DN145B PSD D166 LED10S/840 NO / Luminaire Data Sheet

Luminous emittance 1:

See our luminaire catalog for an image of the


luminaire.

Luminaire classification according to CIE: 100 Luminous emittance 1:


CIE flux code: 61 86 97 100 100

Page 2
B83
06.03.2022

Operator
Telephone
Fax
e-Mail

Room 1 / Summary

Height of Room: 3.000 m, Mounting Height: 3.000 m, Maintenance factor: Values in Lux, Scale 1:22
0.80
Surface  [%] Eav [lx] Emin [lx] Emax [lx] u0
Workplane / 109 93 118 0.856
Floor 20 69 58 75 0.841
Ceiling 70 35 26 40 0.747
Walls (8) 50 66 24 161 /

Workplane:
Height: 0.700 m
Grid: 32 x 32 Points
Boundary Zone: 0.200 m
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.693, Ceiling / Working Plane: 0.317.

Luminaire Parts List

No. Pieces Designation (Correction Factor)  (Luminaire) [lm]  (Lamps) [lm] P [W]
1 1 DN145B PSD D166 LED10S/840 NO (1.000) 1100 1100 13.0
Total: 1100 Total: 1100 13.0

Specific connected load: 4.58 W/m² = 4.20 W/m²/100 lx (Ground area: 2.84 m²)

Page 3
B83
06.03.2022

Operator
Telephone
Fax
e-Mail

Room 1 / Photometric Results

Total Luminous Flux: 1100 lm


Total Load: 13.0 W
Maintenance factor: 0.80
Boundary Zone: 0.200 m

Surface Average illuminances [lx] Reflection factor [%] Average luminance [cd/m²]
direct indirect total
Workplane 74 35 109 / /
Floor 44 25 69 20 4.36
Ceiling 0.00 35 35 70 7.70
Wall 1 24 30 54 50 8.66
Wall 2 27 30 57 50 9.11
Wall 3 42 30 72 50 11
Wall 4 21 33 54 50 8.62
Wall 5 36 31 67 50 11
Wall 6 37 30 67 50 11
Wall 7 36 30 66 50 11
Wall 8 37 30 67 50 11

Uniformity on the working plane


u0: 0.856 (1:1)
Emin / Emax: 0.794 (1:1)

Illuminance Quotient (according to LG7): Walls / Working Plane: 0.693, Ceiling / Working Plane: 0.317.
Specific connected load: 4.58 W/m² = 4.20 W/m²/100 lx (Ground area: 2.84 m²)

Page 4
B83
06.03.2022

Operator
Telephone
Fax
e-Mail

Room 2 / Summary

Height of Room: 3.000 m, Mounting Height: 3.000 m, Maintenance factor: Values in Lux, Scale 1:27
0.80

Surface  [%] Eav [lx] Emin [lx] Emax [lx] u0


Workplane / 100 81 112 0.813
Floor 20 65 53 73 0.819
Ceiling 70 27 20 33 0.717
Walls (4) 50 56 23 113 /

Workplane:
Height: 0.700 m
Grid: 32 x 32 Points
Boundary Zone: 0.200 m
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.615, Ceiling / Working Plane: 0.274.
Luminaire Parts List

No. Pieces Designation (Correction Factor)  (Luminaire) [lm]  (Lamps) [lm] P [W]
1 1 DN145B PSD D166 LED10S/840 NO (1.000) 1100 1100 13.0
Total: 1100 Total: 1100 13.0

Specific connected load: 3.45 W/m² = 3.44 W/m²/100 lx (Ground area: 3.77 m²)

Page 5
B83
06.03.2022

Operator
Telephone
Fax
e-Mail

Room 2 / Photometric Results

Total Luminous Flux: 1100 lm


Total Load: 13.0 W
Maintenance factor: 0.80
Boundary Zone: 0.200 m

Surface Average illuminances [lx] Reflection factor [%] Average luminance [cd/m²]
direct indirect total
Workplane 71 30 100 / /
Floor 42 23 65 20 4.14
Ceiling 0.00 27 27 70 6.11
Wall 1 30 25 54 50 8.62
Wall 2 32 25 57 50 9.03
Wall 3 30 25 54 50 8.62
Wall 4 32 25 57 50 9.08

Uniformity on the working plane


u0: 0.813 (1:1)
Emin / Emax: 0.728 (1:1)

Illuminance Quotient (according to LG7): Walls / Working Plane: 0.615, Ceiling / Working Plane: 0.274.
Specific connected load: 3.45 W/m² = 3.44 W/m²/100 lx (Ground area: 3.77 m²)

Page 6
B83
06.03.2022

Operator
Telephone
Fax
e-Mail

Room 3 / Summary

Height of Room: 3.000 m, Mounting Height: 3.000 m, Maintenance factor: Values in Lux, Scale 1:20
0.80

Surface  [%] Eav [lx] Emin [lx] Emax [lx] u0


Workplane / 121 112 126 0.930
Floor 20 73 65 78 0.887
Ceiling 70 54 37 61 0.685
Walls (4) 50 90 28 243 /

Workplane:
Height: 0.700 m
Grid: 16 x 16 Points
Boundary Zone: 0.200 m
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.878, Ceiling / Working Plane: 0.445.
Luminaire Parts List

No. Pieces Designation (Correction Factor)  (Luminaire) [lm]  (Lamps) [lm] P [W]
1 1 DN145B PSD D166 LED10S/840 NO (1.000) 1100 1100 13.0
Total: 1100 Total: 1100 13.0

