LINEAS 115 kV

LISTADO DE SEÑALES AL CENTRO DE CONTROL

FUNCION DISTANCIA Source Instance Sink Data Object Description Data Attribute Msg PC TT
Type
F21PDIS 1 ITMI Str Start general / dirGeneral /q / t 3 P2 ≤500 ms
2
3
4
5
21 ARRANQUE GENERAL
F21PDIS 1 ITMI Str Start phsA / dirPhsA / q / t 3 P2 ≤500 ms
2
3
4
5
21 ARRANQUE FASE A
F21PDIS 1 ITMI Str Start phsB / dirPhsB / q / t 3 P2 ≤500 ms
2
3
4
5
21 ARRANQUE FASE B
F21PDIS 1 ITMI Str Start phsC / dirPhsC / q / t 3 P2 ≤500 ms
2
3
4
5
21 ARRANQUE FASE C
F21PDIS 1 ITMI Str Start neut / dirNeut / q / t 3 P2 ≤500 ms
2
3
4
5
21 ARRANQUE TIERRA
F21PDIS 1 ITMI Op Operate general / q / t 3 P2 ≤500 ms
2
3
4
5
21 DISPARO GENERAL
F21PDIS 1 ITMI Op Operate phsA / q / t 3 P2 ≤500 ms
2
3
4
5
21 DISPARO FASE A
F21PDIS 1 ITMI Op Operate phsB/ q / t 3 P2 ≤500 ms
2
3
4
5
21 DISPARO FASE B
F21PDIS 1 ITMI Op Operate phsC/ q / t 3 P2 ≤500 ms
2
3
4
5
21 DISPARO FASE C
F21PDIS 1 ITMI Op Operate phsA / phsB / phsC / q / t 3 P2 ≤500 ms
2
3
4
5
21 DISPARO FASES ABC
F68RPSB 1 ITMI BlkZn Blocking of correlated PDIS zone stVal / q / t 3 P2 ≤500 ms
2
3
68 BLOQUEO OSCILACION DE POTENCIA
F21PDIS 1 ITMI Op Operate neut / q / t 3 P2 ≤500 ms
2
3
4
5
21 DISPARO TIERRA
F21PDIS 1 ITMI TxPrm Permissive transmit general / phsA / phsB / phsC / neut / q / t 3 P2 ≤500 ms
2
21 ENVIO TELEPROTECCION
F21PDIS 1 ITMI RxPrm1 Permissive receive general / phsA / phsB / phsC / neut / q / t 3 P2 ≤500 ms
2
21 RECIBO TELEPROTECCION
F21PDIS 2 ITMI Tr Trip general / phsA / phsB / phsC / neut / q / t 3 P2 ≤500 ms
RxPrm1 Permissive receive general / phsA / phsB / phsC / neut / q / t
21 DISPARO Z2 ACELERADA 1
21 ARRANQUE Z1 F21PDIS 1 ITMI Str Start general / dirGeneral / phsA / dirPhsA / phsB / dirPhsB / phsC / dirPhsC / neut / dirNeut / q / t 3 P2 ≤500 ms

21 ARRANQUE Z2 F21PDIS 2 ITMI Str Start general / dirGeneral / phsA / dirPhsA / phsB / dirPhsB / phsC / dirPhsC / neut / dirNeut / q / t 3 P2 ≤500 ms

21 ARRANQUE Z3 F21PDIS 3 ITMI Str Start general / dirGeneral / phsA / dirPhsA / phsB / dirPhsB / phsC / dirPhsC / neut / dirNeut / q / t 3 P2 ≤500 ms

21 ARRANQUE Z4 F21PDIS 4 ITMI Str Start general / dirGeneral / phsA / dirPhsA / phsB / dirPhsB / phsC / dirPhsC / neut / dirNeut / q / t 3 P2 ≤500 ms

21 ARRANQUE Z5 F21PDIS 5 ITMI Str Start general / dirGeneral / phsA / dirPhsA / phsB / dirPhsB / phsC / dirPhsC / neut / dirNeut / q / t 3 P2 ≤500 ms

21 DISPARO Z1 F21PDIS 1 ITMI Op Operate general / phsA / phsB / phsC / neut / q / t 3 P2 ≤500 ms

21 DISPARO Z2 F21PDIS 2 ITMI Op Operate general / phsA / phsB / phsC / neut / q / t 3 P2 ≤500 ms

21 DISPARO Z3 F21PDIS 3 ITMI Op Operate general / phsA / phsB / phsC / neut / q / t 3 P2 ≤500 ms

21 DISPARO Z4 F21PDIS 4 ITMI Op Operate general / phsA / phsB / phsC / neut / q / t 3 P2 ≤500 ms

21 DISPARO Z5 F21PDIS 5 ITMI Op Operate general / phsA / phsB / phsC / neut / q / t 3 P2 ≤500 ms
Common LN 1 ITMI Mod Mode stVal / q / t 3 P2 ≤500 ms
2 Beh Behaviour stVal / q / t
3
4
5
21 ESTADO OFF
Common LN 1 ITMI Mod Mode stVal / q / t 3 P2 ≤500 ms
2 Beh Behaviour stVal / q / t
3
4
5
21 DISTANCIA BLOQUEADA
LPHD 1 ITMI PhyHealth Physical device health stVal / q / t 3 P2 ≤500 ms
Common LN 1 Health Health stVal / q / t
2
3
4
5

