13 13 13 13 13
20A - 18 18 18 18 18 18 18 18 18 18 13 13 13 13 13
Downstream

25A - - 18 18 18 18 18 18 18 18 18 13 13 13 13 13
32A - - - 18 18 18 18 18 18 18 18 13 13 13 13 13
40A - - - - 18 18 18 18 18 18 18 13 13 13 13 13
45A - - - - - 18 18 18 18 18 18 13 13 13 13 13
6A 18 18 18 18 18 18 18 18 18 18 18 13 13 13 13 13
10A 18 18 18 18 18 18 18 18 18 18 18 13 13 13 13 13
C Curve, 10kA, Type A
RCBO - ADA1**U

16A 18 18 18 18 18 18 18 18 18 18 18 13 13 13 13 13
20A - 18 18 18 18 18 18 18 18 18 18 13 13 13 13 13
25A - - 18 18 18 18 18 18 18 18 18 13 13 13 13 13
32A - - - 18 18 18 18 18 18 18 18 13 13 13 13 13
40A - - - - 18 18 18 18 18 18 18 13 13 13 13 13
45A - - - - - 18 18 18 18 18 18 13 13 13 13 13

Upstream
Max Values HDA / HHA HHB / HNB HHG / HNG / HEG HNC / HEC HND / HED HNE / HEE HNF / HEF
(kA) x160 TM x250 TM h250 TM h250 LSI h630 LSI h1000 LSI h1600 LSI
18kA 25kA 25kA 40kA 25kA 50kA 65kA 50kA 70kA 50kA 70kA 50kA 70kA 50kA 70kA
HDA / HHA 18kA - 25kA 25kA 40kA 25kA 40kA 40kA 40kA 40kA 40kA 40kA 40kA 40kA 40kA 40kA
x160 TM 25kA - - - 40kA - 50kA 65kA 50kA 70kA 50kA 50kA 50kA 50kA 50kA 50kA
HHB / HNB 25kA - - - 40kA - 50kA 65kA 50kA 70kA 50kA 50kA 50kA 50kA 50kA 50kA
x250 TM 40kA - - - - - 50kA 65kA 50kA 70kA 50kA 70kA 50kA 70kA 50kA 50kA
HHG / HNG 25kA - - - 40kA - 50kA 65kA 50kA 70kA 50kA 50kA 50kA 50kA 50kA 50kA
/ HEG 50kA - - - - - - 65kA - 70kA - 70kA - 70kA - 70kA
Downstream

h250 TM 65kA - - - - - - - - 70kA - 70kA - 70kA - 70kA


HNC / HEC 50kA - - - - - - - - 70kA - 70kA - 70kA - 70kA
h250 LSI 70kA - - - - - - - - - - - - - - -
HND / HED 50kA - - - - - - - - - - 70kA - 70kA - 70kA
h630 LSI 70kA - - - - - - - - - - - - - - -
HNE / HEE 50kA - - - - - - - - - - - - 70kA - 70kA
h1000 LSI 70kA - - - - - - - - - - - - - - -
HNF / HEF 50kA - - - - - - - - - - - - - - 70kA
h1600 LSI 70kA - - - - - - - - - - - - - - -

Data is subject to errors and technical modifications. 141


Fuse - MCB
Technical Data - Selectivity

Upstream

Max Values Fuse BS88


(kA) In 10A 16A 20A 25A 32A 40A 45A 50A 63A 80A 100A
6A 0.20 0.20 0.30 0.40 0.60 1.30 1.80 2.50 4.00 T T
10A - 0.20 0.30 0.40 0.50 1.10 1.50 2.10 3.30 T T
16A - - 0.30 0.30 0.40 0.90 1.20 1.70 2.70 5.30 T
20A - - - 0.30 0.40 0.80 1.10 1.50 2.30 4.70 T
B Curve
MTN

25A - - - - 0.40 0.70 0.90 1.30 2.10 4.10 T


32A - - - - - - 0.50 0.70 1.10 2.20 T
Commercial
Distribution

40A - - - - - - - 0.90 1.50 2.90 T


50A - - - - - - - - 1.30 2.50 T
63A - - - - - - - - - 2.10 5.30
6A - - - - - 0.80 1.10 1.60 2.80 6.40 T
10A - - - - - 0.70 1.00 1.40 2.40 5.10 T
16A - - - - - 0.60 0.80 1.10 1.90 4.10 13.60
20A - - - - - 0.50 0.70 1.00 1.70 3.60 11.00
B curve
NBN

25A - - - - - - 0.60 0.90 1.50 3.10 9.00


32A - - - - - - 0.60 0.80 1.30 2.70 7.40
40A - - - - - - - 0.70 1.10 2.30 6.10
50A - - - - - - - 0.60 1.00 1.90 5.10
63A - - - - - - - - - 1.60 4.30
0,5A 8.70 T T T T T T T T T T
1A - - - - 0.90 3.40 6.50 T T T T
Downstream

2A - - - - 0.70 2.70 4.80 T T T T


3A - - - - 0.50 1.50 2.20 3.30 6.20 T T
4A - - - - - 1.30 2.00 3.00 5.50 T T
6A - - - - - 1.00 1.40 1.90 3.10 6.50 T
C curve

10A - - - - - 0.80 1.10 1.50 2.20 4.00 11.40


NCN

16A - - - - - 0.70 1.00 1.20 1.90 3.40 8.40


20A - - - - - 0.70 0.90 1.10 1.70 3.10 7.40
25A - - - - - 0.60 0.80 1.00 1.60 2.90 6.70
32A - - - - - - - 0.90 1.40 2.70 6.20
40A - - - - - - - - 1.30 2.40 5.70
50A - - - - - - - - - 1.90 4.80
63A - - - - - - - - - - 4.40
0,5A 12.70 T T T T T T T T T T
1A - - - 0.50 1.00 3.40 5.90 T T T T
2A - - - - 0.90 3.00 5.10 T T T T
3A - - - - 0.70 1.80 2.70 3.90 7.30 T T
4A - - - - 0.50 1.30 2.10 3.10 5.60 T T
6A - - - - - 1.00 1.40 1.80 2.90 5.60 T
D curve

10A - - - - - 0.90 1.20 1.50 2.30 4.30 14.80


NDN

16A - - - - - 0.70 1.00 1.30 2.00 3.60 8.90


20A - - - - - - 0.90 1.10 1.70 3.20 7.80
25A - - - - - - - 1.00 1.50 2.90 7.00
32A - - - - - - - - 1.30 2.50 5.90
40A - - - - - - - - - 2.20 5.10
50A - - - - - - - - - - 4.20
63A - - - - - - - - - - -

