F. Concrete-Encased Ducts: Support on plastic separators coordinated with duct size and
required duct spacing, and install according to the following:
G. Sealing: Provide temporary closure at terminations of ducts that have cables pulled. Seal
spare ducts at terminations. Use sealing compound and plugs.
A. Ducts ending in cable manholes or handholes are to be neatly cut and reamed and set behind
chamfered precast concrete duct end blocks or terminated with appropriate bell-mouth
bushing set in concrete wall. Ducts not ending in cable manholes or handholes are to be
properly capped.
B. Sealing Ends Of Ducts: Completely seal conduits and ducts, active or spare, at entry into
buildings or manholes, with approved plastic moulds or wooden bungs to prevent entry of
rodents, gas and vapor.
A. Drainage: Install drains in bottom of units. Coordinate with drainage provisions indicated.
B. Waterproofing: Apply waterproofing to exterior surfaces of units after concrete has cured at
least 3 days. Apply according to Division 07 Section ["Self-Adhering Sheet
Waterproofing."] and ["APP Modified Bituminous Sheet Waterproofing."] After ducts have
been connected and grouted, and before backfilling, waterproof joints and connections and