Professional Documents
Culture Documents
Load Models: 9.1 Wye-Connected Loads
Load Models: 9.1 Wye-Connected Loads
Load Models
The load models developed are to be used in the iterative process of a power-
flow program, where the load voltages are initially assumed. One of the
results of the power-flow analysis is to replace the assumed voltages with
the actual operating load voltages. All models are initially defined by a com-
plex power per phase and an assumed line-to-neutral voltage (wye load) or
an assumed line-to-line voltage (delta load). The units of the complex power
can be in volt-amperes and volts or per-unit volt-amperes and per-unit volt-
ages. For all loads, the line currents entering the load are required in order to
perform the power-flow analysis.
9.1 Wye-Connected Loads
Figure 9.1 is the model of a wye-connected load.
325
326 Distribution System Modeling and Analysis
IL a +
Sa Van
−
−
− Vcn
Sb Sc
I Lb +
Vbn
+
IL c
FIGURE 9.1
Wye-connected load.
The notation for the specified complex powers and voltages are as follows:
*
S Sa
ILa = a = /δa − θa = ILa /α a
Van Van
*
S Sb
ILb = b = /δb − θb = ILb /α b (9.4)
Vbn Vbn
*
S Sc
ILc = c = /δc − θc = ILc /α c
Vcn Vcn
In this model, the line-to-neutral voltages will change during each iteration
until convergence is achieved.
Load Models 327
2 2
Van Van
Za = * = /θa = Z a /θa
Sa Sa
2 2
Vbn Vbn
Zb = * = /θb = Z b /θb (9.5)
Sb Sb
2 2
Vcn Vcn
Zc = = /θc = Z c /θc
Sc * Sc
The load currents as a function of the “constant load impedances” are given by:
Van Van
ILa = = /δa − θa = ILa /αa
Za Za
Vbn Vbn
ILb = = /δb − θb = ILb /αb (9.6)
Zb Zb
Vcn Vcn
ILc = = /δc − θc = ILc /αc
Zc Zc
In this model, the line-to-neutral voltages will change during each iteration,
but the impedance computed in Equation 9.5 will remain constant.
where
δabc = line-to-neutral voltage angles
θabc = power factor angles
328 Distribution System Modeling and Analysis
9.1.4 Combination Loads
Combination loads can be modeled by assigning a percentage of the total
load to each of the three aforementioned load models. The current for the
constant impedance load is computed assuming the nominal load voltage.
In a similar manner, the current for the constant current load is computed
assuming the nominal load voltage. All load currents will change as the load
voltage changes in the iterative process. The total line current entering the
load is the sum of the three components.
Example 9.1
A combination load is served at the end of a 10,000 ft long, three-phase
distribution line. The impedance of the three-phase line is:
S 1904.0 + j 1180.0
an
[S abc ] = S bn = 2375.0 + j 780.6 kVA
S 1800.0 + j 871.8
cn
The load is specified to be 50% constant complex power, 20% constant
impedance, and 30% constant current. The nominal line-to-line voltage
of the feeder is 12.47 kV.
a. A
ssume the nominal voltage and compute the component of load
current attributed to each of the loads and the total load current.
The assumed line-to-neutral source voltages at the start of the
iterative routine are:
7200/0
[ELN abc ] = 7200/ − 120 V
7200/120
Load Models 329
952.0 + j 590.0
[SP ] = [S abc ] ⋅ 0.5 = 1187.5 + j 390.3
900.0 + j 435.9
380.8 + j 236.0
[SZ ] = [S abc ] ⋅ 0.2 = 475.0 + j 156.1
360.0 + j 174.4
571.2 + j 354.0
[SI ] = [S abc ] ⋅ 0.3 = 712.5 + j 234.2
540.0 + j 261.5
155.6/ − 31.8
*
SPi .1000
Ipq i = = 173.6/ − 138.2 A
VLN i
138.9/94.2
The constant impedances for that part of the load are computed as:
98.4 + j 61.0
VLN i
2
Zi = *
= 98.5 + j 33.4 Ω
SZ i ⋅ 1000
116.6 + j 56.5
For the first iteration, the currents due to the constant impedance
portion of the loads are:
62.2/ − 31.8
VLN i
IZi = = 69.4/ − 138.2 A
Z i
55.6/94.2
330 Distribution System Modeling and Analysis
* 93.3
SL ⋅ 1000
IM i = i = 104.2 A
VLN i
83.3
93.3/ − 31.8
II i = IM i /δ i − θi = 104.2/ − 138.2 A
83.3/94.2
The total load currents are the sum of the three components:
311.1/ − 31.8
[I abc ] = I pq + [IZ ] + [II ] = 347.2/ − 138.2 A
277.8/94.2
1904.0 + j 1180.0
VLN i ⋅ I * abc i
S abc i = = 2375.0 + j 780.6
1000 1800.0 + j 871.8
This gives the same complex powers that were given for nominal
load voltages.
b.
Determine the currents at the start of the second iteration. The
voltages at the load after the first iteration are:
The steps are repeated with the exceptions that the impedances of
the constant impedance portion of the load will not be changed
Load Models 331
and the magnitude of the currents for the constant current portion
of the load change will not change.
