Grid Solutions
Reason RT430/RT434
GPS Precision-Time Clock
Technical Manual
Platform Hardware Version: A
Platform Software Version: 08
Publication Reference: RT430-RT434-GPS-TM-EN-HWA-8v4
imagination at work
Contents
Table of Figures 7
List of Tables 9
Chapter 1: Introduction 11
1 Foreword 11
Target Audience 11
Acronyms and abbreviations 11
2 Product Scope 13
3 Available Models 13
4 Key Features 13
PTP / SNTP / NTP 15
Parallel Redundancy Protocol (PRP) 15
Stationary Mode 15
Time Sync Flexibility 15
Environmental Robustness 16
5 Functional Overview 17
6 Standards Compliance 17
Chapter 2: Safety Information 18
1 Health and Safety 18
2 Symbols 18
3 Installation, Commissioning and Servicing 19
Lifting Hazards 19
Electrical Hazards 19
Fusing Requirements 21
Equipment Connections 21
Pre-energization Checklist 22
Peripheral Circuitry 23
Upgrading/Servicing 23
4 Lithium Battery 24
5 Decommissioning and Disposal 25
Chapter 3: Hardware Design 26
1 Front View 26
2 Rear View 26
3 Network Ports 27
4 Power Supply 27
Chapter 4: Installation 28
1 Unpacking 28
Normal Use of the Equipment 28
External Indications 28
2 Mounting 29
Power Supply 29
Grounding (Earthing) 30
GPS Antenna Terminal 30
TTL Electrical Outputs 32
Open-Collector Electrical Outputs 33
Optical Outputs 34
Amplitude Modulated Output 34
Serial Port (RS232, RS422/485) 34
Dry-Contact Relay 35
Event Input 36
Euro Type Connections 36
3 Ethernet Communication 37
Factory default settings 37
Network port and communication protocols 38
Equipment access 39
4 Powering Up 39
5 Preventive Maintenance Actions 39
Preventive Actions 40
Chapter 5: Operation 42
1 Local Interface (HMI) 42
2 Web Interface (Remote Access) 43
Web Interface Language 43
3 Monitoring Menus – Web Interface 44
Status 44
General Information 45
Event Log 45
Chapter 6: Configuration 47
1 Web Interface 47
User Name and Password 47
Sending Configuration 47
2 Ethernet 48
PRP (only in RT430) 48
Ethernet Ports 49
Default Gateway 49
DNS Server 49
Ethernet - Configuration Summary 49
3 Time Settings 50
Time Parameters 50
Network Time Protocol (NTP) 51
Time Settings - Configuration Summary 51
4 Time Signals 52
Outputs 53
Serial datagram 54
Customizable datagrams 55
Time Signals - Configuration Summary 56
5 PTP Configuration 58
Profile 58
Comparison between PTP Power Profiles 60
Domain number 60
Network protocol 60
Operation mode 60
Delay mechanism 61
Grandmaster Priority 61
PTP Messages 61
PTP - Configuration Summary 61
6 Setup 63
Configuration Management 64
Password configuration 64
Reset Satellites Almanac 64
Stationary Mode 64
Demo mode 64
Log Files 65
Reboot System 65
Chapter 7: Maintenance 66
1 Time Synchronization Failure (Locked Signaling) 66
Locked indicator (HMI) 66
Remote monitoring (Web Interface) 67
Dry-contact relay (Locked) 67
IRIG-B Signal 67
PTP Protocol 67
NTP Protocol 67
SNTP Protocol 67
2 Firmware Update 67
3 Equipment Upgrade - Key Change 68
4 Cleaning Instructions 69
5 Equipment Return 69
Chapter 8: Technical Specification 71
1 Power Supply 71
2 GPS Antenna 71
GPS Antenna Receiver 71
GNSS Antenna Type 72
Antenna Cable 72
Surge Arrester 73
3 Internal Oscillator 73
4 Outputs 73
Connectors 73
TTL Level Electrical Outputs 75
Open Collector Electrical Outputs 75
Optical Outputs 76
Amplitude Modulated Output 76
Serial Port (RS232, RS422/485) 77
5 Dry-contact Relay 77
6 Event Input 77
7 Precision Time Protocol PTP (IEEE 1588) 78
8 Ethernet Ports 78
9 Environment 79
10 Type Test 79
11 Dimensions, Weight 82
Chapter 9: Ordering Options 83
1 RT430 GPS Cortec 84
2 RT434 GPS Cortec 85
Chapter 10: Appendixes 87
Appendix A – IRIG-B Standard Summary 87
Appendix B – PTP Standard Concepts (IEEE1588) 92
Description 92
Definitions according to IEEE 1588 Standard 92
Hierarchical Topology 93
Multicast and Unicast Networks 93
PTP Synchronization 94
Network protocols 95
Clock operation mode 95
Delay measurement mechanism 95
Master, Slave and Grandmaster clocks 96
PTP Messages 96
Appendix C – Serial Datagrams 97
ACEB Datagrams 97
NEMEA GPZDA Datagram 97
Meinberg Datagram 98
Appendix D – Antenna Delay Compensation 100
Signal Attenuation 100
Propagation Delay 100
Appendix E – Application Examples 102
Application Example 1: Traditional and Modern Time Sync 102
Application Example 2: System Wide Grandmaster Clock 102
Application Example 3: Synchrophasor, TWFL and Process Bus Applications 103
Application Example 4: IEEE 1588 in a PRP Network 104
Application Example 5: Time Sync Expansion using RT411 and RT412 105
Appendix F – Kit Mounting for GNSS Antenna (Q065) 106
Table of Figures
Figure 1: Functional Overview of RT430/434 17
Figure 2: Front view of RT430 26
Figure 3: Front view of RT434 26
Figure 4: Rear view of RT430 27
Figure 5: Rear view of RT434 27
Figure 6: Location of Serial number, part number and outputs description. 29
Figure 7: Pre-insulated tubular pin terminals 29
Figure 8: Supply connector assembly 29
Figure 9: RT430/RT434 Power Connection 30
Figure 10: RT430/434 Grounding Strap 30
Figure 11: GPS antenna connector 31
Figure 12: Recommended position for installing the GPS Antenna 31
Figure 13: Recommended position GPS Antenna conduit installation 32
Figure 14: TTL electrical outputs 32
Figure 15: Open collector electrical outputs 33
Figure 16: Connection diagram of the open-collector electrical outputs 33
Figure 17: Optical outputs 34
Figure 18: Amplitude modulated output 34
Figure 19: Serial port RS232 and RS422/485 35
Figure 20: Dry-contact relay 36
Figure 21: Event input 36
Figure 22: Euro Type label for connections 37
Figure 23: Electrical communication interface via Ethernet network 37
Figure 24: Local Interface from RT430 and RT434 42
Figure 25: Navigating the RT430’s local monitoring display 42
Figure 26: RT430 Web Interface 43
Figure 27: Languages available in the Web Interface 43
Figure 28: Section to monitor the status of the unit in the Web Interface 44
Figure 29: Section to visualize general information of the system 45
Figure 30: Section of Web Interface to monitor timestamps of event input 46
Figure 31: Section to configure network parameters of the unit 48
Figure 32: Enabling the PRP redundancy 49
Figure 33: Section to configure time parameters 50
Figure 34: Section to configure time signals applied in the outputs 53
Figure 35: Section to configure PTP parameters 58
Figure 36: Characteristics from PTP Power Profile IEEE C37.238:2011 59
Figure 37: Characteristics from PTP Power Profile IEEE C37.238:2011 59
Figure 38: Setup section in Web Interface 63
Figure 39: Manual Time setting – only available in Demo Mode 65
Figure 40: Section to update firmware 68
Figure 41: Section to equipment upgrade – key change 68
Figure 42: Rear panel connectors of RT430 (top) and RT434 (bottom) 74
Figure 43: RT430/434 Dimensions 82
Figure 44: Traditional x Modern Time Synchronization 102
Figure 45: System Wide Grandmaster Clock 103
Figure 46: Synchrophasor devices synced by RT430/434 103
Figure 47: TWFL application using RT430/434 for Time Sync 104
Figure 48: Process Bus application using PTP via the Station Bus network. 104
Figure 49: Process Bus application using PTP via the Station Bus network. 105
Figure 50: Time Sync expansion using RT411 and RT412 105
Figure 51: Dimensions of antenna kit mounting 106
Figure 52: Items from antenna kit mounting 107
List of Tables
Table 1: Serial port pinout 35
Table 2: Ethernet port 1 default settings 37
Table 3: Ethernet port 2 default settings 37
Table 4: Ethernet port 3 default settings (RT434) 38
Table 5: Ethernet port 4 default settings (RT434) 38
Table 6: Gateway and DNS Server default settings 38
Table 7: Gateway and DNS Server 38
Table 8: Factory default username and password 47
Table 9: Summary of configurable network parameters 50
Table 10: Summary of configurable time parameters 51
Table 11: Customizable datagram special characters 55
Table 12: Summary of all configurable parameters for outputs 56
Table 13: Comparison between PTP Power Profiles 60
Table 14: Summary of configurable PTP parameters 62
Table 15: Power supply specifications 71
Table 16: GPS Antenna input specifications for temporal synchronization 71
Table 17: GNSS Antenna specifications 72
Table 18: Antenna Cable specifications 72
Table 19: Surge arrester specifications 73
Table 20: Internal oscillator specifications 73
Table 21: RT430/434 rear panel connectors 74
Table 22: Electrical outputs specifications 75
Table 23: Open collector outputs specifications 75
Table 24: Optical outputs specifications 76
Table 25: Amplitude modulated output 76
Table 26: RS232 or RS422/485 serial port specifications 77
Table 27: Dry-contact relay specification 77
Table 28: Event Input specification 77
Table 29: PTP time synchronization protocol specifications 78
Table 30: Ethernet ports specification 78
Table 31: Environment specification 79
Table 32: Enclosure Protection IEC 60529 79
Table 33: EMC tests were performed according to IEC 60255-26 referring to the
following standards 79
Table 34: Safety tests 81
Table 35: Environmental tests 81
Table 36: Dimensions and weight specification RT430/434 82
Table 37: IRIG-B standard summary 87
Table 38: ACEB Datagram Information 97
Table 39: GPZDA Datagram Time Information 98
Table 40: GPZDA Datagram Line Feed and Carriage Return Information 98
Table 41: GPZDA Datagram Checksum Information 98
Table 42: Meinberg Datagram Time Information 99
Table 43: Meinberg Datagram Beginning and End Information 99
Table 44: Meinberg Datagram Locked State Information 99
Table 45: Antenna cables attenuation @ 1500 MHz (±1 dB) 100
Table 46: Attenuation of antenna cables 101
Table 47: Dimensions specification of antenna kit mounting 106
Table 48: Description of items from kit mounting 106
Chapter 1 – Introduction RT430/434
Reason RT430/RT434
GPS Precision-Time Clock
Chapter 1: Introduction
This chapter provides general information about the technical manual and an
introduction to RT430 and RT434 GPS Precision-Time Clocks.
