Professional Documents
Culture Documents
Basics of Neural Network
Basics of Neural Network
Basics of Neural Network
3. Contact Hours: L: 3 T: 0 P: 2
9. Pre-requisite: EEN-206
1
Syllabus of Protection and Switchgear (EEN-304)
S. No. Contents Contact Hours
Various types of electromechanical relays, construction and principle of operation and characteristic,
1. applications and limitations; Over and under current, directional, differential, distance and other types of relay; 8
Concept of static relays; Protection system and properties; Introduction to numerical relays.
Protection of transmission lines using overcurrent, differential, directional-overcurrent and distance relays,
2. 6
back-up protection, carrier relaying; Busbar protection.
Protection of transformers against internal faults such as short circuit and turn-to-turn fault using differential
3. 6
and overcurrent relays, protection for other abnormal conditions.
Protection of generators against short circuit and turn-to-turn fault, stator ground fault, field ground fault, loss
4. 6
of excitation, loss of synchronism using different types of relays.
Switchgear, arc and interruption theory, application in different conditions, ratings and selection, principle of
5. 12
operation of air break, oil filled, air blast, vacuum and SF6 circuit breakers, elementary idea of testing methods.
Total 42
2
Suggested Books
Year of Publication/
S. No. Name of Authors /Books / Publishers
Reprint
Van A. R. and Warrington C., “Protective Relays - Theory and Practice”, Vol. I and II, 3rd Ed.,
1. 1982
Chapman and Hall.
2. Mason C. R., “The Art and Science of Protective Relaying”, Wiley Eastern Limited. 1987
Ray S., “Electrical Power Systems: Concepts, Theory and Practice”, Prentice Hall of India Private
3. 2008
Limited.
Ravindranath B. and Chander M., “Power System Protection and Switchgear”, New Age
4. 2008
International Private Limited.
Paithankar Y. G. and Bhide S. R., “Fundamentals of Power System Protection”, Prentice Hall of India
5. 2007
Private Limited.
R eferences
4/3/2021 4
Introduction of Relaying Scheme
5
Occurrence of a Fault can cause
8
Symmetrical Fault
• It involves all the three phases.
• Example: LLL/LLLG
9
Asymmetrical Fault
• It involves one or two phases with or without ground.
• Example: LG/LL/LLG
• LG: R-G, Y-G, B-G
• LL: R-Y, Y-B, B-R
• LLG: R-Y-G, Y-B-G, B-R-G
10
Causes of Symmetrical Fault
Symmetrical Fault:
• It occurs when line is energized and earthing switch is
inadvertently kept ON.
Remote end
Local end
Circuit Breaker
Earthing switch
11
Impact of Symmetrical Fault
12
Asymmetrical Fault
• LL fault occurs due to bridging of two phases/conductors
either in machines or in transformers because of failure
of insulation between phases (conductors of different
phases are in the same slot of a stator).
• In O/H TL, two phase wires may get shorted together by
(i) Birds
(ii) Kite strings
(iii) Tree limbs
13
Asymmetrical Fault
In monsoon, the two conductors may swing due
to winds and storms. The dielectric strength of air
reduces in monsoon.
When the distance between these conductors is
reduced due to swinging, a power arc may occur
between them causing a LL fault.
14
Spacing between Conductors (phases)
Horizontal spacing
SYSTEM Vertical spacing b/n
TYPE OF TOWER b/n
VOLTAGE conductors(mm)
conductors(mm)
A(0-2˚) 1080 4040
SINGLE
B(2-30˚) 1080 4270
CIRCUIT
C(30-60˚) 1220 4880
66 KV
A(0-2˚) 2170 4270
DOUBLE
B(2-30˚) 2060 4880
CIRCUIT
C(30-60˚) 2440 6000
A(0-2˚) 4200 7140
SINGLE B(2-30˚) 4200 6290
CIRCUIT
C(30-60˚) 4200 7150
D(30-60˚) 4200 8820
132KV
A(0-2˚) 3965 7020
DOUBLE B(2-30˚) 3965 7320
CIRCUIT
C(15-30˚) 3965 7320
D(30-60˚) 4270 8540
15
Spacing between Conductors (phases)
Horizontal
SYSTEM Vertical spacing b/n
TYPE OF TOWER spacing b/n
VOLTAGE conductors(mm)
conductors(mm)
