C 1/3/22 ISSUED FOR APPROVAL NDK AAJ ZKN

B 13/2/22 ISSUED FOR APPROVAL NDK AAJ ZKN


0 15/12/21 ISSUED FOR APPROVAL NDK AAJ ZKN
REV. DATE DESCRIPTION PREPARED CHECKED APPROVED
PROJECT

Completion of Work for NWC Water Pipeline Network Supplying Water to PP11,
PP12 & PP13 from NWC Dhurma Pumping Station

OWNER

CONTRACTOR

THIS DOCUMENT IS NOT TO BE USED FOR CONSTRUCTION OR FOR ORDERING MATERIAL UNTIL APPROVED AND
DATED.

DOCUMENT TITLE

POWER PLANT 13 (PP13) – I/O LIST


NO. OF
CONTRACT NO. DOCUMENT NO. REV.
PAGES
4400015651 MSCL-SEC-I&C-IO-004 1 C
Completion of Work for NWC Water Pipeline Network Supplying Water to PP11, PP12 PP13 from NWC Dhurma Pumping StationINPUT / OUTPUT LIST

POWER PLANT 13 - PP13 Local HMI Control Panel


Digital Input (DI)
LLL HH HHH
PLC Min. Max. Eng. LL Alarm L Alarm H Alarm Alarm Terminal
S.No KKS Tags Signal Description Signal Name Signal Type Data Type CARD No. Alarm Alarm Alarm Relay Terminal No. Remarks/Notes
Address Range Range Unit Limit Limit Limit Required Block
Limit Limit Limit
1 PP13-GAF-33-AA-056-XB01 PP13 Raw Water Storage Tank Inlet Valve Opened Feedback MOV106_OPENED Digital Input BOOL PLC CPU I0.0 N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A TBDI 1 2 New Equipment
2 PP13-GAF-33-AA-056-XB02 PP13 Raw Water Storage Tank Inlet Valve Closed Feedback MOV106_CLOSED Digital Input BOOL PLC CPU I0.1 N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A TBDI 3 4 New Equipment
3 PP13-GAF-33-AA-056-XB14 PP13 Raw Water Storage Tank Inlet Valve Local/Remote Feedback MOV106_LOCAL/REMOTE Digital Input BOOL PLC CPU I0.2 N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A TBDI 5 6 New Equipment
4 PP13-GAF-33-AA-056-XB48 PP13 Raw Water Storage Tank Inlet Valve Trip/Fault Feedback MOV106_TRIP/FAULT Digital Input BOOL PLC CPU I0.3 N/A N/A N/A N/A N/A N/A N/A N/A N/A YES N/A TBDI 7 8 New Equipment
5 SPARE SPARE SPARE Digital Input BOOL PLC CPU I0.4 N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A TBDI 9 10 SPARE
6 SPARE SPARE SPARE Digital Input BOOL PLC CPU I0.5 N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A TBDI 11 12 SPARE
7 SPARE SPARE SPARE Digital Input BOOL PLC CPU I0.6 N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A TBDI 13 14 SPARE
8 SPARE SPARE SPARE Digital Input BOOL PLC CPU I0.7 N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A TBDI 15 16 SPARE
9 SPARE SPARE SPARE Digital Input BOOL PLC CPU I1.0 N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A TBDI 17 18 SPARE
10 SPARE SPARE SPARE Digital Input BOOL PLC CPU I1.1 N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A TBDI 19 20 SPARE
11 SPARE SPARE SPARE Digital Input BOOL PLC CPU I1.2 N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A TBDI 21 22 SPARE
12 SPARE SPARE SPARE Digital Input BOOL PLC CPU I1.3 N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A TBDI 23 24 SPARE
13 SPARE SPARE SPARE Digital Input BOOL PLC CPU I1.4 N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A TBDI 25 26 SPARE
14 SPARE SPARE SPARE Digital Input BOOL PLC CPU I1.5 N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A TBDI 27 28 SPARE
Digital Output (DO)
1 PP13-GAF-33-AA-056-XGC02 PP13 Raw Water Storage Tank Inlet Valve Open Command MOV106_OPEN_CMD Digital Output BOOL PLC CPU Q0.0 N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A R-01/A1 TBDO 1 2 New Equipment
2 PP13-GAF-33-AA-056-XGC01 PP13 Raw Water Storage Tank Inlet Valve Close Command MOV106_CLOSE_CMD Digital Output BOOL PLC CPU Q0.1 N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A R-02/A1 TBDO 3 4 New Equipment
3 SPARE SPARE SPARE Digital Output BOOL PLC CPU Q0.2 R-03/A1 TBDO 5 6 SPARE
4 SPARE SPARE SPARE Digital Output BOOL PLC CPU Q0.3 R-04/A1 TBDO 7 8 SPARE
5 SPARE SPARE SPARE Digital Output BOOL PLC CPU Q0.4 TBDO 9 10 SPARE
6 SPARE SPARE SPARE Digital Output BOOL PLC CPU Q0.5 TBDO 11 12 SPARE
7 SPARE SPARE SPARE Digital Output BOOL PLC CPU Q0.6 TBDO 13 14 SPARE
8 SPARE SPARE SPARE Digital Output BOOL PLC CPU Q0.7 TBDO 15 16 SPARE
9 SPARE SPARE SPARE Digital Output BOOL PLC CPU Q0.8 TBDO 17 18 SPARE
10 SPARE SPARE SPARE Digital Output BOOL PLC CPU Q0.9 TBDO 19 20 SPARE
Analog Input (AI)