The constant complex power portion of the load currents is:
167.1/ − 33.1
*
SPi . 1000
Ipq i = = 180.0/ − 141.7 A
VLN i
142.7/92.5
The currents due to the constant impedance portion of the load are:
57.9/ −33.1
VLN i
A
IZ i = = 67.0/ −141.7
Z i
53.1/92.5
The currents due to the constant current portion of the load are:
93.3/ −33.1
II i = IM i /δ i − θi = 104.2/−141.7 A
83.3/92.5
The total load currents at the start of the second iteration will be:
318.4/−33.1
[I abc ] = [Ipq ] + [IZ ] + [II ] = 351.2/−141.7 A
280.1/92.5
The new complex powers of the combination loads are:
1813.7 + j 1124.0
*
VLN i ⋅ I abc
S abc i = i
= 2316.2 + j 761.3
1000 1766.4 + j 855.5
Because the load voltages have changed, the total complex power
has also changed.
Observe how the currents have changed from the original currents. The
currents for the constant complex power loads have increased because
the voltages are reduced from the original assumption. The currents
for the constant impedance portion of the load have decreased because
the impedance stayed constant but the voltages are reduced. Finally,
the magnitude of the constant current portion of the load has remained
constant. Again, all three components of the loads have the same phase
angles because the power factor of the load has not changed.
332 Distribution System Modeling and Analysis
9.2 Delta-Connected Loads
The model for a delta-connected load is shown in Figure 9.2.
The notation for the specified complex powers and voltages in Figure 9.2
are as follows:
*
S S ab
ILab = ab = /δab − θab = ILab /α ab
Vab Vab
*
S S bc
ILbc = bc = /δbc − θbc = ILbc /α bc (9.11)
Vbc Vbc
*
S S ca
ILca = ca = /δca − θca = ILca /α ac
Vca Vca
In this model, the line-to-line voltages will change during each iteration,
resulting in new current magnitudes and angles at the start of each iteration.
ILb
ILab
Sab
ILa
Sca Sbc
ILca ILbc
ILc
FIGURE 9.2
Delta-connected load.
Load Models 333
2 2
Vab Vab
Z ab = * = /θab = Z ab /θab
S ab S ab
2 2
VLbc Vbc
Z bc = = /θbc = Z bc /θbc (9.12)
S bc * S bc
2 2
Vca Vca
Z ca = = /θca = Z ca /θca
S ca * S ca
The delta load currents as a function of the “constant load impedances” are:
Vab Vab
ILab = = /δab − θab = ILab /αab
Z ab Z ab
Vbc Vbc
ILbc = = /δbc − θbc = ILbc /αbc (9.13)
Z bc Z bc
Vca Vca
ILca = = /δca − θca = ILca /αca
Z ca Z ca
In this model, the line-to-line voltages will change during each iteration
until convergence is achieved.
9.2.4 Combination Loads
Combination loads can be modeled by assigning a percentage of the total
load to each of the three aforementioned load models. The total delta current
for each load is the sum of the three components.
I ILab
a 1 0 −1
Ib = −1 1 0 ⋅ ILbc
Ic 0 −1 1 ILca (9.15)
[ I abc ] = [Di ] ⋅ [ ILabc ]
9.4 Shunt Capacitors
Shunt capacitor banks are commonly used in distribution systems to help
in voltage regulation and to provide reactive power support. The capacitor
banks are modeled as constant susceptances connected in either wye or delta.
Similar to the load model, all capacitor banks are modeled as three-phase
banks with the currents of the missing phases set to zero for single-phase
and two-phase banks.
ICa +
jBa Van
−
jBb − Vcn
−
ICb jBc +
Vbn
+
ICc
FIGURE 9.3
Wye-connected capacitor bank.
The individual phase capacitor units are specified in kvar and kV.
The constant susceptance for each unit can be computed in Siemens. The
susceptance of a capacitor unit is computed by:
kvar
Bc = 2
S (9.16)
kVLN ⋅ 1000
With the susceptance computed, the line currents serving the capacitor bank
are given by:
IC a = jB a ⋅Van
IC b = jB b ⋅Vbn (9.17)
IC c = jB c ⋅Vcn
kvar
Bc = 2
S (9.18)
kVLL ⋅ 1000
336 Distribution System Modeling and Analysis
ICb
ICab
ICa Bab
Bca
ICc
FIGURE 9.4
Delta-connected capacitor bank.
With the susceptance computed, the delta currents serving the capacitor
bank are given by:
IC ab = jB a ⋅Vab
IC bc = jB b ⋅Vbc (9.19)
IC ca = jB c ⋅Vca
The line currents flowing into the delta-connected capacitors are c omputed
by applying Kirchhoff’s Current Law at each node. In matrix form, the
equations are:
IC IC ab
a
1 0 −1
IC b = −1 1 0 ⋅ IC bc (9.20)
IC c 0 −1 1 IC ca
have been determined, they are converted to the phase domain. A direct
analysis of the machine in the phase domain is introduced and is employed
for the analysis of both motors and generators.
The given parameters for the induction machine are assumed to be:
Zsi Zri
+ +
Isi Iri
Vsi Ymi RLi Vri
Imi
− −
FIGURE 9.5
Sequence network.
