Industrial Systems

BUS2000
Busbar Differential
Protection System
Differential overcurrent system with
percentage restraint protection

1
Industrial Systems

Typical Busbar Arrangements


– Single Busbar
– Double Busbar with Coupler
– Breaker and a Half
– Double Breaker
– Double Busbar with Transfer Bar
– Segregated Busbars with Coupler

2
Industrial Systems
Typical Single Busbar
Arrangement

3
Industrial Systems
Typical Double Busbar
with Coupler Arrangement

4
Industrial Systems
Typical Breaker and a Half
Arrangement

5
Industrial Systems
Typical Double Breaker
Busbar Arrangement

6
Industrial Systems
Typical Double Busbar
with Transfer Bar

7
Industrial Systems
Typical Segregated Busbar
with Coupler

8
Industrial Systems

Types of Protection
Schemes
–Low Impedance
–High Impedance
• Medium Values
• High Values

9
Industrial Systems

Low Impedance Protection

10
Industrial Systems

Saturation of the Auxiliary


CTs

• A. Primary Fault Current


• B. Secondary Current from the Source CTs
• C. Secondary Current in the Faulty CT
• D. Differential Current
11
Industrial Systems

Low Impedance Protection


Current Detection + Second
Criteria
–Time-delayed Overcurrent Relays
–Directional Overcurrent Relays
–Restraint Overcurrent relays
–CT Saturation Detectors

12
Industrial Systems

High Impedance Protection


Scheme

13
Industrial Systems

High Impedance Protection


• VR = IF x (2RL + RS)
• VOP > VR Stability Criteria
• VS > VOP Operation Criteria
• TI3 Totally Saturated
• RS CT Secondary Winding R Value


• WHERE:
• RL= CONNECTION WIRES RESISTANCE
• IF = SECONDARY RMS CURRENT VALUE IN TI3
• VR = DIFFERENTIAL RELAY VOLTAGE
• VS = CT MINIMUM SATURATION VOLTAGE
• VOP = OPERATION VOLTAGE

14
Industrial Systems
Differential Overcurrent Relay with
Percentage Restraint & Stabilizing
Resistor

15
Industrial Systems

BUS2000-External Fault

16
Industrial Systems

BUS2000-Internal Fault

17
Industrial Systems
BUS2000 - Differential Unit
Block Diagram

18
Industrial Systems
BUS2000-Sensitivity Algorithm
(1)

19
Industrial Systems

BUS2000-Sensitivity
Algorithm (2)

20
Industrial Systems
BUS2000-Sensitivity
Algorithm (3)

21
Industrial Systems
External Fault with CT
Saturation

22
Industrial Systems

BUS2000-Stability Algorithm

23
Industrial Systems

BUS2000-Stability Limit

24
Industrial Systems

BUS2000-Operation Characteristic

25
Industrial Systems

BUS2000-Auxiliary CT. Magnetizing


Curve of the Secondary Side

26
Industrial Systems

BUS2000-Alarm Unit Block


Diagram

27
Industrial Systems
Breaker Failure
Block Diagram

28
Industrial Systems

Numerical Monitoring Module


– Differential and Restraint Currents Metering Information
– Full Human-Machine Interface (Keypad + Graphic
Display)
– IRIG-B Time Synchronization
– Alarm Treatment
– Differential Protection Outputs Status

29
Industrial Systems

Numerical Monitoring Module


(cont)
– Oscillography Waveform Capture
– Event Record
– RS232 or fiber optics Communications
– Configurable I/O
– Undervoltage Supervision

30
Industrial Systems

BUS2000-Single Busbar
(6 feeders) Differential Protection

31
Industrial Systems

BUS2000-Overcurrent and Breaker


Failure (5 feeders) Protection

32
Industrial Systems

BUS2000-Test Rack

33
Industrial Systems

BUS2000-Numerical Monitoring
Module

34
Industrial Systems
External Connections Diagram
of Single Busbar BUS2000
System

35
Industrial Systems

BUS2000-Settings
–K for Sensitivity
–K and RE as low as possible
–RE for CT requirements for
Overvoltage Conditions

36
Industrial Systems

Key Advantages
– Flexibility
– Independent setttings for K and RE done in the field
without any additional changes
– Wide Setting Range
– Suitable for all kinds of installations
– Measurement Units Supervision
– Current Circuits Supervision

37
Industrial Systems

Key Advantages (cont’d)


– Single-Three Phase Breaker Failure
– Test Rack Independent from the protection
– Easy Commisioning (accesible terminal blocks)
– Suitable for updating of old Substations
– Operating Principles well proven in the field
– Numerical Monitoring Module

38