142 Data is subject to errors and technical modifications.


Fuse - RCBO, Fuse - AFDD
Technical Data - Selectivity

Upstream

Max Values Fuse BS88


(kA) In 10A 16A 20A 25A 32A 40A 50A 63A 80A 100A
6A 0.10 0.20 0.30 0.40 0.50 1.00 1.60 3.00 T T
B Curve, 6kA, 30mA

10A - 0.20 0.30 0.40 0.50 0.90 1.50 2.70 6.00 T


16A - 0.20 0.30 0.50 0.90 1.40 2.30 4.80 T
ADA3**G

Type A

20A 0.30 0.40 0.80 1.30 2.10 4.30 T


32A - 0.60 1.10 1.50 3.10 T

Commercial
Distribution
40A - 1.00 1.40 2.80 T
45A 1.10 1.60 2.90 T
6A 0.10 0.20 0.30 0.40 0.50 1.00 1.60 3.00 7.10 T
B Curve, 10kA, 30mA

10A - 0.20 0.30 0.40 0.50 0.90 1.50 2.70 6.00 T


Downstream

16A 0.20 0.30 0.50 0.90 1.40 2.30 4.80 T


ADA1**U

Type A

20A 0.30 0.40 0.80 1.30 2.10 4.30 T


25A - 0.40 0.70 1.20 1.80 4.00 T
32A - 0.60 1.10 1.50 3.10 8.40
40A - 1.00 1.40 2.80 7.70
45A 1.10 1.60 2.90 7.00
6A 0.10 0.10 0.20 0.30 0.50 1.10 2.00 3.30 6.80 T
C Curve, 10kA, 30mA

10A - - 0.20 0.30 0.40 0.90 1.50 2.50 5.40 T


13A - - - 0.40 0.80 1.40 2.20 4.50 T
ADA1**U

Type A

16A - - - 0.70 1.20 1.90 3.70 T


20A - - - 1.10 1.70 3.50 T
25A - - - 1.30 2.60 7.50
32A - - - 2.40 6.60
40A - 1.30 2.60 6.20

Upstream
In
Max Values (kA) Icn
max 10A 16A 20A 25A 32A 35A 40A 50A 63A 80A 100A
ARC906D 6A 0.50 1.00 2.30 2.80 3.80 T T T T T T
ARC910D 10A - 0.70 1.40 1.70 2.20 3.50 4.30 T T T T
ARCxxx
1Ph+N

ARC916D 6kA 16A - 0.50 1.30 1.50 1.90 2.90 3.30 T T T T


B

ARC920D 20A - - 1.10 1.30 1.70 2.60 3.00 T T T T


ARC925D 25A - - - 1.10 1.50 2.40 2.80 5.40 T T T
ARC956D 6A 0.80 1.10 2.40 2.80 4.00 T T T T T T
ARC960D 10A 0.50 0.80 1.40 1.60 2.10 3.40 4.10 T T T T
ARCxxx
Downstream

1Ph+N

ARC966D 6kA 16A - - 1.30 1.50 1.90 3.00 3.50 T T T T


C

ARC970D 20A - - - - 1.50 2.30 2.60 5.20 T T T


ARC975D 25A - - - - - 2.20 2.50 4.80 T T T
ARC506D 6A 0.50 1.00 2.30 2.80 3.80 7.00 8.70 T T T T
ARC510D 10A - 0.70 1.40 1.70 2.20 3.50 4.30 T T T T
ARCxxx
1Ph+N

ARC516D 10kA 16A - 0.50 1.30 1.50 1.90 2.90 3.30 6.90 T T T
B

ARC520D 20A - - 1.10 1.30 1.70 2.60 3.00 6.00 T T T


ARC525D 25A - - - 1.10 1.50 2.40 2.80 5.40 8.80 T T
ARC556D 6A 0.80 1.10 2.40 2.80 4.00 7.20 8.40 T T T T
ARC560D 10A 0.50 0.80 1.40 1.60 2.10 3.40 4.10 T T T T
ARCxxx
1Ph+N

ARC566D 10kA 16A - - 1.30 1.50 1.90 3.00 3.50 7.50 T T T


C

ARC570D 20A - - - - 1.50 2.30 2.60 5.20 T T T


ARC575D 25A - - - - - 2.20 2.50 4.80 9.10 T T

Data is subject to errors and technical modifications. 143


Commercial
Distribution

144
Upstream
Max Values NBN B curve
(kA) In 6A 10A 13A 16A 20A 25A 32A 40A 50A 63A 1A 2A 3A 4A 6A 10A 13A 16A 20A 25A 32A 40A 50A 63A
6A - 0.06 0.10 0.14 0.20 0.25 0.45 0.59 0.75 0.93 - - - - - 0.20 0.27 0.38 0.56 0.79 0.89 1.13 1.44 1.77
10A - - - 0.10 0.15 0.20 0.38 0.54 0.68 0.85 - - - - - - 0.23 0.32 0.51 0.73 0.81 1.03 1.32 1.63
13A - - - 0.10 0.15 0.20 0.38 0.54 0.68 0.85 - - - - - - 0.23 0.32 0.51 0.73 0.81 1.03 1.32 1.63
MCB - MCB

16A - - - - 0.11 0.14 0.28 0.46 0.60 0.75 - - - - - - - - - - 0.72 0.92 1.17 1.45
NBN 20A - - - - - 0.11 - 0.39 0.56 0.70 - - - - - - - - - - 0.67 0.85 1.09 1.35
B curve 25A - - - - - - - 0.33 0.51 0.64 - - - - - - - - - - 0.61 0.78 1.00 1.24
32A - - - - - - - - 0.41 0.57 - - - - - - - - - - - 0.70 0.90 1.11
40A - - - - - - - - 0.30 0.51 - - - - - - - - - - - - 0.80 0.99
50A - - - - - - - - - 0.38 - - - - - - - - - - - - - 0.87
63A - - - - - - - - - - - - - - - - - - - - - - - -
0,5A 0.06 0.13 0.19 0.66 2.17 4.35 T T T T 0.01 0.04 0.06 0.10 0.16 0.45 0.75 T T T T T T T
Technical Data - Selectivity