21 FALLA INTERNA RELE


FUNCION DE ALTO VOLTAJE
F59PTOV 1 ITMI Str Start general / dirGeneral / phsA / dirPhsA / phsB / dirPhsB / phsC / dirPhsC / neut / dirNeut / q / t 3 P2 ≤500 ms
2
59 ARRANQUE
F59PTOV 1 ITMI Op Operate general / phsA / phsB / phsC / neut / q / t 3 P2 ≤500 ms
2
59 DISPARO
F59PTOV 1 ITMI Mod Mode stVal / q / t 3 P2 ≤500 ms
2 Beh Behaviour stVal / q / t
59 OFF
Common LN 1 ITMI Mod Mode stVal / q / t 3 P2 ≤500 ms
2 Beh Behaviour stVal / q / t
59 BLOQUEADA
LPHD 1 ITMI PhyHealth Physical device health stVal / q / t 3 P2 ≤500 ms
Common LN 1 Health Health stVal / q / t
2
59 FALLA INTERNA RELE
FUNCION DE BAJO VOLTAJE
F27PTUV 1 ITMI Str Start general / dirGeneral / phsA / dirPhsA / phsB / dirPhsB / phsC / dirPhsC / neut / dirNeut / q / t 3 P2 ≤500 ms
2
27 ARRANQUE
F27PTUV 1 ITMI Op Operate general / phsA / phsB / phsC / neut / q / t 3 P2 ≤500 ms
2
27 DISPARO
Common LN 1 Mod Mode stVal / q / t 3 P2 ≤500 ms
2 Beh Behaviour stVal / q / t
27 OFF ITMI
Common LN 1 Mod Mode stVal / q / t 3 P2 ≤500 ms
2 Beh Behaviour stVal / q / t
27 BLOQUEADA ITMI
LPHD 1 ITMI PhyHealth Physical device health stVal / q / t 3 P2 ≤500 ms
Common LN 1 Health Health stVal / q / t
2
27 FALLA INTERNA RELE
FUNCION CIERRE EN FALLA
50 SOTF ARRANQUE F50HSRSOF 1 ITMI Str Start general / dirGeneral / phsA / dirPhsA / phsB / dirPhsB / phsC / dirPhsC / neut / dirNeut / q / t 3 P2 ≤500 ms