338 Distribution System Modeling and Analysis
Wye Delta
ZD Ω
ZYΩ = (9.22)
3
Example 9.2
A three-phase induction machine is rated:
kVAbase = 150
150
kVA1base = = 50
3
480
kVLLbase = = 0.48
1000
kVLLbase
kVLN base = = 0.2771
3
Load Models 339
kVA1base
IYbase = = 180.42
kVLN base
kVLLbase 2 ⋅ 1000
ZYbase = = 1.536
kVAbase
Zm = Zm pu ⋅ ZYbase = j 6.2501 Ω
kVA1base
ID base = = 104.1667
kVLLbase
kVLLbase ⋅ 1000
ZD base = = 4.608
ID base
2
kVLLbase 2
⋅ 1000 kVLLbase ⋅ 1000
ZD base = =
kVA1base kVA base
3
2
kVLLbase ⋅ 1000
ZD base = 3 ⋅ = 3 ⋅ ZYbase
kVAbase
ZD m = Zm pu ⋅ ZD base = 18.7504 Ω
340 Distribution System Modeling and Analysis
ZD s
Zs i = = Rs + jX s = 0.1 + j 0.2499 Ω
3
ZD r
Zri = = Rr + X r = 0.0849 + j 0.175 Ω
3
ZD m
Zmi = = jX m = j 6.2501 Ω
3
1
Ymi = = − j 0.16 S
Zmi
where
i = 1 positive sequence
i = 2 negative sequence
1 − si
RLi = ⋅ Rri (9.23)
si
where
ns − nr
positive sequence slip = s1 =
ns
negative sequence slip = s 2 = 2 − s1
120 ⋅ f
ns = synchronous speed in rpm =
p
f = synchronous speed
p = number of poles
nr = rotor speed in rpm
Note that the negative sequence load resistance will be a negative value that
will lead to a negative component of shaft power.
The positive and negative sequence networks can be analyzed i ndividually,
and then sequence currents and voltages are converted to phase components.
At this point, it is assumed that the stator line-to-line voltages are known.
When only the magnitudes of the line-to-line voltages are known, the Law
Load Models 341
of Cosines is used to establish the angles on the voltages. The equivalent line-
to-neutral voltages are needed for the analysis of the sequence networks. The
line-to-neutral voltages are computed by:
V
ab
[VLLabc ] = Vbc
Vca
(9.24)
V
an
[VLN abc ] = [W ] ⋅ [VLLabc ] = Vbn
Vcn
where
2 1 0
1
[W ] = ⋅ 0 2 1
3
1 0 2
The computed line-to-neutral voltages are converted to sequence
voltages by:
0
−1
[Vs ] = [ A ]
012 ⋅ [VLN abc ] = Vs1 (9.25)
Vs 2
where
1 1 1
[A] = 1 a2 a
1 a a2
a = 1/120
With the stator sequence voltages computed, the circuits of Figure 9.5 are
analyzed to compute the sequence stator and rotor currents. The sequence
input impedances for i = 1 and 2 are:
Vs i
Is i =
Z ini
0 (9.27)
[ 012 ] Is1
Is =
Is 2
Vmi = Vs i − Zs i ⋅ Is i
Vmi
Imi =
Zmi
Iri = Is i − Imi
Vri = Vmi − Zri ⋅ Iri
(9.28)
or: Vri = RLi ⋅ Iri
0
[ Ir012 ] = Ir1
Ir2
0
[Vr012 ] = Vr 1
Vr
2
After the sequence voltages and currents have been computed, they are con-
verted to phase components by:
[ Isabc ] = [ A ] ⋅ [ Is 012 ]
[ Irabc ] = [ A ] ⋅ [ Ir012 ] (9.29)
[Vrabc ] = [ A ] ⋅ [Vr012 ]
*
Vsabc i ⋅ ( Isabc i )
Ssabc i =
1000
3
Example 9.3
The motor of Example 9.2 is operating with a positive sequence slip of
0.035 and line-to-line input voltages of:
480/0
[ abc ]
VLL = 490/ − 121.4
475/118.3
Compute:
273.2/ − 30.7
[Vsabc ] = [W ] ⋅ [VLLabc ] = 281.9/ − 150.4
279.1/87.9
0
⋅ [Vsabc ] = 278.1/ − 31.0
−1
[Vs 012 ] = [A ]
5.1/130.1
278.1/ − 31.0
[Vs ] =
5.1/130.1
For: k = 1 and 2
Vs k 115.1/ − 60.2
Is k = =
Z ink 11.5/58.6
254.7/ − 35.4
Vmk = Vs k − Zs ⋅ Is k =
2.0/135.1
104.7/ − 39.6
Irk = Is k − Imk =
11.2/59.0
0 0
[Is 012 ] = Is 1 = 115.1/ − 60.2
Is 2
11.5/58.6
0
0
[Ir012 ] = Ir1 = 104.7/ − 39.6
Ir2 11.2/59.0
110.0/ − 55.0
[Isabc ] = [A ] ⋅ [Is 012 ] = 126.6/179.7
109.6/54.6
103.7/ − 33.4
[Irabc ] = [A ] ⋅ [Ir012 ] = 115.2/ − 161.6
96.2/76.3
The rotor sequence and phase voltages are:
245.2/ − 39.6
Vrk = Irk ⋅ RLk =
0.5/ − 121.0
0
[Vr012 ] = 245.2/ − 39.6
0.5/ − 121.0
245.3−39.7
[Vrabc ] = [A ] ⋅ [Vr012 ] = 244.7/ − 159.5
245.5/80.5
For i = 1, 2, 3
27.4 + j 12.4
Vsabc i ⋅ ( Isabc K )
*
Ssabc i = = 30.9 + j 17.8
1000 25.6 + j 16.8
3
Sstotal = ∑ Ss
k −1
abck = 83.87 + j 47.00 kW + jk var
25.3 + j 2.8
Vrabc i ⋅ ( I 4abc k )
*
Sr abc i = = 28.2 + j 1.0
1000 23.6 + j 1.7
3
Srtotal = ∑ Sr
k =1
abck = 77.03 kW
ZM i = Rs i + jXs i +
( jXmi ) ⋅ ( Rri + RLi + jXri ) (9.31)
Rri + RLi + j ( Xmi + Xri )
Once the input sequence impedances have been determined, the analysis
of an induction machine operating with unbalance voltages requires the
following steps:
Vab 1 1 1 Vab
o
1
Vab1 = 1 a a2 ⋅ Vbc (9.32)
Vab 3 1 a2 a Vca
2
Van0 = Vab0 = 0
(9.34)
Van1 = t * ⋅Vab1
Van2 = t ⋅Vab2
Load Models 347
where
1
t= /30
3
Van 1 0 0 Vab0
0
Van 1 = 0 t* 0 ⋅ Vab1 (9.35)
Van2 0 0 t Vab2
[VLN 012 ] = [T ] ⋅ [VLL012 ]
where
1 0 0
[T ] = 0 t* 0
0 0 t
Step 3: Compute the sequence line currents flowing into the machine:
Ia0 = 0
Van1
Ia1 =
ZM 1 (9.36)
Van2
Ia2 =
ZM 2
Step 4: Transform the sequence currents to phase currents:
where
1 1 1
[A] = 1 a2 a
1 a a2
a = 1/120
The four steps outlined previously can be performed without actually
computing the sequence voltages and currents. The procedure basically
reverses the steps.