1A 0.03 0.06 0.08 0.12 0.16 0.18 0.28 0.38 0.50 0.79 - 0.02 0.03 0.04 0.05 0.11 0.14 0.25 0.35 0.57 0.71 1.18 1.98 3.08
2A 0.03 0.05 0.07 0.10 0.13 0.15 0.23 0.31 0.41 0.55 - - 0.02 0.03 0.05 0.11 0.13 0.21 0.29 0.44 0.50 0.84 1.43 2.24
3A - 0.05 0.06 0.08 0.10 0.11 0.17 0.22 0.28 0.35 - - - - 0.09 0.11 0.15 0.21 0.30 0.34 0.44 0.64 0.99
4A - 0.04 0.06 0.07 0.10 0.11 0.16 0.21 0.27 0.34 - - - - - 0.09 0.11 0.15 0.20 0.29 0.32 0.42 0.58 0.87
6A - - 0.06 0.07 0.09 0.10 0.15 0.19 0.24 0.30 - - - - - 0.08 0.10 0.13 0.18 0.25 0.28 0.36 0.47 0.63
10A - - - - 0.08 0.09 0.14 0.17 0.22 0.28 - - - - - - 0.09 0.12 0.16 0.24 0.27 0.35 0.45 0.59
NCN
13A - - - - 0.08 0.09 0.14 0.17 0.22 0.28 - - - - - - 0.09 0.12 0.16 0.24 0.27 0.35 0.45 0.59
C curve
16A - - - - - - 0.13 0.17 0.22 0.27 - - - - - - - - - 0.23 0.26 0.33 0.43 0.54
20A - - - - - - - 0.17 0.21 0.26 - - - - - - - - - 0.22 0.25 0.32 0.41 0.52
25A - - - - - - - - - 0.26 - - - - - - - - - - 0.24 0.31 0.40 0.50

Downstream
32A - - - - - - - - - 0.25 - - - - - - - - - - - 0.31 0.39 0.48
40A - - - - - - - - - - - - - - - - - - - - - - 0.39 0.48
50A - - - - - - - - - - - - - - - - - - - - - - - 0.48
63A - - - - - - - - - - - - - - - - - - - - - - - -
0,5A 0.05 0.10 0.15 0.45 1.14 2.19 T T T T 0.01 0.02 0.04 0.06 0.10 0.25 0.33 8.51 T T T T T T
1A 0.03 0.05 0.07 0.12 0.16 0.19 0.30 0.41 0.58 0.88 - - 0.02 0.04 0.05 0.11 0.13 0.27 0.38 0.65 0.80 1.28 2.06 3.10
2A - 0.05 0.06 0.10 0.13 0.16 0.26 0.35 0.47 0.70 - - - 0.03 0.05 0.10 0.13 0.23 0.32 0.52 0.65 1.02 1.64 2.44
3A - 0.04 0.06 0.08 0.10 0.12 0.18 0.24 0.31 0.41 - - - - - 0.09 0.11 0.16 0.22 0.34 0.38 0.51 0.81 1.18
4A - - - 0.07 0.09 0.11 0.17 0.22 0.29 0.37 - - - - - 0.08 0.10 0.15 0.21 0.31 0.35 0.47 0.70 1.03
6A - - - - 0.09 0.10 0.14 0.19 0.24 0.30 - - - - - - 0.10 0.13 0.18 0.26 0.29 0.37 0.49 0.66
10A - - - - - - - 0.17 0.22 0.28 - - - - - - - - - 0.24 0.27 0.34 0.45 0.59
NDN
D curve 13A - - - - - - - 0.17 0.22 0.28 - - - - - - - - - 0.24 0.27 0.34 0.45 0.59
16A - - - - - - - - - 0.26 - - - - - - - - - - - 0.32 0.42 0.53
20A - - - - - - - - - - - - - - - - - - - - - 0.31 0.40 0.50
25A - - - - - - - - - - - - - - - - - - - - - - 0.40 0.49
32A - - - - - - - - - - - - - - - - - - - - - - - 0.48
40A - - - - - - - - - - - - - - - - - - - - - - - -
50A - - - - - - - - - - - - - - - - - - - - - - - -
63A

Data is subject to errors and technical modifications.


Upstream
Max Values NDN D curve HMC C curve HMD D curve
(kA) In 0,5A 1A 2A 3A 4A 6A 10A 16A 20A 25A 32A 40A 50A 63A 80A 100A 125A 80A 100A 125A
6A - - - - - 0.14 0.35 0.67 0.80 1.06 1.49 1.62 2.33 2.65 2.61 3.08 3.2 5.2 4.65 5.45
10A - - - - - - - 0.61 0.73 0.97 1.37 1.49 2.14 2.44 2.4 2.84 2.95 4.8 4.29 5.03
13A - - - - - - - 0.61 0.73 0.97 1.37 1.49 2.14 2.44 2.4 2.84 2.95 4.8 4.29 5.03
16A - - - - - - - - - 0.86 1.21 1.32 1.91 2.17 2.14 2.53 2.63 4.29 3.84 4.5
NBN 20A - - - - - - - - - 0.80 1.13 1.23 1.78 2.02 1.99 2.36 2.45 4.01 3.58 4.2
B curve 25A - - - - - - - - - - 1.04 1.13 1.64 1.86 1.84 2.17 2.26 3.7 3.3 3.88
32A - - - - - - - - - - - 1.01 1.47 1.67 1.65 1.96 2.03 3.33 2.97 3.49
40A - - - - - - - - - - - - 1.31 1.50 1.48 1.75 1.82 2.99 2.67 3.13
50A - - - - - - - - - - - - - 1.32 1.3 1.54 1.61 2.64 2.36 2.77
63A - - - - - - - - - - - - - - 1.13 1.34 1.39 2.29 2.04 2.4

Data is subject to errors and technical modifications.


0,5A 0.01 0.02 0.06 0.10 0.16 0.26 1.44 T T T T T T T T T T T T T
1A - - 0.03 0.05 0.07 0.10 0.20 0.44 0.58 1.03 2.13 2.54 5.48 7.56 7.26 T T T T T
2A - - - 0.04 0.06 0.09 0.17 0.36 0.44 0.73 1.53 1.84 4.05 5.34 5.17 7.8 8.64 T T T
3A - - - - - 0.14 0.25 0.30 0.41 0.69 0.82 1.74 2.27 2.2 3.12 3.37 T 7.6 T
4A - - - - - 0.14 0.24 0.29 0.39 0.62 0.73 1.50 1.93 1.87 2.6 2.8 7.27 5.85 7.96
6A - - - - - - 0.12 0.21 0.26 0.34 0.48 0.54 0.95 1.16 1.13 1.47 1.56 3.29 2.77 3.53
10A - - - - - - - 0.20 0.24 0.32 0.47 0.51 0.87 1.05 1.03 1.31 1.38 2.8 2.38 2.99
NCN
13A - - - - - - - 0.20 0.24 0.32 0.47 0.51 0.87 1.05 1.03 1.31 1.38 2.8 2.38 2.99
C curve
16A - - - - - - - - 0.23 0.31 0.44 0.48 0.79 0.95 0.93 1.17 1.24 2.44 2.09 2.61
20A - - - - - - - - - 0.30 0.43 0.47 0.75 0.89 0.87 1.09 1.15 2.22 1.91 2.36

