INTERFACE TECHNOLOGY
TERMINATION BOARD SOLUTIONS
We have been setting global standards for process automation equipment for over sixty
years, and we are the market leader for electronic interface modules, intrinsic safety barriers
and hazardous location protection technology.
South America
Germany São Paulo, Brazil
Committed to engineering excellence, our worldwide
headquarters is located in Mannheim, Germany. More
than 600 specialists are dedicated to continuing our
heritage of high quality and innovation.
Intrinsic Safety
Intrinsic safety (IS) is a protection technique used within various
hardware packages that limits the energy within an electronic
circuit to a point that is safe to operate within a hazardous
(explosive) location.
Surge Protection
Surge protection comes in a wide variety of configurations to
protect electronic equipment from damage and provides long-
term system operation reliability. It also diverts harmful voltage
transients and current spikes to ground.
Signal Conditioning
Signal conditioning is an important part of any automation system
where electrical isolation, electronic signal conversion, and
measurement accuracy are critical characteristics of the control
loop architecture.
06/2009
216312
Edition
System Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Termination Boards
H-System
Selection Tables. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Digital Inputs
Selection Tables. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Termination
Boards
Entity Parameters. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Digital Outputs
Selection Tables. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Digital Inputs
Entity Parameters. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Analog Inputs
Selection Tables. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Digital Outputs
Entity Parameters. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Analog Outputs
Selection Tables. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Accessories
Selection Tables. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Analog Outputs
range of accessories. The H-System includes a wide range of • As low as 4.5 mm per channel
H-System
Termination Boards
• For HiC and HiD isolated barrier modules
• 8- or 16-position Termination Boards
• Redundant and fused powered
• Diagnostic and fault monitoring
Digital Inputs
10
11
12
13
14
15
16
1
2
3
4
5
6
7
8
9
Modules and Termination Boards
Depending on the functionality and application, the
Digital Outputs
Solenoid/
Alarm
Driver available and can be wired in a daisy chain configuration.
ON
FAULT HART TX
06/2009
32 Channel
Multiplexer
2700
MUX
Hart
PWR
ON
OFF
H-System
Topology
This figure illustrates a typical H-System solution. It contains a
DIN mounting rail
Termination Board and a HART Communication Board.
Figure 7 Proper mounting of the H-System Termination Board
Termination HART
Board Communication
Fastening screws
Board
Field wiring
Termination
Boards
OFF ON
HART Multiplexer
Hart
32 Channel
2700
MUX
1
2
3
4
5
6
7
8
FAULT HART TX
ON
PWR
X1 X5
Digital Inputs
potential free
error output
Mounting the module on the Termination
Board
• Ensure that the red Quick Lok Bar (1) is in the upper
Control Power supply 1
position.
system Power supply 2
• Observe the plug orientation of the device. Insert the
Figure 6 H-System topology coding pins (2) of the module in the corresponding coding
holes on the board. Now center the adjustment pins (3) to
Digital Outputs
the adjustment holes on the Termination Board.
Mounting • Carefully press the device into the contacts and
The Termination Boards are mounted on a 35 mm DIN rail. adjustment holes.
The DIN rail is centered under the Termination Board. • For the mechanical adjustment of the module press the
red Quick Lok Bar (1) down on either side of the device
The H-System Termination Boards have been designed for
(see Figure 9)
protection category IP20 with isolated barriers installed (IP00
without modules) according to EN 60529; therefore, the This completes the mounting of a module.
boards must be appropriately protected against splashing
Analog Inputs
water and contamination.
3
06/2009
2
Figure 9 Proper mounting of an H-System isolated barrier
216312
Edition
du
ct
duct
du
ct
TB TB
Earth strip Earth strip
2 32 Field cable tray Field cable tray
5
6
7
8
D x W = 100 x 80 mm D x W = 100 x 80 mm D x W = 100 x 80 mm
1 31
16 x
16 x dual
dual channel
channel HiC
HiC module
module
16 x
Control side
Termination
Duct D x W = 100 x 80 mm
dual
Duct
Duct
16 x
16 x dual
dual channel
Safety Manager channel HiC
module
System connector SiCC-0001 HiC
module
7
8
16 x
16 x dual
dual channel
HiC
Digital Inputs
channel
HART interface connector HiC module
HiACA-UNI-FLK34-FLK34-*M* 16 x
16 x dual
dual channel
channel HiC
HiC module
potential free error output module
recommended cable:
IS Termination Boards can be located close to the field
X5 CA-HWC300-AIO-DIO-*M
Analog Inputs
X1 terminals.
HART interface connector
recommended cable:
HiACA-UNI-FLK34-FLK34-*M*
System cables
The Honeywell IOTAs and IS boards are connected with H-
System Termination Boards via plug-n-play system cables.
06/2009
H-System
Type of signal
0 Analog modules
2010 to 2020 Converters
2020 to 2030 Transmitter Power Supplies
2031 to 2040 Current Drivers
2060 to 2090 Temperature Converter
8 Digital modules
Termination
2820 to 2860 Switch Amplifiers
Boards
2870 to 2880 Solenoid
Housing
C 12.5 mm modules
D 18 mm modules
Hi H-System
Digital Inputs
Termination Boards
C – G P – – P F
Digital Outputs
A O Analog output
A I Analog input
D O Digital output
D I Digital input
A I O Analog input and output
U N I Analog input and output, digital input and output
Analog Inputs
0 8 8-channel Board
1 6 16-channel Board
3 2 32-channel Board
Module information
G Galvanic isolation
P Manufacturer Pepperl+Fuchs
C for HiC modules
Analog Outputs
Signal information
S Safety connection SIL2/3
D O Digital output
0 8 8-channel Board
Module information
G Galvanic isolation
P Manufacturer Pepperl+Fuchs
C for HiC modules
S 1-channel module
Termination
Module information
G Galvanic isolation
P Manufacturer Pepperl+Fuchs
C for HiC modules
S 1-channel module
Termination Board type
S Series C300
C Devices in according to ISA G3 Unused options may be left out.
Analog Inputs
Analog Outputs
06/2009
216312
Edition
Safety information The respective peak values of the field device and the
associated device with regard to explosion protection should
The corresponding data sheets, the Declaration of be considered when connecting intrinsically safe field devices
Conformity, the EC-Type Examination Certificate and with the intrinsically safe circuits of H-System devices
applicable certificates (see data sheet) are an integral part of (demonstration of intrinsic safety). EN 60079-14/
this document. IEC 60079-14 or NEC and CEC electrical codes for US and
Canada respectively must be observed (where appropriate). If
H-System
Intended use available, also the product certification control drawing must
be observed.