50 SOTF DISPARO F50HSRSOF 1 ITMI Op Operate general / phsA / phsB / phsC / neut / q / t 3 P2 ≤500 ms
LPHD 1 ITMI PhyHealth Physical device health stVal / q / t 3 P2 ≤500 ms
Common LN 1 Health Health stVal / q / t
50 SOTF FALLA INTERNA RELE
FUNCION SOBRECORRIENTE DE EMERGENCIA
F50PTOC 1 ITMI Str Start general / dirGeneral / phsA / dirPhsA / phsB / dirPhsB / phsC / dirPhsC / neut / dirNeut / q / t 3 P2 ≤500 ms
2
3
50/51 SOBRECORRIENTE DE EMERGENCIA ACTIVA2
F50PTOC 1 ITMI Str Start general / dirGeneral / q / t 3 P2 ≤500 ms
2
3
50/51 ARRANQUE GENERAL
F50PTOC 1 ITMI Str Start phsA / dirPhsA / q / t 3 P2 ≤500 ms
2
3
50/51 ARRANQUE FASE A
F50PTOC 1 ITMI Str Start phsB / dirPhsB / q / t 3 P2 ≤500 ms
2
3
50/51 ARRANQUE FASE B
F50PTOC 1 ITMI Str Start phsC / dirPhsC / q / t 3 P2 ≤500 ms
2
3
50/51 ARRANQUE FASE C
F50PTOC 1 ITMI Op Operate phsA / phsB / phsC / q / t 3 P2 ≤500 ms
2
3
50/51 DISPARO FASES
F50NPTOC 1 ITMI Op Operate neut / q / t 3 P2 ≤500 ms
2
3
50N/51N DISPARO TIERRA
LPHD 1 ITMI PhyHealth Physical device health stVal / q / t 3 P2 ≤500 ms
Common LN 1 Health Health stVal / q / t
2
3
50/51 FALLA INTERNA RELE
FUNCION STUB
Common LN 1 ITMI Mod Mode stVal / q / t 3 P2 ≤500 ms
2 Beh Behaviour stVal / q / t
50 STUB ACTIVA3
F50PTOC 1 ITMI Str Start general / dirGeneral / phsA / dirPhsA / phsB / dirPhsB / phsC / dirPhsC / neut / dirNeut / q / t 3 P2 ≤500 ms
2
50 STUB ARRANQUE
F50PTOC 1 ITMI Op Operate general / phsA / phsB / phsC / neut / q / t 3 P2 ≤500 ms
2
50 STUB DISPARO
FUNCION DIFERENCIAL DE LINEA
F87LPDIF 1 ITMI Str Start general / dirGeneral/ q / t 3 P2 ≤500 ms
2
87L ARRANQUE GENERAL
F87LPDIF 1 ITMI Op Operate general /q / t 3 P2 ≤500 ms
2
87L DISPARO GENERAL
F87LPDIF 1 ITMI Str Start phsA / dirPhsA / q / t 3 P2 ≤500 ms
2
87L DETECCION DE FALLA FASE A
F87LPDIF 1 ITMI Str Start phsB / dirPhsB / q / t 3 P2 ≤500 ms
2
87L DETECCION DE FALLA FASE B
F87LPDIF 1 ITMI Str Start phsC / dirPhsC / q / t 3 P2 ≤500 ms
2
87L DETECCION DE FALLA FASE C
F87LPDIF 1 ITMI Str Start neut / dirNeut / q / t 3 P2 ≤500 ms
2
87L DETECCION DE FALLA A TIERRA
F87LPDIF 1 ITMI Op Operate phsA/ q / t 3 P2 ≤500 ms
2
87L DISPARO FASE A
F87LPDIF 1 ITMI Op Operate phsB / q / t 3 P2 ≤500 ms
2
87L DISPARO FASE B
F87LPDIF 1 ITMI Op Operate phsC / q / t 3 P2 ≤500 ms
2
87L DISPARO FASE C
Common LN 1 Mod Mode stVal / q / t 3 P2 ≤500 ms
2 Beh Behaviour stVal / q / t
87L ESTADO OFF ITMI
Common LN 1 Mod Mode stVal / q / t 3 P2 ≤500 ms
2 Beh Behaviour stVal / q / t
87L BLOQUEADA ITMI
LPHD 1 ITMI PhyHealth Physical device health stVal / q / t 3 P2 ≤500 ms
Common LN 1 Health Health stVal / q / t
2
87L FALLA INTERNA RELE
FUNCION DIFERENCIAL DE TRANSFORMADOR
F87TPDIF 1 ITMI Str Start general / dirGeneral /q / t 3 P2 ≤500 ms
2
3
4
87T ARRANQUE GENERAL
F87TPDIF 1 ITMI Op Operate general/ q / t 3 P2 ≤500 ms
2
3
4
87T DISPARO GENERAL
F87TNPDIF 1 ITMI Op Operate general / q / t 3 P2 ≤500 ms
2
87TN DISPARO GENERAL
F87TPDIF 1 ITMI Str Start phsA / dirPhsA / q / t 3 P2 ≤500 ms
2
3
4
87T DETECCION DE FALLA FASE A
F87TPDIF 1 ITMI Str Start phsB / dirPhsB / q / t 3 P2 ≤500 ms
2
3
4
87T DETECCION DE FALLA FASE B
F87TPDIF 1 ITMI Str Start phsC / dirPhsC / q / t 3 P2 ≤500 ms
2
3
4
87T DETECCION DE FALLA FASE C
F87TPDIF 1 ITMI Str Start neut / dirNeut / q / t 3 P2 ≤500 ms
2
3
4
87T DETECCION DE FALLA A TIERRA
Common LN 1 Mod Mode stVal / q / t 3 P2 ≤500 ms
2 Beh Behaviour stVal / q / t
3
4
87T ESTADO OFF ITMI
Common LN 1 Mod Mode stVal / q / t 3 P2 ≤500 ms
2 Beh Behaviour stVal / q / t
3
4
87T BLOQUEADA ITMI
LPHD 1 ITMI PhyHealth Physical device health stVal / q / t 3 P2 ≤500 ms
Common LN 1 Health Health stVal / q / t
2
3
4
87T FALLA INTERNA RELE
FUNCION RECIERRE
Common LN 1 Mod Mode stVal / q / t 3 P2 ≤500 ms
Beh Behaviour stVal / q / t
79 BLOQUEO RECIERRE MONOFASICO ITMI
Common LN 2 Mod Mode stVal / q / t 3 P2 ≤500 ms
Beh Behaviour stVal / q / t
79 BLOQUEO RECIERRE TRIFASICO ITMI
F79RREC 1 ITMI 3 P2 ≤500 ms
79 ARRANQUE RECIERRE MONOFASICO AutoRecSt Auto reclosing status stVal / q / t
F79RREC 2 ITMI 3 P2 ≤500 ms
79 ARRANQUE RECIERRE TRIFASICO AutoRecSt Auto reclosing status stVal / q / t
F79RREC 1 ITMI AutoRecSt Auto reclosing status 3 P2 ≤500 ms
2
79 RECIERRE EFECTUADO stVal / q / t
F79RREC 1 3 P2 ≤500 ms
2
79 BLOQUEO DINAMICO ITMI AutoRecSt Auto reclosing status stVal / q / t
F79RREC 1 ITMI AutoRecSt Auto reclosing status 3 P2 ≤500 ms
2
79 RECIERRE EN PROGRESO stVal / q / t
F79RREC 1 ITMI Op Operate (Close) phsA / q / t 3 P2 ≤500 ms
79 RECIERRE FASE A
F79RREC 1 ITMI Op Operate (Close) phsB / q / t 3 P2 ≤500 ms
79 RECIERRE FASE B
F79RREC 1 ITMI Op Operate (Close) phsC q / t 3 P2 ≤500 ms
79 RECIERRE FASE C
F79RREC 2 ITMI 3 P2 ≤500 ms

