Intellivac™ Contactor Control Module: Bulletin 1503Vc
Intellivac™ Contactor Control Module: Bulletin 1503Vc
Contactor
Control Module
Bulletin 1503VC
User Manual
Important User Information
Read this document and the documents listed in the Additional Resources section about installation, configuration, and
operation of this equipment before you install, configure, operate, or maintain this product. Users are required to
familiarize themselves with installation and wiring instructions in addition to requirements of all applicable codes, laws,
and standards.
Activities including installation, adjustments, putting into service, use, assembly, disassembly, and maintenance are required
to be carried out by suitably trained personnel in accordance with applicable code of practice.
If this equipment is used in a manner not specified by the manufacturer, the protection provided by the equipment may be
impaired.
In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from the
use or application of this equipment.
The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables and
requirements associated with any particular installation, Rockwell Automation, Inc. cannot assume responsibility or
liability for actual use based on the examples and diagrams.
No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits, equipment, or
software described in this manual.
Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell Automation,
Inc., is prohibited.
Throughout this manual, when necessary, we use notes to make you aware of safety considerations.
WARNING: Identifies information about practices or circumstances that can cause an explosion in a hazardous environment,
which may lead to personal injury or death, property damage, or economic loss.
ATTENTION: Identifies information about practices or circumstances that can lead to personal injury or death, property
damage, or economic loss. Attentions help you identify a hazard, avoid a hazard, and recognize the consequence.
IMPORTANT Identifies information that is critical for successful application and understanding of the product.
SHOCK HAZARD: Labels may be on or inside the equipment, for example, a drive or motor, to alert people that dangerous
voltage may be present.
BURN HAZARD: Labels may be on or inside the equipment, for example, a drive or motor, to alert people that surfaces may
reach dangerous temperatures.
ARC FLASH HAZARD: Labels may be on or inside the equipment, for example, a motor control center, to alert people to
potential Arc Flash. Arc Flash will cause severe injury or death. Wear proper Personal Protective Equipment (PPE). Follow ALL
Regulatory requirements for safe work practices and for Personal Protective Equipment (PPE).
Allen-Bradley, Rockwell Software, Rockwell Automation, and TechConnect are trademarks of Rockwell Automation, Inc.
Trademarks not belonging to Rockwell Automation are property of their respective companies.
Table of Contents
Product Description
Description (cont.)
Vacuum Contactor
External Trip Coil
Capacitor Coil
Current
(Optional) Power
Regulator
Input Supply
Feedback
Altitude
Aux. CC
c
Select
c
Drop-Out c
Select
c
Configuration Module
Contactor c Inputs Status
Select (DIP
c
c
Outputs
Status
switches)
c
c
TDUV
Time c
Select Contactor
c
Interface
Safety
c
IntelliVAC Features
A wide range of supply voltage (110 – 240 V AC 50/60 Hz,
110 - 250 V DC) allows implementation in multiple applications
Consistent vacuum contactor pick-up time (at a given supply
voltage) ensures repeatable performance
Selectable vacuum contactor drop-out time improves
coordination with upstream power fuses
Electronic altitude compensation (400 A only) eliminates
mechanical compensation required for altitudes above 1,000
meters (800 A contactors include a user-friendly altitude
adjustment)
Power loss ride-through (TDUV) allows the vacuum contactor
to remain closed during short power loss (may require an
optional external capacitor, dependant on ride-through time)
IntelliVAC Versions
Configuration
IntelliVAC is easily configured for a wide variety of medium
voltage motor and feeder control applications. It is configured
using DIP switches, located within the enclosure (front side).
Please refer to Chapter 4 for information.
Firmware
IntelliVAC has firmware stored in flash EEPROM; therefore, this
may be updated in the field (if necessary). The IntelliVAC board
firmware is updated using the mini-DIN connector, which is
accessible inside the enclosure.
TA = Ambient Temperature
Refer to Chapter 6 for suitable EMC filter needed to meet CE requirements.
Also refer to Chapter 3 for EMC filter installation guidelines.
Please consult Factory for DC input current ratings.
Includes idle current.
\ Ensure compatibility of IntelliVAC input ratings with those of circuit components activating these inputs.
Consider means of isolating/loading these signals, as required (using interposing relays or load resistors.)
Consult factory for assistance, if needed.