Laws and regulations applicable to the usage or planned
purpose of usage must be observed. Devices are only If more channels of one device are to be connected in parallel,
approved for proper usage in accordance with intended use. it must be ensured that the parallel connection is made
Improper handling will result in voiding of any warrantee or directly at the terminals. For the demonstration of intrinsic
manufacturer's responsibility. safety, the maximum values of the parallel connection are to
be regarded.
These devices are used in C&I technology for the galvanic
isolation of C&I signals, such as 20 mA and 10 V unit signals, The EC-Type Examination Certificates or standard
and also for the adaptation and/or standardization of signals. certificates/approvals should be observed. It is especially
Devices which have intrinsically safe control circuits are used important to observe the "special conditions" if these are
Termination
to operate field devices within hazardous areas. included in the certificates.
Boards
The devices are not suitable for the isolation of signals in
power engineering, unless this is specifically referred to in the Installation and commissioning of the
respective data sheet. interface devices within Zone 2/Div. 2 of
Protection of operating personnel and the system is not the hazardous area
ensured if the product is not used in accordance with its Only devices with the corresponding manufacturer's
intended use. Declaration of Conformity or separate certificate of conformity
Digital Inputs
Intrinsic safety circuits that were operated with circuits of other can be installed in Zone 2/Div. 2.
types of protection may not be used as intrinsically safe The individual data sheets indicate whether these conditions
circuits afterwards. are met.
Installation and commissioning For US and Canada installations, in Zone 2/Div. 2 follow the
NEC and CEC wiring methods. The enclosure must be able to
Commissioning and installation must be carried out by accept Zone 2/Div. 2 wiring methods. The referenced product
specially trained and qualified personnel only. certification control drawing must be observed.
For all other applications, the devices should be installed in a
Digital Outputs
Installation of the interface devices in the switch or junction box that:
safe area • meets at least IP54 in accordance to EN 60529.
The devices are constructed to satisfy the IP20 protection • meets to the requirements of resistance to light and
classification and must be protected from adverse resistance to impact according to EN 60079-0/
environmental conditions such as water spray or dirt IEC 60079-0.
exceeding the pollution degree 2.
• meets to the requirements of thermal endurance
The devices must be installed outside the hazardous area! according to EN 60079-15/IEC 60079-15.
Depending on the level of protection, the intrinsically safe • must not cause ignition danger by electrostatic charge
Analog Inputs
circuits of the devices (light blue identification on the device) during intended use, maintenance and cleaning.
can be located in the hazardous area. It is especially Depending on the level of protection, the intrinsically safe
important to ensure that the intrinsically safe circuits are circuits of the devices (light blue identification on the device)
safely separated from all non-intrinsically safe circuits. can be located in the hazardous area. It is especially
The installation of the intrinsically safe circuits is to be important to ensure that the intrinsically safe circuits are
conducted in accordance with the relevant installation safely separated from all non-intrinsically safe circuits.
regulations. The installation of the intrinsically safe circuits is to be
Analog Outputs
The respective peak values of the field device and the Technical data
associated device with regard to explosion protection should
be considered when connecting intrinsically safe field devices
with the intrinsically safe circuits of H-System devices Electrical data
(demonstration of intrinsic safety). EN 60079-14/ Power supply (modules)
IEC 60079-14 or NEC and CEC electrical codes for US and
Canada respectively must be observed (where appropriate). If 24 V DC -15 %, +25 %, (20.4 V DC to 30 V DC)
H-System
available, also the product certification control drawing must Each module is protected internally. The Termination Boards
be observed. have redundant power supply connections with fuses that can
be replaced by the customer.
If more channels of one device are to be connected in parallel,
it must be ensured that the parallel connection is made
directly at the terminals. For the demonstration of intrinsic Mechanical data
safety, the maximum values of the parallel connection are to Location
be regarded.
Mounting outside hazardous areas possible as well as in
The EC-Type Examination Certificates, standard Zone 2/Div. 2 where a manufacturer's Declaration of
certificates/approvals or the manufacturer's Declaration of Conformity exists.
Conformity should be observed. It is especially important to
Termination
observe the "special conditions" if these are included in the Protection degree
Boards
Fault elimination
• Board for 16 HiC modules approx. 900 g
No changes can be made to devices which are operated in • Board for 8 HiD modules approx. 500 g
hazardous areas. Repairs on the device are not allowed.
• Board for 16 HiD modules approx. 1000 g
Isolation coordinates for devices with Ex- Modules:
certificate according to EN 50020 and • HiC module approx. 100 g
EN 60079-11 • HiD module approx. 140 g
Digital Outputs
in secluded electrical operating sites where only skilled • Board for 16 HiC modules: 273 x 155 x 153 mm
personnel or electrically instructed personnel will have • Board for 8 HiD modules: 201 x 155 x 153 mm
admission or access.
• Board for 16 HiD modules: 357 x 155 x 153 mm
The devices are assessed for pollution degree 2 and
Modules:
overvoltage category II according to EN 50178.
• HiC module: 12.5 x 106 x 130 mm
For additional details, see data sheets.
• HiD module: 18 x 106 x 130 mm
Housing drawings please refer to the appendix.
Analog Outputs
06/2009
216312
Edition
H-System
Housing: V2 according to UL 94 standard. (Unless stated • Software acc. to NAMUR NE53
otherwise all details relate to the reference conditions.)
Digital inputs/outputs according to NAMUR
Ambient conditions The standards references for this interface have changed
many times:
Ambient temperature:
German standard (old): DIN 19234: Electrical distance
-20 °C to 60 °C, (273 K to 333 K) sensors – DC interface for distance sensors and switch
amplifiers; 1990-06
Storage temperature:
European standard (old): EN 50227: Low voltage switch gear
-40 °C to 70 °C, (253 K to 343 K)
Termination
and control gear – control devices and switching elements –
Boards
Relative humidity: proximity switches, DC interface for proximity sensors and
switch amplifiers (NAMUR), 1996-10
max. 95 % no moisture condensation
German version (old): DIN EN 50227: Low voltage switch
Reference conditions gear – control devices and switching elements – proximity
• temperature: 23 °C (296 K) switches, DC interface for proximity sensors and switch
amplifiers (NAMUR), 1997, German nomenclature VDE 0660,
• relative humidity: 50 %
part 212
• supply voltage: 24 V DC
Digital Inputs
Current designation: DIN EN 60947-5-6: Low voltage switch
• working resistance, where applicable: 250 Ω gear – control devices and switching elements – proximity
• full scale value: 20 mA switches, DC interface for proximity sensors and switch
amplifiers (NAMUR), 2000, German nomenclature. VDE 0660
part 212
Current IEC designation: IEC 60947-5-6: Low voltage
switch gear and control gear – part 5-6: Control circuit devices
and switching elements – DC interface for proximity sensors
Digital Outputs
and switching amplifiers (NAMUR), 1999.