Downstream
25A - - - - - - - - - 0.29 0.42 0.46 0.73 0.86 0.85 1.06 1.11 2.13 1.84 2.27
32A - - - - - - - - - - - 0.44 0.68 0.81 0.79 0.99 1.04 1.98 1.71 2.11
40A - - - - - - - - - - - - 0.67 0.80 0.78 0.97 1.02 1.92 1.66 2.04
50A - - - - - - - - - - - - - 0.80 0.78 0.96 1.01 1.84 1.6 1.95
63A - - - - - - - - - - - - - - 0.74 0.91 0.95 1.73 1.51 1.84
0,5A - 0.02 0.08 0.14 0.25 0.46 4.05 T T T T T T T T T T T T T
1A - - 0.03 0.04 0.06 0.10 0.19 0.48 0.66 1.13 2.20 2.59 5.27 7.35 7 T T T T T
2A - - - 0.04 0.06 0.08 0.16 0.41 0.53 0.90 1.74 2.05 4.12 5.27 5.12 7.66 8.54 T T T
3A - - - - 0.05 0.08 0.14 0.28 0.34 0.47 0.86 1.00 1.96 2.48 2.41 3.28 3.51 9.71 7.35 T
4A - - - - - - 0.13 0.25 0.31 0.43 0.75 0.87 1.71 2.16 2.1 2.86 3.06 8.08 6.1 9.07
6A - - - - - - 0.12 0.21 0.26 0.35 0.51 0.57 0.99 1.20 1.18 1.51 1.6 3.32 2.8 3.55
10A - - - - - - - 0.20 0.24 0.32 0.47 0.51 0.87 1.05 1.03 1.31 1.38 2.8 2.38 2.99
NDN
D curve 13A - - - - - - - 0.20 0.24 0.32 0.47 0.51 0.87 1.05 1.03 1.31 1.38 2.8 2.38 2.99
16A - - - - - - - - 0.22 0.30 0.43 0.47 0.77 0.92 0.9 1.13 1.19 2.34 2 2.49
20A - - - - - - - - - 0.29 0.42 0.46 0.73 0.87 0.85 1.07 1.12 2.16 1.86 2.3
25A - - - - - - - - - - 0.41 0.45 0.71 0.84 0.82 1.02 1.07 2.03 1.76 2.16
32A - - - - - - - - - - - 0.43 0.69 0.81 0.8 0.99 1.04 1.94 1.68 2.06
40A - - - - - - - - - - - - 0.67 0.79 0.77 0.96 1 1.86 1.61 1.97
50A - - - - - - - - - - - - - 0.76 - 0.92 0.97 1.76 1.53 1.86
63A - - 0.94 1.68 1.47 1.78

145
Technical Data - Selectivity
MCB - MCB Continued

Commercial
Distribution
MCB - RCBO
Technical Data - Selectivity

Upstream
Max NBN NCN
Values B Curve C Curve
(kA)
Commercial
Distribution

In 6A 10A 16A 20A 25A 32A 40A 50A 63A 0,5A 1A 2A 3A 4A 6A 10A 16A 20A 25A 32A 40A 50A 63A
6A - 0.05 0.08 0.09 0.11 0.16 0.20 0.25 0.31 - - - - - - 0.09 0.14 0.19 0.26 0.29 0.37 0.48 0.61
B Curve, 10kA Type A

10A - - 0.07 0.09 0.11 0.15 0.19 0.24 0.30 - - - - - - - 0.14 0.18 0.26 0.29 0.36 0.46 0.58
16A - - - 0.09 0.10 0.15 0.19 0.23 0.29 - - - - - - - - - 0.25 0.28 0.35 0.45 0.56
ADA1**U

20A - - - - - 0.15 0.18 0.23 0.29 - - - - - - - - - - 0.27 0.34 0.44 0.55


Downstream

25A - - - - - 0.14 0.18 0.23 0.28 - - - - - - - - - - 0.27 0.34 0.43 0.53


32A - - - - - - - 0.22 0.27 - - - - - - - - - - - - - 0.51
40A - - - - - - - - 0.27 - - - - - - - - - - - - - 0.50
45A - - - - - - - - - - - - - - - - - - - - - - -
6A - - 0.08 0.09 0.11 0.15 0.19 0.24 0.30 - - - - - - 0.09 0.14 0.18 0.26 0.29 0.37 0.47 0.60
C Curve, 10kA, Type A

10A - - - 0.09 0.10 0.15 0.19 0.24 0.29 - - - - - - - 0.14 0.18 0.25 0.28 0.36 0.45 0.57
16A - - - - - 0.15 0.19 0.23 0.29 - - - - - - - - - 0.25 0.28 0.35 0.45 0.56
ADA1**U

20A - - - - - - 0.18 0.23 0.29 - - - - - - - - - - 0.27 0.34 0.44 0.54


25A - - - - - - - 0.22 0.28 - - - - - - - - - - - 0.33 0.42 0.52
32A - - - - - - - - 0.27 - - - - - - - - - - - - - 0.50
40A - - - - - - - - - - - - - - - - - - - - - - 0.48
45A - - - - - - - - - - - - - - - - - - - - - - -

Upstream

Max NDN HMC / HMF HMD


Values D Curve C Curve D Curve
(kA)
In 0,5A 1A 2A 3A 4A 6A 10A 16A 20A 25A 32A 40A 50A 63A 80A 100A 125A 80A 100A 125A
6A - - - - - - 0.14 0.22 0.27 0.35 0.49 0.55 0.86 1.01 1.00 1.23 1.29 2.92 2.38 3.18
B Curve, 10kA Type A

10A - - - - - - - 0.22 0.26 0.34 0.48 0.52 0.81 0.95 0.93 1.14 1.19 2.60 2.11 2.83
16A - - - - - - - - 0.25 0.33 0.46 0.50 0.77 0.90 0.89 1.08 1.13 2.34 1.92 2.54
ADA1**U

20A - - - - - - - - - 0.32 0.45 0.49 0.76 0.88 0.87 1.06 1.11 2.17 1.81 2.34
Downstream

25A - - - - - - - - - - 0.44 0.48 0.73 0.85 0.84 1.02 1.07 2.05 1.71 2.21
32A - - - - - - - - - - - - 0.69 0.80 0.79 0.94 0.99 1.77 1.49 1.90
40A - - - - - - - - - - - - - 0.78 0.76 0.92 0.95 1.67 1.43 1.80
45A - - - - - - - - - - - - - 0.84 0.83 0.97 1.01 1.71 1.46 1.83
6A - - - - - - 0.13 0.22 0.26 0.34 0.48 0.53 0.84 0.99 0.97 1.20 1.26 2.84 2.31 3.09
C Curve, 10kA, Type A

10A - - - - - - - 0.21 0.25 0.33 0.47 0.51 0.80 0.93 0.91 1.12 1.17 2.51 2.04 2.72
16A - - - - - - - - - 0.33 0.46 0.50 0.77 0.89 0.87 1.06 1.11 2.24 1.84 2.43
ADA1**U