1 Foreword
This technical manual provides a functional and technical description of GE Reason
RT43X Precision-Time Clocks, as well as a comprehensive set of instructions for using
the devices. The level at which this manual is written assumes that you are already
familiar with protection engineering and have experience in this discipline. The
description of principles and theory is limited to that which is necessary to
understand the product.
We have attempted to make this manual as accurate, comprehensive and user-
friendly as possible. However, we cannot guarantee that it is free from errors. Nor
can we state that it cannot be improved. We would therefore be very pleased to hear
from you if you discover any errors, or have any suggestions for improvement. Our
policy is to provide the information necessary to help you safely specify, engineer,
install, commission, maintain, and eventually dispose of this product. We consider
that this manual provides the necessary information, but if you consider that more
details are needed, please contact us.
GE Grid Solutions:
Worldwide Contact Center
Web: www.GEGridSolutions.com/contact
Phone: +44 (0) 1785 250 070
Target Audience
This manual is aimed towards all professionals charged with installing,
commissioning, maintaining, troubleshooting, or operating any of the products within
the specified product range. This includes installation and commissioning personnel
as well as engineers who will be responsible for operating the product.
The level at which this manual is written assumes that installation and
commissioning engineers have knowledge of handling electronic equipment. Also,
system and protection engineers have a thorough knowledge of protection systems
and associated equipment.
RT430/434 11
RT430/434 Chapter 1 – Introduction
2 Product Scope
RT430/434 is a clock referenced to GPS satellites, whose main application is to be a
source of temporal synchronization signals in different formats and protocols to
synchronize internal clocks of equipment and systems based on digital processing.
The RT430/434 is ruggedized and specifically designed for operation and to be part
of the large scale electrical fixed installations, as electrical power generation
installations, electrical substations and electrical utilities control systems.
With nanosecond time accuracy, the RT430/434 provides temporal synchronization
for applications as synchrophasor measurement, traveling wave fault location,
current differential protection operating over SONET and MPLS systems, and others.
The time synchronization protocols supported are:
• PTP (Precision Time Protocol) according to IEEE 1588v2:2008;
• PTP Profile for Power Utility Automation, in accordance with IEC 61850-9-3:2016
standard;
• PTP Power Profile, in accordance with IEEE C37.238:2011 standard
• NTP/SNTP;
• IRIG-B004 (Demodulated);
• IRIG-B124 (Modulated);
• DCF77;
• Serial Datagram;
• Low frequency pulses, as PPS, PPM and others configurable options.
The RT430 is the first clock to offer Parallel Redundancy Protocol (PRP). Profit from the
high-availability, reliability, and security of your Ethernet network to distribute time
accurately and economically over the same network used on your digital substation.
The front display of the RT430/434 shows either local or UTC date and time,
considering the DST rules when defined by the user.
3 Available Models
RT430 is available in different versions, depending on the features required in each of
the two Ethernet network interfaces, including PRP for both, and the quantity and
input voltage range of the power supplies.
Apart from the PRP, the RT434 has the same functions and protocols as RT430. The
RT434 versions depends on the features required by each of the two pairs of Ethernet
network interfaces, and the quantity and input voltage range of the power supplies.
The Cortecs from RT430 and RT434 demonstrate the available versions for ordering.
4 Key Features
• Better than 100ns time accuracy;
• IEEE 1588v2 PTP protocol;
• PTP Profile for Power Utility Automation, in accordance with IEC 61850-9-:2016
standard;
RT430/434 13
RT430/434 Chapter 1 – Introduction
14 RT430/434
Chapter 1 – Introduction RT430/434
Stationary Mode
In mostly applications, the equipment providing the time synchronization must be in
locked state. For this reason, the Stationary Mode allows the equipment to be in a
locked state even when receiving signals from a single satellite.
However, these two conditions are necessary to use the Stationary Mode:
• Stationary Mode can be used only when RT430/434 is in a fixed position (in a
substation, for example). If the unit is moved from its position when operation in
Stationary Mode, there will be loss of time accuracy.
• Before operating in Stationary Mode, RT430/434 must lock its sync receiving
information from at least four satellites. This condition applies every time the
unit is powered on.
Environmental Robustness
With a robust design, RT430 and RT434 are in accordance with IEC 61010-1 and IEC
60255-27 standards, ensuring reliability and ruggedness even under harsh
environments. Critical applications can benefit from the optional redundant power
supply for even higher uptime and reliability. Every manufactured unit undergoes
complete functional and stress tests to ensure the highest quality.
16 RT430/434
Chapter 1 – Introduction RT430/434
5 Functional Overview
6 Standards Compliance
The device has undergone a range of extensive testing and certification processes to
ensure and prove compatibility with all target markets. A detailed description of
these criteria can be found in the Technical Specifications chapter.
Compliance with the European Commission Directive on EMC and LVD is
demonstrated using a Technical File.
RT430/434 17
RT430/434 Chapter 2 – Safety Information
Reason RT430/RT434
GPS Precision-Time Clock
Chapter 2: Safety Information
This chapter provides information about the safe handling of the equipment. The
equipment must be properly installed and handled in order to maintain it in a safe
condition and to keep personnel safe at all times. You must be familiar with
information contained in this chapter before unpacking, installing, commissioning, or
servicing the equipment.
Each product is subjected to routine production testing for Dielectric Strength and
Protective Bonding Continuity.
2 Symbols
Throughout this manual you will come across the following symbols. You will also see
these symbols on parts of the equipment.
RT430/434 18
Chapter 2 – Safety Information RT430/434
The term 'Ground' used in this manual is the direct equivalent of the European term
'Earth'.
Lifting Hazards
Many injuries are caused by:
• Lifting heavy objects
• Lifting incorrectly
• Pushing or pulling heavy objects
• Using the same muscles repetitively
Plan carefully, identify any possible hazards and determine how best to move the
product. Look at other ways of moving the load to avoid manual handling. Use the
correct lifting techniques and Personal Protective Equipment (PPE) to reduce the risk
of injury.
Electrical Hazards
All personnel involved in installing, commissioning, or servicing this
equipment must be familiar with the correct working procedures.
19 RT430/434
RT430/434 Chapter 2 – Safety Information
The equipment shall have all their rear connectors attached even if
they are not being used, in order to keep their levels of ingress
protection as high as possible
RT430/434 20
Chapter 2 – Safety Information RT430/434
Fusing Requirements
Reason devices contain an internal fuse for the power supply, which
is only accessed by opening the product. This does not remove the
requirement for external fusing or use of an MCB as previously
mentioned. The ratings of the internal fuses are 2 Amp, type T, 250V.
Equipment Connections
21 RT430/434
RT430/434 Chapter 2 – Safety Information
Always use the correct crimp terminal and tool according to the wire
size.
Pre-energization Checklist
RT430/434 22
Chapter 2 – Safety Information RT430/434
Peripheral Circuitry
Upgrading/Servicing
Internal modules and assemblies can be heavy and may have sharp
edges. Take care when inserting or removing modules into or out of
the IED.
23 RT430/434
RT430/434 Chapter 2 – Safety Information
4 Lithium Battery
A lithium battery with a self-life of at least 10 years is onboard in the equipment.
The waste battery shall be disposed as described by the manufacture of the battery.
RT430/434 24
Chapter 2 – Safety Information RT430/434
25 RT430/434
RT430/434 Chapter 3 – Hardware Design
Reason RT430/RT434
GPS Precision-Time Clock
Chapter 3: Hardware Design
This chapter demonstrates the main hardware characteristics from RT430 and
RT434.
1 Front View
The front panel of the RT430/RT434 comprises a LCD display, two indicators and
buttons to navigate through the screen. The figures below show the front view of
the RT430 and RT434.