Analog Inputs
Analog Outputs
06/2009
216312
Edition
06/2009
216312
Edition
H-System
Digital Inputs
Digital Outputs
Termination
Analog Inputs
Boards
CC-TAIX01/11 16 HiC2025 * 1 SC-GPCS-UNI16-PF 16 16 1 18
Temperature Inputs
Digital Inputs
Analog Outputs
Digital Outputs
Analog Inputs
Analog Outputs
06/2009
216312
Edition
Modules
Digital Inputs
Zone 2/Division 2
H-System
(Loop Powered)
(active/passive)
(Bus Powered)
Dry Contacts
Transistor
Line Fault
Detection
Channels
Mounting
MAMUR/
24 V DC
24 V DC
Safety
Timer
Relay
HiC
HiD
SIL
HiC2821 1 2 2 22
HiC2822 2 2 2 23
Digital Outputs
Termination
Boards
Zone 2/Division 2
(Loop Powered)
(Bus Powered)
Contact Input
Logic Input
Voltage (V)
Channels
Mounting
24 V DC
24 V DC
Digital Inputs
HiC
HiD
SIL
HiC2871 1 12 40 3 24
HiD2874 2 12 40 25
Analog Inputs
Digital Outputs
Zone 2/Division 2
Current Sources
0/4 mA ... 20 mA
0/4 mA ... 20 mA
(Loop Powered)
Signal Splitting
(Bus Powered)
0/1 V ... 5 V
Channels
Mounting
(Source)
24 V DC
24 V DC
SMART
(Sink)
HiC
HiD
SIL
Analog Inputs
HiC2025 1 2 26
HiD2030SK 2 2 27
(Bus Powered)
4 mA ... 20 mA
Potentiometer
Channels
Mounting
1 V ... 5 V
24 V DC
24 V DC
mV/V
RTD
HiC
HiD
SIL
TC
06/2009
HiD2082 2 28
216312
Edition
Zone 2/Division 2
Lead Monitoring
0/4 mA ... 20 mA
1.5 mA ... 50 mA
0/4 mA ... 20 mA
1.5 mA ... 50 mA
(Loop Powered)
(Bus Powered)
H-System
Channels
Mounting
24 V DC
24 V DC
SMART
HiC
HiD
SIL
HiC2031 1 2 29
HiD2032 2 30
Accessories
Termination
Boards
HART Multiplexers
RS 485 Connection
Zone 2/Division 2
Supply 24 V DC
Digital Inputs
Mounting
Channels
HiD Mux2700 32 32
Termination Boards
Digital Outputs
Model Number Page
RS 485 Connection
Zone 2/Division 2
2 x 16 Channels
Supply 24 V DC
4 x 8 Channels
Power Supply
Redundant
Mounting
Channels
Analog Inputs
HiATB01-HART-2X16 32 33
HiATB01-HART-4X8 32 34
Additional Accessories
37-pin Indicators/settings
Boards
The Termination Boards are supplied with Dimensions 273 x 155 x 153 mm (L x W x H),
a robust glass fibre reinforced plastic height including module assembly
housing as standard. This design permits Mounting 35 mm DIN rail
the fast and reliable installation in the Accessories
switch cabinet. Designation optional accessories:
Label Carrier HiALC-HI*TF-SET-***
Analog Inputs
Diagrams
2 32
TB1 TB2
17 ... 32
TDIL01/11
1 ... 16
1 31 TDOB01/11
Analog Outputs
TAIX01/11
TAOX01/11
10
11
12
13
14
15
16
1
2
3
4
5
6
7
8
9
X1
06/2009
24 V DC (I),
24 V DC (II)
216312
ERR
Zone 0, 1, 2 Zone 2
Edition
Div. 1, 2 Div. 2
H-System
Ripple ≤ 10 % • Recommended system cable:
Fusing 4A CA-HW32-F-D37-...
Power loss ≤ 500 mW, without module
• 24 V DC supply voltage
Reverse polarity protection yes
Redundancy
• Hazardous area: pluggable screw
Supply Redundancy available. The supply for the modules is
terminals, blue
decoupled, monitored and fused. • Safe area: Sub-D connector (male),
Output 37-pin
Connection terminal block TB4 (1, 2), error message output,
NO contact Function
Fault signal max. 40 V, 2 A
Termination
The Termination Board has 16 plug-in
Indicators/settings
Boards
slots.
Display elements LEDs PWR ON (power supply)
- LED power supply I, green LED The function of the Termination Board as
- LED power supply II, green LED well as the connector pin assignment
LED Fault (fault indication), red LED exactly fit the requirement of Honeywell
Conformity systems.
Electromagnetic compatibility NE 21
Information about missing supply voltage
Protection degree IEC 60529
of the interface modules is available for
Ambient conditions
Digital Inputs
the system as potential free relay contact.
Ambient temperature -20 ... 60 °C (253 ... 333 K)
Wiring errors from field will be reported if
Mechanical specifications
the interface module supports this
Protection degree IP20
function.
Connection connection hazardous area (field side):
pluggable screw terminals, blue The Termination Boards are supplied with
connection safe area (process side): a robust glass fibre reinforced plastic
Sub-D connector (male), 37-pin housing as standard. This design permits
Mass approx. 900 g the fast and reliable installation in the
Digital Outputs
Dimensions 273 x 155 x 153 mm (L x W x H), switch cabinet.
height including module assembly
Mounting 35 mm DIN rail
Accessories
Designation optional accessories:
Label Carrier HiALC-HI*TF-SET-***
Analog Inputs
Diagrams
2 32
TB1 TB2
1 31
TDIL01/11
Analog Outputs
10
11
12
13
14
15
16
1
2
3
4
5
6
7
8
9
X1 X2
06/2009
24 V DC (I),
24 V DC (II)
216312
ERR
Zone 0, 1, 2 Zone 2
Edition
Div. 1, 2 Div. 2
slots.