A(0-2˚) 5200 8500
SINGLE B(2-30˚) 5250 10500
CIRCUIT
C(15-30˚) 6700 12600
D(30-60˚) 7800 14000
220 KV
A(0-2˚) 5200 9900
16
Spacing between Conductors (phases)
• Mecomb’s formula
𝐷𝐷
Spacing(cm) = 0.03048 ∗ 𝑉𝑉 + 4.010 𝑆𝑆
𝑊𝑊
V= Voltage of system in KV
D= Diameter of conductor in cm
S= Sag in cm
W= Weight of conductor in Kg/m
VDE formula
𝑉𝑉 2
Spacing(cm) =7.5 𝑆𝑆 +
2000
V= Voltage of system in KV
S= Sag in cm
17
Spacing between Conductors (phases)
Still’s formula
𝑙𝑙 2
𝑆𝑆𝑆𝑆𝑆𝑆𝑆𝑆𝑆𝑆𝑆𝑆𝑆𝑆 𝑐𝑐𝑐𝑐 = 5.08 + 1.814 ∗ 𝑉𝑉 +
27.8
Where-
l= average span length(m)
NESC formula
𝑙𝑙
𝑆𝑆𝑆𝑆𝑆𝑆𝑆𝑆𝑆𝑆𝑆𝑆𝑆𝑆 (𝑐𝑐𝑐𝑐) = 0.762 ∗ 𝑉𝑉 + 3.681 𝑆𝑆+
2
Where-
V= Voltage of system in KV
S= Sag in cm
L= Length of insulator string in cm
18
Spacing between Conductors (phases)
Swedish formula
𝑆𝑆𝑆𝑆𝑆𝑆𝑆𝑆𝑆𝑆𝑆𝑆𝑆𝑆 𝑐𝑐𝑐𝑐 = 6.5 𝑆𝑆 + 0.7 ∗ 𝐸𝐸
where-
E= line voltage in KV
S= sag in cm
French formula
𝐸𝐸
𝑆𝑆𝑆𝑆𝑆𝑆𝑆𝑆𝑆𝑆𝑆𝑆𝑆𝑆 𝑐𝑐𝑐𝑐 = 8.0 𝑆𝑆 + 𝐿𝐿 +
𝐿𝐿
Where-
E= line voltage in KV
S= Sag in cm
L= Length of insulator string (cm)
19
Spacing between Conductors (phases)
Sleet Jump:-
The jump of the conductor, resulting from ice dropping off one
span of an ice-covered line, has been the cause of many serious
outages on long-span lines where conductors are arranged in the
same vertical plane.
20
Ground Clearances of Conductors
Ground Clearances
𝑉𝑉−33
𝐶𝐶𝐶𝐶 = 5.182 + 0.305 ∗ 𝐾𝐾, Where- 𝐾𝐾 =
33
21
Ground Clearances of Conductors
Voltage Level Ground
Sr.No
(kV) Clearance (m)
1 ≤33 5.20
2 66 5.49
3 132 6.10
4 220 7.01
5 400 8.84
6 765 14.0
22
Ground Clearances for conductors
crossing over railway tracks
Under maximum sag condition, minimum clearance over rail level
(25 kV system). Broad Gauge
System Outside
Inside station
Voltage Level station
limits(m)
limits(m)
≤66 KV 10.3 7.9
132 KV 10.9 8.5
220 KV 11.2 8.8
400 KV 13.6 11.2
23
Ground Clearances when power line
crossing another power line
24
Asymmetrical Fault (LG)
Most common fault on O/H conductors.
80%-90% faults are SLG.
It occurs due to
(i) flashover across the line insulators
(ii) Failure of insulators due to lightning or switching
overvoltages
(iii) Defective insulators
25
Practical situation for occurrence of a SLG fault
Cross-arm
String of
Tower
insulators
132 kV conductor
26
Number of Insulators required
Sr. No. Voltage level (kV) Number of suspension Actual Number of
insulators insulators
1 66 66
�√3 7
𝑁𝑁 = =6.35
11
2 132 132
�√3 9 to 11
𝑁𝑁 = =6.92
11
3 220 220
�√3 12 or 16
𝑁𝑁 = =11.54
11
4 400 400
�√3 23 or 24
𝑁𝑁 = =20.99
11
5 765 765
�√3 42 or 43
𝑁𝑁 = =40.15
11
27
Asymmetrical Fault (Open Conductor)
Abnormal stoppage of current can occur due to
(i) open conductors
28
Consequences of Faults
1. Thermal damage:
Fault current is very high (2 to 20 times CMR). This
current will heat the conductor (insulation). If the
equilibrium temperature exceeds the temperature
withstand value of the insulation, the thermal
breakdown of insulation will occur.
It occurs slowly as it is related to temperature. Time
delays isolation is required.
29
Consequences of Faults
2. Electrodynamic damage:
The repelling forces generated due to this large current
(8-20 times CMR) would deshape and destruct the
whole equipment structurally.
30
Probability of occurrence of faults on different element
% of occurrence of
Equipment
fault
Overhead Transmission Line 50%
Underground Cable 10%
Switchgears including CTs and
15%
PTs
Power Transformers 15%
Miscellaneous 10%
31
Probability of occurrence of faults on overhead lines
Type of % of occurrence of
fault fault
LG 80% - 90%
LL 6% - 10%
LLG 3% - 6%
LLL/LLLG 1% or less
32
Another classification of Faults
1. Transient:
• It occurs due to
a. power arc between two phases
b. flashover across line insulator due to
overvoltage.
• Automatically die out after few cycles.
2. Permanent:
• Remain for a longer duration and damage the
equipment.