20A - - - - - - - - - - 0.45 0.49 0.75 0.87 0.85 1.03 1.08 2.10 1.74 2.27
25A - - - - - - - - - - - 0.47 0.72 0.83 0.81 0.99 1.03 1.96 1.62 2.11
32A - - - - - - - - - - - - - 0.78 0.77 0.92 0.96 1.70 1.45 1.83
40A - - - - - - - - - - - - - 0.75 0.73 0.88 0.92 1.62 1.40 1.74
45A - - - - - - - - - - - - - 0.82 0.80 0.95 0.98 1.63 1.42 1.75

146 Data is subject to errors and technical modifications.


Upstream
NBN NCN
Max Values (kA) B curve C curve
Icn
In max 6A 10A 16A 20A 25A 32A 40A 50A 63A 0,5A 1A 2A 3A 4A 6A 10A 16A 20A 25A 32A 40A 50A 63A
ARC906D 6A - 0.04 0.07 0.08 0.09 0.15 0.20 0.26 0.34 - - - - - - 0.08 0.13 0.18 0.28 0.32 0.44 0.59 0.77
AFDD ARC910D 10A - - 0.07 0.08 0.09 0.14 0.19 0.25 0.32 - - - - - - - 0.13 0.17 0.26 0.30 0.40 0.53 0.68
ARCxxx
ARC916D 6kA 16A - - - - 0.09 0.14 0.18 0.24 0.31 - - - - - - - - - - 0.29 0.39 0.51 0.65
1Ph+N
B ARC920D 20A - - - - - 0.14 0.18 0.23 0.30 - - - - - - - - - - 0.28 0.37 0.48 0.61
ARC925D 25A - - - - - 0.14 0.18 0.23 0.29 - - - - - - - - - - - 0.36 0.48 0.60
ARC956D 6A - - 0.07 0.08 0.09 0.15 0.20 0.26 0.34 - - - - - - 0.08 0.13 0.18 0.28 0.32 0.44 0.60 0.77
AFDD ARC960D 10A - - - 0.08 0.09 0.14 0.19 0.24 0.32 - - - - - - - 0.13 0.17 0.26 0.30 0.39 0.53 0.67
ARCxxx
ARC966D 6kA 16A - - - - - 0.14 0.18 0.24 0.31 - - - - - - - - - - 0.29 0.38 0.51 0.64
1Ph+N
C ARC970D 20A - - - - - - 0.18 0.23 0.30 - - - - - - - - - - 0.28 0.37 0.48 0.60
ARC975D 25A - - - - - - - 0.23 0.29 - - - - - - - - - - - 0.36 0.47 0.59
ARC506D 6A - 0.04 0.07 0.08 0.09 0.15 0.20 0.26 0.34 - - - - - - 0.08 0.13 0.18 0.28 0.32 0.44 0.59 0.77

Data is subject to errors and technical modifications.


AFDD ARC510D 10A - - 0.07 0.08 0.09 0.14 0.19 0.25 0.32 - - - - - - - 0.13 0.17 0.26 0.30 0.40 0.53 0.68
ARCxxx
ARC516D 10kA 16A - - - - 0.09 0.14 0.18 0.24 0.31 - - - - - - - - - - 0.29 0.39 0.51 0.65
1Ph+N
B ARC520D 20A - - - - - 0.14 0.18 0.23 0.30 - - - - - - - - - - 0.28 0.37 0.48 0.61
ARC525D 25A - - - - - 0.14 0.18 0.23 0.29 - - - - - - - - - - - 0.36 0.48 0.60
ARC556D 6A - - 0.07 0.08 0.09 0.15 0.20 0.26 0.34 - - - - - - 0.08 0.13 0.18 0.28 0.32 0.44 0.60 0.77
AFDD ARC560D 10A - - - 0.08 0.09 0.14 0.19 0.24 0.32 - - - - - - - 0.13 0.17 0.26 0.30 0.39 0.53 0.67
ARCxxx
ARC566D 10kA 16A - - - - - 0.14 0.18 0.24 0.31 - - - - - - - - - - 0.29 0.38 0.51 0.64
1Ph+N
C ARC570D 20A - - - - - - 0.18 0.23 0.30 - - - - - - - - - - 0.28 0.37 0.48 0.60
ARC575D 25A - - - - - - - 0.23 0.29 - - - - - - - - - - - 0.36 0.47 0.59

NDN HMC HMD


D curve C curve D curve

Downstream
Max Values (kA) Icn
In max 0,5A 1A 2A 3A 4A 6A 10A 16A 20A 25A 32A 40A 50A 63A 80A 100A 125A 80A 100A 125A
ARC906D 6A - - - - - - 0.12 0.23 0.29 0.40 0.62 0.69 1.09 1.27 1.25 1.57 1.72 5.27 4.07 5.87
AFDD ARC910D 10A - - - - - - - 0.22 0.27 0.37 0.55 0.61 0.93 1.08 1.06 1.29 1.35 3.37 2.68 3.71
ARCxxx
ARC916D 6kA 16A - - - - - - - - - 0.36 0.53 0.58 0.88 1.02 1.01 1.22 1.27 2.91 2.34 3.19
1Ph+N
B ARC920D 20A - - - - - - - - - - 0.50 0.55 0.83 0.95 0.94 1.13 1.17 2.43 1.98 2.65
ARC925D 25A - - - - - - - - - - 0.49 0.54 0.81 0.93 0.91 1.10 1.14 2.20 1.84 2.37
ARC956D 6A - - - - - - 0.12 0.23 0.29 0.40 0.62 0.69 1.09 1.28 1.25 1.57 1.70 4.58 3.64 5.03
AFDD ARC960D 10A - - - - - - - 0.21 0.27 0.37 0.55 0.60 0.92 1.07 1.05 1.27 1.33 3.30 2.62 3.63
ARCxxx
ARC966D 6kA 16A - - - - - - - - - 0.36 0.53 0.58 0.87 1.01 0.99 1.20 1.26 2.85 2.29 3.12
1Ph+N
C ARC970D 20A - - - - - - - - - - 0.50 0.55 0.82 0.94 0.92 1.11 1.16 2.36 1.92 2.56
ARC975D 25A - - - - - - - - - - - 0.53 0.79 0.91 0.89 1.07 1.11 2.19 1.79 2.38
ARC506D 6A - - - - - - 0.12 0.23 0.29 0.40 0.62 0.69 1.09 1.27 1.25 1.57 1.69 4.57 3.64 5.03
AFDD ARC510D 10A - - - - - - - 0.22 0.27 0.37 0.55 0.61 0.93 1.08 1.06 1.29 1.35 3.10 2.53 3.38
ARCxxx
ARC516D 10kA 16A - - - - - - - - - 0.36 0.53 0.58 0.88 1.02 1.01 1.22 1.27 2.73 2.24 2.96
1Ph+N
B ARC520D 20A - - - - - - - - - - 0.50 0.55 0.83 0.95 0.94 1.13 1.17 2.33 1.93 2.52
ARC525D 25A - - - - - - - - - - 0.49 0.54 0.81 0.93 0.91 1.10 1.14 2.14 1.81 2.30
ARC556D 6A - - - - - - 0.12 0.23 0.29 0.40 0.62 0.69 1.09 1.28 1.25 1.56 1.68 4.12 3.35 4.48
AFDD ARC560D 10A - - - - - - - 0.21 0.27 0.37 0.55 0.60 0.92 1.07 1.05 1.27 1.33 3.04 2.47 3.31
ARCxxx
ARC566D 10kA 16A - - - - - - - - - 0.36 0.53 0.58 0.87 1.01 0.99 1.20 1.26 2.68 2.20 2.90
1Ph+N
C ARC570D 20A - - - - - - - - - - 0.50 0.55 0.82 0.94 0.92 1.11 1.16 2.25 1.88 2.43
ARC575D 25A - - - - - - - - - - - 0.53 0.79 0.91 0.89 1.07 1.11 2.12 1.76 2.29
Technical Data - Selectivity
MCB - AFDD