348 Distribution System Modeling and Analysis
Define:
1
YM i = (9.38)
ZM i
I0 = 0
I 1 = YM 1 ⋅Van1 (9.39)
I 2 = YM 2 ⋅Van2
Since I0 and Vab0 are both zero, the following relationship is true:
I 0 = Vab0 = 0 (9.40)
I 1 0 0 Van 0
0
I1 = 0 YM 1 0 ⋅ Van 1
I2 0 0 YM 2 Van
2 (9.41)
where
1 0 0
[YM 012 ] = 0 YM 1 0
0 0 YM 2
Substitute Equation 9.43 into Equation 9.42, and substitute the resultant
e quation into Equation 9.44 to get:
Define:
Therefore:
The induction machine “phase frame admittance matrix” [YM abc ] is defined
in Equation 9.46. Equation 9.47 is used to compute the input phase currents of
the machine as a function of the phase line-to-line terminal voltages. This is
the desired result. Recall that [YM abc ] is a function of the slip of the machine,
so that a new matrix must be computed every time the slip changes.
Equation 9.47 can be used to solve for the line-to-line voltages as a function
of the line currents by:
where
where
2 1 0
−1 1
[W ] = [A] ⋅ [T ] ⋅ [A] = ⋅ 0 2 1
3
1 0 2
The matrix [W] is a very useful matrix that allows the determination of
the “equivalent” line-to-neutral voltages from the line-to-line voltages. It is
important to know that if the feeder serving the motor is grounded wye,
then there will be line-to-ground voltages at the motor terminals. Because
the motor is either ungrounded wye or delta, it will be necessary to convert
350 Distribution System Modeling and Analysis
where
The inverse of Equation 9.50 can be taken to determine the line currents as a
function of the equivalent line-to-neutral voltages.
where
Care must be taken in applying Equation 9.51 to ensure that the voltages
used are the equivalent line-to-neutral, not the line-to-ground, voltages. As
was pointed out earlier, when the line-to-ground voltages are known, they
must first be converted to the line-to-line values, and then Equation 9.49
should be used to compute the line-to-neutral voltages.
Once the machine terminal currents and line-to-neutral voltages are
known, the input phase complex powers and the total three-phase input
complex power can be computed.
S a = Van ⋅ (I a )*
S b = Vbn ⋅ (I b )*
(9.52)
S c = Vcn ⋅ (I c )*
STotal = S a + S b + S c
Mostly, the only voltages known will be the magnitudes of the three
l ine-to-line voltages at the machine terminals. When this is the case, the Law
of Cosines must be used to compute the angles associated with the measured
magnitudes.
Load Models 351
Example 9.4
The induction machine in Example 9.2 is operating such that:
Vs 480.0/0
ab
[VLLabc ] = Vsbc = 490/ − 121.4 V
Vs 475/118.3
ca
Determine the input line currents and complex power input to the
machine (motor).
Compute the negative sequence slip:
s 2 = 2 − s 1 = 1.965
Compute the sequence load resistance values:
1 − si 2.3408
RLi = ⋅ Rri =
si −0.0417
0.3613 − j 0.2019
1
YM i = =
ZM i 0.7166 − j 2.1385
1 0 0
1
t= ⋅ /30 [ ] 0
T = t* 0
3 0
0 t
1 1 1
a = 1/120 [A ] = 1 a2 a
1 a a2
2 1 0
1
[W ] = ⋅ 0 2 1
3
1 0 2
352 Distribution System Modeling and Analysis
1 0 0 1 0 0
[ 012 ] 0
YM = YM 1 0 = 0 0.3613 − j 0.2019 0
0 0 YM 2 0 0 0.7166 − j 2.1385
−1
[YM abc ] = [A ] ⋅ [YM 012 ] ⋅ [T ] ⋅ [A ]
0.6993 − j 0.3559 −0.0394 − j 0.0684 0.34 + j 0.4243
= 0.34 + j 0.4243 0.6993 − j 0.3559 −0.0394 − j 0.0684
−0.0394 − j 0.0684 0.34 + j 0.4243 0.6993 − j 0.3559
110.0/ − 55.0
[Isabc ] = [YM abc ] ⋅ [VLLabc ] = 126.6/179.7
109.6/54.6
273.2/ − 30.7
[VLN abc ] = [W ] ⋅ [VLLabc ] = 281.9−150.4
279.1/87.9
For j = 1, 2, 3
27.4 + j 12.4
( )
*
VLN abc j ⋅ Isabc j
Ss j = = 30.9 + j 17.8
1000 25.6 + j 16.8
Note that these are the same results as in Example 9.3, and only fewer
steps are required.