The RT430/434 have an LCD display (20 columns x 2 lines) for time monitoring and
network setup. The display's first screen shows temporal reference information: day
of the week, day, month, year, day of the year, hours, minutes, seconds, time zone
and the number of monitored satellites.
By navigating through the display using the buttons (arrows pointing right and left), it
is possible to check the configuration of the equipment's two Ethernet networks. IP
addresses, network mask, gateway, broadcast and DNS server are shown for each
network.
The LOCKED indicator shows if the equipment is synchronized with time reference
from satellites. When the ALARM indicator is on, the equipment is not operating and
operator attention is required.
2 Rear View
The rear panel of the RT430/434 comprises:
• Two power supplies (one is optional), AC/DC high voltage or DC low voltage;
• Two TTL electrical outputs (Euro Type connectors) for synchronization, one of
them insulated;
26 RT430/434
Chapter 3 – Hardware Design RT430/434
• Two TTL electrical outputs (BNC connectors) for synchronization, one of them
insulated;
• Two open collector outputs;
• Locked contactor relay and one CMOS/TTL level input;
• One amplitude-modulated output for IRIG-B124 signal;
• Two optical outputs;
• RS232 and RS422/485 serial ports;
• Two Ethernet network communication ports for the RT430 and four Ethernet
ports for the RT434;
• GPS antenna input.
Refer to figures below to the rear connection of the RT430 and RT434, respectively.
3 Network Ports
The network interface presents the following features depending on the equipment
version:
1. Monitoring and configuration;
2. NTP/SNTP synchronization protocols;
3. IEEE 1588 PTP synchronization protocol;
4. PRP Parallel Redundancy Protocol (only in RT430).
4 Power Supply
Apart from the main power supply, there is a redundant power supply available for
RT430 and RT434. Each power supply can have the nominal voltage ranges as listed
below:
1. 100-240Vac, 110-250Vdc;
2. 24-48Vdc.
Note the redundant power supply is independent from the main one. Please refer to
technical specification for the operating ranges.
RT430/434 27
RT430/434 Chapter 4 – Installation
Reason RT430/RT434
GPS Precision-Time Clock
Chapter 4: Installation
The RT430/434 is ruggedized and specifically designed for operation and to be part
of the large scale electrical fixed installations, as electrical power generation
installations, electrical substations and electrical utilities control systems.
1 Unpacking
Unpack the unit carefully and make sure all the accessories and cables are put aside
so they will not be lost.
Check the contents against the packing list that goes with the product. If any of the
content listed is missing, please contact GE Grid Solutions (see contact information in
Maintenance chapter).
Examine the unit for any shipping damage. If the unit is damaged or fails to operate,
notify the shipping company without delay. Only the consignee (the person or
company receiving the unity) can file a claim against the carrier for shipping damage.
We recommend you to keep the original packing materials for possible transport in
the future.
External Indications
Connector descriptions, serial number and part number are shown on an external
label positioned on the equipment, as illustrated on below.
28 RT430/434
Chapter 4 – Installation RT430/434
2 Mounting
The equipment has been designed to be mounted in a standard 19-inch rack using
four M6x15 screws.
Keep adequate clearance for all connections. In particular, the optical fiber cables
should be installed in compliance with the 30 mm minimum bending radius.
For more information regarding the equipment dimensions, refer to the Technical
Specification chapter.
Power Supply
The unit can be powered from a DC or AC power supply within the limits specified. If
the redundancy power supply was ordered, the two power supplies should be
provided independently to ensure operation if one of them is interrupted.
All power connections must use insulated flameproof flexible cable with a 1.5 mm²
cross section, 70 °C thermal class, and 750 V insulation voltage.
To reduce the risk of electrical shock, pre-insulated tubular pin terminals should be
used on the ends of the power connections.
The pin terminals must be completely inserted into the connector supplied with the
unity so that no metallic parts are exposed, according to the figure below.
A 1.5 mm² ground lead must be connected to the terminal marked with the
protective ground symbol for safety.
RT430/434 29
RT430/434 Chapter 4 – Installation
For AC power connection, the phase conductor must be applied to terminal (+/L),
neutral conductor to terminal (-/N) in each of the supply terminals identified, Power 1
and Power 2.
For DC power connection, the positive line should be applied to terminal (+/L),
negative to terminal (-/N) in each of the supply terminals identified, Power 1 and
Power 2.
For compliance with IEC 61010, install a suitable external switch or circuit breaker in
each current-carrying conductor of RT430/434 power supply; this device must
interrupt both the hot (+/L) and neutral (-/N) power leads. An external 10 A, category
C, bipolar circuit-breaker is recommended. The circuit breaker should have an
interruption capacity of at least 25 kA and comply with IEC 60947-2. The switch or
circuit-breaker must be suitably located and easily reachable, also it must not
interrupt the protective ground conductor.
Grounding (Earthing)
To ensure proper operation of the equipment under extreme electromagnetic
conditions, connect the equipment protective ground terminal to the panel using a
copper strap of at least 10 mm width as M6 ring lug.
30 RT430/434
Chapter 4 – Installation RT430/434
If the GPS antenna is connected and it is possible to receive signal from at least 4
satellites the LOCKED indicator will start to blink after a couple of seconds, indicating
that the internal time-base is being synchronized with the satellites. The LOCKED
indicator will stop blinking and will remain lit as soon as maximum accuracy is
achieved. This process may take several minutes if the equipment was transported
for more than a few hundred kilometers or was unpowered for many weeks. The dry-
contact LOCKED in the rear panel closes when maximum accuracy is achieved.
The antenna must be mounted outdoors, in a vertical position, with an unobstructed
view of the sky. The antenna should be placed above the height of the building as
much as possible. A partially obstructed sky view will compromise the unit's
performance.
The antenna should not be located under overhead power lines or other electric light
or power circuits, or from where it can fall onto such power lines or circuits.
An antenna mast of roof-mounting-kit and any supporting structure must be
properly grounded to provide protection against voltage surges and built-up static
charges. It is recommended the use of a surge arrester for the entire wiring where
there is external antenna cabling.
The antenna must be connected to the unit by using a coaxial cable with a 50 Ω
impedance. The antenna cable should be routed through a conduit, shielded from
rain and/or solar radiation. The conduit should not be shared with any power circuits.
It is recommended to use a 3/4 PVC conduit, threaded on one end. To install it, cut
down to the intended size and screw the antenna in the conduit. The conduit can be
fixed on the wall, so that the antenna is above the wall limit and free from lateral
obstacles, as shown in the next figure.
RT430/434 31
RT430/434 Chapter 4 – Installation
Cables with lengths ranging from 15 m (50 ft) to 150 m (492 ft) can be ordered from
GE Grid Solutions. Be careful when installing the antenna cable to RT43X. The cable
may be too heavy to be supported by the antenna input connector only, damaging
the equipment. Make sure the cable antenna is fixed in the rack (or other support) to
minimize the weight load in the antenna input connector from RT43X.
For use of antennas and cables from other manufacturers, contact GE Grid Solutions
for evaluation.
The antenna cable affects the unit's performance in two distinct ways: satellite signal
attenuation and propagation delay.
More than one device can be connected in parallel from one TTL output. The
maximum number of devices that can be connected to the TTL output depends on
32 RT430/434
Chapter 4 – Installation RT430/434
the current that each device’s input uses. As the maximum current supplied from
each TTL output is 150mA, the sum of the currents from all devices connected cannot
exceed this value (cable resistance should be considered). The TTL voltage level is 5V.
Electrical cable length should not exceed 100m. To minimize EMC effects in IRIG-B
signals, the use of fiber-optic cable is recommended for distances greater than 3 m.
For details on the configuration of TTL-Level electrical outputs, refer to the
Configuration chapter.
See the Technical Specification chapter for more description of signal levels and
maximum ratings.
The open-collector outputs require the use of an external resistor properly sized to
limit current to a value below 300 mA.
RT430/434 33
RT430/434 Chapter 4 – Installation
The resistor power should be adequate for the voltage and current values to be
switched, i.e.
𝑉𝐶2
𝑃𝐶 ≥ 1.2 ∙
𝑅𝐶
Do not connect the open-collector electrical outputs without a properly sized
external resistor or another appropriate mechanism to limit current.
See the Technical Specification chapter for a description of signal levels and
maximum ratings.
Optical Outputs
RT430/434 has 2 outputs for multimode optical fiber. The length of fiber-optic cables
should not exceed 2 km.
The type of signal at each output can be configured through a Web Interface to
generate IRIG-B004, DCF77, 1PPS, 1PPM, 100PPS, or any custom-defined low
frequency, from 1 pulse-every-two-seconds to 1 pulse-per-day. In addition, it is
possible to configure the outputs to generate daily set-time pulses. The polarity of the
signal and the pulse width can also be configured.
See the Technical Specification chapter for optical outputs technical information.
34 RT430/434
Chapter 4 – Installation RT430/434
1 -
3 RXD
5 GND
6 -
8 422/485 TX+
9 422/485 TX-
The bit-rate, format (number of data bits, party, number of stop bits) and datagram
type can be configured using the Web Interface, as well as the type of signal
transmitted by the pin OUT (pin 4).
Pins 2, 3 and 5 are used for the RS232 interface.
Pins 8 and 9 are used for the RS422 or RS485 interface.
For serial port configuration, see the Configuration chapter.
For existing datagrams details, see Appendix.