Indicate if single pole tripping allowed or


79 RECIERRE TRIFASICO CycTrMod1 three pole tripping always requested setVal
F79RREC 1 ITMI 3 P2 ≤500 ms

Indicate if single pole tripping allowed or


79 RECIERRE MONOFASICO CycTrMod1 three pole tripping always requested setVal
Common LN 1 Mod Mode stVal / q / t 3 P2 ≤500 ms
2 Beh Behaviour stVal / q / t
79 RECIERRE ON ITMI
Common LN 1 Mod Mode stVal / q / t 3 P2 ≤500 ms
2 Beh Behaviour stVal / q / t
79 RECIERRE OFF ITMI
FUNCION LOCALIZADOR DE FALLAS
F21FLRFLO 1 ITMI FltZ Fault Impedance cVal / q / t 3 P2 ≤500 ms
RESISTENCIA DE FALLA - OHM PRIMARIOS4
F21FLRFLO 1 ITMI FltZ Fault Impedance cVal / q / t 3 P2 ≤500 ms
REACTANCIA DE FALLA - OHM PRIMARIOS 5
F21FLRFLO 1 ITMI FltDisKm Fault Distance in km mag / q / t 3 P2 ≤500 ms
DISTANCIA DE FALLA - KM
DIRECCIONAL DE SOBRECORRIENTE DIRECCIONAL
F67PTOC 1 ITMI Str Start general / q / t 3 P2 ≤500 ms
2
3
67 ARRANQUE GENERAL
F67PTOC 1 ITMI Str Start phsA / dirPhsA / q / t 3 P2 ≤500 ms
2
3
67 ARRANQUE FASE A
F67PTOC 1 ITMI Str Start phsB / dirPhsB/ q / t 3 P2 ≤500 ms
2
3
67 ARRANQUE FASE B
F67PTOC 1 ITMI Str Start phsC / dirPhsC / q / t 3 P2 ≤500 ms
2
3
67 ARRANQUE FASE C
F67PTOC 1 ITMI Op Operate phsA / q / t 3 P2 ≤500 ms
2
3
67 DISPARO FASE A
F67PTOC 1 ITMI Op Operate phsB/ q / t 3 P2 ≤500 ms
2
3
67 DISPARO FASE B
F67PTOC 1 ITMI Op Operate phsC / q / t 3 P2 ≤500 ms
2
3
67 DISPARO FASE C
F67PTOC 1 ITMI Op Operate phsA / phsB / phsC / q / t 3 P2 ≤500 ms
2
3
67 DISPARO FASES
F67NPTOC 1 ITMI Op Operate neut / q / t 3 P2 ≤500 ms
2
3
67 DISPARO TIERRA
F67PTOC 1 ITMI TxPrm Permissive transmit general / phsA / phsB / phsC / neut / q / t 3 P2 ≤500 ms
2
3
67 ENVIO TELEPROTECCION
F67PTOC 1 ITMI RxPrm1 Permissive receive general / phsA / phsB / phsC / neut / q / t 3 P2 ≤500 ms
2
3
67 RECIBO TELEPROTECCION
F67PTOC 1 ITMI Op Operate general / phsA / phsB / phsC / neut / q / t 3 P2 ≤500 ms
2 RxPrm1 Permissive receive general / phsA / phsB / phsC / neut / q / t
3
67 DISPARO COMPARACION DIRECCIONAL
LPHD 1 ITMI PhyHealth Physical device health stVal / q / t 3 P2 ≤500 ms
Common LN 1 Health Health stVal / q / t
2
3
67 FALLA INTERNA RELE
Common LN 1 Mod Mode stVal / q / t 3 P2 ≤500 ms
2 Beh Behaviour stVal / q / t
3
67 OFF ITMI
Common LN 1 Mod Mode stVal / q / t 3 P2 ≤500 ms
2 Beh Behaviour stVal / q / t
3
67N OFF ITMI
FUNCION BLOQUEO OSCILACION DE POTENCIA
F68RPSB 1 ITMI Str Start general / dirGeneral / phsA / dirPhsA / phsB / dirPhsB / phsC / dirPhsC / neut / dirNeut / q / t 3 P2 ≤500 ms
2
3
68 DETECCION OSCILACION DE POTENCIA
Common LN 1 Mod Mode stVal / q / t 3 P2 ≤500 ms
2 Beh Behaviour stVal / q / t
3
68 OFF ITMI
FUNCION SUPERVISION DE LA MEDIDA
TVTR 1 EEHealth External equipment health stVal / q / t 3 P2 ≤500 ms
Common LN 1 Health Health stVal / q / t
2
3
4
FALLA TRANSFORMADORES DE POTENCIALES ITMI
TCTR 1 EEHealth External equipment health stVal / q / t 3 P2 ≤500 ms
Common LN 1 Health Health stVal / q / t
2
3
4
FALLA TRANSFORMADORES DE CORRIENTE ITMI
FUNCION FALLA INTERRUPTOR
50BF DISPARO FALLA INTERRUPTOR ETAPA 1 F50BFRBRF 1 ITMI OpIn Operate, retrip (“internal trip”) general / phsA / phsB / phsC / neut / q / t 3 P2 ≤500 ms