Load Models 353
Example 9.5
Determine the voltage and current unbalances for the motor in
Examples 9.2 and 9.3.
The terminal line-to-line voltages were:
480/0
[VLLabc ] = 490/ − 121.4
475/118.3
3
Step 1: Vaverage =
1
⋅∑
3 k =1
VLLabc k = 481.7
1.67
Step 2: dev i = VLLi − Vaverage = 8.33
6.67
max(dev ) 8.33
Step 3: Vunbalance = = ⋅ 100 = 1.73%
Vaverage 481.7
The line currents were:
110.0/ − 55.0
[Isabc ] = 126.6/179.7
109.8/54.6
354 Distribution System Modeling and Analysis
Step 1: I average = ⋅
1
3 ∑ Is
k =1
abc k = 115.4
5.39
Step 2: dev i = Isabc i − I average = 11.20
5.82
max(dev ) 11.20
Step 3: I unbalance = I =
115.4
⋅ 100 = 9.71%
average
596.4/ − 97.5
[ Isabc ] = 615.3/142.8
609.2/21.1
When the starting voltage is reduced to one-half, the starting currents are:
298.2/ − 97.5
[ Isabc ] = 307.7/142.8
304.6/21.1
+ Is0 = 0 Ir0 = 0 +
Vs0 = 0 Vr0 = 0
Im0 = 0 −
−
Zero sequence network
Z s1 Zr1
+ Is1 Ir1 +
Vs1 Z m1 Vr1
Im1
− −
Positive sequence network
Zs2 Zr2
+ Is2 Ir2 +
FIGURE 9.6
Induction machine equivalent T sequence networks.
[Zs012] [Zr012]
+ +
[Is012] [Ir012]
[Vs012] [Zm012] [Vr012]
[Im012] −
−
FIGURE 9.7
Sequence equivalent T circuit.
Because the zero sequence voltages and currents are always zero in
Figure 9.7, the sequence matrices are defined as:
0 0
Voltages: [Vs 012 ] = Vs1 [Vr012 ] = Vr1
Vs 2 Vr2
356 Distribution System Modeling and Analysis
0 0 0
Currents: [ Is 012 ] = Is1 [ Im012 ] = Im1 [ Ir012 ] = Ir1
Is 2 Im2 Ir2
0 0 0 0 0 0
Impedances: [ Zs 012 ] = 0 Zs1 0 [ Zr012 ] = 0 Zr1 0
0 0 Zs 2 0 0 Zr2
(9.53)
0 0 0
[ Zm012 ] = 0 Zm1 0
0 0 Zm2
The sequence voltage drops in the rotor circuit of Figure 9.7 are:
[vr012 ] = [ Zr012 ] ⋅ [ Ir012 ] (9.54)
As an example, the rotor phase voltage drops are given by:
[ Zrabc ] = [ A ] ⋅ [ Zr012 ] ⋅ [ A ]−1
The same process is used on the other voltage drops, so that the circuit of
Figure 9.7 can be converted to an equivalent T circuit in terms of the phase
components (Figure 9.8).
The stator voltages and currents of the phase equivalent T circuit as a
function of the rotor voltages and currents are defined by:
Vs Vr
[ abc ] = [ Amabc ] [Bmabc ] ⋅ [ abc ] (9.56)
[ Isabc ] [Cmabc ] [Dmabc ] [ Irabc ]
Load Models 357
where
3 (9.58)
or: Pconv = ∑Vr abc k ⋅ ( Irabc k )
*
k =1
[Zsabc] [Zrabc]
+ +
[Isabc] [Irabc]
[Vsabc] [Ymabc] [Vrabc]
− [Imabc] −
−1
where [Ymabc] = [Zmabc]
FIGURE 9.8
Phase equivalent T circuit.
358 Distribution System Modeling and Analysis
Vs *
abc k ⋅ ( Isabc k )
3
S in = ∑
k =1
1000
= Pin + jQ in kW + jkvar (9.62)
Example 9.6
For the motor in Example 9.2, determine:
1
For: Ymi = = − j 0.16
Zmi
0 0 0 0 0 0
[Zs 012 ] = 0 Zs 1 0 = 0 0.1 + j 0.2499 0
0 0 Zs 2 0 0 0.1 + j 0.2499
Load Models 359
0 0 0 0 0 0
[Zr012 ] = 0 Zr1 0 = 0 0.0849 + j 0.175 0
0 0 Zr2 0 0 0.0849 + j 0.175
0 0 0 0 0 0
[ 012 ] 0
Ym = Ym1 0 = 0 − j 0.16 0
0 0 Ym2 0 0 − j 0.16
Compute the phase impedance and admittance matrices:
245.3/ − 39.7
[Vrabc ] = [Dmabc ] ⋅ [Vsabc ] − [Bmabc ] ⋅ [Isabc ] = 244.7/ − 159.5
245.6/80.5
103.7−33.4
[Irabc ] = − [Cmabc ] ⋅ [Vsabc ] + [Amabc ] ⋅ [Isabc ] = 115.2/ − 161.6
96.2/76.3
Compute the rotor converted and shaft powers:
*
3
(
Vrabc k ⋅ Irabc k )
Pconv = ∑
k =1
1000
= 77.03 kW
29.6/13.2
Vdrops = [ Zsabc ] ⋅ [ Isabc ] = 34.1/ − 112.1
29.5/122.8
Vdrops k ⋅ ( Isabc k )
3 *
Ps =Re ∑
k =1
1000
= 4.01 kW
20.2/30.7
Vdropr = [ Zrabc ] ⋅ [ Irabc ] = 22.4/ − 97.5
18.7/140.4
Vdropr k ⋅ ( Irabc k )
3 *
Pr = Re ∑k =1
1000
= 2.83 kW
Compute complex power into stator:
*
Vsabc k ⋅ ( Isabc k )
3
S in =∑ k =1
1000
= 83.87 + j 47.00
9.5.7 Computation of Slip
When the input power to the motor is specified instead of the slip, an
iterative process is required to compute the value of slip that will force the
input power to be within some small tolerance of the specified input power.