Dry-Contact Relay
The RT430/434 has 1 dry-contact that can be used to remotely signal the locked
state of the unity and to alarm if there is no power on the unit.
RT430/434 35
RT430/434 Chapter 4 – Installation
When the unit is powered up, the dry-contact relay is normally closed. When the
equipment enters in the locked state, the dry-contact will open. The dry-contact
closes in case the unit does not have enough satellites as reference or the power
supply has failed.
See the Technical Specification chapter for information on switching capacity
limitations.
Event Input
The RT430/434 has 1 input to detect TTL-Level external events. This input may be
used to verify the PTP signal quality when RT430/434 synchronizes another clock
using PTP. Thus, the TTL output from the PTP Slave clock may be connected to the
event input from RT430/434 in order to measure the signal quality. is used as a slave
(PTP signal received from external source via network).
The electrical output from the PTP Slave clock should be configured to send pulses in
a time frequency and an event will be registered in a log file containing the pulse
timestamp for each received pulse. The input accuracy is in the magnitude of ns.
36 RT430/434
Chapter 4 – Installation RT430/434
3 Ethernet Communication
The RT430 has 2 Ethernet 10/100BaseT (auto-negotiation) communication interfaces
with RJ45 connectors, and the RT434 has 4 Ethernet 10/100BaseT (auto-negotiation)
ports.
When a CAT5 cable with RJ45 connector is plugged in each port, the LINK led will
indicate that the cable is transmitting signal, and the ACTIVITY led blinks when there is
data exchange.
IP Address 192.168.0.199
Netmask 255.255.255.0
Broadcast 192.168.0.255
IP Address 192.168.1.199
RT430/434 37
RT430/434 Chapter 4 – Installation
Netmask 255.255.255.0
Broadcast 192.168.1.255
IP Address 192.168.2.199
Netmask 255.255.255.0
Broadcast 192.168.2.255
IP Address 192.168.3.199
Netmask 255.255.255.0
Broadcast 192.168.3.255
The factory’s default port to connect to the Gateway is the Ethernet 1. The factory
default settings of the Gateway and DNS Server are:
38 RT430/434
Chapter 4 – Installation RT430/434
Equipment access
The Web Interface is designed for configuring and monitoring the unit through a web
browser, if the unit it is accessible from a local network. To use all features through
the Web Interface, make sure to use one of the following web browsers:
• Internet Explorer version 7.0 or newer.
• Mozilla Firefox version 3.0 or newer.
• Google Chrome
Connect to the Web Interface by entering the unit IP address into the address field of
your web browser. After the page is loaded, the unit’s Web Interface will open,
allowing the user to operate, monitor, and configure it.
4 Powering Up
Before energizing the unit, familiarize yourself with all the risks and attention
indicators in the equipment frame.
• Connect the power supply (including the ground lead) to the appropriate
terminals.
• The unit will perform a self-test procedure, and the Alarm indicator will remain
lit.
• At the end of the self-test, the equipment will perform initialization of the GPS
receiver. At the end of approximately one minute, the Alarm indicator will go out
and information will be shown in the equipment's display. If Alarm indicator
remains on, the unit will not be operating and it will require attention by the
user.
• To turn off the unit, switch off the external switch or circuit breaker. The unit will
record the time, date, satellite orbits parameters, and internal oscillators drift
estimates in non-volatile memory to improve accuracy and reduce the time to
synchronize with satellites in the next energizing process. Also, all indicators
LEDs will turn off.
In case the unit does not behave in a way here described, carefully check all power
and signal connections. See Maintenance chapter for additional suggestion for
problem diagnosis.
RT430/434 39
RT430/434 Chapter 4 – Installation
action should be taken. However, some periodic tests should be carried out to ensure
that they are functioning correctly and that the external wiring is intact.
It is the responsibility of the customer to define the interval between maintenance
periods. If your organization has a Preventative Maintenance Policy, the
recommended product checks should be included in the regular program.
Maintenance periods depend on many factors, such as:
• The operating environment;
• The accessibility of the site;
• The amount of available manpower;
• The importance of the installation in the power system;
• The consequences of failure.
Preventive Actions
For optimum performance of Reason RT430/434, perform the following preventive
maintenance procedures and actions:
Keep temperature and humidity at adequate levels inside the panel. The American
Society of Heating, Refrigerating, and Air Conditioning Engineers (ASHRAE)
recommends operating network equipment within the following ranges of
temperature and relative humidity (see the ASSHRAE TC9.9 “2011 Thermal Guidelines
for Data Processing Environments – Expanded Data Center Classes and Usage
Guidance”).
Operating within this range supports the highest degree of equipment reliability, even
though the equipment data sheets may state wider ranges of minimum and
maximum temperature and humidity (for example, -40° C to 55° C and 5% to 95%
RH). Continuous equipment operation at the minimum and maximum limits is not
recommended.
Keep panel sealed to avoid dust and/or animals and insects.
Inspect the installation site for moisture, loose wires or cables, and excessive dust.
Make sure that airflow is unobstructed around the device and into the air intake
vents.
It is recommended weekly or every two weeks to access the web interface area of
the unit and check the equipment details in Status area. See Operation chapter for
further details regarding the equipment status.
40 RT430/434
RT430/434 Chapter 5 – Operation
Reason RT430/RT434
GPS Precision-Time Clock
Chapter 5: Operation
This chapter introduces the Local and Remote Interface available for RT430/434.
The RT430/434 has an LCD display (20 columns x 2 lines) for time monitoring and
network setup. The display's first screen shows temporal reference information: day
of the week, day, month, year, day of the year, hours, minutes, seconds, time zone
and the number of monitored satellites.
By navigating through the display using the buttons (arrows pointing right and left), it
is possible to check the configuration of the equipment's two Ethernet networks. IP
addresses, network mask, gateway, broadcast and DNS server are shown for each
network. The following illustration presents the possible menu screens for the RT430.
The RT434 menu has the same screens as the RT430, but informing about all 4
Ethernet ports.
42 RT430/434
Chapter 5 – Operation RT430/434
The Alarm indicator will light up for a brief period while the unit powers up. After
concluding the initialization, the unit will start operating and this indicator should turn
off. If Alarm indicator remains on, the unit is not operating normally and will require
user attention. The Alarm will also light up in case a problem occurs with the antenna
or after 66 seconds in unlocked state.
Status
The section Status of Web Interface, as shown below, allows monitoring status
information of the unit in real time.
Figure 28: Section to monitor the status of the unit in the Web Interface
44 RT430/434
Chapter 5 – Operation RT430/434
after from last NTP request sent. Both NTP Graphic and NTP Client List does not
have automatic refresh.
• Channels: monitored satellites information (number, phase noise, azimuth and
elevation). The background of Satellite number (Sat #) is green when receiving
the health ephemeris data. A grey background means the satellite is not
healthy by the moment, and it is not been used as reference.
General Information
The section General Information of the Web Interface displays system information of
the unit.
Event Log
The section Event Log from the Web Interface allows monitoring external timestamp
pulses received from another time source. The timestamp frequency registered in log
files is according to the pulse frequency received through the event input.
RT430/434 45
RT430/434 Chapter 5 – Operation
• Last Events: In the Timestamp area, it is possible to view the last ten
timestamps from a signal received through the event input. The update of
timestamps is not automatic. To view them, click the button <Update>.
• Timestamps Log file: a .txt format file, containing the timestamps registered in
the unit. By clicking <Download> a window will open to save the file in a
directory on the computer.
The RT430/434 event input can register up to 3600 timestamps.
46 RT430/434
Charter 6 – Configuration RT430/434
Reason RT430/RT434
GPS Precision-Time Clock
Chapter 6: Configuration
This chapter describes how to configure the RT430/434.
1 Web Interface
The Reason RT430/434 GPS Precision-Time Clock has a Web Interface for configuring
network parameters, time parameters, time synchronization outputs and PTP
standard, updating firmware, changing key, controlling access and manipulating
configurations.
To connect to the Web Interface, enter the unit Ethernet port IP address into the
address field of a web browser. For information on factory default settings of the
Ethernet ports, see Installation chapter. If the unit is not using factory default
settings, the current IP address can be obtained by the local HMI (LCD display and
keys).
A start page containing the unit status information opens once the Web Interface is
accessed. The remaining monitoring and configuring sections are on a menu on the
left. To access them, click the desired menu item. The configuring sections are:
• Ethernet: allows configuring the network parameters.
• Time Settings: allows configuring the time parameters.
• Time Signals: allows configuring signals sent from outputs.
• PTP: allows configuring PTP clock parameters in accordance with IEEE 1588.
• Setup: allows manipulating configurations, changing access control and key,
and updating firmware.
Password 1234
Sending Configuration
To send the new configuration to the equipment, click on the <Apply> button. Then
the username and password of the equipment will be requested.
RT430/434 47
RT430/434 Chapter 6 – Configuration
Once both entered, click on login and the equipment will update its configuration. A
message will be displayed informing the status of the update.
In case the new configuration is not transmitted to the unit, the changes will not be
saved and will be discarded once the Web Interface is closed.
2 Ethernet
The Ethernet section of the Web Interface allows enabling the PRP (only in RT430) and
configuring network parameters of Ethernet ports 1, and 2, gateway and DNS. RT434
will display four Ethernet ports.
48 RT430/434
Charter 6 – Configuration RT430/434
Ethernet Ports
The Ethernet ports allow communication via TCP/IP or UDP/IP networks.