33
Major components of a power system network
34
35
Abnormalities in Power System Network
• Overload
• Magnetizing inrush
• Power swing
• Prime mover failure
• Stalling
36
Tripping Mechanism of Relay
The relay is always connected in the secondary circuit of CT and PT.
The main function of any type of relay is to detect/sense the inception of
fault, whereas the tripping task is carried out by auxiliary relay and circuit
breaker.
Since the relay only does the function of sensing, the speed of the relay is
increased, and hence, it operates instantaneously.
Auxiliary relay
• It carries high value of trip coil current during a fault.
• It also gives signals to perform certain other functions associated
with relays such as alarms and interlocking.
37
Contacts of Relay
In control circuit, all relay coils are shown in deenergized condition and all
circuit breakers (CBs) are shown in open condition.
38
Tripping Mechanism of Relay
Coil of
auxiliary relay
86
CT Relay
contact
PT R
Contact of
auxiliary relay Tripping coil of
circuit breaker
Power circuit Control circuit
39
Tripping Mechanism of Relay
Working
• If single input relay is used (current-based relay or voltage-based
relay), then the relay receives a signal from the secondary of CT or PT
only.
• Conversely, for two input relays, it receives signals from the secondary
of both CT and PT.
• The relay R senses the fault within a fraction of second (in
millisecond) and gives signal to the auxiliary relay through its contact.
• The contact of auxiliary relay closes owing to energization of the coil
of auxiliary relay.
• This will further energize the trip coil of the circuit breaker.
40
Zones of Protection
• To provide complete protection for the entire system, that is, to avoid
having an unprotected region, neighbouring zones are arranged to
overlap each other.
• When a system is experiencing an abnormal condition, the relays first
identify this condition and then send trip signals to appropriate
circuit breakers that open to isolate the affected zone.
G G
Transformer zone
Bus zone
Generator zone
Distribution zone
i. Selectivity
ii. Speed
iii. Sensitivity
iv. Discrimination
v. Stability
vi. Reliability
vii. Economics
F1
F2
IFL=200 A
IFAULT = 2000 A
4/3/2021 BRB & RPM 47
Requirements of Protective System
Sensitivity
• Protective devices with good sensitivity can sense any faults within
the zone of protection.
• The sensitivity factor usually determines the sensitivity of protective
relays, which depends on the parameters of protected elements and
operating condition of the power system.
Stability
• A protection system should remain stable during external fault.
7) Economics
• Besides the six factors mentioned above, economics of protective
relays is another important factor which should be considered.
• A good protective relay system should combine both features of
maximum protection and minimum cost.
• Moreover, some of these properties are contradictory to one
another, and it is the duty of the protection engineer to maintain
a balance amongst them, when choosing a protection scheme for
a particular application.
54
Requirements of Protective System
7) Economics: Consider total cost of the system = 100%
Component Name % of total cost
Relays 0.54%
Relay panels 0.27%
Wiring 0.11%
Relay room 0.12%
Current transformers 3.10%
Potential transformers 1.08%
Total Cost of Protective Gears 5.22%
55
Requirements of Protective System
Unit Protection
• Unit protection scheme is a scheme that operates for a fault
within its zone.
• Here, zone of protection is decided on the basis of current
transformers (CTs), and it includes each and every fault point
inside the CTs where measurement of currents is carried out.
• This type of protection scheme is widely used in generators,
transformers, and large induction motors. Differential protection
scheme is the best example of this type of protection scheme
56
Requirements of Protective System
Non-unit Protection
• A scheme that achieves protection using grading of successive
relays is known as non-unit protection scheme.
• Overcurrent and distance relays are the best examples of non-unit
protection schemes.
57
Requirements of Protective System
Primary and Back-up Protection
• Two sets of relays, primary and backup, are usually provided for
each zone of protection.
• Main or primary protection schemes are always there as the first
line of defense.
• Equally important and essential is a second line of defense
provided by backup schemes, which will clear the fault if the
primary protection schemes fail to operate for some reason.
• In order to give ample time to the primary relays to make a
decision, backup relays are time delayed.
58
Requirements of Protective System
Primary and Back-up Protection
• The measures taken to provide backup protection vary widely,
depending on the value and importance of the power system
equipment and the consequence of its failure.
• Normally, primary relays have a small operation zone but operate
instantaneously, whereas backup relays have a large operation
zone, namely, overreached area, and operate with a particular
time delay.
There are three kinds of back-up relaying.
59
Requirements of Protective System
1. Relay back-up
• In this relaying scheme, a separate duplicate set of primary relays,
their CTs and PTs are used. Recently, it has been observed that
local backup is required at the local station to open all the breakers
around the bus, rather than at the remote terminals.
2. Breaker back-up
• This scheme is employed to handle the situation when feeder
breaker fails to operate for a fault condition. In this scheme, a
time delay relay is operated by the main relay and it is connected
to trip all the other breakers on the bus.
60
Requirements of Protective System
3. Remote back-up
• Remote backup is provided by a relay on the next station towards
the source. This remote relay will trip in a delayed time if the
breaker in the faulty section has not tripped because of some
reason. This is the most widely used form of backup protection.
61
Thank You
62