50BF DISPARO FASE A FALLA INTERRUPTOR ETAPA 1 F50BFRBRF 1 ITMI OpIn Operate, retrip (“internal trip”) general / phsA / phsB / phsC / neut / q / t 3 P2 ≤500 ms

50BF DISPARO FASE B FALLA INTERRUPTOR ETAPA 1 F50BFRBRF 1 ITMI OpIn Operate, retrip (“internal trip”) general / phsA / phsB / phsC / neut / q / t 3 P2 ≤500 ms

50BF DISPARO FASE C FALLA INTERRUPTOR ETAPA 1 F50BFRBRF 1 ITMI OpIn Operate, retrip (“internal trip”) general / phsA / phsB / phsC / neut / q / t 3 P2 ≤500 ms

50BF DISPARO FALLA INTERRUPTOR ETAPA 2 F50BFRBRF 1 ITMI Opex Breaker Failure trip (external) general / phsA / phsB / phsC / neut / q / t 3 P2 ≤500 ms

FUNCION CHEQUEO DE SINCRONISMO


F25RSYN 1 3 P2 ≤500 ms
VInd Voltage difference indicator
AngInd Angle difference indicator
25 CONDICIONES DE SINCRONIZACION SATISFATORIAS6 ITMI HzInd Frequency difference indicator
25 CHEQUEO DE SINCRONISMO EN PROGRESO7 F25RSYN 1 ITMI Synprg Synchrocheck in progress stVal / q / t 3 P2 ≤500 ms
Common LN 1 Mod Mode stVal / q / t 3 P2 ≤500 ms
Beh Behaviour stVal / q / t
25 OFF ITMI
Common LN 1 ITMI Mod Mode stVal / q / t 3 P2 ≤500 ms
Beh Behaviour stVal / q / t
25 BLOQUEADO
LPHD 1 ITMI PhyHealth Physical device health stVal / q / t 3 P2 ≤500 ms
Common LN 1 Health Health stVal / q / t
25 FALLA INTERNA RELE
FUNCION DIFERENCIAL DE BARRAS
F87BPDIF 1 ITMI Op Operate general / q / t 3 P2 ≤500 ms
2
87B DISPARO GENERAL
F87BPDIF 1 Str Start phsA / dirPhsA q / t 3 P2 ≤500 ms
2
87B DETECCION DE FALLA FASE A ITMI
F87BPDIF 1 Str Start phsB / dirPhsB / q / t 3 P2 ≤500 ms
2
87B DETECCION DE FALLA FASE B ITMI
F87BPDIF 1 Str Start phsC / dirPhsC / q / t 3 P2 ≤500 ms
2
87B DETECCION DE FALLA FASE C ITMI
F87BPDIF 1 Str Start neut / dirNeut / q / t 3 P2 ≤500 ms
2
87B DETECCION DE FALLA A TIERRA ITMI
Common LN 1 Mod Mode stVal / q / t 3 P2 ≤500 ms
2 Beh Behaviour stVal / q / t
87B ESTADO OFF ITMI
Common LN 1 Mod Mode stVal / q / t 3 P2 ≤500 ms
2 Beh Behaviour stVal / q / t
87B BLOQUEADA ITMI
LPHD 1 ITMI PhyHealth Physical device health stVal / q / t 3 P2 ≤500 ms
Common LN 1 Health Health stVal / q / t
2
87B FALLA INTERNA RELE
FUNCION SOBRECORRIENTE-TRAFO
F50PTOC 1 ITMI Str Start general / dirGeneral /q / t 3 P2 ≤500 ms
2
50/51 ARRANQUE GENERAL
F50PTOC 1 ITMI Str Start phsA / dirPhsA / q / t 3 P2 ≤500 ms
2
50/51 ARRANQUE FASE A
F50PTOC 1 ITMI Str Start phsB / dirPhsB/ q / t 3 P2 ≤500 ms
2
50/51 ARRANQUE FASE B
F50PTOC 1 ITMI Str Start phsC / dirPhsC / q / t 3 P2 ≤500 ms
2
50/51 ARRANQUE FASE C
F50NPTOC 1 ITMI Str Start neut / dirNeut / q / t 3 P2 ≤500 ms
2
50N/51N ARRANQUE TIERRA
F50PTOC 1 ITMI Op Operate phsA / phsB / phsC / q / t 3 P2 ≤500 ms
2
50/51 DISPARO FASES
F50NPTOC 1 ITMI Op Operate neut / q / t 3 P2 ≤500 ms
2
50N/51N DISPARO TIERRA
LPHD 1 ITMI PhyHealth Physical device health stVal / q / t 3 P2 ≤500 ms
Common LN 1 Health Health stVal / q / t
2
50/51 FALLA INTERNA RELE
F50GPTOC 1 ITMI Str Start general / dirGeneral / q / t 3 P2 ≤500 ms
2
50/51G ARRANQUE GENERAL
F50GPTOC 1 ITMI Op Operate general / q / t 3 P2 ≤500 ms
2
50/51G DISPARO GENERAL
FUNCION TEMPERATURA
F38STMP 1 ITMI Alm Temperature alarm level reached stVal / q / t 3 P2 ≤500 ms
38 ALARMA ALTA TEMPERATURA DEVANADO HV
F38STMP 2 ITMI Alm Temperature alarm level reached stVal / q / t 3 P2 ≤500 ms
38 ALARMA ALTA TEMPERATURA DEVANADO MV
F38STMP 3 ITMI Alm Temperature alarm level reached stVal / q / t 3 P2 ≤500 ms
38 ALARMA ALTA TEMPERATURA DEVANADO LV
F38STMP 4 ITMI Alm Temperature alarm level reached stVal / q / t 3 P2 ≤500 ms
38 ALARMA ALTA TEMPERATURA ACEITE PARTE INFERIOR CUBA
F38STMP 5 ITMI Alm Temperature alarm level reached stVal / q / t 3 P2 ≤500 ms
38 ALARMA ALTA TEMPERATURA ACEITE PARTE SUPERIOR CUBA
F38STMP 1 ITMI Trip Temperature trip level reached stVal / q / t 3 P2 ≤500 ms
38 DISPARO ALTA TEMPERATURA DEVANADO HV
F38STMP 2 ITMI Trip Temperature trip level reached stVal / q / t 3 P2 ≤500 ms
38 DISPARO ALTA TEMPERATURA DEVANADO MV
F38STMP 3 ITMI Trip Temperature trip level reached stVal / q / t 3 P2 ≤500 ms
38 DISPARO ALTA TEMPERATURA DEVANADO LV
F38STMP 4 ITMI Trip Temperature trip level reached stVal / q / t 3 P2 ≤500 ms
38 DISPARO ALTA TEMPERATURA ACEITE PARTE INFERIOR CUBA
F38STMP 5 ITMI Trip Temperature trip level reached stVal / q / t 3 P2 ≤500 ms
38 DISPARO ALTA TEMPERATURA ACEITE PARTE SUPERIOR CUBA
FUNCION COMPLEMENTARIAS
TA1SIML 3 ITMI GasInsTr Gas Insulation Trip stVal / q / t 3 P2 ≤500 ms
DISPARO SOBREPRESION
TA1SIML 2 ITMI GasInsTr Gas Insulation Trip stVal / q / t 3 P2 ≤500 ms
DISPARO SOBREPRESION SUBITA
QM1SIML 1 ITMI GasInsTr Gas Insulation Trip stVal / q / t 3 P2 ≤500 ms
DISPARO SOBREFLUJO CAMBIADOR DE TAP
QM1SIML 2 ITMI GasInsTr Gas Insulation Trip stVal / q / t 3 P2 ≤500 ms
DISPARO SOBREPRESION CAMBIADOR DE TAP
TA1SIML 1 ITMI GasFlwTr Gas Flow Trip stVal / q / t 3 P2 ≤500 ms
DISPARO BUCHHOLZ