• MAC Address: informs the MAC address of the network port.
• The IP Address field allows entering the IP address of the network port (only
decimal numbers).
• The Network Mask field allows entering the network mask from the network to
which the unit will be connected (only decimal numbers).
• The Broadcast field allows entering the subnet address to which the unit will be
connected (only decimal numbers).
Default Gateway
The gateway configuration allows RT430/434 to communicate with other devices
connected to a local subnet.
• The IP Address field allows entering the network port IP address of the unit (only
decimal numbers).
• The field Port allows choosing the communication port to be used as gateway
DNS Server
The DNS server configuration allows the RT430/434 to communicate with the DNS
server from a local subnet. The IP Address field allows entering the IP Address of the
network's name server (only decimal numbers).
RT430/434 49
RT430/434 Chapter 6 – Configuration
The table below presents all configurable network parameters and its possible values
and variables.
Ethernet Ports
Gateway
DNS Server
* only in RT434
3 Time Settings
The Time Settings section of the Web Interface allows configuring time parameters.
Time Parameters
• The field Timezone allows configuring the time zone of the unit, and converting
UTC time to local time. Half hour time zones are supported.
• The field DST, when enabled, allows configuring the beginning and the end of
Daylight Saving Time.
50 RT430/434
Charter 6 – Configuration RT430/434
• When the option NTP – Send local time is selected, the local time in accordance
with timezone and DST configuration is sent through NTP protocol. If this option
is unselected, the UTC is sent.
Leap Second
The RT430/434 has built-in support for leap seconds, whenever indicated by the GPS
(when operating as GPS Clock) or by PTP Grandmaster (when operating as PTP Slave).
In both cases, the LCD display will show 23:59:60 at the moment the second
increases (leap). In other words, while the last second of a normal day is 23:59:59, the
last second of a day with Leap Second is 23:59:60.
This can also be verified in the Web Interface, under the NTP information of the
Status section. The first field, "leap", indicates whether a leap second will be applied
at the end of the day. Its standard value is 0 (normal, leap second warning). This field
has the value 1 if the last minute of the day has 61 seconds; or the value 2 if the last
minute of the day has 59 seconds. So from the beginning of the day that will take
place the Leap Second field will have a value of 1 or 2; after the application of the
Leap Second this field value is back to its normal value 0.
Besides the Web Interface, leap second treatment is also stored on the equipment’s
event log, and may be checked after the occurrence of a leap. The processing and
treatment of the Leap Second happens automatically and may not be disabled.
RT430/434 51
RT430/434 Chapter 6 – Configuration
h: 00 up to 23 (hours)
m: 00 up to 60 (minutes)
4 Time Signals
The Time Signals section of the Web Interface allows configuring the signals applied
to the outputs of the unit. See figure below:
52 RT430/434
Charter 6 – Configuration RT430/434
Outputs
• TTL 1 / 2: allows configuring the TTL-level electrical outputs 1 and 2. Each
output has two terminals, one screw, and other BNC. Both terminals can be
used simultaneously although its configuration is unique, so the same signal
will be applied to both terminals;
• OPTO 1 / 2: allows configuring the two TTL-Level optical outputs;
• OC 1 / 2: allows configuring the two open collector outputs;
• RS232: allows configuring the Out pine signal of the serial output.
For each electrical, optical, open collector and serial output, it is possible to configure
the following signals:
• OFF - Output turned off;
• PPS - Output with 1 pulse-per-second;
RT430/434 53
RT430/434 Chapter 6 – Configuration
• The field TMARK allows configuring time to generate a pulse with daily
repetition. All outputs programmed to send TMARK pulses will be programmed
within the same time.
• The field DMARK allow to set a date and time for a single pulse signal. All
outputs using DMARK will be programmed to this same date and time.
• The field PPX allows configuring a pulse-frequency that can vary from 1 pulse-
every-2-seconds to 1 pulse-per-day. All outputs programmed to send PPX
pulses will be programmed within the same pulse-frequency.
• The field Pulse Width allows the user to adjust the duty cycle (pulse width of
high state) for PPS, PPM, PPX, TMARK and DMARK.
• Pulse width of 1µs when unlocked: When selected, this option turns the PPS,
PPM, PPX, TMARK and DMARK pulses into a 1µs pulse when not locked to
satellites, indicating that the synchronization signal is local, not global.
• Disable PPS when unlock time after (s): When selected, this option disables the
PPS signal after the specified time, in seconds.
• The field Cable delay compensation allows entering a value between 0 and 999
nanoseconds (ns) to compensate propagation delay according to the cable
length. Refer to Appendix D for more details of how to compensate the cable
delay.
Serial datagram
• The field Datagram allows configuring a datagram sent by the serial port (TDx
pin).
• ACEB, NEMEA, GPZDA, Meinberg and customizable datagrams are possible.
When choosing a customizable datagram, it is necessary to enter characters
with information required. For more details about ACEB, NEMEA, GPZDA and
Meinberg datagrams, see Appendix C;
• A serial datagram is sent each second. The field On-time mark allows choosing
if the sending will be synchronized with the beginning or the end of the
datagram;
o Start of first: pulse synchronized with the beginning of the
datagram;
o Start of last: pulse synchronized with the end of the datagram;
• Serial: allows configuring the serial port parameters.
o The field Speed allows choosing data transmission speed of the
serial port, which can be 38400, 19200, 9600, 4800 or 1200 bps;
o The field Data allows defining the data bits, which can be 7 or 8;
54 RT430/434
Charter 6 – Configuration RT430/434
o The field Parity allows choosing the serial port parity, which can be
odd, even, or none;
o The field Stop bit allows choosing the datagram stop bit, which can
be 1 or 2.
Customizable datagrams
The RT430/434 allows defining a datagram “ASCII'' to be sent once per second by the
serial port, using the characters described below. The datagram characters can be
single or special. The maximum number of character in a customizable datagram is
16.
The single characters allowed are: 0..9 A..Z a..z $ \{ \} ( ) [ ] . , ; : ! ? @ < >$ \# * \_ - \% \$
blank and empty.
• %H %M %S %d %m %y %x correspond to 2 characters; (Date and Time sent
through datagrams refers to the local time zone configured in the RT430/434)
• %j : correspond to 3 characters (length(str) + 1 for each event);
• %Y correspond to 4 characters (length(str) + 2 for each event)
• %u %w %s %o %O %Q %1 %2 %3 %4 %5 %% : correspond to 1 character
(length(str) - 1 for each event)
The following special characters can be used to enter information into the datagram:
%H 00 ... 23 2 Hours
%M 00 ... 59 2 Minutes
%S 00 ... 59 2 Seconds
%m 01 ... 12 2 Month
RT430/434 55
RT430/434 Chapter 6 – Configuration
%x 2 Checksum type 1
Outputs
56 RT430/434
Charter 6 – Configuration RT430/434
Hour: 00 up to 23
TMARK Minutes: 00 up to 59
Seconds: 00 up to 59
Day: 01 to 31
DMARK
Hour: 00 up to 23
Minutes: 00 up to 59
Seconds: 00 up to 59
Pulse width PPS, PPM, PPX, TMARK and DMARK pulses width from 10
to 990 milliseconds
Pulse width of 1us selected: PPS, PPM, PPX, TMARK and DMARK pulses
when unlocked width of 1us when unit is unlocked
Disable PPS when selected: disable PPS signal when the unit is unlocked
unlock time after (s) after defined period in seconds
Serial datagram
Data: 7 or 8
Stop bit: 1 or 2
RT430/434 57
RT430/434 Chapter 6 – Configuration
5 PTP Configuration
The PTP section from Web Interface allows the user to configure the parameters for
the PTP protocol.
To enable the PTP in RT430/434, mark the “PTP Enabled” box. If the field “Force
operation as slave” is unmarked, the RT430/434 operates as Grandmaster Clock,
otherwise the unit acts as Ordinary Clock (slave). Note when equipment is operating
as Ordinary, the antenna signal is ignored.
To disable PTP, make sure both boxes, “PTP Enabled” and “Force operation as slave”,
are disabled.
Profile
When configuring PTP, the first point to be decided is which PTP profile, or which
common parameters, will be used along all PTP devices. The RT430/434 has four
options to be selected as profile:
• Power Profile – IEEE C37.238/2011: profile with predetermined characteristics,
where the user cannot change any major parameter from PTP, such as Network
Protocol, Operation mode and Delay mechanism. The characteristics are shown
in next figure. The configurable parameters for Power Profile are:
o Domain number;
o VLAN ID and Priority;
o Operation as Master or Slave;
o If non-Power messages (PTP messages that are not in compliance
with IEEE C37.238) should be ignored;
o Grandmaster ID (identification);
o Network time inaccuracy, if delays are known from the network
architecture used;
o If the PTP should send the local time (considering the timezone and
DST parameters configured) or UTC time.
58 RT430/434
Charter 6 – Configuration RT430/434
RT430/434 59
RT430/434 Chapter 6 – Configuration
Selectable, allowing to
Grandmaster choose the best
Equal for all Grandmaster
Priority grandmaster for holdover
conditions
Domain number
The RT430/434 allows configuring the domain number to be identified by the PTP
clock, so it only answers messages from this domain. The domain number field
allows selecting a domain number between 0 and 255 which the unit will recognize.