Display elements LEDs PWR ON (power supply)
The function of the Termination Board as - LED power supply I, green LED
well as the connector pin assignment - LED power supply II, green LED
exactly fit the requirement of Honeywell LED Fault (fault indication), red LED
systems. Conformity
Electromagnetic compatibility NE 21
Information about missing supply voltage
Protection degree IEC 60529
of the interface modules is available for
Ambient conditions
Digital Inputs
Diagrams
2 32
TB1 TB2
1 31
TDOB01/11
Analog Outputs
10
11
12
13
14
15
16
1
2
3
4
5
6
7
8
9
X2 X1
06/2009
24 V DC (I),
24 V DC (II)
216312
ERR
Zone 0, 1, 2 Zone 2
Edition
Div. 1, 2 Div. 2
H-System
Ripple ≤ 10 % • Recommended modules:
Fusing 2A HiD2030SK (AI), HID2082 (Temp.),
Power loss ≤ 500 mW, without module HiD2032 (AO)
Reverse polarity protection yes • Recommended system cable:
Redundancy CA-HW32-F-D37-...
Supply Redundancy available. The supply for the modules is
decoupled, monitored and fused.
• 24 V DC supply voltage
Output • Hazardous area: pluggable screw
Connection terminal block TB4 (1, 2), error message output, terminals, blue
NO contact • Safe area: Sub-D connector (male),
Fault signal max. 40 V, 2 A 37-pin
Termination
Indicators/settings
Boards
Display elements LEDs PWR ON (power supply) Function
- LED power supply I, green LED
- LED power supply II, green LED Termination Boards are made to carry
LED Fault (fault indication), red LED isolated barriers and provide terminal
Conformity connection for wiring. The termination
Electromagnetic compatibility NE 21 board and the isolated barriers build the
Protection degree IEC 60529 connection between field and system
Ambient conditions level.
Digital Inputs
Ambient temperature -20 ... 60 °C (253 ... 333 K) System connectors are syntonized to the
Mechanical specifications requirements of the I/O cards used in the
Protection degree IP20 particular automation system. They
Connection connection hazardous area (field side): ensure fast and fail-safe connection.
pluggable screw terminals, blue
connection safe area (process side): Information about missing supply voltage
Sub-D connector (male), 37-pin of the interface modules is available for
Mass approx. 500 g the system as potential free relay contact.
Wiring errors from field will be reported if
Digital Outputs
Dimensions 201 x 155 x 153 mm (L x W x H),
height including module assembly the interface module supports this
Mounting 35 mm DIN rail function.
Accessories The Termination Boards are supplied with
Designation optional accessories: a robust glass fibre reinforced plastic
Label Carrier HiALC-HI*TF-SET-***
housing as standard. This design permits
the fast and reliable installation in the
switch cabinet.
Analog Inputs
Diagrams
2 32
TB1
1 31 TAIX01/11
TAOX01/11
Analog Outputs
HART
1
2
3
4
5
6
7
8
X1 X5
06/2009
24 V DC (I),
216312
24 V DC (II)
ERR
Zone 0, 1, 2 Zone 2
Edition
Div. 1, 2 Div. 2
form A normally open relay contact for the Mechanical life 107 switching cycles
safe area load. The module output Transfer characteristics
changes state when the input signal Switching frequency ≤ 10 Hz
changes state. The normal output state Ambient conditions
can be reversed with the selector Ambient temperature -20 ... 60 °C (253 ... 333 K)
switches on the side of the unit. Mechanical specifications
Protection degree IP20
One additional relay is available for the
Mass approx. 100 g
Digital Inputs
Diagrams
Front view
LED green:
Power supply HiC2821
PWR
1+ 11
10 kΩ I
Switch 1 ... 4
4- 14
HiC 12
2821 II
1ch
Sw/prox
Repeater
15
06/2009
Place for
labeling
216312
22 Pepperl+Fuchs Group USA: +1 330 486 0002 Germany: +49 621 776 2222 Singapore: +65 6779 9091
www.pepperl-fuchs.com pa-info@us.pepperl-fuchs.com pa-info@de.pepperl-fuchs.com pa-info@sg.pepperl-fuchs.com
Catalog_DCS_Honeywell_SC_eng.book Seite 23 Donnerstag, 25. Juni 2009 5:28 17
H-System
Rated values acc. to EN 60947-5-6 (NAMUR)
Open circuit voltage/short-circuit approx. 10 V DC/approx. 8 mA • Up to SIL2 acc. to IEC 61508
current
Switching point/switching hysteresis 1.2 ... 2.1 mA/approx. 0.2 mA Function
Line fault detection breakage I ≤ 0.1 mA, short-circuit I ≥ 6.5 mA
Pulse/Pause ratio ≥ 20 ms/≥ 20 ms This isolated barrier is used for intrinsic
Output safety applications. It transfers digital
Output I signal; relay signals (NAMUR sensors/mechanical
Output II signal; relay contacts) from a hazardous area to a safe
Contact loading 50 V DC/0.5 A area.
Minimum switch current 2 mA/24 V DC The proximity sensor or switch controls a
Termination
Energized/de-energized delay ≤ 20 ms/≤ 20 ms form A normally open relay output for the
Boards
Mechanical life 107 switching cycles safe area load. The module output
Transfer characteristics changes state when the input signal
Switching frequency ≤ 10 Hz changes state. The normal output state
Ambient conditions can be reversed with the selector
Ambient temperature -20 ... 60 °C (253 ... 333 K) switches on the side of the unit.
Mechanical specifications Line fault detection (LFD) can be selected
Protection degree IP20 or disabled via a selector switch.
Mass approx. 100 g
Digital Inputs
During an error condition, the relay
Dimensions 12.5 x 128 x 106 mm (0.5 x 5.1 x 4.2 in)
reverts to its de-energized state and the
Data for application in conjunction see page 31 for entity parameters
with hazardous areas LEDs indicate the fault. A separate fault
EC-Type Examination Certificate BASEEFA 06 ATEX 0093 X
output bus is available. The fault
Group, category, type of protection ¬ II (1)GD [Ex ia] IIC; [Ex ia D]
conditions can be monitored via a Fault
[circuit(s) in zone 0/1/2/20/21/22] Indication Board.
¬ I (M1) [Ex ia] I This module mounts on a HiC
Statement of conformity Pepperl+Fuchs Termination Board.