The iterative process for computing the slip that will produce the specified
input power starts with assuming an initial value of the positive sequence
slip and a change in slip. To compute the slip the initial values are:
sold = 0.0
(9.63)
ds = 0.01
If the error is positive, the slip needs to be increased so that the computed
power will increase. This is done by:
The new value of s1 is used to repeat the calculations for the input power to
the motor.
If the error is negative, it means that a bracket has been established. The
required value of slip lies between sold and s new . In order to zero in on the
required slip, the old value of slip will be used, and the change in slip will
be reduced by a factor of 10.
ds
ds =
10 (9.67)
s i = sold + ds
362 Distribution System Modeling and Analysis
0.04
0.03
Slip
0.02
0.01
0.00
1 2 3 4 5 6 7 8 9 10
Iteration
FIGURE 9.9
Slip vs. iteration.
Example 9.7
For the induction motor and voltages in Example 9.2, determine the value
of positive sequence slip that will develop 100 kW input power to the motor.
To start set:
sold = 0
ds = 0.01
tol = 0.01
Pspecified = 100
Figure 9.10 shows a Mathcad program that computes the required slip.
After 22 iterations, the Mathcad program gives the following results.
s 1 = 0.0426
S total = 100.00 + j 52.54
Error = 0.004
9.5.8 Induction Generator
Three-phase induction generators are becoming common as a source of
distributed generation on a distribution system. In particular, Windmills
generally drive an induction motor. It is, therefore, important that a simple
model of an induction generator be developed for power-flow purposes.
In reality, the same model as that which was used for the induction motor
Load Models 363
X := for n 1 .. 200
s1 sold + ds
s2 2 – s1
for i 1..2
1 – si
RLi Rr
si
Zmi Zri
ZMi Zsi +
Zmi + Zri
1
YMi
ZMi
1 0 0
0 YM1 0
YM012
0 0 YM2
for i 1..3
Vsabci Isabci
Sabc
i
1000
3
Stotal Sabck
k=1
Pcomputed Re Stotal
ds
ds if Pcomputed > Pspecified
10
sold s1
Out1 s1
Out2 Stotal
Out3 Error
Out
FIGURE 9.10
Mathcad program for computed required slip.
364 Distribution System Modeling and Analysis
is used for the induction generator. The only change is that the generator
will be driven at a speed in excess of synchronous speed, which means that
the slip will be a negative value. The generator can be modeled with the
equivalent admittance matrix from Equation 9.46.
Example 9.8
Using the same induction machine and line-to-line voltages in Examples
9.2 and 9.4, determine the slip of the machine so that it will generate
100 kW. Because the same model is being used with the same assumed
direction of currents, the specified power at the terminals of the machine
will be:
Pgen = −100
As before, the initial “old” value of slip is set to 0.0. However, because the
machine is now a generator, the initial change in slip will be:
ds = −0.01
As before, the value of slip to be used for the first iteration will be:
s 1 = sold + ds = −0.01
The same Mathcad program as that which was used in Example 9.7 is
used with the exception that the two “if” statements are reversed in
order to determine the new value of slip. The two equations changed are:
ds
ds ← if Pcomputed < Pspecified
10
s 1 = −0.03997
S computed = −99.99 + j 59.73 kW + jkvar
Error = 0.0084
It must be noted that even though the machine is supplying power to the
system, it is still consuming reactive power. The point being that even
though the induction generator can supply real power to the system, it
will still require reactive power from the system. This reactive power
is typically supplied by shunt capacitors or a static kvar supply at the
location of the Windmill.
Load Models 365
−1 −1
[ Irabc ] = − [Dmabc ] ⋅ [Cmabc ] ⋅ [Vrabc ] + [Dmabc ] ⋅ [ Isabc ] (9.69)
(
Define: [Ethabc ] = [ Amabc ] − [Bmabc ] ⋅ [Dmabc ] ⋅ [Cmabc ] ⋅ [Vrabc ]
−1
)
[ Zthabc ] = [Bmabc ] ⋅ [Dmabc ]
−1
The final form of Equation 9.70 reduces the T circuit to the Thevenin
equivalent circuit of Figure 9.12.
In Figure 9.12, the Thevenin voltage drops are:
[Zsabc] [Zrabc]
+ [Irabc] +
[Isabc]
[Vsabc] [Ymabc] [Vrabc]
[Imabc]
− −
FIGURE 9.11
Induction motor phase equivalent T circuit.
366 Distribution System Modeling and Analysis
Zthaa
+ − Ia +
Etha
Zthca −
Vsab
Vsbc
− −
+ Zthcc
+ Ethc Ethb +
− Zthab Ic
Vsbc Zthbc
− + Zthbb
Ib
FIGURE 9.12
Motor Thevenin equivalent circuit.