Network protocol
This field defines the network layers where the PTP protocol will be applied. It is
possible to use PTP protocol in a network layer with IEEE 802.3 Ethernet (layer 2) or
UDP/IPv4 (layer 3) connection.
If Ethernet (layer 2) is selected, VLAN may be used.
Operation mode
The field operation mode allows configuring the operation mode according to the
form RT430/434 sends its messages, as follows:
• One-step: Sync information and timestamp information are sent in the same
data packet;
• Two-step: Sync information is sent in one data packet, and timestamp
information is sent in another data packet.
60 RT430/434
Charter 6 – Configuration RT430/434
Delay mechanism
The RT430/434 is capable of measuring the delay between master and slave clocks
using End-to-end and Peer-to-peer, according to IEEE1588 standard. The field Delay
mechanism allows configuring the type of measurement of the delay, as follow:
• End-to-end: measurement of delay across the network between master clock
and slave clock;
• Peer-to-peer: measurement of delay only between master and slave clocks as
neighbors.
Grandmaster Priority
When configured as master, BMC algorithm tie breaking criteria priorities must be
attributed. The fields Grandmaster priority #1 and #2 allow configuring the priorities
of both Ethernet ports, in which #1 is the first and #2 is the last tie breaking criterion.
Between the first and the last tie breaking criterion, other clock characteristics are
analyzed. The priority values can vary from 0 to 255. The lower the attributed value is,
the higher its priority is.
PTP Messages
In PTP protocol, messages containing Sync information and timestamps are sent
across the network in multicast mode.
Announce messages are used to inform devices connected to the network about the
existence of a master clock available to send Sync packets. The clock connected to
the network operating as a master should send Sync messages. In case it is a two-
step clock, Follow Up messages containing the timestamp will be send after the Sync
messages.
In RT430/434, it is possible to choose the frequency to send messages and the
waiting time of Announce message receipt, through the fields below:
• Delay request interval allows choosing the frequency to send messages with
delay measurement. It is possible to configure the unit to send 16 messages per
second until one message every-32-seconds.
• Announce interval allows choosing the frequency to send messages that apply
the device to become a network master candidate. It is possible to configure
the unit to send 16 messages per second until one message every-32-seconds.
• Sync interval allows choosing the frequency to send Sync messages. It is
possible to configure the unit to send 16 messages per second until one
message every-32-seconds.
• Announce receipt timeout allows choosing the waiting time of Announce
message receipt when RT430/434 is being used as slave. In case an Announce
message is not received within this time interval, the unit assumes that the
current master clock is unavailable and executes the BMC to select another
master clock. It is possible to configure values between 2 and 255 seconds.
RT430/434 61
RT430/434 Chapter 6 – Configuration
Profile
Parameters
TLV Messages
Send local time Selected: local time is sent through PTP protocol.
Unselected: UTC is sent through PTP protocol.
62 RT430/434
Charter 6 – Configuration RT430/434
6 Setup
The Setup section of the Web Interface allows updating the firmware, manipulating
configurations, changing key and configuring password. Firmware and key change
(equipment upgrade) instructions are described in Maintenance chapter.
RT430/434 63
RT430/434 Chapter 6 – Configuration
Configuration Management
• Backup Configuration: It is possible to receive a file with the current
configuration of the unit and store it in a directory on the computer. Saving the
final configuration of the unit as a backup is recommended.
o Download: allows saving the current configuration of the unit in
“.rt430” or “.rt434”, respectively to RT430 and RT434. By clicking
<Download> a window will open to save the file in a directory on
the computer.
• Restore Configuration: It is possible to send a configuration file in “.rt430” or
“.rt434” format to the respectively unit.
o File: allows entering the directory and file name of the
configuration that will be sent to the unit.
o Search: allows searching the configuration file in Windows'
directories.
o Restore: allows transmitting the selected configuration file to the
unit. By clicking <Restore> a window will open requiring
configuration username and password. Enter the username and
password and click <Login>. To cancel the action, click <Cancel>.
During the transmission, the unit will go momentarily out of
operation.
• Restore to factory default configuration: Restore the equipment to factory
default settings.
Password configuration
• New password: allows entering a new password for configuration.
• Confirm password: confirmation of the new password entered.
Stationary Mode
This option enable the Stationary Mode, which keeps the equipment in locked state
even with one satellite. Note the equipment must track at least four satellites before
entering in stationary mode. Besides, if this option is enabled, the equipment must be
in a fixed position.
To enable the Stationary Mode, select the option “Enabled Stationary Mode” and click
on the <Apply> button.
Demo mode
Mostly used in demonstrations, this option forces the clock into a LOCKED state
independently if the antenna is or is not connected, as the internal oscillator is used
64 RT430/434
Charter 6 – Configuration RT430/434
as time reference. In demo mode, the Locked Led will remain alight and the dry
contact relay opened. When the Demo Mode is activated, it is possible to configure
the date and time manually, in Time Settings tab from equipment Web Interface.
All time protocols work in Demo Mode: PTP, NTP, SNTP, IRIG-B and all other low
frequency signals.
Log Files
Technical support may request log files in case maintenance is required.
Reboot System
This feature reboots the system without the need to withdraw the power supply.
RT430/434 65
RT430/434 Chapter 7 – Maintenance
Reason RT430/RT434
GPS Precision-Time Clock
Chapter 7: Maintenance
This chapter describes the information to consider for an eventual maintenance.
For any further assistance required please contact the information and call center as
follows:
GE Grid Solutions:
Worldwide Contact Center
Web: www.GEGridSolutions.com/contact
Phone: +44 (0) 1785 250 070
66 RT430/434
Chapter 7 – Maintenance RT430/434
IRIG-B Signal
When the Time Quality bits from IRIG-B signal are all in 0, the unit is in Locked state,
i.e., there is time reference in the GPS antenna input. In case the reference is
disconnected or the signal is weak, the bits combination will differ from zero.
PTP Protocol
In PTP protocol, there is a bit called time traceable that, when set, informs the
existence of time reference in the GPS antenna input. Besides the existence of a
reference signal, it is possible to qualify the signal, according to the bits clock class
and clock accuracy, in which the criterion for assessing the quality of the signal is
configured in the device that receives the PTP messages.
NTP Protocol
In NTP protocol, information is given in layers, known as Stratum, numbered from 0
to 16. Layer 1 indicates the unit is operating with time reference from the GNSS
antenna input, when the antenna is connected. Stratum layer 6 indicates the
reference was interrupted, i.e., the unit lost the antenna connection. A stratum level
16 means an antenna was never connected to the unit after initialization.
SNTP Protocol
In SNTP protocol, a data set is sent containing time synchronization and the status of
the external time reference.
When the status data is zero, it represents the lack of time reference in the GPS
antenna input. When it is 1, it represents the existence of reference in the GPS
antenna input, i.e., it is in LOCKED state.
2 Firmware Update
Eventually, new firmware versions will be released with updates and improvements
to the unit.
The Setup section of the Web Interface allows updating the firmware, manipulating
configurations, changing key, and changing configuration username and password.
RT430/434 67
RT430/434 Chapter 7 – Maintenance
To update the unit firmware, access the Setup section of the Web Interface by typing
the unit IP address in a default browser and follow the steps below:
1. Click <SEARCH> and it will allow the search of a new firmware update file in the
directories. Enter the directory and the firmware update file name in the <FILE>
field and it will be sent to the unit. The update file has the extension “.fw430” for
RT430 and “.fw434” for RT434.
2. Click < SEND> to send the new firmware to the unit.
3. After clicking <SEND>, a new window will open requesting username and
configuration password. Enter username and password and click <LOGIN>. To
cancel the action, click on <CANCEL>.
4. During the transmission, the unit will momentarily go out of operation.
5. After the change is completed, check the main page of the Web Interface.
Note: After updating, it is recommended to clear the browsing data (CTRL+ F5) when
accessing the web interface for the first time.
To change the unit key, access the Setup section from Web Interface, typing the unit
IP address in a default browser and follow the steps below:
1. Enter the new key (36 alphanumeric characters) in the Key field.
2. Click <Apply> to send the new key to the unit.
3. After clicking <Apply>, a new window will open requesting username and
configuration password. Enter username and password and click <Login>. To
cancel the action, click <Cancel>.
4. During the transmission, the unit will momentarily go out of operation. A
message communicating the key change will show up on the screen.
5. After the change is completed, check the main page of the Web Interface.
68 RT430/434
Chapter 7 – Maintenance RT430/434
4 Cleaning Instructions
Before cleaning the equipment, make sure that the primary voltage is removed. If it is
necessary cleaning the exterior of the equipment, use only a dry cloth. Internally it is
not required any cleaning.
5 Equipment Return
All parts and components comprising Reason devices must be repaired exclusively
by GE Grid Solutions. In case of equipment malfunction the customer must get in
contact with GE’s Contact Centre and never attempt to repair the device by his own.
To request equipment repair service, call GE Grid Solutions to check out shipment
options and receive the technical assistance order code.
The equipment must be packed in its original package or a suitable package to
protect against impacts and moisture.
Send equipment to address supplied including the sender's identification and the
technical assistance reference.
RT430/434 69
Chapter 8 – Technical Specification RT430/434
Reason RT430/RT434
GPS Precision-Time Clock
Chapter 8: Technical Specification
This chapter describes the technical specifications of the product. The information
described in this manual goes for RT430 and RT434, unless specified.
