Download as pdf or txt
Download as pdf or txt
You are on page 1of 1

Networking

LPH Lift Machinery Area


NOTE :
Transparent Enclosure
• Please use port XG1 and XG4 as the ring XG1 XG4 XG1 XG4 XG1 XG4 XG1 XG4
network when the Group Controller is
KCEGCL, and
• Please use ports XG1 and XG3 for KCEGCH, XE XE XE

LCEGTWO

LCEGTWO

LCEGTWO

LCEGTWO
KCEGCL KCEGCL KCEGCL KCEGCL K-JHL-SWU-3
as indicated on the picture below. XG2 XG2 XG2 XG2

KCELIO KCELIO KCELIO KCELIO

GCM 1 GCM 2 GCM 3 GCM 4 1GB SFP

LCECPU LPH 1 LCECPU LPH 2 LCECPU LPH 3 LCECPU LPH 4


XG XG
1 4

XG XG
1 3

LPP Lift Machinery Area

Transparent Enclosure
XG1 XG4 XG1 XG4 XG1 XG4 XG1 XG4

XE XE XE
LCEGTWO

LCEGTWO

LCEGTWO

LCEGTWO
KCEGCL KCEGCL KCEGCL KCEGCL K-JHL-SWU-2
XG2 XG2 XG2 XG2

KCELIO KCELIO KCELIO KCELIO

GCM 1 GCM 2 GCM 3 GCM 4 1GB SFP

LCECPU LPP 1 LCECPU LPP 2 LCECPU LPP 3 LCECPU LPP 4

Service Elevator Service Elevator


LMR FL.28 LMR FL.15 Transparent Enclosure
ACS PC
Control Control K-JHL-SWU-3
Panel Panel E-Link PC

LCECPU LCECPU 1GB


1GB
SFP
CAN0 SFP

Control Room

LIST OF MATERIAL

No. Model Qty Location Description Provided by


Trendnet TI-G62 Hardened Industrial LPP & LPH Machine room, Main Switch : Non-Managed Switch
1 3 Vendor
Gigabit DIN-Rail Switch Control Room 5 Gigabit, 1 Combo, 1 dedicated SFP port
Trendnet 1000Base-SX Industrial MM LPP & LPH Machine room,
2 4 SFP Module Vendor
LC SFP Module Control Room
LPP & LPH Machine room,
3 Power Supply TI-M6024 3 60 W Single Output Industrial, DIN-Rail Power Supply, 24V Vendor
Control Room
LPP & LPH Machine room, Minmum 40x30x20 cm with MCB 6A, DC/AC FAN, DIN Rail
4 Transparent Enclosure 3 Vendor
Control Room (Assembled by Vendor)
LPP & LPH Machine room,
5 LAN Patch Cable 8* CAT 6 or better Vendor
Control Room
LPP & LPH Machine room,
6 Optical Fibre * OM2 50/125um, MM, SC, 8 core Vendor
Control Room
Note :
* Survey Needed
1. Additional materials and services for the installation and termination of LAN and Fiber cables will be carried out by the Vendor.
2. Tests and Final Test Reports from vendors are required, and meet international standards with proper tools

CAN Cable = 2*0,75mm2 (AWG18). Twistedd pair cable characteristic impedance 120 ohm
Max Distance from KIC to last lift in bus = 1000m (by Project) Design by : Check ed by : Product Code : Language :

Nikolaus EN
RS-485 cable = 3*2*0,25mm2 (Cu conductors) Capacitance <130nF/km Loop resistance < 150ohm/
Department : Date : Approved by : Title :
km. Max Distance from KIC to last lift/escalator in bus = 500m (by KONE Factory) 08/10/2021 Networking
Projec t Name :
CAT 6 or Better Max 90M (Orange = by KONE Factory, Blue = by Vendor) PT KONE INDO ELEVATOR
JHL
MNC LAN D TOWER, 9 t h Floor
MNC Center Complex, Jl. Kebon Sirih No. 17-19
Drawing Number : Iss ue : Page :
Fiber Optic Cable 2*2 pair cables. 50/125 µm, Multi Mode Fiber (OM2), SC Connector (by Vendor) Jakarta Pusat 10340, Indonesia
Phone : +62 21 300 60418 -----E73 A 1