Group, category, type of protection, ¬ II 3G Ex nA nC IIC T4 X
Digital Outputs
temperature classification
FM control drawing 16-534FM-12 (cFMus)
Analog Inputs
Diagrams
Front view
LED green:
HiC2822 Power supply
PWR
1+ 11 STATUS/
FAULT
I 10 kΩ I Switch 1 ... 4 LED yellow/red:
4- 14 Status output/
1.5 k Ω HiC Fault channel 2
2+ 12
II 10 kΩ II 2822
2ch
5- 15 Sw/prox
Repeater
06/2009
Place for
labeling
216312
Pepperl+Fuchs Group USA: +1 330 486 0002 Germany: +49 621 776 2222 Singapore: +65 6779 9091 23
www.pepperl-fuchs.com pa-info@us.pepperl-fuchs.com pa-info@de.pepperl-fuchs.com pa-info@sg.pepperl-fuchs.com
Catalog_DCS_Honeywell_SC_eng.book Seite 24 Donnerstag, 25. Juni 2009 5:28 17
Diagrams
Front view
HiC2871
CH1
SL2 SL1
1+ 11+
5a 8a
4- 14- V
HiC 5b 7a
2871
17+
1ch
Solenoid/
9b
Alarm
Driver 18-
7b
06/2009
Place for
labeling
216312
Zone 0, 1, 2 Zone 2
Div. 1, 2 Div. 2
Edition
24 Pepperl+Fuchs Group USA: +1 330 486 0002 Germany: +49 621 776 2222 Singapore: +65 6779 9091
www.pepperl-fuchs.com pa-info@us.pepperl-fuchs.com pa-info@de.pepperl-fuchs.com pa-info@sg.pepperl-fuchs.com
Catalog_DCS_Honeywell_SC_eng.book Seite 25 Donnerstag, 25. Juni 2009 5:28 17
H-System
Operating mode output on with contact close or transistor on or logic • Line fault detection (LFD)
level > 4 V
output off with contact open or transistor off or logic
Function
level < 1.5 V
Output This isolated barrier is used for intrinsic
Output characteristics 40 mA at 12 V DC, 52 mA current limit safety applications. It supplies power to
Load 0.1 ... 5 kΩ solenoids, LEDs, and audible alarms
Switching frequency f max. 250 Hz located in a hazardous area.
Response time turn-on time 1 ms, turn-off time 2 ms, at 300 Ω load It is controlled with a switch contact,
Fault level lead short-circuit detection at < 25 Ω transistor, or logic-level signal.
lead breakage detection at > 100 kΩ typical
Termination
Fault current 4 mA typical
At full load, 12 V at 40 mA (with 52 mA
Boards
Error output
current limit) is available for the
Output type open collector transistor (common to both channels)
hazardous area application.
Ambient conditions Line fault detection of the field circuit is
Ambient temperature -20 ... 60 °C (253 ... 333 K) indicated by a red LED and an output on
Mechanical specifications the fault bus. The fault conditions are
Protection degree IP20 monitored via a Fault Indication Board.
Mass approx. 140 g This module mounts on a HiD
Digital Inputs
Dimensions 18 x 106 x 128 mm (0.7 x 4.2 x 5 in) Termination Board.
Data for application in conjunction see page 31 for entity parameters
with hazardous areas
EC-Type Examination Certificate CESI 02 ATEX 086
Group, category, type of protection ¬ II (1)G [EEx ia] IIC [circuit(s) in zone 0/1/2]
CSA control drawing 366-005CS-12B (cCSAus)
Digital Outputs
Analog Inputs
Diagrams
Front view
LED green:
PWR Power supply
HiD2874 ON
FAULT STATUS
1+ 11+
CH 1
LEDs yellow:
LEDs red: CH 2 Status output
I I Fault channel 1 ... 2 channel 1 ... 2
Analog Outputs
4- 14-
2+ 12+
2874
II II 2 Channel
Solenoid/
Alarm
5- 15- Driver
06/2009
216312
Pepperl+Fuchs Group USA: +1 330 486 0002 Germany: +49 621 776 2222 Singapore: +65 6779 9091 25
www.pepperl-fuchs.com pa-info@us.pepperl-fuchs.com pa-info@de.pepperl-fuchs.com pa-info@sg.pepperl-fuchs.com
Catalog_DCS_Honeywell_SC_eng.book Seite 26 Donnerstag, 25. Juni 2009 5:28 17
Influence of ambient temperature < 2 μA/°C (0 ... +60 °C); < 4 μA/°C (-20 ... 0 °C)
Boards
Bi-directional communication is
supported for SMART transmitters that Frequency range hazardous area to safe area:
bandwidth with 0.5 Vpp signal 0 ... 3 kHz (-3 dB)
use current modulation to transmit data
safe area to hazardous area:
and voltage modulation to receive data. bandwidth with 0.5 Vpp signal 0 ... 3 kHz (-3 dB)
The output is selected as a current Rise time 10 to 90 % ≤ 20 ms
source, current sink, or voltage source via Ambient conditions
DIP switches on the side of the unit. Ambient temperature -20 ... 60 °C (253 ... 333 K)
Digital Inputs
Diagrams
Front view
LED green:
Power supply HiC2025
PWR
SL2
Analog Outputs
SL1
HART
5-
1b
HART
1+
5a 14- V
HiC 4- 7a
5b
2025
1ch
Analog
Input
06/2009
Place for
labeling
216312
Zone 0, 1, 2 24 V DC Zone 2
Div. 1, 2 Div. 2
Edition
26 Pepperl+Fuchs Group USA: +1 330 486 0002 Germany: +49 621 776 2222 Singapore: +65 6779 9091
www.pepperl-fuchs.com pa-info@us.pepperl-fuchs.com pa-info@de.pepperl-fuchs.com pa-info@sg.pepperl-fuchs.com
Catalog_DCS_Honeywell_SC_eng.book Seite 27 Donnerstag, 25. Juni 2009 5:28 17
H-System
Input resistance 40 Ω, for current source • Usable as signal splitter
Ripple 10 mVrms • Line fault detection (LFD)
Voltage min. 15.5 V at 20 mA
• Up to SIL2 acc. to IEC 61508
Communication pass-through of HART signal to safe area
The current sink terminals 4, 7 and 5, 6 do not pass the
HART signal to safe area. Function
Output This isolated barrier is used for intrinsic
Output sink mode from external supply safety applications. It provides a fully
Output signal 4 ... 20 mA, current limit 24 mA floating supply to power 2-wire SMART
Voltage working voltage 7 ... 30 V transmitters in the hazardous area, and
Response time 70 ms, 10 ... 90 % step change
Termination
repeats the current to drive a safe area
Signal level no fault: 1 mA ... 23.5 mA input current
Boards
load. It is also used with 2-wire SMART
fault detection: < 0.2 mA or > 24 mA input current current sources. It is designed to provide
Error output a sink mode output on the safe area
Output type open collector transistor (common to both channels) terminals
fault bus signal, collective error message
Transfer characteristics Digital signals may be superimposed on
Calibrated accuracy < ± 0.1 % of full-scale value the analog values in the hazardous or
Influence of temperature < ± 0.01 %/ K safe area, which are transferred bi-
directionally.