1 −1 0 va va − vb
Note that: 0 ⋅ v
1 −1 b = vb − vc
−1 0 1 v c vc − va
Apply the matrix [Dv ] :
Vsab 1 −1 0 Etha 1 −1 0 va
⋅ Eth ⋅ v
Vsbc = 0 1 −1 b + 0 1 −1 b
Vsca −1 0 1 Ethc −1 0 1 v c
Vsab 1 −1 0 Etha 1 −1 0
⋅ Eth ⋅
Vsbc = 0 1 −1 b + 0 1 −1
Vsca −1 0 1 Ethc −1 0 1
where
Example 9.9
Use the computed rotor voltages and stator currents from Example 9.3
and the ABCD matrices from Example 9.6 and compute the Thevenin
equivalent terminal line-to-line voltages and Thevenin equivalent
matrix.
From Example 9.3:
238.6/ − 38.9
[Ethabc ] = ([ Amabc ] − [Bmabc ] ⋅ [Dmabc ] ⋅ [Cmabc ])
−1
⋅ Vr abc = 238.1/ − 158.8
238.8/81.3
368 Distribution System Modeling and Analysis
1 −1 0
[ ] 0
Dv = 1 −1
−1 0 1
412.6/ − 8.9
[EthLLabc ] = [Dv ] ⋅ [Ethabc ] = 412.9/ − 128.7
413.8/111.2
480/0
[VmLLabc ] = [EthLLabc ] + [ZthLL ] ⋅ [Isabc ] = 490/ − 121.4
475/118.3
The preferred and the most common method of connecting the motor to the
distribution feeder is through a three-wire secondary and an ungrounded
wye–delta transformer bank. This connection is shown in Figure 9.13.
In Figure 9.13, the voltage drops in the induction motor and secondary
are shown rather than the impedances. For short-circuit studies, it is desired
to develop a Thevenin equivalent circuit at the primary terminals of the
ungrounded wye–delta transformer bank. The resulting primary Thevenin
circuit is shown in Figure 9.14.
The equivalent impedance matrix between the motor and the secondary
terminals of the transformer is given by:
Carson’s equations and the length of the secondary are used to define the
3 × 3 secondary phase impedance matrix as:
vIa vtha
+ IA + − +
Ia
ab
+ −
Zt
FIGURE 9.13
Ungrounded wye–delta with secondary connected to induction motor.
ZthAA
−
+ +
IA
EthA
ZthAB
VAB
ZthCA −
VCA − EthC
IB ZthBB − +
−
+ EthB
+
VBC Ic ZthBC
+ −
ZthCC
FIGURE 9.14
Primary Thevenin circuit.
370 Distribution System Modeling and Analysis
Zl Zl ab Zl ac
aa
[ Zlabc ] = Zlba Zl bb Zl bc (9.75)
Zl Zl cb Zl cc
ca
Zt 0 0
ab
[ Zt abc ] = 0 Zt bc 0 (9.76)
0 0 Zt ca
The voltage drops including the secondary lines and the motor are:
[v abc ] = Zeq abc ⋅ [ I abc ] (9.77)
The line-to-line voltages at the secondary terminals of the transformer
bank are:
[VLLabc ] = [EthLLabc ] + Zeq LL ⋅ [ I abc ]
where
I
A
[ I ABC ] = I B (9.79)
IC
Load Models 371
In Chapter 8, the currents flowing inside the delta secondary windings were
defined as:
−1
[ ID abc ] = [ AI ] ⋅ [ I ABC ] (9.80)
where
I ba
[ IDabc ] = I cb
I ca
1 0 0
1
[ AI ] = ⋅ 0 1 0
nt
0 0 1
kVLN high
nt =
kVLLlow
The secondary line currents as a function of the primary line currents are:
where
1 0 −1
[Di ] = −1 1 0
0 −1 1
[VLLabc ] = [EthLLabc ] + Zeq LL ⋅ [Di ] ⋅ [ AI ]−1 ⋅ [ I ABC ]
372 Distribution System Modeling and Analysis
Vt v Zt 0 0 I
ab
ab ab
ab
Vt bc = v bc +
0 Zt bc 0 ⋅ I bc
Vt ca v ca 0 0 Zt ca I ca
−1
[Vt abc ] = [VLLabc ] + [ Zt abc ] ⋅ [ AI ] ⋅ [ I ABC ]
−1
[VLLabc ] = [EthLLabc ] + [ Zeq LL ] ⋅ [Di ] ⋅ [ AI ] ⋅ [ I ABC ]
where
Load Models 373
[ ZthABC ] = [ AV ] ⋅ ([Dv ] ⋅ Zeq abc ⋅ [Di ] + [ Zthabc ]) ⋅ [ AI ]−1
Example 9.10
For the system in Figure 9.13, the ungrounded wye–delta transformer
bank consists of three single-phase transformers each rated:
The impedance matrix for the transformer bank relative to the 480-V
side is:
0.0507 + j 0.0829 0 0
[Zt abc ] = 0 0.0507 + j 0.0829 0 Ω
0 0 0.0507 + j 0.0829
12470/0
[VLLABC ] = 11850/ − 118 V
12537/123.4
7340.4/ − 28.4
[VLN ABC ] = [W ] ⋅ [VLLABC ] = 6949.6/ − 149.9 V
6989.6/93.7
A simple Mathcad routine was run to compute the stator and rotor
voltages and currents with the following results:
Vrabc k ⋅ Irabc k *
3
Srabc = ∑ 1000
= 65.4 kW
k =1
The ABCD matrices for the motor are those computed in Example 9.6.