Existing Equipment; Calculation in the logic will be provided for Totaliser (m3) and
will be indicated in Local HMI. Totaliser (m3) is the total consumed water. This is in
03-GAC-01-CF-001-XQ30 PP13 Raw Water Flow Meter Transmitter PP11_FT_FLOW_METER Analog Input WORD PLC CPU IW0 m3/hr YES N/A TBAI 1 2
addition to the flow rate (m3/hr) flow transmitter in Local HMI Control Panel. Both
flow rate (m3/hr) and Totaliser (m3) will also be indicated in SCADA HMI thru FO.
1

Existing Equipment; Average calculation will be provided in the logic and average
value will be indicated in the Local HMI in addtion to the individual tranmitter -
03-GAD-02-CL-001-XQ30 PP13 Raw Water Tank Level Transmitter 1 PP13_RW_TANK_LIT_1 Analog Input WORD PLC CPU IW2 mm YES N/A TBAI 4 5
applicable for 1oo2 and 2oo3. The average value will also be indicated in SCADA
HMI thru FO.
2
3 PP13-GAF-33-CP-013-XQ30 PP13 Raw Water Storage Tank Inlet Pressure Transmitter PT_113_PP13 Analog Input WORD AI-01 IW4 bar YES N/A TBAI 7 8 New Equipment

Existing Equipment; Average calculation will be provided in the logic and average
value will be indicated in the Local HMI in addtion to the individual tranmitter -
03-GAD-02-CL-002-XQ30 PP13 Raw Water Tank Level Transmitter 2 PP13_RW_TANK_LIT_2 Analog Input WORD AI-01 IW6 mm YES N/A TBAI 10 11
applicable for 1oo2 and 2oo3. The average value will also be indicated in SCADA
HMI thru FO.
4
5 SPARE SPARE SPARE Analog Input WORD AI-01 IW8 N/A TBAI 13 14 SPARE
6 SPARE SPARE SPARE Analog Input WORD AI-01 IW10 N/A TBAI 16 17 SPARE
Analog Output (AO)
1 SPARE SPARE SPARE Analog Output WORD AO-01 QW0 N/A TBAO 1 2 SPARE
2 SPARE SPARE SPARE Analog Output WORD AO-01 QW2 N/A TBAO 4 5 SPARE
3 SPARE SPARE SPARE Analog Output WORD AO-01 QW4 N/A TBAO 7 8 SPARE
4 SPARE SPARE SPARE Analog Output WORD AO-01 QW6 N/A TBAO 10 11 SPARE