Specific connected load: 6.99 W/m² = 5.78 W/m²/100 lx (Ground area: 1.86 m²)

Page 7
B83
06.03.2022

Operator
Telephone
Fax
e-Mail

Room 3 / Photometric Results

Total Luminous Flux: 1100 lm


Total Load: 13.0 W
Maintenance factor: 0.80
Boundary Zone: 0.200 m

Surface Average illuminances [lx] Reflection factor [%] Average luminance [cd/m²]
direct indirect total
Workplane 77 43 121 / /
Floor 45 28 73 20 4.63
Ceiling 0.00 54 54 70 12
Wall 1 46 41 87 50 14
Wall 2 50 42 92 50 15
Wall 3 46 41 87 50 14
Wall 4 50 41 92 50 15

Uniformity on the working plane


u0: 0.930 (1:1)
Emin / Emax: 0.889 (1:1)

Illuminance Quotient (according to LG7): Walls / Working Plane: 0.878, Ceiling / Working Plane: 0.445.
Specific connected load: 6.99 W/m² = 5.78 W/m²/100 lx (Ground area: 1.86 m²)

Page 8
B83
06.03.2022

Operator
Telephone
Fax
e-Mail

Room 4 / Summary

Height of Room: 3.000 m, Mounting Height: 3.000 m, Maintenance factor: Values in Lux, Scale 1:27
0.80

Surface  [%] Eav [lx] Emin [lx] Emax [lx] u0


Workplane / 100 82 112 0.813
Floor 20 65 53 73 0.816
Ceiling 70 28 20 35 0.711
Walls (4) 50 56 23 113 /

Workplane:
Height: 0.700 m
Grid: 32 x 32 Points
Boundary Zone: 0.200 m
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.617, Ceiling / Working Plane: 0.275.
Luminaire Parts List

No. Pieces Designation (Correction Factor)  (Luminaire) [lm]  (Lamps) [lm] P [W]
1 1 DN145B PSD D166 LED10S/840 NO (1.000) 1100 1100 13.0
Total: 1100 Total: 1100 13.0

Specific connected load: 3.45 W/m² = 3.44 W/m²/100 lx (Ground area: 3.77 m²)

Page 9
B83
06.03.2022

Operator
Telephone
Fax
e-Mail

Room 4 / Photometric Results

Total Luminous Flux: 1100 lm


Total Load: 13.0 W
Maintenance factor: 0.80
Boundary Zone: 0.200 m

Surface Average illuminances [lx] Reflection factor [%] Average luminance [cd/m²]
direct indirect total
Workplane 71 30 100 / /
Floor 42 23 65 20 4.15
Ceiling 0.00 28 28 70 6.15
Wall 1 30 25 54 50 8.65
Wall 2 32 25 57 50 9.13
Wall 3 30 25 55 50 8.68
Wall 4 32 25 57 50 9.07

Uniformity on the working plane


u0: 0.813 (1:1)
Emin / Emax: 0.728 (1:1)

Illuminance Quotient (according to LG7): Walls / Working Plane: 0.617, Ceiling / Working Plane: 0.275.
Specific connected load: 3.45 W/m² = 3.44 W/m²/100 lx (Ground area: 3.77 m²)

Page 10
B83
06.03.2022

Operator
Telephone
Fax
e-Mail

Room 6 / Summary

Height of Room: 3.000 m, Mounting Height: 3.000 m, Maintenance factor: Values in Lux, Scale 1:77
0.80

Surface  [%] Eav [lx] Emin [lx] Emax [lx] u0


Workplane / 139 66 164 0.477
Floor 20 100 50 122 0.501
Ceiling 70 42 23 70 0.537
Walls (7) 50 80 27 304 /

Workplane:
Height: 0.700 m
Grid: 128 x 32 Points
Boundary Zone: 0.200 m
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.655, Ceiling / Working Plane: 0.302.
Luminaire Parts List

No. Pieces Designation (Correction Factor)  (Luminaire) [lm]  (Lamps) [lm] P [W]
1 3 DN145B PSD D166 LED10S/840 NO (1.000) 1100 1100 13.0
Total: 3300 Total: 3300 39.0

Specific connected load: 4.69 W/m² = 3.38 W/m²/100 lx (Ground area: 8.32 m²)

Page 11
B83
06.03.2022

Operator
Telephone
Fax
e-Mail

Room 6 / Photometric Results

Total Luminous Flux: 3300 lm


Total Load: 39.0 W
Maintenance factor: 0.80
Boundary Zone: 0.200 m

Surface Average illuminances [lx] Reflection factor [%] Average luminance [cd/m²]
direct indirect total
Workplane 100 38 139 / /
Floor 69 31 100 20 6.38
Ceiling 0.00 42 42 70 9.35
Wall 1 45 40 85 50 14
Wall 2 57 42 99 50 16
Wall 3 15 27 42 50 6.72
Wall 4 25 31 56 50 8.89
Wall 5 34 29 63 50 10
Wall 6 52 37 89 50 14
Wall 7 21 40 61 50 9.69

Uniformity on the working plane


u0: 0.477 (1:2)
Emin / Emax: 0.403 (1:2)

Illuminance Quotient (according to LG7): Walls / Working Plane: 0.655, Ceiling / Working Plane: 0.302.

Specific connected load: 4.69 W/m² = 3.38 W/m²/100 lx (Ground area: 8.32 m²)