1 Power Supply
Table 15: Power supply specifications
MAX 20 VA MAX 10 W
Power Consumption
Typical 15 W Typical 8 W
2 GPS Antenna
RT430/434 71
RT430/434 Chapter 8 – Technical Specification
Impedance 50 Ω
Antenna Cable
Table 18: Antenna Cable specifications
Attenuation
Length Delay (ns) Description
@1500MHz
72 RT430/434
Chapter 8 – Technical Specification RT430/434
Impedance 50 ohms
Capacitance 81pF/m
Surge Arrester
Table 19: Surge arrester specifications
Impedance 50 Ω
Connector BNC
3 Internal Oscillator
Table 20: Internal oscillator specifications
The RT431 drift is lower than 0.1 ppm. One million seconds corresponds to 11 days,
13 hours, 46 minutes and 40 seconds. So our clock has a drift lower than 100 ms
every million seconds.
This accuracy in ppm can also be expressed as a percentage:
± 0.1 / 1,000,000 = ± 0.00001%.
4 Outputs
Connectors
See figures below to refer to the rear panel connectors of RT430/434.
RT430/434 73
RT430/434 Chapter 8 – Technical Specification
Figure 42: Rear panel connectors of RT430 (top) and RT434 (bottom)
Indicator Description
2 TTL electrical outputs using Euro Type connectors, one of them insulated;
74 RT430/434
Chapter 8 – Technical Specification RT430/434
50 ns (mean)
Time Accuracy
100 ns (peak)
Number of Outputs 4
Impedance 18 Ω
Two electrical outputs are insulated, one from 2-pin connector and another from
BNC connector.
Number of Outputs 2
RT430/434 75
RT430/434 Chapter 8 – Technical Specification
Optical Outputs
Table 24: Optical outputs specifications
50 ns (mean)
Time Accuracy
100 ns (peak)
Number of Outputs 2
Connector ST
Wavelength 820 nm
Number of Outputs 1
Signal IRIG-B124
50 Ω Amplitude 3 Vpp
Outputs Impedance 15 Ω
Maximum Current 80 mA
76 RT430/434
Chapter 8 – Technical Specification RT430/434
Number of Outputs 1
Data bits 7 or 8
Stop bits 1 or 2
5 Dry-contact Relay
Table 27: Dry-contact relay specification
Number of Outputs 1
500 mA @ 24 Vdc
500 mA @ 48 Vdc
Max DC Current Capacity
400 mA @ 125 Vdc
6 Event Input
Table 28: Event Input specification
Number of Inputs 1
RT430/434 77
RT430/434 Chapter 8 – Technical Specification
UDP/IPv4 (Layer 3)
Protocols
IEEE 802.3 (Layer 2)
End-to-End (E2E)
Delay Compensation
Peer-to-Peer (P2P)
• Custom
8 Ethernet Ports
Table 30: Ethernet ports specification
Connector RJ45
SNTP
Protocols Supported
SNMP (v1, v2c and v3), including MIB
support.
IEEE 1588 PTP
78 RT430/434
Chapter 8 – Technical Specification RT430/434
9 Environment
Table 31: Environment specification
10 Type Test
Table 33: EMC tests were performed according to IEC 60255-26 referring to the
following standards
Differential mode: 1 kV
IEC 61000-4-5:2005
Common mode: 2 kV
IEC 61000-4-6:2008 10 V
30 A/m continuous
IEC 61000-4-8:2009
300 A/m @ 1 s
RT430/434 79
RT430/434 Chapter 8 – Technical Specification
Duration time
A.C.: 1 cycle
D.C.: 16,6 ms
Duration time
A.C.: 12 cycles
Duration time
A.C.: 30 cycles
D.C.:500 ms
Duration time
D.C.: 5 s
Shut-down ramp: 60 s
Start-up ramp: 60 s
Radiated emission
80 RT430/434
Chapter 8 – Technical Specification RT430/434
Radiated emission
Conducted emission
IEC 61010-1
Safety Requirements
CE Certification
Impulse: 5 kV
RT430/434 81
RT430/434 Chapter 8 – Technical Specification
11 Dimensions, Weight
Table 36: Dimensions and weight specification RT430/434
82 RT430/434
Chapter 9 - Cortec RT430/434
Reason RT430/RT434
GPS Precision-Time Clock
Chapter 9: Ordering Options
This chapter describes the CORTEC number formation from RT430 and RT434.
RT430/434 83
RT430/434 Chapter 9 - Cortec
Issue I
84 RT430/434
Chapter 9 - Cortec RT430/434
Issue I
RT430/434 85
Chapter 10 - Appendixes RT430/434
Reason RT430/RT434
GPS Precision-Time Clock
Chapter 10: Appendixes
2 Pr + 20 ms seconds 2
3 Pr + 30 ms seconds 4
4 Pr + 40 ms seconds 8
6 Pr + 60 ms seconds 10
7 Pr + 70 ms seconds 20
8 Pr + 80 ms seconds 40
11 Pr + 110 ms minutes 2
12 Pr + 120 ms minutes 4
13 Pr + 130 ms minutes 8
RT430/434 87
RT430/434 Chapter 10 - Appendixes
15 Pr + 150 ms minutes 10
16 Pr + 160 ms minutes 20
17 Pr + 170 ms minutes 40
21 Pr + 210 ms hours 2
22 Pr + 220 ms hours 4
23 Pr + 230 ms hours 8
25 Pr + 250 ms hours 10
26 Pr + 260 ms hours 20
31 Pr + 310 ms days 2
32 Pr + 320 ms days 4
33 Pr + 330 ms days 8
35 Pr + 350 ms days 10
36 Pr + 360 ms days 20
37 Pr + 370 ms days 40
88 RT430/434
Chapter 10 - Appendixes RT430/434
38 Pr + 380 ms days 80
50 Pr + 500 ms year 1 The last 2 digits of the year (00 ... 99)
51 Pr + 510 ms year 2
52 Pr + 520 ms year 4
53 Pr + 530 ms year 8
55 Pr + 550 ms year 10
56 Pr + 560 ms year 20
57 Pr + 570 ms year 40
58 Pr + 580 ms year 80
RT430/434 89
RT430/434 Chapter 10 - Appendixes
0 – none
Pr + 700 ms Time Offset – 0.5h
70 1 – Additional 0.5h time offset
71 Pr + 710 ms Time Quality (bit 1) 4-bit code representing approx. clock time
error:
72 Pr + 720 ms Time Quality (bit 2)
0000: Clock is locked
73 Pr + 730 ms Time Quality (bit 3) 0001, 0010, …. , 1010, 1011: Time within 10-
9s, 10-8s, …. , 1s,10s of UTC
90 RT430/434
Chapter 10 - Appendixes RT430/434
(0 ... 86399)
81 Pr + 810 ms time-of-day 2
82 Pr + 820 ms time-of-day 4
83 Pr + 830 ms time-of-day 8
84 Pr + 840 ms time-of-day 16
85 Pr + 850 ms time-of-day 32
86 Pr + 860 ms time-of-day 64
RT430/434 91
RT430/434 Chapter 10 - Appendixes
Description
The Precision Time Protocol (PTP) is an ultimate time synchronization accuracy
protocol for Ethernet networks. On a local area network, it achieves clock accuracy in
the sub-micro second range, making it suitable for applications where
synchronization is essential to the measurement system. The ultimate time accuracy
of the protocol is obtained from the compensation of propagation delay information
between the source and destination.
IEEE 1588 - 2002 standard, officially entitled “Standard for a Precision Clock
Synchronization Protocol for Networked and Control Systems”, originally defined PTP
protocol. In 2008, the standard was revised and had its protocol accuracy and
robustness improved.
The protocol describes a hierarchical master-slave architecture designed for clock
distribution, where the root timing reference is called Grandmaster clock, which
transmits synchronization information to the clocks residing on its network segment.
The algorithm establishes an order of searching for the attributes and from the
results, determines which will be used as time source.
• Boundary Clock: According to IEEE1588 standard, a boundary clock has multiple
PTP ports in a domain and maintains the timescale used in the domain. It may
92 RT430/434
Chapter 10 - Appendixes RT430/434
serve as the source of time, i.e., be a master clock, and may synchronize to
another clock, i.e., be a slave clock.
• Ordinary Clock: According to IEEE1588 standard, an ordinary clock has a single
PTP port in a domain and maintains the timescale used in the domain. It may
serve as a source of time, i.e., be a master clock, or may synchronize to another
clock, i.e., be a slave clock.
• Transparent Clock: According to IEEE1588, a transparent clock is a device that
measures the time take from a PTP event message to transit the device and
provides this information to clocks receiving this PTP event message.
• End-to-end Transparent Clock: According to IEEE1588 standard, it is a
transparent clock that supports the use of the end-to-end delay measurement
mechanism between slave clocks and master clock.
• Peer-to-peer Transparent Clock: According to IEEE1588 standard, it is a
transparent clock that, in addition to providing PTP event transit time
information, also provides corrections for the propagation delay of the link
connected to the port receiving the PTP event message.
• One-step Clock: According to IEEE1588 standard, it is a clock that provides time
information using a single event message.
• Two-step Clock: According to IEEE1588 standard, it is a clock that provides time
information using the combination of an event message and subsequent
general message.
• Accuracy: According to IEEE1588 standard, the mean of the time or frequency
error between the clock under test and a perfect reference clock, over an
ensemble of measurements. Stability is a measure of how the mean varies with
respect to variables such as time, temperature, and so on. The precision is a
measure of the deviation of the error from the mean.