5.1 (0.20)
29.7 165.9 (6.53)
(1.17)
5.8 (0.228)
2 places
174.8
(6.88)
185.3
(7.29)
59.4
(2.34) Dimensions in mm (inches)
Receiving Upon receiving the controller, remove the packing and check for
damage that may have occurred during shipping. Report any
damage immediately to the claims office of the carrier.
General Precautions In addition to the precautions listed throughout this manual, the
following statements, which are general to the system, must be read
and understood.
OEM
38.1
(1.50)
Dimensions in mm (inches)
38.1
6.4 (0.25)
(1.50)
Arrangements (cont.)
CONTROL POWER
*
CONTROL M-INTELLIVAC
POWER
FUSE 7 + - 8
OPEN
9 + - 10
CLOSE
OVERLOAD START
STOP
16 CONTACTOR
STATUS
15
MODULE 14
STATUS
13
CAPACITOR
(OPTIONAL)
1 - 4
EC TCO
2 + 3
MOV
M
11 6 M
AUX CCO
12 5
CONFIGURATION
DIP SWITCHES
INPUT POWER
L1 G L2/N
CONTROL POWER
M-INTELLIVAC
*
CONTROL
POWER 7 + - 8
OPEN
FUSE
9 + - 10
CLOSE
OVERLOAD START
STOP
16 CONTACTOR
STATUS
15
MODULE 14
STATUS
13
CAPACITOR
(OPTIONAL)
1 - 4
EC TCO
2 + 3
MOV
M
11 6 M
AUX CCO
12 5
CONFIGURATION
DIP SWITCHES
INPUT POWER
L1 G L2/N
Connections There are three green connectors on the IntelliVAC module for
connections to the control circuitry. Connector plugs are provided
with the module. If additional plugs are required, refer to Chapter 6,
Spare parts.
Control Power
Status Relays
Status relay connections are accessed with a four-pole connector
located at the bottom front portion of the module. Refer to Figure
3.5 or 3.6 for connections. There are two status relays, each with one
normally-open contact:
13 14 15 16 L1 L2/N
CONTACTOR STATUS OUTPUT (N.O.) MODULE STATUS OUTPUT (N.O.) POWER INPUT
Ground Connection
13 14 15 16 L1 L2/N
CONTACTOR STATUS OUTPUT (N.O.) MODULE STATUS OUTPUT (N.O.) POWER INPUT
Interface Connections
All other control interface connections are made at a twelve-pole
connector located on the top of the module. Refer to Figure 3.7 or
3.8 and Table 3.B for connections. Refer to the Wiring Guidelines
section in this chapter for guidance in making connections to the
control circuit.
1 2 3 4 5 6 7 8 9 10 11 12
EX. CAP. CONTACTOR INTERFACE
Ground Connection
1 2 3 4 5 6 7 8 9 10 11 12
EX. CAP. CONTACTOR INTERFACE
9 Close command Z
Input to initiate the closure of electrically
held & mechanical latch contactors
10 Close command (common) Z
Wiring Guidelines The IntelliVAC can be applied with two- or three-wire control
Electrically Held circuits. The control system utilized will determine the configuration
Contactors of the input wiring. Consider the following input and output for the
type of control used:
Note:
1. When used with electrically held contactors, the IntelliVAC
allows close commands every six seconds. This is to ensure the
rated contactor duty cycle is not exceeded.
2. If a contactor close command is applied and then removed in less
than 500 milliseconds the IntelliVAC may fault. To clear the
fault, module power has to be removed and reapplied.
3. If IntelliVAC powers up configured for an electrically held
contactor, and the vacuum contactor is detected as being closed,
the module will not respond to a close command until the vacuum
contactor auxiliary contact input is in the correct (open) state and
module power is removed and re-applied. (See Chapter 5). This
is true if the power-up safety DIP switch is enabled.
4. In general, a Close command should only be applied 4 seconds
after energizing IntelliVAC.
Two-Wire Control
CONTROL POWER
CAPACITOR
(OPTIONAL) M-IV
*
CONTROL
1 -
EC TCO
4
POWER 2 + 3
FUSE MOV
M
11 6 M
AUX CCO
12 5
L1 G L2/N
M-IV
OVERLOAD RUN
9 + - 10
CLOSE
∗ Refer to Table 3.A for recommended fuse sizing.