Notas:
1. Se debe definir si la combinación de las señales "Tr" y "RxPrm1" se hace en el gateway o en el centro de control
2. Esta condición no es posible modelarla dentro de la estructura de la norma (pérdida de potenciales) y depende de la implementación decada fabricante como se realice esto dentro del equipo. Por ahora se ha modelado con el elvío del DO "Str"
3. Esta condición depende de cada fabricante, se ha modelado mediante los DOs "Mod" y "Beh"
4. El DO "FltZ" es un valor complejo, el valor de la resistencia de falla debe ser calculado
5. El DO "FltZ" es un valor complejo, el valor de la reactancia de falla debe ser calculado
6. Los DOs "VInd", "AngInd", "HzInd" son opcionales
7. El DO "Synprg" es opcional

Comentarios:
- Se puede usar el DO "Blk" (opcional) para determinar si una función está o no bloqueda, de acuerdo a la edición 2 de la norma IEC 61850.
- Cada uno de los nodos lógicos cuenta con los DOs "Mod", "Beh", "health" (mandatorios en la edición 1 de la norma), y como siempre se encuentran disponibles no es necesario especificarlos.
- Cada uno de los dispositivos físicos cuenta con el DO "Phyhealth" (mandatorio), y como siempre se encuentra disponible no es necesario especificarlo.
BAHIAS 34,5 kV