Digital Inputs
Frequency range communication channel: 0.5 ... 40 kHz within 3 db, (-6
db at 100 kHz), Tx to output and output to Tx, A separate fault output on the bus is
suitable for use with SMART transmitters using HART signaled if the input signal is outside the
or similar protocol
range 0.2 mA ... 24 mA. The fault
Linearity < ± 0.05 % of full-scale value
conditions can be monitored via a Fault
Ambient conditions
Indication Board.
Ambient temperature -20 ... 60 °C (253 ... 333 K)
Mechanical specifications
This module mounts on a HiD
Protection degree IP20 Termination Board.
Digital Outputs
Mass approx. 140 g
Dimensions 18 x 106 x 128 mm (0.7 x 4.2 x 5 in)
Data for application in conjunction see page 31 for entity parameters
with hazardous areas
EC-Type Examination Certificate CESI 02 ATEX 086
Group, category, type of protection ¬ II (1)G [EEx ia] IIC [circuit(s) in zone 0/1/2]
CSA control drawing 366-005CS-12B (cCSAus)
Analog Inputs
Diagrams
Front view
LED green:
PWR Power supply
HiD2030SK ON
FAULT
V CH 2 CH 1
HART
HART
1+ 11+
I + I LED red: LED red:
4 14- Fault channel 2 Fault channel 1
Analog Outputs
mA
- 7-
V
HART
HART
2+ 12+
II + II 2030 SK
5 15- 2 Channel
Fully
mA
- 6- Floating
Analog
Input
Repeater
06/2009
216312
Zone 0, 1, 2 ERR 24 V DC
Div. 1, 2
Edition
Pepperl+Fuchs Group USA: +1 330 486 0002 Germany: +49 621 776 2222 Singapore: +65 6779 9091 27
www.pepperl-fuchs.com pa-info@us.pepperl-fuchs.com pa-info@de.pepperl-fuchs.com pa-info@sg.pepperl-fuchs.com
Catalog_DCS_Honeywell_SC_eng.book Seite 28 Donnerstag, 25. Juni 2009 5:28 17
potentiometers, or resistance
Potentiometer 0.1 ... 20 kΩ
temperature detectors (RTD) from a
Types of measuring 3-wire connection
hazardous area and converts them to an
Input resistance ≥ 1 MΩ (-100 ... 100 mV)
isolated, linearized analog output in the
Output
safe area.
Output I, II analogue, current or voltage output
The outputs can be selected as a current Current range 0/4 ... 20 mA
source, current sink, or voltage source Fault signal downscale 0 or 2 mA, upscale 21.5 mA
with DIP switches on the side panel.
Digital Inputs
Diagrams
Front view
LED green:
PWR Power supply
ON HiD2082
CH 2 CH 1
1 11+
LED red:
FAULT FAULT
+ + V I
LED red: T 2+ 14-
Fault channel 2 Fault channel 1 I V
Analog Outputs
- - 5-
4
2082 7 12+
+ + V II
2 Channel
Temperature
3+ 15-
Converter
II V
6-
- -
8
06/2009
Zone 0, 1, 2 ERR 24 V DC
Div. 1, 2
Edition
28 Pepperl+Fuchs Group USA: +1 330 486 0002 Germany: +49 621 776 2222 Singapore: +65 6779 9091
www.pepperl-fuchs.com pa-info@us.pepperl-fuchs.com pa-info@de.pepperl-fuchs.com pa-info@sg.pepperl-fuchs.com
Catalog_DCS_Honeywell_SC_eng.book Seite 29 Donnerstag, 25. Juni 2009 5:28 17
H-System
Input signal 4 ... 20 mA limited to approx. 30 mA
Voltage drop Ud approx. 6 V or internal resistance 300 Ω at 20 mA
Input resistance > 100 kΩ at max. 23 V, with field wiring open Function
Output
This isolated barrier is used for intrinsic
Current 4 ... 20 mA
safety applications. It repeats a
Load 0 ... 650 Ω
4 mA ... 20 mA input signal from a control
Ripple 20 mVrms
system to drive HART I/P converters,
Transfer characteristics
valve actuators, and displays located in a
Deviation at 20 °C (293 K), 4 ... 20 mA
hazardous area.
≤ ± 0.1 % incl. non-linearity and hysteresis
Influence of ambient temperature < 2 μA/°C (0 ... +60 °C); < 4 μA/°C (-20 ... 0 °C) Digital signals may be superimposed on
the analog values in the hazardous or
Termination
Frequency range hazardous area to safe area:
safe area, which are transferred bi-
Boards
bandwidth with 0.5 Vpp signal 0 ... 3 kHz (-3 dB)
safe area to hazardous area: directionally.
bandwidth with 0.5 Vpp signal 0 ... 3 kHz (-3 dB)
An open field circuit presents a high
Rise time 10 to 90 % ≤ 100 ms
impedance to the control side to allow
Ambient conditions
alarm conditions to be monitored by
Ambient temperature -20 ... 60 °C (253 ... 333 K)
control systems.
Mechanical specifications
Protection degree IP20 This module mounts on a HiC
Termination Board.
Digital Inputs
Mass approx. 100 g
Dimensions 12.5 x 128 x 106 mm (0.5 x 5.1 x 4.2 in)
Data for application in conjunction see page 31 for entity parameters
with hazardous areas
EC-Type Examination Certificate CESI 06 ATEX 017
Group, category, type of protection ¬ II (1)GD [EEx ia] IIC, [Ex ia D]
[circuit(s) in zone 0/1/2/20/21/22]
Statement of conformity Pepperl+Fuchs
Group, category, type of protection, ¬ II 3G Ex nA II T4 X
Digital Outputs
temperature classification
FM control drawing 16-534FM-12 (cFMus)
Analog Inputs
Diagrams
Front view
LED green:
HiC2031 Power supply
PWR
Analog Outputs
SL2 SL1
HART
HART
1+ 11+
I
5a 8a mA
P
4- 14-
5b 7a HiC
2031
1ch
Analog
Output
06/2009
Place for
labeling
216312
Zone 0, 1, 2 24 V DC Zone 2
Div. 1, 2 Div. 2
Edition
Pepperl+Fuchs Group USA: +1 330 486 0002 Germany: +49 621 776 2222 Singapore: +65 6779 9091 29
www.pepperl-fuchs.com pa-info@us.pepperl-fuchs.com pa-info@de.pepperl-fuchs.com pa-info@sg.pepperl-fuchs.com
Catalog_DCS_Honeywell_SC_eng.book Seite 30 Donnerstag, 25. Juni 2009 5:28 17
Signal level input voltage drop < 4 V with field wiring intact
Function input current < 1.2 mA with field wiring open
This isolated barrier is used for intrinsic Output
safety applications. It repeats a Rated current 4 ... 20 mA on a load of max. 750 Ω
Load 0 ... 750 Ω
4 mA ... 20 mA input signal from a control
system to drive I/P converters, valve Output signal 4 ... 20 mA
actuators, and displays located in a Ripple 15 mVrms
Response time 50 ms, 10 ... 90 % step change
hazardous area.