CONTROL POWER
CAPACITOR
(OPTIONAL) M-IV
*
CONTROL
1 -
EC TCO
4
POWER 2 + 3
FUSE MOV
M
11 6 M
AUX CCO
12 5
L1 G L2/N
START M-IV
OVERLOAD STOP
9 + - 10
M-IV CLOSE
15 16
∗ Refer to Table 3.A for recommended fuse sizing.
CONTACTOR
STATUS
15mS
CLOSE COMMAND DEBOUNCE
TO MICRO
15mS 80mS
SELECTABLE DROP
DEBOUNCE Y OUT TIME
5mS (0 TO 190mS)
MICRO OUTPUT CLAMP DELAY
TO CLOSE COIL 200mS
CLOSE LEVEL OF
CURRENT TO CLOSE
COIL ACKNOWLEDGE 60mS
WINDOW
CONTACTOR STATUS X
RELAY OUTPUT
MODULE STATUS
RELAY OUTPUT CONTACTOR PICK UP
90mS NATURAL
CONTACTOR 30mS
DROP OUT
(@120VAC)
CONTACTOR
AUXLIARY
INPUT TO MICRO
X Contact status relay closes on request to close. It will open if the contactor auxiliary contact does not close within 200 milliseconds and
module will fault (opening module status relay).
Y For this example, the 130 millisecond drop-out time has been selected. The base drop-out time is 50 milliseconds. The microcontroller delay is
130-50=80 milliseconds.
Wiring Guidelines IntelliVAC control may be used for mechanically latched contactors.
Mechanically Latched A momentary control signal is needed to close the contactor, and a
second momentary control signal is needed to open the contactor.
Contactors
The momentary open/close commands must be at least 50
milliseconds in duration.
Refer to Figure 3.12 for a typical mechanical latch control scheme.
Note:
1. A mechanically latched contactor may already be closed when
power is applied to the IntelliVAC control module.
2. It is permissible to apply an open command to the IntelliVAC
module as power is re-applied.
CONTROL POWER
M
MOV
M-IV
*
CONTROL
1 -
EC TCO
4 TC
POWER 2 + 3
FUSE
MOV
M
11 6 CC
AUX CCO
12 5
L1 G L2/N
CLOSE M-IV
9 + - 10
CLOSE
OPEN M-IV
7 + - 8
OVERLOAD OPEN
CONTROL POWER
OPEN M-IV
7 + - 8
OVERLOAD OPEN
*
CONTROL
POWER
FUSE
M
MOV
CAPACITOR M-IV
1 - 4 TC
EC TCO
2 + 3
MOV
M
11 6 CC
AUX CCO
12 5
L1 G L2/N
CLOSE M-IV
9 + - 10
CLOSE
∗ Refer to Table 3.A for recommended fuse sizing.
Motor Jogging Control When used with electrically held contactors, the IntelliVAC allows
close commands every six seconds. This is to ensure the rated
contactor duty cycle of 600 operations per hour is not exceeded.
CONTROL POWER
M-IV
*
CONTROL
1 -
EC TCO
4
POWER 2 + 3
FUSE MOV
M
11 6 M
AUX CCO
12 5
L1 G L2/N
START M-IV
OVERLOAD STOP
9 + - 10
M-IV CLOSE
15 16
CONTACTOR
STATUS
JOG M-IV
7 + - 8
OPEN
* Refer to Table 3.A for recommended fuse sizing.
Time Delay Undervoltage The IntelliVAC can be configured to provide time delay undervoltage
(TDUV) protection. The feature is available to keep electrically held
contactors closed during a voltage dip or brief power loss. This
option may require the addition of a capacitor (see below). Refer to
Chapter 6 for typical capacitor sizing. The capacitor is connected to
terminals 1(-) and 2(+) of the IntelliVAC. (Refer to Figure 3.15.)
Table 4.B of the “Setup and Commissioning” chapter has the dip
switch settings to provide TDUV from 0.2 to 2 seconds. IntelliVAC
can provide TDUV protection without the use of an external
capacitor, as shown in Table 3.D.
If the undervoltage condition persists beyond the set delay time, the
contactor will be opened and an undervoltage fault condition will occur.