LISTADO DE SEÑALES AL CENTRO DE CONTROL

FUNCION DE FRECUENCIA Source Instance Sink Data Object Description Data Attribute Msg PC TT
Type
PTUF 1 ITMI Str Start general / q / t 3 P2 ≤500 ms
2
81 ARRANQUE
PTUF 1 ITMI Op Operate (Trip) general / q / t 3 P2 ≤500 ms
2
81 DISPARO
PTUF 1 ITMI Mod Mode stVal / q / t 3 P2 ≤500 ms
2 Beh Behaviour stVal / q / t
81 OFF
Common LN 1 ITMI Mod Mode stVal / q / t 3 P2 ≤500 ms
2 Beh Behaviour stVal / q / t
81 BLOQUEADA
LPHD 1 ITMI PhyHealth Physical device health stVal / q / t 3 P2 ≤500 ms
Common LN 1 Health Health stVal / q / t
2
81 FALLA INTERNA RELE
FUNCION SECUENCIA NEGATIVA
F46PTOC ITMI Str Start general / dirGeneral / phsA / dirPhsA / phsB / dirPhsB / phsC / dirPhsC / neut / dirNeut / q / t 3 P2 ≤500 ms
1
46 ARRANQUE 2
F46PTOC ITMI Op Operate (Trip) general / phsA / phsB / phsC / neut / q / t 3 P2 ≤500 ms
1
46 DISPARO 2
LPHD 1 ITMI PhyHealth Physical device health stVal / q / t 3 P2 ≤500 ms
Common LN 1 Health Health stVal / q / t
2
46 FALLA INTERNA RELE
FUNCION SOBRECORRIENTE
F50PTOC 1 ITMI Str Start general / q / t 3 P2 ≤500 ms
2
3
50/51 ARRANQUE GENERAL
F50PTOC 1 ITMI Str Start phsA / dirPhsA / q / t 3 P2 ≤500 ms
2
3
50/51 ARRANQUE FASE A
F50PTOC 1 ITMI Str Start phsB / dirPhsB/ q / t 3 P2 ≤500 ms
2
3
50/51 ARRANQUE FASE B
F50PTOC 1 ITMI Str Start phsC / dirPhsC / q / t 3 P2 ≤500 ms
2
3
50/51 ARRANQUE FASE C
F50NPTOC 1 ITMI Str Start neut / dirNeut / q / t 3 P2 ≤500 ms
2
3
50N/51N ARRANQUE TIERRA
F50PTOC 1 ITMI Op Operate (Trip) phsA / phsB / phsC / q / t 3 P2 ≤500 ms
2
3
50/51 DISPARO FASES
F50NPTOC 1 ITMI Op Operate (Trip) neut / q / t 3 P2 ≤500 ms
2
3
50N/51N DISPARO TIERRA
Common LN 1 ITMI Mod Mode stVal / q / t 3 P2 ≤500 ms
2 Beh Behaviour stVal / q / t
3
50N/51N BLOQUEADO
LPHD 1 ITMI PhyHealth Physical device health stVal / q / t 3 P2 ≤500 ms
Common LN 1 Health Health stVal / q / t
2
3
50/51 FALLA INTERNA RELE
FUNCION RECIERRE
Common LN 1 Mod Mode stVal / q / t 3 P2 ≤500 ms
Beh Behaviour stVal / q / t
79 BLOQUEO RECIERRE ITMI
F79RREC 1 ITMI 3 P2 ≤500 ms
79 ARRANQUE RECIERRE AutoRecSt Auto reclosing status stVal / q / t
79 RECIERRE EFECTUADO F79RREC 1 ITMI AutoRecSt Auto reclosing status stVal / q / t 3 P2 ≤500 ms
3 P2 ≤500 ms
79 BLOQUEO DINAMICO F79RREC 1 ITMI AutoRecSt Auto reclosing status stVal / q / t
79 RECIERRE EN PROGRESO F79RREC 1 ITMI AutoRecSt Auto reclosing status stVal / q / t 3 P2 ≤500 ms
Common LN 1 Mod Mode stVal / q / t 3 P2 ≤500 ms
Beh Behaviour stVal / q / t
79 RECIERRE ON ITMI
Common LN 1 Mod Mode stVal / q / t 3 P2 ≤500 ms
Beh Behaviour stVal / q / t
79 RECIERRE OFF ITMI
FUNCION LOCALIZADOR DE FALLAS
F21FLRFLO 1 ITMI FltZ Fault Impedance cVal / q / t 3 P2 ≤500 ms
RESISTENCIA DE FALLA - OHM PRIMARIOS1
F21FLRFLO 1 ITMI FltZ Fault Impedance cVal / q / t 3 P2 ≤500 ms
REACTANCIA DE FALLA - OHM PRIMARIOS2
F21FLRFLO 1 ITMI FltDisKm Fault Distance in km mag / q / t 3 P2 ≤500 ms
DISTANCIA DE FALLA - KM
FUNCION SUPERVISION DE LA MEDIDA
TVTR 1 EEHealth External equipment health stVal / q / t 3 P2 ≤500 ms
Common LN 1 Health Health stVal / q / t
2
3
4
FALLA TRANSFORMADORES DE POTENCIALES ITMI
TCTR 1 EEHealth External equipment health stVal / q / t 3 P2 ≤500 ms
Common LN 1 Health Health stVal / q / t
2
3
4
FALLA TRANSFORMADORES DE CORRIENTE ITMI
FUNCION FALLA INTERRUPTOR
50BF DISPARO FALLA INTERRUPTOR ETAPA 1 F50BFRBRF 1 ITMI OpIn Operate, retrip (“internal trip”) general / q / t 3 P2 ≤500 ms