• Profile: According to IEEE1588 standard, profile is a set of all allowed PTP
features applicable to a device.
• Timeout: According to IEEE1588 standard, timeout is the time in which a device
waits to receive synchronization messages. In case the message is not received
within this time interval, the clock that sends messages is considered out of
operation and the BMC algorithm is ran, and chooses a second master clock.
Hierarchical Topology
IEEE1588 defines a hierarchical topology composed of different types of clocks that
send and receive synchronization messages.
In hierarchical topology, a boundary clock is elected the grandmaster clock that
sends PTP messages for the entire network, which are also connected ordinary and
boundary clocks. The boundary clocks connected to the network are used as
intermediate time source for ordinary clock. The selection of the source clock is
performed by each receiver device, using the BMC algorithm.
RT430/434 93
RT430/434 Chapter 10 - Appendixes
The second revision of the standard also specifies the form of unicast
communication where the clock master has to send time synchronization packets for
each slave device connected to the network, which requires the master clock to have
greater processing power and causes the network traffic to be more overloaded.
PTP Synchronization
Through use of the BMC algorithm, PTP elects a master source of time for an
IEEE1588 domain and for each network segment in the domain. Clocks determine the
offset between themselves and their master. Let the variable represent physical time.
For a given slave device, the offset 𝑜(𝑡) at a time 𝑡 is defined by:
𝑜(𝑡) = 𝑠(𝑡) − 𝑚(𝑡)
where 𝑠(𝑡) represents the time measured at the clock at physical time t, and 𝑚(𝑡)
represents the time measured at the master at physical time t.
The master clock periodically broadcasts the current time as a message to the other
clocks. Under IEEE1588-2088, broadcasts are up to 10 messages per second.
Each broadcast begins at time T1 which is a Sync multicast message sent by the
master to all the clocks in the domain. A clock receiving this message takes note of
the local time T1' when this message is received. The master may subsequently send
a multicast Follow Up with accurate timestamp. Not all masters have ability to
present an accurate timestamp in the Sync message. It is only after the transmission
is complete that they are able to retrieve an accurate timestamp for the Sync
transmission from their network hardware. Masters with this limitations use the
Follow Up message to convey T1. Masters with PTP capabilities built into their
network hardware are able to present an accurate timestamp in the Sync message
and do not need to send Follow Up messages.
In order to accurately synchronize to their master, clocks must individually determine
the network transit time of the Sync messages. The transit time is determined
indirectly by measuring round-trip time from each clock to its master. The clocks
initiate an exchange with their master designed to measure the transit time d. The
exchange begins with a clock sending a Delay Req message at time T2 to the master.
The master receives and time stamps the Delay Req at time T2' and responds with a
Delay Resp message. The master includes the time stamp T2' in the Delay Resp
message. Through these exchanges, a clock learns T1, T1', T2 and T2'.
If d is the transit time for the Sync message, and 𝑜̃ is the constant offset between
master and slave clocks, then:
𝑇1 − 𝑇1′ = 𝑜̃ + 𝑑
𝑇2 − 𝑇2′ = −𝑜̃ + 𝑑
The clock now knows the offset õ during this transaction and can correct itself by this
amount to bring it into agreement with their other master.
94 RT430/434
Chapter 10 - Appendixes RT430/434
Network protocols
IEEE1588 standard defines the network layers where the PTP protocol will be applied.
It is possible to use PTP protocol in a network layer with IEEE 802.3 Ethernet (layer 2)
or UDP/IPv4 (layer 3) connection.
The layer 3 (UDP/IPv4) is used in more environments facilitating the compatibility of
sending and receiving messages between the devices connected to the network.
Once the PTP protocol has low traffic when compared to other protocols, the network
traffic is not limiting factor of the use of layer 3.
To use the layer 2 it is necessary that the network has ETHERNET connections between
all master and slave clocks, which are not common when the network is divided into
subnets and there is not an interconnection between them. The advantage of using
layer 2 is that the traffic through the network is smaller because the sent packets do
not require including IP and UDP address.
RT430/434 95
RT430/434 Chapter 10 - Appendixes
PTP Messages
In PTP protocol, Sync messages followed by the timestamp messages are sent to the
entire network in multicast mode, in which a PTP message sent by a network port
can be received by all other ports connected to the same network. The advantage of
multicast mode network is that the master clock sends only one packet containing
time information to the network and this packet is received by all slave devices
connected to this network.
Among the messages specified by IEEE1588 standard, the ones that stand out are
related to synchronization, timestamp and propagation delay.
The Announce messages are used to inform the devices connected to the network
about the existence of a master clock available to send Sync messages. The
Announce message includes a packet of values that indicates the time accuracy of
the clock, enabling the BMC algorithm to decide which of the available clocks will be
used as master. The speed the Announce messages are sent influences directly the
frequency the slave will perform the BMC algorithm. Many announce messages can
be transmitted at the same time through the network and the slave clock is
responsible to process these messages. All devices connected to the network that
are able to operate as master should periodically send Announce messages to the
network, becoming candidates to be master of the network.
The clock connected to the network selected as master by the BMC algorithm, should
send Sync messages, and in case it is a two-step clock, it should also send a Follow
Up message, containing a timestamp. The sending interval of the messages is
configurable and its standard value, specified by IEEE1588 standard, is one-
message-per-second. This interval specifies the frequency the slave devices receive
synchronization information, allowing to adjust its internal clocks to use the master
clock as time reference. In the interval between two Sync messages the slave devices
operate free from external time reference and the time stability in this period is
determined by its internal time base, that can be, for example a crystal oscillator. By
choosing the frequency to send Sync messages through the master clock, it is
important to consider the accuracy of the internal clocks of the slave devices that will
be synchronized by it, and also the bandwidth, because the higher the frequency to
send messages is, the higher the network traffic is.
The delay measurement of messages passing through devices is important to reach
the accuracy required by IEEE1588 standard. Especially in E2E networks, the
propagation delay measurement is crucial for the synchronization. In networks with
E2E delay measurement, the frequency the slave devices should measure delay,
which results in sending and receiving messages, should be according to the network
stability regarding the variation of this information.
96 RT430/434
Chapter 10 - Appendixes RT430/434
ACEB Datagrams
ACEB datagram comprises 13 bytes, sent once per minute in the second second of
the minute (i.e. 12:00:02, then 12:01:02). The datagram information is described
below.
1 Delimiter 0xFF
2 Header 0x01
11 Second BCD 02
$GPZDA,hhmmss.0,DD,MM,YYYY,,*CC<CR><LF>
RT430/434 97
RT430/434 Chapter 10 - Appendixes
hh 00 ... 23 hours
mm 00 ... 59 minutes
ss 00 ... 59 seconds
MM 01 ... 12 month
Table 40: GPZDA Datagram Line Feed and Carriage Return Information
ASCII ASCII
Characters Description
(decimal) (hexadecimal)
Meinberg Datagram
Meinberg datagram comprises 32 characters, sent once per second. The datagram
information is described below:
<STX>D:DD.MM.YY;T:w;U:hh.mm.ss;uv__<ETX>
98 RT430/434
Chapter 10 - Appendixes RT430/434
hh 00 ... 23 hours
mm 00 ... 59 minutes
ss 00 ... 59 seconds
MM 01 ... 12 month
<STX> 02 02 start-of-datagram
<ETX> 03 03 end-of-datagram
_ 32 20 space
RT430/434 99
RT430/434 Chapter 10 - Appendixes
Signal Attenuation
Signal attenuation is related to cable type and overall cable length. When using the
active antenna supplied by GE Grid Solutions, total attenuation should not exceed 32
dB.
Total attenuation can be computed by using:
𝐴 = 𝐴𝑢 ×𝑙
Where 𝐴𝑢 is the attenuation per unit length for the given cable and 𝑙 is the overall
cable length.
The table below shows a few typical cable configurations and the associated total
attenuation.
15 m (50 ft) 7 dB ―
25 m (82 ft) 12 dB ―
40 m (131 ft) 19 dB ―
75 m (246 ft) ― 13 dB
Propagation Delay
The antenna cable delays the signal received from the satellites. In applications in
which the ultimate time accuracy is desired, this delay should be compensated inside
the unit.
Typically, the delay introduced by coaxial cables is in the magnitude of 4 ns/m (1.2
ns/ft) of cable length.
The exact delay can be computed by using:
1
𝑇= ×𝑙
𝐶𝐾𝑣
Where 𝐶 = 3×108 m/s is the speed of light, 𝐾𝑣 = 0.8 … 0.85 is a constant which
depends on the cable and 𝑙 is the cable length in meters.
The table below summarizes some typical delays caused by coaxial cables.
100 RT430/434
Chapter 10 - Appendixes RT430/434
15 m (50 ft) 60 ns
RT430/434 101
RT430/434 Chapter 10 - Appendixes
102 RT430/434
Chapter 10 - Appendixes RT430/434
RT430/434 103
RT430/434 Chapter 10 - Appendixes
Figure 48: Process Bus application using PTP via the Station Bus network.
104 RT430/434
Chapter 10 - Appendixes RT430/434
Figure 49: Process Bus application using PTP via the Station Bus network.
RT430/434 105
RT430/434 Chapter 10 - Appendixes
106 RT430/434
Chapter 10 - Appendixes RT430/434
RT430/434 107