147
Commercial
Distribution
MCCB - RCBO
Technical Data - Selectivity

Upstream

x160
Max Values x250 H250
18/25/40kA TM
(kA) 25/40kATM 50/70kA LSI
HDA

In 16A 20A 25A 32A 40A 50A 63A 80A 100A 125A 160A 100A 125A 160A 200A 250A 40A 125A 250A
6A 1.35 1.35 1.35 1.35 1.35 1.35 3.33 3.33 7.07 7.07 7.98 4.35 6.72 T T T T T T
B Curve 10kA type A

10A 1.26 1.26 1.26 1.26 1.26 1.26 2.96 2.96 6.31 6.31 7.15 3.87 5.99 9.78 T T T T T
Commercial
Distribution

16A
ADA1**U

- 1.19 1.19 1.19 1.19 1.19 2.64 2.64 5.45 5.45 6.13 3.42 5.19 8.18 T T T T T
RCBO

20A - 1.16 1.16 1.16 1.16 2.44 2.44 4.73 4.73 5.27 3.08 4.53 6.97 T T T T T
Downstream

25A - 1.12 1.12 1.12 2.30 2.30 4.49 4.49 5.00 2.92 4.29 6.59 9.81 T T T T
32A - 1.03 1.03 1.98 1.98 3.77 3.77 4.19 2.49 3.61 5.45 8.22 9.15 T T T
40A - 1.00 1.87 1.87 3.59 3.59 3.99 2.35 3.43 5.20 7.85 8.75 T T T
45A 1.05 1.90 1.90 3.56 3.56 3.94 2.38 3.41 5.09 7.38 8.12 T T T
6A 1.33 1.33 1.33 1.33 1.33 1.33 3.23 3.23 6.91 6.91 7.85 4.22 6.55 T T T T T T
10A 1.23 1.23 1.23 1.23 1.23 1.23 2.85 2.85 6.00 6.00 6.81 3.71 5.71 9.35 T T T T T
C curve 10kA type A

16A - 1.17 1.17 1.17 1.17 1.17 2.54 2.54 5.22 5.22 5.87 3.28 4.97 7.92 T T T T T
ADA1**

20A
RCBO

1.13 1.13 1.13 1.13 2.36 2.36 4.69 4.69 5.25 3.01 4.48 7.03 T T T T T
25A - 1.08 1.08 1.08 2.20 2.20 4.38 4.38 4.90 2.81 4.18 6.50 9.84 T T T T
32A 1.01 1.01 1.90 1.90 3.65 3.65 4.06 2.40 3.50 5.30 7.96 8.85 T T T
40A 0.97 1.80 1.80 3.42 3.42 3.79 2.26 3.27 4.92 7.25 8.03 T T T
45A 1.02 1.81 1.81 3.40 3.40 3.76 2.27 3.26 4.86 7.13 7.92 T T T

148 Data is subject to errors and technical modifications.


Upstream

Max Values x160 x250 H250 H250


(kA) 18 / 25 / 40kA TM 25 / 40kA TM 25 / 50 / 65kA TM 50 / 70kA LSI
In 16A 20A 25A 32A 40A 50A 63A 80A 100A 125A 160A 100A 125A 160A 200A 250A 20 32 50 63 100 125 160 200 250 40A 125A 250A
6A 1.20 1.63 2.22 3.13 4.26 5.81 7.92 T T T T T T T T T 1.63 2.22 3.13 4.26 5.81 7.92 T T T T T T
10A 1.11 1.52 2.07 2.91 3.97 5.41 7.35 T T T T T T T T T 1.52 2.07 2.91 3.97 5.41 7.35 T T T T T T
16A - 1.34 1.83 2.59 3.54 4.83 6.61 8.97 T T T 9.94 T T T T 1.34 1.83 2.59 3.54 4.83 6.61 T T T T T T
20A - - 1.70 2.40 3.27 4.46 6.13 8.38 T T T 9.30 T T T T - 1.70 2.40 3.27 4.46 6.13 T T T T T T
NBN
25A - - - 2.24 3.04 4.13 5.68 7.73 T T T 8.56 T T T T - - 2.24 3.04 4.13 5.68 T T T - T T
B curve
32A - - - - 2.74 3.73 5.14 7.03 9.30 9.30 T 7.77 T T T T - - - 2.74 3.73 5.14 T T T - T T
40A - - - - - 3.33 4.57 6.32 8.36 8.36 9.06 6.99 9.24 T T T - - - - 3.33 4.57 T T T - T T
50A - - - - - - 4.01 5.57 7.42 7.42 8.04 6.20 8.19 T T T - - - - - 4.01 T T T - T T
63A - - - - - - - 4.78 6.45 6.45 6.99 5.34 7.13 9.68 T T - - - - - - T T - T T

Data is subject to errors and technical modifications.