50BF DISPARO FALLA INTERRUPTOR ETAPA 2 F50BFRBRF 1 ITMI Opex Breaker Failure trip (external) general / q / t 3 P2 ≤500 ms
LPHD 1 ITMI PhyHealth Physical device health stVal / q / t 3 P2 ≤500 ms
Common LN 1 Health Health stVal / q / t
50BF FALLA INTERNA RELE
FUNCION CHEQUEO DE SINCRONISMO
F25RSYN 1 3 P2 ≤500 ms
Vind Voltage difference indicator
AngInd Angle difference indicator
25 CONDICIONES DE SINCRONIZACION SATISFATORIAS3 ITMI HzInd Frequency difference indicator
F25RSYN 1 ITMI Synprg Synchrocheck in progress stVal / q / t 3 P2 ≤500 ms
25 CHEQUEO DE SINCRONISMO EN PROGRESO4
Common LN 1 Mod Mode stVal / q / t 3 P2 ≤500 ms
Beh Behaviour stVal / q / t
25 OFF ITMI
Common LN 1 ITMI Mod Mode stVal / q / t 3 P2 ≤500 ms
Beh Behaviour stVal / q / t
25 BLOQUEADO
LPHD 1 ITMI PhyHealth Physical device health stVal / q / t 3 P2 ≤500 ms
Common LN 1 Health Health stVal / q / t
25 FALLA INTERNA RELE
FUNCIONES COMPLENTARIAS
QA1SCBR 1 ITMI TrCctAlm Trip circuit health alarm stVal / q / t 3 P2 ≤500 ms
74 FALLA CIRCUITO SUPERVISOR DE DISPARO 1
QA1SCBR 2 ITMI TrCctAlm Trip circuit health alarm stVal / q / t 3 P2 ≤500 ms
74 FALLA CIRCUITO SUPERVISOR DE DISPARO 2

Notas:
1. El DO "FltZ" es un valor complejo, el valor de la resistencia de falla debe ser calculado
2. El DO "FltZ" es un valor complejo, el valor de la reactancia de falla debe ser calculado
3. Los DOs "VInd", "AngInd", "HzInd" son opcionales
4. El DO "Synprg" es opcional

Comentarios:
- Se puede usar el DO "Blk" (opcional) para determinar si una función está o no bloqueda, de acuerdo a la edición 2 de la norma IEC 61850.
- Cada uno de los nodos lógicos cuenta con los DOs "Mod", "Beh", "health" (mandatorios en la edición 1 de la norma), y como siempre se encuentran disponibles no es necesario especificarlos.
- Cada uno de los dispositivos físicos cuenta con el DO "Phyhealth" (mandatorio), y como siempre se encuentra disponible no es necesario especificarlo.
LISTADO DE DATOS DE INFORMACION A INTERCA
SUBESTACIÓN ORTIGAL
RTU
CANAL
DIRECCION RTU
BAUD/RATE

NOMENCL.
NIVEL DE TENSION BAHÍA EQUIPO ELEM INFO
OPERATIVA

UNIT DATA TYPE 2 SINGLE -POINT


13.2
13.2
13.2
13.2
13.2
13.2
13.2
13.2
13.2
13.2
13.2
13.2
13.2
13.2
13.2
13.2

UNIT DATA TYPE 4 DOUBLE -POINT


13.2
13.2
13.2

UNIT DATA TYPE 46 DOUBLE C


13.2
13.2
13.2

UNIT DATA TYPE 47 REGULATIN

UNIT DATA TYPE 9 MEASURED VALUES,N


13.2
13.2
13.2
13.2
13.2
13.2
13.3
13.4
13.5
13.6
13.7
13.8
13.9
13.10
13.11
13.12
13.13
13.14
13.15
UNIT DATA TYPE 15 INTEGRATE
RMACION A INTERCAMBIAR CON CENTROS DE CONTROL

DIRECCIÓN EN LA RTU
HACIA CRC
DESCRIPCIÓN
PROTOCOLO IEC870-5-
101
DATA TYPE 2 SINGLE -POINT WITH TIME TAG
ARRANQUE GENERAL 9020
50/51 DISP SOBRECTE 9021
50N/51N DISP SOBRECTE 9022
IED POSICION LOCAL 9023
74 FALLA CIRCUITO DISPARO 1 9024
74 FALLA CIRCUITO DISPARO 2 9025
50/51 FALLA INTERNA RELE 9026
50/51 FALLA COMUNICACIO IED 9027
79 RECIERRE EFECTUADO 9028
60 FALLA POTENCIALES 9029
50N/51N BLOQUEO TIERRA 9030
81-U DISP BAJA FRECUENCIA 9031
FALLA AC 9032
FALLA DC 9033
BLOQUEO MANDO REMOTO INTERRU 9034
FALLA MECANISMO INTERRUPTOR 9035

ATA TYPE 4 DOUBLE -POINT WITH TIME TAG


INT 10010
Recierre Incluido / Excluido 10011
Bloqueo disparo tierra ON / OFF 10012

UNIT DATA TYPE 46 DOUBLE COMMAND


Comando de Interruptor 410
Incluir / Excluir Recierre 411
Bloqueo disparo tierra ON / OFF 412

IT DATA TYPE 47 REGULATING COMMAND

TYPE 9 MEASURED VALUES,NORMALIZED VALUES


P 18020
Q 18021
Phi 18022
current phase 1 18023
current phase 2 18024
current phase 3 18025
I1 Corriente de falla
I2 Corriente de falla
I3 Corriente de falla
IN Corriente de falla
U1
U2
U3

NIT DATA TYPE 15 INTEGRATED TOTALS


CONTROL
FR.DIS.079,01

OBSERVACIONES OBSERVACIONES

IEC-61850
CTO CABUYAL

CTO CABUYAL