Transfer characteristics
An open field circuit presents a high Calibrated accuracy < ± 0.1 % of full-scale value
impedance to the control side to allow Influence of temperature < ± 0.01 %/K
alarm conditions to be monitored by
Termination
Diagrams
Front view
LED green:
PWR Power supply
ON HiD2032
1+ 11+
I
I mA I
P
4- 14-
Analog Outputs
2+ 12+
2032
I
II mA II
P
2 Channel
Fully 5- 15-
Floating
Analog
Output
Driver
06/2009
216312
Zone 0, 1, 2 24 V DC
Div. 1, 2
Edition
30 Pepperl+Fuchs Group USA: +1 330 486 0002 Germany: +49 621 776 2222 Singapore: +65 6779 9091
www.pepperl-fuchs.com pa-info@us.pepperl-fuchs.com pa-info@de.pepperl-fuchs.com pa-info@sg.pepperl-fuchs.com
Catalog_DCS_Honeywell_SC_eng.book Seite 31 Donnerstag, 25. Juni 2009 5:28 17
H-System
HiC2821 5a, 5b 10.5 17.1 45
HiC2822 5a, 5b; 1a, 1b 10.5 17.1 45
HiC2871 5a, 5b 25.2 110 693
HiD2030SK 1, 4; 2, 5 26 93 605
4, 7; 5, 6 1.2 50 15
HiD2032 1, 4; 2, 5 26 93 605
HiD2082 1, 4; 2, 5; 3, 6; 7, 8 10 15 38
HiD2874 1, 4; 2, 5 26 110 715
Termination
CSA Entity Parameters
Boards
Model Number Terminals Voc (V) Isc (mA)
HiD2030SK 1, 4; 2, 5 26 93
4, 7; 5, 6 1.2 50
1, 4, 7; 2, 5, 6 27.2 143
HiD2032 1, 4; 2, 5 26 93
Digital Inputs
HiD2082 1, 4; 2, 5; 3, 6; 7, 8 10 15
HiD2874 1, 4; 2, 5 26 110
FM Entity Parameters
Digital Outputs
HiC2025 5a, 5b 25.2 100 – –
1a, 1b 7.2 100 – –
HiC2031 5a, 5b 25.2 100 – –
HiC2821 5a, 5b 10.5 17.1 – –
HiC2822 5a, 5b; 1a, 1b 10.5 17.1 – –
HiC2871 5a, 5b 25.2 110 – –
Analog Inputs
Analog Outputs
06/2009
216312
Edition
isolation for freedom of loop connection. Differential mode clamping ± 5.2 V, for transient or AC signals
Each HART Multiplexer Master is Common mode clamping ± 10 V, for transient or AC signals
networked simply by connecting the high- Device type DC isolated bus device
speed RS 485 output in a multidrop Impedance high impedance
configuration. Data link type HART primary and secondary
Field multi point support option available upon request
The device interrogates each field device,
under the supervision of the workstation, Interface
retrieving information for storage in its Transfer rate 9600 MBit/s, 19200 MBit/s or 38400 Mbit/s,
selectable via switch
internal database, which is then easily
Address 1 ... 31, adjustable via DIP switch
accessed.
Type RS 485, differential pair and grounding
This module is intended to mount on an Toplogy multi point, master/slave connection
HiD Termination Board or HART Ambient conditions
Communcation Board. Also special Ambient temperature 0 ... 60 °C (273 ... 333 K)
boards for DCS integration are available. Mechanical specifications
For additional information, refer to the Protection degree IP20
manual and www.pepperl-fuchs.com. Mass approx. 140 g
Dimensions 18 x 106 x 128 mm (0.7 x 4.2 x 5 in)
Data for application in conjunction
with hazardous areas
Declaration of conformity Pepperl+Fuchs
Group, category, type of protection, ¬ II 3G EEx nA II T4
temperature classification
CSA approval 1256050
Approved for Class I, Division 2, Groups A, B, C, D;
Class I, Zone 2, IIC
Diagrams
Front view
LED green:
Power supply
HiD Mux2700
PWR
ON
2
Mux/ RS 485
HART I/F
RS 485
...
MUX
2700 32
32 Channel
Hart
Multiplexer
ON OFF
06/2009
+
-
24 V DC
Switch 1 ... 8
216312
Zone 2
Div. 2
Edition
32 Pepperl+Fuchs Group USA: +1 330 486 0002 Germany: +49 621 776 2222 Singapore: +65 6779 9091
www.pepperl-fuchs.com pa-info@us.pepperl-fuchs.com pa-info@de.pepperl-fuchs.com pa-info@sg.pepperl-fuchs.com
Catalog_DCS_Honeywell_SC_eng.book Seite 33 Donnerstag, 25. Juni 2009 5:28 17
H-System
Power loss ≤ 500 mW, without module Boards
Reverse polarity protection yes
• LED indicator for supply status
Redundancy
Supply Redundancy available. Each supply is decoupled and
fused (500 mA).
Function
Indicators/settings This HART Communication Board can
Display elements - green LED H1 - power supply I interface with two, 16-channel H-System
- green LED H2 - power supply II Termination Boards.
Ambient conditions
It contains one slot to mount the 32-
Ambient temperature -20 ... 60 °C (253 ... 333 K)
channel HART Multiplexer Master type
Storage temperature -40 ... 70 °C (233 ... 343 K)
Accessories
HiD Mux2700.
Mechanical specifications
Protection degree IP20 HART interface cables provide easy
Connection screw terminal for max. 2.5 mm2, fixed
connection between the HiD/HiC
Material housing: polycarbonate, 30 % fibre-glass reinforced
Termination Boards and the HART
Mass approx. 150 g Communication Board.
Dimensions 50 x 200 x 163 mm (1.97 x 7.9 x 6.42 in), It offers fused redundant power supply
height including module assembly connections with LED indication. RS 485
Mounting DIN rail mounting terminals are redundant and can be daisy
Accessories chained.