0,5A T T T T T T T T T T T T T T T T T T T T T T T T T T T T
1A 2.05 6.26 T T T T T T T T T T T T T T 6.26 T T T T T T T T T T T
2A 0.56 2.46 8.16 T T T T T T T T T T T T T 2.46 T T T T T T T T T T T
3A - - 1.28 3.81 8.22 T T T T T T T T T T T - 3.81 T T T T T T T T T T
4A - - 0.79 2.88 7.43 T T T T T T T T T T T - 2.88 T T T T T T T T T T
6A - - - 0.81 1.78 3.89 7.47 T T T T T T T T T - 0.81 3.89 7.47 T T T T T T T T
NCN 10A - - - 0.67 1.34 2.69 5.53 9.18 T T T T T T T T - 0.67 2.69 5.53 T T T T T T T T
C curve 16A - - - 0.58 0.97 1.63 2.79 4.87 7.76 7.76 8.79 5.86 9.06 T T T - 0.58 1.63 2.79 5.86 9.06 T T T - T T
20A - - - 0.56 0.91 1.50 2.50 4.25 6.80 6.80 7.65 5.08 7.87 T T T - 0.56 1.50 2.50 5.08 7.87 T T T - T T
25A - - - 0.54 0.88 1.44 2.39 4.05 6.48 6.48 7.25 4.83 7.45 T T T - 0.54 1.44 2.39 4.83 7.45 T T T - T T
32A - - - - 0.84 1.37 2.26 3.80 6.12 6.12 6.79 4.52 6.96 T T T - - 1.37 2.26 4.52 6.96 T T T - T T
40A - - - - - 1.31 2.13 3.50 5.56 5.56 6.29 4.13 6.46 9.78 T T - - 1.31 2.13 4.13 6.46 9.78 T T - T T
50A - - - - - - 1.99 3.23 5.07 5.07 5.78 3.80 5.96 8.66 T T - - - 1.99 3.80 5.96 8.66 T T - - T

Downstream
63A - - - - - - - 3.11 4.85 4.85 5.51 3.65 5.68 8.29 T T - - - - 3.65 5.68 8.29 T T - - T
0,5A T T T T T T T T T T T T T T T T T T T T T T T T T T T T
1A - 2.94 T T T T T T T T T T T T T T 2.94 T T T T T T T T T T T
2A - 1.41 9.75 T T T T T T T T T T T T T 1.41 T T T T T T T T T T T
3A - - 0.84 3.54 8.47 T T T T T T T T T T T - 3.54 T T T T T T T T T T
4A - - 0.66 2.58 7.29 T T T T T T T T T T T - 2.58 T T T T T T T T T T
6A - - - 0.70 1.61 3.69 7.40 T T T T T T T T T - 0.70 3.69 7.40 T T T T T T T T
NDN 10A - - - 0.63 1.25 2.47 5.00 8.48 T T T 9.90 T T T T - 0.63 2.47 5.00 9.90 T T T T - T T
D curve 16A - - - 0.56 0.95 1.62 2.81 4.96 7.83 7.83 8.83 6.00 9.09 T T T - 0.56 1.62 2.81 6.00 9.09 T T T - T T
20A - - - 0.54 0.89 1.47 2.47 4.24 6.74 6.74 7.52 5.07 7.72 T T T - 0.54 1.47 2.47 5.07 7.72 T T T - T T
25A - - - 0.52 0.85 1.39 2.32 3.93 6.32 6.32 7.05 4.68 7.24 T T T - 0.52 1.39 2.32 4.68 7.24 T T T - - T
32A - - - - 0.83 1.34 2.18 3.62 5.82 5.82 6.52 4.30 6.68 T T T - - 1.34 2.18 4.30 6.68 T T T - - T
40A - - - - - 1.26 2.04 3.33 5.28 5.28 6.02 3.93 6.18 9.25 T T - - 1.26 2.04 3.93 6.18 9.25 T T - - T
50A - - - - - - 1.94 3.11 4.85 4.85 5.51 3.65 5.68 8.29 T T - - - 1.94 3.65 5.68 8.29 T T - - -
63A - - - - - - - 2.93 4.49 4.49 5.08 3.41 5.24 7.77 9.58 T - - - - 3.41 5.24 7.77 9.58 T - - -
HMC / 80A - - - - - - - - 3.29 3.29 3.65 2.61 3.74 5.58 7.03 7.51 - - - - 2.61 3.74 5.58 7.03 7.51 - T T
HMF 100A - - - - - - - - - 3.29 3.65 - 3.74 5.58 7.03 7.51 - - - - - 3.74 5.58 7.03 7.51 - T T
C curve 125A - - - - - - - - - - 3.65 - - 5.58 7.03 7.51 - - - - - - 5.58 7.03 7.51 - - T
80A - - - - - - - - 3.25 3.25 3.52 2.71 3.59 4.90 5.86 6.27 - - - - 2.71 3.59 4.90 5.86 6.27 - T T
HMD
100A - - - - - - - - - - - - - 4.90 5.86 6.27 - - - - - - 4.90 5.86 6.27 - - T

149
Technical Data - Selectivity
MCCB - MCB

D curve
125A - - - - - - - - - - - - - - 5.86 6.27 - - - - - - - 5.86 6.27 - T T

Commercial
Distribution
Commercial
Distribution

150
Upstream

Max. val- x160 TM x250 TM h250 TM h250 LSI h630 LSI h1000 LSI h1600 LSI
ues 18 / 25 kA 25 / 40 kA 25 / 50 / 65 kA 70 kA 50 / 70 kA 50 / 70 kA 50 / 70 kA
(kA)
In (A) 16 20 25 32 40 50 63 80 100 125 160 100 125 160 200 250 20 32 50 63 100 125 160 200 250 40 125 250 250 400 630 630 800 1000 1250 1600
16 - - - - - - 2 2 2.9 2.9 3 2.15 2.9 4.1 5.6 5.4 - - - 1.2 2.15 2.9 4.1 5.6 5.4 T T T T T T T T T T T
20 - - - - - - 2 2 2.9 2.9 3 2.15 2.9 4.1 5.6 5.4 - - - 1.2 2.15 2.9 4.1 5.6 5.4 T T T T T T T T T T T
25 - - - - - - 2 2 2.9 2.9 3 2.15 2.9 4.1 5.6 5.4 - - - 1.2 2.15 2.9 4.1 5.6 5.4 T T T T T T T T T T T
MCCB - MCCB

32 - - - - - - 1.8 1.8 2.6 2.6 2.7 2 2.6 3.6 5 4.8 - - - 1.15 2 2.6 3.6 5 4.8 T T T T T T T T T T T
40 - - - - - - 1.6 1.6 2.35 2.35 2.4 1.8 2.35 3.3 4.3 4.2 - - - 1.1 1.8 2.35 3.3 4.3 4.2 - T T T T T T T T T T
50 - - - - - - 1.6 1.6 2.35 2.35 2.4 1.8 2.35 3.15 4.25 4.15 - - - 1.1 1.8 2.35 3.15 4.25 4.15 - T T T T T T T T T T

x160TM
63 - - - - - - - - 2.15 2.15 2.2 1.7 2.15 3 4.05 3.9 - - - - 1.7 2.15 3 4.05 3.9 - T T T T T T T T T T

18 / 25 kA
80 - - - - - - - - 2.15 2.15 2.2 1.7 2.15 2.9 3.9 3.8 - - - - 1.7 2.15 2.9 3.9 3.8 - T T T T T T T T T T
Technical Data - Selectivity