The Thevenin equivalent voltages and currents are:
218.7/ − 67.4
[Ethabc ] = ([Amabc ] − [Bmabc ] ⋅ [Dmabc ] ⋅ [Cmabc ]) ⋅Vrabc
−1
= 219.5/172.4
220.9/52.3
258.1/ − 58.3
[Vsabc ] = [Ethabc ] + [Zthabc ] ⋅ [Isabc ] = 259.9/ − 179.0
250.8/59.9
These voltages match those from the power-flow program, which
confirms the accuracy of the Thevenin equivalent circuit for the motor.
From Equations 9.78 and 9.85, the Thevenin equivalent voltages and
currents on the primary side of the transformer bank are:
5699.3/ − 37.4
[EthABC ] = [AV ] ⋅ [Dv ] ⋅ [Ethabc ] = 5722.9/ − 157.5
5702.8/82.3
9.6 Summary
This chapter has developed load models for typical loads on a distribution
feeder. It is important to recognize that a combination of constant PW, con-
stant Z, and constant current loads can be modeled using a percentage of
each model. An extended model for a three-phase induction machine has
been developed with examples of the machine operating as a motor and as
a generator. An iterative procedure for the computation of slip to force the
input power to the machine to be a specified value was developed and used
in examples for both a motor and a generator. Thevenin equivalent circuits
376 Distribution System Modeling and Analysis
have been developed for an induction motor. The Thevenin circuit is used to
develop a Thevenin equivalent circuit at the primary terminals of the step-
down transformer feeding the secondary and the induction motor. This final
Thevenin circuit is used in Chapter 10 on short-circuit analysis.
Problems
9.1 A 12.47-kV feeder provides service to an unbalanced wye-connected load
specified to be:
a. Compute the initial load currents, assuming the loads are modeled
as constant complex power.
b. Compute the magnitude of the load currents that will be held
constant, assuming the loads are modeled as constant current.
c. Compute the impedance of the load to be held constant, assuming
the loads are modeled as constant impedance.
d. Compute the initial load currents, assuming that 60% of the
load is complex power, 25% constant current, and 15% constant
impedance.
9.2 Using the results of Problem 9.1, rework the problem at the start of
the second iteration if the load voltages after the first iteration have been
computed to be:
6851/ − 1.9
[VLN abc ] = 6973/ − 122.1 V
6886/117.5
9.3 A 12.47-kV feeder provides service to an unbalanced delta-connected
load specified to be:
a. Compute the load and line currents if the load is modeled as constant
complex power.
b. Compute the magnitude of the load current to be held constant if the
load is modeled as constant current.
c. Compute the impedance to be held constant if the load is modeled as
constant impedance.
d. Compute the line currents if the load is modeled as 25% constant
complex power, 20% constant current, and 55% constant impedance.
9.4 After the first iteration of the system in Problem 9.5, the load voltages are:
11, 981/28.3
[VLLabc ] = 12, 032/ − 92.5 V
11, 857/147.7
a. Compute the load and line currents if the load is modeled as constant
complex power.
b. Compute the load and line currents if the load is modeled as constant
current.
c. Compute the load and line current if the load is modeled as constant
impedance.
d. Compute the line currents if the load mix is 25% constant complex
power, 20% constant current, and 55% constant impedance.
25 Hp, 240 V
Zs = 0.0336 + j0.08 pu
Zr = 0.0395 + j0.08 pu
Zm = j3.12 pu
The motor is operating with a slip of 0.03 with balanced three-phase voltages
of 240 V line-to-line. Determine the following:
a. The input line currents and complex three-phase input complex power
b. The currents in the rotor circuit
c. The developed shaft power in HP
9.6 The motor in Problem 9.5 is operating with a slip of 0.03, and the l ine-to-
line voltage magnitudes are:
378 Distribution System Modeling and Analysis
9.7 The motor of Problem 9.5 is operating with line-to-line voltages of:
a. Required slip
b. The input kW and kvar
c. The converted shaft power
9.9 The motor in Problem 9.8 is operating at a slip of 0.035 with line-to-line
input voltages of:
V 480.0/0
ab
[VLLabc ] = Vbc = 475.0/ − 121.5
Vca 466.7/119.8
[ Amabc ] , [Bmabc ] , [Cmabc ] , [Dmabc ]
b. For the results in Problem 9.9, determine:
i. The rotor currents and output voltages
ii. The rotor converted and shaft powers
iii. Rotor and stator “copper” losses
9.11 For the induction motor in Problem 9.8, determine the value of the
positive sequence slip that will develop 75 kW of input power to the motor.
9.12 The induction motor in Problem 9.9 is operating as a generator with a
positive sequence slip of −0.04. Determine the stator output complex power.
9.13 Using the results of Problem 9.10, determine the line-to-line motor
Thevenin voltages and Thevenin equivalent matrix.
9.14 The motor in Problem 9.8 is connected through a three-phase d
istribution
line to three single-phase transformers as shown in Figure 9.15.
The three-phase induction motor is that of Problem 9.8. The secondary
impedance matrix is:
12,470 – 480 V
1,000 ft
M
12.47 kV
Source
FIGURE 9.15
Simple system.
380 Distribution System Modeling and Analysis
References
1. Kersting, W. H. and Phillips, W. H., Phase frame analysis of the effects of voltage
unbalance on induction machines, IEEE Transactions on Industry Applications,
Vol. 33, pp. 415–420, 1997.
2. American national standard for electric power systems and equipment–
Voltage ratings (60 Hertz), ANSI C84.1-1995, National Electrical Manufacturers
Association, Rosslyn, Virginia, 1996.