Designation optional accessories:
- HART Multiplexer Master HiD Mux2700
- HART connection cable HiACA-...
Diagrams
24 V DC (I),
HART 1 ... 8, 9 ... 16 HART 17 ... 24, 25 ... 32 24 V DC (II)
+ - + -
FAULT HART TX
32 Channel
Multiplexer
2700
MUX
Hart
PWR
ON
OFF
06/2009
216312
Zone 2
Edition
Div. 2
HiD Mux2700.
Mechanical specifications
The HART interface cable provides easy Protection degree IP20
connection between the HiD/HiC Connection screw terminal for max. 2.5 mm2, fixed
Termination Boards and the HART Material housing: polycarbonate, 30 % fibre-glass reinforced
Communication Board. Mass approx. 150 g
It offers fused redundant power supply Dimensions 50 x 200 x 163 mm (1.97 x 7.9 x 6.42 in),
connections with LED indication. RS 485 height including module assembly
terminals are redundant and can be daisy Mounting DIN rail mounting
chained. Accessories
Designation optional accessories:
- HART Multiplexer Master HiD Mux2700
- HART connection cable HiACA-...
Diagrams
Supply II Supply I
RS 485
GND
NET A
NET B
ON
FAULT HART TX
32 Channel
Multiplexer
2700
MUX
Hart
PWR
ON
OFF
06/2009
216312
Zone 2
Edition
Div. 2
Length
114see
mmtechnical
(4.48'') data
Label Carrier Sets
Features
HiALC-HiCTF-SET-114
43,5 mm (1.71'')
H-System
Board
• 2 pieces for 16-position Termination
45 mm (1.77") 9 mm
Board
(0.35") HiALC-HiCTF-SET-228
• For HiC Termination Boards
Technical data
• 1 piece for 16-position Termination
Ambient conditions
Board
Ambient temperature -20 ... 60 °C (253 ... 333 K)
Storage temperature -40 ... 70 °C (233 ... 343 K)
HiALC-HiDTF-SET-156
Mechanical specifications • For HiD Termination Boards
Accessories
Mass HiALC-HiCTF-SET-114: approx. 50 g • 1 piece for 8-position Termination
HiALC-HiCTF-SET-228: approx. 100 g Board
HiALC-HiDTF-SET-156: approx. 70 g
HiALC-HiDTF-SET-312: approx. 140 g
• 2 pieces for 16-position Termination
Dimensions HiALC-HiCTF-SET-114:
Board
43.5 x 45 x 114 mm (1.71 x 1.77 x 4.48 in) HiALC-HiDTF-SET-312
HiALC-HiCTF-SET-228: • For HiD Termination Boards
43.5 x 45 x 228 mm (1.71 x 1.77 x 9 in)
HiALC-HiDTF-SET-156: • 1 piece for 16-position Termination
43.5 x 45 x 156 mm (1.71 x 1.77 x 6.14 in) Board
HiALC-HiDTF-SET-312:
43.5 x 45 x 156 mm (1.71 x 1.77 x12.3 in) Function
Note recommended size of labeling strip:
The Label Carrier Set is assembled on
HiALC-HiCTF-SET-114: 108 x 28 mm (4.25 x 1.1 in)
HiALC-HiCTF-SET-228: 222 x 28 mm (8.7 x 1.1 in)
each Termination Board.
HiALC-HiDTF-SET-156: 150 x 28 mm (5.9 x 1.1 in)
HiALC-HiDTF-SET-312: 306 x 28 mm (12 x 1.1 in)
Termination Boards
• Connects terminal plug on Label 31 32
Honeywell Series C GI/IO TA to a 32-pole grommet 32-pole connector
single 37-pin Sub-D connector on H-
system Termination Boards
Female Sub-D
• Preconfigured lengths socket 37-pin
Technical data
Electrical specifications
Accessories
H-System
Termination
Boards
Digital Inputs
Digital Outputs
Analog Inputs
Analog Outputs
06/2009
216312
Edition
06/2009
216312
Edition
H-System
Termination
Boards
Digital Inputs
Digital Outputs
Analog Inputs
Analog Outputs
06/2009
216312
Edition
C S
CA-HWC300-AIO-DIO-*M . . . . . . . . . . . . . . . . . . . . 36 SC-GPCD-DI32-PF . . . . . . . . . . . . . . . . . . . . . . . . 19
SC-GPDD-AIO16-PF . . . . . . . . . . . . . . . . . . . . . . . 21
H SC-GPDD-DO32-PF . . . . . . . . . . . . . . . . . . . . . . . 20
SC-GPCS-UNI16-PF . . . . . . . . . . . . . . . . . . . . . . . 18
H-System
HiALC-HiCTF-SET-114 . . . . . . . . . . . . . . . . . . . . . . 35
HiALC-HiCTF-SET-228 . . . . . . . . . . . . . . . . . . . . . . 35
HiALC-HiDTF-SET-156 . . . . . . . . . . . . . . . . . . . . . . 35
HiALC-HiDTF-SET-312 . . . . . . . . . . . . . . . . . . . . . . 35
HiATB01-HART-2X16 . . . . . . . . . . . . . . . . . . . . . . . 33
HiATB01-HART-4X8 . . . . . . . . . . . . . . . . . . . . . . . . 34
HiC2025 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
HiC2031 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Termination
Boards
HiC2821 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
HiC2822 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
HiC2871 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
HiD2000 Empty . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
HiD2030SK . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Digital Inputs
HiD2032 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
HiD2082 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
HiD2874 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
HiD Mux2700 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
Digital Outputs
Analog Inputs
Analog Outputs
06/2009
216312
Edition
For over a half century, Pepperl+Fuchs has been continually providing new concepts for the world of process automation. Our
company sets standards in quality and innovative technology. We develop, produce and distribute electronic interface modu-
les, Human-Machine Interfaces and hazardous location protection equipment on a global scale, meeting the most demanding
needs of industry. Resulting from our world-wide presence and our high flexibility in production and customer service, we
are able to individually offer complete solutions – wherever and whenever you need us. We are the recognized experts in our
technologies – Pepperl+Fuchs has earned a strong reputation by supplying the world’s largest process industry companies
with the broadest line of proven components for a diverse range of applications.
6
5 1
3
7
2
1 Worldwide/German Headquarters
Pepperl+Fuchs GmbH
Mannheim · Germany
Tel. +49 621 776 2222 8
E-Mail: pa-info@de.pepperl-fuchs.com
www.pepperl-fuchs.com
Subject to reasonable modifications due to technical advances • Copyright PEPPERL+FUCHS • Printed in Germany • Part. No. 216312 06/09 00