100 - - - - - - - - - - 2.1 - 1.95 2.75 3.7 3.6 - - - - - 1.95 2.75 3.7 3.6 - T T T T T T T T T T
125 - - - - - - - - - - 2.1 - - 2.65 3.5 3.4 - - - - - - 2.65 3.5 3.4 - 1.65 T T T T T T T T T
160 - - - - - - - - - - - - - - 3.45 3.35 - - - - - - - 3.45 3.35 - - T T T T T T T T T
100 - - - - - - - - - - - - 1.95 2.5 3.15 3.3 - - - - - 1.95 2.5 3.15 3 - T T T T T T T T T T
125 - - - - - - - - - - - - - 2.5 3.15 3.3 - - - - - - 2.5 3.15 3 - 1.65 T T T T T T T T T
160 - - - - - - - - - - - - - - 3.15 3.3 - - - - - - - 3.15 3 - - T T T T T T T T T

x250 TM
25 / 40kA
200 - - - - - - - - - - - - - - - 3.3 - - - - - - - - 3 - - T T T T T T T T T
250 - - - - - - - - - - - - - - - - - - - - - - - - - - - 3.25 T T T T T T T T
20 - - - - - - - - - - - 1.55 1.95 2.5 3.15 3.3 - 0.41 0.6 1 1.55 1.95 2.5 3.15 3 T T T T T T T T T T T

Downstream
32 - - - - - - - - - - - 1.55 1.95 2.5 3.15 3.3 - - 0.6 1 1.55 1.95 2.5 3.15 3 T T T T T T T T T T T
50 - - - - - - - - - - - 1.55 1.95 2.5 3.15 3.3 - - - 1 1.55 1.95 2.5 3.15 3 - T T T T T T T T T T
63 - - - - - - - - - - - 1.55 1.95 2.5 3.15 3.3 - - - - 1.55 1.95 2.5 3.15 3 - T T T T T T T T T T
100 - - - - - - - - - - - - 1.95 2.5 3.15 3.3 - - - - 1.55 1.95 2.5 3.15 3 - T T T T T T T T T T

h250TM
125 - - - - - - - - - - - - - 2.5 3.15 3.3 - - - - 1.55 1.95 2.5 3.15 3 - 1.65 T T T T T T T T T

25 / 50 / 65kA
160 - - - - - - - - - - - - - - 3.15 3.3 - - - - 1.55 1.95 2.5 3.15 3 - - T T T T T T T T T
200 - - - - - - - - - - - - - - - 3.3 - - - - - - - - 3 - - T T T T T T T T T
250 - - - - - - - - - - - - - - - - - - - - - - - - - - - 3.25 T T T T T T T T
40 - - - - - - - - - - - - - - - - - - - - - - - - - - 1.63 3.25 T T T T T T T T
125 - - - - - - - - - - - - - - - - - - - - - - - - - - - 3.25 T T T T T T T T

70kA
h250LSI
250 - - - - - - - - - - - - - - - - - - - - - - - - - - - - T T T T T T T T
250 - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 5.2 T T T T T T
400 - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - T T T T T T

h630LSI
50 / 70kA
630 - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - T T T T
630 - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - T T T

800 - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - T T T

50 / 70kA
h1000LSI
1000 - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - T T

1250 - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - T

1600 - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -

50 / 70kA
h1600LSI

Data is subject to errors and technical modifications.


MCCB - AFDD
Technical Data - Selectivity

Upstream

Max x160 x250


Values 18/25/40kA TM 25/40kA TM
(kA) IEC60898-1 Icn In max 16A 20A 25A 32A 40A 50A 63A 80A 100A 125A 160A 100A 125A 160A 200A 250A
ARC906D 6A 1.89 1.89 1.89 1.89 1.89 1.89 T T T T T T T T T T
AFDD ARC910D 10A 1.42 1.42 1.42 1.42 1.42 1.42 3.90 3.90 T T T 5.25 T T T T
ARCxxx
ARC916D 6kA 16A - 1.33 1.33 1.33 1.33 1.33 3.34 3.34 T T T 4.44 T T T T
1Ph+N
B ARC920D 20A n/a - 1.23 1.23 1.23 1.23 2.76 2.76 T T T 3.61 5.58 T T T
ARC925D 25A n/a n/a - 1.20 1.20 1.20 2.47 2.47 4.80 4.80 5.35 3.13 4.59 T T T

Commercial
Distribution
ARC956D 6A 1.85 1.85 1.85 1.85 1.85 1.85 5.29 5.29 T T T T T T T T
AFDD ARC960D 10A 1.40 1.40 1.40 1.40 1.40 1.40 3.81 3.81 T T T 5.15 T T T T
Downstream

ARCxxx
ARC966D 6kA 16A - 1.32 1.32 1.32 1.32 1.32 3.27 3.27 T T T 4.35 T T T T
1Ph+N
C ARC970D 20A n/a - 1.21 1.21 1.21 1.21 2.68 2.68 T T T 3.49 5.36 T T T
ARC975D 25A n/a n/a - 1.16 1.16 1.16 2.49 2.49 5.24 5.24 T 3.24 4.98 T T T
ARC506D 6A 1.84 1.84 1.84 1.84 1.84 1.84 5.28 5.28 T T T 7.12 T T T T
AFDD ARC510D 10A 1.42 1.42 1.42 1.42 1.42 1.42 3.53 3.53 7.50 7.50 8.48 4.61 7.12 T T T
ARCxxx
ARC516D 10kA 16A - 1.33 1.33 1.33 1.33 1.33 3.08 3.08 6.35 6.35 7.14 3.99 6.05 T T T
1Ph+N
B ARC520D 20A n/a - 1.23 1.23 1.23 1.23 2.62 2.62 5.21 5.21 5.83 3.35 4.98 7.72 T T
ARC525D 25A n/a n/a - 1.20 1.20 1.20 2.38 2.38 4.42 4.42 4.88 2.97 4.24 6.28 8.97 T
ARC556D 6A 1.81 1.81 1.81 1.81 1.81 1.81 4.69 4.69 T T T 6.14 9.52 T T T
AFDD ARC560D 10A 1.40 1.40 1.40 1.40 1.40 1.40 3.46 3.46 7.40 7.40 8.37 4.53 7.03 T T T
ARCxxx
ARC566D 10kA 16A - 1.32 1.32 1.32 1.32 1.32 3.03 3.03 6.24 6.24 7.02 3.91 5.94 9.43 T T
1Ph+N
C ARC570D 20A n/a - 1.21 1.21 1.21 1.21 2.53 2.53 4.94 4.94 5.51 3.21 4.72 7.25 T T
ARC575D 25A n/a n/a - 1.16 1.16 1.16 2.39 2.39 4.72 4.72 5.28 3.04 4.51 6.97 T T

Data is subject to errors and technical modifications. 151


Hager Ltd.
Hortonwood 50
Telford
Shropshire
TF1 7FT

Customer Contact Centre: 01952 675612


Technical Helpline: 01952 675689

hager.com/uk
sales@hager.co.uk
technical@hager.co.uk

Commercial Distribution