CONTROL POWER
CAPACITOR M-IV
*
CONTROL
1 -
EC TCO
4
POWER 2 + 3
FUSE MOV
M
11 6 M
AUX CCO
12 5
L1 G L2/N
START M-IV
OVERLOAD STOP
9 + - 10
M-IV CLOSE
∗ Refer to Table 3.A for recommended fuse sizing. 15 16
CONTACTOR
STATUS
Interface Connections
DIP Switches
Ground Stud (Series B)
Status Relay Outputs
Supply Power Input
Internal Control Fuse
UP = 1
DIP switch SW1
DOWN = 0
1 2 3 4 5 6 7 8 9 10 11 12
| | | |
Altitude X 1 2 3 12 Power-Up Safety Y
-1000 to 0 0 0 0 0 Enable
1 to 1000 0 0 1 1 Disable
1001 to 2000 0 1 0
2001 to 3000 0 1 1 10 11 Ext. cap. TDUV time
3001 to 4000 1 0 0 0 0 0.2 sec
4001 to 5000 1 0 1 0 1 0.5 sec
Not defined 1 1 0 1 0 1.0 sec
Not defined 1 1 1 1 1 2.0 sec
9 TDUV config.
0 No TDUV
Drop out time Z 4 5 6 1 TDUV Enabled
50 msec 0 0 0
75 msec 0 0 1 7 8 Contactor Config.
100 msec 0 1 0 0 0 400A Mech. Latch
130 msec 0 1 1 0 1 400A Elec. Held
150 msec 1 0 0 1 0 800A Mech. Latch
175 msec 1 0 1 1 1 800A Elec. Held
200 msec 1 1 0
240 msec 1 1 1
X The altitude compensation by DIP switch settings applies to Series E 400 amp vacuum contactors only. All 800 amp contactors are adapted
for altitude by altering the return springs. 800 amp contactors are to be set for 1 to 1000m (001 DIP setting).
Y Available with IntelliVAC using version 2.001 firmware or newer.
Z By-pass contactors in MV SMC applications must be set for 50 millisecond drop-out time.
Refer to Appendix A for typical drop-out time settings used when power fuses are provided by Rockwell Automation.
Introduction The IntelliVAC module has two light emitting diodes (LEDs) and
relay outputs to indicate the status of the contactor and the module.
The LEDs are visible on the front of the module and the relay
outputs are accessed on the bottom front of the module.
Module Status The Module Status is indicated with a Green LED if the module is
functioning properly and has a valid configuration. If the module
powers up with an invalid configuration the LED will be Red,
indicating a Fault condition which will not allow the contactor to
close. If the module powers up properly and experiences an
undervoltage condition when attempting to close the contactor or
while the contactor is closed, the LED will be Red (Fault). If the
contactor does not close properly, a Fault is generated, the LED turns
Red, and inputs are inhibited until the module power is removed and
reapplied. If the processor has an internal fault, the LED will be Red,
the outputs will be cleared, and the processor will be reset. If the
reset is successful, the LED will be Green and the module will respond
to the control inputs. The input command must be toggled before the
module will respond to a new command (rising edge triggered).
Module Status output relay has a normally open contact. The contact
is open during a Fault condition (LED red), and closed during a
healthy condition (LED green).
Series B Design
Additional module states are indicated with the LED as per Table 5.B.
Contactor Status The Contactor Status is indicated with a yellow LED that is off until
a CLOSE command is received. The LED will stay on if the
contactor closes properly, until the contactor is opened.
Series B Design
Additional module states are indicated with the LED as per Table 5.B.
Spare Parts
Multi-pole connectors:
2 pole (module power) 80174-014-01-R
4 pole (status outputs) 80174-014-03-R
12 pole (coil and I/O connections) 80174-014-11-R
Optional Equipment
TDUV Capacitor*
For 110/120V AC control (1650 µF) 80158-779-51-R
For 220/240V AC control (330 µF) 80158-779-52-R
*Includes mounting bracket and terminal guards
EMC Filter
Schnaffer (FN 670-10/06) 80026-430-01-R
The contactor drop-out times shown in the following table are typical
values used when the power fuses are provided as part of a complete
MV controller from Rockwell Automation. The recommendations
are based on Ferraz Shawmut power fuses. Other fuse types may
require alternate drop-out time settings.
Note: The drop-out time is chosen to be equal to or greater than the intersection of the rated
contactor interrupting current and the fuse melt time curve (except where noted *)